Transformer data
3Ph/1Ph
3
MVA=
25
HV Volts=
21
LV volts=
6.9
HV Amps=
687.342
LV Amps=
2091.910
HV CT Pri=
800
HV CT Sec=
1
LV CT pri=
2500
LV CT sec=
1
KV
KV
A
A
Slope
I1 sec
I2 sec
0.2
0.859
0.837
slope=(I1-I2)/(I1+I2)
Calculating I1 & I2
I1 in terms I1 in terms of I2 in terms I2 in terms of
of pu
sec value
of pu
sec value
I1 sec=
I2 sec=
Idiff=
Slope=
I1 diff 3ph=
I2 diff 3ph=
0.859
0.837
0.1
0.2
0.086
0.084
1
1.5
2
2.5
3
3.5
4
4.5
5
5.5
6
6.5
7
7.5
8
8.5
9
9.5
10
0.859
1.289
1.718
2.148
2.578
3.007
3.437
3.866
4.296
4.725
5.155
5.585
6.014
6.444
6.873
7.303
7.733
8.162
8.592
0.6666667
1
1.3333333
1.6666667
2
2.3333333
2.6666667
3
3.3333333
3.6666667
4
4.3333333
4.6666667
5
5.3333333
5.6666667
6
6.3333333
6.6666667
0.558
0.837
1.116
1.395
1.674
1.952
2.231
2.510
2.789
3.068
3.347
3.626
3.905
4.184
4.463
4.742
5.021
5.300
5.578
Reverse calculation Now on trip value calculating
Slope
I1 in
I2 in
I1 in pu
I2 in pu
Amps(sec)
Amps(sec)
1
1.718
2.578
1.164
2.000
3.001
0.558
1.116
1.674
Calculated value
Insert value
0.667
1.334
2.001
Slope
0.271
0.200
0.200
Type of Fault
Three-phase
Two-Phase
Single-Phase
with Io elimation
Single-Phase
without Io
elimanation
ReferenceWinding
(High Voltage side)
Even VG Numeral
0,2,4,6,8,10
Odd VG Numeral
1,3,5,7,9,11
1
1
1
1
1
0.866
1.5
1.5
1.73
1.73