Product Manual Version: V1.
1 Product overview
1.1 JTY-GD-A30E point-type photoelectric smoke detector (after this referred to as
detector) is a photoelectric smoke detector. The detector has a built-in
microprocessor, supports electrical coding, and accesses the compatible fire alarm
control system through the two-wire bus. The detector can collect the smoke
concentration data in real-time, and transmit the data to the fire alarm control
system, and receive and execute the control command given by the fire alarm control
system.
1.2 The detector is suitable for a significant quantity of smoke when a fire occurs and no smoke under normal
circumstances.Such as restaurants, hotels, teaching buildings, office buildings, computer rooms, communication
computer rooms, libraries, archives and other industrial and civil facilities. However, it is not suitable for places with a
lot of dust and water mist retention, where the places may produce steam and oil mist and retain smoke under normal
circumstances.
2 Product features
2.1 It can realize electronic coding and rewrite the address via coder in situ.
2.2 Within a single-chip microcomputer, it can process the sampling data in real-time, save the latest 144 historical data
and realize a curve tracing for the field situation.
2.3 It has a temperature, humidity and dust accumulation drift compensation function and a sensor fault detection
function (fault reporting to fire alarm control panel).
2.4 Non-polarity, two-bus connection that ensures convenient installation and maintenance.
2.5 Designed with an upper cover and a lower cover and installed on an independent base, it can be installed, debugged
and maintained conveniently.
3 Technical parameters
3.1 Items Parameters
Executive standard GB 4715-2005
Wiring mode Non-polarity two-bus system
Working current inspection status<300uA, alarming status<1.5mA
Weight about 75g
Product dimension diameter: 105mm, height: 43mm(With base)
Installation Height ≤12m
Temperature -10℃~+55℃ RH≤95%(40 ℃±2℃, without condensation)
It can realize electronic coding via coder in situ. Address codes 1 to 324 are available for
Coding mode
selection.
Operating instruction monitoring status: red indicator shining; alarm status: red indicator steady on
about 60m², specific reference to the national standard GB 50116-2013 "Code for Design of
Protection area
automatic fire alarm system" relevant provisions
www.sanjiang-security.com Page 1 of 5 Template (Version):T-006(V01.05)
Product Manual Version: V1.0
Connecting host fire alarm control panel, fire linkage control panel
4 Product Appearance and Size (see Fig.1)
4.1
Fig.1(Unit: mm)
5 Use and engineering application
5.1 Schematic diagram of supporting mounting base (DZ-A16), as shown in Fig. 2:
Terminal definition: (Non-polarity two-bus system)
1 -- Signal terminal L1
2 -- Null
3 -- Signal terminal L2
4 -- Null
Fig.2
5.2 Wiring method: The detector can connect to the compatible fire alarm control system through the two-wire bus, and the
non-polarity connection is adopted. The L1 and L2 of the two-wire bus should connect to the terminal 1 and 3 of the
matched mounting base. Fig. 3 shows a schematic diagram of connecting multiple detectors and control panel.
Addressable
Fire Alarm
Control Panel
Fig. 3
5.3 Address code: As shown in Fig.4, connect the detector through the detector base on the encoder. L1 and L2 use a
non-polarity connection, set the encoder as the coding function, prepare the correct address code, and press the "Run"
key to complete the address code setting. (Note: Please refer to the encoder instruction manual for detailed operation)
Fig.4
www.sanjiang-security.com Page 2 of 5 Template (Version):T-006(V01.05)
Product Manual Version: V1.0
6 Installation and debugging
6.1 According to the national standard GB 50116-2013, "Code for Design of Automatic Fire Alarm System," and the national
standard GB 50166-2019, "Standard for Construction and Acceptance of Automatic Fire Alarm System," the relevant
provisions and requirements to determine the installation position, installation spacing and number of detectors in the
protected area.
The installation of the detector requires the use of a supporting base, shown in Fig.5. The external dimension is 105mm×
13mm(diameter × thickness), the fixed hole diameter is 4.5mm, and the spacing of fixed holes is 45mm ~ 65mm.
Fig.5
Wiring requirements:
It is proper to use RVS twisted pairs with a section area of equal to or larger than 1.0mm2 for the signal buses L1 and L2.
The specific methods of installation and debugging are as follows:
a. Make sure the type of the detector matches the type of the host machine of the fire alarm control panel;
b. Use two M4 screws to fix the matched mounting base on the designated position via the mounting holes C and D
shown in Fig.5, as instructed in the construction drawing and make sure the matched mounting base has been firmly
installed.
c. Use a coder to make the detector coded according to the detector address on the construction drawing.
d. Disconnect the power supply of the fire alarm control panel and connect the detector correctly according to the
construction drawing;
e. Align the indicator light at detector A (as shown in Fig.1) with the pattern at base B (as shown in Fig.5), and then
insert the detector into the base, turn the detector clockwise until the detector is locked in place;
f. After all the products are installed and checked, connect the power supply of the fire alarm control panel and
conduct automatic login.;
g. When automatic login is success, the red indicator of the detector will blink once about every 12 seconds, which
suggests that the detector has begun to operate normally.;
h. Finally conduct an alarm test for the detector through some special tools or direct smoke blowing. After the detector
gives a fire alarm, the indicator will remain lit and the fire alarm control panel will simultaneously show
corresponding alarm prompt information. After the alarm test, reset the fire alarm control panel and restore to the
monitoring status.
7 Precautions
7.1 a. A detector can not share an address with other equipment in a single bus circuit, or else an address conflict may
occur.
www.sanjiang-security.com Page 3 of 5 Template (Version):T-006(V01.05)
Product Manual Version: V1.0
b. Do not remove the protective cover that comes with the detector before it is opened and used after the on-site
installation to avoid the detector contamination.
c. The protected area and installed number of detectors shall comply with the relevant provisions of the national
standard GB 50116-2013 "Code for Design of Automatic Fire Alarm System" and the national standard GB 50166-2019
"Standard for Construction and Acceptance of Automatic Fire Alarm System."
8 Maintenance and Upkeep
8.1 Warning: Before the detector is maintained, the relevant management department should be notified that the system
will be maintained and the monitoring will be temporarily stopped. At the same time, the logical control function of the
area or system to be maintained should be cut off, so as not to cause unnecessary alarm linkage. After the test is over,
notify the management department to restore the system to normal..
a. Ensure that each detector is checked for fire function at least once a year.
b. Operating environment has a great influence on the performance of the detector. If the detector is installed and used
in a place where its normal use is easily affected by dust, high wind speed and other factors, its maintenance period
should be shortened.
c. If a detector fails due to a material defect or a manufacturing process defect under normal conditions of use in one
year following the date of its delivery, we shall repair or replace it for free. However, the faults of the detector due to
artificial damage, improper use, or authorized adjustment, reconstruction or disassembly are not covered in the
guarantee and we shall assume no responsibilities for any the consequence thereby caused.
d. We may provide paid repair service for products with any faults beyond the guarantee range. If you have such
products that need repair, please contact us. When sending such a product to us for repair, you are expected to
provide some important information about the product, such as the phenomenon and possible cause of the product
fault, so that we can find out the cause of the fault in the shortest time and so the information may be used as a
reference in our future product development and improvement.
9 Failure Analysis and Elimination
9.1 Fault phenomena Analysis of Possible causes Methods of elimination Remarks
Send the detector back to the factory for
Can not be coded The internal circuit is damaged.
repair.
Can ’ t be logged into The detector has no address or
Recode the detector address.
normally. has a coincident address.
Send the detector back to the factory for
The sensor has failed.
repair.
Reports a fault after login
The labyrinth is seriously
Clean the labyrinth of the detector.
contaminated.
There is a great deal of smoke dust Log in again after the smoke, dust or the
or steam in the room. steam is eliminated.
The detector reports a fire Send the detector back to the factory for
The internal circuit has failed.
alarm after login. repair.
The labyrinth is seriously
Clean the labyrinth of the detector.
contaminated.
The indicator or the internal Send the detector back to the factory for
The detector cannot
circuit is damaged. repair.
www.sanjiang-security.com Page 4 of 5 Template (Version):T-006(V01.05)
Product Manual Version: V1.0
operate normally after
The contact with the base is poor. Inspect and reinstall the base.
being powered up.
The detector can ’ t send
Send the detector back to the factory for
out fire alarm signal The internal circuit is damaged.
repair.
during an alarm test.