Product Specification of NDB1-125
Product Name: Miniature Circuit Breaker
Product Type: NDB1-125
Date: 2019-1-07
Prepare Review Approvel
Feng Dai MaoYuanXiong Hui Duan
LX7.201R-14B
File name Product Specifications File number NDT500954
Version 0 version
Product NDB1-125
name MCB
Date 2019-1-07
Revision records
Version Revised contents and reasons Date By (full name)
0 Initial release. 2019-1-07 Feng Dai
File number NDT500954 Version 0version Date 2019-1-07
1 Application
●Protection against short circuit
●Protection against overload
●Control
●Isolation
●Protection of DC system
NDB1-125 series is used in low voltage electrical distribution system in industry, real estate,
power, telecom, construction field, etc.
2 Product Picture
1P 2P 3P 4P
3 Model and implication
ND B 1 — 125 □ □ / □
MCB Design Frame Size Tripping Curve Rated current Pole
Nader Brand Serial Nunber 125A C Curve 50A, 63A, 80A 1P, 2P
D Curve 100A, 125A 3P, 4P
4 Main technical parameters
● Electrical parameters
○ Rated voltage (Ue): AC230/240V(1P ); AC400/415V(2P;3P;4P);DC60/80V(1P);DC80/125V(2P)
○ Rated current (In): 50A, 63A, 80A, 100A, 125A
○ Rated breaking capacity (Icn): 10kA
○ Impulse voltage endurance: 6kV
●Isolation function
○Indication of real breaking
○Green color in the indication window indicates the contacts are open.
● Mechanical and electrical life: 20000 times
● Standards and Certificates
○CCC;
○GB/T 10963.1-2005 、IEC 60898-1:2002;
1
File number NDT500954 Version 0version Date 2019-1-07
● Environmental requirements:RoHS
● Used in place without obvious shock and vibration
● Wiring
○ Adopt tunnel type wiring
○ Connection capability: 10mm2 to 50 mm2
○ Connection screw M7,Twisting moment 3.5N.m
5 Working conditions
● Ambient temperature: -40℃~+70℃
● Relative air humidity≤95%
● Altitude: ≤2000m
● Pollution degree: 3
● Used in place without obvious shock and vibration
6 Lower capacity coefflcient table above 2000 meters above sealevel
Rated Remarks
Height Breaking Breaking Capacity
Rated Rated frequency
above sea Capacity and Electrical life
current voltage voltage
level(km)
tolerance
2 In Ue 1.00 1.00 1.00
3 0.99 In Ue 0.89 0.89 0.83
4 0.96In Ue 0.80 0.80 0.71
5 0.94In Ue 0.73 0.73 0.63
7 Side-by-side volume reduction coefflcient table
8 Tripping curves (ambient temperature 40℃)
● C Curve
○ Protection common loads and power distribution circuit
○ Available for the rated current of 50A to 125A
○ Tripping characteristic: instantaneous trip between 5In to 10In
● D Curve
○Protection big impulse load of starting current (Motor, transformer etc)
○Available for the rated current of 50A to 125A
○Tripping characteristic: instantaneous trip between 10In to 14In
2
File number NDT500954 Version 0version Date 2019-1-07
C Curve D Curve
9 Outline dimensions and installation
1P 2P
3P 4P
3
File number NDT500954 Version 0version Date 2019-1-07
10 Mounting
Modularized structure, can be easily installed in TH35mm×7.5 Standard DIN rail.
11 Packing and depositing
● Maximum packing quantity
1P: 9 pieces in a box, 12 boxes in an overwrap carton.
2P: 4 pieces in a box, 12 boxes in an overwrap carton.
3P: 3 pieces in a box, 12 boxes in an overwrap carton.
4P: 2 pieces in a box, 12 boxes in an overwrap carton.
● Products should be stored in the warehouse where there is ventilation. The relative humidity
there should not exceed 80%, and the ambient temperature there is between -40℃ to +70℃. In
addition, there should not be acidic, alkaline and corrosive gas in the air.
● Products should not be deposited more than 3 years in the above mentioned conditions since
the producing date.
12 Accessories
● OF auxiliary contact: Installed on the left hand of the NDB1 series MCCBs to indicate tripping
status of the breaker.
● SD alarm contact: Installed on the left hand of the NDB1series MCCBs to indicate failure
tripping status of the breaker.
● MX+OF shunt release: Installed on the right hand of the NDB1 series MCCBs to control the
breaker from a distance.
13 Notices
13.1Manufacturer will take no responsibility for problems caused by disassembly privately.
13.2 Attention to live part when the breaker is energized and avoid touching them.
13.3 Manufacturer will take no responsibility for the quality problem caused by adjusting the
characteristic of the breaker privately.
13.4 Wiring properly to avoid mis-trip or terminal burn.
13.5 Please open the cover when installing the accessory. Please refer to OF, SD MX+OF