DESIGN OF RAMP
DATA:
L = 6m
Rise = 0.5m
fc’ = 27.6 Mpa
n = 9
fy = 415 Mpa
fs = 248 Mpa
Dead load = 23.54 KN/m3
Live load = 7.22 KN/m3
Figure:
COMPUTATION:
REQUIRED EFFECTIVE DEPTH:
Assume as simply supported
L 6000
Minimum t = = = 300 mm
20 20
Considering one meter strip of slab:
Dead load = (0.300)(1)(23.54)= 7.06 kN/m
Live load = 7.2 KN/m
W = (1.2)7.06 + (1.6)7.22 = 19.99 Kn/m
2
M = W L = (19.99)¿¿ = 89.96 KN.m
8
n 9
k = fs = 248 = 0.50
n+ 9+
fc ' 27.6
k
j = 1 - = 0.83
3
1 1
R = fckj = (27.6)(0.50)(0.83)
2 2
R = 5.73 MPa
d =
√ M =
Rb √ (89.86 x 1 06 ) = 125.30 mm
5.73(1000)
t= 300 mm
d = 300-25 = 275 mm > 125.30 mm (OK)
Spacing of Main Reinforced:
Steel Area:
Use 16 mm ∅ bar
M (89.96 x 1 06 )
As = = = 1589.23 mm2
fsjd (248)(0.83)(275)
2 2
Ab = π d = π (16) = 201.06 mm2
4 4
(201.06)(1000)
S = = 126.51 mm say 125 mm
1589.23
SHEAR:
WL (19.99)(6)
V = – Wd = −(19.99)(0.275)
2 2
(54.47)(1000)
V = 54.47 KN ν= = 0.198 MPa
(1000)(275)
ALLOWABLE SHEAR:
ν = 0.09 √ fc ' = 0.09 √ 27.6
ν = 0.473 MPa
Allowable ν = 0.473 > ν=0.198 (OK)
BOND:
V
u=
∑ jd
0
(19.99)(6)
V = = 59.97 KN
2
1000
∑ ¿ 125 π (16) = 402.12 mm
0
59.97 (1000)
u= = 0.653 MPa
(402.12)(0.83)(275)
Allowable u = 10.14 √ fc ' = 10.14 √ 27.6 = 3.33 MPa
D 16
Allowable u = 3.33 > u = 0.653 (OK)
Use 300 mm thick slab with 16 mm bars Spaced at 125 mm on centers.
Temperature bar:
As= 0.0018bt = 0.0018(1000)(275)= 495 mm2
Spacing of temperature bars:
Use 10 mm ∅ bar
2 2
Ab = π d = π (10) = 78.54 mm2
4 4
(78.54)(1000)
S = = 158.67 mm say 150 mm
495
Use 10 mm ∅ for temperature bars, Spaced at 150 mm on centers.
6