INSTALLATION DIAGRAM IFES CONTROL AND INDICATING ALARM PANEL
Part Number - 3.10.001 (Alarm Panel Only)
- 3.10.105K (Alarm Panel with Kit) External
- 3.10.105L (Alarm Panel with Kit - LV Bracket) 5A Fuse
Main Power
CABLE COLOR/
PIN DESCRIPTION Electric Actuation Supply
PIN NO
Circuit 12-24VDC
[Link] 12 Volt DC Common
POWER SUPPLY 12-24 ( + ) DC
[Link] POWER SUPPLY ( - ) Max 1 Ampere
(eg. solenoid valve) Engine Shutdown
[Link] ACTUATED OUTPUT ( - )
[Link] ACTUATED OUTPUT ( + ) Relay Contacts
[Link] SHUTDOWN COMMON Common
[Link] SHUTDOWN N/O Join In Parallel
N/O
[Link] SHUTDOWN N/C
Join In Series
[Link] FIRE ALARM INPUT 2 N/C
[Link] FIRE ALARM INPUT 2
EOL INPUTS :
[Link] DETECTOR COMMON Resistor
FIRE ALARM INPUT 1 - Fire Detector
[Link]-GREEN 47K Ohm - Fire Alarm Pressure Switch
[Link] LOW PRESSURE DETECTOR
FIRE ALARM 2 - Electric Manual Actuator
EOL
Resistor See Drawing Below
7 8 9 10 11 12
47K Ohm For Detail
FIRE ALARM 1
6 5 4 3 2 1
12 PIN DEUTSCH PLUG MALE LOW PRESSURE SWITCH
(FRONT VIEW) Open at press = 0 KPa
Closed at press = 900KPa +
A. TYPICAL LOP SYSTEM INSTALLATION
FIRE ALARM PRESSURE SWITCH
Fire Alarm 2 - Not Used Closed at press = 0 KPa
Install 47K Ohm Resistor Wire Assembly (3.51.021) Open at press = 200 KPa +
Open 47KOhm EOL Resistor active.
.
Fire Alarm 1 -
LOP Systems EOL Resistor Installed Inside
Deutsch Plug Connector
B. TYPICAL ELECTRIC SYSTEM INSTALLATION
2 pin Small Deutsch
Plug with EOL
Resistor
Electric Manual
Remote Actuator
4 pin Male Deutsch
Plug Bottom view
Linear Heat Detection Cable
4 pin Male
Deutsch Plug
2 pin Male Deutsch Plug
with EOL Resistor
2 Core Tethering Cable
Fire Alarm 2 - Manual
Actuator Electric
Fire Alarm 1 - 2 Core Tethering Cable
LHD Cable
INSTALLATION DIAGRAM INDICATING ALARM PANEL
Part Number - 3.10.002 (Alarm Panel Only)
- 3.10.106K (Alarm Panel with Kit)
External
5A Fuse
CABLE COLOR/ Main Power
PIN NO Supply
12-24VDC
[Link] POWER SUPPLY 12-24 ( + ) DC
[Link] POWER SUPPLY ( - )
[Link] NOT USED Engine Shutdown
[Link] NOT USED Relay Contacts
[Link] SHUTDOWN COMMON Common
[Link] SHUTDOWN N/O Join In Parallel
N/O
[Link] SHUTDOWN N/C
Join In Series
[Link] NOT USED N/C
[Link] NOT USED
[Link] DETECTOR COMMON
[Link]-GREEN FIRE DETECTOR FIRE ALARM PRESSURE SWITCH
Closed at press = 0 KPa
[Link] LOW PRESSURE DETECTOR
Open at press = 200 KPa +
Open 47KOhm EOL resistor active.
7 8 9 10 11 12
6 5 4 3 2 1
LOW PRESSURE SWITCH
12 PIN DEUTSCH PLUG MALE
Open at press = 0 KPa
(FRONT VIEW)
Closed at press = 900KPa +
Faults Code Alarm Panel
LED Fault and Beeps Code Fault Description
1 Beep + 1 Flash Fire Detector 1 Fault
*) 2 Beeps + 2 Flashes Fire Detector 2 Fault or Electric Manual Actuator Fault
3 Beeps + 3 Flashes Cylinder Low Pressure Fault
*) 4 Beeps + 4 Flashes Solenoid Valve Fault
*) 5 Beeps + 5 Flashes Battery Backup Fault
Notes: *) Only applies to Control & Indicating panel.
Fault indications are not latching. This means that the fault indication will disappear when the fault is
repaired without resetting the alarm. The fault audible beep sound can be muted by pressing the
“Mute” button.
Part No 7.100.012: Alarm wiring diagnostic panel
- Used to Analyze the wiring compliance before
connection to the alarm
Part No:
7.100.009A: Demonstration case Alarm Panel W/O panel.
7.100.009: Demonstration case Alarm Panel with panel 3.10.001
- Used to check alarm performance and for training in alarm
use. The data cable used with PC to check programming
parameters and data log history