Types of HVAC Terminal Units Guide
Types of HVAC Terminal Units Guide
com
Course № M-3008
Terminal Units
This document is the course text. You may review this material at
your leisure either before or after you purchase the course. To
purchase this course, click on the course overview page:
[Link]
or type the link into your browser. Next, click on the Take Quiz button
at the bottom of the course overview page. If you already have an
account, log in to purchase the course. If you do not have a
[Link] account, click the New User Sign Up link to create
your account.
After logging in and purchasing the course, you can take the online
quiz immediately or you can wait until another day if you have not yet
reviewed the course text. When you complete the online quiz, your
score will automatically be calculated. If you receive a passing score,
you may instantly download your certificate of completion. If you do
not pass on your first try, you can retake the quiz as many times as
needed by simply logging into your [Link] account and
clicking on the link Courses Purchased But Not Completed.
[Link]
5870 Highway 6 North, Suite 310
Houston, TX 77084
Toll Free: 877 500-7145
administrator@[Link]
B40 Terminals, Controls, and Accessories • Types of Terminals
Types of Terminals
B
Single Duct together with the necessary change-
over circuitry, makes this possible.
This basic terminal consists of casing, Controls can be pneumatic, electric,
a damper, a damper actuator, and analog electronic, or direct digital
associated controls. In response to electronic. Accessories such as round
Engineering Guidelines
control signals from a thermostat or other outlets, multiple outlets, and sound
source, the terminal varies the airflow attenuators may be added. The single
through a single duct handling hot or cold duct terminal is most often used in an
air. In some applications the same interior zone of the building, for
terminal is used for both heating and Figure 47. Elevation - Single
cooling only. Duct
cooling; a dual function thermostat,
Fan Powered, Parallel Type airflow, which is usually less than that
for cooling, the fan can be sized smaller
(Variable Volume) than in the series flow type terminal
In this terminal a fan is added to (see below). During the cooling cycle,
recirculate plenum air, for heating only. the fan is off and cool primary air is
The heating cycle occurs generally when supplied from the central system. A
the primary air is off or at minimum flow. backdraft damper prevents reverse flow
Heat is picked up as the recirculated air is through the fan. The flow of the primary
drawn from the ceiling space and the fan air is regulated by variable air volume Figure 51. Plan View - Fan
motor. Additional heat can be provided by controls. Used in exterior zones. Powered, Parallel Type (Variable
a hot water or electric coil on the terminal. Volume)
Because the fan handles only the heating
Terminals, Controls, and Accessories • Types of Terminals B41
B
Fan Powered, Series Type pressure can be lower than in the
parallel flow terminal (above). The fan,
(Constant Volume) however, is sized to handle the total
The fan runs continuously, fed by a airflow. These are often used in
mixture of primary and plenum air. The applications where constant
Engineering Guidelines
more primary air is forced in, the less background sound and continuous
plenum air is drawn in. The result is airflow are desired.
variable volume from the central system, Figure 52. Plan View - Fan
constant volume (and sound) to the room. Powered, Series Type (Constant
Because the central system need only Volume)
deliver air as far as the fan, the inlet static
Fan Powered, Access Floor The terminal can fit into the floor
plenum without any modifications to
Profile (Constant Volume) the pedestal system.
This series type terminal is designed to
fit around the pedestal support grid of
access, or raised, floor systems. In a
typical access floor the grid is 24”x24”.
Figure 54. Plan View - Fan
Powered, Access Floor Profile
(Constant Volume)
B42 Terminals, Controls, and Accessories • Types of Controls
Types of Controls
B
Reaction to Duct Note: Excessive airflow may lead to excessive noise.
Pressure independent control has less opportunity for
Pressure Controls variable (and unwanted) sounds in the occupied spaces.
Engineering Guidelines
Pressure Independent
With this type of control the terminal
maintains the flow rate required to handle
the heating or cooling load, regardless of
system pressure fluctuations. It is the best
choice where the system pressure will vary
extensively and where precise control is
essential. Key components in pressure
independent control are the velocity sensor,
which furnishes a continuous reading of the
air velocity through the terminal, and the
velocity controller, which processes this
information along with signals from the
thermostat. In the chart (Figure 55), vertical
lines AB and EF represent minimum and
maximum CFM settings which are
adjustable at the controller. Line CD
represents any CFM setting maintained by
the controller in response to the thermostat.
The damper will open and close as needed
to hold the CFM constant up and down this
vertical line for the full range of pressure
drops shown. Notice that the vertical CFM
lines are cut off by the diagonal line AE,
which represents the pressure drop from
inlet to outlet with the damper wide open.
This is the minimum DP shown in our data.
Figure 55. Pneumatic Pressure Independent
Pressure Dependent
A terminal with this type of control is
designed for those applications where
neither pressure independence nor CFM
limit regulation is required. An example is a
variable volume makeup air supply in which
the downstream duct pressure is held
constant by other controls. The terminal
consists essentially of a casing, a damper,
and a damper actuator. There is no
controller and no velocity sensor; the
damper moves in direct response to the
thermostat or other signal input. The line AB
(Figure 56) shows the typical performance
characteristic. It represents a given damper
setting, with the flow rate varying as the
square root of the static pressure drop
through the terminal. This, of course, is
typical of any damper or fixed orifice. Lines
CD and EF represent random additional
settings as the damper opens to the full
open position line GH. Line GH is the
minimum pressure loss of the assembly.
Figure 56. Pneumatic Pressure Dependent
Terminals, Controls, and Accessories • Types of Controls B43
Engineering Guidelines
Room Thermostat rise in temperature drives the damper
or Sensor actuator in the opening direction; a fall
in temperature reverses the actuator.
The thermostat contains not only a
Since the electric system has no
temperature sensing element, but Figure 57. Pneumatic System
velocity sensor and no controller, there
also a means of changing the
is no compensation for duct pressure
setpoint. The room sensor used with
fluctuations. Operation of the terminal is
the direct digital control system is
pressure dependent, the thermostat and
simply an electronic temperature
room response time are typically much
sensor; setpoint changes are handled
less than the actuator response time,
along with other signal processing in
and excessive room temperature
the digital controller.
variations are a likely result.
Velocity Sensor Analog Electronic Systems
Mounted in the inlet of the terminal,
Like the electric controls, analog
this device senses air velocity, which
electronic controls operate at low
can easily be converted to airflow
voltage, usually 24 VAC, supplied by a
rate. The sensor’s signal provides
transformer which is often built into the
feedback to monitor and directs the
control box of the terminal. These
operation of the controller and damper
controls, however, also include a Figure 58. Electric Pressure
actuator. Dependent System
velocity sensor of either the thermistor
Controller type, or pneumatic velocity sensor with
electronic transducer, together with an
Commands from the thermostat or electronic velocity controller that is
room sensor, together with feedback pressure independent. The electronic
from the velocity sensor, are thermostat can control both cooling and
processed in the controller to heating operations. Because of the
regulate the damper actuator. pressure independent operation and
Operation is pressure independent. integrated thermostat, excellent room
temperature control can be achieved.
Damper Actuator
The damper actuator opens and Direct Digital Electronic
closes the damper to change the Systems
airflow, or to hold it constant, as
Here again the power source is a low
dictated by the controller.
voltage supply. Signals from a
pneumatic or electronic velocity sensor,
Pneumatic systems together with signals from the room
Figure 59. Analog Electric Pressure
Independent System
In a pneumatic control system, the temperature sensor, are converted to
various components are powered by digital impulses in the controller, which
compressed air, usually at 15–25 psi, is a specialized microcomputer. The
from a central system. The thermostat controller not only performs the reset
receives air at full pressure directly and pressure independent volume
from the main air supply. In response control functions, but it also can be
to room temperature, the air pressure adjusted and programmed either locally
is modulated to the controller, which or remotely for multiple control
regulates the damper actuator. The strategies, including scheduling. In
sensor and controller compensate for addition, it can link to other controllers
changes in duct pressure so that and interface with security, lighting, and
operation is pressure independent. other equipment. Control can be
centralized in one computer.
Control Operation in
B
Terminals
Damper Operation
Linearity (Figure 61) is the ideal
Engineering Guidelines
Figure 65. Direct Reset Pneumatic Figure 66. Reverse Reset Controller
Velocity Controller
Terminals, Controls, and Accessories • Control Operation in Terminals B45
B
Pneumatic Thermostat-
Controller Combinations
For systems supplying cold air when a
direct acting pneumatic thermostat
Engineering Guidelines
signals a direct acting controller
(Figure 67), an increase in room
temperature produces an increase in
CFM setting. A reverse acting
thermostat with a reverse reset
controller produces the same result. A
direct acting thermostat with a reverse
reset controller or a reverse acting
thermostat with a direct reset controller
(Figure 68) will produce a decrease in Figure 67. DA Pneumatic Figure 68. RA Thermostat with
CFM as the room temperature Thermostat Signaling DA Controller Reverse Reset Controller or RA
increases. With warm supply air, the Combination Thermostat with Direct Reset
logic is reversed. Controller Combination
Operation of a
B
Velocity Controller
Definitions of Terms
Engineering Guidelines
Thermostat Sensitivity
This is the change in output signal
caused by a change in room
temperature. This rating (Figure 70) is
usually 1° F = 2.5 psi for pneumatic
systems. Electronic systems have a
wide variance in output responses.
Hysteresis
This is the failure of an object to return
to its original position after a force has
moved or deflected it. For example, in Figure 70. Thermostat Sensitivity Figure 71. Hysteresis Example
some velocity controllers (Figure 71) Example
the CFM setting increases along the
lower curved line and decreases along
the upper curved line. At the setpoint,
the CFM may be either A or B.
Terminals, Controls, and Accessories • Fan Terminal Flow Control B47
B
Pneumatic Feedback
Signals from the thermostat determine
the CFM setpoint of the controller. The
duct velocity acting on the velocity
Engineering Guidelines
sensor forms a feedback (closed) loop
(Figure 72) that allows the controller
to monitor the airflow resulting from its
settings and make corrections
continuously. This is a form of closed
loop control and is used on both
pneumatic and electronic pressure
independent systems.
In the TITUS ll pneumatic controller
there is also an internal feedback
loop that works in conjunction with Figure 72. Pneumatics Feedback
a positive positioning reset
mechanism to eliminate hysteresis
(see Figure 71, page B46).
B
Voltage Adjustment Fan Speed Control
Voltage adjustment of fan powered terminals typically
involves the use of a silicon controlled rectifier (SCR). An
SCR uses a triac to phase proportion (chop) the electrical The rpm of the motor is reduced by the SCR, lowering the
Engineering Guidelines
sine wave. tip speed of the fan. Since the free area downstream of the
fan is not reduced, the velocity either meets design
In effect, the SCR switches power off 120 times a second conditions or is lowered if the airflow is reduced below
on a 60 Hertz cycle. This reduces the voltage to the motor, design for balancing purposes. There is no increase in
slowing its speed. In operation, the SCR responds to the sound from air disturbances.
current but controls voltage. Thus, while an SCR’s triac
may be energized at zero current, the current sine wave
generally lags the voltage sine wave with an induction
motor. This results in the idealized voltage sine wave
shown below (Figure 74). As the SCR is used to further
reduce fan speed, the true RMS value of the voltage is
reduced.
As voltage to the motor is reduced, the motor tries to
compensate and the motor’s amp draw rises slightly. The
amperes will continue to increase until 50% of the current
sine wave is phase proportioned. After this point, the amp
draw will decrease. The increased amp draw is small
relative to the reduction in voltage. As a result, comparing
power consumption of the mechanical trimming method
with the voltage adjustment method is analogous to
comparing the power consumption of inlet guide vanes on
central air handlers with speed inverters (Figure 75 and
76).
Engineering Guidelines
airflow vs. static pressure. As the static pressure
increases, airflow decreases. A typical fan curve will show
maximum and minimum airflow for a fan powered terminal.
In Figure 77, the top curve represents the maximum
airflow that the fan and motor can provide. This
corresponds to the recommended maximum operating
RPM of the motor. The bottom curve shows the minimum
airflow that the fan and motor can provide. This
corresponds to either the minimum operating RPM of the
motor or the minimum voltage of the SCR fan speed
controller.
The SCR minimum is designed to protect the motor from
operating below its recommended RPM. Most standard
fan powered terminal motors must operate above a
manufacturer’s specified RPM to effectively self-lubricate.
However, the relationship between RPM and SCR voltage
is dependent of static pressure. At minimum voltage on
the SCR, the motor RPM will be different at different static
pressures. Because of this, there is a possibility that at
minimum SCR voltage, the RPM will be below the motor
minimum recommended operating RPM. When this
happens, the cataloged fan curve will use minimum RPM
to set the minimum fan curve, not minimum SCR voltage.
To ensure proper motor operation, always operate a fan
powered terminal with the cataloged fan curve.
1600
800
designed for these conditions must be used.
600
400
200
0 0.1 0.2 0.3 0.4 0.5 0.6
400
• Manually with a screwdriver, similar to the SCR
control 200
0
• Remotely (as an option) through the DDC controls 1263 1350 1601 1786 1849 2081 2162 2200
using a laptop at the unit CFM
ECM
in time creates distortion in the incoming line. 300
SCR
Due to the way a standard split capacitor motor draws 200
Engineering Guidelines
With many years' experience, design engineers have
Table 9. Annual Savings per Motor established the basic principles of temperature control for
heating, ventilating, and air conditioning (HVAC) systems.
Usage KW/hr reductions These control strategies have been applied utilizing
Rate 0.2872 0.35 0.405 conventional pneumatic, electric, or analog electronic
devices.
$0.05 $43.08 $52.50 $60.75
Recent advances in micro-technology have made it
$0.06 $51.70 $63.00 $72.90 possible to apply the power and precision of computers to
HVAC control. Microprocessors, which cost less than ever
$0.07 $60.31 $73.50 $85.05
before and offer superior computing power, are now
$0.08 $68.93 $84.00 $97.20 suitable for application to individual air handlers, packaged
heating/cooling units, VAV terminals, or the entire HVAC
$0.10 $86.16 $105.00 $121.50 system.
$0.12 $103.39 $126.00 $145.80
Direct Digital Control
$0.14 $120.62 $147.00 $170.10 Microprocessor-based controllers inherently perform direct
digital control (DDC) and typically replace the conventional
pneumatic or analog electronic controls. Digital controllers
Also, reduction in demand charges must also be considered. measure signals from sensors (input), process these
Typically, demand charges are calculated during a 15- signals in software (through the microprocessor), and
minute peak window. Some utilities will qualify the peak initiate a corrective action to a controlled device (outputs)
demand to only the summer months and use this peak as (Figure 80). A more technical definition is provided in the
the monthly charge throughout the remainder of the year ASHRAE 1995 Systems and Applications Handbook.
while other utilities will calculate demand charges using that
months peak kW requirement. The savings associated with
reduced demand charges are substantial, as demand
charges are usually several dollars per kW. As an example,
a typical multi-story office application may require 200 fan A direct digital controller receives electronic
signals from the sensors, converts the
terminals.
electronic signals to numbers, and performs
Each fan terminal equipped with an ECM motor may have mathematical operations on these numbers
approximately 0.4 kW reduction in power. This translates to inside the computer. The output from the
an 80 kW reduction in demand and with a demand rate of computer takes the form of a number, and can
be converted to a voltage or pneumatic signal
$10.00 per kW equates to a potential $800 per month
to operate the actuator.
reduction in the demand charges. While this model is
simplistic, it is indicative of the payback potential of the
motor. Utilities will vary not only in price but also in
calculation methods with contract kW's versus actual kW
usage so actual savings must be calculated according to
local market conditions. Advantages of DDC
DDC systems offer several potential advantages over
Coupling the usage and demand savings associated with conventional counterparts.
the ECM motors can provide a substantial savings
throughout the life of the building. • DDC systems provide improved comfort and greater
energy efficiency through precise and accurate control.
Pneumatic and Analog systems utilizing proportional
(P) control have the inherent characteristic of offset
(Figure 81). Microprocessor based controls can
eliminate offset by adding the integral (I) or reset
action. Furthermore, addition of the derivative (D)
action can result in a faster response and greater
stability (Figure 82), but requires significant tuning.
• DDC systems require less maintenance than
conventional systems. Since there are no moving
parts, periodic preventive maintenance (PM) tasks
such as calibration, lubrication, cleaning, and
adjustments are seldom required.
• Control strategies can be modified quickly and easily
without the need to rewire, repipe, or install additional
components.
B52 Terminals, Controls, and Accessories • Direct Digital Control
B
Engineering Guidelines
Figure 80. Direct Digital Controller Figure 81. Inherent Offset - Lost Energy Dollars and
Sacrificed Comfort
B
DDC Distributed Processing
Engineering Guidelines
as distributed processing, DDC
controllers can function as standalone
devices. In this way if one controller
fails, others throughout the system can
continue to function unaffected. The
controllers are connected over a system
communication bus or local area
network (LAN) for system wide sharing
of information. This information is used
to perform sophisticated building control
strategies not possible with conventional
noncommunicating systems. The
network also allows system access
locally through a personal computer or
remotely via modem over telephone
lines (Figure 84).
Sizing Basic Terminals The selection of an appropriate water coil should also
be considered at this time. In some cases, a terminal may
B
from Capacity Tables need to be increased in size in order to obtain the desired
heat output from the coil. With single duct units, the water
coil air pressure drop should be subtracted from the duct
pressure when determining sound generation. (The sound
Certified Air Terminals produced by the damper is proportional to the pressure
To provide engineers with sound power data which can be
Engineering Guidelines
Sizing Basic Terminals from Capacity Tables (Continued) Secondary Air (Fan): From the fan curves, a size 4,
without coils, terminal will handle 1150 CFM at 0.30” static
pressure, with the proper setting of the standard SCR B
Example: Select a Model DTQP for a maximum of speed control. The system curve of the downstream duct
1400 CFM of primary air with 1.00” wg inlet static pressure. and diffusers (a square curve defined by the point
The fan airflow required is 1150 CFM. The downstream 1150 CFM at 0.30” static pressure) intersects the minimum
resistance offered by the duct and diffusers has been speed static pressure curve of the fan at about 875 CFM
determined to be 0.30” static pressure at 1150 CFM.
Engineering Guidelines
and 0.17” static pressure. This is the minimum airflow for
Primary Air: From the chart on page R46, a size 4 with a that duct, without dampering.
12” inlet will handle 1400 CFM of primary air with a
minimum static pressure drop of 0.22” through the primary
air section. But since the downstream resistance is 0.30” at
1150 CFM,
2
(1150
1400 ) x 0.30” = 0.44” sp
Sizing Series Fan Powered Terminals To select a TITUS series fan powered terminal unit, refer to
the published fan curves and primary air pressure drop
B Compared to single duct terminals, series flow (constant curves together with the application and sound power data.
volume) fan powered terminals add the additional factor of An abbreviated table is shown at the right for use with the
fan CFM requirements. The designer must consider both example discussed here.
the primary airflow and the fan. Series terminals are
selected based on the capacity of their fans. The secondary In the series flow type of unit, the fan runs continuously in
(or fan) CFM should be equal to or slightly more than the the standard version. With the optional night shutdown and
Engineering Guidelines
primary air to ensure primary air does not short circuit night setback controls, the fan can be cycled ON and OFF
through the induced air port into the plenum, thereby when the primary air is OFF.
wasting energy.
As shown in the diagrams below, the primary air is drawn
Before selecting the fan, the static pressure downstream of into the fan inlet along with secondary (recirculated) air
the terminal must be determined. This is the resistance of from the room. The maximum primary airflow must always
the ducts and diffuser(s) at design airflow rates. be equal to, or less than, the total airflow through the fan.
Once the downstream static pressure is known, the When the primary air section reduces its airflow in
designer can select the fan based on the fan curves (these response to a reduced demand for cooling, the fan makes
are shown throughout the catalog with the performance up the difference by drawing more recirculated air from the
data for each fan powered terminal). The designer should room. As a result, the flow rate to the room is constant.
find the intersection of the static pressure line on the
horizontal axis and the fan CFM on the vertical axis. The primary air section discharges into the unit casing near
Selecting toward the upper end of the range will ensure that the fan inlet, where the static pressure is slightly below
first costs are kept low and the fan motor efficiency is high. atmospheric. For this reason, the available inlet pressure
Selecting below the indicated minimum flow will result in need only be enough to overcome the internal pressure
shortened motor life as the bearings in the motor are drop through the primary air damper itself.
centrifugally lubricated.
Example: Select a Model DTQS for a maximum of
If a water coil is needed, the designer must use the curves 1200 CFM of primary air at 0.50” wg inlet static pressure.
provided for a one or two row coil. These curves account The fan airflow is 1200 CFM. The downstream resistance
for the additional static pressure generated by the coil. The offered by the duct and diffusers is 0.30” at 1200 CFM.
static pressure added for an electric coil is negligible and
Primary Air: From the table on page R11, a size 4 will
may be disregarded. Neither has an appreciable effect on
handle 1200 CFM of primary air with a minimum static
sound levels.
pressure drop of .2” through the primary air section. Since
Inlet size must also be selected. Fan powered terminals 0.50” static pressure is available at the inlet, the selection
come with varying inlet sizes. In general, inlets should be will work.
selected toward the bottom of the range. This reduces the
Secondary Air (Fan): From the published fan curves, a
face velocity of the inlet and minimizes the sound
size 4 terminal will handle 1200 CFM at 0.30” static
generated by the primary air valve.
pressure, with the proper setting of the standard SCR
speed control.
Typical Problems
B
Oversizing Terminal
The direct result of oversizing is low air velocity.
With the velocity too low, the damper must operate
Engineering Guidelines
in a pinched-down condition most of the time,
making control difficult. The inlet velocity can also
be too low for effective operation of the sensor and
controller. Too low a velocity through an electric
heater will cause the safety airflow switch to shut
down the heater. (Figure 89) Oversizing fan
terminals results in low fan motor rpm and the Figure 89. Low Velocity Effects
potential for under-lubrication of the motor bearings,
resulting in shortened motor life, and additional
sound from larger motors.
Insufficient Space
Carefully planning the locations of the terminals
avoids problems with installation, performance, and
maintenance.
In the example shown at the right, the control side of
the terminal is against the wall, making connections
difficult and service almost impossible. The cramped
location also creates the need for close-coupled duct
elbows, which reduce performance (see below).
(Figure 91) Figure 91. Installation Affecting Performance
B
Incompatibility with Power Source
In fan powered terminals, electrically or
electronically controlled terminals, and all terminals
with electric heating coils, the order to the factory
should be carefully checked against the electrical
Engineering Guidelines
B
Non-Compliance with Local Codes
Some localities have stringent codes of their own,
with requirements beyond those of NEC, UL, and
CSA. An example is the primary fusing in the control
transformer at the right. (Figure 99)
Engineering Guidelines
Installation Techniques—Duct
Connections
The inlet duct slips over the inlet collar of the
terminal. It should be fastened and sealed according Figure 99. Primary Fusing in the Control Transformer
to the job specifications.
The diameter of the inlet duct must be equal to the
listed size of the terminal. For example, a duct that
measures 8" in diameter must be fitted to a size
8 terminal. The inlet collar of the terminal is made
1
/8” smaller than nominal size in order to fit inside
the duct (Figure 100).
Note: A duct should never be inserted inside the
inlet collar of the terminal.
For optimum control accuracy, a straight section
of unrestricted duct at least 11/2 diameters long Figure 100. Terminal Inlet Collar Fitting Properly
should be installed at the inlet (Figure 101). Where
this condition does not exist, field adjustment of
the airflow setting on the velocity controller may
be required.
If space does not permit using the 11/2 diameter
length of straight duct, a hard duct elbow up to 90°
can be installed at the inlet of the TITUS terminal
without altering the factory maximum or minimum
airflow setting by more than 10% (Figure 102).
The outlet end of the TITUS terminal is designed for
a slip and drive connection. Unless a round duct Figure 101. Unrestricted Duct Properly Install at the Inlet
adapter is furnished, a rectangular outlet duct
should be fitted to match the size of the terminal
casing. It should be fastened and sealed according
to the job specifications.
If a round outlet adapter is furnished, it should be
fastened and sealed by the same method used for
the inlet.
Close coupling the terminal inlet to the side of the
main supply duct is not recommended. Where this
condition is unavoidable, a flow straightening device
(Figure 103) should be installed between the main
supply duct and the inlet to the terminal. Even with Figure 102. 90 Degree Hard Elbow Duct Installed to Inlet
the flow straightening device, the terminal may still
require some field adjustment of the factory airflow
settings at the velocity controller.
Air leakage adds significantly to the operating cost
of an HVAC system. Important savings are realized
by carefully fitting and sealing all duct joints and
specifying tightly constructed TITUS [Link]
TITUS box has very low damper and casing loss
leakage. These values can be found on page Q26.
B
The example in Figure 104 shows how many
dollars can be lost in the leakage from just one
terminal together with its connected duct work.
Multiply that amount by the hundreds or thousands
of terminals that may be in one building, and the
Engineering Guidelines
A 10” terminal handles 1150 CFM. The central The amount of leakage in the branch duct serving
system cools air from 80° F dry bulb / 67° F wet the terminal, the connections to the terminal, the
bulb to 53° F dry bulb / 51.5° F wet bulb before terminal itself, and the duct downstream from the
sending it to the terminal. terminal is 5% of the 1150 CFM being handled, or
about 58 CFM.
Some Basic
B
Concepts–Pressure
Measurement
Engineering Guidelines
Three categories of pressure are
connected with air handling:
1. Static pressure may be thought of
as the pressure in a tire or storage
tank. It is exerted in all directions
equally.
2. Velocity pressure, as its name
implies, is entirely a function of air
velocity and its direction. It is the
pressure you feel against your
hand if you hold it outside the
window of a moving car.
3 Total pressure is the sum of static
pressure and velocity pressure. It
and static pressure are the
pressures actually sampled by
velocity sensors in terminals and by
commonly used measuring devices,
as described next.
The interaction of static, velocity, and
total pressures is illustrated by
Figure 105. The Pitot tube, which is
used to measure velocities and
pressures, is really a tube within a tube.
The inner, or impact, tube senses both
the velocity pressure and static pressure
combined (total pressure). The outer
tube, which communicates with the
airstream through small holes in its wall,
avoids the impact of the air movement
and senses only static pressure.
The U-tube manometer, connected to
both parts of the Pitot tube, has the
effect of subtracting static pressure
from total pressure to give a reading of
velocity pressure.
Once the velocity pressure is known,
the velocity can be calculated easily:
2
Pv = ( 4005
V
) or V = 4005 Pv
rpm
Example: 500
400
Engineering Guidelines
rpm
500
P1 = rpm12 400
300
P2 = rpm22 200
100
0
P2 = P1 x rpm22 / rpm12 0 0.5 1 1.5 2 2.5 3
= 2 x (800)2 / (760) 2 Ps, In wg
= 2.22" Figure 107. Fan Law - Pressure
3. Horsepower varies as the cube of shaft speed.
bhp1 = rpm13 Fan Law 3
1000
bhp2 = ((bhp1) x (rpm2)3 / (rpm1)3 900
= ((18) x (800)3) / (760)3 800
700
= 21.0 600
rpm
500
The relationships stated here apply when the air density 400
remains constant and when there is no change in the 300
fan or the system. They are based on Fan Laws 1, 2, 200
and 3. For a complete presentation of the Fan Laws, 100
0
see the ASHRAE Handbook, Systems and Equipment,
0 2 4 6 8 10 12 14 16 18 20
1992.
bhp
Each fan design has its characteristic set of Figure 108. Fan Law - Brake Horsepower
performance curves. Those shown in Figure 109 are
typical of a centrifugal fan with forward curved blades in
the wheel, as commonly used in fan powered terminals. System Curve
For a full discussion of the characteristics of the various 3.5
types of fans, see the ASHRAE Handbook, Systems
and Equipment, 1996. 3
The solid curve represents a fan running at constant B
speed, as it is throttled from free delivery to close-off. 2.5
Total Pressure
0
1000 3000 5000 7000 9000 11000 13000
Volume Flow Rate
Engineering Guidelines
A = Amps
TP = Total Pressure
SP = Static Pressure hp = Horsepower
VP = Velocity Pressure V = Volts
(V) fpm = Feet per Minute
∆P = Differential Pressure E1 = Efficiency
∆Ps = Static Differential Pressure PF = Power Factor
∆PT = Total Differential Pressure
(A) Area Factor = Dimension in Square Feet
VP = TP - SP Power DC Circuits
TP = SP + VP W = VxA
SP = TP - VP
CFM = fpm x Area Factor A = W/V
∆PT = TP1 - TP2 hp = V x A x E / 746
∆Ps = SP1 - SP2
∆P = (CFM / K)2 E = 746 x HP / W
fpm = CFM / Area Factor
K = CFM/ (∆P)
Power AC Circuits (Single Phase)
PF = W / (V x A)
Reheat Coils:
Several types of terminal devices are available with reheat coils, both hot water and electric. When determining the heat
requirement for a terminal, the engineer will often start with the known zone heating demand, typically expressed in BTUH,
or more conveniently, MBH (thousands of BTU’s). The room load requirements for heating are then used to determine the
Room Entering Air temperature (EATr) by the equation:
BTUH (room) = 1.085 * (EATr - Tr) * Q
Where;
EATr = The temperature (°F) entering the room
Tr = Room setpoint temperature or average temperature
Q = Flowrate ( CFM) (typically 30 - 50% of the cooling CFM)
By solving for the EATr, the coil BTUH requirements can then be determined. The room entering air temperature (EATr)
now becomes the required LAT of the VAV box (ignoring any duct heat losses). The coil can now be sized according to:
BTUH (coil) = 1.085 * (LAT - EATc) * Q
Where;
LAT = The coil leaving air temperature
EATc = Coil entering air temperature, (primary or mixed air)
Q = Flowrate ( CFM)
Now that the coil requirements are known, published catalog data may be used to select the proper hot water or electric
coil.