Shield Sprinkler Catalog
Shield Sprinkler Catalog
DESCRIPTION
The SHIELD Sprinklers, SD1010, SD1015, SD1030, SD1032
(Glass Bulb Type), Standard Ori ce, Upright, Pendent and
Recessed Pendent type, design incorporates state-of-the-art,
heat responsive, frangible glass bulb design (standard or quick
response) for prompt, precise operation.
RATINGS
Sprinkler Temperature Norminal Sprinkler N.F.P.A Maximum Ambient
Glass Bulb Color
Classi cation Temperature Rating (Ceiling) Temp.(Allowed)
Ordinary** 155ºF/57ºC 100ºF/38ºC Orange
Ordinary 155ºF/68ºC 100ºF/38ºC Red
Intermediate 175ºF/79ºC 150ºF/65ºC Yellow
Intermediate 200ºF/93ºC 150ºF/65ºC Green
High* 286ºF/141ºC 225ºF/107ºC Blue
Extra High* 360ºF/182ºC 300ºF/149ºC Mauve
Open* Open - No Bulb
* Non-Approved
**UL Listed only.
6 [Link]
PART LIST
DISCHARGE CURVE
[Link] 7
WARNINGS INSTALLATION SEQUENCE
The SHIELD sprinklers must be installed and maintained Step 1 - The unit must be installed in the upright position for
in compliance with this document. Depressurize and drain the Upright Sprinklers, and in the Pendent position for the
the piping system before attempting to install, remove, Pendent Sprinkler, Pendent Recessed Sprinkler.
or adjust any Sprinklers. Failure to do so may impair the
performance of these sprinklers. The owner is responsible Step 2 - Use only a non-hardening pipe joint compound or
for maintaining the re protection system and devices in tape seal. Apply only to the male threads.
operation.
Step 3 - Hand tighten the sprinkler into tting.
WRENCH DESCRIPTION
Step 4 - For Upright and Pendent Sprinklers, use a
The Sprinkler Wrench is a tool speci cally designed for standard wrench. Tighten the unit into the tting. A lead-tight
installing SHIELD Sprinklers. These special wrenches must joint requires only 7 to [Link] (9.5 to 19.0Nm) of torque. A
be used to provide the proper leverage when tightening tangential force of 14 to 28 [Link] (62.3 to 124.5N) delivered
the sprinkler and to minimize slippage during installation. through a 6”(150mm) handle will deliver adequate torque.
Any other wrench may damage the sprinkler. Once torque level reach over [Link] (28.6Nm) it may
distort the ori ce seal, resulting in leakage. For exposed
piping systems, the sprinkler should be oriented so the
frame arms are parallel with the branch line pipe.
CAUTION
Do not over-tighten or under-tighten the sprinkler to
Sprinkler Wrench compensate for inaccurate escutcheon plate adjustment.
ADDITIONAL
Recessed Sprinkler - To install the escutcheon plate,
align with it and push or thread over the sprinkler body
into the upper support piece, until the outer edge of the
escutcheon meets the mounting surface.
8 [Link]
DISTRIBUTION PATTERNS
[Link] 9
DIMENSIONS
10 [Link]
SPRINKLER HEAD
Horizontal Sidewall Sprinkler
DESCRIPTION
The SD1133, SD1121, ½” ori ce, standard horizontal sidewall
sprinkler is designed for standard or recessed installation. The
design provides a crescent-shaped water discharge pattern for
installation along a wall or under a beam or ceiling. The design
incorporates state-of-the-art, heat responsive, frangible glass
bulb design (standard or quick response) for prompt, precise
operation. The die cast frame is more streamlined and attractive
than traditional sand cast frames.
SPRINKLER OPERATION
The operating mechanism is a frangible glass bulb which contains TECHNICAL SPECIFICATION
a heat responsive liquid. During a re, the ambient temperature
rises causing the liquid in the bulb to expand. Sprinkler Identi cation Standard SD1133 (bulb
Number 5mm), Quick Response
When the ambient temperature reaches the rated temperature of SD1121 (bulb 3mm)
the sprinkler, the bulb shatters. As a result, the waterway is cleared Style Horizontal Sidewall
of all sealing parts and water is discharged towards the de ector.
The de ector is designed to distribute the water in a pattern that is K Factor 5.6gpm/psi½. (80lpm/bar½)
most effective in controlling the re. Response Time Index Standard 50
(RTI) Quick Response 30
MAXIMUM COVERAGE Nominal Thread Size ½”NPT(15mm)
Or ce Size 13mm
Standard spray coverage is up to: Light Hazard = 196 square
feet(18,2 sq.m); Ordinary Hazard = 100 square feet(9,3 sq.m)per Max. Working Pressure 175PSI(1200kPa)
NFPA 13.
Factory Hydrostatic Test 100%@500PSI(3450 kPa)
Min. Operation Pressure 7 PSI(48 kPa)
RATINGS
Sprinkler Temperature Norminal Sprinkler N.F.P.A Maximum Ambient
Glass Bulb Color
Classi cation Temperature Rating (Ceiling) Temp.(Allowed)
Ordinary 155ºF/57ºC 100ºF/38ºC Orange
Ordinary 155ºF/68ºC 100ºF/38ºC Red
Intermediate** 175ºF/79ºC 150ºF/65ºC Yellow
Intermediate** 200ºF/93ºC 150ºF/65ºC Green
High* 286ºF/141ºC 225ºF/107ºC Blue
Extra High* 360ºF/182ºC 300ºF/149ºC Mauve
Open* Open - No Bulb
* Non-Approved ** FM Approved only
[Link] 11
PART LIST
SD1133 SD1121
DISCHARGE CURVE
12 [Link]
WARNINGS INSTALLATION SEQUENCE
The SHIELD sprinklers must be installed and maintained Step 1. The unit must be installed in the horizontal sidewall
in compliance with this document. Depressurize and drain position for the Horizontal Sidewall Sprinklers.
the piping system before attempting to install, remove,
or adjust any Sprinklers. Failure to do so may impair the Step 2. Use only a non-hardening pipe joint compound or
performance of these sprinklers. The owner is responsible tape seal. Apply only to the male threads.
for maintaining the re protection system and devices in
operation. Step 3. Hand tighten the sprinkler into tting.
CAUTION
Do not over-tighten or under-tighten the sprinkler to
compensate for inaccurate escutcheon plate adjustment.
Sprinkler Wrench
Protection clips are used to protect its bulb. Please have
clip on at all times during transportation.
INSTALLATION MAINTENANCE
All SHIELD Sprinklers must be installed according to Sprinklers must never be altered after manufacture. Any
NFPA 13 Standards. Deviations from these requirements alteration such as painting and coating will directly harm
and standards or any alteration to the sprinkler itself will the sprinkler and cause malfunctions. Sprinkler in contact
void any warranty made by manufacturer. In addition, with corrosive products should be replaced if they cannot
installation must also meet local government provisions, be cleaned completely.
codes and standards as applicable.
Visual inspections are recommended after installation.
The system piping must be properly sized to insure the After installation, a close-up inspection annually will
minimum required ow rate at the sprinkler. Check for the suf ce.
proper model, style, ori ce size and temperature rating
prior to installation. Install sprinklers after the piping is in Inspection and maintenance of re protection system is
place to avoid mechanical damage, replace any damaged the responsibility of the owner. It is recommended that
units. Wet pipe systems must be protected from freezing. automatic sprinkler system be inspected and tested
according to local and/or national regulations.
Upon completion of the installation, the system must be
tested per recognized standards. In the event of a thread
task, remove the unit, apply new pipe joint compound or
tape, and reinstall.
ADDITIONAL
Recessed Sprinkler - To install the escutcheon plate,
align with it and push or thread over the sprinkler body
into the upper support piece, until the outer edge of the
escutcheon meets the mounting surface.
[Link] 13
DISTRIBUTION PATTERNS
14 [Link]
DIMENSIONS
[Link] 15
SPRINKLER HEAD
Vertical Sidewall Sprinkler
DESCRIPTION
The SD2133, SD2121, ½” ori ce, standard vertical sidewall
sprinkler is designed for standard installation. The design
provides a crescent-shaped water discharge pattern for
installation along a wall or under a beam or ceiling. The design
incorporates state-of-the-art, heat responsive, frangible glass
bulb design (standard or quick response) for prompt, precise
operation. The die cast frame is more streamlined and attractive
than traditional sand cast frames.
MAXIMUM COVERAGE
It is cast with a hex-shaped wrench boss to allow easy tightening
from many angles, reducing assembly effort. This sprinkler is Standard spray coverage is up to:Light Hazard = 196
available in various temperature ratings and nishes to meet square feet(18,2 sq.m); Ordinary Hazard = 100 square
many design requirements. The recessed pendent should be feet(9,3 sq.m)per NFPA 13.
utilized with a recessed escutcheon which provides up ” of
adjustments. All sprinklers are manufactured using the time
proven Belleville seal used exclusively by all major manufactures TECHNICAL SPECIFICATION
to ensure long life and safe operation.
Sprinkler Identi cation Standard SD2133 (bulb
Number 5mm), Quick Response
SPRINKLER OPERATION SD2121 (bulb 3mm)
The operating mechanism is a frangible glass bulb which contains Style Vertical Sidewall
a heat responsive liquid. During a re, the ambient temperature K Factor 5.6gpm/psi½. (80lpm/bar½)
rises causing the liquid in the bulb to expand.
Response Time Index Standard 50
When the ambient temperature reaches the rated temperature (RTI) Quick Response 30
of the sprinkler, the bulb shatters. As a result, the waterway is Nominal Thread Size ½”NPT(15mm)
cleared of all sealing parts and water is discharged towards the
de ector. The de ector is designed to distribute the water in a Or ce Size 13mm
pattern that is most effective in controlling the re. Max. Working Pressure 175PSI(1200kPa)
Factory Hydrostatic Test 100%@500PSI(3450 kPa)
Min. Operation Pressure 7 PSI(48 kPa)
RATINGS
Sprinkler Temperature Norminal Sprinkler N.F.P.A Maximum Ambient
Glass Bulb Color
Classi cation Temperature Rating (Ceiling) Temp.(Allowed)
Ordinary 135ºF/57ºC 100ºF/38ºC Orange
Ordinary 155ºF/68ºC 100ºF/38ºC Red
Intermediate 175ºF/79ºC 150ºF/65ºC Yellow
Intermediate 200ºF/93ºC 150ºF/65ºC Green
16 [Link]
PART LIST
SD2133 SD2121
DISCHARGE CURVE
[Link] 17
WARNINGS INSTALLATION SEQUENCE
The SHIELD must be installed and maintained in Step 1. The unit must be installed in the horizontal sidewall
compliance with this document. Depressurize and drain the position for the Horizontal Sidewall Sprinklers.
piping system before attempting to install, remove, or adjust
any Sprinklers. Failure to do so may impair the performance Step 2. Use only a non-hardening pipe joint compound or
of these sprinklers. The owner is responsible for maintaining tape seal. Apply only to the male threads.
the re protection system and devices in operation.
Step 3. Hand tighten the sprinkler into tting.
WRENCH DESCRIPTION
Step 4. For Horizontal Sidewall Sprinklers, use a
The Sprinkler Wrench is a tool speci cally designed for standard wrench. Tighten the unit into the tting. A
installing SHIELD Sprinklers. These special wrenches must lead-tight joint requires only 7 to 14ft.-lbs (9.5 to19.0Nm) of
be used to provide the proper leverage when tightening the torque. A tangential force of 14 to28ft.-lbs(62.3 to 124.5N)
sprinkler and to minimize slippage during installation. Any delivered through a6”(150mm) handle will deliver adequate
other wrench may damage the sprinkler. torque. Once torque level reach over 21ft.-lbs(28.6Nm)
it may distort the ori ce seal, resulting in leakage. For
exposed piping systems, the sprinkler should be oriented
so the frame arms are parallel with the branch line pipe.
CAUTION
Do not over-tighten or under-tighten the sprinkler to
compensate for inaccurate escutcheon plate adjustment.
Sprinkler Wrench
Protection clips are used to protect its bulb. Please have
clip on at all times during transportation.
INSTALLATION
All SHIELD Sprinklers must be installed according to MAINTENANCE
NFPA 13 Standards. Deviations from these requirements
and standards or any alteration to the sprinkler itself will Sprinklers must never be altered after manufacture. Any
void any warranty made by manufacturer. In addition, alteration such as painting and coating will directly harm
installation must also meet local government provisions, the sprinkler and cause malfunctions. Sprinkler in contact
codes and standards as applicable. with corrosive products should be replaced if they cannot
be cleaned completely.
The system piping must be properly sized to insure the
minimum required ow rate at the sprinkler. Check for the Visual inspections are recommended after installation.
proper model, style, ori ce size and temperature rating After installation, a close-up inspection annually will
prior to installation. Install sprinklers after the piping is in suf ce.
place to avoid mechanical damage, replace any damaged
units. Wet pipe systems must be protected from freezing. Inspection and maintenance of re protection system is
the responsibility of the owner. It is recommended that
Upon completion of the installation, the system must be automatic sprinkler system be inspected and tested
tested per recognized standards. In the event of a thread according to local and/or national regulations.
task, remove the unit, apply new pipe joint compound or
tape, and reinstall.
ADDITIONAL
Recessed Sprinkler - To install the escutcheon plate, align
with it and push or thread over the sprinkler body into the
upper support piece, until the outer edge of the escutcheon
meets the mounting surface.
18 [Link]
DISTRIBUTION PATTERNS
[Link] 19
DIMENSIONS
20 [Link]
SPRINKLER HEAD
Concealed Sprinkler
DESCRIPTION
The SHIELD Sprinklers, SD1050, SD1055 (Glass Bulb Type)
Standard and Quick Response Concealed Sprinkler, design
incorporates state-of-the-art, heat responsive, frangible glass
bulb design for prompt, precise operation. The die cast frame is
more streamlined and attractive than traditional sand cast frames.
RATINGS
Sprinkler Temperature Norminal Sprinkler N.F.P.A Maximum Ambient
Glass Bulb Color
Classi cation Temperature Rating (Ceiling) Temp.(Allowed)
Ordinary 155ºF/68ºC 100ºF/38ºC Red
Intermediate 175ºF/79ºC 150ºF/65ºC Yellow
Intermediate 200ºF/93ºC 150ºF/65ºC Green
[Link] 21
PART LIST
SD1050 SD1055
DISCHARGE CURVE
22 [Link]
WARNINGS INSTALLATION SEQUENCE
The SHIELD Sprinklers must be installed and maintained Step 1. The unit must be installed in the Pendent position
in compliance with this document. Depressurize and drain for the Concealed Sprinkler.
the piping system before attempting to install, remove,
or adjust any Sprinklers. Failure to do so may impair the Step 2. Use only a non-hardening pipe joint compound or
performance of these sprinklers. The owner is responsible tape seal. Apply only to the male
for maintaining the re protection system and devices in threads.
operation.
Step 3. Hand tighten the sprinkler into tting.
WRENCH DESCRIPTION
Step 4. For Concealed Sprinklers, use a standard wrench.
The Sprinkler Wrench is a tool speci cally designed for Tighten the unit into the tting. A lead-tight joint requires
installing SHIELD Sprinklers. These special wrenches must only 7 to 14ft.-lbs(9.5 to 19.0Nm) of torque. A tangential
be used to provide the proper leverage when tightening the force of 14 to 28ft.-lbs(62.3 to124.5N) delivered through
sprinkler and to minimize slippage during installation. Any a 6”(150mm) handle will deliver adequate torque. Once
other wrench may damage the sprinkler. torque level reach over 21ft.-lbs(28.6Nm) it may distort
the ori ce seal, resulting in leakage. For exposed piping
systems, the sprinkler should be oriented so the frame
arms are parallel with the branch line pipe.
Concealed
Sprinkler Wrench CAUTION
Do not over-tighten or under-tighten the sprinkler to
compensate for inaccurate escutcheon plate adjustment.
Protection caps are used to protect its bulb and de ector.
Please have cap on at all times during transportation and
INSTALLATION interior decorating.
ADDITIONAL
Cover Plate - To install the conceal cover plate, align it
with the sprinkler and slowly turn clockwise for the cover
plates and sprinkler to lock in. Make sure the cover plate is
securely locked in, fail to do so may cause the sprinkler to
malfunction.
[Link] 23
DISTRIBUTION PATTERNS
DIMENSIONS
24 [Link]
SPRINKLER HEAD
Quick Response Upright & Pendent Sprinklers
DESCRIPTION
The SHIELD Sprinkler, SD1020, SD1021 (Glass Bulb Type) 3/8”
Standard Ori ce, Upright, Pendent and Recessed Pendent, Quick
Response, design incorporates state-of-the-art, heat responsive,
frangible glass bulb design for prompt, precise operation. The die
cast frame is more streamlined and attractive than traditional sand
cast frames.
RATINGS
Sprinkler Temperature Norminal Sprinkler N.F.P.A Maximum Ambient
Glass Bulb Color
Classi cation Temperature Rating (Ceiling) Temp.(Allowed)
Ordinary 135ºF/57ºC 100ºF/38ºC Orange
Ordinary 155ºF/68ºC 100ºF/38ºC Red
Intermediate 175ºF/79ºC 150ºF/65ºC Yellow
Intermediate 200ºF/93ºC 150ºF/65ºC Green
[Link] 25
PART LIST
SD1020 SD1021
DISCHARGE CURVE
26 [Link]
DISTRIBUTION PATTERNS
[Link] 27
DIMENSIONS
28 [Link]
SPRINKLER HEAD
Conventional Sprinkler
DESCRIPTION
The SHIELD Sprinkler, SD1025, SD1026 (Glass Bulb Type)
½” Ori ce, Conventional sprinkler is designed for standard or
recessed installation. The design incorporates state-of-the-art,
heat responsive, frangible glass bulb design (standard or quick
response) for prompt, precise operation. The die cast frame is
more streamlined and attractive than traditional sand cast frames.
RATINGS
Sprinkler Temperature Norminal Sprinkler N.F.P.A Maximum Ambient
Glass Bulb Color
Classi cation Temperature Rating (Ceiling) Temp.(Allowed)
Ordinary 135ºF/57ºC 100ºF/38ºC Orange
Ordinary 155ºF/68ºC 100ºF/38ºC Red
Intermediate 175ºF/79ºC 150ºF/65ºC Yellow
Intermediate 200ºF/93ºC 150ºF/65ºC Green
High* 286ºF/141ºC 225ºF/107ºC Blue
Extra High* 360ºF/182ºC 300ºF/149ºC Mauve
Open* Open - No Bulb
* Non-Approved
[Link] 29
PART LIST
SD1025 SD1026
DISCHARGE CURVE
30 [Link]
WARNINGS INSTALLATION SEQUENCE
The SHIELD Sprinklers must be installed and maintained Step 1. The unit must be installed in the upright position for
in compliance with this document. Depressurize and drain the Upright Sprinklers, and in the Pendent position for the
the piping system before attempting to install, remove, Pendent Sprinkler, Pendent Recessed Sprinkler.
or adjust any Sprinklers. Failure to do so may impair the
performance of these sprinklers. The owner is responsible Step 2. Use only a non-hardening pipe joint compouind or
for maintaining the re protection system and devices in tape seal. Apply only to the male threads.
operation.
Step 3. Hand tighten the sprinkler into tting.
WRENCH DESCRIPTION
Step 4. For Conventional Sprinklers, use a standard
The Sprinkler Wrench is a tool speci cally designed for wrench. Tighten the unit into the tting. A lead-tight joint
installing SHIELD Sprinklers. These special wrenches must requires only 7 to 14ft.-lbs (9.5 to 19.0Nm) of torque. A
be used to provide the proper leverage when tightening the tangential force of 14 to28ft.-lbs (62.3 to 124.5N) delivered
sprinkler and to minimize slippage during installation. Any through a 6”(150mm) handle will deliver adequate torque.
other wrench may damage the sprinkler. Once torque level reach over 21ft.-lbs (28.6Nm) it may
distort the ori ce seal, resulting in leakage. For exposed
piping systems, the sprinkler should be oriented so the
frame arms are parallel with the branch line pipe.
CAUTION
Do not over-tighten or under-tighten the sprinkler to
compensate for inaccurate escutcheon plate adjustment.
Sprinkler Wrench
Protection clips are used to protect its bulb. Please have
clip on at all times during transportation.
INSTALLATION MAINTENANCE
All SHIELD Sprinklers must be installed according to Sprinklers must never be altered after manufacture. Any
NFPA 13 Standards. Deviations from these requirements alteration such as painting and coating will directly harm
and standards or any alteration to the sprinkler itself will the sprinkler and cause malfunctions. Sprinkler in contact
void any warranty made by manufacturer. In addition, with corrosive products should be replaced if they cannot
installation must also meet local government provisions, be cleaned completely.
codes and standards as applicable.
Visual inspections are recommended after installation.
The system piping must be properly sized to insure the After installation, a close-up inspection annually will
minimum required ow rate at the sprinkler. Check for the suf ce.
proper model, style, ori ce size and temperature rating
prior to installation. Install sprinklers after the piping is in Inspection and maintenance of re protection system is
place to avoid mechanical damage, replace any damaged the responsibility of the owner. It is recommended that
units. Wet pipe systems must be protected from freezing. automatic sprinkler system be inspected and tested
according to local and/or national regulations.
Upon completion of the installation, the system must be
tested per recognized standards. In the event of a thread
task, remove the unit, apply new pipe joint compound or
tape, and reinstall.
ADDITIONAL
Recessed Sprinkler - To install the escutcheon plate,
align with it and push or thread over the sprinkler body
into the upper support piece, until the outer edge of the
escutcheon meets the mounting surface.
[Link] 31
DISTRIBUTION PATTERNS
32 [Link]
DIMENSIONS
[Link] 33
ESCUTECHEONS PLATE
Escutecheon Plate - Single pieces
Bright Chrome Finish
Painted available upon request
Suitable for 1/2” and 3/4” Sprinkler Head
SPRINKLER GUARD
Steel Nickel / Chrome plated
Suitable for 1/2” and 3/4” Sprinkler Head
SPRINKLER CABINETS
Steel, painted Red
Suitable for 1/2” Sprinkler Head
Available for 6, 12, 24 Sprinkler Head
34 [Link]