The document explains the calculation of condenser flow rate, which is determined to be 3.0 GPM per ton based on a cooling load of 1 ton. It assumes a heat conversion efficiency of 90% and uses specific formulas to derive the flow rate. The final calculation results in a flow rate of approximately 3.01 GPM per ton, confirming the 3.0 GPM standard.

Uploaded by

pdeleon.work
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
8 views1 page

Why Condenser Flow Rate Is 3

The document explains the calculation of condenser flow rate, which is determined to be 3.0 GPM per ton based on a cooling load of 1 ton. It assumes a heat conversion efficiency of 90% and uses specific formulas to derive the flow rate. The final calculation results in a flow rate of approximately 3.01 GPM per ton, confirming the 3.0 GPM standard.

Uploaded by

pdeleon.work
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

WHY CONDENSER FLOW RATE IS 3.

0 GPM PER TON

Assume

Cooling Load = 1 Ton

Assume 1.0 kw /Ton for older WC chillers

Assume 90% conversion to heat of compression

HR = 1 Ton + 90%*(1 kW x 1 Ton/3.517) = 1.2559 Tons

1.2559 Tons = GPM x (10 deg F)/24

Solving for GPM

GPM = 1.2843 * (24/10) = 3.01 gpm/ton