Technical Data: Indoor Units Ftx-Gv1B
Technical Data: Indoor Units Ftx-Gv1B
FTX-GV1B
technical data
FTX-GV1B
• Indoor Units • R-410A • FTX-GV1B
TABLE OF CONTENTS
FTX-GV1B
1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4 Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Wiring diagram ....................................................... 8
6 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1 Features
t i y n k U S B 1 r AVt o 0G i o 1- ld 4X npT- RFS•I 3D air flow combines vertical and horizontal auto-swing to circulate a • Titanium apatite photocatalytic air purification filter absorbs
stream of warm/cool air right to the corners of even large spaces microscopic particles, decomposes odours and even deactivates
• Indoor / outdoor unit silent operation: “Silent” buttons on the remote bacteria and viruses
control lower the operation sound of the indoor and/or outdoor unit by • Daikin’s special dry programme reduces humidity in the room without
3dBA variation in room temperature
• Home leave operation saves energy during absence • 24-Hour On/Off timer
• Powerful mode can be selected for rapid cooling • Night set mode saves energy by preventing overcooling or
overheating during night time
• Auto-restart after power failure
2 Specifications
2 Specifications
performance)
(Space for
Rear Rear
Min. 30
Left Right
(Space for
maintenance)
Min. 50 Min. 50
Operation lamp
Model name
Signal receiver plate
Indoor unit on/off
switch Terminal block
Room temp. thermistor with earth
(inside) terminal (inside)
Intelligent eye sensor
Timer lamp Drain hose for VP13
Gas pipe ø12.7 Cut (connection part
Front grille fixing screws Home leave lamp (the lenght of pipe outside I.D. 14.0, O.D. 18.0)
Flaps (inside) the unit: about 430) (The hose length
Liquid pipe ø 6.4 Cut of outside the unit:
Signal (the lenght of pipe outside the about 530)
transmitter unit: about 480)
BLADE ANGELS
Horizontal blade
(automatic)
Cooling Heating Dry
3D055875A
FTX71GV
Air flow (indoor)
(For performance and maintenance)
The mark shows piping direction
performance)
(Space for
Rear Rear
Min. 30
Left Right
(Space for
maintenance)
Min. 50 Min. 50
Operation lamp
Model name
Signal receiver plate
Indoor unit on/off
switch Terminal block
Room temp. thermistor with earth
(inside) terminal (inside)
Intelligent eye sensor
Timer lamp Drain hose for VP13
Gas pipe ø15.9 Cut (connection part
Front grille fixing screws Home leave lamp (the lenght of pipe outside I.D. 14.0, O.D. 18.0)
Flaps (inside) the unit: about 430) (The hose length
Liquid pipe ø 6.4 Cut of outside the unit:
Signal (the lenght of pipe outside the about 530)
transmitter unit: about 480)
BLADE ANGELS
Horizontal blade
(automatic)
Cooling Heating Dry
3D055876A
4D065971A
4 Piping diagram
(7.9 CuT)
Heat exchanger
(6.4 CuT)
Fan motor
Field piping
Refrigerant flow
Cooling
Heating 4D040081V
(7.9 Cut)
Heat exchanger
(6.4 Cut)
Fan motor
Field piping
Refrigerant flow
Cooling
Heating 4D040082T
5 Wiring diagram
5-1 Wiring diagram
FTX50-71GV
Field wiring
RECTIFIER
Outdoor
Transmission CAUTION
circuit Note that operation will restart
automatically if the main power
supply is turned off and then back
on again.
Intelligent eye
sensor
Indoor
Signal
receiver
infrared
remote
control
3D038530T
6 Sound data
6-1 Sound pressure spectrum
FTX50GV
Cooling Heating
Octave band sound pressure level dB (0 dB = 0.0002μ bar)
Octave band center frequency - IEC (Hz) 3D050979B Octave band center frequency - IEC (Hz) 3D050979B
NOTES 50Hz NOTES 50Hz
Scale 220-240V Scale 220-240V
1 Over All (dB): H L 1 Over All (dB): H L
(B,G,N is already rectified) A 43 34 (B,G,N is already rectified) A 42 33
2 Measuring place: measure in anechoic room. 2 Measuring place: measure in anechoic room.
3 Operation noise differs with operation and ambient conditions. 3 Operation noise differs with operation and ambient conditions.
4 Location of microphone. 4 Location of microphone.
1m 1m
JISC9612 JISC9612
The operation noise The operation noise
0.8m
0.8m
measuring method is in measuring method is in
accordance with JISC9612 accordance with JISC9612
3D050979B
FTX60GV
Cooling Heating
Octave band sound pressure level dB (0 dB = 0.0002μ bar)
Approximate Approximate
threshold hearing threshold hearing
for continuous for continuous
noise noise
Octave band center frequency - IEC (Hz) 3D051227D Octave band center frequency - IEC (Hz) 3D051227D
NOTES 50Hz NOTES 50Hz
Scale 220-240V Scale 220-240V
1 Over All (dB): H L 1 Over All (dB): H L
(B,G,N is already rectified) A 45 36 (B,G,N is already rectified) A 44 35
2 Measuring place: measure in anechoic room. 2 Measuring place: measure in anechoic room.
3 Operation noise differs with operation and ambient conditions. 3 Operation noise differs with operation and ambient conditions.
4 Location of microphone. 4 Location of microphone.
1m 1m
JISC9612 JISC9612
The operation noise The operation noise
0.8m
0.8m
3D051227D
6 Sound data
6-1 Sound pressure spectrum
FTX71GV
Cooling Heating
Octave band sound pressure level dB (0 dB = 0.0002μ bar)
Octave band center frequency - IEC (Hz) 3D051225D Octave band center frequency - IEC (Hz) 3D051225D
NOTES 50Hz NOTES 50Hz
Scale 220-240V Scale 220-240V
1 Over All (dB): H L 1 Over All (dB): H L
(B,G,N is already rectified) A 46 37 (B,G,N is already rectified) A 46 37
2 Measuring place: measure in anechoic room. 2 Measuring place: measure in anechoic room.
3 Operation noise differs with operation and ambient conditions. 3 Operation noise differs with operation and ambient conditions.
4 Location of microphone. 4 Location of microphone.
1m 1m
JISC9612 JISC9612
The operation noise The operation noise
0.8m
0.8m
measuring method is in measuring method is in
accordance with JISC9612 accordance with JISC9612
3D051225D
Naamloze Vennootschap
Zandvoordestraat 300
B-8400 Oostende, Belgium
Copyright Daikin