0% found this document useful (0 votes)
67 views9 pages

(英文)NDB1C-63 产品规格书【2024.07.30】

The document provides the product specification for the NDB1C-63 Miniature Circuit Breaker, detailing its application, technical parameters, and installation requirements. It includes information on electrical characteristics, protection features, and compliance with standards such as CCC and CE. Additionally, it outlines packaging, storage conditions, and accessory options for the product.

Uploaded by

Denizhan Akın
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
67 views9 pages

(英文)NDB1C-63 产品规格书【2024.07.30】

The document provides the product specification for the NDB1C-63 Miniature Circuit Breaker, detailing its application, technical parameters, and installation requirements. It includes information on electrical characteristics, protection features, and compliance with standards such as CCC and CE. Additionally, it outlines packaging, storage conditions, and accessory options for the product.

Uploaded by

Denizhan Akın
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

文件编号:NDT2930516 文件版本:1

Shanghai Liangxin Electrical Co., Ltd.

Product Specification of NDB1C-63


(IPD-ENG-DEV-T22 A0 2016-04-20)

Product Name: Miniature Circuit Breaker


Product type: NDB1C-63
Date: 20240730

Prepared Huang Jingkai Date 2024-07-30

Reviewed Liu Xiangqian Date 2024-07-30

Approved Huo Zhiqiang Date 2024-07-30

Add:No.2000, South Shenjiang Road, Pudong New Area, Shanghai, 201315, PRC
Tel:(021)68586699 Fax: (021)23025796
Page 1 of 9
文件编号:NDT2930516 文件版本:1

Revision information

Version Revised contents and reasons Date Prepared Reviewed Approved


Zhu
0 Initial issue 20200416 Huo Zhiqiang Zhang Yang
Tongxiong
Huang Huo
1 Update photos 20240730 Liu Xiangqian
Jingkai Zhiqiang

Add:No.2000, South Shenjiang Road, Pudong New Area, Shanghai, 201315, PRC
Tel:(021)68586699 Fax: (021)23025796
Page 2 of 9
文件编号:NDT2930516 文件版本:1

1、Application
●Short -circuit protection
●Over-load protection
●Isolation
NDB1C-63 dedicated to the low voltage power distribution system of industrial, buildings, energy
communications and infrastructure.

2、Product Pictures (The picture is for reference only,subject to the actual object)

1P 2P 3P 4P

3、Model and implication


ND B 1 C — 63 C 16 / 2

Breaker Design Derive Frame Trip curve Rated current(A) Pole


code code Rating(A) B 1,2, 3, 4, 1=1P, 2=2P,
63 C 5,6,10,16, 3=3P,4=4P
D 20, 25,32,
40,50*,63*

*Note: D curve is not available for 50A and 63A breaker.

4、Main technical parameters


● Electrical parameters

○Number of Poles: 1P, 2P, 3P, 4P


○Rated working Voltage:1P:AC230/400V,AC240/415V,DC60/80V;
2P:AC400/415V,DC60/80V;
3P:AC400/415V;
4P:AC400/415V

○Rated Current: 1A,2A,3A,4A,5A,6A, 10A, 16A,20A,25A,32A,40A,50A,63A(D curve is not available for

50A and 63A breaker)

○Rated Insulation Voltage: 500V

○Rated Frequency: 50/60Hz

○Rated Impulse Withstand Voltage: 4kV

○Rated Frequency Withstand Voltage: AC2500V 50Hz 1min

Add:No.2000, South Shenjiang Road, Pudong New Area, Shanghai, 201315, PRC
Tel:(021)68586699 Fax: (021)23025796
Page 3 of 9
文件编号:NDT2930516 文件版本:1

○Breaking Capacity(Icn): 6 kA (B, C curve breaker 40A and below),


4.5 kA(B, C curve breaker 50A and above, D curve breaker)
10kA(B, C curve breaker,DC60/80V)
○Rated short circuit breaking Capacity(Ics): 6 kA (B, C curve breaker 40A and below),
4.5 kA(B, C curve breaker 50A and above, D curve breaker)
7.5kA(B, C curve breaker,DC60/80V)

○Instantaneous Tripping Characteristic: B、C、D

●Mechanical and Electrical life


○Mechanical Life: 20000 times

○Electrical Life: 10000 times

● Isolation function

○ Practical breaking instructions

○ View window within the green identification said contact in the off position

● Protection Degree

IP20

●Wire Feeding Mode

Lines in for both up and down ends

● Use Category

● Mounting Class

II、III

● Tripping characteristic

B type curve
○ Protection of short circuit current small load
○ rated current:1A~63A
○ tripping characteristic:The instantaneous tripping range 3In~5In
C type curve
○ Protect normal load and distribution wire cable
○ rated current:1A~63A
○ tripping characteristic:The instantaneous tripping range 5In~10In
D type curve
○ Protect starting current big impact load(Such as motor, transformer)
○ rated current:1A~63A
○ tripping characteristic:The instantaneous tripping rang 10In~14In
● Product certification and implementation standard.:
○ Product certificate:CCC,CE,TUV;
○ Product certification standard:GB/T 10963.1,IEC60898-1, GB/T 10963.2,IEC60898-2;
● Environmental requirements:RoHS

Add:No.2000, South Shenjiang Road, Pudong New Area, Shanghai, 201315, PRC
Tel:(021)68586699 Fax: (021)23025796
Page 4 of 9
文件编号:NDT2930516 文件版本:1

5、Normal Working conditions


●Ambient temperature:-40℃~+70℃

●Stored ambient temperature:-40℃~+80℃


●Heat and humidity resistance:The relative air humidity ≤95% at the temperature of +55℃

●Altitude:≤2000m, if you want to apply it more than 2000m, you must refer to Miniature Circuit Breaker’s

reduced capacity table. Also you can refer to GB/T20645 the technological requirement of the low-voltage
electrical equipment when it is used on high altitude.

●Pollution degree: 3

●Free from obvious vibration or shock

6、Lower capacity coefficient table above 2000 meters above sealevel


Height Rated Breaking
Breaking
above Rated Rated frequency Capacity
Capacity Remarks
sea level current voltage voltage and Electrical life
(km) tolerance

2 In Ue 1.00 1.00 1.00

3 0.97 In Ue 0.89 0.89 0.83

4 0.94In Ue 0.80 0.80 0.71

5 0.90In Ue 0.73 0.73 0.63

7、Side-by-side volume reduction coefficient table

8、Temperature Derating

Add:No.2000, South Shenjiang Road, Pudong New Area, Shanghai, 201315, PRC
Tel:(021)68586699 Fax: (021)23025796
Page 5 of 9
文件编号:NDT2930516 文件版本:1

9、Time-Current curves

(3~5)In (5~10)In (10~14)In

Add:No.2000, South Shenjiang Road, Pudong New Area, Shanghai, 201315, PRC
Tel:(021)68586699 Fax: (021)23025796
Page 6 of 9
文件编号:NDT2930516 文件版本:1

10、Outline and installation dimensions

1P 2P

3P 4P

Add:No.2000, South Shenjiang Road, Pudong New Area, Shanghai, 201315, PRC
Tel:(021)68586699 Fax: (021)23025796
Page 7 of 9
文件编号:NDT2930516 文件版本:1

11、Installation method
Modular construction,can be installed in TH35mm x 7.5 standard guide rail.
12、Connect line requirements
The wire capacity: 1mm²~25mm²conducting wire
Terminal screw: M5; Recommended tightening torque: 2.0N.m
13、Packaging and storage
● Maximum packing quantity
1P: 12 pieces in a box, 12 boxes in an overwrap carton.
2P: 6 pieces in a box, 12 boxes in an overwrap carton.
3P: 4 pieces in a box, 12 boxes in an overwrap carton.
4P: 3 pieces in a box, 12 boxes in an overwrap carton.
● Products should be stored in the warehouse where there is ventilation. The relative humidity there
should not exceed 80%, and the ambient temperature there is between -40℃ to +80℃. In addition,
there should not be acidic, alkaline and corrosive gas in the air.
● Products should not be deposited more than 3 years in the above mentioned conditions since the
producing date.

14、Accessory list and installation


●OF1 Auxiliary Contact Be installed to the left side of NDB1C-63 to indicate the t ripping status of
the breaker.
●SD1 Alarm Contact Be installed to the left side of NDB1C-63 to indicate the fault tripping status of
the breaker.
●MX+OF1 Shunt Release Be installed to the left side of NDB1C-63,remotely controls the breaker
opening and indicates the breaker tripping status.
●GQ1A Over&Under Voltage Tripping Device Be installed to the left side of NDB1C-63,used
for circuit of work voltage less than AC 230V,which has defensive function such as over-voltage
protection(G1A)、low-voltage protection(Q1A)、over&low-voltage protection(GQ1A),at the same
time,no-tripping when power down;
●FF1 Double Auxiliary Contact Be installed to the left side of NDB1C-63 to indicate the tripping
status of the breaker
●FS1 Auxiliary and Alarm Contact Be installed to the left side of NDB1C-63 to indicate the fault
tripping status of the breaker.
●NDH1 series busbar is a kind of modulus accessory for NDB1C-63, which applies to connecting the
ends of the same phase incoming line of several breakers. It can also be used as a general standard
accessory which connects the electric appliances of the same phase terminal.

Add:No.2000, South Shenjiang Road, Pudong New Area, Shanghai, 201315, PRC
Tel:(021)68586699 Fax: (021)23025796
Page 8 of 9
文件编号:NDT2930516 文件版本:1

15、Notices
1、The user should responsible for the quality problem caused by taking the products apart or adjust the
tripping parameters without permission.
2、Touch the uninsulated bare part is not allowed when breaker is energized state.
3、Make sure reliable connection to prevent the abnormal heating of terminals. That can cause fault operation
of breakers or terminal damage.
4、Please remove the cover before installation, details please refer to Product Specification.

Add:No.2000, South Shenjiang Road, Pudong New Area, Shanghai, 201315, PRC
Tel:(021)68586699 Fax: (021)23025796