Transformers
Syllabus
Single Phase Transformers:
Construction, principle of operation, EMF equation, phasor diagram; Equivalent circuit,
determination of equivalent circuit parameters, Losses, calculation of efficiency and
regulation by direct and indirect methods; Predetermination of performance by
Sumpner’s test, Load sharing and operation of transformers in parallel, Separation of no
load losses by experimental method, principle of auto transformer; Cooling methods of
transformers.
Three Phase Transformer:
Type of connections, Relation between line and phase voltages and currents, use of
tertiary winding, Scott connection of transformers for phase conversion:
Why Transformers?
• Transformers are electrical devices used to convert or "transform" AC
voltage from one level to another. (high to low or low to high).
• Input and output are AC.
• They do this by the principle of electromagnetic induction.
Power Loss in Transmission Lines
Why Transformers?
Introduction
Introduction
Transformer is a static device which transfers electric power from
one circuit to another without changing its frequency.
The principle of operation of a transformer depends upon Faraday's
Law of Electromagnetic Induction.
Actually mutual inductance between 2 or more windings is
responsible for transformation action in an electrical transformer.
According to Faraday's Law, “Rate of change of flux linkages with
respect to time is directly proportional to the induced EMF in a
conductor or a coil”.
e = -N.dϕ / dt
Transformer
Parts of a Transformer
A transformer consists of 3 basic components
• Primary Coil or Primary Winding : It is an
electrical wire wrapped around the core on the
input side
• Secondary Coil or Secondary Winding: It is an
electrical wire wrapped around the core on the
output side
• Core : A ferromagnetic material that can conduct
a magnetic field through it. Example: Iron
Types of transformer
Based on terminal voltage
•
Step-up transformer
•
Step down transformer
Based on supply voltage
•
Single phase transformer
•
Three phase transformer
Based on construction
•
Core type transformer
•
Shell type transformer
Based on type of cooling
•
Oil-filled self cooled
•
Oil-filled water cooled
•
Air blast type
Types of transformer
• Based on TURNS RATIO
1. step-up
turns ratio > 1
VS > VP
IS < IP
2. step-down
turns ratio < 1
VS < V P
IS > IP
11
Construction - Core
Core is either square or rectangular in size
The vertical portion in which the coils are wound are
called the limb and carries the windings
The horizontal portion is called the yoke which carries the
flux produced by one winding to another.
Core
Core is made up of laminations to prevent eddy
current losses.
Laminations are made up of silicon steel of 0.3 to
0.5mm thick
Laminations are insulated from each other by
insulating materials like varnish.
Laminations are overlapped to avoid airgap at
the joints.
'L', 'E' , 'I' or 'T' shaped laminations are used.
Core
Shell type transformer
The core surrounds a
considerable portion of the
windings.
It is a double magnetic circuit
The core has 3 limbs.
The coils used are multilayered disc
type or sandwich coils.
The core is laminated.
Windings are wrapped around the
center leg of a laminated core.
Laminations
In core type transformers, the steel core laminations are in the shape
of 'L' , and these laminations are placed one above the other
alternatively.
In shell type transformers, the steel core laminations are in the
shape of 'E and I' and placed similar to that of core type.
Types of laminations
Windings
Transformer windings are made of solid copper or
aluminum strip conductors.
The coils used are wound on the limbs and are
insulated from each other.
It carries the current and produces the flux
necessary for the functioning of the transformer.
Working of a transformer
1. When current in the primary coil
changes being alternating in
nature, a changing magnetic
field is produced
2. This changing magnetic field
gets associated with the
secondary through the soft iron
core
3. Hence magnetic flux linked with
the secondary coil changes.
4. Which induces e.m.f. in the
secondary.
Dot notation
Transformers operate only on AC
• Frequency of DC supply = 0Hz
• Inductive reactance XL = 2πfL
• The effective impedance of the winding -very low
= resistance of the copper used.
• Winding draws very high current from the DC supply (I = V/R)
• Overheat & Burnout of windings
Ideal Transformers
• Zero leakage flux:
-Fluxes produced by the primary and secondary currents are
confined within the core
• The windings have no resistance:
- Induced voltages equal applied voltages
• The core has infinite permeability
- Reluctance of the core is zero
- Negligible current is required to establish
Primary Secondary
magnetic flux N : NP S
• Loss-less magnetic core
V P V S
- No hysteresis or eddy currents
Symbol for ideal transformer
Ideal Transformers
V1 – supply voltage ; I1- noload input current ;
V2- output voltgae; I2- output current
Im- magnetising current;
E1-self induced emf ; E2- mutually induced emf
Transformer Equations
Using Faraday’s law, expressions for the primary and secondary
voltages is as follows.
d d
E2 N 2 E1 N1
dt dt
Dividing the above equations we get,
E2 N2
E1 N1
Assuming that there is no power loss,
E2 I1 N 2 V2
V2 I 2 V1 I1 K
E1 I 2 N1 V1
EMF Equation of a transformer
E1 = 4.44fN1Фm E2 = 4.44fN2Фm
A 250 kVA,11000V/400V, 50Hz single –phase transformer
has 80 turns on the secondary. Calculate
(a) The appropriate values of the primary and secondary
currents;
(b) The approximate number of primary turns;
(c) the maximum value of the flux.
P 250 103
(a) Full-load primary current Ip 22.7 A
Vp 11000
P 250 10 -3
Full-load secondary current Is 625 A
Vs 400
(b) Number of primary turns
Vs N s
recall
Vp N p
Ns 80
NP VP 11000 2200
Vs 400
(c) Maximum flux
recall E 4.44 N f m
Es 400
m 22.5mWb
4.44 N s f 4.44 80 50
A single-phase transformer has 480 turns on the primary and
90 turns on the secondary. The mean length of the flux path
in core is 1.8m and the joints are equivalent to the airgap of
0.1mm. The value of the magnetic field strength for 1.1 T in
the core is 400A/m, the corresponding core loss is 1.7W/kg
at 50Hz and the density of the core is 7800kg/m3.
If the maximum value of the flux is to be 1.1T when a p.d of
2200V at 50Hz is applied to the primary, calculate:
(a) the cross-sectional area of the core;
(b) the secondary voltage on no load;
(a) recall E 4.44 N f m
Ep 2200
m 0.0206Wb
4.44N p f 4.44 480 50
recall B A
m 0.026 Practically 10% more
A 0.0187m 2 allow for insulator
B 1 .1
Vs N s
(b) recal
Vp N p
l
Ns 90
N P VP 2200 413V
Vs 480
Transformer-No load condition
Phasor diagram: Transformer on No-load
Transformer- on load
Fig. a: Ideal transformer on load
Fig. b: Main flux and leakage
flux in a transformer
Transformer on load assuming no voltage
drop in the winding
Fig shows the Phasor diagram of a
transformer on load by assuming
[Link] voltage drop in the winding
[Link] no. of primary and secondary turns
Phasor diagram of transformer with UPF
load
11/08/24
Phasor diagram of transformer with
lagging p.f load
Phasor diagram of transformer with
leading p.f load
Equivalent circuit of a transformer
No load equivalent circuit:
Equivalent circuit parameters referred to
primary and secondary sides respectively
Equivalent circuit
• The effect of circuit parameters shouldn’t be changed while
transferring the parameters from one side to another side.
• It can be proved that a resistance of R2 in sec. is equivalent
to R2/k2 will be denoted as R2’(i.e. Equivalent sec. resistance
w.r.t primary) which would have caused the same loss as R2
in secondary.
I 12 R2' I 22 R2
2
I2
R
'
2
R2
I1
R2
2
k
Transferring secondary parameters to
primary side
Equivalent circuit referred to secondary
side
•Transferring primary side parameters to secondary side
Similarly exciting circuit parameters are also transferred to
secondary as Ro’ and Xo’
Equivalent circuit w.r.t primary
where
Approximate equivalent circuit
• Since the no-load current is 1% of the full
load current, the no-load circuit can be
neglected
Transformer Tests
• The performance of a transformer can be calculated on the
basis of equivalent circuit.
• The four main parameters of equivalent circuit are:
- R01 as referred to primary (or secondary R 02)
- the equivalent leakage reactance X01 as referred to primary
(or secondary X02)
- Magnetising susceptance B0 ( or reactance X0)
- core loss conductance G0 (or resistance R0)
• The above constants can be easily determined by two tests:
- Open circuit test (O.C test / No load test)
- Short circuit test (S.C test/Impedance test)
• These tests are economical and convenient.
- these tests furnish the result without actually loading the
transformer
Open-circuit Test
In Open Circuit Test the transformer’s secondary winding is open-circuited, and
its primary winding is connected to a full-rated line voltage.
V0
Core loss Woc V0 I 0 cos 0 R0
Iw
W
cos 0 oc V0
V0 I 0 X0
I
I c or I w I 0 cos 0
I
G0 w
• Usually conducted on H.V I m or I I 0 sin 0 I 02 -I w2 V0
side I I
I 0 V0 Y0 ; Yo 0 B0
• To find V0 V0
(i) No load loss or core Woc V02 G 0 ; Exciting conductance G 0
Woc
loss V02
(ii) No load current Io & Exciting susceptance B0 Y02 G02
which is helpful in finding
Go(or Ro ) and Bo (or Xo )
Short-circuit Test
In Short Circuit Test the secondary terminals are short circuited, and the
primary terminals are connected to a fairly low-voltage source
The input voltage is adjusted until the current in the short circuited
windings is equal to its rated value. The input voltage, current and power is
measured.
Full load cu loss Wsc I sc2 R01
Wsc
R 01
I sc2
V
Z 01 sc
I sc
• Usually conducted on L.V side X 01 Z 012 R012
• To find
(i) Full load copper loss – to pre determine the
efficiency
(ii) Z01 or Z02; X01 or X02; R01 or R02 - to predetermine
the voltage regulation
Transformer Voltage Regulation and
Efficiency
The output voltage of a transformer varies with the load even if the
input voltage remains constant. This is because a real transformer
has series impedance within it. Full load Voltage Regulation is a
quantity that compares the output voltage at no load with the output
voltage at full load, defined by this equation:
Vs
At noload k
V S ,nl VS , fl Vp
Regulation up 100%
VS , fl VP / k VS , fl
Regulation up x 100%
V S ,nl VS , fl VS , fl
Regulation down 100%
VS ,nl VP / k VS , fl
Regulation down x 100%
VS , nl
Ideal transformer, VR = 0%.
Voltage regulation for Lagging Power
Factor
Voltage regulation for Leading Power
Factor
Voltage Regulation
In terms of secondary values
V2 V2 I 2 R02 cos 2 I 2 X 02 sin 2
0
% regulation
0 V2 0 V2
where '' for lagging and '-' for leading
In terms of primary values
V1 V2' I 1 R01 cos 1 I 1 X 01 sin 1
% regulation
V1 V1
where '' for lagging and '-' for leading
Transformer Efficiency
Transformer efficiency is defined as (applies to motors, generators and
transformers):
Pout
100%
Pin
Pout
100%
Pout Ploss
Types of losses incurred in a transformer:
Copper I2R losses
Hysteresis losses
Eddy current losses
Therefore, for a transformer, efficiency may be calculated using the following:
VS I S cos
x100%
PCu Pcore VS I S cos
Losses in a transformer
Core or Iron loss:
Copper loss:
Transformer Core losses
Eddy currents arise because of changing flux in core.
Eddy currents are reduced by laminating the core
Hysteresis losses are proportional to area of BH curve
and the frequency
These losses are reduced
by using material with a
“thin” BH curve
Condition for maximum efficiency
The load at which the two losses are equal =
AUTO TRANSFORMER
At some occasions it is desirable to change voltage level
only by a small amount.
i.e. may need to increase voltage from 110 to 120 V or
from 13.2 to 13.8 kV.
This may be due to small increase in voltage drop that
occur in a power system with long lines.
In such cases it is very expensive to hire a two full
winding transformer, however a special transformer
called: ”auto-transformer” can be used.
AUTO TRANSFORMER
• Diagram of a step-up auto-transformer shown in
figure below:
• C: common, SE: series
AUTO TRANSFORMER
• A step-down auto-transformer :
• IH=ISE
• IL=ISE+IC
AUTO TRANSFORMER
• In step-up autotransformer:
VC / VSE = NC / NSE (1)
NC IC = NSE ISE (2)
voltages in coils are related to terminal voltages as
follows:
VL=VC (3)
VH=VC+VSE (4)
current in coils are related to terminal currents:
IL=IC+ISE (5)
IH=ISE (6)
AUTO TRANSFORMER
• Voltage & Current Relations in Autotransformer
• VH=VC+VSE
• since VC/VSE=NC/NSE VH=VC+ NSE/NC . VC
• Noting that: VL=VC
VH=VL+ NSE/NC . VL= (NSE+NC)/NC . VL
• VL / VH = NC / (NSE+NC) (7)
• Current relations:
• IL=IC+ISE employing Eq.(2) IC=(NSE / NC)ISE
• IL= (NSE / NC)ISE + ISE, since ISE=IH
IL= (NSE / NC)IH +IH = (NSE + NC)/NC . IH
IL / IH = (NSE + NC)/NC (8)
AUTO TRANSFORMER
Apparent Power Rating Advantage of Autotransformer
Note : not all power transferring from primary to
secondary in autotransformer pass through windings
Therefore if a conventional transformer be reconnected as
an autotransformer, it can handle much more power than
its original rating
The input apparent power to the step-up autotransformer
is : Sin=VLIL
And the output apparent power is:
Sout=VH IH
AUTO TRANSFORMER
And :
Sin=Sout=SIO
Apparent power of transformer windings:
SW= VCIC=VSE ISE
This apparent power can be reformulated:
SW= VCIC=VL(IL-IH) =VLIL-VLIH
employing Eq.(8) SW= VLIL-VLIL NC/(NSE+NC)
=VLIL [(NSE+NC)-NC] /(NSE+NC)=SIO NSE /(NSE+NC)
SIO / SW = (NSE+NC) / NSE (9)
AUTO TRANSFORMER
Internal Impedance of an Autotransformer
Another disadvantage: effective per unit
impedance of an autotransformer w.r.t. the related
conventional transformer is the reciprocal of power
advantage
This is a disadvantage where the series impedance
is required to limit current flows during power
system faults (S.C.)
Example of Variable Auto-Transformer
All day efficiency
All day efficiency is defined as the ratio of total
energy output of transformer to thetotal energy
input in 24 hours.
out put in watts
ordinary commercial efficiency
input in watts
output in kWh
all day ( for 24 hours)
Input in kWh
•All day efficiency is always less than the commercial efficiency
Transformer Voltage Regulation and
Efficiency - Tutorial
(a) Find the equivalent circuit referred to H.V. side
(b) Find the equivalent circuit referred to L. V. side
(c) Calculate the full-load voltage regulation at 0.8 lagging PF, 1.0 PF,
and at 0.8 leading PF
(d) Find the efficiency at full load with PF 0.8 lagging
SOLUTION:
Open circuit impedance angle is:
1 POC 1 50
OC cos cos 84
VOC I OC 2300 0.21
Excitation admittance is:
I 0.21
YE OC 84 84 9.13 10 5 84
VOC 2300
0.0000095 j 0.0000908
Transformer Voltage Regulation and
Efficiency - Tutorial
• Impedance of excitation branch referred to primary:
1
RC 105k
0.0000095
1
XM 11k
0.0000908
• Short Circuit Impedance angle:
PSC 160
SC cos 1 cos 1 55.4
VSC I SC 47 6
• Equivalent series Impedance:
VSC 47
Z SE SC 55.4 7.83355.4
I SC 6
Req=4.45 Ω, Xeq=6.45 Ω
4.45 j 6.45
Transformer Voltage Regulation and
Efficiency
• The equivalent circuits shown below:
Transformer Voltage Regulation and
Efficiency
• (b) To find eq. cct. Referred to L.V. side,
impedances divided by a²=NP/NS=10
RC=1050 Ω , XM=110 Ω
Req=0.0445 Ω , Xeq=0.0645 Ω
• (c) full load current on secondary side:
IS,rated=Srated/ VS,rated=15000/230 =65.2 A
To determine V.R., VP/ a is needed
VP/a = VS + Req IS + j Xeq IS , and:
IS=65.2/_-36.9◦ A , at PF=0.8 lagging
Transformer Voltage Regulation and
Efficiency
• Therefore:
VP / a = 2300 (0.0445)(65.2 36.9 ) j 0.0645 65.2 36.9
2300 2.9 36.9 4.2153.1
230 2.32 j1.74 2.52 j 3.36
234.84 j1.62 234.850.4V
V.R.=(234.85-230)/230 x 100 %=2.1 % for 0.8 lagging
• At PF=0.8 leading IS=65.2/_36.9◦ A
VP / a = 2300 ( 0 . 0445)( 65. 2 36. 9 ) j 0 . 0645 65. 2 36. 9
2300 2.936.9 4.21126.9
230 2.32 j1.74 2.52 j 3.36
229.8 j 5.10 229.851.27 V
Transformer Voltage Regulation and
Efficiency
• V.R. = (229.85-230)/230 x 100%= -0.062%
• At PF=1.0 , IS= 65.2 /_0◦ A
• VP/a= 2300 (0.0445)(65.20 ) j (0.0645)(65.20 )
2300 2.90 4.2190 230 2.9 j 4.21
232.9 j 4.21 232.941.04V
• V.R. = (232.94-230)/230 x 100% = 1.28 % for PF=1
Transformer Voltage Regulation and
Efficiency
• Example: Phasor Diagrams …
Transformer Voltage Regulation and
Efficiency
• (d) to plot V.R. as a function of load is by repeating the
calculations of part “c” for many different loads using
MATLAB
Transformer Voltage Regulation and
Efficiency
• (e) Efficiency of Transformer:
- Copper losses:
PCu=(IS)²Req =(65.2)² (0.0445)=189 W
- Core losses:
PCore= (VP/a)² / RC= (234.85)² / 1050=52.5 W
output power:
Pout=VSIS cosθ=230x65.2xcos36.9◦=12000 W
η= VSIS cosθ / [PCu+PCore+VSIS cosθ] x 100%=
12000/ [189+52.5+12000] = 98.03 %