WF2458 - 1000 at 10 BAR Hs
WF2458 - 1000 at 10 BAR Hs
QUALITY POLICY
As part of its ongoing commitment to excellence Waterfall Pumps Manufacturing is committed to supply its
products that meet or exceed the requirements of our customers. By consistently providing product/services that
meet or exceed consumer expectation and international standards to strong business performance.
A key way to achieve this is by operating a Quality Management System (QMS) in accordance with the
requirements of ISO 9001: 2015.
Satisfying applicable requirements by ensuring that All Interested Parties Requirements and All
applicable statutory and regulatory requirements are determined, understood and consistently met.
Continual improvement of the QMS by ensuring the risks and opportunities that can affect conformity of
products and services and the ability to enhance customer satisfaction are determined and addressed
and the focus on enhancing customer satisfaction is maintained.
This policy will be communicated to all employees and organizations working for or on our behalf. Employees and
other organizations are expected to co-operate and assist in the implementation of this policy, whilst ensuring that
their own work, so far as is reasonably practicable, is carried out without risk to themselves, others, or the
environment. This policy will be reviewed annually by top management and where deemed necessary will be
amended and re-issued.
Waterfall Management
Consultant: Contractor:
Project Name:
GENERAL DOCUMENTS
31/12/2020
Ref. No: Rev. No:
Consultant: Contractor:
Project Name:
31/12/2020
Project: Ref.No:
Consultant: Rev.No:
Cross-Sectional Drawing
Diesel Engine Data
Diesel Controller Data
ELECTRIC DRIVEN PUMP
Pump Data Sheet & Curve
G & A Drawing
Cross-Sectional Drawing
Electric Motor Data
Electric Controller Data
JOCKEY PUMP
Pump Data
Jockey Controller Data
ACCESSORIES
31/12/2020
Ref. No: Rev. No:
Consultant: Contractor:
Project Name:
31/12/2020
DIESEL DRIVEN FIRE PUMP
FLOW RATE: 1000 GPM Ref. No:
PRESSURE: 10 Rev. No:
PUMP:
Type : Horizontal Split Case
Model : WF-6X4X12 HS
Speed : 3000 RPM
Listing : UL Listed & FM Approved
Construction :
Accessories : Suction and Discharge Gauges
Diesel Fuel Tank
Batteries and Cables
Automatic Air Release Valve
PRV, Waste Cone
DRIVER:
Type : Diesel Engine
Manufacturer : Clarke
Model : JU4H-UF54
Speed : 3000 RPM
Rating : 145 HP
Listing : UL Listed & FM Approval
CONTROLLER:
Type :
Manufacturer :
Supply : 12V-220
Listing : UL Listed & FM Approval
Enclosure :
31/12/2020
ELECTRIC DRIVEN FIRE PUMP
FLOW RATE: 1000 GPM Ref. No:
PRESSURE: 10 Rev. No
PUMP:
TYPE : Horizontal Split Case
Model : WF-6X4X12 HS
Speed : 2950 RPM
Listing : UL Listed & FM Approved
Construction :
Accessories : Suction and Discharge Gauges
Casing Relief Valve
Flow Meter
Automatic Air Release Valve
DRIVER:
Type : Electric Motor
Manufacturer : WEG
Speed : 2940 RPM
Frame Size : 404/5TS
Rating : 125 HP
Listing : UL Listed
Supply : 380V/3PH/50Hz
Enclosure : ODP
CONTROLLER:
Type : GPY-Controller
Manufacturer : Tornatech
Rating : 125 HP
Listing : UL Listed & FM Approval
Supply : 380V/3PH/50Hz
Enclosure : NEMA-2
31/12/2020
ELECTRIC DRIVEN JOCKEY PUMP
FLOW RATE: 50 GPM Ref. No:
PRESSURE: 11 Rev. No
PUMP:
Type :
Model : RV10-16
Construction :
Accessories :
DRIVE:
Type :
Rating : 7.5 HP
Supply : 380V/3PH/50Hz
Enclosure :
CONTROLLER:
Type :
Manufacturer :
Listing : UL Listed
Supply : 380V/3PH/50Hz
Enclosure : NEMA-2
31/12/2020
Ref. No: Rev. No:
Consultant: Contractor:
Project Name:
31/12/2020
SUB VENDORS LIST
: Pumps (Waterfall,U.A.E)
: Electric Motor ( , )
: ( , )
31/12/2020
Ref. No: Rev. No:
Consultant: Contractor:
Project Name:
31/12/2020
Ref. No: Rev. No:
Consultant: Contractor:
Project Name:
31/12/2020
Project Name: Ref. No:
Model: WF-6X4X12 HS Rev. No:
PUMP DATA
Service Diesel Driven Pump
Series Horizontal Split Case
Size 6X4X12
Rated Flow 1000 GPM
Rated Pressure 145 PSI
Speed 3000 RPM
Rotation Clockwise
Liquid Type Water
Discharge Size 4 inch
Suction Size 6 inch
Impeller Diameter 272 mm
Base Type Steel
Weight 306 KG
Efficiency 73%
HP Maximum 141 HP
MATERIALS OF CONSTRUCTION
Casing Ductile Iron
Impeller Bronze/SS
Shaft steel
Shaft sleeve Stainless steel
Lubrication Grease
DRIVER DATA
Manufacturer Clarke
HP Rating 145 HP
Speed 3000 RPM
Weight 424 KG
Starting Two(2)12V-DC
Model JU4H-UF54
31/12/2020
Performance Curve WF-6x4x12 HS
400
100
60 150% Rated
350
BHP
50 80 300
250
40
60
Min. 65% at
150% Rated
200
30
40 150
20
100
20
10
50
0 0 0
0 250 500 750 1000 1250 1500 175031/12/2020
FLOW (GPM)
Ref. No: Rev. No:
Consultant: Contractor:
Project Name:
31/12/2020
31/12/2020
Ref. No: Rev. No:
Consultant: Contractor:
Project Name:
31/12/2020
31/12/2020
Ref. No: Rev. No:
Consultant: Contractor:
Project Name:
31/12/2020
®
JU4H MODELS
ITEM
• Each engine is factory tested to verify power and performance. • Engines are to be used for stationary emergency standby fire pump service only. Engines
are to be tested in accordance with NFPA 25.
• Although FM-UL ratings are shown at specific speeds, Clarke engines can be
applied at any intermediate speed. To determine the intermediate speed power; • Engines are rated at standard SAE conditions of 29.61 in. (752.1 mm) Hg barometer and
make a linear interpolation from the Clarke FM-UL power curve. Contact Clarke or 77°F (25°C) inlet air temperature [approximates 300 ft. (91.4 m) above sea level] by the
your Pump OEM Representative to obtain details. testing laboratory (see SAE Standard J 1349).
• A deduction of 3 percent from engine horsepower rating at standard SAE conditions shall
be made for diesel engines for each 1000 ft. (305 m) altitude above 300 ft. (91.4 m)
• A deduction of 1 percent from engine horsepower rating as corrected to standard SAE
FM conditions shall be made for diesel engines for every 10°F (5.6°C) above 77°F (25°C)
ambient temperature. 31/12/2020
Page 1 of 12
®
Automatic from Fire Pump Controller and from Engine Instrument Not Supplied (for Vertical Turbine Fire Pump Applications)
Panel (for Horizontal Fire Pump Applications)
On Instrument Panel with Control Position Warning Light
Two (2) 12V-DC Two (2) 24V-DC
Adjustable Speed Control, Tamper Proof
Centrifugal Type, Poly-Vee Belt Driven
Abbreviations: DC –Direct Current, AC – Alternating Current, SAE – Society of Automotive Engineers, NA – Naturally Aspirated, T- Turbocharged, BSP(F) – British
Standard Pipe Thread (Female), SS – Stainless Steel
110
108 108
105
104
100
95
91
90
85
1750 2000 2250 2500 2750 3000 3250
ENGINE SPEED - RPM
RESTRICTED:
USE ONLY FOR STAND-BY FIRE PUMP APPLICATIONS
ENGINE PERFORMANCE:
STANDARD CONDITIONS: (SAE J1349, ISO 3046)
77°F (25°C) AIR INLET TEMPERATURE NAMEPLATE kW (MAXIMUM PUMP LOAD)
29.61 IN. (751.1MM) HG BAROMETRIC PRESSURE
#2 DIESEL FUEL (SEE C13940)
THIS DRAWING AND THE IN- CREATED DATE CREATED
FORMATION HEREIN ARE OUR 05/19/04
PROPERTY AND MAY BE USED BY
OTHER ONLY AS AUTHORIZED BY
US. UNPUBLISHED -- ALL RIGHTS
RESERVED UNDER THE DRAWING NO. REV
KEN WAULIGMAN 27OCT06 COPYRIGHT LAWS. C131946 A
31/12/2020
Page 3 of 12
JU4H-UF54
INSTALLATION & OPERATION DATA (I&O Data)
UK Produced
Basic Engine Description
Engine Manufacturer John Deere Co.
Ignition Type Compression (Diesel)
Number of Cylinders 4
Bore and Stroke - mm (in) 106 (4.19) X 127 (5)
Displacement - L (in³) 4.5 (275)
Compression Ratio 17.0:1
Valves per cylinder
Intake 1
Exhaust 1
Combustion System Direct Injection
Engine Type In-Line, 4 Stroke Cycle
Fuel Management Control Mechanical, Rotary Pump
Firing Order (CW Rotation) 1-3-4-2
Aspiration Turbocharged
Charge Air Cooling Type None
Rotation, viewed from front of engine, Clockwise (CW) Standard
Engine Crankcase Vent System Open
Installation Drawing D545
Weight - kg (lb) 424 (935)
NOTE: This engine is intended for indoor installation or in a weatherproof enclosure. 1Engine H 2O temperature is
dependent on raw water temperature and flow. 2Positive and Negative Cables Combined Length.
Page 1 of 2
31/12/2020
Page 4 of 12
JU4H-UF54
INSTALLATION & OPERATION DATA (I&O Data)
UK Produced
Exhaust System 2350 2600 2800 3000
Exhaust Flow - m³/min (ft.³/min) 21.7 (768) 26.4 (934) 30 (1061) 33.8 (1193)
Exhaust Temperature - °C (°F) 609 (1129) 611 (1132) 607 (1124) 592 (1098)
Maximum Allowable Back Pressure - kPa (in H 20) 7.5 (30) 7.5 (30) 7.5 (30) 7.5 (30)
Minimum Exhaust Pipe Dia. - mm (in) [3] 102 (4) 102 (4) 102 (4) 102 (4)
Lubrication System
Oil Pressure - normal - kPa (lb/in²) 345 (50) - 655 (95)
Low Oil Pressure Alarm Switch - kPa (lb/in²) 138 (20)
In Pan Oil Temperature - °C (°F) 104 (220) - 118 (245)
Total Oil Capacity with Filter - L (qt) 14.7 (15.5)
Page 2 of 2
C131271 Rev K
AC 25FEB16
31/12/2020
Page 5 of 12
CLARKE
Fire Protection Products
JU4H, JU4R & JU6H, JU6R ENGINE MODELS
ENGINE MATERIALS AND CONSTRUCTION
Air Cleaner Cylinder Head
Type…………..………….. .. Indoor Usage Only Type…….. ……………… …Slab 2 Valve
Oiled Fabric Pleats Material……………………. Annealed Gray Iron
Material……..…..…….………Surgical Cotton
Aluminum Mesh Cylinder Liners
Type…….. …………………Centrifugal Cast, Wet Liner
Air Cleaner - Optional Material………………..….…Alloy Iron Plateau, Honed
Type…………………………. Canister
Material……………………… Pleated Paper Fuel Pump
Housing………………..……… Enclosed Type…………………………Diaphragm
Drive…………………………Cam Lobe
Camshaft
Material………….………….. Cast Iron Heat Exchanger (USA) - JU4H & JU6H Only
Chill Hardened Type…………………………Tube & Shell
Location…………...….…….. In Block Materials
Drive……………….………..…Gear, Spur Tube & Headers……………Copper
Type of Cam…………..….... Ground Shell…………………………Copper
Electrode……………………Zinc
Charge Air Cooler (JU6H-60,62,68,74,84, ADK0,
AD58, ADNG, ADN0, ADQ0, ADR0, AAQ8, AARG,
ADP8, ADP0, ADT0, AD88, ADR8, AD98, ADS0, ADW8,
ADX8, AD98 only)
Type……….. ..…………….Raw W ater Cooled Heat Exchanger (UK) - JU4H & JU6H Only
Materials (in contact with raw water) Type…………………………Tube & Bundle
Tubes……… ……………………90/10 CU/NI
Headers ……………………36500 Muntz Materials
Covers ……………………83600 Red Brass Tube & Headers……………Copper
Plumbing ……………………316 Stainless Steel/ Brass Shell………..……………. Aluminum
90/10 Silicone
Injection Pump
Charge Air Cooler (JU6R-AA67, 59, 61, PF, Q7, RF, Type……………………….. Rotary
S9, 83 only) Drive…………………………Gear
Type…...……………………Air to Air Cooled
Materials Lubrication Cooler
Core…………………………Aluminum Type…………………………Plate
Cylinder Block
Type…………………………… One Piece with
Non-Siamese Cylinders
Material……………………… Annealed Gray Iron
31/12/2020
C13615 04NOV14
Page 6 of 12
31/12/2020
Page 7 of 12
31/12/2020
Page 8 of 12
31/12/2020
Page 9 of 12
JU4H-UF54
Stationary Fire Pump Engine Driver
EMISSION DATA
EPA 40 CFR Part 60
4 Cylinders
Four Cycle
Lean Burn
Turbocharged
Notes:
1) 4045TF252 Base Engine Model manufactured by John Deere Corporation.
For John Deere Emissions Conformance to EPA 40 CFR Part 60 see Page 2 of 2.
2) The Emission Warranty for this engine is provided directly to the owner
by John Deere Corporation. A copy of the John Deere Emission Warranty can
be found in the Clarke Operation and Maintenance Manual.
3) Engines are rated at standard conditions of 29.61in. (7521 mm) Hg barometer
and 77°F (25° C) inlet air temperature. (SAE J1349)
4) PM is a measure of total particulate matter, including PM 10 .
CLARKE
FIRE PROTECTION PRODUCTS
3133 EAST KEMPER ROAD
C131870 REV.D CINCINNATI, OH 45241
01NOV 07 KRW PAGE 1 OF 2
31/12/2020
Page 10 of 12
John Deere Power Systems
3801 W. Ridgeway Ave., PO Box 5100
Waterloo, Iowa USA 50704-5100
31 October 2007
Subject: Fire Pump Ratings – Conformance to EPA 40 CFR Part 60 (NSPS requirements)
All John Deere stationary fire pump engines conform to the requirements of 40 CFR Part 60. All such
engines include an emission label, stating the engine conforms to the requirements of 40 CFR Part 60. An
example of the emission label is show below:
This label applies to all of the following engine models, sold to Clarke Fire Protection, for use in stationary
fire pump applications:
All engines conforming to 40 CFR Part 60 (identified by emission label, as shown above) are covered under
the emissions warranty of 40 CFR Part 89.
Sincerely,
Kyle J. Tingle
Regional Sales Manager, JDPS
Page 2 of 2
31/12/2020
Page 11 of 12
CLARKE
www.clarkefire.com Fire Protection Products
JU4H-UF54
FIRE PUMP DRIVER
NOISE DATA
2800 145 106.8 66.3 68.3 82.2 89.3 96.7 98.2 100.3 100.2 98.3 87.7
3000 145 107.9 67.8 69.9 81.0 90.3 98.5 100.3 99.7 101.2 99.6 87.7
2800-3000 145 105.8 95.6 100.0 94.7 96.9 96.5 99.2 95.4 86.1 79.7
* Values above are provided at 3.3ft (1m) from engine block and do not include the raw exhaust noise.
** Values above are provided at 23ft (7m), 90° horizontal, from a vertical exhaust outlet and does not include noise created mechanically by the
engine.
The above data reflects values for a typical engine of this model, speed and power in a free-field environment.
Installation specifics such as background noise level and amplification of noise levels from reflecting off of surrounding objects, will affect the overall noise
levels observed. As a result of this, Clarke makes no guarantees to the above levels in an actual installation.
Page 12 of 12
Ref. No: Rev. No:
Consultant: Contractor:
Project Name:
31/12/2020
Technical Data
Model GPD Diesel Fire Pump Controller
Standard
4°C to 40°C / 39°F to 104°F
Temperature
Rating Optional
4°C to 55°C / 39°F to 131°F
DC 12VDC
General 24VDC
Grounding system • Negative
• Two independent fully automatic
Battery chargers • 10A continuous charge
• 500mA trickle charge
• Battery 1 & Battery 2 voltage
Electrical Reading • Battery 1 & Battery 2 charging amperage
• Charging mode
• Continuous system pressure display
Pressure Reading
• Cut-in and cut-out pressure setting
• Pressure readings with date stamp
• Event recording with date stamp
Pressure and
• Under regular maintained operation, events are stored in memory for the life of the controller.
Event Recorder
• Data viewable on operator interface display screen
• Downloadable by USB port to external memory device
This is a Marketing document. Please consult factory for more information. 31/12/2020
November 2018 2
Manufacturer reserves the right to modify this information without notice
Technical Data
Model GPD Diesel Fire Pump Controller
• Pressure transducer and run test solenoid valve assembly for fresh water application
• Pressure sensing connection 1/2” Female NPT
Pressure sensing • Drain connection 3/8”
• Rated and calibrated for 0-500psi working pressure
• Externally mounted with protective cover
4” alarm bell - 85 dB at 10ft. (3m)
• Engine run • Periodic test
• Main switch AUTO • Cranking Cycle
• Main switch in OFF • AC Power available
• Main switch in HAND • Pump room temperature (ºF or ºC)
Visual only
• Pump room trouble • Loss of continuity 1 • High pump room temperature
• Pump on demand • Loss of continuity 2 • ECM warning
• AC Failure • High fuel level • Weekly test cut-in not reached
• Charger 1 Failure • Fuel tank leak • Check weekly test solenoid
• Charger 2 Failure • PLD low suction pressure • Pressure transducer fault
• Weak battery 1 • High raw water temperature • Invalid Cut-In
• Weak battery 2 • Low pump room temperature • Service required
• Battery 1 overvoltage
• Battery 2 overvoltage
DPDT-8A-250V.AC
• Engine run
• Common controller trouble
• Charger #1 & Charger #2 failure • Pressure transducer fault
• Common engine trouble
• High engine temperature • Battery #1 & battery #2 failure • Overspeed
• Fail to start • DC failure • Fail when running
• Fuel injection malfunction** • Loss of continuity (starter) #1 and/or #2 • Low oil pressure
Contacts
• ECM selector switch in alternate position*** • PLD low suction pressure
This is a Marketing document. Please consult factory for more information. 31/12/2020
November 2018 Manufacturer reserves the right to modify this information without notice 3
Technical Data
Model GPD Diesel Fire Pump Controller
Selector Switch
• Behind lockable and breakable cover
• Start on pressure drop
• Remote start signal from automatic device
• Crank 1 and Crank 2 start pushbuttons
• Run test pushbutton
Manual Start
• Deluge valve start
• Remote start from manual device
• 6 consecutive cycle attempts
• 3 X 15s crank from battery 1 or 2 alternatively
Operation • 15s rest in between each crank attempt
• Manual with Stop pushbutton
Stopping
• Automatic after expiration of minimum run timer ****
12V.DC
32" l x 29" w x 16" h 32” l x 29” w x 26” h
85 (39) 115 (52)
(813 x 737 x 407 ) (813 x 737 x 661)
24V.DC
This is a Marketing document. Please consult factory for more information. 31/12/2020
November 2018 4
Manufacturer reserves the right to modify this information without notice
Technical Data
Model GPD Diesel Fire Pump Controller
Seismic
TRU Compliance, LLC
TWEI Project No.: 15014
Company
Mounting
Rigid wall mounting
details
Seismic
Building Test Seismic
Code Criteria Parameters
SDS z/h P
Seismic IBC
Information ICC- 2.0 1.0 1.5 3.20 2.40 1.33 0.53
2015, ASCE 7-10
ES
CBC Chapter 13
AC156 3.2 0.0 1.5 3.20 1.28 2.13 0.85
2016
Notes:
• Components are tested in accordance with ICC-ES AC156, IBC 2015 & CBC 2016.
This is a Marketing document. Please consult factory for more information. 31/12/2020
November 2018 Manufacturer reserves the right to modify this information without notice 5
Technical Data
Model GPD Diesel Fire Pump Controller
A1 Periodic test alarm contact (DPDT) Engine block heater circuit - 6KW max
C7A (same voltage as battery charger primary)
A2 Overspeed alarm contact (DPDT)
Non pressure actuated controller w/o pressure trans-
A3 Low oil pressure alarm contact (DPDT) C9 ducer and run test solenoid valve
A4 High coolant temperature alarm contact (DPDT)
C13
A5 Failure to start alarm contacts alarm contact (DPDT) Delayed automatic start on AC power failure
C14 (factory set at 15 minutes)
A6 Battery 1 & 2 failure alarm contact (2 x DPDT)
C15 Low zone pump control function
A7 Charger 1 & 2 failure alarm contact (2 x DPDT)
C16 Middle zone pump control function
A8 AC failure alarm contact (DPDT)
C17 High zone pump control function
System overpressure alarm contact (For engines with
A9 PLD) (DPDT) Lockout/interlock circuit from equipment installed inside
C19 the pump room
A11 Extra controller trouble alarm contact (DPDT)
Pressure transducer and run test solenoid valve for
A12 Extra engine trouble alarm contact (DPDT) D4 fresh water rated for 0-500psi (for factory calibration
purposes only)
Additional engine alarm contact (DPDT)
Ax Pressure transducer and run test solenoid valve for sea
(specify function) D6 water rated for 0-500PSI
B1 Low fuel level alarm contact (DPDT)
D7A (1-1/4”)
B2 Water reservoir level low alarm contact (DPDT)
D7B
B3 Water reservoir empty alarm contact (DPDT) (1-1/2”)
B12 Water reservoir level high alarm contact (DPDT) D12 Tropicalization
B13 High pump room temperature alarm contact (DPDT) D25 Mounting stand
Additional pump room alarm contact (DPDT) (specify D25A Mounting stand SST- 304 painted
Bx function)
D25B
C5
D25C Mounting stand SST- 316 painted
Nickel – cadmium battery chargers (Battery data sheet
C6 required) D25D
Engine block heater circuit - 3KW max
C7 (same voltage as battery charger primary) D26
Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.
This is a Marketing document. Please consult factory for more information. 31/12/2020
November 2018 6
Manufacturer reserves the right to modify this information without notice
Technical Data
Model GPD Diesel Fire Pump Controller
L08 Hungarian
L09 Slovak
L10 Croatian
L11 Czech
L12 Portuguese
L13 Dutch
L14 Russian
L15 Turkish
L16 Swedish
L17 Bulgarian
L18 Thai
L19 Indonesian
L20 Slovenian
L21 Danish
L22 Greek
L23 Arabic
L24 Hebrew
L25 Chinese
Additional Options:
Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.
This is a Marketing document. Please consult factory for more information. 31/12/2020
November 2018 Manufacturer reserves the right to modify this information without notice 7
Technical Data
Model GPD Diesel Fire Pump Controller
2 3
9
5 6 7 8
This is a Marketing document. Please consult factory for more information. 31/12/2020
November 2018 8
Manufacturer reserves the right to modify this information without notice
REV. DESCRIPTION DD/MM/YY
31/12/2020
Diesel Engine Fire Pump Controller Model GPD
12VDC or 24VDC Negati e Ground
Wiring schematic Built to the latest edition of the NFPA 20 standard
2
1
NO Blac
AB1
NO -
Controller Trouble C J36 J50 Red
C
Fail Safe TB1 AB
NC NC
2
1
NO NO
SV1
VMB1
J37 Brown
C SV
Engine Run Lou er Acti ation Circuit C J24
TB2 Blue
NC NC
2
1
NO NO
C J38
Main Switch in HAND or OFF C
TB3
NC
NC J16 AI5
2
1 -
NO NO IO
Engine Trouble C J39
C
TB4
NC
NC J14 AI4
2
1 -
NO
COM
NO
DI5
DI4
Pump Room Alarm C J40
C
TB5
NC
NC J15 AI3
2 30 32 31
1 -
NO NO
C J42
Field Programmable C
TB6
NC
NC J17 AI2
-
SS1 H
OFF
A
Red
PT1
Low Fuel Le el IN1 J18 AI1 White
- Blac AUTO
Remote Auto Start J1 IN2
HAND
Deluge Val e Start J2 IN3 J25 53
J44 VIN
54
Fuel Tan Lea IN4
J8 DOWN
MP
J35
MP-
BOOST
16
Electronic Control Module Fault 304 304 B1- B2
J103 J106 17
CF1 Com
PLD Low Suction Pressure 305 305 18
ALARM
NO
High Raw Water Temperature 310 310 NC
- L N
Low Engine Temperature 312 312 B2
19 B1 BC2
BOOST
B2-
20 B2
J107 63 11 13 54
Energi e to Start Solenoid 1 1 CF2
21 Com
22
ALARM
NO
Engine Run 2 2
NC
O erspeed 3 3
BATT. SUPPLY
Low Oil Pressure 4 4 - L N
Battery 2 8 8 63
63
Start Contactor 1 9 9 11
J105 11
Start Contactor 2 10 10
11 83
Ground 11 83
Ground 11 8
11 8
82 CB4
Energi e to Stop Solenoid 12 12 DB1 82
Legend
53 54 AB Alarm Bell
BC Battery Charger
CB Circuit Brea er
53 F Filter
14
1L L IS Isolating Switch
L
CB1 J Jumper
120-240 VAC
50-60H F1 13
PT
SS
Pressure Transducer
Selector Switch
1N
N 54 SV Solenoid Val e
E N VMB Vi iTouch Main Board
31/12/2020
REV. DESCRIPTION DD/MM/YY
31/12/2020
REV. DESCRIPTION DD/MM/YY
31/12/2020
Ref. No: WF-2458 Rev. No:
Project Name:
31/12/2020
Ref. No: WF-2458 Rev. No:
Project Name:
31/12/2020
Project Name: Ref. No: WF-2458
Model: WF-6X4X12 HS Rev. No:
PUMP DATA
Service Electric Driven Pump
Series Horizontal Split Case
Size 6X4X12
Rated Flow 1000 GPM
Rated Pressure 145 PSI
Speed 2950 RPM
Rotation Clockwise
Liquid Type Water
Discharge Size 4 inch
Suction Size 6 inch
Impeller Diameter 275 mm
Base Type Steel
Weight 306 KG
Efficiency 74%
HP Maximum 139 HP
MATERIALS OF CONSTRUCTION
Casing Ductile Iron
Impeller Bronze/SS
Shaft steel
Shaft sleeve Stainless steel
Lubrication Grease
DRIVER DATA
Manufacturer WEG
HP Rating 125 HP
Speed 2940 RPM
Weight 455 KG
Starting Method WYE-Delta
Enclosure Type ODP
Service Factor 1.15
Frame Size 404/5TS
Temperature 50 °C
31/12/2020
Performance Curve WF-6x4x12 HS
Rated 400
60 150
150% Rated 350
BHP
50 300
250
40 100
200
Min. 65% at
30 150% Rated
150
20 50
100
10
50
0 0 0
0 250 500 750 1000 1250 1500 1750
31/12/2020
FLOW (GPM)
Ref. No: WF-2458 Rev. No:
Project Name:
31/12/2020
31/12/2020
Ref. No: WF-2458 Rev. No:
Project Name:
31/12/2020
31/12/2020
Ref. No: WF-2458 Rev. No:
Project Name:
31/12/2020
31/12/2020
Ref. No: WF-2458 Rev. No:
Project Name:
31/12/2020
Technical Data
Model GPY Electric Fire Pump Controller
From normal
incoming power through
Disconnecting Means
(IS/CB)*
Shortcircuit 200V to 208V 220V to 240V 380V to 416V 440V to 480V 575V to 600V
Withstand 60Hz 60Hz 50 Hz / 60Hz 60Hz 60Hz
Rating
HP (kw)
5-150 (3.7 - 110) 5-200 (3.7 - 147) 5-300 (3.7 - 220) 5-450 (3.7 - 335) n/a
200 (147) 250 (184) 350 - 450 (257 - 335) 500 (373) 5-500
n/a n/a n/a n/a (3.7- 373)
This is a Marketing document. Please consult factory if additional information is required. 31/12/2020
November 2018 2
Manufacturer reserves the right to modify this information without notice
Technical Data
Model GPY Electric Fire Pump Controller
Standard: Optional:
Temperature 5°C to 40°C / 41°F to 104°F 5°C to 55°C / 41°F to 131°F
Rating
Controllers built in Dubai, UAE (Tornatech FZE) are supplied standard with 55°C rating.
Surge
Surge arrestor rated to suppress surges above line voltage
Suppression
• Isolating switch and circuit breaker assembly:
- Door interlocked in the ON position
- Isolating switch rated not less than 115% of motor full load current
Disconnecting
- Circuit breaker continuous rating not less than 115% of motor full load current
Means
- Overcurrent sensing non-thermal type, magnetic only
- Instantaneous trip setting of not more than 20 times the motor full load current
Service Entrance
Suitable as service entrance equipment
Rating
• Operate shunt trip to open circuit breaker • Trip between 8 and 20 seconds
Protector • Factory set at 600% of motor full load current
This is a Marketing document. Please consult factory if additional information is required. 31/12/2020
November 2018 Manufacturer reserves the right to modify this information without notice 3
Technical Data
Model GPY Electric Fire Pump Controller
DPDT-8A-250V.AC
• Power available
• Phase reversal
• Motor run
• Overvoltage
• Undervoltage
• Phase unbalance
Contacts • Low pump room temperature
• High pump room temperature
• Overcurrent
• Fail to start
• Undercurrent
• Ground fault
**
This is a Marketing document. Please consult factory if additional information is required. 31/12/2020
November 2018 4
Manufacturer reserves the right to modify this information without notice
Technical Data
Model GPY Electric Fire Pump Controller
This is a Marketing document. Please consult factory if additional information is required. 31/12/2020
November 2018 Manufacturer reserves the right to modify this information without notice 5
Technical Data
Model GPY Electric Fire Pump Controller
Seismic
TRU Compliance, LLC
TWEI Project No.: 15014
Company
Mounting
Rigid base and wall mounting
details
Seismic
Building Test Seismic
Code Criteria Parameters
SDS z/h P
Seismic IBC
Information ICC- 2.0 1.0 1.5 3.20 2.40 1.33 0.53
2015, ASCE 7-10
ES
CBC Chapter 13
AC156 3.2 0.0 1.5 3.20 1.28 2.13 0.85
2016
Notes:
• Components are tested in accordance with ICC-ES AC156, IBC 2015 & CBC 2016.
This is a Marketing document. Please consult factory if additional information is required. 31/12/2020
November 2018 6
Manufacturer reserves the right to modify this information without notice
Technical Data
Model GPY Electric Fire Pump Controller
A4 Flow switch provision High water reservoir level c/w visual indication
C18
and alarm contact (DPDT)
Foam pump application w/o pressure
A8
transducer and run test solenoid valve. C19 Emergency start alarm contact (DPDT)
A9 Low zone pump control function C20 Manual start alarm contact (DPDT)
A10 Middle zone pump control function C21 Deluge valve start alarm contact (DPDT)
A11 High zone pump control function C22 Remote automatic start alarm contact (DPDT)
Non-pressure actuated controller w/o pressure C23 Remote manual start alarm contact (DPDT)
A13
transducer and run test solenoid valve
High pump room temperature alarm contact
Lockout/interlock circuit from equipment C24
A16 (DPDT)
installed inside the pump room
Second set of standard alarm contacts (DPDT)
Built in alarm panel (120V.AC supervisory C25
(Typical for city of Los Angeles and Denver)
power) providing indication for:
• Audible alarm & silence pushbutton for motor Additional visual and alarm contact (Specify
B11 Cx
run, phase reversal, loss of phase. function) (DPDT)
• Pilot lights for loss of phase & supervisory Low suction pressure transducer for fresh
power available D1 water rated at 0-300PSI with visual indication
Built in alarm panel same as B11 but 220- and alarm contact
B11B
240VAC supervisory power Low suction pressure transducer for sea water
High motor temperature c/w thermoster relay D1A rated at 0-300PSI with visual indication and
B19A alarm contact
and alarm contacts (DPDT)
High motor temperature c/w PT100 relay and Pressure transducer and run test solenoid
B19B D5 valve for fresh water rated for 0-500PSI (for
alarm contacts (DPDT)
factory calibration purposes only)
Ground fault alarm detection c/w visual
B21 Pressure transducer and run test solenoid
indication and alarm contact (DPDT) D5D
valve for sea water rated for 0-500PSI
C1 Extra motor run alarm contact (DPDT)
D10 Omit mounting feet (when applicable)
C4 Periodic test alarm contact (DPDT)
High withstand rating for
C6 Low discharge pressure alarm contact (DPDT) D13 (normal power section)
• 208V to 480V = 150kA • 600V = 100kA
Low pump room temperature alarm contact
C7
(DPDT) D14 Anti-condensation heater & thermostat
Low water reservoir level alarm contact
C10 D14A Anti-condensation heater & humidistat
(DPDT)
High electric motor temperature alarm contact
C11 Anti-condensation heater & thermostat &
(DPDT) D14B
humidistat
High electric motor vibration c/w visual
C12
indication and alarm contact (DPDT) D15 Tropicalization
Pump on demand / automatic start alarm D18
C14
contact (DPDT)
Modbus with RTU frame format and RS485
C15 Pump fail to start alarm contact (DPDT) D26
connection
C16 Control voltage healthy alarm contact (DPDT) Motor heater connection (external single
D27
Flow meter valve loop open c/w visual
C17
indication and alarm contact (DPDT) Motor heater connection (internal single phase
D27A
Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.
This is a Marketing document. Please consult factory if additional information is required. 31/12/2020
November 2018 Manufacturer reserves the right to modify this information without notice 7
Technical Data
Model GPY Electric Fire Pump Controller
D28 Customized drawing set L01 Other language and English (bilingual)
Field programmable I/O board - L02 French
D34A
5 Input / 5 output
L03 Spanish
L04 German
L05 Italian
L06 Polish
L07 Romanian
L08 Hungarian
L09 Slovak
L10 Croatian
L11 Czech
L12 Portuguese
L13 Dutch
L14 Russian
L15 Turkish
L16 Swedish
L17 Bulgarian
L18 Thai
L19 Indonesian
L20 Slovenian
L21 Danish
L22 Greek
L23 Arabic
L24 Hebrew
L25 Chinese
Additional Options:
Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.
This is a Marketing document. Please consult factory if additional information is required. 31/12/2020
November 2018 8
Manufacturer reserves the right to modify this information without notice
Technical Data
Model GPY Electric Fire Pump Controller
2 3
8
5 6 7
This is a Marketing document. Please consult factory if additional information is required. 31/12/2020
November 2018 Manufacturer reserves the right to modify this information without notice 9
REV. DESCRIPTION DD/MM/YY
31/12/2020
REV. DESCRIPTION DD/MM/YY
31/12/2020
REV. DESCRIPTION DD/MM/YY
31/12/2020
REV. DESCRIPTION DD/MM/YY
31/12/2020
Ref. No: WF-2458 Rev. No:
Project Name:
31/12/2020
Ref. No: WF-2458 Rev. No:
Project Name:
31/12/2020
Performance Curve RV10-50Hz
0 4 8 12 16 20 24 28 32 36 40 44 48 52 Q(US.GPM)
0 4 8 12 16 20 24 28 32 36 40 44 Q(IMP.GPM)
P H
(kPa) (m) H
-22
2200 RV10 (ft)
220 50Hz
700
-20
2000
200
-18
1800 600
180
50Hz
-16
1600 160
-14 500
1400 140
-12
1200 120 400
-10
1000 100
-9
300
-8
800 80
-7
-6
600 60 200
-5
-4
400 40
-3
100
-2
200 20
-1
0 0 0.0
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10 11 12 13 Q(m 3/h)
P 2 (kW) Eta(%)
0.40 80
Eta
0.30 60
P2
0.20 40
0.10 20
0.00 0
0. 0 1. 0 2. 0 3. 0 4. 0 5. 0 6. 0 7. 0 8. 0 9. 0 10 11 12 13 3
Q(m /h)
NPSH NPSH
(m) (f t)
4.0
12
3.0 9
2.0 6
NPSH
1.0 3
0.0 0
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10 11 12 13 Q(m 3/h)
38
Technical Data RV10-50Hz
Performance table
Power Q
Model P 2(kW) (m 3/h) 2.0 4.0 6.0 8.0 10 12 14
RV10-2 0.75 23 22 20 18 16 13 10
RV10-3 1.1 33 32 31 28 25 21 16
RV10-4 1.5 43 42 40 37 32 27 20
RV10-5 2.2 53 51 48 44 39 32 24
RV10-6 2.2 62 61 58 53 46 38 28
RV10-7 3.0 73 72 67 61 54 43 32
RV10-8 3.0 H 83 81 78 71 62 51 37
(m)
RV10-9 3.0 93 91 87 81 71 59 42
20.5 X18 -
G1/2 23
RV10-9 576 293 848 177 116 63
4- 13.5
188 215
RV10-16 821 390 1211 300 275 210 100
280 256
RV10-18 881 390 1271 300 275 210 125
39
Ref. No: WF-2458 Rev. No:
Project Name:
31/12/2020
Technical Data
Model JP3 Jockey Pump Controller
This is a Marketing document. Please consult factory for more information. 31/12/2020
August 2018 2
Manufacturer reserves the right to modify this information without notice
Technical Data
Model JP3 Jockey Pump Controller
This is a Marketing document. Please consult factory for more information. 31/12/2020
August 2018 Manufacturer reserves the right to modify this information without notice 3
Technical Data
Model JP3 Jockey Pump Controller
Seismic
TRU Compliance, LLC
TWEI Project No.: 15014
Company
Mounting
Rigid wall mounting
details
Seismic
Building Test Seismic
Code Criteria Parameters
SDS z/h P
Seismic IBC
Information ICC- 2.0 1.0 1.5 3.20 2.40 1.33 0.53
2015, ASCE 7-10
ES
CBC Chapter 13
AC156 3.2 0.0 1.5 3.20 1.28 2.13 0.85
2016
Notes:
• Components are tested in accordance with ICC-ES AC156, IBC 2015 & CBC 2016.
This is a Marketing document. Please consult factory for more information. 31/12/2020
August 2018 4
Manufacturer reserves the right to modify this information without notice
Technical Data
Model JP3 Jockey Pump Controller
A4 Elapsed time meter (time totalizer) L01 Other language and English (bilingual)
A5 Motor run alarm contact L02 French
A6 Loss of power alarm contact L03 Spanish
A7 Overload or short circuit alarm contact L04 German
D12 CE Mark c/w externally mounted wetted parts L05 Italian
D13A Externally mounted wetted parts L06 Polish
D14 Export packing for 1 controller L07 Romanian
D18 Audible alarm L08 Hungarian
D19 Anti-condensation heater and thermostat L09 Slovak
D20 Anti-condensation heater and humidistat L10 Croatian
D21 Tropicalization L11 Czech
Phase reversal / failure pilot light and alarm L12 Portuguese
D22
contact L13 Dutch
Controller power healthy pilot light and alarm L14 Russian
D23
contact
L15 Turkish
Pump failure via current sensing relay with pilot
D24 L16 Swedish
light and dry alarm contact
L17 Bulgarian
D25 Low zone pump control function
L18 Thai
D26 Mid zone pump control function
D27 High zone pump control function L19 Indonesian
L20 Slovenian
D28 Selector switch in auto alarm contacts
L21 Danish
D29
D30 Motor heater circuit L22 Greek
This is a Marketing document. Please consult factory for more information. 31/12/2020
August 2018 Manufacturer reserves the right to modify this information without notice 5
Technical Data
Model JP3 Jockey Pump Controller
iPD+
This is a Marketing document. Please consult factory for more information. 31/12/2020
August 2018 6
Manufacturer reserves the right to modify this information without notice
31/12/2020
31/12/2020
31/12/2020
Ref. No: WF-2458 Rev. No:
Project Name:
31/12/2020
31/12/2020
31/12/2020
31/12/2020
31/12/2020
31/12/2020
31/12/2020
31/12/2020
31/12/2020
31/12/2020
R
31/12/2020
03/10/2018
R
31/12/2020
03/10/2018
31/12/2020
03/10/2018
31/12/2020
03/10/2018
31/12/2020
03/10/2018
VENTURI: ZINC PLATED STEEL
31/12/2020
31/12/2020
31/12/2020
31/12/2020
Ref. No: WF-2458 Rev. No:
Project Name:
31/12/2020
31/12/2020
31/12/2020
31/12/2020
31/12/2020
31/12/2020
31/12/2020
Certificate of Compliance
This certificate is issued for the following:
Prepared for:
Waterfall Pumps Manufacturing
Al Ttay, Warehouse No 1-5
Plot No 2840764
PO Box No: 446054, Dubai UAE
Said Approval is subject to satisfactory field performance, continuing Surveillance Audits, and strict conformity to the
constructions as shown in the Approval Guide, an online resource of FM Approvals.
David B. Fuller
VP, Manager Fire Protection
FM Approvals
1151 Boston-Providence Turnpike
Norwood, MA 02062
31/12/2020
Page 1 of 3
Certificate of Compliance
Rated Rated Rated Net Rated Net Rated Suction Discharge
Product Capacity, Capacity, Head at Rated Head at Rated Speed, Inlet, Outlet, Stage(s)
(gal/min) (dm³/min) Capacity, psi Capacity, kPa r/min dia., in. dia., in.
WF-6x4x10 HS 400 1515 134-197 925-1360 3500 6 4 1
WF-6x4x10 HS 450 1705 134-196 925-1350 3500 6 4 1
WF-6x4x10 HS 500 1895 134-197 925-1360 3500 6 4 1
WF-6x4x10 HS 750 2840 134-197 925-1360 3500 6 4 1
WF-6x4x10 HS 1000 3785 126-196 870-1350 3500 6 4 1
WF-6x4x12 HS 750 2840 125-196 860-1350 2800 6 4 1
WF-6x4x12 HS 1000 3785 116-194 800-1340 2800 6 4 1
WF-6x4x12 HS 1000 3785 126-209 870-1440 2900 6 4 1
WF-6x4x12 HS 1000 3785 130-217 895-1495 2950 6 4 1
WF-6x4x12 HS 1000 3785 135-224 930-1545 3000 6 4 1
WF-6x4x12 HS 400 1515 218-310 1505-2135 3500 6 4 1
WF-6x4x12 HS 450 1705 218-309 1505-2130 3500 6 4 1
WF-6x4x12 HS 500 1895 218-308 1505-2125 3500 6 4 1
WF-6x4x12 HS 750 2840 215-311 1480-2145 3500 6 4 1
WF-6x4x12 HS 1000 3785 208-309 1435-2130 3500 6 4 1
WF-6x4x17 HS 500 1895 230-295 1585-2035 2800 6 4 1
WF-6x4x17 HS 750 2840 225-281 1550-1935 2800 6 4 1
WF-6x4x17 HS 1000 3785 192-259 1325-1785 2800 6 4 1
WF-6x4x17 HS 500 1895 247-317 1705-2185 2900 6 4 1
WF-6x4x17 HS 750 2840 242-304 1670-2095 2900 6 4 1
WF-6x4x17 HS 1000 3785 222-280 1530-1930 2900 6 4 1
WF-6x4x17 HS 500 1895 256-328 1765-2260 2950 6 4 1
WF-6x4x17 HS 750 2840 250-315 1725-2170 2950 6 4 1
WF-6x4x17 HS 1000 3785 230-292 1585-2015 2950 6 4 1
WF-6x4x17 HS 500 1895 265-340 1825-2345 3000 6 4 1
WF-6x4x17 HS 750 2840 259-326 1785-2250 3000 6 4 1
WF-6x4x17 HS 1000 3785 240-303 1655-2090 3000 6 4 1
WF-8x5x11 HS 750 2840 122-183 840-1260 2800 8 5 1
WF-8x5x11 HS 1000 3785 117-181 805-1250 2800 8 5 1
WF-8x5x11 HS 1250 4730 111-175 765-1205 2800 8 5 1
WF-8x5x11 HS 1500 5680 105-168 725-1160 2800 8 5 1
WF-8x5x11 HS 750 2840 131-197 905-1360 2900 8 5 1
WF-8x5x11 HS 1000 3785 126-194 870-1340 2900 8 5 1
WF-8x5x11 HS 1250 4730 120-189 825-1305 2900 8 5 1
WF-8x5x11 HS 1500 5680 114-182 785-1255 2900 8 5 1
WF-8x5x11 HS 750 2840 135-204 930-1405 2950 8 5 1
WF-8x5x11 HS 1000 3785 131-201 905-1385 2950 8 5 1
31/12/2020
Page 2 of 3
Certificate of Compliance
Rated Rated Rated Net Rated Net Rated Suction Discharge
Product Capacity, Capacity, Head at Rated Head at Rated Speed, Inlet, Outlet, Stage(s)
(gal/min) (dm³/min) Capacity, psi Capacity, kPa r/min dia., in. dia., in.
WF-8x5x11 HS 1250 4730 124-196 855-1350 2950 8 5 1
WF-8x5x11 HS 1500 5680 119-189 820-1305 2950 8 5 1
WF-8x5x11 HS 750 2840 140-210 965-1450 3000 8 5 1
WF-8x5x11 HS 1000 3785 135-208 930-1435 3000 8 5 1
WF-8x5x11 HS 1250 4730 130-203 895-1400 3000 8 5 1
WF-8x5x11 HS 1500 5680 124-195 855-1345 3000 8 5 1
WF-8x5x11 HS 750 2840 194-277 1340-1910 3500 8 5 1
WF-8x5x11 HS 1000 3785 190-277 1310-1910 3500 8 5 1
WF-8x5x11 HS 1250 4730 185-270 1275-1860 3500 8 5 1
WF-8x5x11 HS 1500 5680 177-265 1220-1820 3500 8 5 1
WF-8x6x11 HS 1500 5680 104-153 715-1055 2900 8 6 1
WF-8x6x11 HS 2000 7570 100-149 690-1025 2900 8 6 1
WF-8x6x11 HS 1500 5680 108-159 745-1095 2950 8 6 1
WF-8x6x11 HS 2000 7570 104-154 715-1060 2950 8 6 1
WF-8x6x11 HS 1500 5680 111-164 765-1130 3000 8 6 1
WF-8x6x11 HS 2000 7570 108-159 745-1095 3000 8 6 1
WF-8x6x11 HS 1500 5680 149-191 1030-1320 3500 8 6 1
WF-8x6x11 HS 2000 7570 144-190 995-1310 3500 8 6 1
WF-8x6x14 HS 1500 5680 135-188 930-1300 2800 8 6 1
WF-8x6x14 HS 2000 7570 124 855 2800 8 6 1
WF-8x6x14 HS 1500 5680 146-203 1010-1400 2900 8 6 1
WF-8x6x14 HS 2000 7570 135-192 930-1320 2900 8 6 1
WF-8x6x14 HS 1500 5680 152-210 1050-1450 2950 8 6 1
WF-8x6x14 HS 2000 7570 140-200 965-1380 2950 8 6 1
WF-8x6x14 HS 1500 5680 157-218 1080-1500 3000 8 6 1
WF-8x6x14 HS 2000 7570 146-207 1010-1430 3000 8 6 1
31/12/2020
Page 3 of 3
31/12/2020
31/12/2020
31/12/2020