FA Design Guide
FA Design Guide
1st Edition
Rev. 0
This manual is a guide for most engineering situations; however it is not a replacement
for good engineering principles or common sense.
1
TABLE OF CONTENTS
Page
1.1 Decide on the appropriate protection category and extent of cover ........................3
2
1 FIRE ALARMS SYSTEM DESIGN PROCESS
3
Malicious false alarms
False alarms with good intent
2.1 ZONING
The floor area of a single zone should not exceed 2,000 m².
Two faults should not remove protection from an area greater than 10,000 m²
(for addressable systems).
If the total floor area of the building is 300 m² or less then it may be regarded as
a single zone.
If the total floor exceeds 300 m² then all zones should be restricted to a single
floor level.
As an exception to the above stairwells, lift shafts or other vertical shafts (non
stop risers) with a single fire compartment should be considered as one or more
separate zones.
The maximum distance traveled within a zone to locate the fire should not
exceed 60 m.
fire alarm
control panel
LCD
display
1524 mm
floor
Shall be located where the panel can be accessed easily in 24 hours and audio
alarm signal can be heard clearly by the assigned personnel such as operator or
security guard.
The place must be clean and safe for the panel, without dust, smoke and high
humidity.
Avoid conduit entry on the top of the FACP enclosure.
Install FACP 1,520 mm (5 feet) above finished floor (AFF) from the panel’s LCD display.
4
2.3 FIRE ALARM REMOTE ANNUNCIATOR
Remote annunciator can be located in different place other than fire alarm panel.
Remote annunciator should be located in the place where it can draw the attention
of the assigned personnel quickly when the fire alarm occurs.
The length of cable from fire alarm panel to the remote annunciator should not
exceed 1000 m.
Install fire alarm remote annunciator 1,524 mm above finished floor (AFF) from the
panel’s LCD display.
5
2.4 MANUAL PULL STATIONS
Manual pull stations shall be located within 1,525 mm (5 feet) of each exit door.
Allowable mounting height of 1067 mm to 1,219 mm (42 inches to 48 inches) from the
floor to the handle.
Where the fire alarm system does not annunciate at a 24/7 manned location signage
is required at each pull station – “When alarm sounds- notify Fire Department and
Control Center”.
The smoke detector should be installed close to the center of the room if the room
size is smaller than 9 x 9 m.
The smoke detector should not be blew by the air conditioner or fan directly.
The distance from the smoke detector to wall should not exceed 4.5 m.
In a large area, the distance between two smoke detectors should not exceed the
9m.
In a corridor, if the width is not more than 3.6 m, the distance between smoke
detectors to wall should be not more than 6m; the distance between two smoke
detectors should be not more than12 m.
6
Standard Reference: NFPA 72, 2007 Edition A.[Link]
not in
this area
102 mm
anywhere
in this area
900 mm 900 mm
S S
1/2S 1/2S
7
6.4 m
6.4 m
6.4 m
6.4 m 6.4 m 6.4
m
3.1 m
6.1 m
5.6 m 11.3 m
22.6 m
25 m
S S S S
1/2S 900 mm
max
= smoke or heat detector
S = space between detectors
8
ceiling 100 mm
acceptable 100 mm
here minimum
never here
300 mm
maximum
Top of the detector
acceptable here
1/4S 1/2S
detectors on bottom
S of joists
1/4S
9
Standard Reference: NFPA 72, 2007 Edition, A.[Link].2
W W W
Smoke detector spacing rules:
D If the ceiling height H is 3.7 m or <, and if the
beam depth D is 0.3 m or <, 1/2S max should be
used in the direction perpendicular to the
H beams, with detectors placed either in the beam
solid beams pocket or the bottoms of beams.
3.1 m
minimum
HVAC
duct 1.2 m
minimum
HVAC
duct
10
Shall be equivalent to a row of spot-type smoke detectors for level and sloping ceiling
applications.
beam beam
1/2S receiver
projector
1/4S S 1/4S
beam beam
1/2S
projector receiver
Must be located downstream of HVAC air filters and ahead of any branch
connections in air-supply system greater than 2,000 cfm except when the entire
space serve by the distribution center is protected by a system of area smoke
detectors, or where fan unit serves solely to exhaust air directly to the outside of the
building.
Duct detectors must be placed at each storey prior to the connection in air-return
system having a capacity greater than 15,000 cfm, or where fan unit serves solely to
exhaust air directly to the outside of the building.
Install 1 duct smoke detector centered in the opening for return ducts up to 0.9m
wide.
11
Install 2 duct smoke detectors in the quarter points of the opening for return ducts 0.9
– 1.8m wide.
For return ducts over 1.8m wide, 2 ducts smoke detectors are required for each 0.6m
of opening in excess of 1.8m, 1 additional smoke duct detector is required.
The heat detector should be installed close to the center of the room if the room size
is smaller than 7.2 x 7.2 m.
The heat detector should not be blew by the air conditioner or fan directly.
The distance from the heat detector to wall should not exceed 4 m.
In a large area, the distance between two heat detectors should not exceed 8 m.
In a corridor, if the width is not more than 3.6 m, the distance between heat detector
to wall should be not more than 4.75 m; the distance between two heat detectors
should be not more than 9.5 m.
12
A A
CB B
C listed
D D spacing
Spot
detector
D’ D’
C’ C’
B’ B’
A’ A’
Rectangles
A = (3.1 m)*(12.5 m) = 38.1 m^2
B = (4.6 m)*(11.9 m) = 51.3 m^2
C = (6.1 m)*(11.3 m) = 68.8 m^2
D = (7.6 m)*(10.4 m) = 78.9 m^2
listed spacing = (9.1 m)*(9.1 m) = 83.6 m^2
not in
this area
102 mm
anywhere
in this area
900 mm 900 mm
S S
1/2S 1/2S
13
6.4 m
6.4 m
6.4 m
6.4 m 6.4 m 6.4
m
3.1 m
6.1 m
5.6 m 11.3 m
22.6 m
25 m
S S S S
1/2S 900 mm
max
= smoke or heat detector
S = space between detectors
14
ceiling 100 mm
acceptable 100 mm
here minimum
never here
300 mm
maximum
Top of the detector
acceptable here
15
Standard Reference: NFPA 72, 2007 Edition, A.[Link]
Maximum
Temperature Ceiling
Rating Range Temperature Color
C C Code
W W W
Heat detector spacing rules:
If D is < or = to 10.7 cm, assume smooth ceiling
D and space detectors at max S.
D = beam depth If D/H is < 0.10 or W/H is < 0.40, place detectors
H = ceiling height on the bottoms of the beams, spaced per rule
W = distance between beams bullets 1 and 2 above.
16
Ceiling Height Up to Multiply
Above and Including Listed
m m Spacing by
0 3.05 1.00
3.05 3.66 0.91
3.66 4.27 0.84
4.27 4.88 0.77
4.88 5.49 0.71
5.49 6.10 0.64
6.10 6.71 0.58
6.71 7.32 0.52
7.32 7.93 0.46
7.93 8.54 0.40
8.54 9.14 0.34
The audible notification appliance should be installed in place where it can be heard
from all rooms in the same floor clearly.
ceiling
Audible
Notification 15.2 cm
appliance minimum
2.3 m minimum
Audible notification appliance
should be located above the
elevation of furniture and
fixtures that could be placed
against the wall.
floor
17
Average Ambient
Location
Sound Level (dbA)
Business occupancies 55
Educational occupancies 45
Industrial occupancies 80
Institutional occupancies 50
Mercantile occupancies 40
Mechanical rooms 85
Piers & water-surrounded structure 40
Places of assembly 55
Residential occupancies 35
Storage occupancies 30
Thoroughfares, high density urban 70
Thoroughfares, medium density urban 55
Thoroughfares, rural & suburban 40
Tower occupancies 35
Underground structures & windowless buildings 40
Vehicles & vessels 50
12.3 m
6.1 m
3.1 m
A B C
Audible
notification
appliance
18
90 axis
si
ax
45
45
ax
is
90 axis
The flash rate shall not exceed two flashes per second (2 Hz) nor be less than one
flash every second (1 Hz) throughout the listed voltage range of the appliance.
Maximum pulse duration shall be 0.2 second with a maximum duty cycle of 40
percent
Light used shall be clear or nominal white and shall not exceed 1000 cd.
Wall mounted appliances shall be mounted such that the entire lens is not less than
2030mm (80 in.) and not greater than 2440 mm (96 in.) above the finished floor.
Where low ceiling heights do not permit mounting at a minimum of 2030 mm (80 in.),
visible appliances shall be mounted within 150mm (6 in.) of the ceiling. The room size
covered by a strobe of a given value shall be reduced by twice the difference
between the minimum mounting height of 2030 mm (80 in.) and the actual, lower
mounting height.
19
Visible
12.2 m
appliance
6.1 m
9.1 m
15.2 m
6.1 m
9.1 m
12.1 m
15.1 m
6.10 x 6.10 3 15
9.10 x 9.10 3 30
12.2 x 12.2 3 60
13.4 x 13.4 3 75
15.2 x 15.2 3 95
16.2 x 16.2 3 110
16.8 x 16.8 3 115
18.0 x 18.0 3 135
19.2 x 19.2 3 150
20.7 x 20.7 3 177
21.3 x 21.3 3 185
6.10 x 6.10 20 30
9.10 x 9.10 20 45
12.2 x 12.2 20 75
13.4 x 13.4 20 80
15.2 x 15.2 20 75
16.2 x 16.2 20 80
16.8 x 16.8 20 95
18.0 x 18.0 20 110
19.2 x 19.2 20 115
20.7 x 20.7 20 135
21.3 x 21.3 20 150
6.10 x 6.10 30 177
9.10 x 9.10 30 185
12.2 x 12.2 30 55
13.4 x 13.4 30 75
15.2 x 15.2 30 95
16.2 x 16.2 30 110
16.8 x 16.8 30 115
18.0 x 18.0 30 135
19.2 x 19.2 30 150
20.7 x 20.7 30 177
21.3 x 21.3 30 185
20
Standard Reference: NFPA 72, 2002 Edition
21
4.5 m
If [Link] is used, it is not necessary to have a corridor strobe within 4.5 m of the end of
the corridor.
Where there are more than 1 in the field of view, they need to be synchronized.
0 - 9.14 1
9.45 - 39.6 2
39.93 - 70 3
70.4 - 100.6 4
100.9 - 131.1 5
131.4 - 161.5 6
22