Kes Klima: Louvred Face

The CDA Louvred Face Ceiling Diffuser is designed for ceiling applications and can be used for both supply and extract air. It features fixed and straight blades for horizontal air throws and is suitable for ceiling heights up to 4 meters. The product includes various accessories such as dampers and plenum boxes, and is available in multiple sizes and colors.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
28 views13 pages

Kes Klima: Louvred Face

The CDA Louvred Face Ceiling Diffuser is designed for ceiling applications and can be used for both supply and extract air. It features fixed and straight blades for horizontal air throws and is suitable for ceiling heights up to 4 meters. The product includes various accessories such as dampers and plenum boxes, and is available in multiple sizes and colors.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

C 04.

01
EN.00

CDA
Louvred Face Ceiling Diffuser

KES KLiMA
A I R C O N T R O L S Y S T E M S
CDA
Description Surface Treatment
The CDA type diffusers are designed for ceiling applications. The surfaces of the diffusers are first cleaned, then treated
They can be used for supply or extract air, together with with chromating process; after which, are painted
the accessories required for various demands. electrostatically, with 20% gloss RAL 9010 (white) as
standard. Other colours are also available upon request.
Louvred Face Ceiling Diffuser

Accessories
Properties Damper With Opposed Blades
The CDA type diffusers have fixed and straight blades. Depending on application characteristics, an opposed
For supply air purposes, they are characteristically blade damper can be installed on the back side of the
suitable for horizontal air throws. Where "Coanda effect" diffuser. This damper is a separate item which can be
is required, they should be installed close to the ceiling. operated by its special tool from the face of the diffuser.
These diffusers are recommended for use with ceiling Opposed blade dampers are manufactured from
heights up to 4 m., with a supply air temperature difference ETIAL-60 norm aluminium extruded profiles. To prevent
of (+/-) 10oC.The diffuser is made of a frame and a central reflection, they are painted RAL 9005 (matt black) as
blade block. The blade block is fixed to the frame by the standard.
aid of spring pins and can easly be removed / installed.
The standard sizes start from 150 x 150 mm, and go up Flap Damper With Rectifier
to 600 x 600 mm with increments of 75 mm.
This type of damper is used in high velocity ducts. The
One, two, three and four way throwing types are available.
rectifier is made of ETIAL-60 norm aluminium profiles
and the flap damper part is formed from steel sheets.
To prevent reflection, they are painted RAL 9005
(matt black) as standard

Plenum Box
Materials The plenum box is used to achieve optimum throw
The frame and the blades are manufactured from ETIAL- characteristics. It has the inlet either at the top or at one
60 norm aluminium profiles. side. Depending on request, a damper can be installed
at the inlet, which can be operated internally or externally
(has to be specified with the order).The plenum boxes are
made from 0.6 mm thick galvanized steel sheets and have
4 hanging brackets on their body.Optionally, a 6 mm thick
acoustic foam can be laid inside the plenum box.

KES KLiMA

2
CDA
Dimensions

TE=E+90 / TB=B+90
E+4/B+4
E/B

Louvred Face Ceiling Diffuser


61

61

6,5 E+145 / B+145 6,5


CDA.32.AA CDA.32.AA

Standard Dimensions (mm)

E B ØD H G E B ØD H G

150 170 250 150 300 295 450 225


225 244 350 175 375 346 450 225
300 244 350 175 300 450 447 550 275
150 375 295 450 225 525 447 550 275
450 346 450 225 600 498 600 300
525 346 450 225 375 396 500 250
600 346 450 225 450 447 550 275
375
225 244 350 175 525 498 600 300
300 295 400 225 600 498 600 300
375 346 450 225 450 498 600 300
225
450 396 500 250 450 525 498 600 300
525 396 500 250 600 498 600 300
600 447 550 275 525 498 600 300
525
600 498 600 300
600 600 498 600 300
KES KLiMA

Externally Operated Side Inlet Internally Operated Side Inlet

KE / KB KE / KB
G G

25 25

ØD ØD
H H

KE= E+ 90 KE= E+ 90
KB= B+ 90 KB= B+ 90

Externally Operated Top Inlet Internally Operated Top Inlet


K /K KE / KB
E B
ØD ØD
G
G

H H

KE= E+ 90 KE= E+ 90
KB= B+ 90 KB= B+ 90

3
CDA
Installation
With Screws Concealed Fixing
Louvred Face Ceiling Diffuser

35

min. 12 mm
maks. 22 mm
6,5

A set of Ø 4.2 x 38 mm self-drilling screws, painted the same, Suitable for ceiling thickness 12-22 mm. For other thicknesses,
are given with the product please contact us.

Plenum box installation (top inlet) Plenum Box installation (side inlet)

KES KLiMA
There are 4 hanging brackets on the box as standard There are 4 hanging brackets on the box as standard

Application of flap damper with rectifier

Applied in high speed ducts

4
CDA
Nomenclature

L1 (m)
veff. (m/s)
veff. (m/s) veff. (m/s)
V (m3/h) L (m) = L1 + h2
V (m3/h) V (m3/h)

Louvred Face Ceiling Diffuser


L1 (m)
h2 (m)

h2 (m)
L (m) = (L1 / 2) + h2

H(m) 7,5 cm H(m)

vL
(m/s) vL (m/s)
h1 (m)
1,7 m

h1 (m)
1,7 m
Comfort Zone
Comfort Zone

L1 Distance between diffuser centres or diffuser centre and wall. (m)


h1 Comfort zone height (m)
h2 Distance between a diffuser and comfort zone (m)
veff Effective outlet velocity (m/s)
vL Velocity of core in comfort zone
t0 Difference between supply air and room temperature ( o C)
tL Difference between core and comfort zone temperature (oC)
L Throw distance (m)
V Air flow rate (m3/h)
H Room height (m)
S Sound power level dB(A)
KES KLiMA

To achieve "Coanda effect", the outlet velocity must be Note: The tables are given for 4 types of blade blocks
greater than 2m/s. The general comfort conditions (11,21,24,41). For other types of blocks listed on page
require that the sound power level is below 40 dB(A). 11, please contact us.
The height of the comfort zone is taken as 1.70m above
the floor. It is important that 0.25 m/s core velocity is not
exceeded in this zone.

Sound power pressure drop The data given in the tables are valid for supply air, without
level
dampers. For other conditions, the correction factors in the
Supply air, with damper +3 dB (A) x 1,0
table (left) have to be applied
Extract air +3 dB (A) x 1,1
Extract air with damper +13 dB (A) x 1,15

5
CDA Technical Data

11
Louvred Face Ceiling Diffuser

KESKLiMA

Size Flow Rate Throw, L (m) Pressure loss Sound power level
E/B (mm) V(m3/h) vL=0,25 m/s vL=0,10 m/s P (Pa) S (dB(A))

120 1,50 2,50 9 <20


160 2,00 3,50 15 <20
150 x 150 200 2,20 4,50 23 25
250 2,50 5,50 33 29
280 3,00 6,00 43 33
280 2,00 4,00 9 <20
370 2,50 5,50 15 25
225 x 225 460 3,50 6,50 23 30
550 4,00 8,00 33 34
640 4,50 9,00 43 37
490 2,50 5,50 9 <20
650 3,50 6,50 15 28
300 x 300 810 4,50 8,50 23 33

KES KLiMA
970 5,00 10,50 33 37
1130 6,50 12,00 43 40
760 3,50 6,50 9 <20
1010 4,50 8,50 15 30
375 x 375 1270 5,50 11,00 23 35
1520 6,50 13,50 33 39
1770 7,50 15,00 43 42
1100 3,50 7,00 9 <20
1460 5,50 10,00 15 30
450 x 450 1820 6,50 13,00 23 40
2190 7,50 16,00 33 40
2550 9,00 18,00 43 45
1490 4,00 8,00 9 25
1980 5,50 10,00 15 35
525 x 525 2480 6,50 13,00 23 40
2980 7,00 14,00 33 45
3470 9,50 18,50 43 45
1950 4,50 8,50 9 25
2590 6,00 11,00 15 35
600 x 600 3240 7,00 14,00 23 40
3890 8,50 17,00 33 45
4540 10,00 19,00 43 50

6
CDA
Technical Data

21

Louvred Face Ceiling Diffuser


KESKLiMA

Size Flow Rate Throw, L (m) Pressure loss Sound power level
E/B (mm) V(m3/h) vL=0,25 m/s vL=0,10 m/s P (Pa) S (dB(A))

120 1,00 2,00 9 <20


160 1,20 2,50 15 <20
150 x 150 200 1,50 3,00 23 25
250 2,00 3,50 33 29
280 2,20 4,50 43 32
280 1,50 2,50 9 <20
370 2,00 3,50 15 25
225 x 225 460 2,50 5,00 23 30
550 2,70 5,50 33 34
640 3,00 6,00 43 37
490 2,00 3,50 9 <20
650 2,50 5,00 15 28
300 x 300 810 3,00 6,00 23 32
KES KLiMA

970 3,50 7,50 33 37


1130 4,50 8,50 43 40
760 2,50 4,50 9 <20
1010 3,00 6,00 15 30
375 x 375 1270 4,00 7,50 23 35
1520 5,00 9,50 33 39
1770 5,50 11,00 43 42
1100 2,50 6,00 9 26
1460 3,50 7,50 15 32
450 x 450 1820 4,50 9,00 23 37
2190 5,50 11,00 33 40
2550 6,50 13,00 43 44
1490 3,00 6,50 9 30
1980 4,00 8,00 15 35
525 x 525 2480 5,00 10,00 23 40
2980 6,50 13,00 33 45
3470 7,50 15,00 43 45
1950 3,50 7,00 9 30
2590 4,50 8,50 15 35
600 x 600 3240 5,50 10,50 23 40
3890 6,50 13,00 33 45
4540 7,00 15,00 43 45

7
CDA Technical Data

24
Louvred Face Ceiling Diffuser

KESKLiMA

Size Flow Rate Throw, L (m) Pressure loss Sound power level
E/B (mm) V(m3/h) vL=0,25 m/s vL=0,10 m/s P (Pa) S (dB(A))
120 1,00 2,00 9 <20
160 1,10 2,50 15 <20
150 x 150 200 1,50 3,00 23 20
250 2,00 3,50 33 24
280 2,00 4,50 43 28
280 1,50 2,50 9 <20
370 2,00 3,50 15 20
225 x 225 460 2,50 5,00 23 25
550 2,70 5,50 33 29
640 3,00 6,00 43 32
490 2,00 3,50 9 <20
650 2,50 5,00 15 23
300 x 300 810 3,00 6,00 23 28

KES KLiMA
970 3,50 7,50 33 32
1130 4,50 8,50 43 35
760 2,50 4,50 9 <20
1010 3,00 6,00 15 25
375 x 375 1270 4,00 7,50 23 30
1520 5,00 9,50 33 34
1770 5,50 11,00 43 37
1100 2,50 6,00 9 21
1460 3,50 7,50 15 27
450 x 450 1820 4,50 9,00 23 32
2190 5,50 11,00 33 35
2550 6,50 13,00 43 39
1490 3,00 6,50 9 25
1980 4,00 8,00 15 30
525 x 525 2480 5,00 10,00 23 35
2980 6,00 12,00 33 40
3470 7,00 14,00 43 40
1950 3,00 7,00 9 25
2590 4,00 9,00 15 30
600 x 600 3240 5,00 11,00 23 35
3890 6,00 13,00 33 40
4540 7,00 15,00 43 40

8
CDA
Technical Data

41

Louvred Face Ceiling Diffuser


KESKLiMA

Size Flow Rate Throw, L (m) Pressure loss Sound power level
E/B (mm) V(m3/h) vL=0,25 m/s vL=0,10 m/s P (Pa) S (dB(A))
120 1,00 1,50 9 <20
160 1,10 2,00 15 <20
150 x 150 200 1,50 2,50 23 <20
250 1,70 3,00 33 <20
280 2,00 3,50 43 19
280 1,00 2,00 9 <20
370 1,50 2,50 15 <20
225 x 225 460 2,00 3,50 23 <20
550 2,10 4,00 33 23
640 2,20 4,50 43 27
490 1,50 2,50 9 <20
650 2,00 3,50 15 20
300 x 300 810 2,20 4,50 23 25
KES KLiMA

970 2,50 5,00 33 29


1130 3,00 6,00 43 32
760 2,00 3,50 9 <20
1010 2,20 4,50 15 24
375 x 375 1270 2,50 5,50 23 29
1520 3,50 6,50 33 33
1770 4,00 7,50 43 37
1100 2,00 4,00 9 22
1460 2,50 5,00 15 28
450 x 450 1820 3,50 6,50 23 33
2190 4,00 8,00 33 36
2550 4,50 9,00 43 40
1490 2,50 5,00 9 25
1980 3,00 6,00 15 30
525 x 525 2480 4,00 8,00 23 35
2980 4,50 9,00 33 40
3470 5,00 10,50 43 45
1950 2,50 5,50 9 30
2590 3,50 7,00 15 35
600 x 600 3240 4,50 8,50 23 40
3890 5,00 10,50 33 45
4540 6,00 12,00 43 45

9
CDA
Example:
Air at 6000 m3/h, is to be supplied into a room with Determine diffuser spacings so that the core velocity in
dimensions 16 x 8m, and a height of 3.10 m .The supply air comfort zone is below 0.25 m/s.
is 8oC below room temperature and 4 units of 4-way diffusers
will be used.
Louvred Face Ceiling Diffuser

4m 2m

Max.distance Min.distance
(L=5.4 metre) (L=3.4 metre)
1500m3/h
4m 8m 4m
Max.Distance
Min. Distance

1.4 m
2m

1500m3/h 1500m3/h
v=0.25 m/s v=0.25 m/s

3.1 m
4m

Comfort zone

1.7 metre
1500m3/h 1500m3/h
2m

Solution:

1) Diffusers are placed on the ceiling plan symmetrically.

2) Air flow rate per diffuser is calculated as 6000 / 4 = 1500 m3/h.

3) Calculation of path length to the comfort zone:

Minimum distance: L= 2.0 + 1.40 = 3.40 m

KES KLiMA
Maximum distance: L= 4.0 + 1.40 = 5.40 m.

4) From the table on page 9, the most suitable size is found as

375x375 mm; for 1500 m3/h and 3.40 m throw.

5) From the same table with interpolation, pressure loss is read

as 32 Pa and sound power level as 33 dB(A).

10
CDA
Blade Block Codes

11 12 13

Louvred Face Ceiling Diffuser


21 22 23

24 25 26
KES KLiMA

31 32 33

41 42

Note: The views shown are face views, and throw directions are as seen from below. For blocks 25 and 26 care should be
taken when ordering.

11
CDA
Specification Text
Air diffuser for ceiling installation. The diffuser will be 0.6 mm galvanized steel sheets by seams. There will be 4
manufactured from ETIAL-60 norm aluminium profiles, hanging brackets on the box. Optionally, the entry spigot
and chromated. After chromating, will be painted to ordered will be equipped with a volume control damper, operated
request with electrostatic powder paint and a minimum externally or internally, depending on request. Also, optionally,
Louvred Face Ceiling Diffuser

thickness of 60 m.The diffuser will be made of a frame and 6-mm thick acoustic foam (according to BS 476 Part 6 & 7
a central blade block. The blade block will be fixed to the Class 0) will be installed inside the plenum box.
frame by the aid of spring pins and will be easy to be
removed / installed.Optionally, a damper will be installed on
the back side of the diffuser. This damper will be a separate
item which will be formed from ETIAL-60 norm aluminium
profiles and be operated from the face of the diffuser.
To prevent reflection, the damper will be painted RAL 9005
(matt black).The plenum box will be manufactured from

Order Code
Model CDA.32.AA.1 1-375 x 375 - 41 - 9010
E x B (mm) Refer to indicate
Refer to page 3 page 11 RAL
Frame 32 mm 11, 12, 13, colour
code
21, 22, 23,
AA ..W i t h o u t a c c e s s o r i e s 24, 25, 26,
Accessories ZA ..Opposed blade damper 31, 32, 33,
41, 42

0.....Without screw holes


Installation 1.....WÝth screw holes
3.....Concealed fixing

Installation accessories 0.....Without installlation bridge Standard block Colour


1.....With installation bridge Dimensions code Code

KES KLiMA
Plenum Box Order Code
Model PLA.10.S B.1 1-465 x 465 x 500 x 396 x 1
Please indicate if special dimensions are requested
10...With Screws
Installation 30...Concealed Fixing
KE x KB x H x ØD (mm) x s (no. of inlet spigots)

S ....Side Inlet
Box Inlet T.....Top Inlet

A ....Without Damper
spigot Damper B ....Externally Operated
C ....Internally Operated

Perforated 0.....Without Plate


Rectifier Plate 1.....With Plate

0.....Without Insulation
Insulation 1.....With Acoustic Insulation Plenum Box Dimensions

12
C.04.01.EN.00

C Louvered Face
CDA Ceiling Diffuser

KES KLiMA
I N D U S T R I A L A N D T R A D E C O .

Uzay Çaðý Caddesi No:10