The document provides detailed operating instructions for the Proline Promag 10 Electromagnetic flowmeter with Modbus RS485 communication. It includes information on device parameters, menus, and wizards for commissioning, diagnostics, and application settings. The target audience is specialists who require in-depth knowledge for configuration and troubleshooting throughout the device's lifecycle.

Uploaded by

waqasasad409
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
48 views144 pages

Proline Promag 10 Modbus RS485 Guide

The document provides detailed operating instructions for the Proline Promag 10 Electromagnetic flowmeter with Modbus RS485 communication. It includes information on device parameters, menus, and wizards for commissioning, diagnostics, and application settings. The target audience is specialists who require in-depth knowledge for configuration and troubleshooting throughout the device's lifecycle.

Uploaded by

waqasasad409
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

GP01158D/06/EN/02.

22-00 Products Solutions Services


71575137
2022-08-01
Valid as of version
[Link] (Device firmware)

Description of Device Parameters


Proline Promag 10
Electromagnetic flowmeter
Modbus RS485
Proline Promag 10 Modbus RS485 Table of contents

Table of contents

1 About this document . . . . . . . . . . . . . . . . 4 5.2 "User management" submenu . . . . . . . . . . . . . 93


5.2.1 "Define access code" wizard . . . . . . . . . 95
1.1 Document function . . . . . . . . . . . . . . . . . . . . . 4 5.3 "Connectivity" submenu . . . . . . . . . . . . . . . . . 96
1.2 Target group . . . . . . . . . . . . . . . . . . . . . . . . . . 4 5.3.1 "Bluetooth configuration" submenu . . . 96
1.3 Using this document . . . . . . . . . . . . . . . . . . . . 4 5.4 " Date / Time" submenu . . . . . . . . . . . . . . . . . 97
1.3.1 Symbols . . . . . . . . . . . . . . . . . . . . . . . 4 5.5 "Information" submenu . . . . . . . . . . . . . . . . . . 99
1.3.2 Information on the document 5.5.1 "Device" submenu . . . . . . . . . . . . . . . . 99
structure . . . . . . . . . . . . . . . . . . . . . . . 4 5.5.2 "Sensor electronic module (ISEM)"
1.3.3 Structure of a parameter description . . 5 submenu . . . . . . . . . . . . . . . . . . . . . 102
1.4 Associated documentation . . . . . . . . . . . . . . . . 5 5.5.3 "Display module" submenu . . . . . . . . 102
5.6 "Display" submenu . . . . . . . . . . . . . . . . . . . . 104
2 "Guidance" menu . . . . . . . . . . . . . . . . . . . 6 5.7 "Software configuration" submenu . . . . . . . . . 108
2.1 "Commissioning" wizard . . . . . . . . . . . . . . . . . . 6
2.1.1 Device identification . . . . . . . . . . . . . . 8 6 Modbus RS485 register
2.1.2 System units . . . . . . . . . . . . . . . . . . . . 9
2.1.3 Totalizer 1 to n . . . . . . . . . . . . . . . . . 13
information . . . . . . . . . . . . . . . . . . . . . . 109
2.1.4 Process parameters . . . . . . . . . . . . . . 15 6.1 Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
2.1.5 Measurement conditions . . . . . . . . . . 16 6.1.1 Structure of the register information 109
2.1.6 Current output . . . . . . . . . . . . . . . . . 20 6.1.2 Address model . . . . . . . . . . . . . . . . 109
2.1.7 Display . . . . . . . . . . . . . . . . . . . . . . . 25 6.2 Overview of the operating menu . . . . . . . . . . 110
2.1.8 Date/time . . . . . . . . . . . . . . . . . . . . . 27 6.3 Register information . . . . . . . . . . . . . . . . . . 119
6.3.1 "Guidance" menu . . . . . . . . . . . . . . . 119
6.3.2 "Diagnostics" menu . . . . . . . . . . . . . . 125
3 "Diagnostics" menu . . . . . . . . . . . . . . . . 29 6.3.3 "Application" menu . . . . . . . . . . . . . 128
3.1 "Actual diagnostics" submenu . . . . . . . . . . . . . 30 6.3.4 "System" menu . . . . . . . . . . . . . . . . . 136
3.2 "Diagnostic list" submenu . . . . . . . . . . . . . . . . 32
3.3 "Simulation" submenu . . . . . . . . . . . . . . . . . . . 35
3.4 "Heartbeat Technology" submenu . . . . . . . . . . 38
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
3.5 "Diagnostic settings" submenu . . . . . . . . . . . . . 39
3.5.1 "Properties" submenu . . . . . . . . . . . . . 39
3.5.2 "Diagnostic configuration" submenu . . 39

4 "Application" menu . . . . . . . . . . . . . . . . 49
4.1 "Measured values" submenu . . . . . . . . . . . . . . 49
4.1.1 "Totalizer" submenu . . . . . . . . . . . . . . 51
4.2 "System units" submenu . . . . . . . . . . . . . . . . . 53
4.3 "Totalizers" submenu . . . . . . . . . . . . . . . . . . . 58
4.3.1 "Totalizer handling" submenu . . . . . . . 58
4.3.2 "Totalizer 1 to n" submenu . . . . . . . . . 58
4.4 "Sensor" submenu . . . . . . . . . . . . . . . . . . . . . . 63
4.4.1 "Process parameters" submenu . . . . . . 63
4.4.2 "Low flow cut off" submenu . . . . . . . . 66
4.4.3 "Partially filled pipe detection"
submenu . . . . . . . . . . . . . . . . . . . . . . 67
4.4.4 "Sensor adjustment" submenu . . . . . . . 69
4.4.5 "Calibration" submenu . . . . . . . . . . . . 70
4.4.6 "Electrode cleaning cycle" submenu . . . 72
4.5 "Current output" submenu . . . . . . . . . . . . . . . . 74
4.6 " Communication" submenu . . . . . . . . . . . . . . 85
4.6.1 "Modbus configuration" submenu . . . . 85
4.6.2 "Modbus data map" submenu . . . . . . . 88
4.6.3 "Modbus information" submenu . . . . . 89

5 "System" menu . . . . . . . . . . . . . . . . . . . . 90
5.1 "Device management" submenu . . . . . . . . . . . . 91

Endress+Hauser 3
About this document Proline Promag 10 Modbus RS485

1 About this document

1.1 Document function


The document is part of the Operating Instructions and serves as a reference for
parameters, providing a detailed explanation of each individual parameter of the operating
menus.
It is used to perform tasks that require detailed knowledge of the function of the device:
• Optimal adaptation of the measurement to difficult conditions
• Detailed configuration of the communication interface
• Error diagnostics in difficult cases

1.2 Target group


The document is aimed at specialists who work with the device over the entire life cycle
and perform specific configurations.

1.3 Using this document

1.3.1 Symbols

Types of information

Preferred procedures, processes or actions


Permitted procedures, processes or actions
Forbidden procedures, processes or actions
Additional information
Reference to documentation
A
Reference to page
Reference to graphic

1.3.2 Information on the document structure


The parameters of all the operating menus and the commissioning wizard are described in
this document.
• Guidance menu with the Commissioning wizard (→  6), which guides the user
automatically through all the device parameters that are required for commissioning
• Application menu (→  49)
• Diagnostics menu (→  29)
• System menu (→  90)

4 Endress+Hauser
Proline Promag 10 Modbus RS485 About this document

1.3.3 Structure of a parameter description


The individual parts of a parameter description are described in the following section:

Complete parameter name Write-protected parameter =

Navigation Navigation path to the parameter via the operating tool


The names of the menus, submenus and parameters are abbreviated to the form in which they appear on
the display and in the operating tool.

Prerequisite The parameter is only available under these specific conditions

Description Description of the parameter function

Selection List of the individual options for the parameter


• Option 1
• Option 2

User entry Input range for the parameter

User interface Display value/data for the parameter

Additional information Additional explanations (e.g. in examples):


• On individual options
• On display values/data
• On the input range
• On the parameter function

1.4 Associated documentation


Technical Information Overview of the device with the most important technical data.
Operating Instructions All the information that is required in the various phases of the life cycle of
the device: from product identification, incoming acceptance and storage, to
mounting, connection, operation and commissioning through to
troubleshooting, maintenance and disposal as well as the technical data and
dimensions.
Sensor Brief Operating Instructions Incoming acceptance, transport, storage and mounting of the device.
Transmitter Brief Operating Electrical connection and commissioning of the device.
Instructions
Description of Parameters Detailed explanation of the menus and parameters.
Safety Instructions Documents for the use of the device in hazardous areas.
Special Documentation Documents with more detailed information on specific topics.
Installation Instructions Installation of spare parts and accessories.

The related documentation is available online:


W@M Device Viewer On the [Link]/deviceviewer website, enter the serial number of
the device: nameplate
Endress+Hauser Operations App ‣ Scan the Data Matrix code: nameplate
‣ Enter the serial number of the device: nameplate

Endress+Hauser 5
"Guidance" menu Proline Promag 10 Modbus RS485

2 "Guidance" menu
Main functions for use – from fast and safe commissioning to guided support during
operation.

Navigation  Guidance

Guidance

‣ Commissioning → 6

2.1 "Commissioning" wizard


Complete this wizard to commission the device. NOTE: If you exit the wizard beforehand,
the changes you made will be saved. For this reason, the device may be in an undefined
state! In this case, reset the device to the default settings.

Navigation  Guidance → Commissioning

‣ Commissioning

Device tag → 8

Serial number → 8

Firmware version → 8

Device name → 8

Volume flow unit → 9

Volume unit →  10

Mass flow unit →  11

Mass unit →  11

Density unit →  12

Temperature unit →  12

Conductivity unit →  12

Assign process variable →  13

Unit totalizer 1 to n →  13

Totalizer operation mode →  14

6 Endress+Hauser
Proline Promag 10 Modbus RS485 "Guidance" menu

Failure mode →  15

Flow damping →  15

Low flow cut off →  17

On value low flow cutoff →  18

Off value low flow cutoff →  18

Pressure shock suppression →  16

Empty pipe detection →  19

Empty pipe adjust value →  19

Full pipe adjust value →  19

Process variable current output →  20

Current range output →  20

Lower range value output →  21

Upper range value output →  22

Damping current output →  23

Fixed current →  23

Failure behavior current output →  23

Failure current →  24

Value 1 display →  25

Value 2 display →  25

Value 3 display →  26

Value 4 display →  26

Display damping →  26

Time format →  27

Time zone →  27

Set date/time →  28

Endress+Hauser 7
"Guidance" menu Proline Promag 10 Modbus RS485

2.1.1 Device identification

Navigation  Guidance → Commissioning

Device tag 

Navigation  Guidance → Commissioning → Device tag

Description Enter a unique designation for the measuring point to be able to easily identify it within
the plant.

User entry Character string comprising numbers, letters and special characters (32)

Serial number

Navigation  Guidance → Commissioning → Serial number

Description Displays the serial number of the measuring device. The serial number can be used to
identify the measuring device and to retrieve further information on the measuring device,
such as the related documentation, via the Device Viewer or Operations app.
Additional information:
The serial number can also be found on the nameplate of the sensor and transmitter.

User interface Character string comprising numbers, letters and special characters

Firmware version

Navigation  Guidance → Commissioning → Firmware version

Description Displays the device firmware version installed.

User interface Character string comprising numbers, letters and special characters

Device name

Navigation  Guidance → Commissioning → Device name

Description Displays the name of the transmitter.


Additional information:
The name can also be found on the transmitter's nameplate.

8 Endress+Hauser
Proline Promag 10 Modbus RS485 "Guidance" menu

User interface Character string comprising numbers, letters and special characters

2.1.2 System units

Navigation  Guidance → Commissioning

Volume flow unit 

Navigation  Guidance → Commissioning → Volume flow unit

Description Select volume flow unit.

Endress+Hauser 9
"Guidance" menu Proline Promag 10 Modbus RS485

Selection SI units US units Imperial units


• cm³/s • af/s • gal/s (imp)
• cm³/min • af/min • gal/min (imp)
• cm³/h • af/h • gal/h (imp)
• cm³/d • af/d • gal/d (imp)
• dm³/s • ft³/s • Mgal/s (imp)
• dm³/min • ft³/min • Mgal/min (imp)
• dm³/h • ft³/h • Mgal/h (imp)
• dm³/d • ft³/d • Mgal/d (imp)
• m³/s • MMft³/s • bbl/s (imp;beer)
• m³/min • MMft³/min • bbl/min (imp;beer)
• m³/h • MMft³/h • bbl/h (imp;beer)
• m³/d • Mft³/d • bbl/d (imp;beer)
• ml/s • fl oz/s (us) • bbl/s (imp;oil)
• ml/min • fl oz/min (us) • bbl/min (imp;oil)
• ml/h • fl oz/h (us) • bbl/h (imp;oil)
• ml/d • fl oz/d (us) • bbl/d (imp;oil)
• l/s • gal/s (us)
• l/min • gal/min (us)
• l/h • gal/h (us)
• l/d • gal/d (us)
• hl/s • Mgal/s (us)
• hl/min • Mgal/min (us)
• hl/h • Mgal/h (us)
• hl/d • Mgal/d (us)
• Ml/s • bbl/s (us;liq.)
• Ml/min • bbl/min (us;liq.)
• Ml/h • bbl/h (us;liq.)
• Ml/d • bbl/d (us;liq.)
• bbl/s (us;beer)
• bbl/min (us;beer)
• bbl/h (us;beer)
• bbl/d (us;beer)
• bbl/s (us;oil)
• bbl/min (us;oil)
• bbl/h (us;oil)
• bbl/d (us;oil)
• bbl/s (us;tank)
• bbl/min (us;tank)
• bbl/h (us;tank)
• bbl/d (us;tank)
• kgal/s (us)
• kgal/min (us)
• kgal/h (us)
• kgal/d (us)

Volume unit 

Navigation  Guidance → Commissioning → Volume unit

Description Select volume unit.

10 Endress+Hauser
Proline Promag 10 Modbus RS485 "Guidance" menu

Selection SI units US units Imperial units


• cm³ • af • gal (imp)
• dm³ • ft³ • Mgal (imp)
• m³ • Mft³ • bbl (imp;beer)
• ml • fl oz (us) • bbl (imp;oil)
•l • gal (us)
• hl • kgal (us)
• Ml Mega • Mgal (us)
• bbl (us;oil)
• bbl (us;liq.)
• bbl (us;beer)
• bbl (us;tank)

Mass flow unit 

Navigation  Guidance → Commissioning → Mass flow unit

Description Select mass flow unit.

Selection SI units US units


• g/s • oz/s
• g/min • oz/min
• g/h • oz/h
• g/d • oz/d
• kg/s • lb/s
• kg/min • lb/min
• kg/h • lb/h
• kg/d • lb/d
• t/s • STon/s
• t/min • STon/min
• t/h • STon/h
• t/d • STon/d

Mass unit 

Navigation  Guidance → Commissioning → Mass unit

Description Select mass unit.

Selection SI units US units


•g • oz
• kg • lb
•t • STon

Endress+Hauser 11
"Guidance" menu Proline Promag 10 Modbus RS485

Density unit 

Navigation  Guidance → Commissioning → Density unit

Description Select density unit.

Selection SI units US units Imperial units


• g/cm³ • lb/ft³ • lb/gal (imp)
• g/m³ • lb/gal (us) • lb/bbl (imp;beer)
• kg/l • lb/bbl (us;liq.) • lb/bbl (imp;oil)
• kg/dm³ • lb/bbl (us;beer)
• kg/m³ • lb/bbl (us;oil)
• SD4°C • lb/bbl (us;tank)
• SD15°C
• SD20°C
• SG4°C
• SG15°C
• SG20°C

Temperature unit 

Navigation  Guidance → Commissioning → Temperature unit

Prerequisite Temperature measurement is only optionally available for Promag H 10 (5HBB): Under
order code for "Functionality", option D (extended transmitter) and order code for "Sensor
option", option CI (medium temperature measurement)

Description Select temperature unit.

Selection SI units US units


• °C • °F
•K • °R

Conductivity unit 

Navigation  Guidance → Commissioning → Conductiv. unit

Prerequisite Conductivity measurement is switched on in the Conductivity measurement parameter


(→  64).
Conductivity measurement is only optionally available: Under order code for
"Functionality", option D (extended transmitter) and order code for "Sensor option",
option CX (conductivity measurement)

Description Select conductivity unit.

12 Endress+Hauser
Proline Promag 10 Modbus RS485 "Guidance" menu

Selection SI units
• nS/cm
• µS/cm
• µS/m
• µS/mm
• mS/m
• mS/cm
• S/cm
• S/m
• kS/m
• MS/m

2.1.3 Totalizer 1 to n

Navigation  Guidance → Commissioning

Assign process variable 

Navigation  Guidance → Commissioning → Assign variable

Description Select process variable for totalizer.


Additional information:
If the option selected is changed, the device resets the totalizer to "0".

Selection • Off
• Volume flow
• Mass flow

Unit totalizer 1 to n 

Navigation  Guidance → Commissioning → Unit totalizer 1 to n

Prerequisite A process variable has been selected in the Assign process variable parameter in the
Totalizer 1 to n submenu.

Description Select process variable totalizer unit.

Selection SI units US units


• g* • oz *
• kg * • lb *
• t* • STon *

* Visibility depends on order options or device settings

or

Endress+Hauser 13
"Guidance" menu Proline Promag 10 Modbus RS485

SI units US units Imperial units


• cm³ * • af * • gal (imp) *
• dm³ * • ft³ * • Mgal (imp) *
• m³ * • Mft³ * • bbl (imp;beer) *
• ml * • fl oz (us) * • bbl (imp;oil) *
• l* • gal (us) *
• hl * • kgal (us) *
• Ml Mega * • Mgal (us) *
• bbl (us;liq.) *
• bbl (us;beer) *
• bbl (us;oil) *
• bbl (us;tank) *

* Visibility depends on order options or device settings

or

Other units
None *

* Visibility depends on order options or device settings

Additional information Description


The unit is selected separately for each totalizer. The unit is independent of the option
selected in the System units submenu (→  53).

Selection
The selection is dependent on the process variable selected in the Assign process variable
parameter (→  13).

Totalizer operation mode 

Navigation  Guidance → Commissioning → Operation mode

Prerequisite A process variable has been selected in the Assign process variable parameter in the
Totalizer 1 to n submenu.

Description Select totalizer calculation mode.

Selection • Net flow total


• Forward flow total
• Reverse flow total

Additional information Selection


• Net flow total option
The flow values in the forward and reverse flow directions are totalized and netted
against each other. Net flow is recorded in the flow direction.
• Forward flow total option
Only the flow in the forward flow direction is totalized.
• Reverse flow total option
Only the flow in the reverse flow direction is totalized (= reverse flow quantity).

14 Endress+Hauser
Proline Promag 10 Modbus RS485 "Guidance" menu

Failure mode 

Navigation  Guidance → Commissioning → Failure mode

Prerequisite A process variable has been selected in the Assign process variable parameter in the
Totalizer 1 to n submenu.

Description Specify how the totalizer should behave in the event of a device alarm.
Additional information:
The failsafe mode that applies to any other totalizers or outputs is specified separately in
other parameters and is not impacted by this setting.

Selection • Stop
• Actual value
• Last valid value

Additional information Selection


• Stop option
The totalizer is stopped in the event of a device alarm.
• Actual value option
The totalizer continues to totalize based on the current value measured; the device alarm
is ignored.
• Last valid value option
The totalizer continues to totalize based on the last valid value measured before the
device alarm occurred.

2.1.4 Process parameters

Navigation  Guidance → Commissioning

Flow damping 

Navigation  Guidance → Commissioning → Flow damping

Description Enter value for damping of the flow measured value in order to reduce the variability of
the flow measured value when exposed to interference.
Additional information:
The depth of the flow filter is determined by this setting. As the filter depth increases, so
does the reaction time of the device.
- Value = 0: No damping. Damping of 0 is not recommended, as the measuring signal is
then so noisy that it is almost impossible to perform a measurement.
- Value > 0: Damping increases
Optimal damping depends on the measuring period.
Damping impacts the following measuring device variables:
- Outputs
- Low flow cut off
- Totalizers

Endress+Hauser 15
"Guidance" menu Proline Promag 10 Modbus RS485

User entry 0 to 15

2.1.5 Measurement conditions

Pressure shock suppression

Navigation  Guidance → Commissioning

Pressure shock suppression 

Navigation  Guidance → Commissioning → Pres. shock sup.

Description Enter time frame for signal suppression (= pressure shock suppression active), for example
to prevent the device from registering flow movements in the pipe when a valve is closed.
Additional information:
Pressure schock suppression is activated when the flow rate drops below the on value for
low flow cutoff. Output values when pressure shock suppression is active:
- Flow: 0
- Totalizer: Last valid value
Pressure shock suppression is deactivated when:
- The time frame specified has elapsed and
- Flow exceeds the off value for low flow cutoff

User entry 0 to 100 s

Additional information Example


When a valve is closed, momentarily strong fluid movements may occur in the pipeline,
which are registered by the device. These totalized flow values lead to a false totalizer
status, particularly during batching processes.

16 Endress+Hauser
Proline Promag 10 Modbus RS485 "Guidance" menu

Q D C D

1 2 3 4

6
5
t

A B

A0012888

Q Flow
t Time
A After run
B Pressure shock
C Pressure shock suppression active as specified by the time entered
D Pressure shock suppression inactive
1 Valve closes
2 Flow falls below the on-value of the low flow cut off: pressure shock suppression is activated
3 The time entered has elapsed: pressure shock suppression is deactivated
4 The actual flow value is now displayed and output
5 On-value for low flow cut off
6 Off-value for low flow cut off

Low flow cut off

Navigation  Guidance → Commissioning

Low flow cut off 

Navigation  Guidance → Commissioning → Low flow cut off

Description Select process variable for low flow cut off to activate low flow cut off.

Selection • Off
• Volume flow
• Mass flow

Additional information Description

Endress+Hauser 17
"Guidance" menu Proline Promag 10 Modbus RS485

Q 2 2

4
H
3
t
1 A 1 A

A0012887

Q Flow
t Time
H Hysteresis
A Low flow cut off active
1 Low flow cut off is activated
2 Low flow cut off is deactivated
3 On-value entered
4 Off-value entered

On value low flow cutoff 

Navigation  Guidance → Commissioning → On value

Description Enter on value to switch on low flow cut off.


Value = 0: No low flow cut off
Value > 0: Low flow cut off is activated

User entry Positive floating-point number

Off value low flow cutoff 

Navigation  Guidance → Commissioning → Off value

Description Enter off value to switch off low flow cut off. The off value is entered as a positive
hysteresis with respect to the on value.

User entry 0 to 100.0 %

18 Endress+Hauser
Proline Promag 10 Modbus RS485 "Guidance" menu

Empty pipe detection

Navigation  Guidance → Commissioning

Empty pipe detection 

Navigation  Guidance → Commissioning → Empty pipe det.

Description Switch empty pipe detection on or off. Switch on empty pipe detection to detect a partially
filled or empty measuring tube.

Selection • Off
• On

Empty pipe adjust value 

Navigation  Guidance → Commissioning → Empty pipe value

Description Displays adjustment value when the measuring tube is empty.


NOTE
Users logged on in the Service role have write access!

User interface Positive floating-point number

Full pipe adjust value 

Navigation  Guidance → Commissioning → Full pipe value

Description Displays adjustment value when the measuring tube is full.


NOTE
Users logged on in the Service role have write access!

User interface Positive floating-point number

Endress+Hauser 19
"Guidance" menu Proline Promag 10 Modbus RS485

2.1.6 Current output

Navigation  Guidance → Commissioning

Process variable current output 

Navigation  Guidance → Commissioning → [Link]. outp

Description Select process variable for current output

Selection • Off *
• Mass flow
• Conductivity *
• Corrected conductivity *
• Volume flow
• Temperature *
• Noise *
• Coil current shot time *

Current range output 

Navigation  Guidance → Commissioning → [Link] out

Description Select the current range for the measured value output and the upper and lower fault
condition signal level.
Additional information:
- The measured value range is specified in the "Lower range value output " parameter and
the "Upper range value output " parameter.
- If the measured value lies outside the scaled measured value range, diagnostic message
"441 Current output faulty" is generated.
- In the event of a device alarm, the current output adopts the behavior specified in the
"Failure behavior current output " parameter.

Selection • 4...20 mA NE (3.8...20.5 mA)


• 4...20 mA US (3.9...20.8 mA)
• 4...20 mA (4... 20.5 mA)
• Fixed value

Additional information Selection


• 4...20 mA NE (3.8...20.5 mA) option
Select this option to set the current range in accordance with NAMUR recommendation
NE43.
• Fixed value option
Select this option to set the current output to a current value instead of a range.

The current value is defined in the Fixed current parameter (→  23).

* Visibility depends on order options or device settings

20 Endress+Hauser
Proline Promag 10 Modbus RS485 "Guidance" menu

The graphic shows the relationship between the current range for the output of the
process value and the lower and upper alarm levels:

2 1 3

I [mA]
A0034351

1 Current range for process value


2 Lower level for signal on alarm
3 Upper level for signal on alarm

Selection (current range for process value) Lower level for signal on Upper level for signal on
alarm alarm

4...20 mA NE (3.8...20.5 mA) < 3.6 mA > 21.5 mA

4...20 mA US (3.9...20.8 mA)

4...20 mA (4... 20.5 mA)

Lower range value output 

Navigation  Guidance → Commissioning → [Link] outp

Prerequisite In the Current range output parameter, one of the following options is selected:
• 4...20 mA NE (3.8...20.5 mA)
• 4...20 mA US (3.9...20.8 mA)
• 4...20 mA (4... 20.5 mA)

Description Enter lower range value for the measured value range.
Additional information:
- Depending on the setting selected for the "Measuring mode current output " parameter,
the value specified for this parameter and the "Upper range value output " parameter must
have the same algebraic sign or not.
- As a rule, the lower range value is scaled to be lower than the upper range value. As a
result, the behavior of the current output is proportional to the process variable assigned.
If the lower range value is scaled to be higher than the upper range value, then the
behavior of the current output will be inversely proportional to the process variable
assigend.

User entry Signed floating-point number

Additional information Examples of the behavior, depending on the option selected in the Measuring mode
current output parameter (→  75).

Example: Measuring mode with "Forward flow" option


• Lower range value output parameter (→  21) = not equal to zero flow (e.g. –250
m3/h)
• Upper range value output parameter (→  22) = not equal to zero flow (e.g. +750
m3/h)
• Calculated current value = 8 mA at zero flow

Endress+Hauser 21
"Guidance" menu Proline Promag 10 Modbus RS485

I [mA]
20
8
4
Q
-250 0 +750
1 1
A0013757

Q Flow
I Current
1 Measuring range is exceeded or undershot

The linear operational range of the measuring device is defined by the values entered for
the Lower range value output parameter (→  21) and Upper range value output
parameter (→  22), and by the selected current range.

Example: Measuring mode with the "Forward/Reverse flow" option

I [mA]

20

4
0 Q
0
3 1 2
A0013758

Q Flow
I Current
1 Value assigned to 0/4 mA current
2 Forward flow
3 Reverse flow

The current output signal is independent of the direction of flow (absolute amount of the
measured variable). The values for the Lower range value output parameter (→  21)
and Upper range value output parameter (→  22) must have the same algebraic sign.
The value for the Upper range value output parameter (→  22) (e.g. reverse flow)
corresponds to the mirrored value for the Upper range value output parameter
(→  22) (e.g. forward flow).

Example: Measuring mode with the "Reverse flow compensation" option


If flow is characterized by severe fluctuations (e.g. when using reciprocating pumps), flow
components outside the measuring range are buffered, balanced and output after a
maximum delay of 60 s.

Upper range value output 

Navigation  Guidance → Commissioning → [Link] outp

Prerequisite In the Current range output parameter, one of the following options is selected:
• 4...20 mA NE (3.8...20.5 mA)
• 4...20 mA US (3.9...20.8 mA)
• 4...20 mA (4... 20.5 mA)

22 Endress+Hauser
Proline Promag 10 Modbus RS485 "Guidance" menu

Description Enter upper range value for the measured value range.

User entry Signed floating-point number

Additional information Examples of the behavior, depending on the option selected in the Measuring mode
current output parameter: Lower range value output parameter (→  21):

Damping current output 

Navigation  Guidance → Commissioning → [Link]

Prerequisite A process variable is selected in the Process variable current output parameter and one
of the following options is selected in the Current range output parameter:
• 4...20 mA NE (3.8...20.5 mA)
• 4...20 mA US (3.9...20.8 mA)
• 4...20 mA (4... 20.5 mA)

Description Enter time constant (PT1 element) to set the reaction time of the output signal to
fluctuations in the measured value caused by process conditions.
Additional information:
- The smaller the time constant the faster the output reacts to fluctuations in the
measured value.
- If the time constant is 0, damping is deactivated.

User entry 0.0 to 999.9 s

Fixed current 

Navigation  Guidance → Commissioning → Fixed current

Prerequisite In the Current range output parameter in the Current output 1 submenu, the Fixed
value option is selected.

Description Enter the value for the "Fixed value" option.

User entry 3.59 to 21.5 mA

Failure behavior current output 

Navigation  Guidance → Commissioning → [Link]

Prerequisite A process variable is selected in the Process variable current output parameter and one
of the following options is selected in the Current range output parameter:
• 4...20 mA NE (3.8...20.5 mA)
• 4...20 mA US (3.9...20.8 mA)
• 4...20 mA (4... 20.5 mA)

Endress+Hauser 23
"Guidance" menu Proline Promag 10 Modbus RS485

Description Specify how the output should behave in the event of a device alarm.

Selection • Min.
• Max.
• Last valid value
• Actual value
• Fixed value

Additional information Selection


• Min. option
The current output outputs the lower fault condition signal level for the specified current
range.
Additional information:
The current range is specified in the "Current range output " parameter.
• Max. option
The current output outputs the upper fault condition signal level for the specified current
range.
Additional information:
The current range is specified in the "Current range output " parameter.
• Last valid value option
The current output outputs the last valid value measured before the device alarm
occurred.
• Actual value option
The current output outputs the flow value currently measured. The device alarm is
ignored.
• Fixed value option
The current output outputs the value specified.
Additional information:
The value is specified in the "Failure current " parameter.

Failure current 

Navigation  Guidance → Commissioning → Fail. current

Prerequisite In the Failure behavior current output parameter in the Current output 1 submenu, the
Fixed value option is selected.

Description Enter the value for the "Fixed value" option in the "Failure behavior current output "
parameter.

User entry 3.59 to 21.5 mA

24 Endress+Hauser
Proline Promag 10 Modbus RS485 "Guidance" menu

2.1.7 Display

Navigation  Guidance → Commissioning

Value 1 display 

Navigation  Guidance → Commissioning → Value 1 display

Description Select the measured value that is displayed first on the local display.
Additional information:
The applicable unit of measure is specified in the "System units" submenu.

Selection • Volume flow


• Mass flow
• Conductivity *
• Corrected conductivity *
• Temperature *
• Totalizer 1
• Totalizer 2
• Totalizer 3

Value 2 display 

Navigation  Guidance → Commissioning → Value 2 display

Description Select the measured value that is shown second on the local display.
Additional information:
The applicable unit of measure is specified in the "System units" submenu.

Selection • None
• Volume flow
• Mass flow
• Conductivity *
• Corrected conductivity *
• Temperature *
• Totalizer 1
• Totalizer 2
• Totalizer 3

* Visibility depends on order options or device settings

Endress+Hauser 25
"Guidance" menu Proline Promag 10 Modbus RS485

Value 3 display 

Navigation  Guidance → Commissioning → Value 3 display

Description Select the measured value that is shown third on the local display.
Additional information:
The applicable unit of measure is specified in the "System units" submenu.

Selection • None
• Volume flow
• Mass flow
• Conductivity *
• Corrected conductivity *
• Temperature *
• Totalizer 1
• Totalizer 2
• Totalizer 3

Value 4 display 

Navigation  Guidance → Commissioning → Value 4 display

Description Select the measured value that is shown fourth on the local display.
Additional information:
The applicable unit of measure is specified in the "System units" submenu.

Selection • None
• Volume flow
• Mass flow
• Conductivity *
• Corrected conductivity *
• Temperature *
• Totalizer 1
• Totalizer 2
• Totalizer 3

Display damping 

Navigation  Guidance → Commissioning → Display damping

Description Enter time constant (PT1 element) to set reaction time of the display to fluctuations in the
measured value.
Additional information:
- The smaller the time constant the faster the display reacts to fluctuations in the
measured value.
- If the time constant is set to 0, damping is deactivated.

* Visibility depends on order options or device settings

26 Endress+Hauser
Proline Promag 10 Modbus RS485 "Guidance" menu

User entry 0.0 to 999.9 s

2.1.8 Date/time

Navigation  Guidance → Commissioning

Time format 

Navigation  Guidance → Commissioning → Time format

Description Select time format.

Selection • 24 h
• 12 h AM/PM

Time zone 

Navigation  Guidance → Commissioning → Time zone

Description Select the time zone. Every time the time zone is changed, a logbook entry is created.

Endress+Hauser 27
"Guidance" menu Proline Promag 10 Modbus RS485

Selection
Other units
• UTC-12:00
• UTC-11:00
• UTC-10:00
• UTC-09:30
• UTC-09:00
• UTC-08:00
• UTC-07:00
• UTC-06:00
• UTC-05:00
• UTC-04:00
• UTC-03:30
• UTC-03:00
• UTC-02:00
• UTC-01:00
• UTC 00:00
• UTC+01:00
• UTC+02:00
• UTC+03:00
• UTC+03:30
• UTC+04:00
• UTC+04:30
• UTC+05:00
• UTC+05:30
• UTC+05:45
• UTC+06:00
• UTC+06:30
• UTC+07:00
• UTC+08:00
• UTC+08:45
• UTC+09:00
• UTC+09:30
• UTC+10:00
• UTC+10:30
• UTC+11:00
• UTC+12:00
• UTC+12:45
• UTC+13:00
• UTC+14:00

Set date/time 

Navigation  Guidance → Commissioning → Set date/time

Description Set the date and local time. Every time the date or time is changed, a logbook entry is
created.

User entry Date and time

28 Endress+Hauser
Proline Promag 10 Modbus RS485 "Diagnostics" menu

3 "Diagnostics" menu
Troubleshooting and preventive maintenance – settings for device behavior during process
and device events as well as assistance and measures for diagnostic purposes.

Navigation  Diagnostics

Diagnostics

‣ Active diagnostics →  30

‣ Diagnostic list →  32

‣ Simulation →  35

‣ Heartbeat Technology →  38

‣ Diagnostic settings →  39

Endress+Hauser 29
"Diagnostics" menu Proline Promag 10 Modbus RS485

3.1 "Actual diagnostics" submenu


Navigation  Diagnostics → Active diagnos.

‣ Active diagnostics

Actual diagnostics →  30

Timestamp →  30

Previous diagnostics →  30

Timestamp →  31

Operating time from restart →  31

Operating time →  31

Actual diagnostics

Navigation  Diagnostics → Active diagnos. → Actual diagnos.

Prerequisite A diagnostic event has occurred.

Description Displays the currently active diagnostic message.


If there is more than one pending diagnostic event, the message for the diagnostic event
with the highest priority is displayed.

User interface Positive integer

Timestamp

Navigation  Diagnostics → Active diagnos. → Timestamp

Description Displays the timestamp for the currently active diagnostic message.

User interface Days (d), hours (h), minutes (m), seconds (s)

Previous diagnostics

Navigation  Diagnostics → Active diagnos. → [Link]

Prerequisite At least two diagnostic events have already occurred.

30 Endress+Hauser
Proline Promag 10 Modbus RS485 "Diagnostics" menu

Description Displays the diagnostic message for the last diagnostic event that has ended.

User interface Positive integer

Timestamp

Navigation  Diagnostics → Active diagnos. → Timestamp

Description Displays the timestamp of the diagnostic message generated for the last diagnostic event
that has ended.

User interface Days (d), hours (h), minutes (m), seconds (s)

Operating time from restart

Navigation  Diagnostics → Active diagnos. → Time fr. restart

Description Indicates how long the device has been in operation since the last time the device was
restarted.

User interface Days (d), hours (h), minutes (m), seconds (s)

Operating time

Navigation  Diagnostics → Active diagnos. → Operating time

Description Indicates how long the device has been in operation.

User interface Days (d), hours (h), minutes (m), seconds (s)

Endress+Hauser 31
"Diagnostics" menu Proline Promag 10 Modbus RS485

3.2 "Diagnostic list" submenu


Navigation  Diagnostics → Diagnostic list

‣ Diagnostic list

Diagnostics 1 →  32

Timestamp →  32

Diagnostics 2 →  33

Timestamp →  33

Diagnostics 3 →  33

Timestamp →  33

Diagnostics 4 →  33

Timestamp →  34

Diagnostics 5 →  34

Timestamp →  34

Diagnostics 1

Navigation  Diagnostics → Diagnostic list → Diagnostics 1

Description Displays the currently active diagnostic message with the highest priority.

User interface Positive integer

Timestamp

Navigation  Diagnostics → Diagnostic list → Timestamp

Description Displays the timestamp for the diagnostic message with the highest priority.

User interface Days (d), hours (h), minutes (m), seconds (s)

32 Endress+Hauser
Proline Promag 10 Modbus RS485 "Diagnostics" menu

Diagnostics 2

Navigation  Diagnostics → Diagnostic list → Diagnostics 2

Description Displays the currently active diagnostic message with the second highest priority.

User interface Positive integer

Timestamp

Navigation  Diagnostics → Diagnostic list → Timestamp

Description Displays the timestamp for the diagnostic message with the second highest priority.

User interface Days (d), hours (h), minutes (m), seconds (s)

Diagnostics 3

Navigation  Diagnostics → Diagnostic list → Diagnostics 3

Description Displays the currently active diagnostic message with the third highest priority.

User interface Positive integer

Timestamp

Navigation  Diagnostics → Diagnostic list → Timestamp

Description Displays the timestamp for the diagnostic message with the third highest priority.

User interface Days (d), hours (h), minutes (m), seconds (s)

Diagnostics 4

Navigation  Diagnostics → Diagnostic list → Diagnostics 4

Description Displays the currently active diagnostic message with the fourth highest priority.

User interface Positive integer

Endress+Hauser 33
"Diagnostics" menu Proline Promag 10 Modbus RS485

Timestamp

Navigation  Diagnostics → Diagnostic list → Timestamp

Description Displays the timestamp for the diagnostic message with the fourth highest priority.

User interface Days (d), hours (h), minutes (m), seconds (s)

Diagnostics 5

Navigation  Diagnostics → Diagnostic list → Diagnostics 5

Description Displays the currently active diagnostic message with the fifth-highest priority.

User interface Positive integer

Timestamp

Navigation  Diagnostics → Diagnostic list → Timestamp

Description Displays the timestamp for the diagnostic message with the fifth highest priority.

User interface Days (d), hours (h), minutes (m), seconds (s)

34 Endress+Hauser
Proline Promag 10 Modbus RS485 "Diagnostics" menu

3.3 "Simulation" submenu


Navigation  Diagnostics → Simulation

‣ Simulation

Assign simulation process variable →  35

Process variable value →  36

Current output 1 simulation →  36

Current output value →  36

Device alarm simulation →  37

Diagnostic event category →  37

Diagnostic event simulation →  37

Assign simulation process variable 

Navigation  Diagnostics → Simulation → Assign [Link].

Description Select a process variable for the simulation, thereby activating it.

Selection • Off
• Volume flow
• Mass flow
• Conductivity *
• Corrected conductivity *
• Temperature *

Additional information Description


The display alternates between the measured value and a diagnostics message of the
"function check" category (C) when simulation is active.

* Visibility depends on order options or device settings

Endress+Hauser 35
"Diagnostics" menu Proline Promag 10 Modbus RS485

Process variable value 

Navigation  Diagnostics → Simulation → Proc. var. value

Description Enter the simulation value for the selected process variable. Processing of measured values
downstream as well as the signal ouput follow this value. In this way, it is possibe to verify
whether the measuring device has been configured correctly.
Additional information:
The applicable unit of measure is specified in the "System units" submenu.

User entry Signed floating-point number

Current output 1 simulation 

Navigation  Diagnostics → Simulation → [Link] 1 sim.

Description Switch simulation of the current output on or off.


Additional information:
When simulation is on, the current output signal is set to the value specified in the
"Current output value" parameter.

Selection • Off
• On

Additional information Description


The display alternates between the measured value and a diagnostics message of the
"function check" category (C) when simulation is active.

Current output value 

Navigation  Diagnostics → Simulation → [Link] val.

Description Enter the current value for the simulation. In this manner, it is possible to verify the
current output is configured correctly and downstream processing units are functioning
properly.
Additional information:
The valid input range is determined by the "Current range output " parameter.

User entry 3.59 to 21.5 mA

36 Endress+Hauser
Proline Promag 10 Modbus RS485 "Diagnostics" menu

Device alarm simulation 

Navigation  Diagnostics → Simulation → Dev. alarm sim.

Description Switch the device alarm simulation on or off.


While simulation is in progress, the display alternates between the measured value and a
diagnostic message of the Function Check (C) category.

Selection • Off
• On

Diagnostic event category 

Navigation  Diagnostics → Simulation → Event category

Description Select the category of diagnostic events that should be available for selection in the
"Diagnostic event simulation" parameter.

Selection • Sensor
• Electronics
• Configuration
• Process

Diagnostic event simulation 

Navigation  Diagnostics → Simulation → Diag. event sim.

Description Select the diagnostic event to simulate.

Selection Off

Endress+Hauser 37
"Diagnostics" menu Proline Promag 10 Modbus RS485

3.4 "Heartbeat Technology" submenu


The Heartbeat Technology submenu (→  38) is only available with the optional
"Heartbeat Verification + Monitoring" application package.
• Order code for: Application package
• Option: EB "Heartbeat Verification + Monitoring"
Detailed information and all descriptions of the device parameters of the application
package are available in the "Heartbeat Verification + Monitoring" Special
Documentation

Navigation  Diagnostics → HBT

‣ Heartbeat Technology

38 Endress+Hauser
Proline Promag 10 Modbus RS485 "Diagnostics" menu

3.5 "Diagnostic settings" submenu


Navigation  Diagnostics → Diag. settings

‣ Diagnostic settings

‣ Properties →  39

‣ Diagnostic configuration →  39

3.5.1 "Properties" submenu

Navigation  Diagnostics → Diag. settings → Properties

‣ Properties

Alarm delay →  39

Alarm delay 

Navigation  Diagnostics → Diag. settings → Properties → Alarm delay

Description Enter a duration for the alarm delay. When a diagnostic event of the "Alarm" category
occurs, the diagnostic message is not generated until the delay has elapsed.

User entry 0 to 60 s

3.5.2 "Diagnostic configuration" submenu

Navigation  Diagnostics → Diag. settings → Diag. config.

‣ Diagnostic configuration

‣ Sensor →  40

‣ Electronics →  40

‣ Configuration →  43

‣ Process →  43

Endress+Hauser 39
"Diagnostics" menu Proline Promag 10 Modbus RS485

"Sensor" submenu

Navigation  Diagnostics → Diag. settings → Diag. config. → Sensor

‣ Sensor

Assign behavior of diagnostic no. 043 →  40

Assign behavior of diagnostic no. 043 

Navigation  Diagnostics → Diag. settings → Diag. config. → Sensor → Diagnostic no. 043

Description Select behavior for diagnostic event "043 Sensor short circuit detected".

Selection • Off
• Alarm
• Warning
• Logbook entry only

Additional information Selection


• Off option
The diagnostic event is ignored and no diagnostic message is generated or logged.
• Alarm option
The device stops measuring. The signal outputs and totalizers assume the specified
alarm condition. A diagnostic message is generated.
• Warning option
The device continues measuring. The signal outputs and totalizers are not affected. A
diagnostic message is generated.
• Logbook entry only option
The device continues measuring. The diagnostic message is only displayed in the "Event
logbook" submenu and does not alternate with the standard operational information
displayed.

"Electronics" submenu

Navigation  Diagnostics → Diag. settings → Diag. config. → Electronics

‣ Electronics

Assign behavior of diagnostic no. 230 →  41

Assign behavior of diagnostic no. 231 →  41

Assign behavior of diagnostic no. 302 →  41

40 Endress+Hauser
Proline Promag 10 Modbus RS485 "Diagnostics" menu

Assign behavior of diagnostic no. 376 →  41

Assign behavior of diagnostic no. 377 →  42

Assign behavior of diagnostic no. 230 

Navigation  Diagnostics → Diag. settings → Diag. config. → Electronics → Diagnostic no. 230

Description Select behavior for diagnostic event "230 Date/time incorrect".

Selection • Alarm
• Warning
• Logbook entry only

Assign behavior of diagnostic no. 231 

Navigation  Diagnostics → Diag. settings → Diag. config. → Electronics → Diagnostic no. 231

Description Select behavior for diagnostic event "231 Date/time not available".

Selection • Alarm
• Warning
• Logbook entry only

Assign behavior of diagnostic no. 302 

Navigation  Diagnostics → Diag. settings → Diag. config. → Electronics → Diagnostic no. 302

Description Select behavior for diagnostic event "302 Device verification active".

Selection • Off
• Warning
• Logbook entry only

Assign behavior of diagnostic no. 376 

Navigation  Diagnostics → Diag. settings → Diag. config. → Electronics → Diagnostic no. 376

Description Select behavior for diagnostic event "376 Main electronics faulty".

Endress+Hauser 41
"Diagnostics" menu Proline Promag 10 Modbus RS485

Selection • Off
• Alarm
• Warning
• Logbook entry only

Additional information Selection


• Off option
The diagnostic event is ignored and no diagnostic message is generated or logged.
• Alarm option
The device stops measuring. The signal outputs and totalizers assume the specified
alarm condition. A diagnostic message is generated.
• Warning option
The device continues measuring. The signal outputs and totalizers are not affected. A
diagnostic message is generated.
• Logbook entry only option
The device continues measuring. The diagnostic message is only displayed in the "Event
logbook" submenu and does not alternate with the standard operational information
displayed.

Assign behavior of diagnostic no. 377 

Navigation  Diagnostics → Diag. settings → Diag. config. → Electronics → Diagnostic no. 377

Description Select behavior for diagnostic event "377 Sensor electronics (ISEM) faulty".

Selection • Off
• Alarm
• Warning
• Logbook entry only

Additional information Selection


• Off option
The diagnostic event is ignored and no diagnostic message is generated or logged.
• Alarm option
The device stops measuring. The signal outputs and totalizers assume the specified
alarm condition. A diagnostic message is generated.
• Warning option
The device continues measuring. The signal outputs and totalizers are not affected. A
diagnostic message is generated.
• Logbook entry only option
The device continues measuring. The diagnostic message is only displayed in the "Event
logbook" submenu and does not alternate with the standard operational information
displayed.

42 Endress+Hauser
Proline Promag 10 Modbus RS485 "Diagnostics" menu

"Configuration" submenu

Navigation  Diagnostics → Diag. settings → Diag. config. → Configuration

‣ Configuration

Assign behavior of diagnostic no. 441 →  43

Assign behavior of diagnostic no. 441 

Navigation  Diagnostics → Diag. settings → Diag. config. → Configuration → Diagnostic no. 441

Description Select behavior for diagnostic event "441 Current output faulty".

Selection • Off
• Alarm
• Warning
• Logbook entry only

Additional information Selection


• Off option
The diagnostic event is ignored and no diagnostic message is generated or logged.
• Alarm option
The device stops measuring. The signal outputs and totalizers assume the specified
alarm condition. A diagnostic message is generated.
• Warning option
The device continues measuring. The signal outputs and totalizers are not affected. A
diagnostic message is generated.
• Logbook entry only option
The device continues measuring. The diagnostic message is only displayed in the "Event
logbook" submenu and does not alternate with the standard operational information
displayed.

"Process" submenu

Navigation  Diagnostics → Diag. settings → Diag. config. → Process

‣ Process

Assign behavior of diagnostic no. 832 →  44

Assign behavior of diagnostic no. 833 →  44

Assign behavior of diagnostic no. 834 →  45

Assign behavior of diagnostic no. 835 →  45

Endress+Hauser 43
"Diagnostics" menu Proline Promag 10 Modbus RS485

Assign behavior of diagnostic no. 842 →  46

Assign behavior of diagnostic no. 937 →  46

Assign behavior of diagnostic no. 938 →  47

Assign behavior of diagnostic no. 961 →  47

Assign behavior of diagnostic no. 962 →  48

Assign behavior of diagnostic no. 832 

Navigation  Diagnostics → Diag. settings → Diag. config. → Process → Diagnostic no. 832

Description Select behavior for diagnostic event "832 Electronics temperature too high".

Selection • Off
• Alarm
• Warning
• Logbook entry only

Additional information Selection


• Off option
The diagnostic event is ignored and no diagnostic message is generated or logged.
• Alarm option
The device stops measuring. The signal outputs and totalizers assume the specified
alarm condition. A diagnostic message is generated.
• Warning option
The device continues measuring. The signal outputs and totalizers are not affected. A
diagnostic message is generated.
• Logbook entry only option
The device continues measuring. The diagnostic message is only displayed in the "Event
logbook" submenu and does not alternate with the standard operational information
displayed.

Assign behavior of diagnostic no. 833 

Navigation  Diagnostics → Diag. settings → Diag. config. → Process → Diagnostic no. 833

Description Select behavior for diagnostic event "833 Electronics temperature too low".

Selection • Off
• Alarm
• Warning
• Logbook entry only

44 Endress+Hauser
Proline Promag 10 Modbus RS485 "Diagnostics" menu

Additional information Selection


• Off option
The diagnostic event is ignored and no diagnostic message is generated or logged.
• Alarm option
The device stops measuring. The signal outputs and totalizers assume the specified
alarm condition. A diagnostic message is generated.
• Warning option
The device continues measuring. The signal outputs and totalizers are not affected. A
diagnostic message is generated.
• Logbook entry only option
The device continues measuring. The diagnostic message is only displayed in the "Event
logbook" submenu and does not alternate with the standard operational information
displayed.

Assign behavior of diagnostic no. 834 

Navigation  Diagnostics → Diag. settings → Diag. config. → Process → Diagnostic no. 834

Description Select event category (status signal) for diagnostic event "834 Process temperature too
high".

Selection • Off
• Alarm
• Warning
• Logbook entry only

Additional information Selection


• Off option
The diagnostic event is ignored and no diagnostic message is generated or logged.
• Alarm option
The device stops measuring. The signal outputs and totalizers assume the specified
alarm condition. A diagnostic message is generated.
• Warning option
The device continues measuring. The signal outputs and totalizers are not affected. A
diagnostic message is generated.
• Logbook entry only option
The device continues measuring. The diagnostic message is only displayed in the "Event
logbook" submenu and does not alternate with the standard operational information
displayed.

Assign behavior of diagnostic no. 835 

Navigation  Diagnostics → Diag. settings → Diag. config. → Process → Diagnostic no. 835

Description Select behavior for diagnostic event "835 Process temperature too low".

Selection • Off
• Alarm
• Warning
• Logbook entry only

Endress+Hauser 45
"Diagnostics" menu Proline Promag 10 Modbus RS485

Additional information Selection


• Off option
The diagnostic event is ignored and no diagnostic message is generated or logged.
• Alarm option
The device stops measuring. The signal outputs and totalizers assume the specified
alarm condition. A diagnostic message is generated.
• Warning option
The device continues measuring. The signal outputs and totalizers are not affected. A
diagnostic message is generated.
• Logbook entry only option
The device continues measuring. The diagnostic message is only displayed in the "Event
logbook" submenu and does not alternate with the standard operational information
displayed.

Assign behavior of diagnostic no. 842 

Navigation  Diagnostics → Diag. settings → Diag. config. → Process → Diagnostic no. 842

Description Select behavior for diagnostic event "842 Process value above limit".

Selection • Off
• Alarm
• Warning
• Logbook entry only

Additional information Selection


• Off option
The diagnostic event is ignored and no diagnostic message is generated or logged.
• Alarm option
The device stops measuring. The signal outputs and totalizers assume the specified
alarm condition. A diagnostic message is generated.
• Warning option
The device continues measuring. The signal outputs and totalizers are not affected. A
diagnostic message is generated.
• Logbook entry only option
The device continues measuring. The diagnostic message is only displayed in the "Event
logbook" submenu and does not alternate with the standard operational information
displayed.

Assign behavior of diagnostic no. 937 

Navigation  Diagnostics → Diag. settings → Diag. config. → Process → Diagnostic no. 937

Description Select behavior for diagnostic event "937 Sensor symmetry".

Selection • Off
• Alarm
• Warning
• Logbook entry only

46 Endress+Hauser
Proline Promag 10 Modbus RS485 "Diagnostics" menu

Additional information Selection


• Off option
The diagnostic event is ignored and no diagnostic message is generated or logged.
• Alarm option
The device stops measuring. The signal outputs and totalizers assume the specified
alarm condition. A diagnostic message is generated.
• Warning option
The device continues measuring. The signal outputs and totalizers are not affected. A
diagnostic message is generated.
• Logbook entry only option
The device continues measuring. The diagnostic message is only displayed in the "Event
logbook" submenu and does not alternate with the standard operational information
displayed.

Assign behavior of diagnostic no. 938 

Navigation  Diagnostics → Diag. settings → Diag. config. → Process → Diagnostic no. 938

Description Select behavior for diagnostic event "938 EMC interference".

Selection • Off
• Alarm
• Warning
• Logbook entry only

Additional information Selection


• Off option
The diagnostic event is ignored and no diagnostic message is generated or logged.
• Alarm option
The device stops measuring. The signal outputs and totalizers assume the specified
alarm condition. A diagnostic message is generated.
• Warning option
The device continues measuring. The signal outputs and totalizers are not affected. A
diagnostic message is generated.
• Logbook entry only option
The device continues measuring. The diagnostic message is only displayed in the "Event
logbook" submenu and does not alternate with the standard operational information
displayed.

Assign behavior of diagnostic no. 961 

Navigation  Diagnostics → Diag. settings → Diag. config. → Process → Diagnostic no. 961

Description Select behavior for diagnostic event "961 Electrode potential out of specification".

Selection • Off
• Alarm
• Warning
• Logbook entry only

Endress+Hauser 47
"Diagnostics" menu Proline Promag 10 Modbus RS485

Additional information Selection


• Off option
The diagnostic event is ignored and no diagnostic message is generated or logged.
• Alarm option
The device stops measuring. The signal outputs and totalizers assume the specified
alarm condition. A diagnostic message is generated.
• Warning option
The device continues measuring. The signal outputs and totalizers are not affected. A
diagnostic message is generated.
• Logbook entry only option
The device continues measuring. The diagnostic message is only displayed in the "Event
logbook" submenu and does not alternate with the standard operational information
displayed.

Assign behavior of diagnostic no. 962 

Navigation  Diagnostics → Diag. settings → Diag. config. → Process → Diagnostic no. 962

Description Select behavior for diagnostic event "962 Pipe empty".

Selection • Off
• Alarm
• Warning
• Logbook entry only

Additional information Selection


• Off option
The diagnostic event is ignored and no diagnostic message is generated or logged.
• Alarm option
The device stops measuring. The signal outputs and totalizers assume the specified
alarm condition. A diagnostic message is generated.
• Warning option
The device continues measuring. The signal outputs and totalizers are not affected. A
diagnostic message is generated.
• Logbook entry only option
The device continues measuring. The diagnostic message is only displayed in the "Event
logbook" submenu and does not alternate with the standard operational information
displayed.

48 Endress+Hauser
Proline Promag 10 Modbus RS485 "Application" menu

4 "Application" menu
Targeted optimization to the application – comprehensive device settings from sensor
technology to system integration for optimum application adaptation.

Navigation  Application

Application

‣ Measured values →  49

‣ System units →  53

‣ Totalizers →  58

‣ Sensor →  63

‣ Current output 1 →  74

‣ Communication →  85

4.1 "Measured values" submenu


Navigation  Application → Measured values

‣ Measured values

Mass flow →  49

Volume flow →  50

Conductivity →  50

Corrected conductivity →  50

Temperature →  51

‣ Totalizer →  51

Mass flow

Navigation  Application → Measured values → Mass flow

Description Displays the mass flow currently calculated.


Additional information:
The applicable unit of measure is specified in the "System units" submenu.

Endress+Hauser 49
"Application" menu Proline Promag 10 Modbus RS485

User interface Signed floating-point number

Volume flow

Navigation  Application → Measured values → Volume flow

Description Displays the volume flow currently measured.


Additional information:
The applicable unit of measure is specified in the "System units" submenu.

User interface Signed floating-point number

Conductivity

Navigation  Application → Measured values → Conductivity

Prerequisite Conductivity measurement is switched on in the Conductivity measurement parameter


(→  64).
Conductivity measurement is only optionally available: Under order code for
"Functionality", option D (extended transmitter) and order code for "Sensor option",
option CX (conductivity measurement)

Description Displays the conductivity currently measured.


Additional information:
The applicable unit of measure is specified in the "System units" submenu.

User interface Positive floating-point number

Corrected conductivity

Navigation  Application → Measured values → CorrConductivity

Prerequisite Conductivity measurement is switched on in the Conductivity measurement parameter


(→  64).
Conductivity measurement is only optionally available: Under order code for
"Functionality", option D (extended transmitter) and order code for "Sensor option",
option CX (conductivity measurement)

Description Displays the currently measured conductivity compensated for temperature.


Additional information:
The applicable unit of measure is specified in the "System units" submenu.

User interface Positive floating-point number

50 Endress+Hauser
Proline Promag 10 Modbus RS485 "Application" menu

Temperature

Navigation  Application → Measured values → Temperature

Prerequisite Temperature measurement is only optionally available for Promag H 10 (5HBB): Under
order code for "Functionality", option D (extended transmitter) and order code for "Sensor
option", option CI (medium temperature measurement)

Description Displays the medium temperature currently measured.


Additional information:
The applicable unit of measure is specified in the "System units" submenu.

User interface Positive floating-point number

4.1.1 "Totalizer" submenu

Navigation  Application → Measured values → Totalizer

‣ Totalizer

Totalizer value 1 to n →  51

Totalizer overflow 1 to n →  52

Totalizer value 1 to n 

Navigation  Application → Measured values → Totalizer → Totalizer val. 1 to n

Prerequisite A process variable has been selected in the Assign process variable parameter in the
Totalizer 1 to n submenu.

Description Displays the current totalizer counter.


Additional information:
Since the operating tool cannot display figures with more than 7 digits, the current counter
above this range equals the sum of the totalizer counter plus the overflow displayed for the
"Totalizer overflow " parameter.
Example for how to calculate the current totalizer counter when the value exceeds the 7
digit display range limit of the operating tool:
- Value of "Totalizer value " parameter: 1,968,457 m³
- Value of "Totalizer overflow " parameter: 1 × 107 m³ = 10,000,000 m³
- Current totalizer reading: 11,968,457 m³
In the event of an error, the totalizer behaves as specified in the "Failure mode" parameter.

User interface Signed floating-point number

Endress+Hauser 51
"Application" menu Proline Promag 10 Modbus RS485

Totalizer overflow 1 to n 

Navigation  Application → Measured values → Totalizer → Tot. overflow 1 to n

Prerequisite A process variable has been selected in the Assign process variable parameter in the
Totalizer 1 to n submenu.

Description Displays the current totalizer overflow.


Additional information:
If the current totalizer counter exceeds the operating tool's maximum numerical display
range of 7 digits, the amount above this range is expressed as an overflow. The current
totalizer counter therefore equals the sum of the overflow and the totalizer value displayed
in the "Totalizer value " parameter.
Example of how to calculate the current totalizer counter when the value exceeds the 7
digit display limit of the operating tool:
- Value of "Totalizer value " parameter: 1,968,457 m³
- Value of "Totalizer overflow " parameter: 1 × 10^7 m³ = 10,000,000 m³
- Current totalizer reading: 11,968,457 m³

User interface –32 000.0 to 32 000.0

52 Endress+Hauser
Proline Promag 10 Modbus RS485 "Application" menu

4.2 "System units" submenu


Navigation  Application → System units

‣ System units

Volume flow unit →  53

Volume unit →  54

Mass flow unit →  55

Mass unit →  55

Density unit →  56

Temperature unit →  56

Conductivity unit →  56

Volume flow unit 

Navigation  Application → System units → Volume flow unit

Description Select volume flow unit.

Endress+Hauser 53
"Application" menu Proline Promag 10 Modbus RS485

Selection SI units US units Imperial units


• cm³/s • af/s • gal/s (imp)
• cm³/min • af/min • gal/min (imp)
• cm³/h • af/h • gal/h (imp)
• cm³/d • af/d • gal/d (imp)
• dm³/s • ft³/s • Mgal/s (imp)
• dm³/min • ft³/min • Mgal/min (imp)
• dm³/h • ft³/h • Mgal/h (imp)
• dm³/d • ft³/d • Mgal/d (imp)
• m³/s • MMft³/s • bbl/s (imp;beer)
• m³/min • MMft³/min • bbl/min (imp;beer)
• m³/h • MMft³/h • bbl/h (imp;beer)
• m³/d • Mft³/d • bbl/d (imp;beer)
• ml/s • fl oz/s (us) • bbl/s (imp;oil)
• ml/min • fl oz/min (us) • bbl/min (imp;oil)
• ml/h • fl oz/h (us) • bbl/h (imp;oil)
• ml/d • fl oz/d (us) • bbl/d (imp;oil)
• l/s • gal/s (us)
• l/min • gal/min (us)
• l/h • gal/h (us)
• l/d • gal/d (us)
• hl/s • Mgal/s (us)
• hl/min • Mgal/min (us)
• hl/h • Mgal/h (us)
• hl/d • Mgal/d (us)
• Ml/s • bbl/s (us;liq.)
• Ml/min • bbl/min (us;liq.)
• Ml/h • bbl/h (us;liq.)
• Ml/d • bbl/d (us;liq.)
• bbl/s (us;beer)
• bbl/min (us;beer)
• bbl/h (us;beer)
• bbl/d (us;beer)
• bbl/s (us;oil)
• bbl/min (us;oil)
• bbl/h (us;oil)
• bbl/d (us;oil)
• bbl/s (us;tank)
• bbl/min (us;tank)
• bbl/h (us;tank)
• bbl/d (us;tank)
• kgal/s (us)
• kgal/min (us)
• kgal/h (us)
• kgal/d (us)

Volume unit 

Navigation  Application → System units → Volume unit

Description Select volume unit.

54 Endress+Hauser
Proline Promag 10 Modbus RS485 "Application" menu

Selection SI units US units Imperial units


• cm³ • af • gal (imp)
• dm³ • ft³ • Mgal (imp)
• m³ • Mft³ • bbl (imp;beer)
• ml • fl oz (us) • bbl (imp;oil)
•l • gal (us)
• hl • kgal (us)
• Ml Mega • Mgal (us)
• bbl (us;oil)
• bbl (us;liq.)
• bbl (us;beer)
• bbl (us;tank)

Mass flow unit 

Navigation  Application → System units → Mass flow unit

Description Select mass flow unit.

Selection SI units US units


• g/s • oz/s
• g/min • oz/min
• g/h • oz/h
• g/d • oz/d
• kg/s • lb/s
• kg/min • lb/min
• kg/h • lb/h
• kg/d • lb/d
• t/s • STon/s
• t/min • STon/min
• t/h • STon/h
• t/d • STon/d

Mass unit 

Navigation  Application → System units → Mass unit

Description Select mass unit.

Selection SI units US units


•g • oz
• kg • lb
•t • STon

Endress+Hauser 55
"Application" menu Proline Promag 10 Modbus RS485

Density unit 

Navigation  Application → System units → Density unit

Description Select density unit.

Selection SI units US units Imperial units


• g/cm³ • lb/ft³ • lb/gal (imp)
• g/m³ • lb/gal (us) • lb/bbl (imp;beer)
• kg/l • lb/bbl (us;liq.) • lb/bbl (imp;oil)
• kg/dm³ • lb/bbl (us;beer)
• kg/m³ • lb/bbl (us;oil)
• SD4°C • lb/bbl (us;tank)
• SD15°C
• SD20°C
• SG4°C
• SG15°C
• SG20°C

Temperature unit 

Navigation  Application → System units → Temperature unit

Prerequisite Temperature measurement is only optionally available for Promag H 10 (5HBB): Under
order code for "Functionality", option D (extended transmitter) and order code for "Sensor
option", option CI (medium temperature measurement)

Description Select temperature unit.

Selection SI units US units


• °C • °F
•K • °R

Conductivity unit 

Navigation  Application → System units → Conductiv. unit

Prerequisite Conductivity measurement is switched on in the Conductivity measurement parameter


(→  64).
Conductivity measurement is only optionally available: Under order code for
"Functionality", option D (extended transmitter) and order code for "Sensor option",
option CX (conductivity measurement)

Description Select conductivity unit.

56 Endress+Hauser
Proline Promag 10 Modbus RS485 "Application" menu

Selection SI units
• nS/cm
• µS/cm
• µS/m
• µS/mm
• mS/m
• mS/cm
• S/cm
• S/m
• kS/m
• MS/m

Endress+Hauser 57
"Application" menu Proline Promag 10 Modbus RS485

4.3 "Totalizers" submenu


Navigation  Application → Totalizers

‣ Totalizers

‣ Totalizer handling →  58

‣ Totalizer 1 to n →  58

4.3.1 "Totalizer handling" submenu

Navigation  Application → Totalizers → Totalizer

‣ Totalizer handling

Reset all totalizers →  58

Reset all totalizers

Navigation  Application → Totalizers → Totalizer → Reset all tot.

Description Reset all totalizers to "0" and restart the totaling process. All flow quantities thus far
totalized are thereby deleted.

Selection • Cancel
• Reset + totalize

4.3.2 "Totalizer 1 to n" submenu

Navigation  Application → Totalizers → Totalizer 1 to n

‣ Totalizer 1 to n

Assign process variable →  59

Unit totalizer 1 to n →  59

Totalizer operation mode →  60

Control Totalizer 1 to n →  60

58 Endress+Hauser
Proline Promag 10 Modbus RS485 "Application" menu

Preset value 1 to n →  61

Failure mode →  61

Assign process variable 

Navigation  Application → Totalizers → Totalizer 1 to n → Assign variable

Description Select process variable for totalizer.


Additional information:
If the option selected is changed, the device resets the totalizer to "0".

Selection • Off
• Volume flow
• Mass flow

Unit totalizer 1 to n 

Navigation  Application → Totalizers → Totalizer 1 to n → Unit totalizer 1 to n

Prerequisite A process variable has been selected in the Assign process variable parameter in the
Totalizer 1 to n submenu.

Description Select process variable totalizer unit.

Selection SI units US units


• g* • oz *
• kg * • lb *
• t* • STon *

* Visibility depends on order options or device settings

or

SI units US units Imperial units


• cm³ * • af * • gal (imp) *
• dm³ * • ft³ * • Mgal (imp) *
• m³ * • Mft³ * • bbl (imp;beer) *
• ml * • fl oz (us) * • bbl (imp;oil) *
• l* • gal (us) *
• hl * • kgal (us) *
• Ml Mega * • Mgal (us) *
• bbl (us;liq.) *
• bbl (us;beer) *
• bbl (us;oil) *
• bbl (us;tank) *

* Visibility depends on order options or device settings

Endress+Hauser 59
"Application" menu Proline Promag 10 Modbus RS485

or

Other units
None *

* Visibility depends on order options or device settings

Additional information Description


The unit is selected separately for each totalizer. The unit is independent of the option
selected in the System units submenu (→  53).

Selection
The selection is dependent on the process variable selected in the Assign process variable
parameter (→  13).

Totalizer operation mode 

Navigation  Application → Totalizers → Totalizer 1 to n → Operation mode

Prerequisite A process variable has been selected in the Assign process variable parameter in the
Totalizer 1 to n submenu.

Description Select totalizer calculation mode.

Selection • Net flow total


• Forward flow total
• Reverse flow total

Additional information Selection


• Net flow total option
The flow values in the forward and reverse flow directions are totalized and netted
against each other. Net flow is recorded in the flow direction.
• Forward flow total option
Only the flow in the forward flow direction is totalized.
• Reverse flow total option
Only the flow in the reverse flow direction is totalized (= reverse flow quantity).

Control Totalizer 1 to n

Navigation  Application → Totalizers → Totalizer 1 to n → Control Tot. 1 to n

Prerequisite A process variable has been selected in the Assign process variable parameter in the
Totalizer 1 to n submenu.

Description Operate the totalizer.

60 Endress+Hauser
Proline Promag 10 Modbus RS485 "Application" menu

Selection • Totalize
• Reset + hold
• Preset + hold
• Reset + totalize
• Hold

Additional information Selection


• Totalize option
The totalizer is started or continues running.
• Reset + hold option
The totaling process is stopped and the totalizer is reset to "0".
• Preset + hold option
The totaling process is stopped and the totalizer is set to the start value specified in the
"Preset value " parameter.
• Reset + totalize option
The totalizer is reset to "0" and the totaling process is restarted.
• Hold option
Totalizing is stopped.

Preset value 1 to n

Navigation  Application → Totalizers → Totalizer 1 to n → Preset value 1 to n

Prerequisite A process variable has been selected in the Assign process variable parameter in the
Totalizer 1 to n submenu.

Description Specify start value for totalizer.

User entry Signed floating-point number

Additional information Description


The unit of the selected process variable is specified for the totalizer in the Unit totalizer
parameter (→  13).

Example
This configuration is suitable for applications such as iterative filling processes with a fixed
batch quantity.

Failure mode 

Navigation  Application → Totalizers → Totalizer 1 to n → Failure mode

Prerequisite A process variable has been selected in the Assign process variable parameter in the
Totalizer 1 to n submenu.

Description Specify how the totalizer should behave in the event of a device alarm.
Additional information:
The failsafe mode that applies to any other totalizers or outputs is specified separately in
other parameters and is not impacted by this setting.

Endress+Hauser 61
"Application" menu Proline Promag 10 Modbus RS485

Selection • Stop
• Actual value
• Last valid value

Additional information Selection


• Stop option
The totalizer is stopped in the event of a device alarm.
• Actual value option
The totalizer continues to totalize based on the current value measured; the device alarm
is ignored.
• Last valid value option
The totalizer continues to totalize based on the last valid value measured before the
device alarm occurred.

62 Endress+Hauser
Proline Promag 10 Modbus RS485 "Application" menu

4.4 "Sensor" submenu


Navigation  Application → Sensor

‣ Sensor

‣ Process parameters →  63

‣ Low flow cut off →  66

‣ Empty pipe detection →  67

‣ Sensor adjustment →  69

‣ Calibration →  70

‣ Electrode cleaning cycle →  72

4.4.1 "Process parameters" submenu

Navigation  Application → Sensor → Process param.

‣ Process parameters

Flow damping →  64

Flow override →  64

Conductivity measurement →  64

Conductivity temperature coefficient →  65

Conductivity damping time →  65

Temperature damping time →  66

Fixed density →  66

Endress+Hauser 63
"Application" menu Proline Promag 10 Modbus RS485

Flow damping 

Navigation  Application → Sensor → Process param. → Flow damping

Description Enter value for damping of the flow measured value in order to reduce the variability of
the flow measured value when exposed to interference.
Additional information:
The depth of the flow filter is determined by this setting. As the filter depth increases, so
does the reaction time of the device.
- Value = 0: No damping. Damping of 0 is not recommended, as the measuring signal is
then so noisy that it is almost impossible to perform a measurement.
- Value > 0: Damping increases
Optimal damping depends on the measuring period.
Damping impacts the following measuring device variables:
- Outputs
- Low flow cut off
- Totalizers

User entry 0 to 15

Flow override 

Navigation  Application → Sensor → Process param. → Flow override

Description Stops the measuring process. Can be used for example when cleaning the pipeline.

Selection • Off
• On

Additional information Selection


"On" option
Activates flow override. The diagnostic message "453 Flow override active" is generated.
Additional information:
Output values:
- Temperature: Measurement continues
- Totalizers 1 to 3: No longer totalize

Conductivity measurement 

Navigation  Application → Sensor → Process param. → Conduct. measur.

Prerequisite Conductivity measurement is only optionally available: Under order code for
"Functionality", option D (extended transmitter) and order code for "Sensor option", option
CX (conductivity measurement)

64 Endress+Hauser
Proline Promag 10 Modbus RS485 "Application" menu

Description Switch conductivity measurement on or off.


Additional information:
To be able to measure conductivity, the medium must have a minimum conductivity of 5
μS/cm.

Selection • Off
• On

Conductivity temperature coefficient 

Navigation  Application → Sensor → Process param. → Cond. [Link]

Prerequisite Conductivity measurement is switched on in the Conductivity measurement parameter


(→  64).
Conductivity measurement is only optionally available: Under order code for
"Functionality", option D (extended transmitter) and order code for "Sensor option",
option CX (conductivity measurement)

Description Enter the temperature coefficient for conductivity.

User entry Signed floating-point number

Conductivity damping time 

Navigation  Application → Sensor → Process param. → ConductDampTime

Prerequisite Conductivity measurement is switched on in the Conductivity measurement parameter


(→  64).
Conductivity measurement is only optionally available: Under order code for
"Functionality", option D (extended transmitter) and order code for "Sensor option",
option CX (conductivity measurement)

Description Enter time constant for conductivity damping (PT1 element):


- Value = 0: No damping
- Value > 0: Damping increases
Additional information:
Damping is implemented by means of a proportional transmission behavior with first
order delay (PT1 element).

User entry 0 to 999.9 s

Endress+Hauser 65
"Application" menu Proline Promag 10 Modbus RS485

Temperature damping time 

Navigation  Application → Sensor → Process param. → TempDampingTime

Prerequisite Temperature measurement is only optionally available for Promag H 10 (5HBB): Under
order code for "Functionality", option D (extended transmitter) and order code for "Sensor
option", option CI (medium temperature measurement)

Description Enter time constant for damping the temperature value.

User entry 0 to 999.9 s

Fixed density 

Navigation  Application → Sensor → Process param. → Fixed density

Description Enter a fixed value for the density.


Additional information:
The applicable unit of measure is specified in the "System units" submenu.

User entry Positive floating-point number

4.4.2 "Low flow cut off" submenu

Navigation  Application → Sensor → Low flow cut off

‣ Low flow cut off

Low flow cut off →  66

On value low flow cutoff →  67

Off value low flow cutoff →  67

Low flow cut off 

Navigation  Application → Sensor → Low flow cut off → Low flow cut off

Description Select process variable for low flow cut off to activate low flow cut off.

Selection • Off
• Volume flow
• Mass flow

66 Endress+Hauser
Proline Promag 10 Modbus RS485 "Application" menu

Additional information Description

Q 2 2

4
H
3
t
1 A 1 A

A0012887

Q Flow
t Time
H Hysteresis
A Low flow cut off active
1 Low flow cut off is activated
2 Low flow cut off is deactivated
3 On-value entered
4 Off-value entered

On value low flow cutoff 

Navigation  Application → Sensor → Low flow cut off → On value

Description Enter on value to switch on low flow cut off.


Value = 0: No low flow cut off
Value > 0: Low flow cut off is activated

User entry Positive floating-point number

Off value low flow cutoff 

Navigation  Application → Sensor → Low flow cut off → Off value

Description Enter off value to switch off low flow cut off. The off value is entered as a positive
hysteresis with respect to the on value.

User entry 0 to 100.0 %

4.4.3 "Partially filled pipe detection" submenu

Navigation  Application → Sensor → Partial pipe det

‣ Empty pipe detection

Empty pipe detection →  68

Endress+Hauser 67
"Application" menu Proline Promag 10 Modbus RS485

New adjustment →  68

Empty pipe adjust value →  68

Full pipe adjust value →  69

Measured value EPD →  69

Empty pipe detection 

Navigation  Application → Sensor → Empty pipe det. → Empty pipe det.

Description Switch empty pipe detection on or off. Switch on empty pipe detection to detect a partially
filled or empty measuring tube.

Selection • Off
• On

New adjustment 

Navigation  Application → Sensor → Empty pipe det. → New adjustment

Description Select empty pipe or full pipe adjustment to perform a new adjustment. To adjust empty
pipe detection, perform the empty pipe adjustment first and then the full pipe adjustment.
Additional information:
The measuring device is pre-adjusted at production using water (approx. 300 μS/cm). For
liquids that deviate from this conductivity, a new empty pipe and full pipe adjustment must
be performed on site.

Selection • Cancel
• Empty pipe adjust
• Full pipe adjust

Empty pipe adjust value 

Navigation  Application → Sensor → Empty pipe det. → Empty pipe value

Description Displays adjustment value when the measuring tube is empty.


NOTE
Users logged on in the Service role have write access!

User interface Positive floating-point number

68 Endress+Hauser
Proline Promag 10 Modbus RS485 "Application" menu

Full pipe adjust value 

Navigation  Application → Sensor → Empty pipe det. → Full pipe value

Description Displays adjustment value when the measuring tube is full.


NOTE
Users logged on in the Service role have write access!

User interface Positive floating-point number

Measured value EPD

Navigation  Application → Sensor → Empty pipe det. → Meas. value EPD

Description Displays the value currently measured for empty pipe detection.

User interface Positive floating-point number

4.4.4 "Sensor adjustment" submenu

Navigation  Application → Sensor → Sensor adjustm.

‣ Sensor adjustment

Installation direction →  69

Integration time →  70

Measuring period →  70

Installation direction 

Navigation  Application → Sensor → Sensor adjustm. → Install. direct.

Description Select sign of flow direction

Selection • Forward flow


• Reverse flow

Endress+Hauser 69
"Application" menu Proline Promag 10 Modbus RS485

Integration time 

Navigation  Application → Sensor → Sensor adjustm. → Integration time

Description Displays the duration of an integration cycle.


NOTE
Users logged on in the Service role have write access!

User interface 1 to 65 ms

Measuring period 

Navigation  Application → Sensor → Sensor adjustm. → Measuring period

Description Displays the duration of a full measuring period.


Additional information:
The measuring period is the time span during which the excitation of the magnetic field
takes place and a measuring point is created.
NOTE
Users logged on in the Service role have write access!

User interface 0 to 1 000 ms

4.4.5 "Calibration" submenu

Navigation  Application → Sensor → Calibration

‣ Calibration

Nominal diameter →  70

Calibration factor →  71

Zero point →  71

Conductivity calibration factor →  71

Nominal diameter

Navigation  Application → Sensor → Calibration → Nominal diameter

Description Shows the nominal diameter of the sensor.

70 Endress+Hauser
Proline Promag 10 Modbus RS485 "Application" menu

User interface Character string comprising numbers, letters and special characters

Calibration factor

Navigation  Application → Sensor → Calibration → Cal. factor

Description Displays the current calibration factor for the flow rate measuring sensor.
Additional information:
The factory setting for the calibration factor can be found on the sensor's nameplate.

User interface Positive floating-point number

Zero point 

Navigation  Application → Sensor → Calibration → Zero point

Description Displays the zero point correction value for the sensor.
NOTE
Users logged on in the Service role have write access!

User interface Signed floating-point number

Conductivity calibration factor 

Navigation  Application → Sensor → Calibration → Cond. cal. fact.

Prerequisite Conductivity measurement is switched on in the Conductivity measurement parameter


(→  64).
Conductivity measurement is only optionally available: Under order code for
"Functionality", option D (extended transmitter) and order code for "Sensor option",
option CX (conductivity measurement)

Description Displays calibration factor for conductivity measurement.


NOTE
Users logged on in the Service role have write access!

User interface 0.01 to 10 000

Endress+Hauser 71
"Application" menu Proline Promag 10 Modbus RS485

4.4.6 "Electrode cleaning cycle" submenu

Navigation  Application → Sensor → Elec. clean cycl

‣ Electrode cleaning cycle

Electrode cleaning cycle →  72

ECC duration →  72

ECC recovery time →  72

ECC interval →  73

ECC polarity →  73

Electrode cleaning cycle 

Navigation  Application → Sensor → Elec. clean cycl → Elec. clean cycl

Description Switch electrode cleaning on or off.

Selection • Off
• On

ECC duration 

Navigation  Application → Sensor → Elec. clean cycl → ECC duration

Description Enter the duration of the cleaning cycle.

User entry 0.01 to 30 s

ECC recovery time 

Navigation  Application → Sensor → Elec. clean cycl → ECC recov. time

Description Specify a timespan for recovery after a cleaning cycle has completed to prevent
interference with the signal outputs. The output signal values will be frozen for the
duration of the recovery.

User entry 1 to 600 s

72 Endress+Hauser
Proline Promag 10 Modbus RS485 "Application" menu

ECC interval 

Navigation  Application → Sensor → Elec. clean cycl → ECC interval

Description Specify the duration of the interval between one cleaning cycle and the next.

User entry 0.5 to 168 h

ECC polarity

Navigation  Application → Sensor → Elec. clean cycl → ECC polarity

Description Displays the setting for the electrode cleaning polarity.


Additional information:
The polarity depends on the material of the electrodes:
- Platinum: Negative
- Tantalum, Alloy C22, stainless steel: Positive

User interface • Positive


• Negative

Endress+Hauser 73
"Application" menu Proline Promag 10 Modbus RS485

4.5 "Current output" submenu


Navigation  Application → [Link] 1

‣ Current output 1

Process variable current output →  74

Measuring mode current output →  75

Current range output →  79

Fixed current →  80

Lower range value output →  80

Upper range value output →  82

Damping current output →  82

Failure behavior current output →  83

Failure current →  83

Output current 1 →  84

Process variable current output 

Navigation  Application → [Link] 1 → [Link]. outp

Description Select process variable for current output

Selection • Off *
• Mass flow
• Conductivity *
• Corrected conductivity *
• Volume flow
• Temperature *
• Noise *
• Coil current shot time *

* Visibility depends on order options or device settings

74 Endress+Hauser
Proline Promag 10 Modbus RS485 "Application" menu

Measuring mode current output 

Navigation  Application → [Link] 1 → [Link] outp

Prerequisite A process variable is selected in the Process variable current output parameter
(→  20).

Description Select the measuring mode for the output.

Selection • Forward flow


• Forward/Reverse flow *
• Reverse flow compensation

* Visibility depends on order options or device settings

Endress+Hauser 75
"Application" menu Proline Promag 10 Modbus RS485

Additional information Selection


• Forward flow option
The current output signal is proportional to the measured value for the process variable
assigned.
Additional information:
- The lower limit value ("Lower range value output " parameter) and the upper limit value
("Upper range value output " parameter) of the measured value range do not have to have
the same algebraic sign, i.e. the lower limit value can be negative and the upper limit
value positive.
- If the measured value lies outside the scaled measured value range, diagnostic message
"441 Current output faulty" is generated.
• Forward/Reverse flow option
The current output outputs the absolute value for the assigned process variable
(reflection across the lower limit value of the measured value range).
Additional information:
- The lower limit value ("Lower range value output " parameter) and the upper limit value
("Upper range value output " parameter) of the measured value range must have the
same algebraic sign.
- If the absolute value exceeds the upper limit value of the measured value range,
diagnostic message "441 Current output faulty" is generated.
- This setting is generally only used for flow-related process variables.
• Reverse flow compensation option
The current output signal is proportional to the measured value for the process variable
assigned.
Additional information:
- The lower limit value ("Lower range value output " parameter) and the upper limit value
("Upper range value output " parameter) of the measured value range do not have to have
the same algebraic sign, i.e. the lower limit value can be negative and the upper limit
value positive.
- Reverse flow (a measured value below the lower limit value of the measured value
range) is stored in a buffer and processed after a maximum delay of 60 s with the next
forward flow.
- When the flow exceeds the maximum value or the reverse flow stored in the buffer
cannot be processed within approx. 60 s, diagnostic message "441 Current output faulty"
is generated.
- This option is used e.g. to compensate intermittent reverse flow, which may occur in
connection with positive displacement pumps as a result of wear and tear or high
viscosity.
- There is no flow damping with this setting.

1. Examples of the behavior of the current output


Defined measuring range: lower range value and upper range value with the same
algebraic sign.

I [mA]

20

4
0 Q
1 2
A0028084

I Current
Q Flow
1 Lower range value (value assigned to 0/4 mA current)
2 Upper range value (value assigned to 20 mA current)

76 Endress+Hauser
Proline Promag 10 Modbus RS485 "Application" menu

With the following flow response:

A0028091

Q Flow
t Time

With the Forward flow option


The current output signal is proportional to the process variable assigned. The flow
components outside the scaled measuring range are not taken into account for signal
output:.

I [mA]

t
A0028092

I Current
t Time

With the Forward/Reverse flow option


The current output signal is independent of the direction of flow.

I [mA]

A0028093

I Current
t Time

With the Reverse flow compensation option


Flow components outside the measuring range are buffered, balanced and output after a
maximum delay of 60 s.

Endress+Hauser 77
"Application" menu Proline Promag 10 Modbus RS485

I [mA]

A
t
S
S=A
A0028094

I Current
t Time
S Flow components saved
A Balancing of saved flow components

2. Examples of the behavior of the current output


Defined measuring range: lower range value and upper range value with different
algebraic signs.

I [mA]

20

4
0 Q
0
1 2
A0028095

I Current
Q Flow
1 Lower range value (value assigned to 0/4 mA current)
2 Upper range value (value assigned to 20 mA current)

With flow a (—) outside, b (- -) inside the measuring range:

Q
1
+
0 t
-
2
a=
b=
A0028098

Q Flow
t Time
a Lower range value (value assigned to 0/4 mA current)
b Upper range value (value assigned to 20 mA current)

With the Forward flow option


• a (—): The flow components outside the scaled measuring range cannot be taken into
account for signal output. The diagnostic message S441 Current output 1 to n
diagnostic message is displayed.
• b (- -): The current output signal is proportional to the process variable assigned.

78 Endress+Hauser
Proline Promag 10 Modbus RS485 "Application" menu

I [mA]

t
a=
b=
A0028100

I Current
t Time

With the Forward/Reverse flow option


This option cannot be selected here since the values for the 20 mA value parameter
(→  22) and 20 mA value parameter (→  22) have different algebraic signs.
With the Reverse flow compensation option
Flow components outside the measuring range are buffered, balanced and output after a
maximum delay of 60 s.

I [mA]

t
S
S=A
A0028101

I Current
t Time
S Flow components saved
A Balancing of saved flow components

Current range output 

Navigation  Application → [Link] 1 → [Link] out

Description Select the current range for the measured value output and the upper and lower fault
condition signal level.
Additional information:
- The measured value range is specified in the "Lower range value output " parameter and
the "Upper range value output " parameter.
- If the measured value lies outside the scaled measured value range, diagnostic message
"441 Current output faulty" is generated.
- In the event of a device alarm, the current output adopts the behavior specified in the
"Failure behavior current output " parameter.

Selection • 4...20 mA NE (3.8...20.5 mA)


• 4...20 mA US (3.9...20.8 mA)
• 4...20 mA (4... 20.5 mA)
• Fixed value

Endress+Hauser 79
"Application" menu Proline Promag 10 Modbus RS485

Additional information Selection


• 4...20 mA NE (3.8...20.5 mA) option
Select this option to set the current range in accordance with NAMUR recommendation
NE43.
• Fixed value option
Select this option to set the current output to a current value instead of a range.

The current value is defined in the Fixed current parameter (→  23).


The graphic shows the relationship between the current range for the output of the
process value and the lower and upper alarm levels:

2 1 3

I [mA]
A0034351

1 Current range for process value


2 Lower level for signal on alarm
3 Upper level for signal on alarm

Selection (current range for process value) Lower level for signal on Upper level for signal on
alarm alarm

4...20 mA NE (3.8...20.5 mA) < 3.6 mA > 21.5 mA

4...20 mA US (3.9...20.8 mA)

4...20 mA (4... 20.5 mA)

Fixed current 

Navigation  Application → [Link] 1 → Fixed current

Prerequisite In the Current range output parameter in the Current output 1 submenu, the Fixed
value option is selected.

Description Enter the value for the "Fixed value" option.

User entry 3.59 to 21.5 mA

Lower range value output 

Navigation  Application → [Link] 1 → [Link] outp

Prerequisite In the Current range output parameter, one of the following options is selected:
• 4...20 mA NE (3.8...20.5 mA)
• 4...20 mA US (3.9...20.8 mA)
• 4...20 mA (4... 20.5 mA)

80 Endress+Hauser
Proline Promag 10 Modbus RS485 "Application" menu

Description Enter lower range value for the measured value range.
Additional information:
- Depending on the setting selected for the "Measuring mode current output " parameter,
the value specified for this parameter and the "Upper range value output " parameter must
have the same algebraic sign or not.
- As a rule, the lower range value is scaled to be lower than the upper range value. As a
result, the behavior of the current output is proportional to the process variable assigned.
If the lower range value is scaled to be higher than the upper range value, then the
behavior of the current output will be inversely proportional to the process variable
assigend.

User entry Signed floating-point number

Additional information Examples of the behavior, depending on the option selected in the Measuring mode
current output parameter (→  75).

Example: Measuring mode with "Forward flow" option


• Lower range value output parameter (→  21) = not equal to zero flow (e.g. –250
m3/h)
• Upper range value output parameter (→  22) = not equal to zero flow (e.g. +750
m3/h)
• Calculated current value = 8 mA at zero flow

I [mA]
20
8
4
Q
-250 0 +750
1 1
A0013757

Q Flow
I Current
1 Measuring range is exceeded or undershot

The linear operational range of the measuring device is defined by the values entered for
the Lower range value output parameter (→  21) and Upper range value output
parameter (→  22), and by the selected current range.

Example: Measuring mode with the "Forward/Reverse flow" option

I [mA]

20

4
0 Q
0
3 1 2
A0013758

Q Flow
I Current
1 Value assigned to 0/4 mA current
2 Forward flow
3 Reverse flow

Endress+Hauser 81
"Application" menu Proline Promag 10 Modbus RS485

The current output signal is independent of the direction of flow (absolute amount of the
measured variable). The values for the Lower range value output parameter (→  21)
and Upper range value output parameter (→  22) must have the same algebraic sign.
The value for the Upper range value output parameter (→  22) (e.g. reverse flow)
corresponds to the mirrored value for the Upper range value output parameter (→  22)
(e.g. forward flow).

Example: Measuring mode with the "Reverse flow compensation" option


If flow is characterized by severe fluctuations (e.g. when using reciprocating pumps), flow
components outside the measuring range are buffered, balanced and output after a
maximum delay of 60 s.

Upper range value output 

Navigation  Application → [Link] 1 → [Link] outp

Prerequisite In the Current range output parameter, one of the following options is selected:
• 4...20 mA NE (3.8...20.5 mA)
• 4...20 mA US (3.9...20.8 mA)
• 4...20 mA (4... 20.5 mA)

Description Enter upper range value for the measured value range.

User entry Signed floating-point number

Additional information Examples of the behavior, depending on the option selected in the Measuring mode
current output parameter: Lower range value output parameter (→  21):

Damping current output 

Navigation  Application → [Link] 1 → [Link]

Prerequisite A process variable is selected in the Process variable current output parameter and one
of the following options is selected in the Current range output parameter:
• 4...20 mA NE (3.8...20.5 mA)
• 4...20 mA US (3.9...20.8 mA)
• 4...20 mA (4... 20.5 mA)

Description Enter time constant (PT1 element) to set the reaction time of the output signal to
fluctuations in the measured value caused by process conditions.
Additional information:
- The smaller the time constant the faster the output reacts to fluctuations in the
measured value.
- If the time constant is 0, damping is deactivated.

User entry 0.0 to 999.9 s

82 Endress+Hauser
Proline Promag 10 Modbus RS485 "Application" menu

Failure behavior current output 

Navigation  Application → [Link] 1 → [Link]

Prerequisite A process variable is selected in the Process variable current output parameter and one
of the following options is selected in the Current range output parameter:
• 4...20 mA NE (3.8...20.5 mA)
• 4...20 mA US (3.9...20.8 mA)
• 4...20 mA (4... 20.5 mA)

Description Specify how the output should behave in the event of a device alarm.

Selection • Min.
• Max.
• Last valid value
• Actual value
• Fixed value

Additional information Selection


• Min. option
The current output outputs the lower fault condition signal level for the specified current
range.
Additional information:
The current range is specified in the "Current range output " parameter.
• Max. option
The current output outputs the upper fault condition signal level for the specified current
range.
Additional information:
The current range is specified in the "Current range output " parameter.
• Last valid value option
The current output outputs the last valid value measured before the device alarm
occurred.
• Actual value option
The current output outputs the flow value currently measured. The device alarm is
ignored.
• Fixed value option
The current output outputs the value specified.
Additional information:
The value is specified in the "Failure current " parameter.

Failure current 

Navigation  Application → [Link] 1 → Fail. current

Prerequisite In the Failure behavior current output parameter in the Current output 1 submenu, the
Fixed value option is selected.

Description Enter the value for the "Fixed value" option in the "Failure behavior current output "
parameter.

User entry 3.59 to 21.5 mA

Endress+Hauser 83
"Application" menu Proline Promag 10 Modbus RS485

Output current

Navigation  Application → [Link] 1 → Output curr. 1

Description Displays the current value currently calculated.

User interface 3.59 to 21.5 mA

84 Endress+Hauser
Proline Promag 10 Modbus RS485 "Application" menu

4.6 " Communication" submenu


Navigation  Application → Communication

‣ Communication

‣ Modbus configuration →  85

‣ Modbus data map →  88

‣ Modbus information →  89

4.6.1 "Modbus configuration" submenu

Navigation  Application → Communication → Modbus config.

‣ Modbus configuration

Bus address →  85

Baudrate →  86

Parity →  86

Byte order →  87

Telegram delay →  87

Failure mode →  87

Fieldbus writing access →  88

Bus address 

Navigation  Application → Communication → Modbus config. → Bus address

Description Enter device address.

User entry 1 to 247

Endress+Hauser 85
"Application" menu Proline Promag 10 Modbus RS485

Baudrate 

Navigation  Application → Communication → Modbus config. → Baudrate

Description Define data transfer speed.

Selection • 1200 BAUD


• 2400 BAUD
• 4800 BAUD
• 9600 BAUD
• 19200 BAUD
• 38400 BAUD
• 57600 BAUD
• 115200 BAUD

Parity 

Navigation  Application → Communication → Modbus config. → Parity

Description Select parity bits.


Additional information:
"ASCII" picklist option:
- 0 = "Even" option
- 1 = "Odd" option
"RTU" picklist option:
- 0 = "Even" option
- 1 = "Odd" option
- 2 = "No parity bit/1 stop bit" option
- 3 = "No parity bit/2 stop bits" option

Selection • Odd
• Even
• None / 1 stop bit
• None / 2 stop bits

86 Endress+Hauser
Proline Promag 10 Modbus RS485 "Application" menu

Byte order 

Navigation  Application → Communication → Modbus config. → Byte order

Description Select byte transmission sequence. The transmission sequence must be coordinated with
the Modbus master.
Additional information:
The byte sequence is not standardized by the Modbus protocol. However, if the host
system and the measuring device do not use the same byte sequence, correct data
exchange is not possible.
Changing the byte sequence in the host system often requires extensive knowledge and
significant programming effort. This parameter can be used to keep the standard settings
of the host system, while adjusting the byte sequence on the measuring device by means
of trial and error. If it is not possible to achieve correct data exchange in this manner, then
it is the host system's settings for the byte sequence that must be modified.

Selection • 0-1-2-3
• 3-2-1-0
• 1-0-3-2
• 2-3-0-1

Telegram delay 

Navigation  Application → Communication → Modbus config. → Telegram delay

Description Enter a delay time after which the measuring device replies to the request telegram of the
Modbus master. This is to enable communication with slow Modbus RS485 masters.

User entry 0 to 100 ms

Failure mode 

Navigation  Application → Communication → Modbus config. → Failure mode

Description Select the preferred Modbus communication output mode for the measured value, when a
diagnostic event of the category specified in the "Assign diagnostic behavior" parameter
occurs.

Selection • NaN value


• Last valid value

Additional information Selection


• NaN value option
The device outputs the NaN value ("Not a number" value).
• Last valid value option
The device displays the last valid measured value before the issue occurred.

Endress+Hauser 87
"Application" menu Proline Promag 10 Modbus RS485

Fieldbus writing access

Navigation  Application → Communication → Modbus config. → [Link].

Description Restrict access to the measuring device via Fieldbus.


Additional information:
Once read and/or write protection has been enabled, this parameter can only be accessed
and reset via local operation. Access via an operating tool is no longer possible.
NOTE
The cyclical transmission of measured values to the higher-order system is not impacted
by these restrictions and always guaranteed!

Selection • Read + write


• Read only

4.6.2 "Modbus data map" submenu

Navigation  Application → Communication → Modbus data map

‣ Modbus data map

Scan list register 0 to 15 →  88

Scan list register 0 to 15 

Navigation  Application → Communication → Modbus data map → Scan list reg.0 to 15

Description Enter the scan list register.


Additional information:
By entering the register address (1-based), it is possible to group up to 16 device
parameters, which thereby are assigned to the scan list registers 0 to 15. The data
corresponding to the device parameters assigned is read out via the register addresses
5051 to 5081.

User entry 0 to 65 535

88 Endress+Hauser
Proline Promag 10 Modbus RS485 "Application" menu

4.6.3 "Modbus information" submenu

Navigation  Application → Communication → Modbus info

‣ Modbus information

Device ID →  89

Device revision →  89

Device ID

Navigation  Application → Communication → Modbus info → Device ID

Description Displays the device ID to identify the measuring device.

User interface 0 to 65 535

Device revision

Navigation  Application → Communication → Modbus info → Device revision

Description Displays device revision.

User interface 0 to 65 535

Endress+Hauser 89
"System" menu Proline Promag 10 Modbus RS485

5 "System" menu
Overall device management and security settings – management of system settings and
adaption to operational requirements.

Navigation  System

System

‣ Device management →  91

‣ User management →  93

‣ Connectivity →  96

‣ Date/time →  97

‣ Information →  99

‣ Display →  104

‣ Software configuration →  108

90 Endress+Hauser
Proline Promag 10 Modbus RS485 "System" menu

5.1 "Device management" submenu


Navigation  System → Device manag.

‣ Device management

Device tag →  91

Locking status →  91

Configuration counter →  92

Device reset →  92

Device tag 

Navigation  System → Device manag. → Device tag

Description Enter a unique designation for the measuring point to be able to easily identify it within
the plant.

User entry Character string comprising numbers, letters and special characters (32)

Locking status

Navigation  System → Device manag. → Locking status

Description Indicates the write protection with the highest priority that is currently active.

User interface • Hardware locked


• Temporarily locked

Additional information User interface


• Hardware locked option
The DIP switch for the hardware lock is enabled. As a result write access to the
parameters is locked.
• Temporarily locked option
Due to internal procedures that are currently in progress (e.g. data upload/download,
reset, etc.), write access to the parameters is temporarily [Link] parameters can be
modified again, once the internal procedures are complete.

Endress+Hauser 91
"System" menu Proline Promag 10 Modbus RS485

Configuration counter

Navigation  System → Device manag. → Config. counter

Description Displays the counter for changes to the device parameters.


Additional information:
- If the value for a static parameter is changed when optimizing or configuring the
parameter, the counter is incremented by 1. This is to enable tracking different parameter
versions.
- When multiple parameters are changed simultaneously, e.g. when loading parameters
into the device from an external source such as FieldCare, the counter may display a higher
value. The counter cannot be reset, nor is it reset to a default value on performing a device
reset.
- Once the counter has reached the value 65535, it restarts at 0.

User interface 0 to 65 535

Device reset 

Navigation  System → Device manag. → Device reset

Description Reset the device configuration - either entirely or in part - to a defined state.

Selection • Cancel
• To delivery settings
• Restart device
• Restore S-DAT backup *
• Create T-DAT backup
• Restore T-DAT backup *

Additional information Selection


• To delivery settings option
Every parameter for which a customer-specific default setting was ordered is reset to the
customer-specific value. All other parameters are reset to the factory setting.
• Restart device option
The restart resets every parameter with data stored in volatile memory (RAM) to the
factory setting (e.g. measured value data). The device configuration remains unchanged.
• Restore S-DAT backup option
Restore the data that is saved on the S-DAT. The data record is restored from the
electronics memory to the S-DAT.
• Create T-DAT backup option
Create T-DAT backup.

* Visibility depends on order options or device settings

92 Endress+Hauser
Proline Promag 10 Modbus RS485 "System" menu

5.2 "User management" submenu


Navigation  System → User manag.

‣ User management

User role →  93

Enter access code →  94

Reset Maintenance code →  94

‣ Define Maintenance code →  95

User role

Navigation  System → User manag. → User role

Description Displays the role the user is currently logged on in. The role determines the user's access
rights for the parameters.
Additional information:
- Until a Maintenance code has been set in the "Define Maintenance code" parameter, all
users are automatically logged on in the Maintenance role. Once the Maintenance code
has been set, all users are automatically logged on in the Operator role.
- The access rights can be changed via the "Enter access code" parameter.

User interface • Operator


• Maintenance
• Service
• Production
• Development

Additional information User interface


• Operator option
Provides only read access to parameters.
• Maintenance option
Provides read and write access to parameters.
Additional information:
For some parameters, the user must be logged on in the Service role to obtain write
access.
• Service option
Provides read and write access to Service parameters.

Endress+Hauser 93
"System" menu Proline Promag 10 Modbus RS485

Enter access code

Navigation  System → User manag. → Ent. access code

Description For users logged on in the Operator role, enter the Maintenance code to change the access
status to Maintenance and disable write protection of parameters. For users logged on in
the Maintenance role, enter the Service code to change the access status to Service and
enable read and write access to Service parameters.

User entry 0 to 9 999

Reset Maintenance code

Navigation  System → User manag. → Reset Maint code

Description Enter the code provided by Endress+Hauser Technical Support to reset the Maintenance
code.

User entry Character string comprising numbers, letters and special characters (32)

94 Endress+Hauser
Proline Promag 10 Modbus RS485 "System" menu

5.2.1 "Define access code" wizard


Complete this wizard to specify an access code for the Maintenance role.

Navigation  System → User manag. → Def. access code

‣ Define Maintenance code

Define Maintenance code →  95

Confirm Maintenance code →  95

Define Maintenance code 

Navigation  System → User manag. → Def. Maint. code → Def. Maint. code

Description Specify an access code that is required to obtain the access rights for the Maintenance role.

User entry 0 to 9 999

Confirm Maintenance code 

Navigation  System → User manag. → Def. Maint. code → Conf. Maint code

Description Confirm the access code entered for the Maintenance role.

User entry 0 to 9 999

Endress+Hauser 95
"System" menu Proline Promag 10 Modbus RS485

5.3 "Connectivity" submenu


Navigation  System → Connectivity

‣ Connectivity

‣ Bluetooth configuration →  96

5.3.1 "Bluetooth configuration" submenu

Navigation  System → Connectivity → Bluetooth conf.

‣ Bluetooth configuration

Bluetooth →  96

Communication established →  96

Bluetooth 

Navigation  System → Connectivity → Bluetooth conf. → Bluetooth

Description Enable or disable Bluetooth.

Selection • Enable
• Disable
• Not available *

Communication established

Navigation  System → Connectivity → Bluetooth conf. → Communi. establ.

User interface • No
• Yes

* Visibility depends on order options or device settings

96 Endress+Hauser
Proline Promag 10 Modbus RS485 "System" menu

5.4 " Date / Time" submenu


Navigation  System → Date / Time

‣ Date/time

Set date/time →  97

Time format →  97

Time zone →  97

Set date/time 

Navigation  System → Date/time → Set date/time

Description Set the date and local time. Every time the date or time is changed, a logbook entry is
created.

User entry Date and time

Time format 

Navigation  System → Date/time → Time format

Description Select time format.

Selection • 24 h
• 12 h AM/PM

Time zone 

Navigation  System → Date/time → Time zone

Description Select the time zone. Every time the time zone is changed, a logbook entry is created.

Endress+Hauser 97
"System" menu Proline Promag 10 Modbus RS485

Selection
Other units
• UTC-12:00
• UTC-11:00
• UTC-10:00
• UTC-09:30
• UTC-09:00
• UTC-08:00
• UTC-07:00
• UTC-06:00
• UTC-05:00
• UTC-04:00
• UTC-03:30
• UTC-03:00
• UTC-02:00
• UTC-01:00
• UTC 00:00
• UTC+01:00
• UTC+02:00
• UTC+03:00
• UTC+03:30
• UTC+04:00
• UTC+04:30
• UTC+05:00
• UTC+05:30
• UTC+05:45
• UTC+06:00
• UTC+06:30
• UTC+07:00
• UTC+08:00
• UTC+08:45
• UTC+09:00
• UTC+09:30
• UTC+10:00
• UTC+10:30
• UTC+11:00
• UTC+12:00
• UTC+12:45
• UTC+13:00
• UTC+14:00

98 Endress+Hauser
Proline Promag 10 Modbus RS485 "System" menu

5.5 "Information" submenu


Navigation  System → Information

‣ Information

‣ Device →  99

‣ Sensor electronic module (ISEM) →  102

‣ Display module →  102

5.5.1 "Device" submenu

Navigation  System → Information → Device

‣ Device

Device name →  99

Device tag →  100

Serial number →  100

Order code →  100

Firmware version →  100

Extended order code 1 →  101

Extended order code 2 →  101

Extended order code 3 →  101

ENP version →  101

Manufacturer →  102

Device name

Navigation  System → Information → Device → Device name

Description Displays the name of the transmitter.


Additional information:
The name can also be found on the transmitter's nameplate.

Endress+Hauser 99
"System" menu Proline Promag 10 Modbus RS485

User interface Character string comprising numbers, letters and special characters

Device tag

Navigation  System → Information → Device → Device tag

Description Displays the name for the measuring point.

User interface Character string comprising numbers, letters and special characters

Serial number

Navigation  System → Information → Device → Serial number

Description Displays the serial number of the measuring device. The serial number can be used to
identify the measuring device and to retrieve further information on the measuring device,
such as the related documentation, via the Device Viewer or Operations app.
Additional information:
The serial number can also be found on the nameplate of the sensor and transmitter.

User interface Character string comprising numbers, letters and special characters

Order code 

Navigation  System → Information → Device → Order code

Description Displays the device order code.


Additional information:
The order code can be used for instance to order a replacement or spare device or to verify
that the device features specified on the order form match the shipping note.

User interface Character string comprising numbers, letters and special characters

Firmware version

Navigation  System → Information → Device → Firmware version

Description Displays the device firmware version installed.

User interface Character string comprising numbers, letters and special characters

100 Endress+Hauser
Proline Promag 10 Modbus RS485 "System" menu

Extended order code 1 

Navigation  System → Information → Device → Ext. order cd. 1

Description Displays the first, second and/or third part of the extended order code. Due to character
length restrictions, the extended order code is split into a maximum of 3 parameters. The
extended order code indicates for each feature in the product structure the selected option,
thereby uniquely identifying the device model.
Additional information:
The extended order code can also be found on the nameplate.

User interface Character string comprising numbers, letters and special characters

Extended order code 2 

Navigation  System → Information → Device → Ext. order cd. 2

Description Displays the first, second and/or third part of the extended order code. Due to character
length restrictions, the extended order code is split into a maximum of 3 parameters. The
extended order code indicates for each feature in the product structure the selected option,
thereby uniquely identifying the device model.
Additional information:
The extended order code can also be found on the nameplate.

User interface Character string comprising numbers, letters and special characters

Extended order code 3 

Navigation  System → Information → Device → Ext. order cd. 3

Description Displays the first, second and/or third part of the extended order code. Due to character
length restrictions, the extended order code is split into a maximum of 3 parameters. The
extended order code indicates for each feature in the product structure the selected option,
thereby uniquely identifying the device model.
Additional information:
The extended order code can also be found on the nameplate.

User interface Character string comprising numbers, letters and special characters

ENP version

Navigation  System → Information → Device → ENP version

Description Displays the version of the electronic nameplate (ENP).

Endress+Hauser 101
"System" menu Proline Promag 10 Modbus RS485

User interface Character string comprising numbers, letters and special characters

Manufacturer

Navigation  System → Information → Device → Manufacturer

Description Displays the manufacturer.

User interface Character string comprising numbers, letters and special characters

5.5.2 "Sensor electronic module (ISEM)" submenu

Navigation  System → Information → Sens. electronic

‣ Sensor electronic module (ISEM)

Firmware version →  102

Firmware version

Navigation  System → Information → Sens. electronic → Firmware version

Description Displays the firmware version of the module.

User interface Positive integer

5.5.3 "Display module" submenu

Navigation  System → Information → Display module

‣ Display module

Firmware version →  103

102 Endress+Hauser
Proline Promag 10 Modbus RS485 "System" menu

Firmware version

Navigation  System → Information → Display module → Firmware version

Description Displays the firmware version of the module.

User interface Positive integer

Endress+Hauser 103
"System" menu Proline Promag 10 Modbus RS485

5.6 "Display" submenu


Navigation  System → Display

‣ Display

Language →  104

Value 1 display →  105

Value 2 display →  105

Value 3 display →  106

Value 4 display →  106

Display damping →  106

Rotation display →  107

Brightness →  107

Color scheme →  107

Language

Navigation  System → Display → Language

Description Set display language.

Selection • English
• Deutsch
• Français
• Español
• Italiano
• Nederlands
• Portuguesa
• Polski
• русский язык (Russian)
• Svenska
• Türkçe
• 中文 (Chinese)
• 日本語 (Japanese)
• 한국어 (Korean)
• ‫( الْعَرَبيّة‬Arabic) *
• Bahasa Indonesia

* Visibility depends on order options or device settings

104 Endress+Hauser
Proline Promag 10 Modbus RS485 "System" menu

• ภาษาไทย (Thai) *
• tiếng Việt (Vietnamese)
• čeština (Czech)

Value 1 display 

Navigation  System → Display → Value 1 display

Description Select the measured value that is displayed first on the local display.
Additional information:
The applicable unit of measure is specified in the "System units" submenu.

Selection • Volume flow


• Mass flow
• Conductivity *
• Corrected conductivity *
• Temperature *
• Totalizer 1
• Totalizer 2
• Totalizer 3

Value 2 display 

Navigation  System → Display → Value 2 display

Description Select the measured value that is shown second on the local display.
Additional information:
The applicable unit of measure is specified in the "System units" submenu.

Selection • None
• Volume flow
• Mass flow
• Conductivity *
• Corrected conductivity *
• Temperature *
• Totalizer 1
• Totalizer 2
• Totalizer 3

* Visibility depends on order options or device settings

Endress+Hauser 105
"System" menu Proline Promag 10 Modbus RS485

Value 3 display 

Navigation  System → Display → Value 3 display

Description Select the measured value that is shown third on the local display.
Additional information:
The applicable unit of measure is specified in the "System units" submenu.

Selection • None
• Volume flow
• Mass flow
• Conductivity *
• Corrected conductivity *
• Temperature *
• Totalizer 1
• Totalizer 2
• Totalizer 3

Value 4 display 

Navigation  System → Display → Value 4 display

Description Select the measured value that is shown fourth on the local display.
Additional information:
The applicable unit of measure is specified in the "System units" submenu.

Selection • None
• Volume flow
• Mass flow
• Conductivity *
• Corrected conductivity *
• Temperature *
• Totalizer 1
• Totalizer 2
• Totalizer 3

Display damping 

Navigation  System → Display → Display damping

Description Enter time constant (PT1 element) to set reaction time of the display to fluctuations in the
measured value.
Additional information:
- The smaller the time constant the faster the display reacts to fluctuations in the
measured value.
- If the time constant is set to 0, damping is deactivated.

* Visibility depends on order options or device settings

106 Endress+Hauser
Proline Promag 10 Modbus RS485 "System" menu

User entry 0.0 to 999.9 s

Rotation display 

Navigation  System → Display → Rotation display

Description Select rotation angle of the display text to optimize local display readability.

Selection • Auto
• 0 degree
• 90 degree
• 180 degree
• 270 degree

Brightness

Navigation  System → Display → Brightness

Description Adjust brightness.

User entry 0 to 100 %

Color scheme 

Navigation  System → Display → Color scheme

Description Select preferred color scheme.

Selection • Light
• Dark

Endress+Hauser 107
"System" menu Proline Promag 10 Modbus RS485

5.7 "Software configuration" submenu


Navigation  System → Software config.

‣ Software configuration

Activate SW option →  108

Software option overview →  108

Activate SW option 

Navigation  System → Software config. → Activate SW opt.

Description Enter application package code or code of the functionality ordered separately to activate
it.
Additional information:
- If a measuring device was ordered with an add-on software option, the activation code is
programmed into the measuring device ex factory.
- After entering the activation code: Check whether the new software option is displayed
in the "Software option overview" parameter and therefore active.
NOTE
If an an invalid code is entered the software options that have already been activated are
invalidated!
Before entering a new activation code: Create a record of the existing activation code.

User entry Positive integer

Software option overview

Navigation  System → Software config. → SW option overv.

Description Displays all software options included in the order ex factory or ordered at a later date that
have been enabled via the operating interface.
Additional information:
If a new software option is not displayed after entering the activation code, the code
entered was inaccurate or invalid. In this case, contact the appropriate Endress+Hauser
sales organization to activate the software option.

User interface • Heartbeat Verification


• Heartbeat Monitoring

108 Endress+Hauser
Proline Promag 10 Modbus RS485 Modbus RS485 register information

6 Modbus RS485 register information

6.1 Notes

6.1.1 Structure of the register information


The individual parts of a parameter description are described in the following section:

Navigation: navigation path to the parameter

Parameter Register Data type Access type Selection/input →

Name of parameter Indicated in decimal • Float length = Possible type of access Selection Page number information
numerical format 4 byte to parameter: List of the individual and cross-reference to the
• Integer length = • Read access via options for the standard parameter
2 byte function codes 03, parameter description
• String length, 04 or 23 • Option 1
depending on • Write access via • Option 2
parameter function codes 06, • Option 3 (+)
16 or 23
 • Factory
setting
highlighted in
bold
• (+) = Factory
setting
depends on
country, order
options or
device
settings
Input
Input range for the
parameter

NOTICE
If non-volatile device parameters are modified via the MODBUS RS485 function codes
06, 16 or 23, the change is saved in the EEPROM of the measuring device.
The number of writes to the EEPROM is technically restricted to a maximum of 1 million.
‣ Make sure to comply with this limit since, if it is exceeded, data loss and measuring
device failure will result.
‣ Avoid constantly writing non-volatile device parameters via the MODBUS RS485.

6.1.2 Address model


The Modbus RS485 register addresses of the measuring device are implemented in
accordance with the "Modbus Applications Protocol Specification V1.1".
In addition, systems are used that work with the register address model "Modicon Modbus
Protocol Reference Guide (PI-MBUS-300 Rev. J)".
Depending on the function code used, a number is added at the start of the register
address with this specification:
• "3" → "Read" access
• "4" → "Write" access

Endress+Hauser 109
Modbus RS485 register information Proline Promag 10 Modbus RS485

Function code Access type Register in accordance with "Modbus Register in accordance with
Applications Protocol Specification" "Modicon Modbus Protocol
Reference Guide"

03 Read XXXX 3XXXX


04 Example: mass flow = 2007 Example: mass flow = 32007
23

06 Write XXXX 4XXXX


16 Example: reset totalizer = 6401 Example: reset totalizer = 46401
23

6.2 Overview of the operating menu


The following table provides an overview of the menu structure of the operating menu and
its parameters. The page reference indicates where the associated description of the
submenu or parameter can be found.

Guidance →  119

‣ Commissioning →  119

Device tag →  119

Serial number →  119

Firmware version →  119

Device name →  119

Volume flow unit →  120

Volume unit →  121

Mass flow unit →  122

Mass unit →  122

Density unit →  122

Temperature unit →  122

Conductivity unit →  122

Assign process variable →  123

Unit totalizer 1 to n →  123

Totalizer operation mode →  123

Failure mode →  123

Flow damping →  123

110 Endress+Hauser
Proline Promag 10 Modbus RS485 Modbus RS485 register information

Low flow cut off →  123

On value low flow cutoff →  123

Off value low flow cutoff →  123

Pressure shock suppression →  123

Empty pipe detection →  123

Empty pipe adjust value →  123

Full pipe adjust value →  123

Process variable current output →  123

Current range output →  124

Lower range value output →  124

Upper range value output →  124

Damping current output →  124

Fixed current →  124

Failure behavior current output →  124

Failure current →  124

Value 1 display →  124

Value 2 display →  124

Value 3 display →  124

Value 4 display →  124

Display damping →  124

Time format →  125

Time zone →  125

Diagnostics →  125

‣ Active diagnostics →  125

Actual diagnostics →  125

Endress+Hauser 111
Modbus RS485 register information Proline Promag 10 Modbus RS485

Timestamp →  125

Previous diagnostics →  125

Timestamp →  125

Operating time from restart →  126

Operating time →  126

‣ Diagnostic list →  126

‣ Simulation →  126

Assign simulation process variable →  126

Process variable value →  126

Current output 1 simulation →  126

Current output value →  126

Device alarm simulation →  126

Diagnostic event simulation →  126

‣ Heartbeat Technology →  126

‣ Diagnostic settings →  126

‣ Properties →  126

Alarm delay →  126

‣ Diagnostic configuration →  126

‣ Sensor →  126

Assign behavior of diagnostic no. 043 →  126

‣ Electronics →  127

Assign behavior of diagnostic no. 230 →  127

Assign behavior of diagnostic no. 231 →  127

Assign behavior of diagnostic no. 302 →  127

112 Endress+Hauser
Proline Promag 10 Modbus RS485 Modbus RS485 register information

Assign behavior of diagnostic no. 376 →  127

Assign behavior of diagnostic no. 377 →  127

‣ Configuration →  127

Assign behavior of diagnostic no. 441 →  127

‣ Process →  127

Assign behavior of diagnostic no. 832 →  127

Assign behavior of diagnostic no. 833 →  127

Assign behavior of diagnostic no. 834 →  127

Assign behavior of diagnostic no. 835 →  127

Assign behavior of diagnostic no. 842 →  127

Assign behavior of diagnostic no. 937 →  128

Assign behavior of diagnostic no. 938 →  128

Assign behavior of diagnostic no. 961 →  128

Assign behavior of diagnostic no. 962 →  128

Application →  128

‣ Measured values →  128

Mass flow →  128

Volume flow →  128

Conductivity →  128

Corrected conductivity →  128

Temperature →  128

‣ Totalizer →  128

Totalizer value 1 to n →  128

Totalizer overflow 1 to n →  128

Endress+Hauser 113
Modbus RS485 register information Proline Promag 10 Modbus RS485

‣ System units →  129

Volume flow unit →  129

Volume unit →  130

Mass flow unit →  131

Mass unit →  131

Density unit →  131

Temperature unit →  131

Conductivity unit →  131

‣ Totalizers →  132

‣ Totalizer handling →  132

Reset all totalizers →  132

‣ Totalizer 1 to n →  132

Assign process variable →  132

Unit totalizer 1 to n →  132

Totalizer operation mode →  132

Control Totalizer 1 to n →  132

Preset value 1 to n →  132

Failure mode →  132

‣ Sensor →  133

‣ Process parameters →  133

Flow damping →  133

Flow override →  133

Conductivity measurement →  133

Conductivity temperature coefficient →  133

Fixed density →  133

114 Endress+Hauser
Proline Promag 10 Modbus RS485 Modbus RS485 register information

‣ Low flow cut off →  133

Low flow cut off →  133

On value low flow cutoff →  133

Off value low flow cutoff →  133

‣ Empty pipe detection →  133

Empty pipe detection →  133

New adjustment →  133

Empty pipe adjust value →  133

Full pipe adjust value →  133

Measured value EPD →  133

‣ Sensor adjustment →  133

Installation direction →  133

Integration time →  133

Measuring period →  133

‣ Calibration →  134

Nominal diameter →  134

Calibration factor →  134

Zero point →  134

Conductivity calibration factor →  134

‣ Electrode cleaning cycle →  134

Electrode cleaning cycle →  134

ECC duration →  134

ECC recovery time →  134

ECC interval →  134

ECC polarity →  134

Endress+Hauser 115
Modbus RS485 register information Proline Promag 10 Modbus RS485

‣ Current output 1 →  134

Process variable current output →  134

Measuring mode current output →  134

Current range output →  134

Fixed current →  134

Lower range value output →  134

Upper range value output →  134

Damping current output →  134

Failure behavior current output →  134

Failure current →  135

Output current 1 →  135

‣ Communication →  135

‣ Modbus configuration →  135

Bus address →  135

Baudrate →  135

Parity →  135

Byte order →  135

Telegram delay →  135

Failure mode →  135

Fieldbus writing access →  135

116 Endress+Hauser
Proline Promag 10 Modbus RS485 Modbus RS485 register information

‣ Modbus data map →  135

Scan list register 0 to 15 →  135

‣ Modbus information →  136

Device ID →  136

Device revision →  136

System →  136

‣ Device management →  136

Device tag →  136

Locking status →  136

Configuration counter →  136

Device reset →  136

‣ User management →  136

User role →  136

Enter access code →  136

Reset Maintenance code →  136

‣ Define Maintenance code →  136

Define Maintenance code →  136

Confirm Maintenance code →  136

‣ Connectivity →  137

‣ Bluetooth configuration →  137

Bluetooth →  137

Communication established →  137

‣ Date/time →  137

Time format →  137

Time zone →  137

Endress+Hauser 117
Modbus RS485 register information Proline Promag 10 Modbus RS485

‣ Information →  138

‣ Device →  138

Device name →  138

Device tag →  138

Serial number →  138

Order code →  138

Firmware version →  138

Extended order code 1 →  138

Extended order code 2 →  138

Extended order code 3 →  138

ENP version →  138

Manufacturer →  138

‣ Sensor electronic module (ISEM) →  138

Firmware version →  138

‣ Display module →  138

Firmware version →  138

‣ Display →  139

Language →  139

Value 1 display →  139

Value 2 display →  139

Value 3 display →  139

Value 4 display →  139

Display damping →  139

Rotation display →  139

118 Endress+Hauser
Proline Promag 10 Modbus RS485 Modbus RS485 register information

Brightness →  140

Color scheme →  140

‣ Software configuration →  140

Activate SW option →  140

Software option overview →  140

6.3 Register information

6.3.1 "Guidance" menu

"Commissioning" wizard

Navigation: Guidance → Commissioning

Parameter Register Data type Access Selection / User entry / User interface → 

Device tag 29243 to 29258 String Read / Write Character string comprising numbers, 8
letters and special characters (32)

Serial number 7003 to 7008 String Read Character string comprising numbers, 8
letters and special characters

Firmware version 7277 to 7280 String Read Character string comprising numbers, 8
letters and special characters

Device name 7263 to 7270 String Read Character string comprising numbers, 8
letters and special characters

Endress+Hauser 119
Modbus RS485 register information Proline Promag 10 Modbus RS485

Navigation: Guidance → Commissioning

Parameter Register Data type Access Selection / User entry / User interface → 

Volume flow unit 2103 Integer Read / Write 0 = cm³/s 9


1 = cm³/min
2 = cm³/h
3 = cm³/d
4 = dm³/s
5 = dm³/min
6 = dm³/h
7 = dm³/d
8 = m³/s
9 = m³/min
10 = m³/h
11 = m³/d
12 = ml/s
13 = ml/min
14 = ml/h
15 = ml/d
16 = l/s
17 = l/min
18 = l/h
19 = l/d
20 = hl/s
21 = hl/min
22 = hl/h
23 = hl/d
24 = Ml/s
25 = Ml/min
26 = Ml/h
27 = Ml/d
32 = af/s
33 = af/min
34 = af/h
35 = af/d
36 = ft³/s
37 = ft³/min
38 = ft³/h
39 = ft³/d
40 = fl oz/s (us)
41 = fl oz/min (us)
42 = fl oz/h (us)
43 = fl oz/d (us)
44 = gal/s (us)
45 = gal/min (us)
46 = gal/h (us)
47 = gal/d (us)
48 = Mgal/s (us)
49 = Mgal/min (us)
50 = Mgal/h (us)
51 = Mgal/d (us)
52 = bbl/s (us;liq.)
53 = bbl/min (us;liq.)
54 = bbl/h (us;liq.)
55 = bbl/d (us;liq.)
56 = bbl/s (us;beer)
57 = bbl/min (us;beer)
58 = bbl/h (us;beer)
59 = bbl/d (us;beer)
60 = bbl/s (us;oil)
61 = bbl/min (us;oil)
62 = bbl/h (us;oil)
63 = bbl/d (us;oil)
64 = bbl/s (us;tank)
65 = bbl/min (us;tank)
66 = bbl/h (us;tank)
67 = bbl/d (us;tank)
68 = gal/s (imp)
69 = gal/min (imp)
70 = gal/h (imp)

120 Endress+Hauser
Proline Promag 10 Modbus RS485 Modbus RS485 register information

Navigation: Guidance → Commissioning

Parameter Register Data type Access Selection / User entry / User interface → 
71 = gal/d (imp)
72 = Mgal/s (imp)
73 = Mgal/min (imp)
74 = Mgal/h (imp)
75 = Mgal/d (imp)
76 = bbl/s (imp;beer)
77 = bbl/min (imp;beer)
78 = bbl/h (imp;beer)
79 = bbl/d (imp;beer)
80 = bbl/s (imp;oil)
81 = bbl/min (imp;oil)
82 = bbl/h (imp;oil)
83 = bbl/d (imp;oil)
88 = kgal/s (us)
89 = kgal/min (us)
90 = kgal/h (us)
91 = kgal/d (us)
92 = MMft³/s
93 = MMft³/min
94 = MMft³/h
96 = Mft³/d

Volume unit 2104 Integer Read / Write 0 = cm³ 10


1 = dm³
2 = m³
3 = ml
4=l
5 = hl
6 = Ml Mega
8 = af
9 = ft³
10 = fl oz (us)
11 = gal (us)
12 = Mgal (us)
13 = bbl (us;liq.)
14 = bbl (us;beer)
15 = bbl (us;oil)
16 = bbl (us;tank)
17 = gal (imp)
18 = Mgal (imp)
19 = bbl (imp;beer)
20 = bbl (imp;oil)
22 = kgal (us)
23 = Mft³

Endress+Hauser 121
Modbus RS485 register information Proline Promag 10 Modbus RS485

Navigation: Guidance → Commissioning

Parameter Register Data type Access Selection / User entry / User interface → 

Mass flow unit 2101 Integer Read / Write 0 = g/s 11


1 = g/min
2 = g/h
3 = g/d
4 = kg/s
5 = kg/min
6 = kg/h
7 = kg/d
8 = t/s
9 = t/min
10 = t/h
11 = t/d
12 = oz/s
13 = oz/min
14 = oz/h
15 = oz/d
16 = lb/s
17 = lb/min
18 = lb/h
19 = lb/d
20 = STon/s
21 = STon/min
22 = STon/h
23 = STon/d

Mass unit 2102 Integer Read / Write 50 = g 11


51 = kg
52 = t
53 = oz
54 = lb
55 = STon

Density unit 2107 Integer Read / Write 0 = g/cm³ 12


2 = kg/dm³
3 = kg/l
4 = kg/m³
5 = SD4°C
6 = SD15°C
7 = SD20°C
8 = SG4°C
9 = SG15°C
10 = SG20°C
11 = lb/ft³
12 = lb/gal (us)
13 = lb/bbl (us;liq.)
14 = lb/bbl (us;beer)
15 = lb/bbl (us;oil)
16 = lb/bbl (us;tank)
17 = lb/gal (imp)
18 = lb/bbl (imp;beer)
19 = lb/bbl (imp;oil)
21 = g/m³

Temperature unit 2109 Integer Read / Write 0 = °C 12


1=K
2 = °F
3 = °R

Conductivity unit 2121 Integer Read / Write 1 = MS/m 12


2 = kS/m
3 = S/m
4 = S/cm
5 = mS/m
6 = mS/cm
7 = µS/m
8 = µS/cm
9 = µS/mm
10 = nS/cm

122 Endress+Hauser
Proline Promag 10 Modbus RS485 Modbus RS485 register information

Navigation: Guidance → Commissioning

Parameter Register Data type Access Selection / User entry / User interface → 

Assign process variable 2601 Integer Read / Write 0 = Off 13


1 = Volume flow
11 = Mass flow

Unit totalizer 1 to n 1: 4604 Integer Read / Write 0 = cm³ * 13


2: 4605 1 = dm³ *
3: 4606 2 = m³ *
3 = ml *
4 = l*
5 = hl *
6 = Ml Mega *
8 = af *
9 = ft³ *
10 = fl oz (us) *
11 = gal (us) *
12 = Mgal (us) *
13 = bbl (us;liq.) *
14 = bbl (us;beer) *
15 = bbl (us;oil) *
16 = bbl (us;tank) *
17 = gal (imp) *
18 = Mgal (imp) *
19 = bbl (imp;beer) *
20 = bbl (imp;oil) *
22 = kgal (us) *
23 = Mft³ *
50 = g *
51 = kg *
52 = t *
53 = oz *
54 = lb *
55 = STon *
251 = None *

Totalizer operation mode 2605 Integer Read / Write 0 = Net flow total 14
1 = Forward flow total
2 = Reverse flow total

Failure mode 2606 Integer Read / Write 0 = Stop 15


1 = Actual value
2 = Last valid value

Flow damping 2274 Integer Read / Write 0 to 15 15

Low flow cut off 5101 Integer Read / Write 0 = Off 17


1 = Volume flow
11 = Mass flow

On value low flow cutoff 5138 to 5139 Float Read / Write Positive floating-point number 18

Off value low flow cutoff 5104 to 5105 Float Read / Write 0 to 100.0 % 18

Pressure shock suppression 5140 to 5141 Float Read / Write 0 to 100 s 16

Empty pipe detection 5106 Integer Read / Write 0 = Off 19


1 = On

Empty pipe adjust value 2181 to 2182 Float Read Positive floating-point number 19

Full pipe adjust value 2832 to 2833 Float Read Positive floating-point number 19

Process variable current output 5927 Integer Read / Write 0 = Off * 20


1 = Volume flow
4 = Conductivity *
7 = Temperature *
9 = Corrected conductivity *
11 = Mass flow
40 = Noise *
41 = Coil current shot time *

Endress+Hauser 123
Modbus RS485 register information Proline Promag 10 Modbus RS485

Navigation: Guidance → Commissioning

Parameter Register Data type Access Selection / User entry / User interface → 

Current range output 5923 Integer Read / Write 0 = 4...20 mA (4... 20.5 mA) 20
1 = 4...20 mA US (3.9...20.8 mA)
2 = 4...20 mA NE (3.8...20.5 mA)
4 = Fixed value

Lower range value output 6195 to 6196 Float Read / Write Signed floating-point number 21

Upper range value output 5915 to 5916 Float Read / Write Signed floating-point number 22

Damping current output 5903 to 5904 Float Read / Write 0.0 to 999.9 s 23

Fixed current 5987 to 5988 Float Read / Write 3.59 to 21.5 mA 23

Failure behavior current output 5911 Integer Read / Write 0 = Min. 23


1 = Max.
4 = Actual value
5 = Last valid value
6 = Fixed value

Failure current 5979 to 5980 Float Read / Write 3.59 to 21.5 mA 24

Value 1 display 34918 Integer Read / Write 1 = Volume flow 25


4 = Conductivity *
7 = Temperature *
9 = Corrected conductivity *
11 = Mass flow
16 = Totalizer 1
17 = Totalizer 2
18 = Totalizer 3

Value 2 display 34919 Integer Read / Write 1 = Volume flow 25


4 = Conductivity *
7 = Temperature *
9 = Corrected conductivity *
11 = Mass flow
16 = Totalizer 1
17 = Totalizer 2
18 = Totalizer 3
251 = None

Value 3 display 34922 Integer Read / Write 1 = Volume flow 26


4 = Conductivity *
7 = Temperature *
9 = Corrected conductivity *
11 = Mass flow
16 = Totalizer 1
17 = Totalizer 2
18 = Totalizer 3
251 = None

Value 4 display 34923 Integer Read / Write 1 = Volume flow 26


4 = Conductivity *
7 = Temperature *
9 = Corrected conductivity *
11 = Mass flow
16 = Totalizer 1
17 = Totalizer 2
18 = Totalizer 3
251 = None

Display damping 27602 to 27603 Float Read / Write 0.0 to 999.9 s 26

124 Endress+Hauser
Proline Promag 10 Modbus RS485 Modbus RS485 register information

Navigation: Guidance → Commissioning

Parameter Register Data type Access Selection / User entry / User interface → 

Time format 2150 Integer Read / Write 12 = 12 h AM/PM 27


24 = 24 h

Time zone 27339 Integer Read / Write 0 = UTC 00:00 27


1 = UTC+01:00
2 = UTC+02:00
3 = UTC+03:00
4 = UTC+04:00
5 = UTC+05:00
6 = UTC+06:00
7 = UTC+07:00
8 = UTC+08:00
9 = UTC+09:00
10 = UTC+10:00
11 = UTC+11:00
12 = UTC+12:00
13 = UTC+13:00
14 = UTC+14:00
35 = UTC+03:30
45 = UTC+04:30
55 = UTC+05:30
57 = UTC+05:45
65 = UTC+06:30
87 = UTC+08:45
95 = UTC+09:30
105 = UTC+10:30
127 = UTC+12:45
135 = UTC-03:30
195 = UTC-09:30
201 = UTC-01:00
202 = UTC-02:00
203 = UTC-03:00
204 = UTC-04:00
205 = UTC-05:00
206 = UTC-06:00
207 = UTC-07:00
208 = UTC-08:00
209 = UTC-09:00
210 = UTC-10:00
211 = UTC-11:00
212 = UTC-12:00

* Visibility depends on order options or device settings


* Visibility depends on order options or device settings
* Visibility depends on order options or device settings

6.3.2 "Diagnostics" menu

"Active diagnostics" submenu

Navigation: Diagnostics → Active diagnostics

Parameter Register Data type Access Selection / User entry / User interface → 

Actual diagnostics 2732 Integer Read Positive integer 30

Timestamp 29726 String Read Days (d), hours (h), minutes (m), seconds 30
(s)

Previous diagnostics 2734 Integer Read Positive integer 30

Timestamp 29715 String Read Days (d), hours (h), minutes (m), seconds 31
(s)

Endress+Hauser 125
Modbus RS485 register information Proline Promag 10 Modbus RS485

Navigation: Diagnostics → Active diagnostics

Parameter Register Data type Access Selection / User entry / User interface → 

Operating time from restart 2624 String Read Days (d), hours (h), minutes (m), seconds 31
(s)

Operating time 2631 String Read Days (d), hours (h), minutes (m), seconds 31
(s)

"Diagnostic list" submenu

"Simulation" submenu

Navigation: Diagnostics → Simulation

Parameter Register Data type Access Selection / User entry / User interface → 

Assign simulation process variable 6813 Integer Read / Write 0 = Off 35


1 = Volume flow
4 = Conductivity *
7 = Temperature *
9 = Corrected conductivity *
11 = Mass flow

Process variable value 6814 to 6815 Float Read / Write Signed floating-point number 36

Current output 1 simulation 5939 Integer Read / Write 0 = Off 36


1 = On

Current output value 5995 to 5996 Float Read / Write 3.59 to 21.5 mA 36

Device alarm simulation 6812 Integer Read / Write 0 = Off 37


1 = On

Diagnostic event simulation 4259 Integer Read / Write 0 = Off 37

* Visibility depends on order options or device settings

"Heartbeat Technology" submenu

"Diagnostic settings" submenu


"Properties" submenu

Navigation: Diagnostics → Diagnostic settings → Properties

Parameter Register Data type Access Selection / User entry / User interface → 

Alarm delay 6808 to 6809 Float Read / Write 0 to 60 s 39

"Diagnostic configuration" submenu


"Sensor" submenu

Navigation: Diagnostics → Diagnostic settings → Diagnostic configuration → Sensor

Parameter Register Data type Access Selection / User entry / User interface → 

Assign behavior of diagnostic no. 9666 Integer Read / Write 0 = Off 40


043 1 = Logbook entry only
2 = Warning
3 = Alarm

126 Endress+Hauser
Proline Promag 10 Modbus RS485 Modbus RS485 register information

"Electronics" submenu

Navigation: Diagnostics → Diagnostic settings → Diagnostic configuration → Electronics

Parameter Register Data type Access Selection / User entry / User interface → 

Assign behavior of diagnostic no. 27632 Integer Read / Write 1 = Logbook entry only 41
230 2 = Warning
3 = Alarm

Assign behavior of diagnostic no. 28535 Integer Read / Write 1 = Logbook entry only 41
231 2 = Warning
3 = Alarm

Assign behavior of diagnostic no. 6484 Integer Read / Write 0 = Off 41


302 1 = Logbook entry only
2 = Warning

Assign behavior of diagnostic no. 6442 Integer Read / Write 0 = Off 41


376 1 = Logbook entry only
2 = Warning
3 = Alarm

Assign behavior of diagnostic no. 5183 Integer Read / Write 0 = Off 42


377 1 = Logbook entry only
2 = Warning
3 = Alarm

"Configuration" submenu

Navigation: Diagnostics → Diagnostic settings → Diagnostic configuration → Configuration

Parameter Register Data type Access Selection / User entry / User interface → 

Assign behavior of diagnostic no. 4742 Integer Read / Write 0 = Off 43


441 1 = Logbook entry only
2 = Warning
3 = Alarm

"Process" submenu

Navigation: Diagnostics → Diagnostic settings → Diagnostic configuration → Process

Parameter Register Data type Access Selection / User entry / User interface → 

Assign behavior of diagnostic no. 6440 Integer Read / Write 0 = Off 44


832 1 = Logbook entry only
2 = Warning
3 = Alarm

Assign behavior of diagnostic no. 6439 Integer Read / Write 0 = Off 44


833 1 = Logbook entry only
2 = Warning
3 = Alarm

Assign behavior of diagnostic no. 6438 Integer Read / Write 0 = Off 45


834 1 = Logbook entry only
2 = Warning
3 = Alarm

Assign behavior of diagnostic no. 6437 Integer Read / Write 0 = Off 45


835 1 = Logbook entry only
2 = Warning
3 = Alarm

Assign behavior of diagnostic no. 9661 Integer Read / Write 0 = Off 46


842 1 = Logbook entry only
2 = Warning
3 = Alarm

Endress+Hauser 127
Modbus RS485 register information Proline Promag 10 Modbus RS485

Navigation: Diagnostics → Diagnostic settings → Diagnostic configuration → Process

Parameter Register Data type Access Selection / User entry / User interface → 

Assign behavior of diagnostic no. 26404 Integer Read / Write 0 = Off 46


937 1 = Logbook entry only
2 = Warning
3 = Alarm

Assign behavior of diagnostic no. 5837 Integer Read / Write 0 = Off 47


938 1 = Logbook entry only
2 = Warning
3 = Alarm

Assign behavior of diagnostic no. 28459 Integer Read / Write 0 = Off 47


961 1 = Logbook entry only
2 = Warning
3 = Alarm

Assign behavior of diagnostic no. 6441 Integer Read / Write 0 = Off 48


962 1 = Logbook entry only
2 = Warning
3 = Alarm

6.3.3 "Application" menu

"Measured values" submenu

Navigation: Application → Measured values

Parameter Register Data type Access Selection / User entry / User interface → 

Mass flow 2007 to 2008 Float Read Signed floating-point number 49

Volume flow 2009 to 2010 Float Read Signed floating-point number 50

Conductivity 2099 to 2100 Float Read Positive floating-point number 50

Corrected conductivity 37423 to 37424 Float Read Positive floating-point number 50

Temperature 2017 to 2018 Float Read Positive floating-point number 51

"Totalizer" submenu

Navigation: Application → Measured values → Totalizer

Parameter Register Data type Access Selection / User entry / User interface → 

Totalizer value 1 to n 1: 2610 to 2611 Float Read Signed floating-point number 51


2: 2810 to 2811
3: 3010 to 3011

Totalizer overflow 1 to n 1: 2612 to 2613 Float Read –32 000.0 to 32 000.0 52


2: 2812 to 2813
3: 3012 to 3013

128 Endress+Hauser
Proline Promag 10 Modbus RS485 Modbus RS485 register information

"System units" submenu

Navigation: Application → System units

Parameter Register Data type Access Selection / User entry / User interface → 

Volume flow unit 2103 Integer Read / Write 0 = cm³/s 53


1 = cm³/min
2 = cm³/h
3 = cm³/d
4 = dm³/s
5 = dm³/min
6 = dm³/h
7 = dm³/d
8 = m³/s
9 = m³/min
10 = m³/h
11 = m³/d
12 = ml/s
13 = ml/min
14 = ml/h
15 = ml/d
16 = l/s
17 = l/min
18 = l/h
19 = l/d
20 = hl/s
21 = hl/min
22 = hl/h
23 = hl/d
24 = Ml/s
25 = Ml/min
26 = Ml/h
27 = Ml/d
32 = af/s
33 = af/min
34 = af/h
35 = af/d
36 = ft³/s
37 = ft³/min
38 = ft³/h
39 = ft³/d
40 = fl oz/s (us)
41 = fl oz/min (us)
42 = fl oz/h (us)
43 = fl oz/d (us)
44 = gal/s (us)
45 = gal/min (us)
46 = gal/h (us)
47 = gal/d (us)
48 = Mgal/s (us)
49 = Mgal/min (us)
50 = Mgal/h (us)
51 = Mgal/d (us)
52 = bbl/s (us;liq.)
53 = bbl/min (us;liq.)
54 = bbl/h (us;liq.)
55 = bbl/d (us;liq.)
56 = bbl/s (us;beer)
57 = bbl/min (us;beer)
58 = bbl/h (us;beer)
59 = bbl/d (us;beer)
60 = bbl/s (us;oil)
61 = bbl/min (us;oil)
62 = bbl/h (us;oil)
63 = bbl/d (us;oil)
64 = bbl/s (us;tank)
65 = bbl/min (us;tank)
66 = bbl/h (us;tank)
67 = bbl/d (us;tank)
68 = gal/s (imp)

Endress+Hauser 129
Modbus RS485 register information Proline Promag 10 Modbus RS485

Navigation: Application → System units

Parameter Register Data type Access Selection / User entry / User interface → 
69 = gal/min (imp)
70 = gal/h (imp)
71 = gal/d (imp)
72 = Mgal/s (imp)
73 = Mgal/min (imp)
74 = Mgal/h (imp)
75 = Mgal/d (imp)
76 = bbl/s (imp;beer)
77 = bbl/min (imp;beer)
78 = bbl/h (imp;beer)
79 = bbl/d (imp;beer)
80 = bbl/s (imp;oil)
81 = bbl/min (imp;oil)
82 = bbl/h (imp;oil)
83 = bbl/d (imp;oil)
88 = kgal/s (us)
89 = kgal/min (us)
90 = kgal/h (us)
91 = kgal/d (us)
92 = MMft³/s
93 = MMft³/min
94 = MMft³/h
96 = Mft³/d

Volume unit 2104 Integer Read / Write 0 = cm³ 54


1 = dm³
2 = m³
3 = ml
4=l
5 = hl
6 = Ml Mega
8 = af
9 = ft³
10 = fl oz (us)
11 = gal (us)
12 = Mgal (us)
13 = bbl (us;liq.)
14 = bbl (us;beer)
15 = bbl (us;oil)
16 = bbl (us;tank)
17 = gal (imp)
18 = Mgal (imp)
19 = bbl (imp;beer)
20 = bbl (imp;oil)
22 = kgal (us)
23 = Mft³

130 Endress+Hauser
Proline Promag 10 Modbus RS485 Modbus RS485 register information

Navigation: Application → System units

Parameter Register Data type Access Selection / User entry / User interface → 

Mass flow unit 2101 Integer Read / Write 0 = g/s 55


1 = g/min
2 = g/h
3 = g/d
4 = kg/s
5 = kg/min
6 = kg/h
7 = kg/d
8 = t/s
9 = t/min
10 = t/h
11 = t/d
12 = oz/s
13 = oz/min
14 = oz/h
15 = oz/d
16 = lb/s
17 = lb/min
18 = lb/h
19 = lb/d
20 = STon/s
21 = STon/min
22 = STon/h
23 = STon/d

Mass unit 2102 Integer Read / Write 50 = g 55


51 = kg
52 = t
53 = oz
54 = lb
55 = STon

Density unit 2107 Integer Read / Write 0 = g/cm³ 56


2 = kg/dm³
3 = kg/l
4 = kg/m³
5 = SD4°C
6 = SD15°C
7 = SD20°C
8 = SG4°C
9 = SG15°C
10 = SG20°C
11 = lb/ft³
12 = lb/gal (us)
13 = lb/bbl (us;liq.)
14 = lb/bbl (us;beer)
15 = lb/bbl (us;oil)
16 = lb/bbl (us;tank)
17 = lb/gal (imp)
18 = lb/bbl (imp;beer)
19 = lb/bbl (imp;oil)
21 = g/m³

Temperature unit 2109 Integer Read / Write 0 = °C 56


1=K
2 = °F
3 = °R

Conductivity unit 2121 Integer Read / Write 1 = MS/m 56


2 = kS/m
3 = S/m
4 = S/cm
5 = mS/m
6 = mS/cm
7 = µS/m
8 = µS/cm
9 = µS/mm
10 = nS/cm

Endress+Hauser 131
Modbus RS485 register information Proline Promag 10 Modbus RS485

"Totalizers" submenu
"Totalizer handling" submenu

Navigation: Application → Totalizers → Totalizer handling

Parameter Register Data type Access Selection / User entry / User interface → 

Reset all totalizers 2609 Integer Read / Write 0 = Cancel 58


1 = Reset + totalize

"Totalizer 1 to n" submenu

Navigation: Application → Totalizers → Totalizer 1 to n

Parameter Register Data type Access Selection / User entry / User interface → 

Assign process variable 1: 2601 Integer Read / Write 0 = Off 59


2: 2801 1 = Volume flow
3: 3001 11 = Mass flow

Unit totalizer 1 to n 1: 4604 Integer Read / Write 0 = cm³ * 59


2: 4605 1 = dm³ *
3: 4606 2 = m³ *
3 = ml *
4 = l*
5 = hl *
6 = Ml Mega *
8 = af *
9 = ft³ *
10 = fl oz (us) *
11 = gal (us) *
12 = Mgal (us) *
13 = bbl (us;liq.) *
14 = bbl (us;beer) *
15 = bbl (us;oil) *
16 = bbl (us;tank) *
17 = gal (imp) *
18 = Mgal (imp) *
19 = bbl (imp;beer) *
20 = bbl (imp;oil) *
22 = kgal (us) *
23 = Mft³ *
50 = g *
51 = kg *
52 = t *
53 = oz *
54 = lb *
55 = STon *
251 = None *

Totalizer operation mode 1: 2605 Integer Read / Write 0 = Net flow total 60
2: 2805 1 = Forward flow total
3: 3005 2 = Reverse flow total

Control Totalizer 1 to n 1: 2608 Integer Read / Write 0 = Totalize 60


2: 2808 1 = Reset + totalize
3: 3008 2 = Preset + hold
3 = Reset + hold
5 = Hold

Preset value 1 to n 1: 2590 to 2591 Float Read / Write Signed floating-point number 61
2: 2592 to 2593
3: 2594 to 2595

Failure mode 1: 2606 Integer Read / Write 0 = Stop 61


2: 2806 1 = Actual value
3: 3006 2 = Last valid value

* Visibility depends on order options or device settings

132 Endress+Hauser
Proline Promag 10 Modbus RS485 Modbus RS485 register information

"Sensor" submenu
"Process parameters" submenu

Navigation: Application → Sensor → Process parameters

Parameter Register Data type Access Selection / User entry / User interface → 

Flow damping 2274 Integer Read / Write 0 to 15 64

Flow override 5503 Integer Read / Write 0 = Off 64


1 = On

Conductivity measurement 2268 Integer Read / Write 0 = Off 64


1 = On

Conductivity temperature coefficient 2886 to 2887 Float Read / Write Signed floating-point number 65

Fixed density 2830 to 2831 Float Read / Write Positive floating-point number 66

"Low flow cut off" submenu

Navigation: Application → Sensor → Low flow cut off

Parameter Register Data type Access Selection / User entry / User interface → 

Low flow cut off 5101 Integer Read / Write 0 = Off 66


1 = Volume flow
11 = Mass flow

On value low flow cutoff 5138 to 5139 Float Read / Write Positive floating-point number 67

Off value low flow cutoff 5104 to 5105 Float Read / Write 0 to 100.0 % 67

"Empty pipe detection" submenu

Navigation: Application → Sensor → Empty pipe detection

Parameter Register Data type Access Selection / User entry / User interface → 

Empty pipe detection 5106 Integer Read / Write 0 = Off 68


1 = On

New adjustment 2335 Integer Read / Write 0 = Cancel 68


1 = Empty pipe adjust
2 = Full pipe adjust

Empty pipe adjust value 2181 to 2182 Float Read Positive floating-point number 68

Full pipe adjust value 2832 to 2833 Float Read Positive floating-point number 69

Measured value EPD 2298 to 2299 Float Read Positive floating-point number 69

"Sensor adjustment" submenu

Navigation: Application → Sensor → Sensor adjustment

Parameter Register Data type Access Selection / User entry / User interface → 

Installation direction 5501 Integer Read / Write 0 = Forward flow 69


1 = Reverse flow

Integration time 2260 to 2261 Float Read 1 to 65 ms 70

Measuring period 2852 to 2853 Float Read 0 to 1 000 ms 70

Endress+Hauser 133
Modbus RS485 register information Proline Promag 10 Modbus RS485

"Calibration" submenu

Navigation: Application → Sensor → Calibration

Parameter Register Data type Access Selection / User entry / User interface → 

Nominal diameter 2048 to 2057 String Read Character string comprising numbers, 70
letters and special characters

Calibration factor 2313 to 2314 Float Read Positive floating-point number 71

Zero point 2870 to 2871 Float Read Signed floating-point number 71

Conductivity calibration factor 19806 to 19807 Float Read 0.01 to 10 000 71

"Electrode cleaning cycle" submenu

Navigation: Application → Sensor → Electrode cleaning cycle

Parameter Register Data type Access Selection / User entry / User interface → 

Electrode cleaning cycle 2280 Integer Read / Write 0 = Off 72


1 = On

ECC duration 2330 to 2331 Float Read / Write 0.01 to 30 s 72

ECC recovery time 2332 to 2333 Float Read / Write 1 to 600 s 72

ECC interval 2328 to 2329 Float Read / Write 0.5 to 168 h 73

ECC polarity 2334 Integer Read 0 = Positive 73


1 = Negative

"Current output 1" submenu

Navigation: Application → Current output 1

Parameter Register Data type Access Selection / User entry / User interface → 
*
Process variable current output 5927 Integer Read / Write 0 = Off 74
1 = Volume flow
4 = Conductivity *
7 = Temperature *
9 = Corrected conductivity *
11 = Mass flow
40 = Noise *
41 = Coil current shot time *

Measuring mode current output 5899 Integer Read / Write 0 = Forward flow 75
2 = Reverse flow compensation
13 = Forward/Reverse flow *

Current range output 5923 Integer Read / Write 0 = 4...20 mA (4... 20.5 mA) 79
1 = 4...20 mA US (3.9...20.8 mA)
2 = 4...20 mA NE (3.8...20.5 mA)
4 = Fixed value

Fixed current 5987 to 5988 Float Read / Write 3.59 to 21.5 mA 80

Lower range value output 6195 to 6196 Float Read / Write Signed floating-point number 80

Upper range value output 5915 to 5916 Float Read / Write Signed floating-point number 82

Damping current output 5903 to 5904 Float Read / Write 0.0 to 999.9 s 82

Failure behavior current output 5911 Integer Read / Write 0 = Min. 83


1 = Max.
4 = Actual value
5 = Last valid value
6 = Fixed value

134 Endress+Hauser
Proline Promag 10 Modbus RS485 Modbus RS485 register information

Navigation: Application → Current output 1

Parameter Register Data type Access Selection / User entry / User interface → 

Failure current 5979 to 5980 Float Read / Write 3.59 to 21.5 mA 83

Output current 1 5931 to 5932 Float Read 3.59 to 21.5 mA 84

* Visibility depends on order options or device settings

"Communication" submenu
"Modbus configuration" submenu

Navigation: Application → Communication → Modbus configuration

Parameter Register Data type Access Selection / User entry / User interface → 

Bus address 4910 Integer Read / Write 1 to 247 85

Baudrate 4912 Integer Read / Write 0 = 1200 BAUD 86


1 = 2400 BAUD
2 = 4800 BAUD
3 = 9600 BAUD
4 = 19200 BAUD
5 = 38400 BAUD
6 = 57600 BAUD
7 = 115200 BAUD

Parity 4914 Integer Read / Write 0 = Even 86


1 = Odd
2 = None / 2 stop bits
3 = None / 1 stop bit

Byte order 4915 Integer Read / Write 0 = 0-1-2-3 87


1 = 3-2-1-0
2 = 2-3-0-1
3 = 1-0-3-2

Telegram delay 4916 to 4917 Float Read / Write 0 to 100 ms 87

Failure mode 4920 Integer Read / Write 1 = Last valid value 87


255 = NaN value

Fieldbus writing access 6807 Integer Read / Write 0 = Read + write 88


1 = Read only

"Modbus data map" submenu

Navigation: Application → Communication → Modbus data map

Parameter Register Data type Access Selection / User entry / User interface → 

Scan list register 0 to 15 0: 5001 Integer Read / Write 0 to 65 535 88


1: 5002
2: 5003
3: 5004
4: 5005
5: 5006
6: 5007
7: 5008
8: 5009
9: 5010
10: 5011
11: 5012
12: 5013
13: 5014
14: 5015
15: 5016

Endress+Hauser 135
Modbus RS485 register information Proline Promag 10 Modbus RS485

"Modbus information" submenu

Navigation: Application → Communication → Modbus information

Parameter Register Data type Access Selection / User entry / User interface → 

Device ID 2547 Integer Read 0 to 65 535 89

Device revision 4481 Integer Read 0 to 65 535 89

6.3.4 "System" menu

"Device management" submenu

Navigation: System → Device management

Parameter Register Data type Access Selection / User entry / User interface → 

Device tag 29243 to 29258 String Read / Write Character string comprising numbers, 91
letters and special characters (32)

Locking status 4918 Integer Read 256 = Hardware locked 91


512 = Temporarily locked

Configuration counter 4818 Integer Read 0 to 65 535 92

Device reset 6817 Integer Read / Write 0 = Cancel 92


1 = Restart device
2 = To delivery settings
25 = Restore S-DAT backup *
35 = Restore T-DAT backup *
36 = Create T-DAT backup

* Visibility depends on order options or device settings

"User management" submenu

Navigation: System → User management

Parameter Register Data type Access Selection / User entry / User interface → 

User role 2178 Integer Read 0 = Operator 93


1 = Maintenance
2 = Service
3 = Production
4 = Development

Enter access code 2177 Integer Read / Write 0 to 9 999 94

Reset Maintenance code 8880 to 8895 String Read / Write Character string comprising numbers, 94
letters and special characters (32)

"Define Maintenance code" wizard

Navigation: System → User management → Define Maintenance code

Parameter Register Data type Access Selection / User entry / User interface → 

Define Maintenance code 29482 Integer Read / Write 0 to 9 999 95

Confirm Maintenance code 29481 Integer Read / Write 0 to 9 999 95

136 Endress+Hauser
Proline Promag 10 Modbus RS485 Modbus RS485 register information

"Connectivity" submenu
"Bluetooth configuration" submenu

Navigation: System → Connectivity → Bluetooth configuration

Parameter Register Data type Access Selection / User entry / User interface → 

Bluetooth 27662 Integer Read / Write 0 = Disable 96


1 = Enable
4 = Not available *

Communication established 27927 Integer Read 0 = Yes 96


1 = No

* Visibility depends on order options or device settings

"Date/time" submenu

Navigation: System → Date/time

Parameter Register Data type Access Selection / User entry / User interface → 

Time format 2150 Integer Read / Write 12 = 12 h AM/PM 97


24 = 24 h

Time zone 27339 Integer Read / Write 0 = UTC 00:00 97


1 = UTC+01:00
2 = UTC+02:00
3 = UTC+03:00
4 = UTC+04:00
5 = UTC+05:00
6 = UTC+06:00
7 = UTC+07:00
8 = UTC+08:00
9 = UTC+09:00
10 = UTC+10:00
11 = UTC+11:00
12 = UTC+12:00
13 = UTC+13:00
14 = UTC+14:00
35 = UTC+03:30
45 = UTC+04:30
55 = UTC+05:30
57 = UTC+05:45
65 = UTC+06:30
87 = UTC+08:45
95 = UTC+09:30
105 = UTC+10:30
127 = UTC+12:45
135 = UTC-03:30
195 = UTC-09:30
201 = UTC-01:00
202 = UTC-02:00
203 = UTC-03:00
204 = UTC-04:00
205 = UTC-05:00
206 = UTC-06:00
207 = UTC-07:00
208 = UTC-08:00
209 = UTC-09:00
210 = UTC-10:00
211 = UTC-11:00
212 = UTC-12:00

Endress+Hauser 137
Modbus RS485 register information Proline Promag 10 Modbus RS485

"Information" submenu
"Device" submenu

Navigation: System → Information → Device

Parameter Register Data type Access Selection / User entry / User interface → 

Device name 7263 to 7270 String Read Character string comprising numbers, 99
letters and special characters

Device tag 2026 to 2041 String Read Character string comprising numbers, 100
letters and special characters

Serial number 7003 to 7008 String Read Character string comprising numbers, 100
letters and special characters

Order code 2058 to 2067 String Read Character string comprising numbers, 100
letters and special characters

Firmware version 7277 to 7280 String Read Character string comprising numbers, 100
letters and special characters

Extended order code 1 2212 to 2221 String Read Character string comprising numbers, 101
letters and special characters

Extended order code 2 2222 to 2231 String Read Character string comprising numbers, 101
letters and special characters

Extended order code 3 2232 to 2241 String Read Character string comprising numbers, 101
letters and special characters

ENP version 4003 to 4010 String Read Character string comprising numbers, 101
letters and special characters

Manufacturer 8001 to 8016 String Read Character string comprising numbers, 102
letters and special characters

"Sensor electronic module (ISEM)" submenu

Navigation: System → Information → Sensor electronic module (ISEM)

Parameter Register Data type Access Selection / User entry / User interface → 

Firmware version 7039 Integer Read Positive integer 102

"Display module" submenu

Navigation: System → Information → Display module

Parameter Register Data type Access Selection / User entry / User interface → 

Firmware version 7039 Integer Read Positive integer 103

138 Endress+Hauser
Proline Promag 10 Modbus RS485 Modbus RS485 register information

"Display" submenu

Navigation: System → Display

Parameter Register Data type Access Selection / User entry / User interface → 

Language 35001 Integer Read / Write 0 = English 104


1 = Deutsch
2 = Français
3 = Español
4 = Italiano
5 = Nederlands
8 = Svenska
10 = Bahasa Indonesia
11 = 日本語 (Japanese)
12 = Portuguesa
13 = Polski
14 = русский язык (Russian)
15 = čeština (Czech)
16 = 中文 (Chinese)
17 = ภาษาไทย (Thai) *
18 = Türkçe
19 = tiếng Việt (Vietnamese)
20 = 한국어 (Korean)
21 = ‫( الْعَرَبيّة‬Arabic) *

Value 1 display 34918 Integer Read / Write 1 = Volume flow 105


4 = Conductivity *
7 = Temperature *
9 = Corrected conductivity *
11 = Mass flow
16 = Totalizer 1
17 = Totalizer 2
18 = Totalizer 3

Value 2 display 34919 Integer Read / Write 1 = Volume flow 105


4 = Conductivity *
7 = Temperature *
9 = Corrected conductivity *
11 = Mass flow
16 = Totalizer 1
17 = Totalizer 2
18 = Totalizer 3
251 = None

Value 3 display 34922 Integer Read / Write 1 = Volume flow 106


4 = Conductivity *
7 = Temperature *
9 = Corrected conductivity *
11 = Mass flow
16 = Totalizer 1
17 = Totalizer 2
18 = Totalizer 3
251 = None

Value 4 display 34923 Integer Read / Write 1 = Volume flow 106


4 = Conductivity *
7 = Temperature *
9 = Corrected conductivity *
11 = Mass flow
16 = Totalizer 1
17 = Totalizer 2
18 = Totalizer 3
251 = None

Display damping 27602 to 27603 Float Read / Write 0.0 to 999.9 s 106

Rotation display 36770 Integer Read / Write 0 = 0 degree 107


8 = Auto
9 = 90 degree
18 = 180 degree
27 = 270 degree

Endress+Hauser 139
Modbus RS485 register information Proline Promag 10 Modbus RS485

Navigation: System → Display

Parameter Register Data type Access Selection / User entry / User interface → 

Brightness 36768 to 36769 Float Read / Write 0 to 100 % 107

Color scheme 30228 Integer Read / Write 11 = Light 107


12 = Dark

* Visibility depends on order options or device settings

"Software configuration" submenu

Navigation: System → Software configuration

Parameter Register Data type Access Selection / User entry / User interface → 

Activate SW option 2795 Integer Read / Write Positive integer 108

Software option overview 2902 Integer Read 16384 = Heartbeat Monitoring 108
32768 = Heartbeat Verification

140 Endress+Hauser
Proline Promag 10 Modbus RS485 Index

Index
A Date / Time (Submenu) . . . . . . . . . . . . . . . . . . . . . . . 97
Activate SW option (Parameter) . . . . . . . . . . . . . . . 108 Define access code (Wizard) . . . . . . . . . . . . . . . . . . . 95
Active diagnostics (Submenu) . . . . . . . . . . . . . . . . . . 30 Density unit (Parameter) . . . . . . . . . . . . . . . . . . . 12, 56
Actual diagnostics (Parameter) . . . . . . . . . . . . . . . . . 30 Device (Submenu) . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Alarm delay (Parameter) . . . . . . . . . . . . . . . . . . . . . . 39 Device alarm simulation (Parameter) . . . . . . . . . . . . . 37
Application (Menu) . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Device management (Submenu) . . . . . . . . . . . . . . . . . 91
Assign behavior of diagnostic no. 043 (Parameter) . . . 40 Device name (Parameter) . . . . . . . . . . . . . . . . . . . . 8, 99
Assign behavior of diagnostic no. 230 (Parameter) . . . 41 Device reset (Parameter) . . . . . . . . . . . . . . . . . . . . . . 92
Assign behavior of diagnostic no. 231 (Parameter) . . . 41 Device tag (Parameter) . . . . . . . . . . . . . . . . . 8, 91, 100
Assign behavior of diagnostic no. 302 (Parameter) . . . 41 Diagnostic configuration (Submenu) . . . . . . . . . . . . . 39
Assign behavior of diagnostic no. 376 (Parameter) . . . 41 Diagnostic event category (Parameter) . . . . . . . . . . . . 37
Assign behavior of diagnostic no. 377 (Parameter) . . . 42 Diagnostic event simulation (Parameter) . . . . . . . . . . 37
Assign behavior of diagnostic no. 441 (Parameter) . . . 43 Diagnostic list (Submenu) . . . . . . . . . . . . . . . . . . . . . 32
Assign behavior of diagnostic no. 832 (Parameter) . . . 44 Diagnostic settings (Submenu) . . . . . . . . . . . . . . . . . . 39
Assign behavior of diagnostic no. 833 (Parameter) . . . 44 Diagnostics (Menu) . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Assign behavior of diagnostic no. 834 (Parameter) . . . 45 Diagnostics 1 (Parameter) . . . . . . . . . . . . . . . . . . . . . 32
Assign behavior of diagnostic no. 835 (Parameter) . . . 45 Diagnostics 2 (Parameter) . . . . . . . . . . . . . . . . . . . . . 33
Assign behavior of diagnostic no. 842 (Parameter) . . . 46 Diagnostics 3 (Parameter) . . . . . . . . . . . . . . . . . . . . . 33
Assign behavior of diagnostic no. 937 (Parameter) . . . 46 Diagnostics 4 (Parameter) . . . . . . . . . . . . . . . . . . . . . 33
Assign behavior of diagnostic no. 938 (Parameter) . . . 47 Diagnostics 5 (Parameter) . . . . . . . . . . . . . . . . . . . . . 34
Assign behavior of diagnostic no. 961 (Parameter) . . . 47 Display (Submenu) . . . . . . . . . . . . . . . . . . . . . . . . . 104
Assign behavior of diagnostic no. 962 (Parameter) . . . 48 Display damping (Parameter) . . . . . . . . . . . . . . . 26, 106
Assign process variable (Parameter) . . . . . . . . . . . 13, 59 Display module (Submenu) . . . . . . . . . . . . . . . . . . . 102
Assign simulation process variable (Parameter) . . . . . 35 Document
Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
B
Bluetooth (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 96 E
Bluetooth configuration (Submenu) . . . . . . . . . . . . . . 96 ECC duration (Parameter) . . . . . . . . . . . . . . . . . . . . . 72
Brightness (Parameter) . . . . . . . . . . . . . . . . . . . . . . 107 ECC interval (Parameter) . . . . . . . . . . . . . . . . . . . . . . 73
ECC polarity (Parameter) . . . . . . . . . . . . . . . . . . . . . . 73
C ECC recovery time (Parameter) . . . . . . . . . . . . . . . . . 72
Calibration (Submenu) . . . . . . . . . . . . . . . . . . . . . . . . 70 Electrode cleaning cycle (Parameter) . . . . . . . . . . . . . 72
Calibration factor (Parameter) . . . . . . . . . . . . . . . . . . 71 Electrode cleaning cycle (Submenu) . . . . . . . . . . . . . . 72
Color scheme (Parameter) . . . . . . . . . . . . . . . . . . . . 107 Electronics (Submenu) . . . . . . . . . . . . . . . . . . . . . . . . 40
Commissioning (Wizard) Empty pipe adjust value (Parameter) . . . . . . . . . . . . . 19
. . . . . . . . . . . . . . . 6, 8, 9, 13, 15, 16, 17, 19, 20, 25, 27 Empty pipe detection (Parameter) . . . . . . . . . . . . . . . 19
Communication (Submenu) . . . . . . . . . . . . . . . . . . . . 85 ENP version (Parameter) . . . . . . . . . . . . . . . . . . . . . 101
Communication established (Parameter) . . . . . . . . . . 96 Enter access code (Parameter) . . . . . . . . . . . . . . . . . . 94
Conductivity (Parameter) . . . . . . . . . . . . . . . . . . . . . . 50 Extended order code 1 (Parameter) . . . . . . . . . . . . . 101
Conductivity calibration factor (Parameter) . . . . . . . . 71 Extended order code 2 (Parameter) . . . . . . . . . . . . . 101
Conductivity damping time (Parameter) . . . . . . . . . . . 65 Extended order code 3 (Parameter) . . . . . . . . . . . . . 101
Conductivity measurement (Parameter) . . . . . . . . . . . 64
Conductivity temperature coefficient (Parameter) . . . . 65 F
Conductivity unit (Parameter) . . . . . . . . . . . . . . . 12, 56 Failure behavior current output (Parameter) . . . . . 23, 83
Configuration (Submenu) . . . . . . . . . . . . . . . . . . . . . 43 Failure current (Parameter) . . . . . . . . . . . . . . . . . 24, 83
Configuration counter (Parameter) . . . . . . . . . . . . . . 92 Failure mode (Parameter) . . . . . . . . . . . . . . . . . . 15, 61
Connectivity (Submenu) . . . . . . . . . . . . . . . . . . . . . . 96 Firmware version (Parameter) . . . . . . . 8, 100, 102, 103
Control Totalizer 1 to n (Parameter) . . . . . . . . . . . . . . 60 Fixed current (Parameter) . . . . . . . . . . . . . . . . . . 23, 80
Corrected conductivity (Parameter) . . . . . . . . . . . . . . 50 Fixed density (Parameter) . . . . . . . . . . . . . . . . . . . . . 66
Current output 1 (Submenu) . . . . . . . . . . . . . . . . . . . 74 Flow damping (Parameter) . . . . . . . . . . . . . . . . . 15, 64
Current output 1 simulation (Parameter) . . . . . . . . . . 36 Flow override (Parameter) . . . . . . . . . . . . . . . . . . . . . 64
Current output value (Parameter) . . . . . . . . . . . . . . . 36 Full pipe adjust value (Parameter) . . . . . . . . . . . . . . . 19
Current range output (Parameter) . . . . . . . . . . . . 20, 79
G
D Guidance (Menu) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Damping current output (Parameter) . . . . . . . . . . 23, 82

Endress+Hauser 141
Index Proline Promag 10 Modbus RS485

H S
Heartbeat Technology (Submenu) . . . . . . . . . . . . . . . 38 Sensor (Submenu) . . . . . . . . . . . . . . . . . . . . . . . . 40, 63
Sensor adjustment (Submenu) . . . . . . . . . . . . . . . . . . 69
I Sensor electronic module (ISEM) (Submenu) . . . . . . 102
Information (Submenu) . . . . . . . . . . . . . . . . . . . . . . . 99 Serial number (Parameter) . . . . . . . . . . . . . . . . . . 8, 100
Installation direction (Parameter) . . . . . . . . . . . . . . . 69 Set date/time (Parameter) . . . . . . . . . . . . . . . . . . . . . 28
Integration time (Parameter) . . . . . . . . . . . . . . . . . . . 70 Simulation (Submenu) . . . . . . . . . . . . . . . . . . . . . . . . 35
Software configuration (Submenu) . . . . . . . . . . . . . . 108
L Software option overview (Parameter) . . . . . . . . . . . 108
Language (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 104 Submenu
Locking status (Parameter) . . . . . . . . . . . . . . . . . . . . 91 Active diagnostics . . . . . . . . . . . . . . . . . . . . . . . . 30
Low flow cut off (Parameter) . . . . . . . . . . . . . . . . 17, 66 Bluetooth configuration . . . . . . . . . . . . . . . . . . . . 96
Low flow cut off (Submenu) . . . . . . . . . . . . . . . . . . . . 66 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Lower range value output (Parameter) . . . . . . . . . 21, 80 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
M Connectivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Manufacturer (Parameter) . . . . . . . . . . . . . . . . . . . . 102 Current output 1 . . . . . . . . . . . . . . . . . . . . . . . . . 74
Mass flow (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 49 Date / Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Mass flow unit (Parameter) . . . . . . . . . . . . . . . . . 11, 55 Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Mass unit (Parameter) . . . . . . . . . . . . . . . . . . . . . 11, 55 Device management . . . . . . . . . . . . . . . . . . . . . . . 91
Measured values (Submenu) . . . . . . . . . . . . . . . . . . . 49 Diagnostic configuration . . . . . . . . . . . . . . . . . . . . 39
Measuring mode current output (Parameter) . . . . . . . 75 Diagnostic list . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Measuring period (Parameter) . . . . . . . . . . . . . . . . . . 70 Diagnostic settings . . . . . . . . . . . . . . . . . . . . . . . . 39
Menu Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Display module . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Electrode cleaning cycle . . . . . . . . . . . . . . . . . . . . 72
Guidance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Electronics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 Heartbeat Technology . . . . . . . . . . . . . . . . . . . . . 38
Modbus configuration (Submenu) . . . . . . . . . . . . . . . 85 Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Modbus data map (Submenu) . . . . . . . . . . . . . . . . . . 88 Low flow cut off . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Modbus information (Submenu) . . . . . . . . . . . . . . . . 89 Measured values . . . . . . . . . . . . . . . . . . . . . . . . . 49
Modbus configuration . . . . . . . . . . . . . . . . . . . . . 85
N
Modbus data map . . . . . . . . . . . . . . . . . . . . . . . . . 88
Nominal diameter (Parameter) . . . . . . . . . . . . . . . . . 70
Modbus information . . . . . . . . . . . . . . . . . . . . . . . 89
O Partially filled pipe detection . . . . . . . . . . . . . . . . . 67
Off value low flow cutoff (Parameter) . . . . . . . . . . 18, 67 Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
On value low flow cutoff (Parameter) . . . . . . . . . . 18, 67 Process parameters . . . . . . . . . . . . . . . . . . . . . . . 63
Operating time (Parameter) . . . . . . . . . . . . . . . . . . . . 31 Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Operating time from restart (Parameter) . . . . . . . . . . 31 Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40, 63
Order code (Parameter) . . . . . . . . . . . . . . . . . . . . . . 100 Sensor adjustment . . . . . . . . . . . . . . . . . . . . . . . . 69
Output current 1 (Parameter) . . . . . . . . . . . . . . . . . . 84 Sensor electronic module (ISEM) . . . . . . . . . . . . . 102
Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
P Software configuration . . . . . . . . . . . . . . . . . . . . 108
Partially filled pipe detection (Submenu) . . . . . . . . . . 67 System units . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Preset value 1 to n (Parameter) . . . . . . . . . . . . . . . . . 61 Totalizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Pressure shock suppression (Parameter) . . . . . . . . . . 16 Totalizer 1 to n . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Previous diagnostics (Parameter) . . . . . . . . . . . . . . . . 30 Totalizer handling . . . . . . . . . . . . . . . . . . . . . . . . 58
Process (Submenu) . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Totalizers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Process parameters (Submenu) . . . . . . . . . . . . . . . . . 63 User management . . . . . . . . . . . . . . . . . . . . . . . . 93
Process variable current output (Parameter) . . . . . 20, 74 System (Menu) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Process variable value (Parameter) . . . . . . . . . . . . . . . 36 System units (Submenu) . . . . . . . . . . . . . . . . . . . . . . 53
Properties (Submenu) . . . . . . . . . . . . . . . . . . . . . . . . 39
T
R Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Reset all totalizers (Parameter) . . . . . . . . . . . . . . . . . 58 Temperature (Parameter) . . . . . . . . . . . . . . . . . . . . . 51
Reset Maintenance code (Parameter) . . . . . . . . . . . . . 94 Temperature damping time (Parameter) . . . . . . . . . . 66
Rotation display (Parameter) . . . . . . . . . . . . . . . . . . 107 Temperature unit (Parameter) . . . . . . . . . . . . . . . 12, 56
Time format (Parameter) . . . . . . . . . . . . . . . . . . . . . . 27
Time zone (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 27

142 Endress+Hauser
Proline Promag 10 Modbus RS485 Index

Timestamp (Parameter) . . . . . . . . . . . 30, 31, 32, 33, 34


Totalizer (Submenu) . . . . . . . . . . . . . . . . . . . . . . . . . 51
Totalizer 1 to n (Submenu) . . . . . . . . . . . . . . . . . . . . 58
Totalizer handling (Submenu) . . . . . . . . . . . . . . . . . . 58
Totalizer operation mode (Parameter) . . . . . . . . . 14, 60
Totalizer overflow 1 to n (Parameter) . . . . . . . . . . . . . 52
Totalizer value 1 to n (Parameter) . . . . . . . . . . . . . . . 51
Totalizers (Submenu) . . . . . . . . . . . . . . . . . . . . . . . . 58

U
Unit totalizer 1 to n (Parameter) . . . . . . . . . . . . . 13, 59
Upper range value output (Parameter) . . . . . . . . . 22, 82
User management (Submenu) . . . . . . . . . . . . . . . . . . 93
User role (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 93

V
Value 1 display (Parameter) . . . . . . . . . . . . . . . . 25, 105
Value 2 display (Parameter) . . . . . . . . . . . . . . . . 25, 105
Value 3 display (Parameter) . . . . . . . . . . . . . . . . 26, 106
Value 4 display (Parameter) . . . . . . . . . . . . . . . . 26, 106
Volume flow (Parameter) . . . . . . . . . . . . . . . . . . . . . 50
Volume flow unit (Parameter) . . . . . . . . . . . . . . . . 9, 53
Volume unit (Parameter) . . . . . . . . . . . . . . . . . . . 10, 54

W
Wizard
Commissioning 6, 8, 9, 13, 15, 16, 17, 19, 20, 25, 27
Define access code . . . . . . . . . . . . . . . . . . . . . . . . 95

Z
Zero point (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 71

Endress+Hauser 143
*71575137*
71575137