Gempro Software Guide
Gempro Software Guide
Volume 3 – GEMPRO
276192-113 Rev. I
Foreword
This Technical Handbook provides the User with the information necessary to Install,
Commission, Operate, Maintain and Test the equipment (as applicable). It is essential that
any Operator(s) reads and understands the content of this Technical Handbook and
follows the instructions contained within.
Every care has been taken to ensure the accuracy of the contents at the date of publication.
If the use of this equipment introduces new technology to your Operators, product training is
available from COMECA to assist you in complying with relevant Health and Safety
Regulations.
Should you require further guidance or information regarding this equipment, or information
on our After Sales Services available, please contact our Customer Services Department at
the address below who will be pleased to assist:
Web: www.comeca-group.com
Our policy is one of continuous product development. We reserve the right to supply
equipment that may vary from that described.
The information contained within this Technical Handbook may not be reproduced or passed
on to third parties, either wholly or in part, without the express prior written consent of
COMECA.
-2-
Gemstart 5
Web: www.comeca-group.com
-3-
Gemstart 5
Customer Services
COMECA’s Customer Services Department can provide continuous Customer support
throughout the lifetime of your equipment. A comprehensive range of services is available,
including:
COMECA’s specialised Customer Service Engineers are available to provide the services
listed above, either in our workshop, or alternatively, at your site.
To assist us in providing an efficient and timely service, before contacting COMECA to
discuss existing equipment, please help us by having the following information available:
The original COMECA works order number or
The unit serial number and the unit type and voltage
When you have the information listed above, please contact us at the address below:
Web: www.comeca-group.com
-4-
Gemstart 5
Table of Revisions
-5-
Gemstart 5
MECHANICAL DANGER:
precautions to be taken to
avoid injury to personnel.
-6-
Gemstart 5
Table of Contents
1 ABOUT THIS MANUAL ............................................................................................................................ 9
2 INTRODUCTION ..................................................................................................................................... 10
2.1 DEFINITIONS .......................................................................................................................................... 10
3 GEMPRO INSTALLATION .................................................................................................................... 12
3.1 INSTALLATION POLICY .......................................................................................................................... 12
3.2 MINIMUM SYSTEM REQUIREMENTS ....................................................................................................... 12
3.3 GEMPRO INSTALLATION ..................................................................................................................... 12
3.4 UNINSTALLING GEMPRO ..................................................................................................................... 16
3.5 INSTALLING THE SECURITY KEY DRIVER (OPTIONAL) .......................................................................... 16
4 USING GEMPRO ...................................................................................................................................... 17
4.1 START MENU OPTIONS .......................................................................................................................... 17
4.2 STARTING GEMPRO ............................................................................................................................. 18
4.3 CONNECTING TO GEMSTART ................................................................................................................. 18
4.4 GEMPRO MAIN SCREEN ...................................................................................................................... 21
4.5 LANGUAGE OPTIONS ............................................................................................................................. 22
4.6 SECURITY OPTIONS ............................................................................................................................... 23
5 MONITORING GEMSTART DATA ...................................................................................................... 24
5.1 CURRENTS ............................................................................................................................................. 25
5.2 VOLTAGE AND POWER........................................................................................................................... 26
5.3 TIMER AND COUNTERS .......................................................................................................................... 27
5.4 TEMPERATURE SENSORS ....................................................................................................................... 28
5.5 FAULTS AND HISTORY ........................................................................................................................... 29
5.6 SERIAL LINK .......................................................................................................................................... 34
5.7 MAINTENANCE ...................................................................................................................................... 37
5.8 COMMISSIONING .................................................................................................................................... 38
6 CONTROLLING GEMSTART ............................................................................................................... 40
6.1 LEVELS OF CONTROL............................................................................................................................. 40
7 CONFIGURING GEMSTART ................................................................................................................ 43
7.1 PROJECT DATABASE .............................................................................................................................. 43
7.2 OFFLINE CONFIGURATION ..................................................................................................................... 44
7.3 ONLINE EDIT ......................................................................................................................................... 44
7.4 LEVELS OF CONTROL............................................................................................................................. 44
7.5 CONFIGURATION WINDOW (ONLINE AND OFFLINE) .............................................................................. 45
7.6 CONFIGURATION FORMS ....................................................................................................................... 51
8 GEMSTART WIZARDS........................................................................................................................... 68
-7-
Gemstart 5
-8-
Gemstart 5
This reference manual contains information about GEMPRO, the PC based monitoring,
control and configuration package.
Readership:
This publication is for the GEMPRO user and expert engineers. It explains the main features
of the GEMPRO software, including how to take control of your Gemstart. It also explains the
features of the Configuration Editor, including how the database structure works, and how it
is used to enter Gemstart’s settings.
Related publications:
Volume 2 is for use by expert engineers who will be setting up Gemstart systems.
-9-
Gemstart 5
2 Introduction
2.1 Definitions
Gemstart 5 is provided with COMECA’s bespoke Monitoring, Control and Configuration
software program “GEMPRO” which is supplied to the User under freeware license. It runs
on most standard PC’s with a Windows VISTA or 7, 8, 10 (by disabling the windows
XP SP2 compatibility mode).
Note: If you have already installed GemPRO version 4.8.4.0 or earlier on your computer,
using GemPRO 4.9.0.0 version or later, make sure to disable the compatibility mode XP SP2
to get an optimum operation.
You can connect the PC to the front panel of a Gemstart using a standard PC serial port and
a straight through male to female 9 way cable with D type connectors. GEMPRO allows you
to do the following on the connected Gemstart:
Monitoring
View system measurements such as currents, volts, & power
Check the status of overload timers, input counters and starts in previous hour
View a full list of the active faults
View historical data recorded in the Faults log
View maintenance data
View commissioning data
- 10 -
Gemstart 5
This reference manual gives specific details about the operation of GEMPRO. This can be
split into the following main areas:
GEMPRO Installation
Setting Up GEMPRO
Connecting to Gemstart
Monitoring Gemstart Data
Controlling Gemstart (Start / Stop / Reset)
Configuring Gemstart
The configuration editor is a major part of GEMPRO. The GEMPRO Configuration Editor can
be “called” as an ActiveX component from other applications such as Gemview.
- 11 -
Gemstart 5
3 GEMPRO Installation
3.1 Installation Policy
GEMPRO is the property of COMECA and is freeware.
GEMPRO is provided as a tool for configuring Gemstart 5 and you are licensed to install
GEMPRO on as many PC’s as you wish.
If you are concerned about the security issues that multiple GEMPRO installations introduce
then you can use GEMPRO with a Security Key. The Security Key can only be purchased
from COMECA and prevents control and configuration changes from a GEMPRO package
that is not Key enabled.
Note: Profibus communication using Siemens CP card through GemPRO is available
just for GemPRO 4.8.4.0 or earlier with Windows XP or 2000.
To begin installation download install file from the website www.comeca-group.com and run
GemproEN_X_X_X_X.exe or GemproFR_X_X_X_X.exe (_X_X_X_X is the version number).
- 12 -
Gemstart 5
Press Next>.
- 13 -
Gemstart 5
You must decide how many users of this PC should have GEMPRO added to their start
menu.
Press Next>.
This is the default installation directory. If you want to install in a different directory then
select Change.
- 14 -
Gemstart 5
- 15 -
Gemstart 5
Administrator Rights are required to install the driver for the Security Key. Once you have
installed GEMPRO you can install the Security Key Driver from the Start Menu.
Start > Programs > GEMPRO > Install Sentinel SuperPro Driver (Security Key)
This is a fully automatic installation which should end with a success message.
- 16 -
Gemstart 5
4 Using GEMPRO
4.1 Start Menu Options
Installing GEMPRO creates a new group of shortcuts in the Start button menus and a single
shortcut to GEMPRO on the Desktop.
Click Start / Programs / GEMPRO and you see the shortcuts installed for GEMPRO.
GEMPRO This is the main shortcut. Starts the monitor, control and configuration
program.
Install SuperPro This starts the automatic installation of the optional Security Key driver.
Driver (Security Installing this driver allows the Security Key to be used. Note: Installing
Key) the driver does not force you to use a Key but without the driver you
cannot use a Key.
- 17 -
Gemstart 5
Profibus Link
Access any
Gemstart on the link
via the Profibus link (Gemview)
- 18 -
Gemstart 5
…and selecting the relevant COM port, and ticking “Lock Channel”. This prevents GEMPRO
scanning the other COM ports when a connection is not found.
- 19 -
Gemstart 5
Gemstart can operate with one Gemview and one GEMPRO’s connected using RS232.
Each package can monitor and reset faults from monitor mode without taking control.
The first application to request control will lock out all the other applications. When an
application is locked out it cannot send any reset commands but it can still monitor the data.
Gemstart can indicate which application is in control when you select “status” for the LCD.
Options are:
* GEMPRO for GEMPRO control via RS232
* Profibus Gemview for Gemview control via Profibus
- 20 -
Gemstart 5
Gemstart 5
Configuration
Gemstart 5
Data
Windows
reminder
- 21 - Window Footer
Gemstart 5
There is one button on the Button Bar that is not present on the main screen. The “Control”
button is a copy of the Control button in the Control Gemstart window.
The “Control” button is a Padlock when GEMPRO is not controlling Gemstart 5. Pressing the
Padlock button requests control of Gemstart 5. If Gemstart 5 grants control to GEMPRO
then the Padlock changes to a Key. Pressing the Control button again releases GEMPRO
control and the button changes back to a Padlock. See Levels of Control explanation later in
the manual.
The list of available language is shown here. Changes to this item are implemented
immediately and are remember for the next session of GEMPRO.
- 22 -
Gemstart 5
Physically the key plugs into the USB port on the PC.
Each Gemstart 5 individually stores the security setting (not the PC). The Level of Security is
one of the Gemstart configuration settings. This allows some parts of an installation to be
protected with a Key whilst other parts allow general access.
To make use of the additional security offered by the Key you must set the “Key Required”
configuration item in the GEMPRO window to “Required”.
The “Key Required” option can be changed in Offline Mode without a Key present but the
configuration can only be downloaded to Gemstart if a Key is present when the down load
occurs. This prevents clearing or accidental setting of this requirement when there is no Key
available.
Key Required can only be changed in Online Edit mode when a Key is present.
Once the configuration has be set to “Key Required” then control and configuration changes
can only be performed while the Key is present on the USB link.
- 23 -
Gemstart 5
The monitoring windows can be opened from the main GEMPRO screen or from the button
bar.
The monitoring windows can all be opened at the same time and positioned around the
screen for best viewing. The placement of these windows is remembered and the next time
the window is opened it appears in the same place.
- 24 -
Gemstart 5
5.1 Currents
Individual Phase measurements are based on the CT readings. On Gemstart 5.3 where
there are only 2 CT’s fitted the Phase 2 current is a residual sum of CT’s 1 and 3. On
Gemstart 5.1, no measurement is made.
The Highest Phase current is the highest of the 3 individual phase readings. This is the
current that is used for most protection items.
The Average is the average of the 3 phase currents.
Each of the above current measurements are displayed as:
%FLC. A percentage of the configured Full Load Current
%ALC. A percentage of the configured Actual Load Current.
Amps. The current in Amps adjusted for external CT’s if configured.
Imbalance current is the difference between the highest and lowest phase current and is
displayed as a percentage of the configured fault limit. I.e. 100% Set Point is the fault limit.
Thermal Content is a model of the heating effects in the motor and is displayed as a
percentage of the Overload limit. I.e. 100% Set Point is the fault limit.
Earth Current is calculated from the external CBCT and is displayed in Amps and as a
percent of the Earth Current limit. I.e. 100% Set Point is the fault limit.
- 25 -
Gemstart 5
Monitored Voltage is the voltage measured by Gemstart on the Motor Voltage input. This
voltage is then converted to the Motor Voltage based on the configured voltages for the
motor and for Gemstart.
Motor Power is calculated from the motor voltage and the phase currents. The percentage
reading is a percentage of the configured motor power rating.
Power Factor is derived from the ratio of the motor power to apparent power. Power flow is
always assumed to be positive and the power factor is always displayed as positive.
The kWh Meter is a cumulative total based on the Motor Power. The kWh meter can be
reset from the Maintenance Window.
- 26 -
Gemstart 5
5.3.1 Timers
Each Timer is greyed out unless it is active.
The Overload Trip timer is an estimate of how much time is left before the Thermal Content
reaches 100% and an overload trip occurs.
The Restart Inhibit timer is an estimate of how much time is left before there is enough spare
Thermal Content to allow another start. This is based on how much Thermal Content was
used in the last start.
The Reset Inhibit timer is the time left before this configured time delay has elapsed.
The Starts / Hour timer is the time left before the Starts/Hour protection will allow another
start.
The Auto Restart timer is a count down to an automatic close by the Auto Restart feature.
5.3.2 Counters
Inputs counters 1 to 3 are 3 counters that can be configured to monitor the activity of any
digital input. They can count up to 65,565,999 each. The counter can be reset from this
window if GEMPRO has a sufficient level of control. See Levels of Control explanation later
in the manual.
Starts in the Last Hour is a count of the starts in the last hour. Gemstart can count up to 255
in any 15 minute period.
- 27 -
Gemstart 5
This shows the status of the PTC input on Gemstart 5.4. Options are:
Not Available – Gemstart is not 5.4
Cold – the PTC is low resistance
Hot – the PTC is high resistance
Short Circuit – the resistance is too low
The status of the RTD unit is shown. This indicates if the RTD Unit is connected. In case of
the loss of this connection, a protection can be activated (in Fuses and Contactor,
configuration editor).
The 6 RTD’s are grouped into two groups of 3. The group temperature shows the highest of
the 3 CT readings in the group.
The temperature of each RTD is shown and, if the protection is enabled, the fault level is
shown.
The following special conditions are indicated for the RTD inputs.
Not Available – the RTD unit is not connected or the group temperature cannot
be calculated.
Not Connected – the RTD+ input is not connected to RTD common
Short Circuit – the RTD resistance is too low
Open Circuit – the RTD resistance is too high
- 28 -
Gemstart 5
This view shows all the faults that are present on Gemstart 5.
* Latched Trips (LTrips) are faults that stop the motor and prevent Gemstart from starting it
again. Pressing Reset Trips clears these faults. If the fault is still present the fault returns.
* Self Clearing Trips (Trips) are faults that are continuously monitored. If the fault goes away
the fault report is removed (i.e. Self Clearing). A Trip stops the motor and prevents it from
starting again as long as the fault is still present. Reset Trips will not clear these faults.
* Latched Alarms (Alarms) are warning messages that must be reset. Alarms do not affect
control of the motor. Pressing Reset Trips clears these faults. If the fault is still present the
fault report returns.
* Self Clearing Warnings (Warnings) are faults that are continuously monitored. If the fault
goes away the fault report is removed (i.e. Self Clearing). A Warning does not affect control
of the motor. Reset Trips has no effect on Warnings.
Trip Counters
The 4 trip counters count the number of faults that have occurred in that group. The list of
faults in Volume 1 defines which faults are included in each group. These counters can be
reset from the Maintenance Window.
- 29 -
Gemstart 5
The Trip History shows the last 16 Trips (Latched or Self Clearing) that stopped the motor. A
trip that occurs while the motor is stopped is not stored in this list. The faults are listed with
the most recent Trip at the top of the list. Each fault has the following information:
Severity. This can only be Trip or Latched Trip
Fault. This is the protection type that has created the Trip
Time. This is the time that the trip occurred. There are 3 levels of accuracy for
this time and this is covered below
Highest Phase Current. This is the highest phase current flowing when the fault
occurred
Gemstart 5 Time
Gemstart 5 maintains the time internally while it is powered. After a power off and on, the
time continues to be maintained with no adjustment for the time that Gemstart was powered
down.
GEMPRO automatically updates the time in Gemstart if the time in Gemstart has not been
updated since Gemstart was powered on.
The time in Gemstart is displayed by GEMPRO and can be updated with the PC time by
pressing the Update Gemstart Time. Gemstart 5 allow time synchronisation from the
Modbus or Profibus communication links.
The levels of time accuracy are:
Synchronised. The time has been updated from Modbus or Profibus in the last
100s. A Synchronised time is within +/- 10ms of the time source
Estimate. Gemstart time has been updated since the last power on but a
Synchronised Time message has not been received in the last 100s
Invalid. The time of the fault is not correct because it happened between a power
up and down of Gemstart when no time messages were received
- 30 -
Gemstart 5
The Event History shows the events that have occurred to change the status of the motor.
The following events are recorded:
Events Comments
Start A A start command has been actioned.
A start command has been actioned. The B contactor is used for Reverse,
Start B
High Speed or to close a motor operated valve.
Stop A stop command has been actioned.
Gemstart When Gemstart powers up it recovers the power down time from the
Power Up PAMM and generates a power down and power up event. The power
Gemstart down event is always stored as an estimated time. The power up time will
Power Down be updated later when a time message is received.
Time This event is generated if time was not synchronised before a time sync
Synchronised message was received.
If a time sync message is not received within 100s of the previous time
Time Sync Lost
sync message then the accuracy in Gemstart may be outside +/- 10ms.
Start A If the slow down delay is configured and active when a Start command is
Delayed received the Start command is delayed. The Start Delayed event is
generated when the Start command is received. Once the slow down
Start B delay has elapsed a new Start command is automatically generated by
Delayed Gemstart and is shown in the event history with a Delayed Action source.
If the current is over the contactor protection threshold and a stop
command is issued or a trip occurs then the stop is delayed until the
Stop Delayed current drops or the fuse has had time to blow. At the end of the delay
Gemstart automatically generates a new stop command which is shown in
the event history with a Delayed Action source.
- 31 -
Gemstart 5
Events Comments
Protection A protection item has caused the motor to trip. This source only produces
stops.
Serial Link The control system has started or stopped the motor via the serial link.
GEMPRO GEMPRO has started or stopped the motor.
Local Manual Gemstart is set up for Local/Remote manual controls and the local controls
(Stop A / Start A) have started or stopped the motor.
Remote Gemstart is set up for Local/Remote manual controls and the remote
Manual controls (Stop B / Start B) have started or stopped the motor.
Emergency An emergency start input has been activated.
AutoRestart This source generates a stop after the supply ride through time and
generates a start after the delayed start time.
Delayed When a start or stop is delayed due to Slow Down, Auto Acceleration or
Action Contactor Protection then the Delayed Action source records when the
actual stop or start is actioned.
Manual Test A manual start or stop command was actioned while the chassis was in the
test position.
Manual A manual start or stop command was actioned. i.e. Not configured for
Local/Remote.
- 32 -
Gemstart 5
We can look at the event history in the example above in more detail. We shall start with
event 16 which is the oldest event. For this example we need to know:
Gemstart is configured as a Forward/Reverse motor
Slow Down time is 4s
Auto Restart delay is 5s.
Event Comments
16
A supply dip of 316ms occurred. The motor was not affected. (Already stopped)
15
14 The motor was put in reverse from manual mode.
13 The motor was stopped from manual mode.
A forward command was sent from manual mode but it is being delayed to allow
12
the motor to slow down from reverse.
11 The delayed start command is actioned 4s after the motor was stopped.
A protection trip has stopped the motor. The trip history will indicate the source of
10
the trip.
9 A start command was sent from GEMPRO.
8
A supply dip of 98ms did not affect the motor.
7
6
A supply dip of 497ms caused the motor to be stopped after the supply dip ride
5
through time of 200ms.
4
3 Auto Restart started the motor 5s after the supply had recovered.
2 A protection trip occurred.
1 The serial link started the motor in reverse.
- 33 -
Gemstart 5
The Rx Data frame contains the data received from the Profibus Master.
Profile Type is the data format definition requested by the Profibus Master. Since
Gemstart5 firmware H04 and Gempro 4.6.3.0, the profile type is given by a
hexadecimal code. See Profibus GSD file for signification.
The remaining values are the numerical values of the data received from the Profibus
Master.
The Profibus Status Flags give an indication of the low level status of the Profibus driver
within Gemstart 5. The following flags may help debugging.
- 34 -
Gemstart 5
The Parameters & Config frame shows the parameters and Profibus configuration received
from the Profibus Master. Refer to Profibus Specifications for a definition of these bits. Nota:
since Gempro 4.6.3.0, Config bytes are 4 instead of 3.
The Profibus Messages frame gives an indication of the type of messages being processed
and the frequency of these messages. The left column number is the number of data read
messages by the Profibus Master. The right column is the number of write messages sent by
the Profibus Master.
Cyclic data is the data that is regularly exchanged with the Profibus Master.
Acyclic data is the data that is additionally requested by the Profibus Master. This
would normally only occur if the Profibus Master is gathering additional data for
Gemview.
GEMPRO messages count the number of reads and writes by GEMPRO via the
Profibus Connection.
5.6.3 Modbus
- 35 -
Gemstart 5
- 36 -
Gemstart 5
5.7 Maintenance
- 37 -
Gemstart 5
5.8 Commissioning
The Inputs frame shows the state of all the physical inputs. Inputs 1 to 4 are local inputs fed
from a 24V supply from Gemstart. The interlock input and inputs 5 to 8 are multi voltage
inputs.
The Additional Inputs frame shows the state of the inputs on the additional Input module.
For all the inputs “0” indicates there are no volts on the input; “1” indicates that the
configured input voltage is present. N/O, N/C configuration does not affect the input display.
The Outputs frame shows the physical state of the 4 Gemstart outputs. “0” indicates output
relay open, “1” indicates output relay closed.
Gemstart Firmware. This frame shows version details about the firmware running in
Gemstart.
Update Gemstart Firmware. This button is the access point for updating the firmware in
Gemstart. The button is greyed unless GEMPRO is in Control. See the Special Operation
section before using this button.
User Language & Character set opens a form which allows you to read / write the
language definitions and character set definitions to / from Gemstart.
Show Diagnostics. Tick this option to show 32 words of debug information. This information
is for debugging and development use.
- 38 -
Gemstart 5
User Language
Gemstart 5 has the facility to display a user defined language. A language file can be read
from, or written into, Gemstart by GEMPRO via the front RS232 port. When reading the
language file from Gemstart the language read is the configured language. Language files
can be read from or written to Gemstart during normal running. I.e. motor protection and
System Control is not affected.
See section 9.5, to find out about reading, editing and writing language files.
Character Set
Gemstart 5 has the facility to use a user defined character set. A character set definition file
can be read from, or written into, Gemstart by GEMPRO via the front RS232 port. When
reading the character set file from Gemstart the character set read is the configured
character set. Character set files can be read from or written to Gemstart during normal
running. I.e. motor protection and System Control is not affected.
See section 9.6,Updating the Gemstart User Defined Character Set, to find out about
reading, editing and writing language files.
- 39 -
Gemstart 5
6 Controlling Gemstart
6.1 Levels of Control
GEMPRO has 3 levels of control. “In Control”, “Requesting Control” and “Monitoring”.
6.1.1 Monitoring
Monitoring is the startup state of GEMPRO.
If Gemstart configuration requires a Security Key and a Security Key is not present then the
Monitoring Button is greyed.
In this state:
The motor cannot be started or stopped
The motor data can be monitored and, depending on the Gemstart configuration,
statistical data can be reset
Configuration can be monitored but not changed
If Gemstart is under Priority or Emergency control then Gemstart cannot grant control to
GEMPRO. GEMPRO stays in the Requesting Control mode.
In this state:
The motor cannot be started or stopped
The motor data can be monitored and, depending on the Gemstart configuration,
statistical data can be reset
Configuration can be edited
- 40 -
Gemstart 5
In this state:
The motor can be started or stopped.
The motor data can be monitored and statistical data can be reset.
Configuration can be edited.
6.1.4 Security Key
Each Gemstart contains a configuration item which defines if a Security Key must be present
to control that particular Gemstart.
If the Key is required but is not present then GEMPRO disables the ability to request control.
Once Gemstart is in Control Mode the Start and Stop Buttons allow the user to start and stop
the motor. The status bar indicates the status of the motor. This text is dependent on the
contactor type. In the above example the motor is stopped.
Start A is used for Start, Close, Forward, Star or Low Speed contactors.
Start B is used for Reverse or High Speed contactors.
Stop is used for Stop or Open.
- 41 -
Gemstart 5
Replace PAMM is an advance operation and is covered in the Special Operation section of
this manual.
Test LCD & LED’s can be used to test the LCD and LED’s displays. This forces the LCD to
show the Company and product name, software reference and version and copyright details.
At the same time the 4 programmable LED’s go green then red. The LCD and LED’s then go
back to normal operation. This test does not affect control or protection and can be used at
any time.
- 42 -
Gemstart 5
7 Configuring Gemstart
GEMPRO can be connected to Gemstart to edit the configuration “Online”. The configuration
in Gemstart is backed up in the Project Database which contains the details of every link and
address combination. I.e. link 0 address 0 to link 15 address 254.
If GEMPRO is not connected to Gemstarts then the Project Database can be edited
“Offline”.
Gemview 5 (an Engineering Workstation available separately) can also open the GEMPRO
Configuration Editor. This allows the Gemview user to edit Gemstart configuration using the
same user interface.
GEMPRO
02 02 02 02 02
- 43 -
add add add add add
or
If you intend to change configuration settings, you must request control prior to opening the
editor.
- 44 -
Gemstart 5
When the Gemstart link and address are not set there is no corresponding entry in the
Project Database. It is recommended that you set the address, even if you are not using
the serial link. Once the address is set the Project Database maintains a backup of the
configuration.
- 45 -
Gemstart 5
if the Gemstart configuration is right but must not change the database configuration
(e.g. the gemstart configuration has been changed for testing), it is possible to create
a new database (Project File) to keep track of this testing configuration without
modifying the “official” configuration : click on “New”
if an other database must be used for this Gemstart (see File name on the Footer), it
is possible at this stage to directly open an existing database : click on “Open”. The
new configuration will be compared once again
- 46 -
Gemstart 5
When editing the configuration offline you can select and change which Gemstart
configuration you are editing. You do this by selecting the link number then the Gemstart
Address. To help you the link names and Gemstart Motor Tag are also displayed.
Online Editing automatically uses the link and address of the connected Gemstart.
- 47 -
Gemstart 5
This information allows a quick validation of the configuration data. An unchanged CRC
(Cyclic Redundancy Check) method gives a very good indication that the configuration has
not changed.
The Overall CRC is a CRC of the all the Gemstart configuration. By recording the Overall
CRC’s for critical motors you can quickly audit the configuration settings by checking that
this CRC has not changed.
The factory settings CRC is based on Page 2 of the configuration printout (See Appendix A).
This is typically the same for a group of Gemstarts with the same basic configuration.
Commissioning settings is based on Page 3 of the configuration printout (See Appendix A).
Typically this covers the protection settings and is likely to be different for each motor and
application.
- 48 -
Gemstart 5
Copy… opens the “Copy From... To…” window and allows the configuration from one
address to be copied to several other addresses.
The Copy From Project Database can be changed with the Change Source Database
button.
The Copy To Project Database is fixed as the current Project Database.
Project Name is the name in each of the Project Databases.
A single Gemstart in the Copy From database can be selected and copied to multiple
addresses on a single link in the “Copy To” database. To copy to multiple Gemstarts you can
separate individual addresses with a comma or you can copy to a range of units by using a
dash. e.g. 1, 4, 6-9 copies to units 1, 4, 6, 7, 8 and 9.
The amount of configuration copied can be limited as follows:
All Configuration copies all configuration options to the Copy To addresses. The
overall CRC will be the same on the Copy From and Copy To units
Partial Configuration. The configuration copied is limited and defined by the
following selections. Ticking all the options is NOT the same as selecting “All
Configuration” as the Gemstart type, Ride Through, Auto Restart, Comms Control
Group, language and character set are not copied
Schematic Name. The (Unit Summary) Schematic name is copied
Page 2 Configuration. This copies the configuration included in the Page 2 CRC
(see Appendix A). This can be limited by disabling the User Text or Motor Tag texts.
Other options are not submitted to CRC.
Page 3 Configuration. This copies the configuration included in the Page 3 CRC
(see Appendix A)
- 49 -
Gemstart 5
7.5.9 Export
Export exports the configuration detail for the selected Gemstart to an
Microsoft Excel spreadsheet file.
A template Excel spreadsheet is installed with GEMPRO in the Export
directory. As long as you do not inset or delete any rows or columns you can edit this
template to add your own company logo if you wish.
This area of the page contains 16 buttons that open up windows with specific areas of
configuration data.
The layout reproduces the separate areas of configuration for different parts of the circuit
and flows across the screen from the 3 phase supply through the fuses and contactor, phase
CT’s, earth fault CT to the motor and finally to the application “load”.
The motor protection is above and below the motor drawing and the application protection is
above and below the application drawing.
The motor and digital inputs are configured separately and a third button configures the 9
multi voltage inputs.
Communications configuration is connected by the two wire network and the PAMM by 3
wires.
Configuration of the display data is next to the LCD module drawing and GEMPRO
configuration next to the laptop.
- 50 -
Gemstart 5
At the bottom of every configuration screen is a status bar with details about the connected
Gemstart and the connection to that Gemstart. Each section has the following information:
The connection route (Standalone, Front Port or Gemview)
The editing status (Monitoring, Editing Enabled, or Locked)
The status the security key (No Key, Key Present)
The Gemstart link number and address
The Gemstart Motor Tag
If the configuration data for an item is invalid then the selection box is shown in red. This can
occur if the database has been corrupted or a new option has been selected with a newer
version of GEMPRO than the one you are using.
Non Default Setting (Yellow Background)
A configuration item that is not normally changed from its default is shown in yellow if the
default value is not selected. This is intended to highlight unusual configuration settings.
- 51 -
Gemstart 5
A configuration item that cannot be changed is shown with grey text. This can occur when a
configuration item is not relevant or you do not have permission to change the configuration.
In this example the speed 2 settings are now relevant and are greyed out.
Close Button
Each window has a close button which closes the form and allows access to the GEMPRO
windows or allows another Editor form to be opened.
CT, FLC and ALC dependencies
CT, FLC and ALC configuration are all defined in Amps. This allows incompatible options to
be set. E.g. CT = 1A, FLC=100A. Clearly a 1A CT would not be able to read 100A.
Some range checking is performed by Gemstart and incompatible configuration settings
generate Configuration Warnings. If you are editing online GEMPRO highlights this error by
displaying a warning message. The GEMPRO error message can be cancelled and the fault
remedied. Gemstart continues to show the error report until it is fixed.
The rules for the CT, FLC and ALC settings are:
At 100%FLC the current on the internal Gemstart CT’s must be between 0.5A and
30A
ALC must be less than or equal to FLC.
Speed 1 and Speed 2 Configuration
Some protection items can have different protection for each speed of a two speed motor.
These settings are shown regardless of the contactor type configured. If the contactor type is
not a two speed type then the speed 2 options are greyed.
Speed 1 settings are used for low speed and all non “2 speed” contactor types.
- 52 -
Gemstart 5
Protection
…
For consistency the common protection features use the same format. Each item has the
following meaning:
Active. Tick to enable the protection.
Disabled in Startup. Tick to prevent the protection operating during the startup phase.
PreWarn at. Disable pre warning or select the pre warning percentage. The pre warning
percentage is a percentage of the fault level and does not take the protection time delay
into account. Selecting 100% produces a warning once the protection time delay has
started.
Severity. Select the action to take when the protection is triggered.
Warn. Self clearing message. Motor not stopped.
Alarm. Latched message. Motor not stopped.
Trip. Self clearing message. Motor is stopped. Motor can be started once fault clears.
LTrip. Latched message. Motor is stopped. Reset required before starting again.
Trip then Alarm. Latched message. Motor is stopped. Motor can be started once fault clears.
For consistency all the input functions use the same format. Each item has the following
meaning:
Source. This is the hardware input that the input function monitors. Two special
cases can be selected:
Disabled. The input function is always off. Changing the sense has no effect.
Active. The input function is always on. Changing the sense has no effect.
Sense. Defines if the input is a normally open or a normally closed input. Defining an
input as normally closed effectively inverts the sense of the input
Severity. Defines the action to be taken when the input becomes active.
- 53 -
Gemstart 5
- 54 -
Gemstart 5
- 55 -
Gemstart 5
- 56 -
Gemstart 5
- 57 -
Gemstart 5
- 58 -
Gemstart 5
- 59 -
Gemstart 5
- 60 -
Gemstart 5
- 61 -
Gemstart 5
- 62 -
Gemstart 5
Define the Voltage Level of each input then consider how much dip time you want to ignore.
The Ride Through Time allows the Gemstart to ignore short dips in supply. Setting the ride
through time to 20ms results in the Gemstart not reporting the loss of signal for 20ms. If the
voltage recovers before this time then no change of state is reported. This ride through time
only affects loss of voltage; it does not apply to the return of voltage which is always
detected within 3ms.
- 63 -
Gemstart 5
- 64 -
Gemstart 5
- 65 -
Gemstart 5
- 66 -
Gemstart 5
The default LED Function setting is Auto. Gemstart 5.1 has a different set of “Auto” functions
to Gemstart 5.3 and 5.4. When GEMPRO is connected to Gemstart, Gemstart automatically
updates the function configuration “Auto” settings depending on the Gemstart used. For 5.3
and 5.4 the Auto settings are Running, Stopped, Fault and Serial Mode. For 5.1 the Auto
settings are Input 1, Input 2, Input 3 and Input 4.
Because Gemstart can change the Auto Function configuration (for example by changing a
Gemstart 5.1 to a Gemstart 5.3 or 5.4) the CRC for page 2 will also change. If you are using
the Page 2 CRC as a method of configuration validation then you should set the LED
functions explicitly. Auto colour does not necessary have to be set explicitly.
The default colour option is Auto. For some functions the Auto option has 3 colours. In most
cases the Auto option is what you would expect. If not you can override the colours used.
The first colour listed is the Inactive state, the second the active state. E.g. if you pick
Off/Green for the Running LED then the LED is OFF while the motor is stopped and Green
while the motor is running.
- 67 -
Gemstart 5
8 Gemstart Wizards
The wizards are intended to quickly configure Gemstart at each stage of the chassis life.
Namely:
- 68 -
Gemstart 5
When you select the Reset Configuration button the following confirmation form is shown.
Check that you are resetting the unit that you want to reset and then press OK.
Following is a summary of the main configuration settings after they have been reset:
- 69 -
Gemstart 5
- 70 -
Gemstart 5
You can move around all the tabs by using the “Back” or “Next” buttons or by clicking on the
desired tab.
When you “Close” the Chassis Wizard no changes to the Gemstart configuration are made.
Changes are only made when you select “Apply Changes” on the Summary page. Any
settings you select in the Chassis Wizard are remembered until you close GEMPRO. So you
can close the Chassis Wizard and come back to it later if you wish.
Once you reach the Summary page you have completed all the information required by the
Chassis Wizard. A summary of all the relevant data is shown. If you are happy you can
implement all the changes by clicking on “Apply Changes”.
8.2.2 Instructions
The first tab of the Chassis Wizard gives brief instructions on how to complete the Wizard.
Select the correct options on this page. Remember no changes are made to the
configuration until you select “Apply Changes” on the summary page.
- 71 -
Gemstart 5
- 72 -
Gemstart 5
If you have an Earth Fault CT then define the primary rating of the CT here. Gemstart Earth
Fault CT’s must have a secondary rating of 20mA. Two Core balance Current Transformers
(CBCTs) are available from COMECA: 8A:20mA and 16A:20mA.
8.2.8 Supply
Gemstarts 5.3 and 5.4 can read voltage. The motor voltage and the method of connection to
the motor supply are defined here. The Monitored Voltage could be the secondary voltage of
the transformer connected to the motor supply or the single phase voltage of a 3 phase
system. E.g. 240V is the single phase voltage of a 415V, 3 phase system.
- 73 -
Gemstart 5
- 74 -
Gemstart 5
The 3 items above are updated in the Gemstart configuration immediately (if you quit the
Wizard, these changes remain). The following items are only updated once you click the
“Apply Changes” button on the summary page.
Start Current
Start Time
Thermal Overload
To make full use of the Motor Wizard you must have the following motor information. If you
do not have all this information then reasonable default values are suggested by the wizard.
Motor Power Rating
Motor FLC
Motor Acceleration Time
- 75 -
Gemstart 5
After running the Motor Wizard Gemstart will provide accurate motor protection. The first
start of the motor can now be performed.
The Motor Wizard can be used in online or offline editing.
8.3.2 Instructions
The first tab of the Motor Wizard gives brief instructions on how to complete the Wizard.
- 76 -
Gemstart 5
To protect the contactor from breaking currents above its rating you need to enter the rating
of the contactor. For AC4 systems this has to be at least 10 times the motor FLC. For AC3
systems this contactor must be rated to 6 times the FLC. If the current is above the contactor
rating Gemstart will keep the contactor closed long enough for the fuse to blow. Enter the
maximum time that the fuse should take to blow when the current is above the contactor
rating. If the fuse does not blow within this time the Gemstart will attempt to open the
contactor.
Unlike other settings in the Wizards, changes to this Motor Wizard page are updated in
Gemstart immediately (if you quit the Wizard, these changes remain). All other Wizard
changes are not passed to Gemstart until the “Apply Changes” button is selected.
- 77 -
Gemstart 5
- 78 -
Gemstart 5
- 79 -
Gemstart 5
Based on the data entered on the Basic Ratings and Motor Details page a new Overload
Curve is suggested. This page shows you the existing configuration in the top half of the
page. The lower half shows the new suggestion. You can adjust the suggestions if you wish.
The suggestions are updated every time a change is made to the Basic Ratings or Motor
Details page.
The Curve suggestion is the curve that allows the indicated number of starts from cold where
each start is at the inrush current for the acceleration time.
The Hot/Cold Ratio suggestion is set to unknown if the stall withstand time from hot is 0. For
non zero times the ratio is calculated as the Withstand Time From Hot / Withstand time From
- 80 -
Gemstart 5
More information about the Overload Protection can be found in Volume 2, section 3.5.15,
Thermal Protection / Overload.
8.3.7 Summary
Once you have finished entering data to the Wizard you can review the data on the summary
page. If there are any errors they can be corrected by returning to the relevant tab. Once you
are happy that the data entered is correct you can tick the relevant Accept boxes. Clicking
the “Apply Change” button will modify the configuration in Gemstart for the protection item
suggestions that have been accepted. You can now close the wizard.
- 81 -
Gemstart 5
Note: The FLC must be correctly set and a successful motor start performed before
using this Wizard.
This Wizard is only available if Gemstart is connected and a successful start has been
completed since Gemstart was last powered up. For two speed motors Gemstart keeps
separate records for each of the speeds. This allows the Protection Wizard to analyse the
data for low and high speed at the same time.
- 82 -
Gemstart 5
On each of the Protection Pages the existing protection settings are shown greyed in the top
half of the page. The bottom half of each page shows the suggested settings. The
suggestions can be adjusted as required. If you click “refresh the motor data” then the
suggestions are updated and any adjustments are lost.
When you “Close” the Motor Wizard no changes to the configuration are made. Changes are
only made when you select “Apply Changes” on the Summary page.
On the Summary page you will find a summary of the protection suggestions. If you do not
want to update one of the protection items you can clear the Accept box for that protection
item. You can implement the accepted changes by clicking on “Apply Changes”.
- 83 -
Gemstart 5
- 84 -
Gemstart 5
The ALC suggestion is always accepted and cannot be disabled because the Under Current
and Instant ALC protection suggestions are based on the new ALC suggestion. However
you can adjust the suggested ALC setting if required.
It is possible to turn off the protection by clearing the Active flag and clicking Apply Changes.
You can return to any of the protection suggestions by clicking the relevant tab or clicking
the “Review Settings” button next to the relevant protection item.
Once the changes have been applied the Wizard automatically clears the Accept flags.
- 85 -
Gemstart 5
- 86 -
Gemstart 5
The start current suggestion is the Wizard Margin above the Start Peak Current. E.g. 20% of
600% start peak = 120%. 600% + 120% = 720%.
The start time suggestion is the Wizard Margin above the startup time. E.g. 20% of 2s is 0.4s
2s + 0.4s = 2.4s. The next option above this is 3s.
- 87 -
Gemstart 5
The Overload Curve suggestion aims to allow the desired number of starts from cold to take
the thermal content to 100%. The wizard margin is taken into account.
E.g. If the last start used 10% and the margin is 20% then 5 starts from cold would use,
(10% + 20% of 10%) * 5 = 60%
Gemstart then adjusts the curve to speed up the protection. The ratio between curves is
1.259. So changing from curve 15 to curve 13 would alter the total thermal content from 60%
to 95% (i.e. 0.60 * 1.259 * 1.259).
The Hot Cold Ratio is calculated by dividing the number of starts from Hot by the starts from
cold and converting to a percentage. E.g. 1/5 * 100% = 20%
- 88 -
Gemstart 5
The ALC suggestion is half way between the minimum and maximum current after starting.
The undercurrent suggestion is the margin below the minimum current. E.g. Minimum
current was 7.0A which is 7/7.5 * 100%ALC = 93% ALC. Minus 20% for the margin =
73%ALC. The first setting below 73% is 70%.
The instant ALC is the margin above the maximum current. E.g. Maximum was 8.0A = 8/7.5
* 100%ALC = 107%ALC. Add 20% for the margin = 127% The first setting above is 130%.
- 89 -
Gemstart 5
The Power Factor High suggestion is the max power factor + the margin. E.g. 0.70 + 0.20 =
0.90
The Power Factor Low suggestion is the min power factor - the margin. E.g. 0.50 - 0.20 =
0.30
- 90 -
Gemstart 5
The Over Power suggestion is based on the maximum power plus the margin percent. E.g.
80% + 20% = 100%.
The under Power suggestion is based on the minimum power minus the margin percent.
E.g. 70% - 20% = 50%.
- 91 -
Gemstart 5
- 92 -
Gemstart 5
9 Special Operations
9.1 Updating Gemstart Firmware
From time to time new releases of Gemstart firmware are issued which contain new features
or fault fixes. If your system requires the new feature or is suffering from a fault that has
been fixed then you can update the firmware in Gemstart from GEMPRO.
This operation can only be performed by taking Gemstart out of service for about 1 minute.
As every new firmware version is upward compatible it is now impossible
to update a Gemstart5 with an older version than the one already present
in it. In case it is necessary, please contact us.
Obtain the necessary permission to work on Gemstart. You need to stop the motor. You will
not need to power cycle Gemstart or remove it from the service position.
Start GEMPRO and connect to Gemstart. Open the Control Gemstart window.
Click the monitoring button to take control. Stop the motor. Close the window.
Stay in control and open the Commissioning Window.
At the bottom of the window are the details about the firmware already loaded in Gemstart.
In this example the firmware is 5450 H23. The CRC is provided for verification.
Click Update Gemstart Firmware and a warning message is shown.
- 93 -
Gemstart 5
Select the new version to be downloaded. The file name should be in the format
XXXXYYY_crc_ZZZZ.bin. XXXX specifies the firmware reference. For Gemstart 5 this
should be 5450. YYY specifies the firmware issue. This is a letter followed by a 2 digit
number. A major release increments the letter and resets the number to 01. Minor releases
increment the number. Take a note of the file name to allow the download to be verified.
Click Open.
If the file name differs from the structure given above, an error message will show up.
If the selected file is an older version than the one in Gemstart5, an warning message
concerning upward compatibility will be displayed. The update will be forbidden.
Check the file name in the header is correct. This is the last chance to abort programming.
To abort from here click the X at the top right.
- 94 -
Gemstart 5
Programming progress is shown on the status bar. If power to Gemstart or the PC was lost
during the programming stage then go to the next section “recovering a partially updated
Gemstart”.
WARNING : it is important to wait for the CRC to update before closing the
“Commissioning” window. Otherwise, GEMPRO may not refresh correctly its
data.
Once programming has completed the Finished Programming box appears. Click OK.
After a few seconds the version details and CRC should be updated in the Commissioning
window. Verify these against the original file name.
- 95 -
Gemstart 5
Select the com port used to connect to Gemstart and click Load Binary File.
Navigate to the new firmware file, select the file and click Open.
Flash loader now displays the file name in the header and has enabled the other two
buttons. Click Enter Flash Mode.
- 96 -
Gemstart 5
- 97 -
Gemstart 5
As standard GEMPRO comes with an option for English and French. The texts for these
languages are defined in the files G5English.ced and G5French.ced. These files can be
found in the GEMPRO installation directory.
You can modify the English and French texts by modifying these files but any changes are
overwritten when you install a new version of GEMPRO.
The default language option uses English text that is built into GEMPRO and cannot be
modified.
To create a new language file take a copy of either the G5English or G5French files and
rename it in the form G5xxxxxx.ced. e.g. G5AltEng.ced. The next time GEMPRO is started it
detects the new file and gives the new set of options:
To customise the file you must edit the new file in a simple text editor such as Notepad.
This file is made up of several sections and each section has a set of keywords. The section
names are in square brackets. The keywords are before the equals sign ‘=’ on separate
lines. Do not change the section names or the keywords. The text after the equals sign ‘=’ is
the text to be translated.
The first section in the file is called Language and the first keyword is ThisLanguage.
ThisLanguage defines the name of the language shown in the language options box. If you
change this to “New Language” and save…
- 98 -
Gemstart 5
The next section in the file is called [Common]. This section contains keywords that are used
throughout GEMPRO. The text after the equals sign ‘=’ should be translated.
Some strings contain “%c” or “%d”. e.g. “Operations of %c (Hundreds)” This marks where a
character or number is placed. Your translation should contain the same place markers.
Some texts are split across two lines. The point where the text is spit is marked with “\n”.
E.g. Fuses And\nContactor.
The remaining sections contain text for the windows (forms) in GEMPRO. As you translate
each section you should check the relevant window to ensure the translated text fits.
Not all forms are available under normal operations.
[Language] File identification
[Common] Common texts
[ConfigForm] Main configuration form
[SupplyForm] Configuration form
[FusesAndContactor] Configuration form
[PhaseCTs] Configuration form
[EarthFault] Configuration form
[MotorProtection] Configuration form
[ApplicationProtection] Configuration form
[ManualControls] Configuration form
[DigitalInputs] Configuration form
[MVIConfiguration] Multi voltage inputs configuration form
[RawHexEditor] Not normally available
[PAMM] Configuration form
[Communications] Configuration form
[Thermal] Configuration form
[Power] Configuration form
[Display] Configuration form
[GEMPRO] Configuration form
[Wizards] Configuration form
[AddressChange] Define Address form
[EditLinks] Link names form
- 99 -
Gemstart 5
- 100 -
Gemstart 5
The method for replacing the PAMM depends on the configuration of the PAMM Missing at
Power On item.
- 101 -
Gemstart 5
- 102 -
Gemstart 5
GEMPRO can read the translatable messages in Gemstart and create a file with the name of
the language and a .glf (Gemstart Language File) extension e.g. English.glf. This file is in the
same format as an .ini file with section and item definitions. GEMPRO reads all of the
translatable messages from Gemstart and places each message in the correct section of the
.glf file.
In “Commissioning”, click “User Language & Character Set” then “Read Active Language
from Gemstart to File”.
The language file that is read from Gemstart is the language that Gemstart is configured to
display. This allows any of the built in languages or the previously written User Defined
language to be read.
Once all of the translatable text has been downloaded you are prompted to save the data.
The default file name (language name . glf) is the name of the language downloaded.
- 103 -
Gemstart 5
- 104 -
Gemstart 5
0140 Œ Ž
0150 ˜ š œ ž Ÿ
0160 ¡ §
0170 ± ² ³
0180 µ · ¸ ¹ º ¼ ½
0190 ¾ ¿ À Á Â Ã Ä Å Æ Ç
0200 È É Ê Ë Ì Í Î Ï Ð Ñ
0210 Ò Ó Ô Õ Ö × Ø Ù Ú Û
0220 Ü Ý Þ ß à á â ã ä å
0230 æ ç è é ê ë ì í î ï
0240 ð ñ ò ó ô õ ö ÷ ø ù
0250 ú û ü ý þ ÿ
9.5.5 Editing Limitations
When editing any message the number of # characters in the message must not be
changed. The # is used to mark where data is inserted in a message and if the wrong
number of # characters exist then the displayed data will be wrong.
The fault text messages can be up to 50 characters long INCLUDING the severity text. So if
the longest severity text (e.g. Alarm) is 5 characters then the faults string should be limited to
45 characters. Fault messages wider than the LCD (about 25-30 characters depending on
the characters used) will be scrolled to display the whole text.
The Bottom Line Status messages and the Motor Data messages are not scrolled. Check
that the message fits on the LCD. The limit is about 25-30 characters depending on the
characters used.
If a message definition is not present in the .glf file then Gemstart will use the built in English
message.
- 105 -
Gemstart 5
Finally, in the Editor, click “Display” and choose “User Defined Language” to enable the new
language.
- 106 -
Gemstart 5
The character set that is read from Gemstart is the character set that Gemstart is configured
to display. This allows the built in or the previously written User Defined Character Set to be
read.
Once all of the character set has been downloaded you are prompted to save the data. The
default file name is UserCharSet.gcs.
- 107 -
Gemstart 5
[Char_49]
Default='1'
Char_49_0=" * "
Char_49_1=" ** "
Char_49_2="* * "
Char_49_3=" * "
Char_49_4=" * "
Char_49_5=" * "
Char_49_6="*****"
Char_49_7=" "
The section name [in square brackets] defines the ASCII character number. The default item
shows the default ASCII character for this character number. The Default item is only
provided by GEMPRO for information and is not required.
The text before the “=” is the item name and must not be changed. The text after the “=”
and between the quotes is the character definition. A space character is a blank pixel. A “*”
character turns the pixel on. Each character definition has 8 rows, 0 to 7, and can be up to
16 pixels wide.
- 108 -
Gemstart 5
- 109 -
Gemstart 5
Finally, go to the Editor Configuration, click on “Display” and choose “User Defined
Character Set” to enable the new character set.
- 110 -
Gemstart 5
- 111 -
Gemstart 5
- 112 -
Gemstart 5
- 113 -
Gemstart 5
11 Index
Adding a new language to GEMPRO .... 98 FLC ............................ 6, 21, 25, 37, 52, 57
Administrator Rights .............................. 12 French .................................................. 12
ALC....................................... 6, 25, 52, 58 Fuses and Contactors ........................... 55
Application ............................................ 58 Gembus .......................................... 36, 67
Button Bar ................................. 22, 40, 41 GEMPRO Configuration ........................ 67
COM Port .............................................. 18 GEMPRO Main Screen ......................... 21
Commands ..................................... 41, 65 Gemstart Address ........................... 45, 47
Commissioning3, 21, 24, 38, 48, 93, 95, Gemstart Selection ......................... 45, 47
100
Grey Background ................................ 52
Common Data ....................................... 34
Grey Foreground................................. 52
Common Features ................................ 51
Installation............................... 3, 4, 12, 15
Communications ................. 46, 50, 65, 99
Key .................... 12, 16, 17, 21, 40, 41, 67
Configuration CRC’s ............................. 48
Language ........... 12, 16, 22, 47, 66, 98, 99
Configuration Data Mismatch ................ 46
Maintenance ......................................... 37
Configuration Forms.............................. 51
Manual Controls .................................... 61
Configuration Window ........................... 45
Modbus ..................................... 30, 35, 67
Configuring Gemstart ...................... 11, 43
Monitoring ..........................11, 24, 40, 101
Connecting to Gemstart .................. 11, 18
Motor21, 26, 47, 48, 49, 51, 53, 54, 57,
Control10, 21, 22, 27, 38, 40, 41, 42, 44, 60, 62, 67
51, 93, 100, 101
Multi Voltage Inputs .............................. 63
Controlling Gemstart ....................... 11, 40
Offline Configuration ............................. 44
Copy ..................................................... 49
Online Edit ................................ 23, 44, 45
Counters ............................................... 27
Operating System ............................... 12
CT ..............................6, 25, 50, 52, 56, 57
PAMM .................. 42, 50, 64, 99, 101, 102
Currents ................................................ 25
Power21, 24, 26, 37, 60, 64, 99, 100, 101,
Digital Input ......................................... 53 102
Digital Inputs ......................................... 62 Print ..................................................... 50
Display .................................................. 66 Printing ................................................ 12
Earth Fault ...................................... 56, 57 Profibus ................... 24, 30, 34, 35, 65, 67
English .................................................. 12 Project Database ..... 43, 44, 45, 46, 47, 49
Event History ........................................ 31 Protection ............... 53, 56, 57, 58, 59, 60
Export ................................................... 50 Recovering a Partially Updated Gemstart
.......................................................... 96
Exporting ............................................. 12
Red Background ................................. 51
Fault List ............................................... 29
Replacing a Faulty PAMM ................... 101
Faults and History ................................. 29
Requesting Control ............................... 40
Flash Loader ................................... 96, 97
- 114 -
Gemstart 5
- 115 -
COMECA Equipements Basse Tension
Route de Givry – ZI La Garenne – F 71880 Châtenoy-le-Royal France Tel.: +33 (0)3 85 98 22 00 Fax+33 (0)3 85 98 22 01
Internet: www.comeca-group.com