NXHB 125 Switch Disconnector
NXHB 125 Switch Disconnector
1. General description
2. Technical data
Circuit breaker and switch parameters
63、80、100(1P、2P、3P、
1~63 70A, 80A 63~125 63~125
4P),125(1P、2P)
240/415 230/400 230/400 230/400 230/400
50/60 50/60 50/60 50/60 50
1P, 1P+N, 2P, 3P, 3P+N, 4P 1P, 1P+N, 2P, 3P, 3P+N, 4P 1P, 2P, 3P, 4P 1P, 2P, 3P, 4P 1P, 2P, 3P, 4P
20000 20000 20000 20000 10000
10000 6000 6000(In≤100A), 4000(In>100A) 6000(In≤100A), 4000(In>100A) 3000
4500 6000 10000 10000 20Ie
4500 6000 7500 7500 3Ie
4 4 4 4 6
(Power frequency 1 minute) 2000 (Power frequency 1 minute) 2000 (Power frequency 1 minute) 1890 (Power frequency 1 minute) 2000 (Power frequency 1 minute) 1890
1 25 16 16 1
25 25 50 50 50
2 3.5 3.5 3.5 3.5
2.5 4 4 4 4
12.5 15 15 15 15
30 30 30 30 30
-35~+70 -35~+70 -35~+70 -35~+70 -35~+70
-35~+85 -35~+85 -35~+85 -35~+85 -35~+85
2000 2000 2000 2000 2000
■ ■ ■
■ ■ ■
■ ■ ■
■
■
Top or bottom entry Top or bottom entry Top or bottom entry Top or bottom entry Top or bottom entry
TH35-7.5-rail mounting TH35-7.5-rail mounting TH35-7.5-rail mounting TH35-7.5-rail mounting TH35-7.5-rail mounting
Pollution degree Ⅱ Pollution degree Ⅱ Pollution degree Ⅱ Pollution degree Ⅱ Pollution degree Ⅱ
IP20 IP20 IP20 IP20 IP20
IP40 IP40 IP40 IP40 IP40
AX-X1, AL-X1, SHT-X1OVT-X1, AX-X1, AL-X1, SHT-X1,OVT-X1, AX-X3, AL-X3, SHT-X3 AX-X3, AL-X3, SHT-X3
UVT-X1, OUVT-X1 UVT-X1, OUVT-X1 OVT-X3, UVT-X3, OUVT-X3 OVT-X3, UVT-X3, OUVT-X3
P- 005 A.1 NXB Series Technical data
Test Type Test current Starting state Trip/Not trip time limit Expected outcome Notes
B 3In
Connect the current by
d C 5In Cold t≤0.1s Not trip
closing the auxiliary switch
D 10In
B 5In
Connect the current by
e C 10In Cold t<0.1s Trip
closing the auxiliary switch
D 20In
Release type Test current Starting state Trip/Not trip time limit Expected outcome Notes
t≤1 h(for In≤63A)
C,D 1.05In Cold Cold
t≤2 h(for In > 63A)
t < 1 h(for In≤63A) Current increase
C,D 1.3In Right after test Right after test
t < 2 h(for In > 63A) steadily within 5s
C,D 2In Cold t < 900s Cold
C 6.4In
Cold t≤0.2s t≤0.2s
D 9.6In
Connect the current by
C 9.6In
Cold t < 0.2s t < 0.2s closing the auxiliary switch
D 14.4In
Tripping curve
Compliant with standard IEC60898-1 and IEC61009-1 Compliant with standard IEC60947-2
Technical data A.1 NXB Series P- 008
The following table shows the cross-sectional area of the copper wire corresponding to the rated current (recommended value):
Circuit breakers
Product model Number of poles Electromagnetic release type Rated current Rated residual operating current
NXB-40
1P+N C, D 6A, 10A, 16A, 20A, 25A, 32A, 40A
NXBLE-40 0.01A, 0.03A
1P, 1P+N, 2P, 1A, 2A, 3A, 4A, 6A, 10A, 16A,
NXB-63 B, C, D
3P, 3P+N, 4P 20A, 25A, 32A, 40A, 50A, 63A
NXBLE-32 1P+N, 2P, 3P, 6A, 10A, 16A, 20A, 25A, 32A 0.03A, 0.05A, 0.075A,
B, C, D
NXBLE-63 3P+N, 4P 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A 0.1A, 0.3A
NXBLE-63Y 1P+N C, D 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A 0.01A, 0.03A
NXB-80 1P, 1P+N, 2P B, C, D 80A
NXB-125 1P, 2P, C, D 63A, 80A, 100A, 125A
NXB-125G 3P, 4P B, C, D 63A, 80A, 100A
NXBLE-125 1P+N, 2P, C, D 63A, 80A, 100A, 125A 0.03A, 0.05A, 0.075A,
NXBLE-125G 3P, 3P+N, 4P B, C, D 63A, 80A, 100A 0.1A, 0.3A
NXL-63 2P, 4P / 16A, 25A, 32A, 40A, 63A 0.01A(only 2P 16/25A) 0.03A, 0.3A
2. Compliant certification
CE, RoHS
3. Major function
Isolation function
4. Technical data
Rated current Ie: 20A, 32A, 40A, 63A, 80A, 100A, 125A;
Number of poles: 1P, 2P, 3P, 4P;
Rated insulation voltage Ui: 500V;
Rated operation voltage Ue: 240V~(1P), 415V~(2P, 3P, 4P);
Rated impulse withstand voltage Uimp: 6kV;
Rated short time withstand current Icw: 12 Ie, power-on time of 1s;
Rated short-circuit making capacity Icm: 20Ie, power-on time of 0.1s;
Rated making and breaking capacity: 3Ie, 1.05Ue, COSΦ=0.65;
Operation performance: mechanical life of 10,000 cycles, electrical life of 3000 cycles;
Pollution degree: Ⅱ ;
Utilization category: AC-22A, AC-21B;
Installation category: Ⅱ , Ⅲ ;
Installation: TH35-7.5 steel rail mounting, the gradient of the mounting surface from the
vertical plane should be ≤5°;
Wiring: screw clamp wiring, tightening torque 3.5N·m (80A ~ 125A);
tightening torque 2.0N·m(20A ~ 63A).
44.5±0.31
34.5±0.31
80 -1.20
0
0
65.5±0.37
1P 18 -0.43
H
0
2P 36 -0.62
0
3P 54 -1.20
0
72 -1.20
4P
1P 2P~4P
0 0
H(mm) 76.3 -1.2 78 -1.2
P- 145 A.1 NXB Series Switch Disconnector
NXHB-125 1P 125A
1P
2P
NXHB-125 20A~125A
3P
4P