0% found this document useful (0 votes)
44 views10 pages

NXHB 125 Switch Disconnector

The document provides a comprehensive overview of the NXB Series Miniature Circuit Breakers, detailing various models such as NXB-40, NXB-63, and others, along with their technical specifications. It includes information on compliant standards, rated currents, voltage, mechanical and electrical life cycles, and other operational parameters. Additionally, it outlines features like thermal magnetic release types, derating factors, and mounting options for the circuit breakers.

Uploaded by

mg1001
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
44 views10 pages

NXHB 125 Switch Disconnector

The document provides a comprehensive overview of the NXB Series Miniature Circuit Breakers, detailing various models such as NXB-40, NXB-63, and others, along with their technical specifications. It includes information on compliant standards, rated currents, voltage, mechanical and electrical life cycles, and other operational parameters. Additionally, it outlines features like thermal magnetic release types, derating factors, and mounting options for the circuit breakers.

Uploaded by

mg1001
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

P- 001 A.

1 NXB Series General description

1. General description

NXB-63 Miniature circuit breaker


General description A.1 NXB Series P- 002

NXB-63 Miniature circuit breaker


P- 003 A.1 NXB Series Technical data

2. Technical data
Circuit breaker and switch parameters

Product model NXB-40 NXB-63 NXB-63H NXB-63G


IEC/EN 60947-2、VC8036、
Compliant standards IEC/EN60898-1 IEC/EN60898-1 IEC/EN60898-1
SANS 556-1、SANS 60947-2

Rated current (A) 6~40 1~63 1~63 1~63

Rated voltage (V~) 230 240/415 240/415 240/415


Rated frequency (Hz) 50/60 50/60 50/60 50/60
Number of poles 1P+N 1P, 1P+N, 2P, 3P, 3P+N, 4P 1P, 1P+N, 2P, 3P, 3P+N, 4P 1P, 2P, 3P, 4P

Mechanical life (cycles) 20000 20000 20000 20000


Electrical life (cycles) 10000 10000 10000 10000
Rated short-circuit breaking capacity Icu (A) 4500 6000 10000 6000
Short-circuit breaking capacity Ics (A) 4500 6000 7500 6000
Rated impulse withstand voltage (1.2/50)(kV) 4 4 4 4
(Power frequency 1 minute) (Power frequency 1 minute) (Power frequency 1 minute)
Dielectric test voltage (V) (Power frequency 1 minute) 2000
2000 2000 2000
Anti-humid and heat properties (IEC60068-2-
28 cycles 28 cycles 28 cycles 28 cycles
30:55℃ /90~96%,25℃ /95~100%)
2
Minimum cross section (mm ) 1 1 1 1
Maximum cross section (mm2) 10 25 25 25
Terminals Standard connection torque (N·m) 1.5 2 2 2
Maximum withstand torque (N m) 2.0 2.5 2.5 2.5
Wire insertion depth (mm) 10 12.5 11 12.5
Reference temperature for setting of thermal element (℃ ) 30 30 30 40
Operating ambient temperature (℃ ) -35~+70 -35~+70 -35~+70 -35~+70
Ambient storage temperature (℃ ) -35~+85 -35~+85 -35~+85 -35~+85
Applicable altitude (m) 2000 2000 2000 2000
Type B (3In~5In) ■ ■
Type C (5In~10In) ■ ■ ■
Type D (10In~16In) ■ ■ ■
Thermal magnetic
Type C (6.4In~9.6In)
release
Type D (9.6In~14.4In)
Ii=10In (8In~12In) ■
Ii=14.2In (11.36In~17.04In) ■
<=3 (0.9~0.95)In (0.9~0.95)In (0.9~0.95)In (0.9~0.95)In
Derating facter with
multiple products 4~6 (0.86~0.80)In (0.86~0.80)In (0.80~0.86)In (0.86~0.80)In
side by side 7~9 (0.78~0.76)In (0.78~0.76)In (0.76~0.78)In (0.78~0.76)In
(recommended value)
>9 0.76In 0.76In 0.76In 0.76In
Temperature Change for every 10℃ increase from
-(0.03~0.07)In -(0.03~0.05)In -(0.03~0.06)In -(0.02~0.07)In
compensation the reference temp
coefficient Change for every 10℃ decrease
(recommended value) +(0.03~0.07)In +(0.03~0.08)In +(0.02~0.07)In +(0.02~0.08)In
from the reference temp
Cable entry Top or bottom entry Top or bottom entry Top or bottom entry Top or bottom entry
Mounting TH35-7.5-rail mounting TH35-7.5-rail mounting TH35-7.5-rail mounting TH35-7.5-rail mounting
Pollution degree Pollution degree Ⅱ Pollution degree Ⅱ Pollution degree Ⅱ Pollution degree Ⅱ
Direct mounting IP20 IP20 IP20 IP20
Protection degree
Mounted in the distribution box IP40 IP40 IP40 IP40
AX-X1, AL-X1, SHT-X1 AX-X1, AL-X1, SHT-X1 AX-X1, AL-X1, SHT-X1 AX-X1, AL-X1, SHT-X1
Accessories that can be assembled
OVT-X1, UVT-X1, OUVT-X1 OVT-X1, UVT-X1, OUVT-X1 OVT-X1, UVT-X1, OUVT-X1 OVT-X1, UVT-X1, OUVT-X1
Technical data A.1 NXB Series P- 004

NXB-63S NXB-80 NXB-125 NXB-125G NXHB-125

IEC/EN60898-1 IEC/EN60898-1 IEC60947-2 IEC60898-1 IEC60947-3

63、80、100(1P、2P、3P、
1~63 70A, 80A 63~125 63~125
4P),125(1P、2P)
240/415 230/400 230/400 230/400 230/400
50/60 50/60 50/60 50/60 50
1P, 1P+N, 2P, 3P, 3P+N, 4P 1P, 1P+N, 2P, 3P, 3P+N, 4P 1P, 2P, 3P, 4P 1P, 2P, 3P, 4P 1P, 2P, 3P, 4P
20000 20000 20000 20000 10000
10000 6000 6000(In≤100A), 4000(In>100A) 6000(In≤100A), 4000(In>100A) 3000
4500 6000 10000 10000 20Ie
4500 6000 7500 7500 3Ie
4 4 4 4 6

(Power frequency 1 minute) 2000 (Power frequency 1 minute) 2000 (Power frequency 1 minute) 1890 (Power frequency 1 minute) 2000 (Power frequency 1 minute) 1890

28 cycles 28 cycles 28 cycles 28 cycles 28 cycles

1 25 16 16 1
25 25 50 50 50
2 3.5 3.5 3.5 3.5
2.5 4 4 4 4
12.5 15 15 15 15
30 30 30 30 30
-35~+70 -35~+70 -35~+70 -35~+70 -35~+70
-35~+85 -35~+85 -35~+85 -35~+85 -35~+85
2000 2000 2000 2000 2000
■ ■ ■
■ ■ ■
■ ■ ■

(0.9~0.95)In (0.9~0.95)In (0.9~0.95)In (0.9~0.95)In


(0.86~0.80)In (0.86~0.80)In (0.8~0.9)In (0.8~0.9)In
(0.78~0.76)In (0.78~0.76)In (0.7~0.8)In (0.7~0.8)In
0.76In 0.76In 0.7In 0.7In

-(0.03~0.05)In -(0.02~0.08)In -(0.03~0.08)In -(0.03~0.08)In

+(0.03~0.08)In +(0.02~0.08)In +(0.03~0.08)In +(0.03~0.08)In

Top or bottom entry Top or bottom entry Top or bottom entry Top or bottom entry Top or bottom entry
TH35-7.5-rail mounting TH35-7.5-rail mounting TH35-7.5-rail mounting TH35-7.5-rail mounting TH35-7.5-rail mounting
Pollution degree Ⅱ Pollution degree Ⅱ Pollution degree Ⅱ Pollution degree Ⅱ Pollution degree Ⅱ
IP20 IP20 IP20 IP20 IP20
IP40 IP40 IP40 IP40 IP40
AX-X1, AL-X1, SHT-X1OVT-X1, AX-X1, AL-X1, SHT-X1,OVT-X1, AX-X3, AL-X3, SHT-X3 AX-X3, AL-X3, SHT-X3
UVT-X1, OUVT-X1 UVT-X1, OUVT-X1 OVT-X3, UVT-X3, OUVT-X3 OVT-X3, UVT-X3, OUVT-X3
P- 005 A.1 NXB Series Technical data

Residual current operated circuit breaker parameter

Product model NXBLE-40 NXBLE-63Y


Compliant standards IEC/EN61009-1 IEC61009-1
Rated current (A) 6~40 6~63
Rated residual operating current (A) 0.01, 0.03 0.01, 0.03
Leakage protection type AC AC
Rated voltage (V~) 230 240
Rated frequency (Hz) 50/60 50
Number of poles 1P+N 1P+N
Mechanical life (cycles) 20000 20000
Electrical life (cycles) 10000 10000
Rated short-circuit breaking capacity (A) 4500 4500
Short-circuit breaking capacity (A) 4500 4500
Rated impulse withstand voltage (1.2/50)(kV) 4 4
Dielectric test voltage (V) (Power frequency 1 minute) 2000 (Power frequency 1 minute) 2000
Anti-humid and heat properties (IEC60068-2-30:55℃ /90~96%,25℃ /95~100%) 28 cycles 28 cycles
Minimum cross section (mm2) 1 1
Maximum cross section (mm2) 10 25
Terminals Standard connection torque (N·m) 1.5 2
Maximum withstand torque (N m) 2.0 2.5
Wire insertion depth (mm) 10 10
Reference temperature for setting of thermal element (℃ ) 30 30
Operating ambient temperature (℃ ) -35~+70 -35~+70
Ambient storage temperature (℃ ) -35~+85 -35~+85
Applicable altitude (m) 2000 2000
Type B (3In~5In)
Type C (5In~10In) ■ ■
Thermal magnetic
Type D (10In~16In) ■ ■
release
Type C (6.4In~9.6In)
Type D (9.6In~14.4In)
≤3 (0.9~0.95)In (0.9~0.95)In
Derating facter with
multiple products 4~6 (0.86~0.80)In (0.86~0.80)In
side by side 7~9 (0.78~0.76)In (0.78~0.76)In
(recommended value)
>9 0.76In 0.76In
Temperature Change for every 10℃ increase from the reference temp -(0.03~0.07)In -(0.03~0.050)In
compensation coefficient
(recommended value) Change for every 10℃ decreasefrom the reference temp +(0.03~0.07)In +(0.04~0.07)In
Cable entry Top-in, Bottom-out Top-in, Bottom-out
Mounting TH35-7.5-rail mounting TH35-7.5-rail mounting
Pollution degree Pollution degree Ⅱ Pollution degree Ⅱ
Direct mounting IP20 IP20
Protection degree
Mounted in the distribution box IP40 IP40
AX-X1, AL-X1, SHT-X1 AX-X1, AL-X1, SHT-X1
Accessories that can be assembled
OVT-X1, UVT-X1, OUVT-X1 OVT-X1, UVT-X1, OUVT-X1
Technical data A.1 NXB Series P- 006

NXBLE-32 NXBLE-63 NXBLE-125 NXBLE-125G


IEC61009-1 IEC61009-1 IEC60947-2 IEC61009-1
6~32 6~63 63、80、100(1P+N、2P、3P、3P+N、4P)125(1P+N、2P) 63~125
0.03, 0.05, 0.075, 0.1, 0.3 0.03, 0.05, 0.075, 0.1,0.3 0.03, 0.05, 0.075, 0.1, 0.3 0.03, 0.05, 0.075, 0.1, 0.3
AC AC AC, A AC
230/400 230/400 230/400 230/400
50/60 50/60 50/60 50
1P+N, 2P, 3P, 3P+N, 4P 1P+N, 2P, 3P, 3P+N, 4P 1P+N, 2P, 3P, 3P+N, 4P 1P+N, 2P, 3P, 3P+N, 4P
20000 20000 20000 20000
10000 10000 6000(In≤100A), 4000(In>100A) 6000(In≤100A), 4000(In>100A)
6000 6000 10000 10000
6000 6000 7500 7500
4 4 4 4
(Power frequency 1 minute) 2000 (Power frequency 1 minute) 2000 (Power frequency 1 minute) 1890 (Power frequency 1 minute) 2000
28 cycles 28 cycles 28 cycles 28 cycles
1 1 16 16
6 16 50 50
2 2 3.5 3.5
2.5 2.5 4 4
12.5 12.5 15 15
30 30 30 30
-35~+70 -35~+70 -35~+70 -35~+70
-35~+85 -35~+85 -35~+85 -35~+85
2000 2000 2000 2000
■ ■ ■
■ ■ ■
■ ■ ■


(0.9~0.95)In (0.9~0.95)In (0.9~0.95)In (0.9~0.95)In
(0.86~0.80)In (0.86~0.80)In (0.8~0.9)In (0.8~0.9)In
(0.78~0.76)In (0.78~0.76)In (0.7~0.8)In (0.7~0.8)In
0.76In 0.76In 0.7In 0.7In
-(0.03~0.050)In -(0.03~0.050)In -(0.03~0.08)In -(0.03~0.08)In
+(0.04~0.07)In +(0.04~0.08)In +(0.03~0.08)In +(0.03~0.08)In
Top-in, Bottom-out Top-in, Bottom-out Top-in, Bottom-out Top-in, Bottom-out
TH35-7.5-rail mounting TH35-7.5-rail mounting TH35-7.5-rail mounting TH35-7.5-rail mounting
Pollution degree Ⅱ Pollution degree Ⅱ Pollution degree Ⅱ Pollution degree Ⅱ
IP20 IP20 IP20 IP20
IP40 IP40 IP40 IP40
AX-X1, AL-X1, SHT-X1 AX-X1, AL-X1, SHT-X1
AX-X3, AL-X3 AX-X3, AL-X3
OVT-X1, UVT-X1, OUVT-X1 OVT-X1, UVT-X1, OUVT-X1
P- 007 A.1 NXB Series Technical data

Tripping characteristics are in compliant with standard IEC60898-1 and IEC61009-1

Test Type Test current Starting state Trip/Not trip time limit Expected outcome Notes

t≤1 h(for In≤63A)


a B,C,D 1.13In Cold Not trip
t<=2 h(for In >63A)

t<1 h(for In ≤63A) Current increase


b B,C,D 1.45In Right after test Trip
t<2 h(for In >63A) steadily within 5s

1s<t<60s (for In≤32A)


c B,C,D 2.55In Cold Trip
1s<t<120s (for In>32A)

B 3In
Connect the current by
d C 5In Cold t≤0.1s Not trip
closing the auxiliary switch
D 10In
B 5In
Connect the current by
e C 10In Cold t<0.1s Trip
closing the auxiliary switch
D 20In

Tripping characteristics are in compliant with standard IEC60947-2

Release type Test current Starting state Trip/Not trip time limit Expected outcome Notes
t≤1 h(for In≤63A)
C,D 1.05In Cold Cold
t≤2 h(for In > 63A)
t < 1 h(for In≤63A) Current increase
C,D 1.3In Right after test Right after test
t < 2 h(for In > 63A) steadily within 5s
C,D 2In Cold t < 900s Cold
C 6.4In
Cold t≤0.2s t≤0.2s
D 9.6In
Connect the current by
C 9.6In
Cold t < 0.2s t < 0.2s closing the auxiliary switch
D 14.4In

Tripping curve

Compliant with standard IEC60898-1 and IEC61009-1 Compliant with standard IEC60947-2
Technical data A.1 NXB Series P- 008

The following table shows the cross-sectional area of the copper wire corresponding to the rated current (recommended value):

Copper wire cross-sectional area Smm2 Rated current In(A)


1 In≤6
1.5 6 < In≤13
2.5 13 < In≤20
4 20 < In≤25
6 25 < In≤32
10 32 < In≤50
16 50 < In≤63
25 63 < In≤80
35 80 < In≤100
50 100 < In≤125

Circuit breakers

Product model Number of poles Electromagnetic release type Rated current Rated residual operating current
NXB-40
1P+N C, D 6A, 10A, 16A, 20A, 25A, 32A, 40A
NXBLE-40 0.01A, 0.03A

1P, 1P+N, 2P, 1A, 2A, 3A, 4A, 6A, 10A, 16A,
NXB-63 B, C, D
3P, 3P+N, 4P 20A, 25A, 32A, 40A, 50A, 63A

NXBLE-32 1P+N, 2P, 3P, 6A, 10A, 16A, 20A, 25A, 32A 0.03A, 0.05A, 0.075A,
B, C, D
NXBLE-63 3P+N, 4P 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A 0.1A, 0.3A

NXBLE-63Y 1P+N C, D 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A 0.01A, 0.03A
NXB-80 1P, 1P+N, 2P B, C, D 80A
NXB-125 1P, 2P, C, D 63A, 80A, 100A, 125A
NXB-125G 3P, 4P B, C, D 63A, 80A, 100A
NXBLE-125 1P+N, 2P, C, D 63A, 80A, 100A, 125A 0.03A, 0.05A, 0.075A,
NXBLE-125G 3P, 3P+N, 4P B, C, D 63A, 80A, 100A 0.1A, 0.3A

NXL-63 2P, 4P / 16A, 25A, 32A, 40A, 63A 0.01A(only 2P 16/25A) 0.03A, 0.3A

Ordering example: NXB-40 C16 50 units

NXB-63 3P D63 50 units

NXBLE-63 1P+N C63 0.03A 30 units

NXL-63 2P 63A 0.03A 90 units

Maximum discharge [Link] Maximum impulse


Product model Auxiliary contact Number of poles
currentlmax(8/20us)(kA) rational voltage Uc(V~) current(10/350us) limp(kA)
Default:NO 1P, 1P+N,2P,
NXU-IIG /F:YES 3P,3P+N,4P 40,65 255,275,320,385,440 /
Default:NO 1P, 1P+N,2P,
NXU-I+ll /F:YES / 255,275,385 12.5
3P,3P+N,4P

Ordering example: NXU-IIG/F 40kA/385V 2P 50 units


NXU-I+II/F12.5kA/275V 2P 50 units
Switch Disconnector A.1 NXB Series P- 144

NXHB-125 Isolation switch


1. Compliant standards
IEC60947-3

2. Compliant certification
CE, RoHS

3. Major function
Isolation function

4. Technical data

Rated current Ie: 20A, 32A, 40A, 63A, 80A, 100A, 125A;
Number of poles: 1P, 2P, 3P, 4P;
Rated insulation voltage Ui: 500V;
Rated operation voltage Ue: 240V~(1P), 415V~(2P, 3P, 4P);
Rated impulse withstand voltage Uimp: 6kV;
Rated short time withstand current Icw: 12 Ie, power-on time of 1s;
Rated short-circuit making capacity Icm: 20Ie, power-on time of 0.1s;
Rated making and breaking capacity: 3Ie, 1.05Ue, COSΦ=0.65;
Operation performance: mechanical life of 10,000 cycles, electrical life of 3000 cycles;
Pollution degree: Ⅱ ;
Utilization category: AC-22A, AC-21B;
Installation category: Ⅱ , Ⅲ ;
Installation: TH35-7.5 steel rail mounting, the gradient of the mounting surface from the
vertical plane should be ≤5°;
Wiring: screw clamp wiring, tightening torque 3.5N·m (80A ~ 125A);
tightening torque 2.0N·m(20A ~ 63A).

5. Dimensions and installation sizes


Fig 1 Dimensions and installation sizes

44.5±0.31
34.5±0.31
80 -1.20
0

0
65.5±0.37
1P 18 -0.43
H
0
2P 36 -0.62

0
3P 54 -1.20
0
72 -1.20
4P

1P 2P~4P
0 0
H(mm) 76.3 -1.2 78 -1.2
P- 145 A.1 NXB Series Switch Disconnector

NXHB-125 1P 125A

Frame Poles Current(In)

1P
2P
NXHB-125 20A~125A
3P
4P

Diagram Poles Ie(A) Ue(V) Description Code

1P 20 AC240 NXHB-125 1P 20A 193166

1P 32 AC240 NXHB-125 1P 32A 193167

1P 40 AC240 NXHB-125 1P 40A 193168

1P 63 AC240 NXHB-125 1P 63A 193169

1P 80 AC240 NXHB-125 1P 80A 193170

1P 100 AC240 NXHB-125 1P 100A 193171

1P 125 AC240 NXHB-125 1P 125A 193172

2P 20 AC415 NXHB-125 2P 20A 193173

2P 32 AC415 NXHB-125 2P 32A 193174

2P 40 AC415 NXHB-125 2P 40A 193175

2P 63 AC415 NXHB-125 2P 63A 193176

2P 80 AC415 NXHB-125 2P 80A 193177

2P 100 AC415 NXHB-125 2P 100A 193178

2P 125 AC415 NXHB-125 2P 125A 193179

3P 20 AC415 NXHB-125 3P 20A 193180

3P 32 AC415 NXHB-125 3P 32A 193181

3P 40 AC415 NXHB-125 3P 40A 193182

3P 63 AC415 NXHB-125 3P 63A 193183

3P 80 AC415 NXHB-125 3P 80A 193184

3P 100 AC415 NXHB-125 3P 100A 193185

3P 125 AC415 NXHB-125 3P 125A 193186

4P 20 AC415 NXHB-125 4P 20A 193187

4P 32 AC415 NXHB-125 4P 32A 193188

4P 40 AC415 NXHB-125 4P 40A 193189

4P 63 AC415 NXHB-125 4P 63A 193190

4P 80 AC415 NXHB-125 4P 80A 193191

4P 100 AC415 NXHB-125 4P 100A 193192

4P 125 AC415 NXHB-125 4P 125A 193193

You might also like