1. GENERAL DESCRIPTION OF PUMP ROOM
2. SPRINKLER FIRE PUMPS AND CONTROLS
2.1 JOCKEY PUMP
2.2 JOCKEY PUMP CONTROLLER
2.3 DIESEL SPRINKLER PUMP
2.4 DIESEL SPRINKLER PUMP CONTROLLER
3. ALARM CONDITIONS
4. WEEKLY TEST PROCEDURE
5. DRAWINGS
* Auto start Arrangement Drawing
* Fuel Tank Drawing
* Electrical Drawings
6. PUMP CURVES
7. MANUFACTURERS OPERATING BOOKLETS
* Flow meter
* RS1000
* Grundfos Jockey Pump
* KSB Etanorm Pump
* Clarke Engine
Page 1 of 15
Cc:
1991/013122/23
Tel no:
012 372 5910
Fax
no: 012 372 5913
P.O.
Box 31514
Wonderboompoort 0033
1. GENERAL DESCRIPTION OF PUMP ROOM
The sprinkler system consists of a diesel driven unit and a
jockey / pressurization pump.
There are separate wall mounted controllers for each of
the above pumps. Test arrangements for testing the
automatic starting of all pumps are mounted on the pump
house wall, these test arrangements have pressure
switches, which automatically start the pumps at the
preset pressures.
2. SPRINKLER FIRE PUMPS AND CONTROLS
2.1 JOCKEY PUMP
The jockey pump is a pressure maintaining pump, which
will keep the system at a pressure, which is above that
which will cause the diesel sprinkler pump to operate
automatically.
Page 2 of 15
Cc:
1991/013122/23
Tel no:
012 372 5910
Fax
no: 012 372 5913
P.O.
Box 31514
Wonderboompoort 0033
2.2 JOCKEY PUMP CONTROLLER
With the selector, which in the “manual” mode the pump
will start and run continuously.
With the selector switch in the “auto” mode the pump will
start and stop via a pressure switch on the test
arrangement to maintain the system pressure.
A pump running and a pump trip indicator is on the facia
of the jockey controller.
2.3 DIESEL SPRINKLER PUMP
The diesel sprinkler pump is the duty pump and would
operate on a fire condition.
2.4 DIESEL SPRINKLER PUMP CONTROLLER
Should the pressure drop in the sprinkler system and
reach the predetermined set point pressure on the test
arrangement for the diesel sprinkler pump then the
Page 3 of 15
Cc:
1991/013122/23
Tel no:
012 372 5910
Fax
no: 012 372 5913
P.O.
Box 31514
Wonderboompoort 0033
controller will latch onto this signal and start the diesel
fire pump automatically.
The fire alarm and pump run light will be illuminated. To
stop the pump, the reset push-button must be pressed
and then manually stopped on the diesel engine. If the
pressure in the sprinkler system is not up to the normal
level the diesel pump will restart as soon as the engine
stop lever is released.
If the diesel engine does not start immediately on
receiving a test or automatic signal the diesel engine will
proceed through a crank cycle.
The diesel engine will crank on battery No1 for 15
seconds and dwell for 6 seconds before attempting to
crank on battery No2. A total of 6 start attempts are
made, after which the start cycle will stop and a pump fail
light will be illuminated on the diesel controller.
Should the diesel engine start at any time during the
cranking of the diesel engine the diesel controller will
Page 4 of 15
Cc:
1991/013122/23
Tel no:
012 372 5910
Fax
no: 012 372 5913
P.O.
Box 31514
Wonderboompoort 0033
receive a signal from the diesel engine and will abort the
crank cycle.
The test push-button on the diesel controller will simulate
an automatic start from the test arrangement and the
pump will operate as listed above.
Emergency start push buttons 1 or 2 will bypass the
automatic and control circuits and will start the diesel
pump set. When the diesel pump set is started like this
the pump run light only will be illuminated.
The diesel engine must be manually stopped by pulling
the engine stop lever on the diesel engine.
3. ALARM CONDITIONS
NORMAL CONDITIONS
The Green System on indicator must be illuminated.
1. FIRE ALARM CONDITION:
a) The fire alarm indicator must flash.
Page 5 of 15
Cc:
1991/013122/23
Tel no:
012 372 5910
Fax
no: 012 372 5913
P.O.
Box 31514
Wonderboompoort 0033
b) Siren 1 must sound.
c) Strobe light must flash.
d) The bleeper must sound.
2. PUMP RUNNING:
a) The pump running indicator must flash.
b) Strobe light must flash.
c) The bleeper must sound.
3. PUMP FAIL:
a) Pump fail indicator must flash.
b) Siren 2 must sound.
c) Strobe light must flash.
d) The bleeper must sound.
4. MAINS FAIL:
a) The mains fail indicator must flash.
b) The local bell must sound.
c) The strobe light must flash.
d) The bleeper must sound.
Page 6 of 15
Cc:
1991/013122/23
Tel no:
012 372 5910
Fax
no: 012 372 5913
P.O.
Box 31514
Wonderboompoort 0033
5. CONTROL CIRCUIT FAIL:
a) The control circuit fail indicator must flash.
b) The local bell must sound.
c) The strobe light must flash.
d) The bleeper must sound.
6. BATTERY CHARGER: 1 + 2 FAIL:
a) The battery charger fail indicator must flash.
b) The local bell must sound.
c) The strobe light must flash.
d) The bleeper must sound.
7. LOW OIL PRESSURE:
a) The low oil pressure indicator must flash.
b) The local bell must sound.
c) The strobe light must flash.
d) The bleeper must sound.
Page 7 of 15
Cc:
1991/013122/23
Tel no:
012 372 5910
Fax
no: 012 372 5913
P.O.
Box 31514
Wonderboompoort 0033
8. HIGH ENGINE TEMPERATURE:
a) The high engine temperature indicator must flash.
b) The local bell must sound.
c) The strobe light must flash.
d) The bleeper must sound.
9. PUMP HOUSE PROTECTION:
a) The pump house protection indicator must flash.
b) The local bell must sound.
c) The strobe light must flash.
d) The bleeper must sound.
10. SYSTEMS FAULT:
a) The systems fault indicator must flash.
b) The local bell must sound.
c) The fault bleeper must sound.
11. AUDIBLE AND STROBE LIGHT FAULT:
Page 8 of 15
Cc:
1991/013122/23
Tel no:
012 372 5910
Fax
no: 012 372 5913
P.O.
Box 31514
Wonderboompoort 0033
Siren 1; siren 2; bell and strobe light fault indicators are
mounted on the fault monitoring control circuits in the
panel. Should any of the above and any of 1-10 detect a
fault condition on the lines, the following must occur:
a) System fault indicator must flash.
b) Local bell must sound.
c) Fault bleeper must pulse.
d) The relevant LED indicator must be illuminated.
12. ALARM ACCEPT:
In the event of an alarm or a fault the following procedure
must be implemented:
Press the alarm accept switch, all audible alarms will
silence, and all visual indicators will go steady.
13. LAMP TEST SWITCH:
Operation of this switch will test all lamps on the front
facia of the panel.
Page 9 of 15
Cc:
1991/013122/23
Tel no:
012 372 5910
Fax
no: 012 372 5913
P.O.
Box 31514
Wonderboompoort 0033
********************
4. WEEKLY TEST PROCEDURE SPRINKLER PUMPS
It is an A.S.I.B. requirement that the sprinkler pumps are
tested weekly.
4.1 SPRINKLER INSTALLATION CONTROL VALVES
1) Before and after testing record the pressure at
the installation gauge and water supply gauge.
2) Actuate the alarm valve by opening the test
valve and check the valve for correct operation.
3) Check for the correct operation on the external
alarm, motor and gong.
4) Check that all stop valves are secured in the
open or closed position, as appropriate.
Attention must be given to the main control
valves, alarm clocks, waste and test valves.
Page 10 of 15
Cc:
1991/013122/23
Tel no:
012 372 5910
Fax
no: 012 372 5913
P.O.
Box 31514
Wonderboompoort 0033
5) Check that the required spare sprinklers and
sprinkler spanner are on hand.
4.2 PUMP HOUSE AND WATER SUPPLIES
1) Check water level and automatic filling facilities
of water supply tanks.
2) Check all water level warning devices.
3) Check the diesel and annunciator batteries and
battery chargers are free from corrosion in
battery cabinet or compartment and security of
battery in its position.
4) Check diesel engine oil level with dipstick.
5) Check water coolant level in heat exchanger,
should be approx. ¾ full.
6) Start all pumping units from the test valve on
the auto start arrangement.
4.3 JOCKEY PUMP
A. Manually test pump starting by switching
hand/auto to the hand position. After start up,
return switch to the auto position.
Page 11 of 15
Cc:
1991/013122/23
Tel no:
012 372 5910
Fax
no: 012 372 5913
P.O.
Box 31514
Wonderboompoort 0033
B. Test the automatic starting of this pump by
dropping the pressure on the pressure switch in
the following manner:
1. Close valve A on the auto start arrangement (refer
to auto start drawing).
2. Slowly open valve B to drop the pressure and at
the predetermined setting. The pump will start.
Close valve B and open valve A to allow the
pressure to return, the pump will stop.
4.4 DIESEL ENGINE PUMP SET
A. Start engine on test buttons and check the
following:
1. Water, oil and fuel leaks and for loose fittings and
ancillary equipment.
2. Cooling water flow in sight glass (Stop engine
immediately should this not be flowing).
Page 12 of 15
Cc:
1991/013122/23
Tel no:
012 372 5910
Fax
no: 012 372 5913
P.O.
Box 31514
Wonderboompoort 0033
3. Efficient pump gland operation.
4. Check that the audible (Continuous) siren and
flashing light outside the pump house are operating.
5. Check “Fire” and “pump running” pilot lights are
alight on the diesel/annunciator panel.
6. Ensure “Low Oil Pressure” light is not signalling.
7. Before and after running, check oil, water and fuel
levels. Top up if required.
8. Stop the engine by FIRST depressing the
“STOP/RESET” button then holding the fuel shut-off
lever on the diesel engine in the off position until the
engine is stationary.
THE ENGINE WILL RESTART IF THE “STOP/RESET”
BUTTON IS NOT FIRST DEPRESSED
Page 13 of 15
Cc:
1991/013122/23
Tel no:
012 372 5910
Fax
no: 012 372 5913
P.O.
Box 31514
Wonderboompoort 0033
9. After running engine for a minimum period of 15
minutes ensure that the engine stop mechanism
automatically returns to start position.
B. Start the engine via the Auto / Start
arrangement by the following procedure:
1. Close valve C on the auto start arrangement (refer
auto start drawing).
2. Slowly open valve D to allow the pressure to drop,
check that the pumps start at the predetermined
pressure setting.
3. Check all items as per (A) above.
4. Close valve D and open valve C to allow
pressure to return to normal reset pressure. Stop
pump set as per A8 above.
C. Start the engine via the Auto / Start
arrangement by the following
procedure:
Page 14 of 15
Cc:
1991/013122/23
Tel no:
012 372 5910
Fax
no: 012 372 5913
P.O.
Box 31514
Wonderboompoort 0033
1. Close valve E on the auto start arrangement (refer
auto start drawing).
2. Slowly open valve F to allow the pressure to drop,
check that the pumps start at the predetermined
pressure setting.
3. Check all items as per (A) above.
4. Close valve F and open valve E to allow pressure to
return to normal reset pressure. Stop pump set as
per A8 above.
All pressure switch settings will be available once
commissioning has been completed and will be
recorded on the commissioning schedule.
Page 15 of 15