The document outlines fire-resistance ratings for products certified under ANSI/UL 263, emphasizing the need for consultation with authorities having jurisdiction for installation requirements. It details specific design criteria, allowable variances, and the necessary materials and thicknesses for fire-resistant assemblies. Only products bearing the UL or cUL Certification Mark are considered certified and compliant with UL's Follow-Up Service.

Uploaded by

Kush Sura
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
73 views2 pages

Y705-Ul CFT Columns

The document outlines fire-resistance ratings for products certified under ANSI/UL 263, emphasizing the need for consultation with authorities having jurisdiction for installation requirements. It details specific design criteria, allowable variances, and the necessary materials and thicknesses for fire-resistant assemblies. Only products bearing the UL or cUL Certification Mark are considered certified and compliant with UL's Follow-Up Service.

Uploaded by

Kush Sura
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

4/22/2021 BXUV.

Y705 - Fire-resistance Ratings - ANSI/UL 263 | UL Product iQ

BXUV.Y705 - Fire-resistance Ratings - ANSI/UL 263

Design/System/Construction/Assembly Usage Disclaimer


Authorities Having Jurisdiction should be consulted in all cases as to the particular requirements covering the installation and use of UL Certified products,
equipment, system, devices, and materials.
Authorities Having Jurisdiction should be consulted before construction.
Fire resistance assemblies and products are developed by the design submitter and have been investigated by UL for compliance with applicable
requirements. The published information cannot always address every construction nuance encountered in the field.
When field issues arise, it is recommended the first contact for assistance be the technical service staff provided by the product manufacturer noted for the
design. Users of fire resistance assemblies are advised to consult the general Guide Information for each product category and each group of assemblies. The
Guide Information includes specifics concerning alternate materials and alternate methods of construction.
Only products which bear UL's Mark are considered Certified.

BXUV - Fire Resistance Ratings - ANSI/UL 263 Certified for United States
BXUV7 - Fire Resistance Ratings - CAN/ULC-S101 Certified for Canada
See General Information for Fire-resistance Ratings - ANSI/UL 263 Certified for United States
Design Criteria and Allowable Variances

See General Information for Fire Resistance Ratings - CAN/ULC-S101 Certified for Canada
Design Criteria and Allowable Variances

Design No. Y705


January 21, 2020

Ratings — 1, 1-1/2, 2, 3 & 4 Hr


* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL
or cUL Certification (such as Canada), respectively.

1. Steel Pipe — Steel circular pipe with a min. diam (ID) 12 in. with a min wall thickness of 3/16 in. Steel pipe will be vented with a min of one pair of 1/2 in.
diam holes or 0.145 sq in. of vent per cu foot of concrete, whichever is greater. The spacing of the vents shall not exceed 8 ft OC.

2. Normal Weight Concrete — Siliceous or carbonate aggregate, min density of 150 pcf, min 3000 psi compressive strength, vibrated.

3. Spray-Applied Fire Resistive Materials* — Applied by mixing with water and spraying in more than one coat to the thickness shown below, to steel
surfaces which are clean and free of dirt, loose scale and oil. Min avg and min ind density of 18/16 pcf for Type CP-2 and 23/21 pcf for Type P-20, respectively.
Min average and min individual density of 15/14 pcf, respectively, for Types 300, and 22/19 pcf for Type 400. Min avg density of 44 pcf with min ind value of 40
pcf for Type M-II. For method of density determination, see Design Information Section, Sprayed Material.
Rating Hr Min Thkns In.

https://iq.ulprospector.com/en/profile?e=15560 1/2
4/22/2021 BXUV.Y705 - Fire-resistance Ratings - ANSI/UL 263 | UL Product iQ

1 3/8

1-1/2 7/16

2 1/2

3 3/4

4 1-1/16

GREENTECH ASIA PACIFIC SDN BDH — Types 300 and 400

GREENTECH THERMAL INSULATION PRODUCTS MFG CO L L C — Types M-II, CP-2, 300, 300HS, 400, and 3000.

ISOLATEK INTERNATIONAL — Types CP-2, P-20, 300, 300HS, 400, and 3000.

NEWKEM PRODUCTS CORP — Type CP-2, 300 and 400.

* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing
the UL or cUL Certification (such as Canada), respectively.
Last Updated on 2020-01-21

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only
those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Assemblies, Constructions,
Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The
statement "Reprinted from the Online Certifications Directory with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must
include a copyright notice in the following format: "© 2021 UL LLC"

https://iq.ulprospector.com/en/profile?e=15560 2/2

You might also like