0% found this document useful (0 votes)
19 views9 pages

2 Sws

The document presents a detailed overview of the New England Test System, which includes 39 buses, 9 generators, and 2 areas. It provides specific data on power flow, losses, and operational metrics for various buses and loads in the system. The information is crucial for analyzing the performance and efficiency of the power system.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as TXT, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
19 views9 pages

2 Sws

The document presents a detailed overview of the New England Test System, which includes 39 buses, 9 generators, and 2 areas. It provides specific data on power flow, losses, and operational metrics for various buses and loads in the system. The information is crucial for analyzing the performance and efficiency of the power system.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as TXT, PDF, TXT or read online on Scribd

PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS(R)E SUN, MAY 18 2025 14:29

NEW ENGLAND TEST SYSTEM, 39 BUSES, 9 GENERATORS, 2 AREAS, 4 RATING


%MVA FOR TRANSFORMERS
UPDATED BY JOSE CONTO SET 1
% I FOR NON-TRANSFORMER BRANCHES

BUS 1 BUS1 345.00 CKT MW MVAR MVA % 1.0314PU -12.27


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 1
355.85KV
MW MVAR 1 WEST 1 NWEST
TO 2 BUS2 345.00 1 96.5 29.0 100.7 56
0.45 5.29 1 WEST 1 NWEST
TO 39 GEN39 345.00 1 -96.5 -29.0 100.7 78
0.09 2.22 1 WEST 2 SWEST

BUS 2 BUS2 345.00 CKT MW MVAR MVA % 1.0025PU -14.34


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 2
345.85KV
MW MVAR 1 WEST 1 NWEST
TO 1 BUS1 345.00 1 -96.0 -96.0 135.8 77
0.45 5.29 1 WEST 1 NWEST
TO 3 LOAD3 345.00 1 557.1 286.7 626.6 96
5.18 60.13 1 WEST 1 NWEST
TO 25 LOAD25 345.00 1 -211.1 -53.0 217.7 84
3.25 3.99 1 WEST 1 NWEST
TO 30 GEN30 34.500 1 -250.0 -137.8 285.4 75 1.0250LK
0.00 15.42 1 WEST 1 NWEST

BUS 3 LOAD3 345.00 CKT MW MVAR MVA % 0.9535PU -19.15


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 3
328.95KV
MW MVAR 1 WEST 1 NWEST
TO LOAD-PQ 600.0 250.0 650.0
TO 2 BUS2 345.00 1 -552.0 -251.2 606.4 98
5.18 60.13 1 WEST 1 NWEST
TO 4 LOAD4 345.00 1 14.4 89.6 90.7 76
0.14 2.37 1 WEST 2 SWEST
TO 18 LOAD18 345.00 1 -62.5 -88.4 108.2 91
0.12 1.48 1 WEST 1 NWEST

BUS 4 LOAD4 345.00 CKT MW MVAR MVA % 0.9310PU -19.27


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 4
321.20KV
MW MVAR 1 WEST 2 SWEST
TO LOAD-PQ 450.0 184.0 486.2
TO SWITCHED SHUNT 0.0 -86.7 86.7
TO 3 LOAD3 345.00 1 -14.3 -106.9 107.8 93
0.14 2.37 1 WEST 1 NWEST
TO 5 BUS5 345.00 1 -202.2 109.0 229.7 82
0.50 7.98 1 WEST 2 SWEST
TO 14 BUS14 345.00 1 -233.6 -99.4 253.8 91
0.58 9.42 2 EAST 3 NEAST

BUS 5 BUS5 345.00 CKT MW MVAR MVA % 0.9174PU -17.47


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 5
316.52KV
MW MVAR 1 WEST 2 SWEST
TO SWITCHED SHUNT 0.0 -168.3 168.3
TO 4 LOAD4 345.00 1 202.7 -112.4 231.8 84
0.50 7.98 1 WEST 2 SWEST
TO 6 BUS6 345.00 1 -420.4 -7.2 420.5 99
0.42 5.46 1 WEST 2 SWEST
TO 8 LOAD8 345.00 1 217.7 288.0 361.1 85
1.27 17.83 1 WEST 2 SWEST

BUS 6 BUS6 345.00 CKT MW MVAR MVA % 0.9186PU -16.73


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 6
316.91KV
MW MVAR 1 WEST 2 SWEST
TO 5 BUS5 345.00 1 420.8 9.1 420.9 99
0.42 5.46 1 WEST 2 SWEST
TO 7 LOAD7 345.00 1 322.2 538.4 627.5 98
2.84 43.49 1 WEST 2 SWEST
TO 11 BUS11 345.00 1 -250.1 -255.0 357.2 83
1.03 12.11 1 WEST 2 SWEST
TO 31 GEN31 34.500 1 -492.9 -292.5 573.2 82 1.0000UN
0.00 97.33 1 WEST 2 SWEST

BUS 7 LOAD7 345.00 CKT MW MVAR MVA % 0.8626PU -18.63


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 7
297.58KV
MW MVAR 1 WEST 2 SWEST
TO LOAD-PQ 233.8 840.0 871.9
TO 6 BUS6 345.00 1 -319.4 -503.9 596.6 99
2.84 43.49 1 WEST 2 SWEST
TO 8 LOAD8 345.00 1 85.6 -336.1 346.8 87
0.64 7.32 1 WEST 2 SWEST

BUS 8 LOAD8 345.00 CKT MW MVAR MVA % 0.8799PU -19.03


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 8
303.58KV
MW MVAR 1 WEST 2 SWEST
TO LOAD-PQ 522.0 176.0 550.9
TO 5 BUS5 345.00 1 -216.5 -282.1 355.6 87
1.27 17.83 1 WEST 2 SWEST
TO 7 LOAD7 345.00 1 -85.0 337.5 348.0 86
0.64 7.32 1 WEST 2 SWEST
TO 9 BUS9 345.00 1 -220.6 -231.4 319.7 78
2.84 44.81 1 WEST 2 SWEST

BUS 9 BUS9 345.00 CKT MW MVAR MVA % 0.9788PU -14.03


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 9
337.69KV
MW MVAR 1 WEST 2 SWEST
TO 8 LOAD8 345.00 1 223.4 243.2 330.3 72
2.84 44.81 1 WEST 2 SWEST
TO 39 GEN39 345.00 1 -223.4 -243.2 330.3 84
0.88 22.03 1 WEST 2 SWEST

BUS 10 BUS10 345.00 CKT MW MVAR MVA % 0.9562PU -14.70


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 10
329.87KV
MW MVAR 1 WEST 2 SWEST
TO 11 BUS11 345.00 1 313.2 263.1 409.1 93
0.74 7.95 1 WEST 2 SWEST
TO 13 BUS13 345.00 1 336.8 52.8 340.9 83
0.51 5.48 1 WEST 2 SWEST
TO 32 GEN32 21.000 1 -650.0 -315.9 722.7 89 1.0700LK
0.00 130.81 1 WEST 2 SWEST

BUS 11 BUS11 345.00 CKT MW MVAR MVA % 0.9430PU -15.48


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 11
325.32KV
MW MVAR 1 WEST 2 SWEST
TO 6 BUS6 345.00 1 251.1 255.1 358.0 81
1.03 12.11 1 WEST 2 SWEST
TO 10 BUS10 345.00 1 -312.5 -261.7 407.6 94
0.74 7.95 1 WEST 2 SWEST
TO 12 LOAD12 138.00 1 61.3 6.6 61.7 49 1.0000UN
0.07 1.86 1 WEST 2 SWEST

BUS 12 LOAD12 138.00 CKT MW MVAR MVA % 0.9449PU -17.20


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 12
130.40KV
MW MVAR 1 WEST 2 SWEST
TO LOAD-PQ 120.0 30.0 123.7
TO 11 BUS11 345.00 1 -61.3 -4.8 61.5 49 1.0060LK
0.07 1.86 1 WEST 2 SWEST
TO 13 BUS13 345.00 1 -58.7 -25.2 63.9 51 1.0060LK
0.07 2.01 1 WEST 2 SWEST

BUS 13 BUS13 345.00 CKT MW MVAR MVA % 0.9523PU -15.59


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 13
328.56KV
MW MVAR 1 WEST 2 SWEST
TO 10 BUS10 345.00 1 -336.3 -54.0 340.6 83
0.51 5.48 1 WEST 2 SWEST
TO 12 LOAD12 138.00 1 58.8 27.2 64.8 52 1.0000UN
0.07 2.01 1 WEST 2 SWEST
TO 14 BUS14 345.00 1 277.5 26.7 278.7 77
0.78 8.71 2 EAST 3 NEAST

BUS 14 BUS14 345.00 CKT MW MVAR MVA % 0.9465PU -17.36


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 14
326.54KV
MW MVAR 2 EAST 3 NEAST
TO 4 LOAD4 345.00 1 234.2 96.7 253.3 89
0.58 9.42 1 WEST 2 SWEST
TO 13 BUS13 345.00 1 -276.7 -33.5 278.7 77
0.78 8.71 1 WEST 2 SWEST
TO 15 LOAD15 345.00 1 42.5 -63.1 76.1 64
0.08 0.97 2 EAST 3 NEAST

BUS 15 LOAD15 345.00 CKT MW MVAR MVA % 0.9565PU -17.99


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 15
329.98KV
MW MVAR 2 EAST 3 NEAST
TO LOAD-PQ 320.0 153.0 354.7
TO 14 BUS14 345.00 1 -42.5 31.0 52.5 44
0.08 0.97 2 EAST 3 NEAST
TO 16 LOAD16 345.00 1 -277.5 -184.0 333.0 81
1.06 11.10 2 EAST 3 NEAST

BUS 16 LOAD16 345.00 CKT MW MVAR MVA % 0.9767PU -16.49


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 16
336.97KV
MW MVAR 2 EAST 3 NEAST
TO LOAD-PQ 329.4 323.0 461.3
TO 15 LOAD15 345.00 1 278.6 179.1 331.2 79
1.06 11.10 2 EAST 3 NEAST
TO 17 BUS17 345.00 1 212.8 -1.6 212.8 84
0.33 4.23 1 WEST 1 NWEST
TO 19 BUS19 345.00 1 -449.7 -224.2 502.4 93
4.13 50.32 2 EAST 4 SEAST
TO 21 LOAD21 345.00 1 -328.8 -103.0 344.5 82
0.98 16.46 2 EAST 3 NEAST
TO 24 LOAD24 345.00 1 -42.4 -173.4 178.5 79
0.10 1.90 2 EAST 3 NEAST

BUS 17 BUS17 345.00 CKT MW MVAR MVA % 0.9750PU -17.63


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 17
336.36KV
MW MVAR 1 WEST 1 NWEST
TO 16 LOAD16 345.00 1 -212.4 -7.0 212.6 84
0.33 4.23 2 EAST 3 NEAST
TO 18 LOAD18 345.00 1 221.0 92.8 239.7 82
0.43 5.06 1 WEST 1 NWEST
TO 27 LOAD27 345.00 1 -8.6 -85.8 86.2 71
0.07 0.92 1 WEST 1 NWEST

BUS 18 LOAD18 345.00 CKT MW MVAR MVA % 0.9652PU -18.69


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 18
332.99KV
MW MVAR 1 WEST 1 NWEST
TO LOAD-PQ 158.0 30.0 160.8
TO 3 LOAD3 345.00 1 62.6 70.2 94.0 78
0.12 1.48 1 WEST 1 NWEST
TO 17 BUS17 345.00 1 -220.6 -100.2 242.2 84
0.43 5.06 1 WEST 1 NWEST

BUS 19 BUS19 345.00 CKT MW MVAR MVA % 1.0296PU -11.68


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 19
355.21KV
MW MVAR 2 EAST 4 SEAST
TO 16 LOAD16 345.00 1 453.8 243.9 515.2 91
4.13 50.32 2 EAST 3 NEAST
TO 20 LOAD20 138.00 1 175.0 -66.4 187.2 81 1.0600LK
0.26 5.12 2 EAST 4 SEAST
TO 33 GEN33 21.000 1 -628.8 -177.5 653.3 93 1.0700LK
3.23 65.47 2 EAST 4 SEAST

BUS 20 LOAD20 138.00 CKT MW MVAR MVA % 0.9798PU -13.16


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 20
135.21KV
MW MVAR 2 EAST 4 SEAST
TO LOAD-PQ 680.0 103.0 687.8
TO 19 BUS19 345.00 1 -174.7 71.5 188.8 82 1.0000UN
0.26 5.12 2 EAST 4 SEAST
TO 34 GEN34 15.500 1 -505.3 -174.5 534.6 95 1.0090LK
2.73 54.55 2 EAST 4 SEAST

BUS 21 LOAD21 345.00 CKT MW MVAR MVA % 0.9930PU -13.91


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 21
342.58KV
MW MVAR 2 EAST 3 NEAST
TO LOAD-PQ 274.0 115.0 297.2
TO 16 LOAD16 345.00 1 329.7 94.7 343.1 81
0.98 16.46 2 EAST 3 NEAST
TO 22 BUS22 345.00 1 -603.7 -209.7 639.1 99
3.27 57.27 2 EAST 3 NEAST

BUS 22 BUS22 345.00 CKT MW MVAR MVA % 1.0290PU -9.25


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 22
355.01KV
MW MVAR 2 EAST 3 NEAST
TO 21 LOAD21 345.00 1 607.0 240.8 653.0 98
3.27 57.27 2 EAST 3 NEAST
TO 23 LOAD23 345.00 1 43.0 49.1 65.2 51
0.03 0.48 2 EAST 4 SEAST
TO 35 GEN35 15.500 1 -650.0 -289.8 711.7 100 1.0250LK
0.00 71.86 2 EAST 3 NEAST

BUS 23 LOAD23 345.00 CKT MW MVAR MVA % 1.0233PU -9.46


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 23
353.03KV
MW MVAR 2 EAST 4 SEAST
TO LOAD-PQ 247.5 84.6 261.6
TO 22 BUS22 345.00 1 -43.0 -68.0 80.5 63
0.03 0.48 2 EAST 3 NEAST
TO 24 LOAD24 345.00 1 353.9 85.5 364.1 76
2.86 45.51 2 EAST 3 NEAST
TO 36 GEN36 12.500 1 -558.5 -102.1 567.7 101 1.0000LK
1.54 83.72 2 EAST 4 SEAST

BUS 24 LOAD24 345.00 CKT MW MVAR MVA % 0.9871PU -16.37


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 24
340.56KV
MW MVAR 2 EAST 3 NEAST
TO LOAD-PQ 308.6 -92.2 322.1
TO 16 LOAD16 345.00 1 42.5 168.7 174.0 77
0.10 1.90 2 EAST 3 NEAST
TO 23 LOAD23 345.00 1 -351.1 -76.5 359.3 78
2.86 45.51 2 EAST 4 SEAST

BUS 25 LOAD25 345.00 CKT MW MVAR MVA % 1.0212PU -13.50


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 25
352.33KV
MW MVAR 1 WEST 1 NWEST
TO LOAD-PQ 224.0 47.2 228.9
TO 2 BUS2 345.00 1 214.4 42.1 218.4 82
3.25 3.99 1 WEST 1 NWEST
TO 26 LOAD26 345.00 1 99.8 -0.7 99.8 78
0.33 3.30 1 WEST 1 NWEST
TO 37 GEN37 12.500 1 -538.2 -88.6 545.4 99 1.0250LK
1.80 69.53 1 WEST 1 NWEST

BUS 26 LOAD26 345.00 CKT MW MVAR MVA % 1.0103PU -15.24


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 26
348.57KV
MW MVAR 1 WEST 1 NWEST
TO LOAD-PQ 139.0 17.0 140.0
TO 25 LOAD25 345.00 1 -99.5 -48.9 110.9 88
0.33 3.30 1 WEST 1 NWEST
TO 27 LOAD27 345.00 1 291.0 122.2 315.6 82
1.41 14.80 1 WEST 1 NWEST
TO 28 LOAD28 345.00 1 -140.9 -43.4 147.4 83
0.84 9.22 2 EAST 3 NEAST
TO 29 LOAD29 345.00 1 -189.7 -46.8 195.4 84
2.01 22.05 2 EAST 3 NEAST

BUS 27 LOAD27 345.00 CKT MW MVAR MVA % 0.9876PU -17.59


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 27
340.72KV
MW MVAR 1 WEST 1 NWEST
TO LOAD-PQ 281.0 75.5 291.0
TO 17 BUS17 345.00 1 8.6 55.8 56.4 46
0.07 0.92 1 WEST 1 NWEST
TO 26 LOAD26 345.00 1 -289.6 -131.3 318.0 85
1.41 14.80 1 WEST 1 NWEST

BUS 28 LOAD28 345.00 CKT MW MVAR MVA % 1.0202PU -11.54


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 28
351.95KV
MW MVAR 2 EAST 3 NEAST
TO LOAD-PQ 206.0 27.6 207.8
TO 26 LOAD26 345.00 1 141.7 -27.8 144.4 81
0.84 9.22 1 WEST 1 NWEST
TO 29 LOAD29 345.00 1 -347.7 0.2 347.7 85
1.63 17.57 2 EAST 3 NEAST

BUS 29 LOAD29 345.00 CKT MW MVAR MVA % 1.0243PU -8.65


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 29
353.38KV
MW MVAR 2 EAST 3 NEAST
TO LOAD-PQ 283.5 126.9 310.6
TO 26 LOAD26 345.00 1 191.7 -37.7 195.3 83
2.01 22.05 1 WEST 1 NWEST
TO 28 LOAD28 345.00 1 349.3 -8.6 349.4 85
1.63 17.57 2 EAST 3 NEAST
TO 38 GEN38 34.500 1 -824.5 -80.6 828.4 99 1.0250LK
5.50 107.21 2 EAST 3 NEAST

BUS 30 GEN30 34.500 CKT MW MVAR MVA % 1.0046PU -11.70


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 30
FROM GENERATION 250.0 153.2H 293.2 107 34.658KV
MW MVAR 1 WEST 1 NWEST
TO 2 BUS2 345.00 1 250.0 153.2 293.2 77 1.0000UN
0.00 15.42 1 WEST 1 NWEST

BUS 31 GEN31 34.500 CKT MW MVAR MVA % 0.9208PU -9.07


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 31
FROM GENERATION 572.9 429.8H 716.2 86 31.769KV
MW MVAR 1 WEST 2 SWEST
TO LOAD-PQ 80.0 40.0 89.4
TO 6 BUS6 345.00 1 492.9 389.8 628.4 90 0.9143LK
0.00 97.33 1 WEST 2 SWEST

BUS 32 GEN32 21.000 CKT MW MVAR MVA % 0.9752PU -6.12


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 32
FROM GENERATION 650.0 446.7H 788.7 93 20.480KV
MW MVAR 1 WEST 2 SWEST
TO 10 BUS10 345.00 1 650.0 446.7 788.7 97 1.0000UN
0.00 130.81 1 WEST 2 SWEST
BUS 33 GEN33 21.000 CKT MW MVAR MVA % 0.9972PU -6.41
X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 33
FROM GENERATION 632.0 242.9R 677.1 58 20.941KV
MW MVAR 2 EAST 4 SEAST
TO 19 BUS19 345.00 1 632.0 242.9 677.1 97 1.0000UN
3.23 65.47 2 EAST 4 SEAST

BUS 34 GEN34 15.500 CKT MW MVAR MVA % 1.0123PU -7.94


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 34
FROM GENERATION 508.0 229.1R 557.3 52 15.691KV
MW MVAR 2 EAST 4 SEAST
TO 20 LOAD20 138.00 1 508.0 229.1 557.3 100 1.0000UN
2.73 54.55 2 EAST 4 SEAST

BUS 35 GEN35 15.500 CKT MW MVAR MVA % 1.0493PU -4.19


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 35
FROM GENERATION 650.0 361.7R 743.9 69 16.264KV
MW MVAR 2 EAST 3 NEAST
TO 22 BUS22 345.00 1 650.0 361.7 743.9 104 1.0000UN
0.00 71.86 2 EAST 3 NEAST

BUS 36 GEN36 12.500 CKT MW MVAR MVA % 1.0635PU -1.46


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 36
FROM GENERATION 560.0 185.8R 590.0 58 13.294KV
MW MVAR 2 EAST 4 SEAST
TO 23 LOAD23 345.00 1 560.0 185.8 590.0 105 1.0000UN
1.54 83.72 2 EAST 4 SEAST

BUS 37 GEN37 12.500 CKT MW MVAR MVA % 1.0278PU -6.53


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 37
FROM GENERATION 540.0 158.1R 562.7 58 12.847KV
MW MVAR 1 WEST 1 NWEST
TO 25 LOAD25 345.00 1 540.0 158.1 562.7 102 1.0000UN
1.80 69.53 1 WEST 1 NWEST

BUS 38 GEN38 34.500 CKT MW MVAR MVA % 1.0265PU -1.48


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 38
FROM GENERATION 830.0 187.8R 851.0 51 35.414KV
MW MVAR 2 EAST 3 NEAST
TO 29 LOAD29 345.00 1 830.0 187.8 851.0 102 1.0000UN
5.50 107.21 2 EAST 3 NEAST

BUS 39 GEN39 345.00 CKT MW MVAR MVA % 1.0300PU -10.96


X--- LOSSES ---X X---- AREA -----X X---- ZONE -----X 39
FROM GENERATION 720.9 345.6R 799.4 67 355.35KV
MW MVAR 1 WEST 2 SWEST
TO LOAD-PQ 400.0 250.0 471.7
TO 1 BUS1 345.00 1 96.6 -48.5 108.1 84
0.09 2.22 1 WEST 1 NWEST
TO 9 BUS9 345.00 1 224.3 144.1 266.6 65
0.88 22.03 1 WEST 2 SWEST

PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS(R)E SUN, MAY 18 2025 14:31


NEW ENGLAND TEST SYSTEM, 39 BUSES, 9 GENERATORS, 2 AREAS, 4
UPDATED BY JOSE CONTO

************************ SUMMARY FOR COMPLETE SYSTEM ************************


SYSTEM SWING BUS SUMMARY
X-------- SWING BUS --------X X---- AREA -----X X---- ZONE -----X
BUS#-SCT X-- NAME --X BASKV # X-- NAME --X # X-- NAME --X MW
MVAR MVABASE
39 GEN39 345.00 1 WEST 2 SWEST 720.9
345.6 1199.0

39 BUSES 10 PLANTS 10 MACHINES 0 INDUCTION GENS 0


INDUCTION MOTORS
19 LOADS 0 FIXED SHUNTS 2 SWITCHED SHUNTS
46 BRANCHES 12 TRANSFORMERS 0 DC LINES 0 FACTS DEVICES 0
GNE DEVICES

X------ ACTUAL ------X X----- NOMINAL ------X


MW MVAR MW MVAR
FROM GENERATION 5913.8 2740.8 5913.8 2740.8
FROM INDUCTION GENERATORS 0.0 0.0 0.0 0.0
TO CONSTANT POWER LOAD 5856.8 2780.6 5856.8 2780.6
TO CONSTANT CURRENT 0.0 0.0 0.0 0.0
TO CONSTANT ADMITTANCE 0.0 0.0 0.0 0.0
TO INDUCTION MOTORS 0.0 0.0 0.0 0.0
TO BUS SHUNT 0.0 -255.0 0.0 -300.0
TO FACTS DEVICE SHUNT 0.0 0.0 0.0 0.0
TO GNE BUS DEVICES 0.0 0.0 0.0 0.0
TO LINE SHUNT 0.0 0.0 0.0 0.0
FROM LINE CHARGING 0.0 1018.9 0.0 1034.3

VOLTAGE X----- LOSSES -----X X-- LINE SHUNTS --X CHARGING


LEVEL BRANCHES MW MVAR MW MVAR MVAR
345.0 37 41.96 630.42 0.0 0.0 1018.9
138.0 1 0.26 5.12 0.0 0.0 0.0
34.5 2 5.50 122.63 0.0 0.0 0.0
21.0 2 3.23 196.28 0.0 0.0 0.0
15.5 2 2.73 126.41 0.0 0.0 0.0
12.5 2 3.34 153.25 0.0 0.0 0.0
TOTAL 46 57.01 1234.12 0.0 0.0 1018.9

PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS(R)E SUN, MAY 18 2025 14:34


NEW ENGLAND TEST SYSTEM, 39 BUSES, 9 GENERATORS, 2 AREAS, 4
UPDATED BY JOSE CONTO

************************ SUMMARY FOR COMPLETE SYSTEM ************************

SYSTEM SWING BUS SUMMARY


X-------- SWING BUS --------X X---- AREA -----X X---- ZONE -----X
BUS#-SCT X-- NAME --X BASKV # X-- NAME --X # X-- NAME --X MW
MVAR MVABASE
39 GEN39 345.00 1 WEST 2 SWEST 736.4
558.4 1199.0

39 BUSES 10 PLANTS 10 MACHINES 0 INDUCTION GENS 0


INDUCTION MOTORS
19 LOADS 0 FIXED SHUNTS 0 SWITCHED SHUNTS
46 BRANCHES 12 TRANSFORMERS 0 DC LINES 0 FACTS DEVICES 0
GNE DEVICES

X------ ACTUAL ------X X----- NOMINAL ------X


MW MVAR MW MVAR
FROM GENERATION 5929.4 3332.2 5929.4 3332.2
FROM INDUCTION GENERATORS 0.0 0.0 0.0 0.0
TO CONSTANT POWER LOAD 5856.8 2780.6 5856.8 2780.6
TO CONSTANT CURRENT 0.0 0.0 0.0 0.0
TO CONSTANT ADMITTANCE 0.0 0.0 0.0 0.0
TO INDUCTION MOTORS 0.0 0.0 0.0 0.0
TO BUS SHUNT 0.0 0.0 0.0 0.0
TO FACTS DEVICE SHUNT 0.0 0.0 0.0 0.0
TO GNE BUS DEVICES 0.0 0.0 0.0 0.0
TO LINE SHUNT 0.0 0.0 0.0 0.0
FROM LINE CHARGING 0.0 957.1 0.0 1034.3

VOLTAGE X----- LOSSES -----X X-- LINE SHUNTS --X CHARGING


LEVEL BRANCHES MW MVAR MW MVAR MVAR
345.0 37 56.56 845.90 0.0 0.0 957.1
138.0 1 0.30 5.98 0.0 0.0 0.0
34.5 2 5.66 126.64 0.0 0.0 0.0
21.0 2 3.52 225.93 0.0 0.0 0.0
15.5 2 2.87 137.98 0.0 0.0 0.0
12.5 2 3.64 166.27 0.0 0.0 0.0
TOTAL 46 72.55 1508.70 0.0 0.0 957.1

PTI INTERACTIVE POWER SYSTEM SIMULATOR--PSS(R)E SUN, MAY 18 2025 14:37


NEW ENGLAND TEST SYSTEM, 39 BUSES, 9 GENERATORS, 2 AREAS, 4
UPDATED BY JOSE CONTO

BUSES WITH VOLTAGE GREATER THAN 1.1000:

BUS#-SCT X-- NAME --X BASKV AREA V(PU) V(KV) BUS#-SCT X-- NAME --X BASKV
AREA V(PU) V(KV)

* NONE *

BUSES WITH VOLTAGE LESS THAN 0.9000:

BUS#-SCT X-- NAME --X BASKV AREA V(PU) V(KV) BUS#-SCT X-- NAME --X BASKV
AREA V(PU) V(KV)
4 LOAD4 345.00 1 0.8454 291.68 5 BUS5 345.00
1 0.8172 281.93
6 BUS6 345.00 1 0.8197 282.81 7 LOAD7 345.00
1 0.7602 262.26
8 LOAD8 345.00 1 0.7821 269.83 10 BUS10 345.00
1 0.8672 299.19
11 BUS11 345.00 1 0.8507 293.48 12 LOAD12 138.00
1 0.8542 117.88
13 BUS13 345.00 1 0.8663 298.88 14 BUS14 345.00
2 0.8688 299.72
31 GEN31 34.500 1 0.8367 28.865 32 GEN32 21.000
1 0.8970 18.838

You might also like