Chiller & Condenser Approach

The document explains the Chiller Approach and Condenser Approach in HVAC systems, highlighting their importance in measuring heat transfer efficiency and performance. The Chiller Approach is defined as the temperature difference between the Leaving Chilled Water Temperature and the Evaporator Refrigerant Saturation Temperature, with normal values varying for air and water-cooled chillers. The Condenser Approach indicates the condenser's heat rejection efficiency, with normal values typically between 0.5°C and 1.5°C, and both approaches serve as indicators for maintenance and operational issues.

Uploaded by

arenaswapnil
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
98 views2 pages

Chiller & Condenser Approach

The document explains the Chiller Approach and Condenser Approach in HVAC systems, highlighting their importance in measuring heat transfer efficiency and performance. The Chiller Approach is defined as the temperature difference between the Leaving Chilled Water Temperature and the Evaporator Refrigerant Saturation Temperature, with normal values varying for air and water-cooled chillers. The Condenser Approach indicates the condenser's heat rejection efficiency, with normal values typically between 0.5°C and 1.5°C, and both approaches serve as indicators for maintenance and operational issues.

Uploaded by

arenaswapnil
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 2

1.

Chiller Approach And Condenser Approach in HVAC System


Chiller Approach is a very important parameter in an HVAC system.
It is used to measure the performance of the chiller and its heat transfer efficiency.
What is Chiller Approach?
Chiller Approach means –
The temperature difference between Leaving Chilled Water Temperature (LCWT) and Evaporator
Refrigerant Saturation Temperature.
In simple words:
The cold water coming out of the chiller (Leaving Chilled Water Temperature)
And the refrigerant saturation temperature inside the evaporator
The difference between these two is called Chiller Approach.
Formula
\text{Chiller Approach} = T_{LCWT} - T_{Refrigerant \, Saturation}
Where:
TLCWT = Leaving Chilled Water Temperature
Refrigerant Saturation Temp = Saturation temperature of refrigerant inside the evaporator
Normal Value
Air Cooled Chiller: 5°F to 10°F (≈ 2.7°C to 5.5°C)
Water Cooled Chiller: 3°F to 7°F (≈ 1.7°C to 3.9°C)
Importance
1. Efficiency Check – If the approach is high, it means heat transfer is not happening properly.
2. Fouling Indication – High approach indicates evaporator tubes may be dirty or scaled.
3. Maintenance Indicator – Shows whether the chiller needs cleaning or servicing.
4. Performance Monitoring – Regular checking of approach gives an idea of chiller health.
Causes of High Approach
Scaling / Fouling / Oil film in the evaporator.
Low refrigerant charge (gas shortage).
Poor water quality.
Refrigerant flow restriction.
Heat exchanger design problem or defect.
Example
Leaving Chilled Water Temp (LCWT) = 7°C
Evaporator Refrigerant Saturation Temp = 4°C
{Chiller Approach} = 7 - 4 = 3°C
Here’s the full English translation of your text about Condenser Approach:

2. Condenser Approach
Why is Condenser Approach measured?
1. It indicates heat transfer efficiency.
2. To assess the performance of the condenser in a chiller.
3. If the approach is high, it means the condenser is not rejecting heat properly.
4. It is very important for preventive maintenance and energy saving.
Normal Value of Condenser Approach
Normally considered 0.5°C to 1.5°C (under design conditions).
If it goes above 2°C, there may be some issue with the condenser.
Causes of High Condenser Approach
If condenser approach is higher than 2°C, possible reasons are:
1. Fouling/Scaling – Dirt or scale deposition on condenser tubes.
2. Insufficient Water Flow – Inadequate flow from cooling tower or pump.
3. High Condenser Load – Excessive heat rejection.
4. Air Pockets – Air trapped inside the condenser.
5. Tube Corrosion/Damage – Poor condition of condenser tubes.
Low Condenser Approach
If the approach is very low (below 0.5°C), it is also an abnormal condition.
This may be due to sensor calibration error or measuring mistake.