Modular DIN Rail Products
MCB
3. Type designation
N B 1 - 63 DC
Driect Current
Frame size rated current
Designed sequence number
MCB
Company code
4. Operating conditions
4.1 Ambient temperature:-35℃~+70℃(Refer to 4.3)
4.2 The atmosphere condition:≤95%
4.3 Pollution degree:II
4.4 Altitude:≤2000m(if exceed 2000m,Refer to 4.4)
5. Technical data
NB1-63DC 5.1 Classification
DC Circuit Breaker 5.1.1 Rate Current In: 1A,2A,3A,4A,6A,10A,13A,16A,20A,25A,
32A,40A,50A,63A
5.1.2 Number of poles: 1P,2P,4P
1. General 5.1.3 Tripping curves: C Type,(7~10)In
5.2 Parameters
1.1 Certificates: CCC,CE,CB,SAA,TUV; 5.2.1 Rated breaking capacity Icn
1.2 Standard: IEC/EN 60947-2 ,RoHS;
1.3 Rated voltage up to 1000V, Rated current up to 63A;
1.4 Protection of circuits against overload currents;
1.5 Protection of circuits against short-circuit currents;
1.6 NB1-63 DC circuit-breakers are used in
communication systems and PV DC systems.
2. Features
2.1 Excellent breaking capacity
2.2 Double connection function of lead wire and bus bar
2.3 Stored energy operation, fast closing, long service life
2.4 Convenient installation, disassembly
2.5 Contact on-off indication, higher security
2.6 Green environmental protection and energy saving
11 >> Empower the World
Modular DIN Rail Products
MCB
Rated current Number of Rated voltage Rated breaking
In (A) poles Ue (V) capacity Icn (A)
1 250 6000
1~63 2 500 6000
4 1000 6000
5.2.2 Electrical and mechancial life
a. Electrical life:> 1500
b. Mechancial life:>20,000
5.2.3 Rated impulse withstand voltage Uimp:4KV
5.2.4 (28-32)℃ ambient temperature over-current protection features.
Test Initial Time limit for tripping Expected
Test Remarks
current state or not tripping result
a 1.05In Cold state a t≤1h Not tripping
b 1.30In Right after test number a t<1h Tripping The current is rising within 5s
0.2s<t<15s (In≤32A)
c 7In Cold state a Tripping
0.2s<t≤30s (In>32A)
d 10In Cold state a t<0.1s Tripping
Note: The terminology”Cold state”means that the test is performed at the base calibration temperature with no load prior to the test.
5.3 Temperature derating
Temperature compensation coefficient under various operational temperature.
Rated current (A)
-35℃ -30℃ -20℃ -10℃ 0℃ 10℃ 20℃ 30℃ 40℃ 50℃ 60℃ 70℃
1 1.3 1.26 1.23 1.19 1.15 1.11 1.05 1 0.96 0.93 0.88 0.83
2 2.6 2.52 2.46 2.38 2.28 2.2 2.08 2 1.92 1.86 1.76 1.66
3 3.9 3.78 3.69 3.57 3.42 3.3 3.12 3 2.88 2.79 2.64 2.49
4 5.2 5.04 4.92 4.76 4.56 4.4 4.16 4 3.84 3.76 3.52 3.32
6 7.8 7.56 7.38 7.14 6.84 6.6 6.24 6 5.76 5.64 5.28 4.98
10 13.2 12.7 12.5 12 11.5 11.1 10.6 10 9.6 9.3 8.9 8.4
13 17.16 16.51 16.25 15.6 14.95 14.43 13.78 13 12.48 12.09 11.57 10.92
16 21.12 20.48 20 19.2 18.4 17.76 16.96 16 15.36 14.88 14.24 13.44
20 26.4 25.6 25 24 23 22.2 21.2 20 19.2 18.6 17.8 16.8
25 33 32 31.25 30 28.75 27.75 26.5 25 24 23.25 22.25 21
32 42.56 41.28 40 38.72 37.12 35.52 33.93 32 30.72 29.76 28.16 26.88
40 53.2 51.2 50 48 46.4 44.8 42.4 40 38.4 37.2 35.6 33.6
50 67 65.5 63 60.5 58 56 53 50 48 46.5 44 41.5
63 83.79 81.9 80.01 76.86 73.71 70.56 66.78 63 60.48 58.9 55.44 52.29
5.4 Altitude derating
Rated current Current correction factor
Tripping type For example
In (A) ≤2000 2000~3000m ≥3000m
1,2,3,4,6,10,
Rated current of 10A products rated
C 13,16,20,32, 1 0.9 0.8
current derating 2500m:0.9×10=9A
40,50,63
Empower the World >> 12
Modular DIN Rail Products
MCB
5.5 Curves shown in Figure 1
5.6 Wiring: Apply to 25 mm2 wire connection terminals
Tightening torque 2.5N·m
t(s)
10000 Copper wire nominal
Rated current In (A)
5000 cross sectional area(mm2)
1h
2000
1000
1~6 1
500 10 1.5
200 13,16,20 2.5
100
50 25 4
20 32 6
10
5
40,50 10
2 63 16
1
0.5
0.2
0.1
0.05 5.7 Each pole power consumption of the circuit breaker
0.02
Each pole maximum
0.01 Rated current In (A)
power consumption(W)
0.005
0.002 1~10 2
0.001 3.5
0.5 1 2 3 4 5 7 1 0 20 30 50 70 100 200 I/In
13~32
40~63 5
5.8 DC application wiring diagram shown in Figure 2
1P 2P 4P
L- L+
Wiring diagram description:
L+ 1. Negative
Positive
2. L+ Load positive L- Load negative
L-
3. Prohibit power reversed
4. Rated voltage: 1P:250V, 2P:500V, 4P:1000V
5. Strictly forbidden to remove the four poles
L- L+ products of sealing plug wiring operation.
6. Overall and mounting dimensions (mm)
34.5±0.50
45±0.13
86 -1.4
0
35
0
1P 18-0.02
7.5
0
49.5±0.31 36-0.02
0
2P 27
78-1.2 0
72-1.2
4P
13 >> Empower the World