Honeywell Rc500 Rc-Scontrl Rtu Users Guide
Honeywell Rc500 Rc-Scontrl Rtu Users Guide
Release 100
Honeywell
Notices and Trademarks
While this information is presented in good faith and believed to be accurate, Honeywell disclaims
the implied warranties of merchantability and fitness for a particular purpose and makes no
express warranties except as may be stated in its written agreement with and for its customers.
In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The
information and specifications in this document are subject to change without notice.
Honeywell, PlantScape, Experion PKS, and TotalPlant are registered trademarks of Honeywell
International Inc.
Release Information
Document Name Document Release Publication
ID Number Date
Europe
Contact: Honeywell TAC-EMEA
Phone: +32-2-728-2732
Facsimile: +32-2-728-2696
Mail: TAC-BE02
Hermes Plaza
Hermeslaan, 1H
B-1831 Diegem, Belgium
Pacific
Contact: Honeywell Global TAC – Pacific
Phone: 1300-300-4822 (toll free within Australia)
+61-8-9362-9559 (outside Australia)
Fascimile: +61-8-9362-9564
Mail: Honeywell Limited Australia
5 Kitchener Way
Burswood 6100, Western Australia
Email: [email protected]
India
Contact: Honeywell Global TAC – India
Phone: +91-20- 6603-9400
Fascimile: +91-20- 6603-9800
Mail: Honeywell Automation India Ltd
56 and 57, Hadapsar Industrial Estate
Hadapsar, Pune –411 013, India
Email: [email protected]
Korea
Contact: Honeywell Global TAC – Korea
Phone: +82-80-782-2255 (toll free within Korea)
Fascimile: +82-2-792-9015
Mail: Honeywell Co., Ltd
4F, Sangam IT Tower B4-4 Block
1590, DMC Sangam-dong, Mapo-gu,
Seoul, 121-835, Korea
Email: [email protected]
Singapore
Contact: Honeywell Global TAC – South East Asia
Phone: +65-6580-3500
Fascimile: +65-6580-3501
+65-6445-3033
Mail: Honeywell Private Limited
Honeywell Building
17, Changi Business Park Central 1
Singapore 486073
Email: [email protected]
Taiwan
Contact: Honeywell Global TAC – Taiwan
Phone: +886-7-536-2567
Fascimile: +886-7-536-2039
Mail: Honeywell Taiwan Ltd.
17F-1, No. 260, Jhongshan 2nd Road.
Cianjhen District
Kaohsiung, Taiwan, ROC
Email: [email protected]
Japan
Contact: Honeywell Global TAC – Japan
Phone: +81-3-6730-7160
Fascimile: +81-3-6730-7228
Mail: Honeywell Japan Inc.
New Pier Takeshiba, South Tower Building,
20th Floor, 1-16-1 Kaigan, Minato-ku,
Tokyo 105-0022, Japan
Email: [email protected]
Elsewhere
http://www.honeywell.com/ps
Training Classes
Honeywell Automation College:
http://www.automationcollege.com
Symbol Definitions
The following table lists those symbols used in this document to denote certain conditions.
Symbol Definition
Symbol Definition
Feature Description
Feature Description
Redundancy
Feature Description
Ethernet ports
Feature Description
Feature Description
Serial ports
Feature Description
Diagnostic LEDs on each port Transmit Data (TD) and Receive Data
(RD)
Feature Description
Data bits 8, 7
Stop bits 1, 2
RS485 Features
Feature Description
Data bits 8, 7
Stop bits 1, 2
Feature Description
REFERENCE - INTERNAL
Refer to the Honeywell RC500 SIUG for more information regarding
Honeywell RC500 I/O Tool Kit installation and registration.
ATTENTION
In the Honeywell RC500 I/O Tool Kit, RTUs and I/O modules are known as
station.
If you want to add a station to an existing project, on the left-pane, in the Tree
views right-click All Stations and choose New Station under By Type tab.
4 In the list, click RC500 RTU and click OK.
ATTENTION
• Station name should not exceed 20 characters, and in special
characters, only the underscore is allowed.
• Value for the station number should be between 0 and 15999.
• The serial number can be found at the base of the RTU.
7 In the Station Type list, click RC-SCONTRL.
8 Click Configure Later.
The two Ethernet ports should be assigned IP addresses and subnet masks such that they
operate on independent Ethernet networks. If the two Ethernet ports are configured to
reside on the same Ethernet network, the RTU’s operating system may disable one of the
two Ethernet ports and might result in undesired behavior.
The following table provides information about the protocols supported by the RTU.
• Peer-to-peer RTU
DNP3 UDP / TCP 20000 Used for communication between RTU and
SCADA.
Step Action
4 Under IP address, click any one of the options provided.
• Automatically assign IP address based on station number
Select this option to automatically assign IP address based on station
number.In this case, if the station number is changed, the IP address also
changes automatically.
• Use DHCP
Select this option to allow DHCP server to assign the IP addresses to the
stations.
• Manually assign IP address
Select this option to assign IP address manually.
5 Click Advanced.
ATTENTION
Subnet Mask
TCP/IP Timeout
TCP/IP gateway
This feature allows the station to communicate with devices on other
networks. If you specify TCP/IP gateway address, then the TCP/IP
gateway routes messages to the other networks.
9 Click Ethernet2 and then click Configure Selected Port.
Step Action
10 Perform the steps from step 4 to step 8.
11 In the Ethernet Port Configuration dialog box, click OK.
Protocol Use
DNP3 Serial protocol Used for communication between RTU and SCADA.
ATTENTION
ATTENTION
RC500, Modbus RTU Master, Modbus ASCII Master, Modbus
RTU Slave, Modbus ASCII Slave, and DNP V3.00 Slave are the
protocols that are supported currently.
5 Select appropriate values in the Baud rate, Parity, Data bits, and Stop bits
list.
6 In the Flow control list, click the required flow control method.
ATTENTION
For RS485 port, the only value available is 2-Wire Party Line.
7 In the Lead time box and in the Lag time box, enter appropriate values.
ATTENTION
The Lead time and Lag time boxes are enabled only if the Half
Duplex Modem or the Full Duplex Modem is selected as flow
control method.
8 In the Passthru to list, click the required COM port through which the data
should be passed.
ATTENTION
The Passthru to list is enabled only for RC500 protocol.
Step Action
9 If you want to connect a modem to the port, select Set modem check box, and
enter the Modem Initialization string in the Set modem box.
The RTUs use built-in redundancy features to identify the failure and to switch-over
between the RTUs.
The conditions in which the redundancy are supported or not supported are provided in
the following list.
Supported:
• Serial port redundancy is supported. Redundant RTUs communicates to third-party
serial devices through Modbus. Here, the RTU acts as Modbus master. If there is
RTU to third-party communication over serial, and if switch over happens, then the
redundancy is achieved.
• RTU-SCADA redundancy over TCP/IP for single LAN (Ethernet) is supported.
RTU redundancy to SCADA is achieved through Modbus and DNP3 protocols over
TCP/IP. Here, RC500 acts as slave.
• I/O Module communication redundancy is achieved through ring configuration using
the ring switches.
Not Supported:
• RTU-SCADA redundancy over serial is not supported. RTU redundancy to SCADA
is not achieved through Modbus and DNP3 over serial, and over terminal server
configurations. If the RTU communicates to SCADA over serial, and if there is a
switch over, then the redundancy is not achieved.
• I/O Module redundancy is not supported.
The following table provides more information about the Station Status Module
variables.
Variable Description
Other_Active This bit is the Self_Active bit from the other station. This
is used by the built-in redundancy feature to determine
whether the RTU should be in Active mode or in Back-
up mode.
ATTENTION
If you want to add a station to an existing project, right-click All
Stations and choose New Station under By Type tab in the tree
views.
4 In the list, click RC500 RTU and click OK.
Step Action
ATTENTION
If you want to enable the secondary RTU to an existing station,
perform the following steps.
1. Right-click the station and choose Configure.
The RC500 RTU Station Configuration dialog box appears.
2. In the General tab, select the Automatically configure a
secondary controller check box and the Enable built-in
redundancy check box.
10 Click Next.
Step Action
h) In the Ethernet Port Configuration dialog box, click OK.
ATTENTION
Subnet Mask
TCP/IP Timeout
Or
• If you want to use different station numbers for secondary RTU station and
primary RTU station, click Use a unique station number and enter a
station number in the box.
Step Action
ATTENTION
• If the communication between SCADA and RTU is through
Modbus, then use the same station number for the primary
RTU and the secondary RTU.
• If the communication between SCADA and RTU is through
DNP3, then you can either use same station number for both
primary RTU and the secondary RTU or you can use unique
station number for both RTUs.
18 In the IP Address box and in the 2nd IP Address box, enter the IP
addresses for the secondary RTU.
ATTENTION
Ensure that both the IP addresses are in different subnet mask.
19 Under Built-in redundancy options, click the General tab.
20 Select Enable built-in redundancy and select Enable common IP.
The Common IP box and the Subnet mask box are available for editing.
ATTENTION
The Enable common IP option is enabled only if the Enable
built-in redundancy check box is selected.
21 Enter an IP address in the Common IP box.
ATTENTION
Common IP address should be a unique IP address in LAN2. The
Experion server uses this IP address to communicate with the
RTU. The common IP address is bound to the RTU that is
currently acting as primary.
Step Action
ATTENTION
• If the primary RTU fails, then the secondary RTU waits for the
allowable loss period and changes the status to primary.
• The default synchronization period is 50 ms. You can change
the synchronization period by performing the following steps.
a) Click I/O Transfers tab.
b) Click _StaStatWire_ transfer and click Edit Selected
Transfer.
The I/O Transfer Configuration page appears.
c) Click Action Definition tab.
d) Under Scan time/ trigger,
− In the Scan option list, click Use the Specified Interval
Time.
− In the Scan interval time list, click the period of your
choice. This interval is the synchronization period.
e) To add an alert about the synchronization failure, in the
Scan enable flag list, click Self_Active.
23 Click Virtual I/O Synch.
24 Enter the number of registers required in Num Regs and the starting register
number in Start Addr for different I/O types.
These are used to create the range for all output types and to synchronize
outputs between the two RTUs.
ATTENTION
• Do not change the Redundancy bits (Digital Output) starting
address. The default starting address is zero.
• Do not synchronize the first seven Digital Output registers as
they are used by the RTUs for redundancy operations.
Step Action
25 Click Finish.
ATTENTION
To enable redundancy, you have to create an ISaGRAF program
and load it in the RTU. To know more about creating and loading
ISaGRAF program, refer to Creating and loading ISaGRAF
program for redundancy.
Step Action
1 Open the ISaGRAF tool.
2 Create a new ISaGRAF project.
3 Add a new program and add a functional block diagram to the program.
4 In the Honeywell RC500 I/O Tool Kit, choose File > Export > I/O Definitions
to > ISaGRAF.
Step Action
11 Once the tags are exported, click Close.
12 Open the ISaGRAF tool and open the functional block diagram.
13 Create a functional block diagram for redundancy similar to the diagram
shown below.
14 In the Honeywell RC500 I/O Tool Kit, load the ISaGRAF program to the RTU.
REFERENCE INTERNAL
For more information about loading an ISaGRAF program to the
RTU, refer to Loading an ISaGRAF program to RTU.
Configure synchronization
While adding secondary RTU, it is essential to synchronize the output of the primary
RTU with the secondary RTU.
ATTENTION
• Heart beat messages are exchanged through Ethernet1 port.
• Ethernet1 port of Primary RTU and Secondary RTU should be connected
through a switch and should not be connected directly. If connected
directly and if the cable between both the Ethernet1 ports fails, then both
the RTUs go to backup state, which results in a single point failure.
Perform the following steps to synchronize outputs between the primary RTU and the
secondary RTU.
Step Action
1 Right-click the station (primary RTU) and choose Configure.
ATTENTION
Only outputs can be synchronized.
7 Click Redundant Controller Options tab.
8 Under Built-in redundancy options, click Virtual I/O Synch tab.
9 In Discrete Output row, click the cell under Start Addr and enter the value
from which the register number must start.
ATTENTION
Ensure to enter the same value entered for Starting Register
Number in Auto-Create Virtual Modules dialog box.
10 In Discrete Output row, click the cell under Num Regs and enter the number
of registers required.
Step Action
ATTENTION
Ensure to enter the same value entered for Number of Registers in
Auto-Create Virtual Modules dialog box.
11 In Analog Output row, click the cell under Start Addr and enter the value from
which the register number must start.
ATTENTION
Ensure to enter the same value entered for Starting Register
Number in Auto-Create Virtual Modules dialog box.
12 In Analog Output row, click the cell under Num Regs and enter the number of
registers required.
ATTENTION
Ensure to enter the same value entered for Number of Registers in
Auto-Create Virtual Modules dialog box.
13 Click OK.
Step Action
1 Right-click the station (primary RTU) and choose Configure.
Or
Step Action
6 Click Next.
ATTENTION
Using I/O transfers, you can either read data from the remote
station or write data to the remote station.
8 Click Next.
ATTENTION
Peer-to-peer communication is possible through the serial ports
and the Ethernet ports.
10 Check the Current port settings.
Serial ports
a) Click Advanced.
b) In the Data format list, click either Binary or Hex, depending on the type
of data transfer.
Select Binary if 8-bit data format is required and select ASCII (Hex) if
7-bit data format is required.
c) In the Messaging sequence list, click either Rapid Fire or Wait for
Reply.
Step Action
Normally, whenever there is heavy network traffic, 'Wait for Reply' is
used. Whenever there is high network bandwidth, 'Rapid fire' is used.
d) In the Message timeout box, enter the time in milliseconds.
The default communication timeout is three seconds. This is displayed
as a "3000" in the Message timeout box. Enter a longer timeout to
compensate for transmission delays or data errors. Enter a shorter
timeout to communicate over direct wiring and to perform quicker retries
if there is any communication error.
e) In the Message attempts, enter the number of times the station would
send messages to remote station or I/O module before moving to the
next station or I/O module.
Whenever the network traffic is high, the number of message attempts is
also high. Whenever the traffic is low, then the number of message
attempts is also low.
f) Select Most significant word (MSW) first check box.
Select this parameter only if the station communicates with a third-party
Modbus slave device that swaps the word order when reading or writing
32-bit long integer values. By default, RC500 products that support
Modbus communication do not swap the word order.
If this parameter is selected, the master station reverses the order of the
two analog registers in each 32-bit long integer value when sending or
replying to third-party Modbus commands for long integer I/O. This
parameter has no effect on floating point values or when using Daniel
Extensions to read or write long integer values.
ATTENTION
If there is any mismatch between the Serial port type selected in the
Current port settings, and the protocol type selected in the Ports tab,
then a protocol error message appears.
If the error occurs, click Yes and update the port settings in Select
Transfer Type page to match the protocol.
Ethernet ports
Step Action
d) In the Message attempts, enter the number of times the station would
send messages to remote station or I/O module before moving to the
next station or I/O module.
e) Click Next.
The Scan Options page appears.
Or
ATTENTION
Local registers - Virtual I/O module address of RTU that
requests data.
Step Action
13 Click Next.
The summary of the I/O transfer appears and if you click any of the
parameter, the corresponding configuration page of the I/O transfer appears.
For more information about how to add a virtual I/O module, refer to Adding
Virtual I/O modules section.
3 Click the I/O Transfers tab.
4 Click Wizard – Add New Transfer.
Or
Step Action
different manufacturer, then
a) Select the Specify by station number check box.
b) In the Remote station number box, enter the remote station number.
c) Click Next.
The Select Transfer Name page appears.
6 In the Name box, enter a name for the transfer.
ATTENTION
Using I/O transfers, you can either read data from the remote
station or write data to the remote station.
9 Click Next.
ATTENTION
Peer-to-peer communication is possible through the serial ports
and the Ethernet ports.
11 Check the Current port settings.
Step Action
Serial ports
a) Click Advanced.
b) In the Data format list, click either Binary or Hex, depending on the type
of data transfer.
c) In the Messaging sequence list, click either Rapid Fire or Wait for
Reply.
Normally, whenever there is heavy network traffic, 'Wait for reply' is used.
Whenever there is high network bandwidth, 'Rapid fire' is used.
d) In the Message timeout box, enter the time in milliseconds.
The default communication timeout is three seconds. This is displayed
as a "3000" in the Message timeout box. Enter a longer timeout to
compensate for transmission delays or data errors. Enter a shorter
timeout to communicate over direct wiring and to perform quicker retries
if there is any communication error.
e) In the Message attempts, enter the number of times the station would
send messages to remote station or I/O module before moving to the
next station or I/O module.
Whenever the network traffic is high, the number of message attempts is
also high. Whenever the traffic is low, then the number of message
attempts is also low.
f) Select the Most significant word (MSW) first check box.
Select this parameter only if the station communicates with a third-party
Modbus slave device that swaps the word order when reading or writing
32-bit long integer values. By default, RC500 products that support
Modbus communication do not swap the word order.
If this parameter is selected, the master station reverses the order of the
two analog registers in each 32-bit long integer value when sending or
replying to third-party Modbus commands for long integer I/O. This
parameter has no effect on floating point values or when using Daniel
Extensions to read or write long integer values.
g) Click Next.
The Scan Options page appears.
ATTENTION
If there is any mismatch between the Serial port type selected in
the Current port settings, and the protocol type selected in the
Ports tab, then a protocol error message appears.
If the error occurs, click Yes and update the port settings in Select
Transfer Type page to match the protocol.
Step Action
Ethernet ports
Or
Or
Step Action
• Select the Use a Trigger Name box and enter the trigger name that is
assigned for this I/O transfer.
14 Click Next.
You can configure up to 1024 registers in each type of virtual I/O module. The following
are the types of virtual I/O modules that can be added to the RTU.
• Discrete Inputs
• Discrete Outputs
• Analog Inputs
• Analog Outputs
• Floating Point Inputs
• Floating Point Outputs
• Long Integer Inputs
• Long Integer Outputs
Perform the following steps to add a virtual I/O module.
Step Action
1 Right-click the station and choose Configure.
ATTENTION
The types of Input/Output available are given in a tabular format. By
default, the value of the starting register number and the number of
registers is set to None. You can change these values as per
requirement.
Step Action
4 For a particular I/O type, click the respective cell under Starting Register
Number.
5 Enter the value from which the particular I/O type register number must start.
6 For a particular I/O type, click the respective cell under Number of Registers
and enter the number of registers required.
Step Action
1 Choose Operations > Advanced Operations > Tag Restrictions.
ATTENTION
To follow IEC 1131-3 tag name standard, under Restriction
Types, click IEC 1131-3 Tags.
3 Select the options given under Restrictions as per requirement.
Once you select the options, if any tag name does not follow the restriction,
then in the Honeywell RC500 I/o Tool Kit the particular tag name is
highlighted in yellow color.
The following list provides the options that are available for selection.
• Spaces Not Allowed in Tag Names
4 Click Options.
These options are used to check the duplicate tag names, IP addresses,
station numbers, and so on. Once you select the options, and if any duplicate
item is found, then the Status field displays ‘ERROR’ message.
6 Click OK and again click OK.
Note: The Current port settings vary depending on the port that is selected.
a) In the Data format list, click Binary or Hex, depending on the type of
data transfer.
b) In the Messaging sequence list, click either Rapid Fire or Wait for
Reply.
Normally, whenever there is heavy network traffic, 'Wait for reply' is used
and whenever high network bandwidth is used, 'Rapid fire' is used.
c) In the Message timeout box, enter the time in milliseconds.
The default communication timeout is three seconds. This is displayed
as a "3000" in the Message timeout box. Enter a longer timeout to
compensate for transmission delays or data errors. Enter a shorter
timeout to communicate over direct wiring and to perform quicker retries
if there is any communication error.
d) In the Message attempts, enter the number of times the station would
send messages to remote station or I/O module before moving to the
next station or I/O module.
Whenever the traffic is high, then the number of message attempts is
also high. Whenever the traffic is low, then the number of message
attempts is also low.
Step Action
6 Under Scan time/trigger, perform the following tasks.
ATTENTION
To configure an I/O module for a redundant RTU, perform the
following:
1. Under I/O scan options, select Use built-in redundancy
options check box.
2. In the Read output enable list, click Self_Backup and select
Read DO and Read AO check boxes. Selecting the Read DO
and Read AO check boxes ensures that the outputs are read
by the redundant RTU.
3. In the Write output enable list, click Self_Active and select
Write DO and Write AO check boxes. Selecting the Write DO
and Write AO check boxes ensures that the outputs are set by
the primary RTU. Both the RTUs read the input parameters.
7 Click Discrete Options tab.
8 Under Discrete input options, enter a value in First DI register box.
ATTENTION
The I/O address of the Discrete input starts from the value entered in
the First DI register box. For example, if you enter 2 in the First DI
register box, the discrete input I/O address starts from X2.
9 Select Retain values on power loss check box.
The RTU retains the current values of the module if power is lost or cycled.
10 Click Discrete Tags tab.
Step Action
11 Perform the following steps in the Discrete Tags page.
a) In the I/O Tag Name column, enter the name for the particular I/O
register.
b) In the OFF Message column, enter the message to be displayed if the
specific register is in OFF state.
c) In the ON Message column, enter the message to be displayed if the
specific register is in ON state.
12 Click Analog Options tab.
13 Under Analog input options, enter a value in First AI register box.
ATTENTION
The I/O address of the Analog input starts from the value entered
in the First AI register box. For example, if you enter 2 in the First
AI register box, the Analog Input I/O Address starts from AX2.
14 Select Retain values on power loss check box.
The RTU retains the current values of the module if power is lost or cycled.
15 Click Analog Tags tab.
16 In the I/O Tag Name column, enter the name for the particular I/O register.
17 Click OK.
ATTENTION
To know about the I/O module that a particular station is
configured to, click Address Map in the I/O Modules tab and
check the details in the Station I/O Address Map dialog box.
The DNP3 Slave Driver is an add-on option to the firmware that needs to be purchased
separately and registered before it can run continuously.
If the DNP3 is not registered, the DNP3 Slave Driver executes in the demo mode. In this
mode, the driver is fully functional, but operates as follows:
• The driver runs continuously for one hour, then the driver stops and does not process
any DNP3 request from the master station.
• The DNP3 configuration needs to be reloaded before the driver works for another
hour.
Step Action
ATTENTION
• If you click Level 2 option button, it does not support frozen
analog input, frozen analog event, and frozen counter change.
• If you select Enable Unsolicited Responses, then the RTU
sends event data to SCADA without any request from SCADA.
6 Under On new event when Event Queue is full,
• Click Discard Newest Event, if you want to remove the new event.
or
• Click Discard Oldest Event, if you want to remove the oldest event.
Step Action
ATTENTION
SCADA Master monitors the data from many DNP3 Slaves through
RS-485 network (multi-drop links). However, RS-485 network
supports only simplex (one-way communication at a time) and if
unsolicited response is enabled, then multiple RTUs try to transmit
data at the same time. In this scenario, RTU supports a collision
avoidance algorithm.
or
• If you want to establish Ethernet TCP communication from RTU based
controllers, click TCP option button and perform the following under
TCP/UDP.
a) Click Client and type the IP address of the host (server).
b) Type the value in TCP/UDP Port box that is used in TCP/UDP
communication.
or
a) Click Server.
b) Type the value in TCP/UDP Port box that is used in TCP/UDP
communication.
or
• If you want to establish Ethernet UDP communication from RTU based
controllers, click UDP option and type the value in TCP/UDP Port box.
ATTENTION
TCP server configuration is common.
ATTENTION
If Same as IPm Station Number is selected, then the DNP address
is same as the station number.
Step Action
9 Type the time delay before sending the response from the slave in Min
Response Delay box.
ATTENTION
• Enable Data Link Confirmations is not selected by default.
• Care must be taken to set the Data Link Timeout and
Retries as it might load the network.
11 Type the value in Data Link Retries and Retry Timeout boxes.
The DNP3 Slave Driver can be configured to send its own DNP Address
when a DNP Master requests for it. When Enable Self Address is selected,
if a message is sent with the "Self Address" (65532) in the destination
address field, RC500 responds with its unique individual address. This
feature simplifies the commissioning, troubleshooting, and maintenance of
devices with an unknown address. If this feature is not enabled, the station
ignores the messages sent to the "Self Address.”
Step Action
ATTENTION
• If Auto Detect is selected, the detected last register address
shows in the Highest Register Address box automatically and
No DNP Points is unavailable.
• If you do not want to map the RC500 I/O points to DNP3 points,
select No DNP Points.
In the Object 1-Binary Inputs tab, you can map each of the Binary inputs
configured in the station to a respective DNP Point.
Similarly, you can also map the following I/O types that are configured in the
station to a respective DNP Point.
• Binary Outputs
• Analog Inputs
• Analog Outputs
• Long Inputs
• Long Outputs
• Binary Counters
For more information about how to map all I/O types to DNP points, refer to
section Mapping I/O types to DNP points.
Step Action
ATTENTION
The Delete Selected Configuration option is used for deleting the
DNP3 configuration. Hence, the selected station does not act as a
DNP3 slave.
Step Action
1 In the Station dialog box, under Object Mapping tab, double-click the Binary
Inputs (D IN (X)) or select the I/O type and click Map I/O.
The confirmation message appears displaying DNP points are more than I/O
tags.
4 Click OK.
ATTENTION
Assigning classes to DNP points varies based on the compatibility
mode selection in General tab and I/O type selection in Object
Mapping tab.
8 If you want to assign a class to required DNP point, select the DNP point and
assign a class from the Object 2 – Binary Change Event drop-down list.
9 Click OK.
Step Action
1 In the Station dialog box, under Object Mapping tab, double-click the
Binary Outputs (D OUT (Y)) or select the I/O type and click Map I/O.
The confirmation message appears displaying DNP points are more than I/O
tags.
4 Click OK.
Step Action
1 In the Station dialog box, under Object Mapping tab, double-click the
Analog Inputs (A IN (AX)) or select the I/O type and click Map I/O.
The confirmation message appears displaying DNP points are more than I/O
tags.
4 Click OK.
ATTENTION
The events are generated only if you enter the deadband value
greater than the DNP point value.
6 Enter the deadband value and then click Assign All.
If you want to enter the deadband value to required I/O type, type the
deadband value.
Step Action
7 If the Compatibility Mode is Level 2+, then Object 31 Frozen Analog Input
and Object 33 Frozen Change Event columns are also enabled along with
Object 32 Analog Change Event.
• If a DNP point generates Frozen (Object 31 Frozen Analog Input) event,
then assign DNP points to Class 0 or None.
To assign all DNP points, click and then
click Assign All.
• If a DNP point generates Object 32 Analog Change Event or Object 33
Frozen Change Event, then assign DNP points to Class1, Class2, or Class
3.
ATTENTION
A DNP point does not generate Object 33 Frozen Change Event that
has a value of None in Object 31 Frozen Analog Input.
8 Click OK.
Step Action
1 In the Station dialog box, under Object Mapping tab, double-click the
Analog Outputs (A OUT (AY)) or select the I/O type and click Map I/O.
The confirmation message appears displaying DNP points are more than I/O
tags.
4 Click OK.
Step Action
1 In the Station dialog box, under Object Mapping tab, double-click the
Floating Point Inputs (F IN (FX)) or select the I/O type and click Map I/O.
The confirmation message appears displaying DNP points are more than I/O
tags.
4 Click OK.
ATTENTION
The events are generated only if you enter the deadband value
greater than the DNP point value.
6 Enter the deadband value and then click Assign All.
If you want to enter the deadband value to required I/O type, type the
deadband value.
7 If the Compatibility Mode is Level 2+, then Object 31 Frozen Analog Input
and Object 33 Frozen Change Event columns are also enabled along with
Object 32 Analog Change Event.
• If a DNP point generates Frozen (Object 31 Frozen Analog Input) event,
then assign DNP points to Class 0 or None.
To assign all DNP points, click and then
click Assign All.
Step Action
ATTENTION
A DNP point does not generate Object 33 Frozen Change Event that
has a value of None in Object 31 Frozen Analog Input.
8 Click OK.
Step Action
1 In the Station dialog box, under Object Mapping tab, double-click the
Floating Point Outputs (F OUT (FY)) or select the I/O type and click Map I/O.
The confirmation message appears displaying DNP points are more than I/O
tags.
4 Click OK.
Step Action
1 In the Station dialog box, under Object Mapping tab, double-click the Long
Inputs (L IN (LX)) or select the I/O type and click Map I/O.
Step Action
ATTENTION
The highest register address must be greater than LX512.
3 Click Object 30 – Long Inputs tab.
ATTENTION
The events are generated only if you enter the deadband value
greater than the DNP point value.
5 Enter the deadband value and then click Assign All.
If you want to enter the deadband value to required I/O type, type the
deadband value.
6 If the Compatibility Mode is Level 2+, then Object 31 Frozen Analog Input
and Object 33 Frozen Change Event columns are also enabled along with
Object 32 Analog Change Event.
• If a DNP point generates Frozen (Object 31 Frozen Analog Input) event,
then assign DNP points to Class 0 or None.
To assign all DNP points, click and then
click Assign All.
• If a DNP point generates Object 32 Analog Change Event or Object 33
Frozen Change Event, then assign DNP points to Class1, Class2,
or Class 3.
ATTENTION
A DNP point does not generate Object 33 Frozen Change Event that
has a value of None in Object 31 Frozen Analog Input.
7 Click OK.
Step Action
1 In the Station dialog box, under Object Mapping tab, double-click the Long
Outputs (L OUT (LY)) or select the I/O type and click Map I/O.
The confirmation message appears displaying DNP points are more than I/O
tags.
4 Click OK.
Step Action
1 In the Station dialog box, under Object Mapping tab, double-click the Binary
Counters (COUNTERS (LX)) or select the I/O type and click Map I/O.
The confirmation message appears displaying DNP points are more than I/O
tags.
4 Click OK.
Step Action
6 If the Compatibility Mode is Level 2+, then Object 23 Frozen Change Event
column is also enabled along with Object 21 Frozen Counter and Object 22
Counters Change Event.
• If a DNP point generates Object 21 Frozen Counter event, then assign
DNP points to Class 0 or None.
To assign all DNP points, click and then click
Assign All.
• If a DNP point generates Object 22 Counters Change Event or Object 23
Frozen Change Event, then assign DNP points to Class1, Class2, or Class
3.
ATTENTION
A DNP point does not generate Object 23 Frozen Change Event that
has a value of None in Object 21 Frozen Counter.
7 Click OK.
Prerequisite
The following prerequisite required to establish the communication between Experion
and RTU using DNP3.
• Apply the Experion license, which has DNP3 and DNP3 history backfill feature. The
general license contains only the basic DNP3 protocol and does not have History
Backfill feature.
Before you establish the communication between Experion and RTU using DNP3,
perform the following steps in Experion Server for enabling History Backfill feature.
Step Action
1 Apply the Experion license, which has DNP3 and DNP3 history backfill
feature. The general license contains only the basic DNP3 protocol and does
not have History Backfill feature.
2 Choose Start > Programs > Accessories > Command Prompt.
Step Action
It prompts you to enter the Word offset.
7 Type the Word offset as 26 and press ENTER.
It displays the list of parameters and prompts you to select the parameter that
has to be altered.
8 Type 1 to select Integer option and press ENTER.
The default integer value is 0.
9 Type the new value as 100 and press ENTER.
The systems history initialization percent is set to 100% and then save the
setting.
10 Type the Word offset as 470 and press ENTER.
It displays the list of parameters.
11 Type 1 and press ENTER to select the Integer option.
The default integer value is 0.
12 Type the new value 1 and press ENTER.
The value entered should not be greater than the number of days of standard
history snapshots that is configured for the system. This value entered is the
maximum number of days that can be backfilled into the system.
13 Save the setting and then type the Word offset as 494. It displays the list of
options for all parameters.
14 Type 1 and press ENTER to select the Integer option.
The default value is 0.
15 Type any value between 1 and 3 and press ENTER. This sets the priority of
the alarm due to an overflow in the controller's event buffer or an overload of
the history backfill task. A journal, low, high, or urgent priority alarm is raised
in the System Alarm Summary page on entering 0, 1, 2, or 3 values
respectively.
ATTENTION
The hstbck.exe is available in the Task Manager only after
downloading at least one DNP3 channel to Experion Server.
Perform the following steps to configure the Quick Builder component manager.
Step Action
1 Create a new project in Quick Builder.
ATTENTION
For an existing project, perform the following steps.
4. Open the project in Quick Builder.
5. Choose Tools > Component Manager.
Modify Project dialog box appears.
4 Select DNP3 Protocol from Device.
Step Action
5 Select Analog Point and Status Point from Point components.
6 Click OK.
REFERENCE - EXTERNAL
For more details about Experion Quick Builder tool, refer to Quick
Builder Guide in Knowledge Builder.
Step Action
5 Click the Port tab, and in the Port Type list, click one of the following:
• LANVendor (if an Ethernet channel is required)
• Serial
• Terminal Server
6 Specify the Redundant Port properties, if any.
REFERENCE - EXTERNAL
For more details about DNP3 Protocol channel Main properties,
DNP3 Protocol Port properties, and Redundant port properties,
refer to DNP3 Protocol Interface Reference in Experion
Knowledge Builder.
REFERENCE - EXTERNAL
For more details about DNP3 Protocol controller Main properties
and DNP3 Protocol controller protocol specific properties, refer to
DNP3 Protocol Interface Reference in Experion Knowledge
Builder.
Step Action
1 Create a new project in Quick Builder.
2 Add a DNP3 Protocol Channel and one (or more) DNP3 Protocol
Controller(s).
REFERENCE – INTERNAL
For more details about adding DNP3 Channel and DNP3
Controller, see Adding a DNP3 Protocol channel and Adding a
DNP3 Protocol controller.
3 Right-click the Point icon from the right-pane of the Quick Builder window
and select Add Item.
ATTENTION
Honeywell recommends that the Parent Asset configured here
must be the same as the Experion Asset Name.
7
In the Main tab, click next to PV Source Address.
Step Action
REFERENCE - EXTERNAL
For details about defining a DNP3 Protocol address for a point
parameter value, refer to DNP3 Protocol Interface Reference in
Experion Knowledge Builder.
Step Action
1 Create a new project in Quick Builder.
2 Add a DNP3 Protocol Channel and one (or more) DNP3 Protocol
Controller(s)
REFERENCE – INTERNAL
For more details about adding DNP3 Channel and DNP3
Controller, see Adding a DNP3 Protocol channel and Adding a
DNP3 Protocol controller.
3 Right-click the Point icon from the right-pane of the Quick Builder window
and select Add Item.
ATTENTION
Honeywell recommends that the Parent Asset configured here
must be the same as the EXPERION Asset Name.
7
In the Main tab, click next to PV Source Address.
Step Action
8 Select Controller from the Address Type list and appropriate Controller
name from the Controller list.
9 Enter the Point name in the Location box.
REFERENCE - EXTERNAL
For details about defining a DNP3 Protocol address for a point
parameter value, refer to DNP3 Protocol Interface Reference in
Experion Knowledge Builder.
Step Action
1 Create a new project in Quick Builder.
Step Action
ATTENTION
For an existing project, perform the following steps.
1. Open the project in Quick Builder.
2. Choose Tools > Component Manager.
Modify Project dialog box opens.
4 Select Modbus Protocol from Devices.
6 Click OK.
REFERENCE - EXTERNAL
For more details about Experion Quick Builder tool, refer to Quick
Builder Guide in Knowledge Builder.
REFERENCE - EXTERNAL
For more details on Modbus Protocol channel Main properties,
Modbus Protocol Port properties, and Redundant port properties,
refer to Modbus Protocol Interface Reference in Experion
Knowledge Builder.
REFERENCE - EXTERNAL
For more details about Modbus Protocol controller Main properties
and Modbus Protocol controller protocol specific properties, refer
to Modbus Protocol Interface Reference in Experion Knowledge
Builder.
Step Action
1 Create a new project in Quick Builder.
2 Add a Modbus Protocol Channel and one (or more) Modbus Protocol
Controller(s).
REFERENCE – INTERNAL
For more details about adding Modbus Channel and Modbus
Controller, see Adding a Modbus Protocol channel and Adding a
Modbus Protocol controller.
Step Action
3 Right-click the Point icon on the right-pane of the Quick Builder window and
select Add Item.
ATTENTION
Honeywell recommends that the Parent Asset configured here
must be the same as the Experion Asset Name.
7
In the Main tab, click next to PV Source Address.
REFERENCE - EXTERNAL
For details about defining a Modbus address for a point parameter
value, refer to Modbus Interface Reference in Experion
Knowledge Builder.
Step Action
1 Create a new project in Quick Builder.
2 Add a Modbus Protocol Channel and one (or more) Modbus Protocol
Controller (s).
REFERENCE – INTERNAL
For more details on adding Modbus Channel and Modbus
Controller, see Adding a Modbus Protocol channel and Adding a
Modbus Protocol controller.
3 Right-click the Point icon from the right-pane of the Quick Builder window
and select Add Item.
ATTENTION
Honeywell recommends that the Parent Asset configured here
must be the same as the Experion Asset Name.
7
In the Main tab, click next to PV Source Address.
REFERENCE - EXTERNAL
For details about defining a Modbus address for a point parameter
value, refer to Modbus Interface Reference in Experion
Knowledge Builder.
Step Action
1 Right-click the station and choose Configure.
ATTENTION
The RTU as Modbus Master over Ethernet is supported by default.
4 In the Port protocol list, click either Modbus ASCII Master or Modbus RTU
Master.
5 Click appropriate values in Baud rate, Parity, Data bits, Stop bits, and Flow
control list.
6 Select First register low in 32 bit integer types (Modbus) check box if the
RTU communicates with Modbus master or slave device that swaps the word
order when reading or writing 32-bit long integer values.
7 Select First register low in 32 bit float types (Modbus) check box if the
RTU communicates with Modbus master or slave device that swaps the word
order when reading or writing 32-bit floating point values.
8 Click OK.
9 Click I/O Transfers tab.
10 Click Wizard – Add New Transfer.
Step Action
Or
ATTENTION
Using I/O transfers, you can either read data from the remote
station or write data to the remote station.
15 Click Next.
Step Action
compensate for transmission delays or data errors. Enter a shorter
timeout if you are communicating over direct wiring and require quicker
retries if there is any communication error.
b) In the Message attempts box, enter the number of times the station
would send messages to remote station or I/O module before moving to
the next station or I/O module.
Whenever the network traffic is high, the number of message attempts is
also high. Whenever the network traffic is low, the number of message
attempts is also low.
18 Click Next.
ATTENTION
To enable secondary RTU to act as Modbus Master, perform the
following steps.
1. In the Scan Options page, click Advanced.
2. In the Scan enable flag list, click Self_Active.
20 Click Next.
The summary of the I/O transfer appears and if you click on any of the
parameter, the corresponding configuration page of the I/O transfer appears.
Step Action
1 Right-click the station and choose Configure.
ATTENTION
RTU as Modbus Slave over Ethernet is supported by default.
4 In the Port protocol list, click either Modbus ASCII Slave or Modbus RTU
Slave.
5 Click appropriate values in Baud rate, Parity, Data bits, Stop bits, and Flow
control list.
6 Select First register low in 32 bit integer types (Modbus) if the RTU
communicates with Modbus master or slave device that swaps the word
order when reading or writing 32-bit long integer values.
7 Select First register low in 32 bit float types (Modbus) if the RTU
communicates with Modbus master or slave device that swaps the word
order when reading or writing 32-bit floating point values.
8 Click OK.
9 Click Advanced tab in RC500 RTU Station Configuration dialog box.
10 Check the Modbus Starting Addresses. The addressing range for Modbus in
RC500 RTU is given below.
Step Action
REFERENCE - EXTERNAL
For more details about Modbus addressing, refer to Modbus
Interface Reference in Experion Knowledge Builder.
11 Click OK.
Datalogging is used to record I/O values and log them into data files in the RTU. These
data files are later retrieved and displayed by the Windows system.
Perform the following steps to perform Host transfer.
Step Action
1 In the Tree Views, click RC500 DataLog tab.
2 Click the station to which you want to configure datalogging.
3 Choose Configure > Datalogging > New Datalog Configuration.
ATTENTION
Use only lowercase letters and numbers for naming datalog.
5 In the Timestamp format, click the relevant time format and click Next.
Or
• If you want the datalogging to be stopped until the previous records are
retrieved and the buffer is cleared, then click Save until cleared.
8 Click Next.
Step Action
ATTENTION
You can also select multiple I/O points at one time and then click
Add. Ensure that the I/O points have tag names.
10 In the Additional variables list, click the variables that you want to be logged in
the record and click Add.
Step Action
14 Under Transfer action, click one of the following actions to be taken while
transferring the data.
Append and erase data older than ___ Hours – To add new data and remove
old data from the specified file.
Erase and store new – To remove the old data completely and add new data.
ATTENTION
• If you select Append and erase data older than ___ Hours,
ensure that you enter a value in hours in the box.
• If you select Sequential file name, ensure that you enter a
number in the Next number box.
15 Click Next.
The data is transferred and saved in the .csv file provided in the Host Transfer
configuration.
ATTENTION
Use only lowercase letters and numbers for naming the datalog.
5 In the Timestamp format, click the relevant time format and click Next.
If you want the oldest data to be overwritten by the new data, then click Cyclic
buffer.
Or
If you want the datalogging to be stopped until the previous records are retrieved
and buffer is cleared, then click Save until cleared.
8 Click Next.
Step Action
ATTENTION
You can also select multiple I/O points at one time and then click
Add. Ensure that the I/O points have tag names.
10 In the Additional variables list, click the variables that you want to be logged in
the record and click Add.
Step Action
15 Under What to Send, perform one of the following actions.
• If you want all the records since previous transfer to be transferred, then click
All records since last transfer.
• If you want the recent particular number of records to be transferred, click
Most recent ____ records and enter the number of records in the box.
• If you want all the new records logged in the past specific number of minutes,
click All records for the past _____ minutes and enter the number of
minutes in the box.
16 Under When to Send, perform the following actions based on requirement.
• To transfer data in fixed intervals, select Define fixed transfer rate and
enter the time interval in seconds.
• To transfer data based on data transfer from a particular discrete I/O, select
Start/Stop control, and click a discrete tag in the list.
• To indicate that the transfer is complete, select Set transfer complete tag
and click a discrete tag from the list.
17 Enter the following details under Communications.
a) In the Port list, select the communication port to be used for transfer.
b) If IP (Ethernet and PPP) is selected as port, then in the Protocol list select
the protocol to be used.
c) In the Retry count box, enter the number of times to retry incase of
transfer failure.
d) In the Timeout box, enter a timeout period for data transmission.
e) In the Station Identifier list, click Use Station Number if only one client
transfer is configured in the station.
f) Click Use a Specific Value, if multiple client transfers are configured in the
station, and assign a unique value for each client transfer configuration.
g) If IP (Ethernet and PPP) is selected as port, then enter the Datalog
Server’s IP address in the Destination IP box, and the port number in the
IP port box.
18 Click Finish.
ATTENTION
To create a new file, enter the file name in File name box and click
Open.
11 Click OK in Record Storage Options dialog box, and again click OK in Add
From File dialog box.
12 Click UDP/TCP Ports tab.
Step Action
13 Click Add.
Or
• Click OK
Step Action
5 In the Data file base name list, click any one of the naming method to name
the data file.
• Station Name
• Station Number
Depending upon the naming method that you select, the file name also
changes. A sample of the file name is displayed accordingly below the Data file
base name list.
6 Click UDP/TCP Ports tab and click Add.
Or
• Click OK
ATTENTION
To overwrite the datalog configuration of any existing datalog in the
destination station, select Overwrite configuration check box and
click the datalog to be overwritten in the list.
8 Click Copy Now.
c) In the Delay box, enter the number of seconds after which the alarm
should be executed.
5 Click Next.
Step Action
7 Click a channel in Channel list.
This field indicates which I/O point to monitor. I/O is listed in the list for virtual or
physical points defined in the station’s configuration.
7 In the Delay box, enter the number of seconds after which the alarm should be
executed.
Step Action
8 Click Next.
Alarm limit: For ‘Analog high limit’ types, this is the value that the monitored
point must be equal or more before an alarm is initiated. For ‘Analog low limit’
types, the monitored I/O must be equal to or lesser than this value before an
alarm is initiated.
Deadband: Deadband value indicates the value that the monitored I/O point
can fluctuate before it is considered to be in the ‘cleared’ state. For ‘Analog high
limit’ types, the monitored point can decrease by this value below the ‘Limit’
before the alarm state changes. For ‘Analog low limit’ types, the monitored point
can increase by this value above the ‘Limit’ before the alarm state changes.
10 Click Next.
ATTENTION
Periodic alarms cannot use sxio as channel type.
10 In the Destination list, enter a trigger name.
11 Click Finish.
Add a recipient
Perform the following steps to add a recipient.
Step Action
1 Right-click the station and choose Configure.
Step Action
1 Connect the power cables to the RTU.
ATTENTION
Check the power rating of the RTU before connecting the power
supply to it. As the RTU supports power supply redundancy,
ensure that the +ve terminal, the -ve terminal, and the ground
terminal of both the power supplies are wired to the RTU.
2 Supply power to the RTU and check the P1 and P2 status LEDs in the RTU.
If the LEDs are ON, then the power supplies to the RTU are functioning
normally.
3 Check the Status LED in the RTU. If it glows steadily, then the RTU is
functioning properly.
ATTENTION
If the LEDs are blinking or not glowing continuously, then refer to
section Maintenance and troubleshooting.
Establish communication between Honeywell RC500 I/O Tool Kit and RTU
Once the RTU is started, you need to establish communication between the computer on
which the Honeywell RC500 I/O Tool Kit runs and the RTU.
Perform the following steps to establish communication between the Honeywell RC500
I/O Tool Kit and the RTU.
Step Action
1 Choose Device > Select.
Step Action
1 Choose Operations > Load > Load Now (Basic Parameters Only).
Each time the station configuration is loaded, the real-time clock in the
stations is set to the computer's clock time or to GMT time.
For more information about how to Set the station’s real-time clock, refer to
Step Action
1 Click the station to which the configuration needs to be loaded.
2 Choose Operations > Load > Load Now (Basic Parameters Only).
Step Action
3 The following parameters are loaded.
• Load module EEROMs
• Load IP security
• Set clock
ATTENTION
• The progress bar closes once the files are loaded to the RTU.
The status of the files loaded is displayed in the Report
Views.
• To enable Report Views, choose View > Report Views.
ATTENTION
The progress bar closes once the files are loaded. The status of
the files loaded is displayed in the Report Views.
Step Action
1 Click the station to which the configuration needs to be loaded.
2 Choose Operations > Load > Load Advanced (Select Files).
Step Action
ATTENTION
ATTENTION
The progress bar closes once the files are loaded. The status of
the files loaded is displayed in the Report Views.
The Loading station configuration dialog box appears and the files are
loaded.
ATTENTION
The progress bar closes once the files are loaded. The status of
the files loaded is displayed in the Report Views.
Step Action
1 Right-click the station and choose Configure.
Step Action
1 Remove the primary RTU from the network.
The Verifying station configuration dialog box appears and the station
configuration is verified.
ATTENTION
• The progress bar closes once the files are verified. The status
of the files verified is displayed in the Report Views.
• To enable Report Views, choose View > Report Views.
ATTENTION
• The status of the files read is displayed in the Report Views.
• To enable Report Views, choose View > Report Views.
Step Action
1 Right-click the I/O module and choose Test I/O.
The I/O value column displays the analog input values of each I/O.
3 To monitor the analog output values, click A OUT tab.
The I/O value column displays the analog output values of each I/O.
4 To monitor the discrete input values, click D IN tab.
The I/O value column displays the discrete input values of each I/O.
5 To monitor the discrete output values, click D OUT tab.
The I/O value column displays the discrete output values of each I/O.
Step Action
1 Right-click the I/O module and choose Test I/O.
ATTENTION
Ensure that while adding an I/O module to the RTU, Assign watchdog
output to first channel is selected in Discrete/Analog output options.
Perform the following steps to monitor the communication between RTU and the I/O
module.
Step Action
1 Choose Configure > Configure Station/Module.
Monitor redundancy
The secondry RTU status is observed by the Test I/O window. The Self_Heartbeat
provides the status of the primary RTU and the Other_heartbeat provides the status of the
secondary RTU.
Perform the following steps to monitor the redundant RTU status.
Step Action
1 In the Tree Views, select the station.
2 Choose Operations > Test I/O.
Step Action
5 Check the status of the Self_Active.
If the status is ‘Idle’, then the primary RTU is not functioning as primary RTU.
6 Check the status of the Other_Active.
If the status is ‘Running’, then the secondary RTU is healthy and connected.
If the status is ‘Idle’, then the secondary RTU is not healthy or disconnected
from primary RTU and hence need to check the secondary RTU and bring it to
running status.
DI register Status
address
DI register Status
address
DI register Status
address
Perform the following steps to monitor the ring switch status using the RTU.
Step Action
1 Choose Configure > Configure Station/Module.
ATTENTION
The MAC address field is located at the right-hand side of the
ring switch.
Step Action
6 In the Select or enter the switch to be monitored list, enter the MAC
address of the ring switch and click OK.
The ring switch is added to the Ring Switches to monitor list and a virtual
Discrete Input module is automatically added.
ATTENTION
When you add a ring switch, a virtual discrete input I/O module is
automatically added. The I/O module name is same as the MAC
address entered. You can change the module name by entering a
different name in the Module name box.
7 In the Advanced Ethernet/IP Security dialog box, click OK.
8 In the Ethernet Port Configuration dialog box, click OK.
9 Click I/O Modules tab.
If the RTU is ON, the message would be ‘On_line’ and if the RTU is OFF, the
message would be ‘Off_line’.
Step Action
1 Click the station that needs to be reset.
2 Choose Operations > Advanced Operations > Perform Hard Reset.
Step Action
1 Select the RTU and then Choose Operations > Set the Clock.
ATTENTION
You can also set the real-time clock to Computer's GMT time
automatically in the Load Options dialog box before you load
configurations into RTU.
3 If you select Use User Set Time, the New time to set in station is enabled,
then set your own date and time.
4 Click Apply.
The date and time are synched with the RTU and the updated date and time
appears under the Current station date/time.
5 Click Close.
Considerations
• To load the firmware, establish the Ethernet connection from the computer to the
station’s primary Ethernet port (use "Ethernet 1" only, on RC500 RTU models).
• To upgrade the firmware, establish the connection from serial port to primary RS232
Port B.
• The Ethernet port of the computer should be assigned a fixed IP address that is on
the same subnet as the IP address you assigned to RTU.
Perform the following steps to upgrade firmware.
Step Action
1 Select RTU and then click Operations > Advanced Operations>Upgrade
Firmware.
ATTENTION
• You cannot stop loading the firmware once it starts.
• You cannot load firmware for ring switches.
Step Action
ATTENTION
The Station name list shows all RTU stations configured in that
project. Ensure that the required RTU is selected.
4 Under Firmware Selection,
c) Click to browse the firmware file.
The Browse for Folder dialog box appears and select the latest
firmware file. The firmware version is selected automatically in the Select
firmware version list.
d) Click Options.
The Search Options dialog box appears. Analyze and select all the
archive types (.zip, .tar, .tgz, and .gz) provided for firmware files and then
click OK.
ATTENION
By default, firmware is available in C:\Program Files\Honeywell
Tools\Programs\Firmware.
5 Click Next.
ATTENTION
Select the type of connection as Use Ethernet only (no serial
port connection) if station supports Ethernet-only loading.
7 Click Next.
The IP Settings dialog box appears. The IP address of computer and RTU
are selected by default from the project files. Enter the IP address and/or
subnet mask of your station if the value is different from the default values
saved in the project file.
Step Action
ATTENTION
If the IP address of computer and station are on a compatible
subnet and the Ethernet communication to the station is proper,
then you need not enter Gateway IP address. However, if you
need to route messages through an IP gateway, enter the
Gateway IP address.
8 Click Next.
The Cycle Power message box appears. Turn on the power of RTU.
The firmware starts loading and the confirmation message appears after the
completion of firmware load.
11 Click OK in the confirmation message box.
ATTENTION
The Reset System Com Port option is not available for configured Ethernet
I/O-2.
Step Action
1 Select the station and then click Operations>Advanced Operations>Reset
System Com Port.
5 Click OK.
ATTENTION
The Format Battery Backed RAM option is not available for configured
Ethernet I/O-2.
To use this option, connect a serial port of your computer to port B of your RTU station.
The NVRAM reformatting takes approximately 30 seconds to complete. After
completion of the reformatting, you must reload the following:
• Datalog configuration, if any
• The Honeywell RC500 I/O Tool Kit configuration
• User files (if any) that were loaded into the /nvram folder of the station
Perform the following steps to format the battery backed RAM.
Step Action
1 Select the RTU and then click Operations > Advanced Operations >
Format Battery Backed RAM.
The data deleted from the selected port. There are two LEDs are available in
Format Battery Backed RAM dialog box.
- Transmit LED
- Receive LED
If both the LEDs are blinking, it indicates that RTU and computer are
communicating with each other.
LED Description
PWR P1/P2 Indicates whether the power supply is connected to the particular
screw terminal.
Resolution
a) Apply power to the RTU.
b) Load firmware through serial and Ethernet ports. To
load the firmware, go to Operations > Advanced
Operations > Upgrade Firmware
Resolution
a) Perform a project load from Honeywell RC500 I/O
Tool Kit.
b) Clear the station memory. Go to Operations >
Advanced Operations > Clear Configuration.
Resolution
a) Verify power connections are adequate and 10 -30
Vdc is present on the power terminals.
b) Contact Honeywell TAC.
Resolution
a) Verify the IP address or serial communication
parameters in the Honeywell RC500 I/O Tool Kit are
compatible with IP address/communication
parameters in engineering workstation through
Device > Select menu.
b) Load the configuration using the single station mode
in the Device > Select menu window and connect
directly to the RC500 RTU’s Ethernet port.
c) Load the IP address through the RS232 port B in the
RTU.
Resolution/Workaround
a) Choose Operations > Load > Load Options.
b) Select Archive the station with every load check
box and click OK.
− Ensure that the RTU is loaded at least once after
selecting this option.
• Ensure communication between the RTU and
Engineering Station.
Resolution/Workaround
• Memory can be analyzed through Telnet using ‘free’
command. The analysis provides information about
total memory, memory used, and memory free.
• Reduce the load on RTU by reducing Virtual I/O that
are not used and are reserved.
Resolution/Workaround
• Switch off the RTU and then start the firmware
upgrade. Repeat the operation, if the firmware
upgrade fails
• The Honeywell RC500 I/O Tool Kit communicates with
the station, when the Upgrade Firmware command is
selected. Even if this initial communication fails,
proceed with the "Upgrade Firmware and OS" and
follow the instructions.
• Check the communication path to the station and