10-2413 Masterbox Supervisor
Installation Instructions
DESCRIPTION
The 10-2413, Masterbox Supervisor is an interface
option to provide activation of a master box on a
Local Energy Type Auxiliary Fire Alarm System.
The interface is designed to activate a master box
over an electrical circuit that is electrically isolated
from the municipal system circuits. The assembly
includes the electronic circuit board mounted to a
polished steel cover plate. The plate can be
installed onto a 2 gang switch box, RACO 680 or
Exhibit 1: Masterbox Supervisor
equivalent.
COMPATIBILITY PROGRAMMING
The 10-2413 is compatible with the CyberCat Fire The C-Linx software requires the addressable
Alarm and Cheetah Xi Suppression Control notification output module to be configured in the
Systems. Each system requires the 10-2413 to be system on the addressable loop. The activation
interfaced with an addressable Supervised Control state should be programmed for ALARM. The
Module (P/N 55-042/55-047). module should be non-silenceable and it should be
non-functional for Walktest and Drill states.
SPECIFICATIONS
OPERATIONS
Input Voltage: 24VDC
Current Consumption: 22mA standby The Masterbox Supervisor will monitor that the
283mA alarm masterbox solenoid is connected and free from
Output: 2 Amp max. @ 24VDC ground faults. If the wiring is open, shorted, or
Power Limited grounded the NORM LED will turn OFF and the
Rated for 14.5 to 500 Ω coil addressable output module will register a trouble at
Minimum 18AWG wire the associated control panel. The same trouble
Dimensions (LxWxD): response would also be the case if 24V power is
4.56” x 4.5” x 1” removed from the module.
(11.6cm x 11.43cm x 2.54cm)
When the addressable output module activates from
Weight (Circuit Board): 0.32 lbs. (145 grams)
the programmed alarm state, it signals the
Operating Temp: 32ºF to 120ºF
Masterbox Supervisor to activate the Masterbox
(0ºC to 49ºC)
solenoid. It applies 24VDC to the coil for activation.
Operating Humidity: 93% RH, non-condensing
The module’s ACTIVE LED will turn ON; the NORM
LED will turn OFF. The output will remain active
LISTINGS AND APPROVALS
until Reset.
UL S3217
FM 3023436 SPARE PARTS
CSFM 7165-0900:137 CyberCat Non High-Rise
7170-0900:148 CyberCat High-Rise 10-2397 Masterbox Supervisor
7165-0900:149 Cheetah Xi Non High-Rise (Printed Circuit Board only)
MEA 490-04-E CyberCat 254/1016 10-2414 Cover Plate with Fike logo
307-05-E Cheetah Xi 02-2715 Standoff, 0.625” M/F, 6x32 hex
490-04-E Vol. 2 CyberCat 50 02-1589 Screw, 6-32 x 0.375 Phillips
307-05-E Vol. 2 Cheetah Xi 50 02-1361 Hex Nut, #6-32
City of Denver 4153-142 Lock Washer, #6
® th
Fike , 704 SW 10 Street, P.O. Box 610, Blue Springs, Missouri 64013-0610 U.S.A. ● Tel: (816) 229-3405 ● Fax: (816) 229-4615
While every precaution has been taken during the preparation of this document to ensure the accuracy of its content, Fike assumes no responsibility for errors or omissions.
Fike reserves the right to make changes to the product or this document without notice.
www.fike.com P/N 06-229 Rev. 3 page 1 of 2
INSTALLATION INSTRUCTIONS
1. If the system is already powered, disable critical
functions and power down system.
I CAUTION
The Masterbox Supervisor circuit board contains
static sensitive components. Handle the electronics
by the edges only and avoid touching the integrated
components. Keep the electronics in the protective
static bag it was shipped in until time for installation.
Always ground yourself with a proper wrist strap
before handling the module(s). If the installer is
properly grounded at all times, damage due to static
discharge will not occur. If the module requires
repair or return to Fike, it must be shipped in an anti-
static bag.
2. Carefully unpack the module and check for
shipping damage.
3. Install the Control Module and Power Supply
wiring to the module as noted in Exhibit 2.
4. Move SW1 to the position that appropriately
matches the resistance of the masterbox
solenoid coil (10-100Ω or 100-500Ω).
5. Apply power, program, and test for proper
operation.
6. Once proper operation is validated, fully secure
mounting plate to the switch box using the 4
screws provided.
TOP
MASTERBOX
P/N 10-2413
Exhibit 2: Masterbox Supervisor Wiring Diagram