Expansion Vessels. Reflex
Expansion Vessels. Reflex
Reflex, Refix
Expansion vessels
Pressure maintenance
Water uptake volume of a pressure expansion vessel Expansion volume flow and point of zero pressure
Pressure maintenance is required to compensate fluctuations A balancing volume flow must be transported via the
in volume between the maximum and the minimum system expansion line between the system and pressure
temperature and thus to maintain the pressure within a maintenance such that the calculated pressures for the
permissible range. To achieve this, there must be a sufficient pressure maintenance are produced correctly at the
water uptake volume which must correspond to the expan- point of zero pressure.
sion volume Ve and the water reservoir Vv. If devices are
In closed heating, solar and cooling systems, it is assumed
installed which extract and feed back a volume of water VD
that the expansion volume flow !e is the largest possible
from the system during operation, such as a vacuum
balancing volume flow. It occurs when the thermal output
degasser, this must also be taken into consideration. This
" G of heating or cooling sources is switched on or off.
also applies to volumes of steam VS which occur during
downtimes in solar collectors. If the temperature of the
medium drops below 0 °C or exceeds 70 °C at the connection
point of the pressure maintenance in the facility system, an
auxiliary vessel is to be installed in order to protect the
Thermal output "G
bladder of the expansion vessel.
Point of zero pressure
t
Water uptake volume Water uptake volume
Z
in heating systems proportion of Ve for t > 70 °C
Z
in cooling systems proportion of Ve for t < 0 °C
6
Pressure maintenance
Membrane ΔV = V₁ − V₂
Water chamber
Pressure booster system
Water uptake Water release
V₂ V₁
Facility system Consumer unit
The pressure pad supports the water column in the system and is pressure, the pump switches on and feeds the water.
adjusted accordingly before the vessel is filled with a volume of If the consumer units remove a lesser amount, the difference is
water. As the system is heated, the pressure increases resulting in temporarily stored in the buffer tank until the pressure pad is
the expanding water flowing from the facility system to the water compressed to the cut-out pressure and the pressure booster
chamber. The pressure pad in the gas chamber is compressed and system switches off. The resulting pressure drop leads to a
the pressure increases. As the system cools, the volume decreas- reduction in volume. If the consumer units draw water, temporari-
es and the pressure drops: the expansion water flows out of the ly stored water is extracted from the buffer tank until the cut-in
water chamber back into the facility system. The pressure pad in pressure occurs at the pressure pad and the pressure booster
the gas changer is adjusted to just under the cut-in pressure of system is switched on again.
the feed device. When the pressure drops below the cut-in
7
Selection and calculation
System pressure
Supply pressure
Static pressure
Final pressure
tv
psv
tR
pe
pF
pa
p0
VV V V + VE
Calculation values
Pressures are given as excess pressures and relate
to the connecting pieces for the expansion vessel
up to the highest point in the system.
Reflex recommendations
Z
Set the safety valve operating pressure sufficiently high:
pSV ≥ p0 + 1.5 bar
Z
If possible, when calculating the inlet gas pressure, select an extra 0.2 bar:
p0 ≥ H [m] + 0.2 bar
10
Z
Select an supply pressure of at least 1 bar on account of the necessary supply pressure
for the flow-through pumps—even for rooftop infrastructure centres: p0 ≥ 1 bar
Z
Set the fill or supply pressure on the water side in vented systems in cold
condition at least 0.3 bar above the supply pressure to ensure a water
reservoir inthe expansion vessel (VV = 0.005 × VA at least 3 l for
Vn > 15 l minimum volume indication according to the standard): pF ≥ p0 + 0.3 bar
21
Reflex
Inlet Pressure p0 [bar] 0.5 1.0 1.5 0.5 1.0 1.5 1.8 1.5 2.0 2.5 3.0
8 107 48 – 133 82 31 – 87 48 8 –
12 161 71 – 199 122 46 – 131 71 12 –
18 268 134 – 325 210 96 27 223 134 45 –
25 424 238 52 504 344 185 89 362 238 114 –
35 639 387 126 730 536 313 179 561 387 213 –
50 912 608 238 1,043 782 504 313 811 608 362 114
80 1,460 973 461 1,668 1,251 834 580 1,298 973 649 263
100 1,825 1,217 608 2,086 1,564 1,043 730 1,622 1,217 811 362
140 2,555 1,703 852 2,920 2,190 1,460 1,022 2,271 1,703 1,135 561
200 3,650 2,433 1,217 4,171 3,128 2,086 1,460 3,244 2,433 1,622 811
250 4,562 3,041 1,521 5,214 3,910 2,607 1,825 4,055 3,041 2,028 1,014
300 5,474 3,650 1,825 6,257 4,692 3,128 2,190 4,866 3,650 2,433 1,217
400 7,299 4,866 2,433 8,342 6,257 4,171 2,920 6,488 4,866 3,244 1,622
500 9,124 6,083 3,041 10,428 7,821 5,214 3,650 8,110 6,083 4,055 2,028
600 10,949 7,299 3,650 12,513 9,385 6,257 4,380 9,732 7,299 4,866 2,433
Reflex
800 14,599 9,732 4,866 16,684 12,513 8,342 5,839 12,976 9,732 6,488 3,244
1,000 18,248 12,165 6,083 20,855 15,641 10,428 7,299 16,221 12,165 8,110 4,055
22
Selection and calculation
Inlet Pressure p0 [bar] 2.0 2.5 3.0 3.5 4.0 2.0 2.5 3.0 3.5 4.0 5.0
8 91 58 26 – – 118 90 63 35 7 –
12 136 88 39 – – 177 136 94 52 10 –
18 231 158 85 12 – 293 230 167 105 42 –
25 373 272 170 69 – 459 372 285 197 110 –
35 576 434 292 150 8 679 574 452 330 208 –
50 829 664 475 272 69 969 827 684 529 354 6
80 1,327 1,062 796 515 191 1,551 1,323 1,095 867 639 89
100 1,659 1,327 995 664 272 1,939 1,654 1,369 1,083 798 145
140 2,322 1,858 1,393 929 434 2,714 2,315 1,916 1,517 1,118 257
200 3,318 2,654 1,991 1,327 664 3,878 3,307 2,737 2,167 1,597 424
250 4,147 3,318 2,488 1,659 829 4,847 4,134 3,422 2,709 1,996 564
300 4,977 3,981 2,986 1,991 995 5,817 4,961 4,106 3,250 2,395 684
400 6,636 5,309 3,981 2,654 1,327 7,755 6,615 5,474 4,334 3,193 912
500 8,295 6,636 4,977 3,318 1,659 9,694 8,269 6,843 5,417 3,992 1,141
600 9,954 7,963 5,972 3,981 1,991 11,633 9,922 8,212 6,501 4,790 1,369
Reflex
800 13,271 10,617 7,963 5,309 2,654 15,511 13,230 10,949 8,668 6,387 1,825
1,000 16,589 13,271 9,954 6,636 3,318 19,389 16,537 13,686 10,835 7,984 2,281
" /kW
2,100 3,600 4,800 7,500 14,000 19,000 29,000
Lengths ≤ 10 m
" /kW
1,400 2,500 3,200 5,000 9,500 13,000 20,000
Lengths > 10 m ≤ 30 m
If the length of the expansion line is > 10 m, we recommend selecting the nominal diameter one dimension larger.
23
Reflex
Final pressure pE
0% 0.37 0.72 1.15 1.66 2.24 2.88 3.58 4.34 4.74 5.15 6.03 6.96 7.96 9.03
n%
34 % 1.49 1.99 2.53 3.11 3.71 4.35 5.01 5.68 - 6.39 7.11 7.85 8.62 9.41
* Values apply for Antifrogen N. We recommend a concentration of 25 to 50 %. Lower doses lead to a risk of corrosion!
0% –0.96 –0.93 –0.88 –0.80 –0.69 –0.53 –0.3 0.01 0.21 0.43 0.98 1.7 2.61 3.76
pD bar
34 % –0.90 –0.80 –0.70 –0.60 –0.40 –0.10 – 0.23 0.70 1.33 2.13 3.15
* Values apply for Antifrogen N. We recommend a concentration of 25 to 50 %. Lower doses lead to a risk of corrosion!
** pD with respect to ±0 m NN, we recommend an additional 0.1 bar for each 1 km height.
Standard values for sizing expansion lines, make-up pipes and lines to control vessel
DN 20 25 32 40 50 65 80 100
24
Selection and calculation
Volume of vacuum spray pipe degasser VD ,which has to be absorbed by pressure maintenance
Degassing VD l
Servitec 25…30 1
Servitec 35…120 6
Special Servitec …–2…4 35
Special Servitec …–6…8 70
25
Reflex
26
Selection and calculation
* Only applies when using Reflex Servitec in accordance with the ‘Degassing’ table see page 25
27
Reflex
28
Selection and calculation
pe + 1
pa = − 1 bar
(Ve + VD*) (pe + 1)
1+
Control supply pressure pa [bar] Vn (p0 + 1) pa = ... bar
Precondition: pa ≥ p0 + 0.25…0.3 bar,
otherwise calculate for larger nominal volume
Result
Reflex …/ … bar …litres p0 = … bar Check before commissioning!
pa = … bar Check make-up setting!
pF = … bar Refill the system!
pe =… bar
* Only applies when using Reflex Servitec in accordance with the ‘Degassing’ table see page 25
29
Reflex
30
Selection and calculation
pe + 1
vpa = – 1 bar
(Ve + VKges*) (pe + 1)
Control 1+
Vn (p0 + 1) 2n pa = … bar
Supply pressure pa [bar]
Precondition: pa ≥ p0 + 0.25…0.3 bar,
otherwise calculate for larger nominal volume
Filling pressure pF [bar] pF = Vn × – 1 bar pF = … bar
Result
Reflex S /… bar … litres p0 = … bar Check before commissioning!
pa = … bar Check make-up setting!
pF = … bar Refill the system!
pe =… bar
* Only applies when using Reflex Servitec in accordance with the ‘Degassing’ table see page 25
31
Reflex
32
Installation and commissioning
33
Reflex
Reflex N
Fillsoft I
The directive VDI 2035 describes the state of the art for water
quality in hot water heating systems and contributes to min-
imising damage due to corrosion and scale deposits in these
systems. The Fillsoft series of Reflex products comply with this
directive. Further information can be found in our Make-up and
Water Treatment brochure.
34
Installation examples
Installation examples
Reflex vessel with automatic make-up Solution N-o 01
We recommend the
use of an automatic
make-up such as
Reflex Fillcontrol
Plus Compact
combined with static
Servitec Mini pressure mainte-
nance in order to
Reflex ensure an adequate
water seal.
Servitec vacuum
spray pipe degassing
and the dirt and
SINUS MultiFlow Domestic sludge separators
remove disruptive
factors such as
Exdirt gasses and dirt from
the facility water.
Refix
FE external pressure sensor Fillguard
Fillsoft I
A Longtherm heat
M M
exchanger is used to
Exdirt separate the heating
and potable water
>500 mm
.
circuit.
Compact distributor
Kompaktverteiler
Servitec 35
Reflex
35
Reflex
1. Visual inspection
Z
Inspect vessel for damage, corrosion, etc.
In the event of damage, complete repairs or replace and determine the possible cause.
Z
Match vessel suitability to on-site use.
2. Check bladder
Briefly activate the gas filling valve. If water leaks out:
Z
For vessels which do not have a facility for replacing the bladder,
replace the expansion vessel.
Z
for vessels which have a facility for replacing the bladder, replace the bladder
or alternatively contact Reflex Service for further advice.
36
Selection and calculation
Excess pressures
pst = static pressure
p0 = minimum operating pressure psv
pa = supply pressure
pe = final pressure pe ≤ pSV − 0.5 bar
psv = safety valve actuating pressure (Reflex recommendation)
pa
p0 = pa − 0.2…1 bar
Supply pressure /
System pressure
Final pressure
p0
pa
pe
PI
51
Refix
Z
Gas supply pressure p0 = 3.0 bar Z
Gas supply pressure p0 = 4.0 bar = standard
Z
Pressure reducer Z
Pressure reducer
preset pressure pa ≥ 3.2 bar preset pressure pa ≥ 4.2 bar
Hot water temperature Tww = 60 °C Expansion (60 °C/10 °C) n = 1.7 % Vessel volume → Vn = 31.5 litres Selection
example
Pressure reducer Supply pressure p₀ = 4.0 bar
preset pressure pa = 4.2 bar
52
Selection and calculation
Refix DD 8–33 l
with or without Flowjet Rp ¾" = standard ≤ 2.5 m³/h ∆p = 0.03 bar × ( 2.5! m³/h
m³/h )
²
Refix DT 60–500 l
Refix DT 80–3.000 l
Refix DE, DC
53
Refix
Circuit
Vn
" pa pSV VSp
p0
"S
The safety valve is usually installed directly at the cold water Refix DD with T-piece: Rp ¾" max. 200 l water heater
inlet on the water heater. On Refix DD and DT, the safety valve Rp 1" max. 1,000 l water heater
may also be installed immediately upstream of the flow
through, shut-off and drain valve when viewed from the Refix DT flow-
direction of flow if the following conditions are met: through fitting: Rp 1¼" max. 5,000 l water heater
54
Selection and calculation
Once the nominal volume of the Refix has been selected, checks must be carried out on vessels with
flow-through to establish whether the peak volume flow !s , resulting from the calculation of the
pipe network in accordance with DIN 1988 can be implemented on the Refix vessels. If this is the
case, for Refix DD, a 60 litre Refix DT is to be used instead of the 8–33 litre vessel for greater flow.
Alternatively, a Refix DD with a suitably larger T-piece can be used whereby it should be noted that
the flow-through insert of the DD vessel protrudes into the full bore of the T-piece.
recommended max. actual pressure loss
Available connections
peak volume flow "S* at volume flow "
( )
60–500 l
! m³/h ²
Refix DT
!S G =…
Duo-Anschluss DN 65 ≤ 27 m³/h ∆p = 0,11 bar × ( 27! m³/h
m³/h )
²
80–3.000 l
!
Refix DT
Result
Refix DT5 …… l Vn = … l
Refix DD …… l
G = …… (Standard Rp 3/4" incl.) p0 = … bar
Refix DT5 …… l
55
Refix
Calculation
The calculation is completed in accordance with DIN 1988 part 5,
Codes of practice for drinking water installations, pressure
boosting and pressure reduction.
Circuit
pe pe
Connection pipe
Connection pipe
pa pa, pe pa
p0 pmax /pSV p0
pmax /pSV
pVmax
pminV
On the upstream side of a pressure boosting system (DEA), On the downstream side of a pressure booster system (DEA)
Refix expansion vessels relieve the pressure on the connection the switching frequency is reduced when installing Refix,
pipe and the supply network. Installation is to be agreed with particularly in cascade controlled systems. Installation on both
the water supply company. sides of the DEA may be necessary.
56
Selection and calculation
Result
Refix DT5 ....... l Vn = ... l
with twin connection DN 50 p0 = ... bar
Refix DT5 ....... l
pA + 1
Nominal volume Vn [l] Vn = 0,33 × VmaxP Vn = ... litres
(pA − pE) × s × n
For storing the minimum feed quantity Ve between On and Off for the DEA
Cut-in pressure pE [bar]
Cut-out pressure pA [bar]
Reflex recommendation: for p0 = pE − 0,5 bar p0 = ... bar
Refix supply pressure p0 [bar]
Feed quantity Ve [l]
(pE + 1) (pA + 1)
Nominal volume Vn [l] Vn = Ve Vn = ... litres
(p0 + 1) (pA − pE)
Initial data
Refix DT5 ....... l Vn = ... l
with twin connection DN 50 Vn = ... l
Refix DT5 ....... l p0 = ... bar
57
Refix
Installation examples
Refix in water heating systems–installation examples
Refix DD, DT 60–500 with Flowjet flow through, shut-off and drain valve
Z
The complete solution with Flowjet flow through,
shut-off and drain valve
Z
Benefits: Flowjet is easy to fit and DIN-compliant
Guaranteed shut off, drainage and flow-through
1
for Refix.
4 3
1 Refix DD or Refix DT 60–500
2 Flowjet flow through, shut-off and drain valve
optional accessory for Refix DD:
2 Z
standard with T-piece Rp ¾", ! ≤ 2. 5 m³/h
Z
for T-piece Rp 1" ! ≤ 4.2 m³/h
for Refix DT 60–500’ with Flowjet:
Z
standard with Rp 1¼" ! ≤ 7.2 m³/h
3 Reflex wall-hung holder for 8–25 litres
(33 l with butt straps, DT with feet)
4 A safety valve may also be fitted upstream in
the direction of flow of the Refix DD or the DT5
with Flowjet provided the nominal diameter of
the required SV ≤ than the downstream
storage feed.
Refix DD without Flowjet flow through, shut-off and drain valve
Z
If no Flowjet flow through, shut-off and drain valve is
fitted, the feed to the water heater must be shut-off
during maintenance work and the Refix DD drained
via an on-site fitting.
1 1 Refix DD
2 T-piece Rp ¾", ! ≤ 2.5 m³/h
3
For T-piece Rp 1" ! ≤ 4.2 m³/h
3 Reflex wall-hung holder for 8–25 litres
2 (33 l with butt straps feet)
58
Operation & Maintenance
1. Visual inspection
Z
Inspect vessel for damage, corrosion, etc.
In the event of damage, complete repairs or replace and determine the possible cause.
Z
Match vessel suitability to on-site use.
2. Check bladder
Briefly activate the gas filling valve. If water leaks out:
Z
For vessels which do not have a facility for replacing the bladder, replace
the expansion vessel.
Z
for vessels which have a facility for replacing the bladder,replace the bladder
or alternatively contact Reflex Service for further advice.
Z
If the pressure is too high, blow off the gas with the gas filling valve.
Z
If the pressure is too low, refill with nitrogen from a pressurised container.
Z
Enter the reset or corrected supply pressure p0 on the type plate.
59