OC Lecturenotes ConctructionTech1 Course Reader PartB PDF
OC Lecturenotes ConctructionTech1 Course Reader PartB PDF
BUILT ENVIRONMENT
DEPARTMENT OF CONSTRUCTION ECONOMICS
AND MANAGEMENT
CONSTRUCTION TECHNOLOGY I
COURSE READER
PART B BUILDING COMPONENTS
Compiled By:
Illustrated By:
Bayonle Windapo
January 2012
CONTENTS
1.
2.
3.
4.
5.
Foundation
Floor
Walls
Roof Systems
Stairs and Ramps
FOUNDATION
DEFINITION
Any part of the structure that serves to transmit load to the earth or rock, usually below
ground level (Harris, 2001);
The part of a structure that transfers the dead and imposed loads safely onto the ground
(Brett, 1997);
That part of a building which is in direct contact with and is intended to transmit loads to
the ground;
It has to anchor the superstructure of the building against uplift and racking forces.
Factors that aff ect the choice of Foundation
Often the foundation is considered as a separate entity from the structure. This approach
leads to the belief that the foundation should be designed on its own to provide a stable base
for the structure. However, the foundation is only one element in the overall picture of soil
structure interaction.
This means that:
1. The type of building structure and how it transmits the load to the ground places
demands on the foundation; and
2. The type of soil and soil behaviour, which is likely to occur, also influences the
foundation design.
The influence of structure type can be seen simply in the case of a three-storey block of flats
where load bearing walls will have a bearing pressure that can be carried on relatively
shallow strip footings, whereas a framed building of the same size will concentrate the loads
on the columns, possibly necessitating much deeper foundations or even piles.
Similarly a flexible structure on a soil likely to settle a little will need only a light foundation as
it can tolerate the movement, whereas, a design using rigid brittle finishes will require a much
more complicated foundation to prevent any movement reaching the structure.
Therefore, in choosing a suitable foundation, the factors to be considered are the type of
building structure and the soil type. While the structural design may be altered, the soil exists
on the site and can only be changed at great cost. It must therefore be accepted as it is and
its probable long-term behaviour assessed.
Rocks
Igneous Rocks which include granite are massively bedded soils and therefore not subject to
cracking and shrinkage
Suitable Foundation: Simple Strip Foundation
Peat
Decayed Vegetable matter Black or dark brown in colour
Highly compressible and unsuitable to receive foundations
Suitable Foundation: Piles driven down to underlying firm stratum
Consolidation Settlement
The soil mass consists of an arrangement of soil grains which may be rounded or angular in
sands and plate-like in clays. Starting with a newly deposited soil layer, these grains are
relatively openly packed but as load is applied they are compressed and become more
tightly packed. This process is known as consolidation.
In sands and silts, there is good drainage between the particles and as load is applied the
water between the grains is squeezed out rapidly and settlement, if it takes place, occurs
almost instantaneously, whereas in clays, the drainage is poor and any settlement occurring
may continue for a long while after the application of load. Loose sands, silts, gravels and
soft clays will show marked settlements under load.
It is important to note that while bearing capacity failure involves the physical displacement of
soil from beneath the foundation, consolidation settlement is the compression in situ of soil
beneath the foundation.
Serious consolidation problems may arise where buildings cover two different soil conditions,
which have very different settlement characteristics, e.g. half on rock outcrop and half on
deep fills. This commonly occurs where a building on a slope has foundations in a cut and on
fill and breaks its back near the changeover. All fills are highly suspect unless there is proof
of adequate compaction. Rubbish tips are worse because they contain compressible
vegetable matter, which will rot, and metal, which will corrode over time. Normal
consolidation settlement is generally not a major problem in house construction; however,
care must be exercised in dune areas at the coast, in windblown sand areas in the interior
and where fill has been placed.
Apart from the foundation design, it is possible in some cases to adapt the structure. This
can be made more flexible to tolerate the expected differential movements, or it may be
designed as a single rigid unit with its foundation, so that it will settle as a unit without
distortion.
When the dry season comes the soil will shrink and in some cases the building may even
subside. This settlement may create new cracks and when the rains come again the situation
can deteriorate further. There are different terms used in explaining heaving of expansive
soils including:
a. Mechanism of heaving: For heaving to occur, a potentially expansive soil must be
subjected to a change in moisture content within the critical moisture content range for
that soil.
Potential expansiveness is determined by the amount of expansive clay minerals the
soil contains, which can be ascertained by means of various laboratory tests; and the
thickness of the potentially expansive layers.
b. Effect of climate: The higher the initial moisture content of the soil, the smaller the
amount of heave likely. Therefore in the relatively dry inland regions of South
Africa, this change in moisture content usually occurs in whole or in part within the
critical range, and swelling will occur causing the structure to heave.
In wet regions, the initial moisture content may be above the upper limit of the
critical range and consequently no swelling will occur. In this case however, drying out
as a result of drought or of higher than usual evaporation by vegetation will cause
shrinkage settlement if the moisture content drops to within the critical range.
In the very dry semi-desert regions the rainfall is so sparse and the water-table
so deep that building causes no natural change in the moisture content of the soil and,
even if the soil is potentially expansive and the initial moisture content is within the
critical range, no heaving will occur.
c. Rate of heave: This depends on the availability of moisture and the permeability of
the soil, which controls the ingress of moisture into the soil. During years of low rainfall
there would be less movement than during wet years.
Where there is a high permeability due to fissures and cracks in the soil, the moisture
can enter rapidly and most of the movement will occur during the first wet season. In
deep less permeable soil on the other hand, the movement is more gradual.
d. Crack patterns: The cracking of buildings is due to differential movement and there
is no specific pattern, which distinguishes cracks due to heaving from those resulting
from other causes.
The construction of a building involves removal of vegetation, thus cutting off
evaporation losses as well as the direct ingress of moisture. When it rains, the soil
outside the building gets wet and moisture moves inwards under the building. The soil
under the outer walls therefore becomes moister and heaves, causing a dishing
pattern with the centre of the building lower than the corners. This leads to vertical and
diagonal cracks, which are wider lower down than they are at the top. In addition,
walls often tend to be pushed over the foundation at the level of the damp-proof
course.
As more moisture moves under the building, the centre will rise too. During the dry
season, the outer walls will settle slightly as the soil under them dries out a little, but
the centre will be unaffected. This means that after a period, the centre will be higher
than the sides of the building and will remain so, resulting in the doming or corners
down - pattern of cracking as shown below in Figure 1.
Here the cracks are widest at the top and the cracking of brickwork over internal doors and
above windows is particularly noticeable.
Methods used to solve the problem of heav ing soil: Since movements on expansive
soils are as a result of changes in moisture content of the soil, the solutions to this problem
include:
Structural treatment must be applied so that the building can either withstand or
tolerate the movement. Structural treatment can be divided into three categories:
a. Isolation of the structure from the soil movements: anchor piles can be
used or deep strip foundations.
Anchor piles: To isolate the building structure from the soil movements, piles
taken down below the layer of potentially expansive soil, or below the permanent
water table or below 10m whichever is the shallowest are used. The building is
carried on grade-beams, which span between the piles at least 300mm above
ground level in order to prevent any surface movements of the soil from being
transmitted to the gradebeams.
b. Rigid construction to withstand the soil movement: The building and its
foundation are designed as a rigid base, which will ride out the movement like a
ship at sea. This may be done by designing the foundation as a rigid raft and
sitting the building on it, or the rigidity may be achieved by using the walls as deep
beams. This requires engineering design and high standards of workmanship.
c. Flexible construction to tolerate the differential movements: There are
few building systems available today that will tolerate differential movement
however small. Certain industrialized building systems involving panel construction
and some lightweight framed construction may more readily accommodate
movement than traditional masonry construction.
The method that has found wide application in South Africa has been to make
single storey structures semi-flexible by providing vertical open joints/gaps
approximately 12mm wide in the brickwork at selected positions in the masonry
walls and reinforcing the individual units so formed to prevent them from cracking
or floors separated from the walls as shown in the figure below or constructing
internal doorways so that they act as open joints. This is known as split
construction.
10
According to Kohler (1984) a combination of soil, moisture and structural treatment is often
the best result and the final choice depends on cost.
11
12
related to the second, is that the soil must be capable of being eroded by the flow of water
passing through it.
Methods used to solve the problem of sinkholes & subsidence: There is no method of
construction suitable to withstand the severe subsidence that occurs. The formation of a
sinkhole could have catastrophic consequences. The obvious solution therefore would be
site selection steps should be taken to prevent buildings being subjected to these types of
movement.
If the site must be used for whatever reason, the only factor over which control can be
exercised is the source of water that may cause erosion. Therefore, all water retaining
structures, pipelines, canals and drains should be watertight and checked frequently to see
that they remain so.
Quicksand
Contrary to popular belief, quicksand is not a type of sand but a condition, which in special
circumstances can occur, in any granular material from fine sand to gravel. It is
characterized, in the extreme case by the inability of the material to support a load; while in
the partial condition, where the material is likely to become quick, a great reduction in the
expected load-carrying capacity of the material results.
A common practical observation of quicksand conditions may be found on many beaches
where at low tide the damp sand is firm enough to support motor vehicles, but once the tide
starts coming in, the upward flow of water through these sands causes them to lose stability,
and hence bearing capacity, until the extreme case arises where all stability is lost and the
sand can support no load.
Quicksand conditions are also frequently encountered at the bottom of excavations below
the water table where these conditions are produced by seepage pressure. According to
Kohler (1984), the running sands of the Table Bay area are typical of these conditions. It is
therefore evident that quicksand conditions are intimately associated with the flow of water
through the soil. This flow tends to float the grains in the water, gradually reducing the intergranular pressure as the rate of flow is increased until, in the extreme case, the material
becomes liquid and all the particles are in suspension.
However, in building practice, such extreme cases are very rare. The more common cases
occur where a flow of water, either still existing, or present in some past history of the
deposit, is holding or has left a layer of material in a very loose state. The soil profile as a
whole is usually able to support a fair load without failure, but if the load is increased to the
point where the shearing force transferred to the weak layer becomes greater than the
available shear strength of that layer, a sudden and spectacular collapse of the whole profile
occurs, usually with disastrous results. This increase in shearing force may also be brought
about by sudden shock, such as occurs with pile driving, and is a frequent cause of damage
to buildings on sites adjacent to new constructions founded on piles.
Trenches dug in sands where the water table is virtually at the surface can produce similar
conditions due to the effect of water flowing into the trench. This is not only a danger to the
trench, but can affect foundations if the trench is close to them.
13
Sloping Ground
Soil cover results from the action of wind and rain, frost and plants, which break down the
surface of rocks. The dangerous zone in sloping grounds is midway because as we go up
the hillside, the soil cover is less, the soil collects at the base, while midway, the soil can
slide down the slope. Soils have a natural angle of repose. Gravel and soil particles always
tend to settle at an angle, which is fixed by the natural characteristics of the soil itself. If a
spade full of sand is taken from the side of a heap, the grains above this point will slide down
to fill the space. This is because an unstable slope was created. Therefore, cutting out a site
for a house in a slope will make the system unstable and may create landslip problems (see
Fig. 3 below).
If on the other hand the building is placed on the outer edge of the cut or too close to the top
of a slope, the additional weight may cause the loose material to slide.
Methods used to solve the problem posed by sloping grounds: When any building on a
sloping site is considered, a competent engineers opinion should be obtained on the overall
stability of the project. Where there are inherent signs of instability in the surface material,
the project should be abandoned or approached with the utmost care.
Where cuts are made into hillsides, it should be ensured that one is not cutting across dip
planes or in any other way undermining the stability of the portion left behind. If it is
necessary to maintain material at slopes greater than the natural angle of repose, properly
retaining walls should be used.
14
HH2
HH2.1
HH2.2
HH2.3
HH2.4
The width of any continuous strip foundation shall be not less than
(a)
600mm in the case of foundation to a masonry wall or to a timber framed
wall supporting a roof with Class B covering (concrete tiles, clay tiles of
similar materials and thatch); or
(b)
400mm in the case of a foundation to a masonry wall or to a timber
framed wall supporting a roof with Class A or Class C covering (metal
roof tiles/sheets and fibre-cement sheets).
HH2.5
(a) Where any strip foundation is laid at more than one level, the higher portion
of the foundation shall extend over the lower portion for a distance at least
equal to the thickness of the foundation (see Figure below).
15
(b) Any void between the top of the lower portion of such foundation and the
underside of the higher portion shall be completely filled with concrete of the
same strength as that required for such foundation
It is also important to note the requirement of Part G: Excavations Clause GG2.5 that states
that: Except where the foundation for any external masonry wall is placed on solid rock, the
bottom of the excavation for such a foundation shall not be less than 300 mm below the level
of the adjoining finished ground.
16
a) Traditional Shallow Strip Foundations: is commonly adopted for two or threefloored domestic buildings on good firm
non-shrinkable sub-soils such as gravel
(See Figure 4).
The section at Figure 5 is adopted for dwelling houses of three-floors on compact and stiff
sub-soils. For shrinkable sub-soils, the depth should be 915mm minimum.
b) Wide Strip Foundations: This type of foundation is used where the structural
loading is very high relative to the sub-soil bearing capacity. Figures 6 and 7 show the two
possible forms of construction, one is unreinforced with the thickness at least
equivalent to the projection, whilst the
second is reinforced in the area of
greatest tensile stress to economize in
concrete.
Figure 6 Wide Strip Foundation (Mass
Concrete)
17
Trench fill is a very simple form of construction designed to save considerable substructural construction time.
After trench excavation to the
required width and depth,
concrete is placed to within
450mm of the finished ground
level.
18
19
Pad foundations are suitable for most subsoils except loose sands, loose gravel and filled
areas. Pad foundations are usually constructed of reinforced concrete and where possible
are square in plan.
Pile Foundations
Pile foundations are used where conventional foundations would be very deep and
uneconomical. It is uneconomical to consider normal excavation beyond 2m. The lack of
suitable foundation conditions may be caused by:
1. Natural low bearing capacity of subsoil such as shrinkable clays, in-fill or waste tips
and peat;
2. High water table in poorly drained areas giving rise to permanent dewatering costs:
3. Subsoil(s) which may be subject to moisture movement; and
4. Steep slopes
Pile foundations can be defined as a series of columns constructed or inserted in the ground
to transmit the load(s) of a structure to a lower level of subsoil. This system resembles
building on stilts or columns, with the base of the support resting on a load-bearing stratum
up to about 4m below the surface. Piles may be classified by their basic design functions into
- end bearing piles, friction or floating piles, replacement piles or displacement piles or by
their method of construction into cast in-situ or precast piles.
Figure 11 shows the principle, which
is the same for cast in situ or precast
driven piles.
Figure 11 Piled Foundations
20
Cast In-situ Piles: These piles are generally end bearing, but may have an enlarged
diameter for frictional resistance to settlement where quality subsoil is impossible to locate.
Boring is by powered auger to a depth rarely exceeding 4m. (Beyond this is expensive for
simple dwellings). A steel tube lining is required where the boring is liable to collapse, and
this should be extracted after reinforcement and concrete are placed. Figure 12 below shows
the construction of a typical cast in-situ end bearing pile with longitudinal reinforcement to
resist the effect of ground movement.
Precast Concrete Piles: These are fibre reinforced concrete hollow shells of
approximately
300mm
diameter and 1 m length
linked with a steel
sleeve. Placing is by
driving each section with
a vertical drop hammer
until sufficient resistance
is achieved. The hollow
core
receives
reinforcement and in-situ
concrete, which ties in
with an in-situ concrete
edge
beam.
The
potential in poor subsoil
is
considerable,
as
boring equipment is not
required and depth of
ground penetrations is
less critical.
21
Basic Design Procedure ~ this according to Chudley and Greeno (2006) can be
considered as a series of steps or stages including ~
1. Assessment of site conditions in the context of the site and soil investigation report.
2. Calculation of anticipated structural loading(s).
3. Choosing the foundation type taking into consideration
a. Soil conditions;
b. Type of structure;
c. Structural loadings;
d. Economic factors;
e. Time factors relative to the proposed contract period; and
f. Construction problems.
4. Sizing the chosen foundation in the context of loading(s), ground bearing capacity and
any likely future movements of the building or structure.
Figure 14 shows a cross-section through a house with the roof resting on the walls and the
walls supported on concrete
strip footing bearing on firm
ground. The function of the
footing is to spread the load
from the wall over a
sufficiently large area to
ensure that the safe bearing
capacity of the supporting
ground is not exceeded. If the
soil has a high bearing
capacity it should be possible
to build the brick wall directly
onto the bottom of a level
foundation trench.
22
Generally, it would be found out however that the safe bearing capacity is likely to be
exceeded if a foundation footing is not provided and the wall will be subjected to excessive
settlement as shown in Figure 14 A. A further practical reason for having a footing is that the
bricklayer needs a level surface on which to start his first course of brickwork. For both these
reasons therefore, a concrete footing as shown in Figure 14 B is employed.
23
24
Remedy is to increase plan size of foundation, to reduce the load per unit area or
alternatively reduce the loads being carried by the foundation.
Whatever solution that is adopted, the thickness of the concrete footing should not be less
than the projection of the strip each side of the wall because if there were a failure by shear,
the 450 angle of shear would not reduce the bearing of the base on the subsoil as shown in
Figure 16. If T is not less than P, then the bearing area is not reduced.
25
lower but there are no structural reasons for making the thickness d of the footing the same
with the overlap as shown in Figure 14 D.
On steeply sloping sites as shown in Figure 14, it is common to employ a bulldozer to create
a level area on which to build the house. This often means that the house is sited partly on
cut and partly on fill as in the section shown in Figure 14. In such cases, it is imperative to
take the foundation excavations through the fill into undisturbed ground if settlement and
cracking are to be avoided.
26
ii.
Concrete is a material, which is strong in compression but weak in tension. If its tensile
strength is exceeded, cracks will occur resulting in a weak and unsuitable foundation (see
Figures 14 C and 17).
Concrete M aterials
Source: Group 11 CON1018W 2010
One method of providing tensile resistance is to include in the concrete foundation, bars of
steel as a form of reinforcement to resist all the tensile forces induced into the foundation
(see Figure 18).
27
Steel a material that has high tensile strength is available as rolled bars.
Steel Reinforcement
Source: Group 11 CON1018W 2010)
28
The strip foundation is produced by first of all, excavating a trench to the required design
depth and width as shown in Figure 19(a-e). The bottom of the trench is leveled and
compacted and then blinded with concrete 50mm thick (also known as concrete blinding). A
concrete bed not less than 150mm thick is then placed on the blinding and leveled.
Brick/block wall is then set till the designed height of the foundation is achieved (Figure 20(ac)). The side of the trench is then backfilled with selected excavated materials. There are two
possible forms of construction of the strip foundation:
Un-reinforced with the thickness of the concrete at least equivalent to the projection of
the footing on both sides of the foundation wall, which is un-economical; or
Reinforced in the area of greatest tensile stress to economize the amount of concrete
used.
29
30
31
32
On completion of the foundation walls, the foundation cavity is filled with sand and
compressed. Also, the gap between the two external layers of bricks is filled with concrete.
33
FLOORS
A floor is the ground or upper levels in a building, which provides an acceptable surface for
walking, living and working (Brett, P. (1997) An Illustrated Dictionary of Building).
Types of Floors
Ground Floors
- In-situ Concrete (Solid or Suspended)
- Suspended Timber
Suspended Floors
Timber
Steel Joist
Concrete (Filler Joist; Reinforced Concrete; Hollow Pot; and Pre-cast concrete
floors)
JJ2
Concrete Floors
1. Any floor of any building shall comply with the fire requirements
2. Any floor supported on ground or on filling shall be constructed ofa. impervious floor units not less than 40mm thick and consisting of slate, bricks,
natural stone or other approved material; or
34
b. a concrete slab which shall have a compressive strength of not less than 10 M
Pa at 28 days, or be mixed in the proportions by volume of one part cement,
four parts sand and five parts coarse aggregate, and the thickness of such slab
shall not be less than 75mm.
Filling Material
Source: CON1018W 2010 Group 11
4. Any concrete floor slab passing over or supported on foundation walls shall be
designed as a suspended floor slab.
35
Timber Floors
6. Any suspended timber floor shall be constructed in accordance with SABS 082.
7. The underside of any floorboards other than those laid on a concrete slab shall not
be less than 550mm above the surface of the ground immediately below such
floorboards.
8. Provision for ventilation under suspended timber floors and the protection of
ventilation openings shall be in accordance with SABS 082 (Code of Practice for
timber buildings).
36
9. The materials used in any suspended timber floor shall be in accordance with
SABS 082.
Floor Fabrication
!"#$%&'()'*+,-%&.&'!/0%"-/."+,'
'
Source: CON1018W 2010 Group 11
$%&'()*!+,-.#./0!1#.#!2(&'3!..4!
!
Insitu
Concrete Ground Floor Construction
!
Components:
Hardcore:
Materials with fairly large particles that are hard and durable such as rock wastes,
brick rejects, demolition rubble or any other broken rubble
37
38
Components Used in Suspended Timber Ground Floor Construction: These are as follows:
Air Brick/Air Void:
Placed at least 125mm beneath the wooden floor joists. The air brick/air void
provides air circulation to prevent condensation (water from humid air collecting
as droplets on a cold surface. It can also refer to the conversion of a vapour or gas
to a liquid).
Wall Plate:
A horizontal piece of timber 75mm x 100mm in cross section bedded level on the
DPC in order to distribute load, ensure a level surface and provide a bearing and
fixing point for the joists.
Joists:
One of a series of parallel timber beams 75mm x 100mm in cross section that
directly supports the floorboards. It is nailed to the wall plates across the shortest
span @ 300 400mm centres.
Floor Boards:
100 x 25mm wide x 25 38mm thick timber boards nailed to joists. (The narrower
the floor boards the better to avoid warping (become bent or twisted out of shape)
caused by shrinkage.
39
The timber floorboards are planed to a level and smooth surface, either by hand or machine.
Scraped, rubbed smooth with sandpaper and finally oiled or waxed and polished.
2. Steel
Steel is used in steel joist floors. It is a structural material that combines high strength
and stiffness with elasticity. Measured in terms of weight to volume, it is probably the
strongest low-cost material available.
3. Concrete
It is used in concrete floor construction. It is a composite material made from a
mixture of cement, aggregate and water. It is classified as plain, reinforced, pre
stressed, cast in situ, precast or lightweight.
Advantages of concrete:
Disadvantages:
It is heavy
It requires a forming or molding process before it is placed to set and
harden if insitu.
40
FLOOR FINISHING
Factors to consider ~
When selecting a floor finish, many factors deserve consideration but not all are of equal
importance as requirements vary from one room to another. For example:
Resistance to moisture
Appearance
Maybe relevant in the sitting room, but is of little consequence in a store
Functional requirements considered in choice of floor finish ~
Durability
Resistance
To wear, oil, grease, chemical and moisture
Safety
That is the finishes should be non-slip, particularly in bathrooms and kitchens
where floors may become damp
2. Wood Flooring
Durable, hard, close-grained species of hardwood such as mahogany, masonia and
cedar are mostly used. The three basic types of wood flooring include ~
Strip, Plank and Block Flooring, examples of its different design format are shown
below ~
41
3. Resilient Flooring
This provides an economical, dense, non-absorbent flooring surface with good
durability and ease of maintenance. Because of its resilience (able to recoil or spring
back into shape, after bending, stretching or being compressed), it is able to
withstand permanent indentation, whilst contributing to its quietness. Types include ~
Flexible PVC tiles
Cork tiles
Rubber tiles
Linoleum
Asphalt
4. Terrazzo Flooring
This is a decorative form of concrete usually made in situ or precast, from marble
chips and white or coloured cement to a mix of 2:1
5. Carpets
Made from synthetic fibres placed on jute backing, it provides warmth, comfort,
additional texture and acoustically absorbent floors
42
WALLS
A wall is the vertical enclosing and dividing elements of a building. The wall may be
classified as load bearing or non-load bearing, structural or non-structural. It may also be
classified as either solid, framed or cavity. External walls form part of the external envelope
of buildings.
A structural wall is one, which is provided to resist the loads acting on a building and to
transfer these loads to the ground.
A non-structural wall is defined as one which does not form part of a structural system but
which may from time to time be subject to forces other than its own weight. Examples of
which are panel walls in framed structures, partition walls, balustrade walls and parapet
walls, all of which may from time to time have to resist horizontal forces due to wind or use
by occupants of the building. The strength of non-structural walls is thus just as important as
that of structural walls.
The National Building Regulations (NBR) in Part K states the requirements for wall based on
its functions as follows:
K2 Water Penetration
Any wall shall be so constructed that it will adequately resist the penetration of water into any
part of the building where it would be detrimental to the health of occupants or to the
durability of such building.
K3 Roof Fixing
Where any roof truss, rafter or beam is supported by any wall, provision shall be made to fix
such truss, rafter or beam to such wall in a secure manner that will ensure that any forces to
which the roof may normally be subjected will be transmitted to such wall.
K4 Behaviour in Fire
Any wall shall have combustibility and fire resistance characteristics appropriate to the
location and use of such wall.
K5 Deemed-to-Satisfy Requirements
The requirements of regulations K1, K2, K3 and K4 shall be deemed to be satisfied where
the structural strength and stability of any wall, the prevention of water penetration into or
through such wall, the fixing of any roof to such wall and the behaviour in a fire of such wall,
as the case may be, comply with Part K of section 3 of SABS 0400 (the How part).
43
(a)
(i)
is the subject of a rational design indicating that the strength and
stability of such wall comply with the requirements of Part B; or
(ii) forms part of the structural system in any building contemplated in provision
KK2 (Building Limitations for Empirical Design) and complies with deemed-tosatisfy rules contained in provisions KK3 to KK11 inclusive;
KK3 Empirical Rules for Walls
KK4 Materials
KK5 Wall Dimensions
KK6 External masonry Cladding or Infilling Panels in Framed Buildings
KK7 Column and Piers in Walls
KK8 Cavity Walls
KK9 Foundation Walls
KK10 Balustrade Walls
KK11 Free-Standing Walls
This clause is concerned only with the structural design of walls. Two options
are given rational design in accordance with Part B of the NBR, or empirical
design in agreement with Rules KK3 to KK11
(b)
(c)
(d)
(b)
The span between supporting walls of a timber or metal roof truss, roof rafter or
roof beam shall not exceed 10m and the span between supporting walls of any
first floor or roof slab shall not exceed 6m.
(c)
(i) The dead load of the roof covering material shall not exceed 800N/mm2 of
slope area for roofs other than concrete slabs.
44
(ii) Concrete roof slabs shall not exceed 175mm in thickness if of solid
construction or the equivalent mass if of voided construction.
(d)
(e)
KK4 Materials
KK4.1 Masonry units used in the erection of walling shall comply with the requirements for
compressive strength contained in Table 1.
KK4.2 Mortar used in the erection of a building shall comply with Table 1.
KK4.3 Materials used in any wall of timber framed construction shall be in accordance with
SABS 082.
TABLE 1 STRENGTH REQUIREMENTS FOR MASONRY UNITS AND MORTAR
1
Wall Type
Structural other than
foundation and retaining
walls
Non-structural other than
parapet, balustrade and
free-standing walls
2
Position
Single storey
building
Double storey
building
External
Internal
External or
Internal
External or
Internal
3
4
Minimum average
compressive strength, MPa
Solid units
Hollow units
7.0
3.5
5
Class* of
mortar
required
II
10.5 or
**14.0
7.0
7.0
II
3.5
II
7.0
3.5
III
45
Free-standing
External or internal
10.5
7.0
II
Foundation
Supporting single storey
7.0
3.5
II
Foundation
Supporting double storey
10.5 or 14.0
7.0
II
Parapet
7.0
3.5
II
Balustrade
7.0
3.5
II
Retaining
10.5
7.0
II
* Lime may be added to the mortar mix
SABS 0164 specifies the method of test for the compressive strength of mortar and gives details of the
compressive strength required of the various classes of mortar and appropriate mix proportions used to
attain the required strength.
** See Table 2 Permissible Dimension of masonry Walls in Buildings
Nominal wall
thickness, mm
(b) Where any wall is of timber framed construction, the height and unsupported
length shall not exceed the values given in Table 3.
46
4
5
6
7
Maximum panel length, m
*Max. height,
Max. storey
m
height, m
Supported
Supported
both ends
one end
Structural
114 x 38
400
4.8
2.4
6.0
4.0
114 x 38
600
4.0
2.0
6.0
3.0
76 x 38
450
3.6
1.8
3.0
3.0
Non114 x 38
600
4.8
3.0
4.0
Structural
76 x 38
600
4.2
2.4
3.0
*Maximum height means height to wall plate of highest storey or height to top of gable, if there is a gable.
(c)
2
Stud size,
mm
3
Stud
spacing, mm
KK5.2 Where effective lateral support is to be provided to any masonry wall by means of an
intersecting masonry wall, such intersecting wall shall
(a)
(b)
be constructed of masonry units and mortar of strengths not less than those of
the units and mortar used in the wall it supports;
intersect the supported wall at an included angle of between 600 and 1200
(c)
(d)
(e)
have a height of not less than 80% of the height of the supported wall
have a thickness of not less than 45% of the thickness of the supported wall or
90mm, whichever is greater, such thickness in the case of a cavity wall being
deemed to be the sum of the thickness of the leaves of the wall, and
have a length of not less than one-fifth of the height of the wall panel to be
supported or one-eighth of the greatest distance between such intersecting
wall and any other intersecting wall providing lateral support, whichever is the
greater, and such length shall not include the thickness of the supported wall.
KK5.3 Where effective lateral support is to be provided to any wall by means of an integral
masonry pier, such pier shall
(a)
have a depth perpendicular to the length of any such wall, of three times the
thickness of such wall where such depth includes the thickness of such wall
47
(b)
(c)
have a width along the length of any such wall of twice the thickness of such
wall
be effective only if the height of such pier is at least 80% of the height of any
such wall.
48
KK8.2 Wall ties shall be installed in any cavity wall in an evenly distributed pattern, at a rate
of 2.5 ties per square metre of the face area of such wall where the cavity does not
exceed 75mm and at a rate of 3 ties per square metre of face area where the cavity is
greater than 75mm in width.
KK8.3 Such wall ties shall comply with the requirements contained in SABS 28.
It should be noted that the wall thicknesses, heights etc for the leaves of structural (load
bearing) cavity walls presented in Table 2 of Rule KK5 are based on the assumption that the
entire load at first floor or roof level may be borne by the inner leaf only. This enables the
cavity to remain open at the level of the first floor slab.
The height of any foundation wall not acting as a retaining wall shall not
exceed 1.5m
Where a difference in ground level including backfill exists between the two
sides of any foundation wall, such difference shall not exceed 1.0m
No foundation wall shall have a thickness less than the relevant value given in
Table 4: Provided that such thickness shall not be less than
External
Internal
External
Internal
5
6
7
8
9
Minimum Thickness of the wall, mm
Acting as a retaining wall
Not acting as a retaining wall
*Difference in ground level,
Height, mm
mm
Less than
500 to
750 to
Less
300 to 500 to
1000 to
500
750
1000
than
500
1000
1500
300
140
190
230
140
140
140
190
190
230
90
140
140
190
140
190
230
140
140
140
190
140
190
230
90
140
140
190
190
190
Cavity walls
External
230
190
190
190
190
49
(i)
(ii)
KK10
Balustrade Walls
KK11
Freestanding Walls
KK12
KK13
Roof Anchoring
KK13.1
KK13.2
Such strap of wire shall extend into the wall to a depth of at least 300mm in the
case of a heavy roof (concrete or clay tiles or slate) or at least 600mm in the
case of a sheeted roof except that in the case where the depth of the masonry
or in-situ concrete is less than 300mm or 600mm, respectively, such strap or
wire shall extend as far as possible into such masonry or concrete.
KK13.3
(a) Galvanized steel strap anchors shall be taken up over the top of the rafter
or tie beam, bent down on the other side and nailed down from both sides, or
galvanized roof ties shall be made of two strands of wire which shall be taken
up on either side of the rafter or tie beam, twisted together so as to have no
slack, but so as not to overstrain the wire, and the free ends then nailed down
to prevent untwisting.
50
(b) Any roof truss, rafter or beam shall be fixed to any wall by using one of the
following types of anchors:
(i) Type A: two strands of 4 mm galvanized steel wire
(ii) Type B: 30 mm x 1.2mm galvanized steel strap
(iii) Type C: 30 mm x 1.6 mm galvanized steel strap
(c) For any roof truss, rafter or beam the type of anchor to be used shall be in
accordance with Table 7.
TABLE 7 TYPES OF ANCHOR
1
Roof slope, degrees
Less than 15
15 to 30
Greater than 30
KK13.4
2
Max. roof truss, rafter or
beam spacing, mm
760
1050
1 350
760
1050
1 350
Any
4
Type of anchor required
Light roof
Heavy roof
A, B or C
B or C
C
Type A for all
applications
A, B or C
B or C
C
A, B or C
Note that this regulation gives details of acceptable methods of anchoring roofs to walls in
order to resist upward forces caused by means.
KK14
Water Penetration
KK14.1
KK14.2
KK15
KK15.1
Any wall or sleeper pier of a building shall be provided with a DPC in such
position and to an extent that will protect the wall against rising damp and the
interior of the building against ingress of moisture from abutting ground.
KK15.2
(a)
(b)
(i)
at the level of a top of a
concrete floor slab resting on
the ground; or,
52
(ii)
where applicable, below any ground
floor timber beam or joist.
(c)
In any timber framed wall a DPC shall be installed between the bottom
plate of the wall and any foundation wall or concrete floor slab.
(d)
In the case of any solid masonry wall or timber-framed wall, any DPC
shall extend over the full thickness of such wall.
(e)
53
(ii)
each leaf of such wall shall be
covered by a membrane which
extends across the cavity provided that
the position of the membrane at the
inner leaf is higher than its position at
the outer leaf; and
(iii)
where necessary, weep holes to prevent build-up of water in the cavity wall shall be
provided in the external leaf of every cavity wall, spaced not more than 1m apart, in the
masonry unit course immediately below the DPC contemplated in paragraph (i) or in the
masonry unit course immediately above the membrane contemplated in paragraph (ii).
54
(f)
(g)
(h)
No horizontal DPC shall be installed less than 150mm above the level of
the adjacent finished ground
Transverse joints in the DPC shall be overlapped to a minimum distance
of 150kk and at junctions and corners to a distance equal to the full
thickness of the wall or the leaf; as the case may be.
(i) Where any part of any wall of a room is so situated that the ground
will be in contact therewith, it shall be protected by a vertical waterproof
membrane or by a drained cavity which shall extend below the level of
the floor of such room;
(ii) drainage shall be provided at the base of such wall to prevent water
accumulating there.
It should be noted that Clause KK15 deals mainly with the movement of moisture through
walls which are in contact with the ground or retained earth as a result of capillary action and
does not deal with water entering the tops of parapet walls or penetrating window sills or
reveals or similar situations.
KK16
Behaviour in Fire
Any wall shall comply with the relevant requirements for fire resistance, noncombustibility and, where appropriate, wall lining index set out in rules (fire
requirements) TT2, TT5, TT6, TT7, TT8, TT9, TT10, TT39, TT40, TT41, TT45,
TT49, TT52 and subrules TT18.1 and TT19.1, as the case may be.
KK17
KK17.1
Test Method
The wall shall be thoroughly air-dry before being tested. In the case of a
masonry or similar wall, the inner surface may be lime washed or other means
may be adopted to facilitate the detection of moisture, which has penetrated
through the wall. The portion of the outer surface under test shall then be
continuously sprayed with water in the form of a finely divided spray distributed
over the whole area under test at the rate of 40 50mm depth of water per
hour.
KK17.2
Test Criteria
The test wall shall, in regard to rain penetration, be considered to comply with
the requirements of regulation K2 where
(a)
no moisture has penetrated to the inner surface of the wall within the
relevant minimum test period given
(b)
in the case of a timber framed wall, there is no evidence of water having
been retained within the cavity in the wall.
55
TYPES OF WALLS
Walls can be classified as:
Walls to Framed Buildings ~
1. Wood Stud Walls
2. Metal Stud Walls
3. Wood Post and Beam Framing Walls
4. Steel and Reinforced Conrete Framing Walls
56
57
58
59
2. Concrete Blocks
These are made from Portland cement and aggregates. They are either, dense and
used for sub-structural works etc. or hollow blocks for load bearing and non-load
bearing walls.
3. Stone Masonry
This is usually generally limited to its availability in the construction area. Building
stones include igneous rock such as granite, sedimentary rocks like sandstone and
limestone and metamorphic rocks like marble. Stonework may be coursed by
dressing the stones to an agreeable size of about 200 or 300 mm square,
alternatively, walls may be constructed from stones as they arrive from the quarry.
4. Wall Ties
These are manufactured from galvanized or plastic coated mild steel, copper, zinc,
stainless steel or polypropylene.
The two leaves of a cavity wall
are tied together with 3 wall ties
for every m2 of wall face.
60
TYPES OF BONDS
Bricks and blocks are bonded together to ~
1. Make them strong and also provide adequate distribution of vertical and horizontal
loads over the wall. Un-bonded walls have continuous vertical walls which is prone to
failure due to possible transverse settlement and collapse
2. Minimize movement between bricks by providing lateral stability and resistance to
side thrust, and
3. For appearance/aesthetics.
Bonds are influenced by the ~ situation, function and thickness of the wall. For example,
external walls to buildings usually require a good appearance whilst for walls in inspection
chambers/manholes, strength is of utmost importance.
Brick bond types include ~
a. Stretcher
b. English, and
c. Flemish bonds
61
62
Tooth Bonding
63
MORTAR
Mortars are used in bedding and joining of bricks and blocks. A good mortar should spread
readily and retain its plasticity whilst being laid so as to provide a good bond between bricks
and mortar. The mortars in use include:
1. Lime Mortar: - It was used in the past before the advent of cement. It is mixed at a
ratio of one part of lime to three of sand. Its characteristic is that it develops its
strength slowly. With the discovery of cement, it is hardly ever used in construction.
2. Cement Mortar: - It is mixed at a ratio of 1: 6 (cement and sand) except in extremely
wet situations where a ratio 1: 4 is workable but too strong.
3. Cement-Lime Mortar: - It is the most useful general-purpose mortar because it
combines the best properties of both lime and cement to produce a mortar, which has
good working, water-retention and bonding qualities, and also develops early strength
without an excessively high mature strength.
4. Air-entrained (plasticized) Mortar: - It has the ability to trap air in the mix and is
used as an alternative to lime in improving the working qualities of lean cement and
sand mixes.
5. Mortars containing special cements: - High alumina cement and sulphate resisting
cement are special cements, which may be used where high early strength or
resistance to chemical/sulphate attack is possible.
Types of Arches ~
Simple brick arches can be classified into three ~
a. Flat gauged;
b. Axed; and
c. Rough
64
65
66
Types of Lintels ~
Lintels can also be classified into two main types:
a. Brick Lintels or Soldier Arches: These are superior to wood lintels, which tend to
decay and concrete lintels, which are not aesthetically pleasing.
b. Concrete Lintels: These are subject to forces, which tend to cause bending, inducing
compression at the top and tension at the bottom. Since concrete is strong in
compression and weak in tension, steel reinforcement is introduced to resist the
tensile stresses.
The mix of concrete is normally 1:2:4. When forming the lintels in-situ, timber or steel
formwork depending on the span, is assembled over the opening, reinforcement is
fixed into the formwork and concrete poured. The formwork is struck after the
concrete has hardened sufficiently to take the super-imposed loads and this is usually
after 28 days.
67
68
PARTITION WALLING
Definition
Partition walls can be defined as a wall between rooms, non-load bearing and generally one
floor high. Partitions can be built in a variety of ways, the commonest permanent ones being
of plastered brick or block work but dry construction is possible.
69
Joists running square to the wall with at least 100mm thickness as shown below provide
restraints at floor and ceiling ~
Stability at the ends of the block wall is achieved with metal ties or alternate courses bonded
into the inner leaf as tooth or
block bonds shown in the
following diagrams ~
70
71
WALL FINISHES
A finish is the final surface, which can be ~
Self finished e.g. facing bricks; or
An applied finish such as rendering or wall tiles.
72
Wall Tiling
Materials used ~
Ceramic or mosaic tiles; and
Adhesives ~
o Ready mixed patented (thin bedding) and
o Cement based (thick backing 10mm thick)
73
ROOFS
The roof is the uppermost external envelope of a building that spans the walls. It is a critical
element in the visual image of a building and it can be classified as either being flat or pitch
or according to its structure, or its shape.
Part L of the NBR states the requirements for roof ~
L1 General Requirements
The roof of any building shall be so constructed that it will ~
a. resist any forces to which it is likely to be subjected
b. be durable and waterproof
c. not allow the accumulation of any rain-water upon its surface; and
d. as part of a roof and ceiling assembly provide adequate height in any room
immediately such assembly.
L3 Deemed-to-Satisfy Requirements
The requirements of regulations L1 and L2 shall be deemed to be satisfied where any roof or
roof and ceiling assembly, as the case may be complies with Part L of section 3 of SABS
0400.
The structural design of roofs may be carried out either by calculation or by the
application of empirical rules.
The empirical rules for structural design of roofs stated in LL3 may, however be used
only where the building conforms to the limitations set out in sub rule KK2.2. Which
means that the span of trusses or rafters may not exceed 10 m and the roof covering
74
may not weigh more than 800 N/m2 measured on the slope. However, most common
roof coverings (sheeting, boarding, slates and tiles) fall within this limit.
LL3
LL3.1 The location and dimensions of any part of any roof shall be such that the minimum
height requirements contained in Part C are satisfied.
LL3.2 Roof timbers shall comply with the requirements of the relevant SABS 563, SABS
653, SABS 876, SABS 1089, or SABS 1245
LL3.3 The requirements of sub rules LL3.4 and LL3.4 shall apply only to single or double
pitched Howe-type trusses, with a span not exceeding 10m, supported at heel joints
only and having bays of equal lengths not greater than 1.5 m.
LL5 Waterproofing
LL5.1 For the purpose of runoff of water any roof with a covering of one of the materials
referred to in column 2 of Table 3 shall, subject to the limitations on roof slope
contained in subrule LL3.4, be constructed to a slope not less than the relevant figure
given in column 3 and such covering shall, where applicable, be provided with end
laps not less than the relevant figure given in column 4 or 5 as the case may be.
75
2
Roof Covering
Description
3
Minimum angle of
slope, degrees
5
11
15
17
22
11
15
17
22
26
5
4
5
Minimum end lap, mm
End laps sealed
End laps not
sealed
250
Not permitted
150
250
150
225
150
200
150
150
200
300
175
275
150
250
150
200
150
150
As required by the local authority
LL5.2
Flashing
Flashing shall be used where a roof abuts against a wall or around any projection
through a roof covering and at any other place where it is deemed necessary by the
local authority
(c)
76
Single Roofs
o Flat roofs
o Shed roofs and
o Pitched/Gable Roofs Couple Roof, Close Couple Roof and Collar Roof
Single Roofs ~
c. Gable Roofs ~
It is built from pairs of opposing rafters with central rigidity provided by a ridge board.
They are relatively weak and are limited to small garages, sheds etc. The weakness
77
caused as a result of the deflection of the rafters may be resolved by using ceiling
ties, which also provide support for a ceiling finish.
Gable Roof
ii.
Close Couple Roofs the weakness of the deflection of the rafters in the
couple roof is resolved by using the ceiling
joists as ties.
Advantages
provides insulation,
space for water storage cisterns and
storage space
iii.
tied couple roof but, framed with collars joined across pairs of rafters 1/3rd up
the height of the roof. It extends 1st
floor rooms into the unused roof
space.
Disadvantages :
B.
Double Roofs ~
175 mm x 175 mm Purlins are used at 3 m centres to give intermediate support to 125 mm
x 50 mm rafters in two ways ~
i.
ii.
internal
bearing walls
load
125 mm x 50 mm
ceiling joists also
serve as ties and
ceiling support
79
The earlier trusses include King Post Truss which was used for spans of 6m 9m and
Queen Post Truss which was used for spans of 9 m 12.75 m (when supported).
80
1. Rafters: - These are sloping roof members in a pitched roof, spanning from wall
plate to ridge and which gives the roof its triangular shape. Variously named
according to their position as jack, hip, valley, crown or principle.
o Jack Rafter are the short lengths of rafters, that spans from the wall plate to
the hipped rafter
o Hip Rafter is the pitched roof rafter used where two sloping roof surfaces meet
at an external angle, providing a fixing point for the jack rafter and transferring
their load to the wall plate.
81
o Valley Rafter is the rafter used where two pitched roofs meet at an internal
angle. It provides fixing for the Jack rafters, supports the valley gutter and
transfer loads to the wall.
o Crown or Principle Rafter is the central common rafter of a hipped end roof.
2. Wall Plate is a horizontal piece of timber fixed to the top of walls in order to
distribute load from and to
provide a bearing and fixing
point for joists and rafters.
The sawn softwood wall plate,
usually 100 mm x 75 mm in
section is laid on its 100 mm
face.
A birdsmouth cut is made in
the top of each rafter to fit
closely round the wall plate.
3. Ridge Board: This is a horizontal piece of timber at the apex of a pitched roof,
which provides a bearing and fixing points for the top of rafters.
The ridge board is one continuous
length of hardwood, usually 32 mm
thick.
The depth of the ridge board is
determined by the depth of the splay cut
ends of rafters that must bear fully on
each side of the board.
82
5. Fascia Board: This is a deep board fixed to the end of rafters at the eaves of a
roof.
6. A Verge is where the roof covering
overhangs the gable end. It is the
termination of a pitched roof at the gable
end
7. A Barge Board is the continuation of
the fascia board around the sloping verge
of a pitched roof
8. Purlin is a beam/horizontal roof member
used in a double roof to provide
83
A. Timber
Timber is the most common material used in roof construction and can be used in the
construction of single, double, trussed or framed roofs. Timber used must be of structural
quality (see NBR) and must be planed on all faces to ensure accuracy and efficiency of
location. Pitched roofs can also be constructed from pre-fabricated timber trusses.
Timber Joints ~
The wall plates should be butt jointed together and at intersections lap jointed as shown
below ~
Purlins could also butt jointed and battened at the sides one to the other, the joint can also
be mitred and kept in position with a cleat/wedge as shown below ~
84
B. Concrete
Reinforced concrete roofs are constructed in a similar manner to reinforced concrete floors
and may be solid, hollow pot or self-centering. Concrete roof slabs are often reinforced with
steel bars in both directions, with larger bars following the span. It should also bear on walls
of at least 100 mm thick (NBR).
Pre-cast concrete is widely used in the construction of single roofs either flat or shed roofs.
Pre-cast concrete planks are placed on top of solid block or continuous bond beams or steel
or concrete beam support as shown below ~
Lightweight pre-cast concrete which may be used for sloping roofs is supported by light steel
framing or trusses. Steel angle stops are required to absorb the downward thrust of planks
and prevent the pre-cast concrete planks from slipping, especially for slopes above 4 in 12.
The slab is generally finished level and the fall obtained with a screed. It is also required that
the slab is waterproofed (NBR).
C. Steel
The general principles of design for Steel Roof Structures are similar to those adopted for
timber trusses, with members given direct support at specific points and those in
compression kept as short as possible. Steel roof trusses are very impotant for use in
industrial, commercial (warehouses) and agricultural buildings.
Steel roof trusses are made up of members of small section, can be used for spans which
would be beyond the economic capacity of timber in character and quality.
85
1. Slates
Slates are hard, fine-grained naturally occuring material. Clayey stone slate is as a result of
tremendous lateral pressure and heat on clay. The slates may be nailed to ~
o Battens fixed direct to rafters,
o Boarding fixed to rafters or
o Battens on boarding
The slates are arranged to bond so that side joints in one course are over the centre of
slates in the course below.
Good slates are hard, tough and durable, of rough texture, would not split when holed or
dressed, practically non-absorbent and of a satisfactory colour.
Advantages ~
a. These are the lightest form of roof tiling. Hence,
the roof structure of rafters and purlins can be
lighter
b. It permits a flatter slope of roof because it can be
obtained in larger sizes
Disadvantages ~
a. It is difficult to replace
b. It is not adaptable to complicated designs.
86
Three layers of felt bonded with hot bitumen are essential for all except temporary buildings.
Vapour barriers which include asphalt saturated felt is first placed on the roof deck. Roofing
felts applied with asphalt or tar pitch surface bitumen is then placed on top of the vapour
barrier. Finally, white granite stones are used to finish the surface of the felt for appearance
also, the stones may aid in stiffening the membrane and resisting wind blow off.
Lead is ductile and flexible, easily cut and shaped, highly resistant to corrosion and has a
long life. It is however of low strength, high cost, very heavy in weight, creeps on all but the
flattesst slopes, can be attacked by damp cement mortar, and is supplied in smallish sheets
entailing many expensive joints. A lead flat is laid on roof boarding which are laid on roof
joists which bridge the shortest span.
87
The sheets are normally about 2400 mm x 900 mm and should have a minimum
thickness of 14 zinc guage.
Advantage: It may be used as a cheaper alternative to other metal roof covring, it does
not creep, it is light weight and reasonably ductile.
Disadvantage: It corrodes in coastal and heavy industrialized areas and has a shorter
life span.
6. Asbestos Sheet
It is made of fiberised asbestos and Portland cement; the natural colour is Grey but, it is
obtainable in other colours. Sheets are normally corrugated about 50 mm deep in various
lengths up to 4.60 m. They are generally laid with an end lap of 150 mm and the side lap
varies with the design (see NBR). Asbestos cement sheets are fixed to wood purlins with
galvanized drive screws or to steel angle purlins with hook bolts.
Advantages: It is incombustible, light weight and corrosion resistant.
Disadvantages: Unattractive in appearance, the surface softens with weathering, the
materials become brittle with age and is unlikely to have a life span exceeding 30 years.
Asbestos sheet is hardly used nowadays due to the health conditions such as cancer that
results from its prolonged use.
7. Thatch Roofs
It is a roof covering of reed, straw or palm fronds laced with flexible willow sticks such as
those used for basket weaving. It provides a most
attractive finish to steep roofs of at least 450 and preferably
550 inclination. Several are twisted into a cable for tying
reeds onto rafters in thatching.
Reed is the most durable thatching material with a life of 50
to 75 years, while the life of a good straw or palm frond
roof is not more than 20 years. However, about every
seven years, thatch must be cleaned to lengthen its life.
Reed is laid about 300mm thick and it is best
confined to simple roofs. Rafters spaced at
about 400 mm centres support battens (25
mm x 19 mm at 225 mm centres) which carry
the reed.
Advantage: An attractive finish to steep roofs
and high thermal insulation
Disadvantage:
It
requires
regular
mainteneance; short life; unpleasantness of
thatching; the difficulty of finding experienced
thatchers; high cost; liable to attack from birds and vermins; and prone to fire damage than
other types of roof covering materials. Its susceptibility to fire can now be reduced by
soaking the reed or straw in a fire resisting solution instead of in water before laying it.
88
STAIRWAY
This is defined as a set of steps or flight leading from one floor to another, giving floor-tofloor access including any landing, balustrade or handrail. Each continuous set of steps in
between floors or landings is termed a flight of stairs. The space in within which a flight of
stairs was built now used to mean the flight itself was formally called a staircase. Internal
stairways are now often of reinforced concrete or timber; escape stairs are fabricated with
steel, cast iron or reinforced concrete.
A stairway must be designed to provide a safe, serviceable and commodious means of
access from one floor to another of a building. The National Building Regulations prescribe
certain minimum requirements for stairs design and construction.
The National Building Regulations in Part M: Stairways stipulates the requirements for
stairway construction as follows ~
M1 General requirements
1. Any stairway, including any wall, screen, railing or balustrade to such stairway, shall
be capable of safely sustaining any loads to which it is likely to be subjected and shall
permit safe movement of persons from floor to floor.
2. Any such stairway shall have dimensions appropriate to its use.
M2 Fire Requirements
A stairway contemplated in regulations M1 shall comply with the relevant requirements in
Part T of these regulations.
M3 Deemed-to-Satisfy Requirements
The requirements of regulations M1 and M2 shall be deemed to be satisfied where the
design of any stairway complies with Part M of section 3 of SABS 0400.
MM2
Dimensional Requirements
MM2.1
The clear headroom at any point of any stairway shall not be less than 2.1m
measured vertically from the pitch line, and the clear width of any stairway not
forming part of any emergency route shall not be less than 750mm.
89
MM2.2
(a)
(b)
(c)
Any landing serving two flights in the same straight line shall ~
(i)
have a length of not less than 900 mm; and
(ii)
have a width of not less than that of such flights
No flight of stairs shall have a vertical rise greater than 3 m
between landings
No door shall open onto a stairway unless such door opens onto
a landing and the width of such landing shall not be less than that
of such door.
MM2.3
MM2.4
The going and width of any tread shall not be less than 250 mm: Provided that
where the stairway does not have solid risers, each tread shall overlap the next
lower tread by not less than 25 mm
MM2.5
The variation in the dimension of the risers and the going of the treads in any
one flight shall not be more than 6mm: Provided that this requirement shall not
be construed as prohibiting the use of tapered treads in the same flight as
treads that are not tapered.
MM2.6
MM2.7
MM3
MM3.1
(a)
Any flight of steps which contains more than three risers shall have
protection on each side provided by a secure wall, screen, railing or
balustrade which shall not be more than 1 m high and so erected that
any such wall, screen, railing or balustrade in any occupancy classified
E2, E3, H1, H2 or H3 shall not have any opening that permits the
passage of a 100 mm diameter ball: Provided that such protection in
any occupancy not being classified E2, E3, H1, H2, H3 or H4, shall
consist of at least a handrail, one rail not more than 150 mm above the
90
stair nosing, and one other rail or other form of protection in between
such rail and handrail.
(b)
(i) Any flight of steps which contains more than 5 risers shall be provided
with at least one continuous handrail extending the full length of such
flight: Provided that this requirement shall not apply to any building
classified H4, or within individual dwelling units in an occupancy
classified H3.
(ii) Such handrail shall be securely fixed to such wall, screen, railing or
balustrade at a height of not less than 850 mm and not more than 1 m
measured vertically from the pitch line to the upper surface of the
handrail.
(iii) Such handrail shall be of such design and be so fixed that there
shall be no obstructions on, above or near to it, which may obstruct the
movement of any hand moving along it.
(c)
(i) Subject to paragraph b (i), any flight which is less than 1.1 m wide
shall have a handrail on at least one side and where the width of any
flight is greater than 1.1 m, handrails shall be provided on both sides of
such flight.
(ii) such handrails shall comply with the requirements contained in
paragraphs b (ii) and b (iii).
It can be inferred from the rules stated in Sub rule MM3.1 (b) that ~
a. If the flight has fewer than four risers, no balustrade, screen etc and handrail are
required.
b. If it has four or five risers, a balustrade, screen etc is required but no handrail is
required.
c. If it has six or more risers, both a balustrade, screen etc and a handrail are required.
MM4
Fire Requirements
Any stairway shall comply with the requirements contained in rules TT5, TT7,
TT19, TT20, TT21, TT22, TT23, TT24, TT25, TT26 and TT27, as the case may
be.
91
92
13. Tapered Tread: A tread, which has a greater width at one side than at the other
and a going, which changes at a constant rate throughout its length. Tapered treads
may not taper to a point.
14. Winder: A tread, which tapers to a point.
TYPES OF STAIRWAYS
There are various types of stairways depending on the layout. However, the most common
are the following ~
93
94
95
96
97
E. Spiral Stairs
References
Barry (2001) Construction of Buildings, Vol. 1-4, Wiley: New York
Brett, P. (1997) An Illustrated Dictionary of Building: A Reference Guide for Practitioners and Students, 2
Elsevier Butterworth Heinemann, Oxford
nd
Ed.,
Chappell, D., Cowlin, M., and Dunn, M. (2009) Building Law Encyclopaedia, Wiley-Blackwell, Chichester
th
Chudley, R., and Greeno, R. (2006) Building Construction Handbook, 6 Ed., Elsevier Butterworth-Heinemann,
Oxford
Freeman, C. J. (1990) The National Building Regulations: An Explanatory Handbook; Juta & Co Ltd
98
Grobellar, A. (1992) Building Construction Graphics Standards, Anglo-Rand Publications, South Africa
Kohler, T. H. (1984) A Technical Guide to Good House Construction, National building Research Institute of the
CSIR in collaboration with the Association of Building Societies of South Africa
99