Testing and Commissioning of MetalClad Switchgear

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

elect rical-engineering-port al.

com

http://electrical-engineering-portal.com/testing-andcommissioning-of-metal-clad-switchgear? utm_source=EEP+Monthly+Download+Updates&utm_campaign=99f 90e1405Oct_7_2012_Monthly_Updates10_6_2012&utm_medium=email

Testing and Commissioning of Metal-Clad Switchgear

Distribution substation - 20/04kV MCset metal-clad switchgear (Schneider Electric)

Electrical testing and commissioning of Metal-Clad switchgear is essential to the safe start for the first time, regardless of its size, type or industry. This article cover testing and start-up / commisioning procedures for all the components of medium voltage switchgear like circuit breaker, busbars, instrument transformers (current/voltage), disconnect and grounding switches etc.

1.1. Objective

To verify the physical condition and proper connections of bus bar.

1.2. Test Equipment Required:


Insulation test (Megger) Micro ohmmeter High voltage tester Torque wrench

1.3. Test Procedure:


1.3.1. Mechanical Checks and Visual Inspection:
Inspect switchgear and all components for any physical damage / defects. Check nameplate information for correctness. Inspect enclosures for proper alignment, foundation fixing, and grounding and vermin entry. Inspect all covers, panels section and doors for paintwork and proper fit. Check all the transport locks are removed. Check for smooth and proper movementof racking mechanisms, shutter, rollers, rails and guides. Check proper alignment of the primary and secondary contacts. Check operation of all mechanical interlocks. Check tightness of all bolted connections. Check for correct phasing connection of bus bar. Perform mechanical check and visual inspection for breaker / Contactor as per section. Perform mechanical check and visual inspection for instrument transformers as per section Perform mechanical check and visual inspection on all disconnect / grounding switches as per section.

1.3.2. Insulation Resistance T est:


It includes panel enclosure, busbar, CT and circuit breaker. The following precautions should be taken care, before starting the testing. A visual inspection will be made to ensure the surface dust and moisture has been removed from the component under test. Ensure the component is isolated from other connected system, which may feed back to other components or circuits not under test.

On testing, voltage shall be applied between one phase and other phases connected with ground, testing shall be repeated for other phases as mentioned above. Test voltage limits mentioned in table below: Rated voltage 100-1000V AC/DC >1000 to <5000V AC > 5000V AC Test voltage 1000V DC 2500V DC 5000V DC

1.3.3. Contact Resistance T est:


This test is to confirm the busbar joints are connected properly and verify the tightness. The test connection diagram is as shown in Figure below. The test shall be done with CBs inserted and closed. Measure the contact dc resistance between panels by injecting 100A DC . This will include busbar joint, CB contact resistance, CB cluster resistance, and CT primary resistance (if applicable).

Limits:
The obtained results should be similar for all phases for each set of measurement. Other influencing factors to be considered, like length of the measured path, rating of the busbar, rating of CB, rating of CT and temperature.

1.3.4 High Voltage

1.3.4 High Voltage T est


To determine the equipment is in propercondition to put in service, after installation for which it was designed and to give some basis for predicting whether or not that a healthy condition will remain or if deterioration is underway which can result in abnormally short life.

T est Instruments Required:

Figure 1 - Contact resistance test

Calibrated AC Hi-pot test set for switchgear with leakage current indicator and overload protection. Calibrated DC Hi-pot test set for cables with leakage current indicator and overload protection.

1.4. Applicable Standard


IEC60298: AC metal enclosed switchgear and control gear for rated voltage above 1KV to 52KV. Resource: Procedures for Testing and Commissioning of Electrical Equipment Schneider Electric

You might also like