Programming S&C Overcurrent Control
Programming S&C Overcurrent Control
Page
Introduction
Qualified Persons. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Read this Instruction Sheet. . . . . . . . . . . . . . . . . . . . . . .
Retain this Instruction Sheet. . . . . . . . . . . . . . . . . . . . . .
Warranty. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
3
3
4
Description
General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power and Sensing. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Time-Current Characteristics . . . . . . . . . . . . . . . . . . . . .
Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Event Recording. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Self Testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Single-Pole or Three-Pole Tripping. . . . . . . . . . . . . . . . .
Page
Self-Test Report
2
2
2
2
Safety Information
Understanding Safety-Alert Messages. . . . . . . . . . . . . .
Following Safety Instructions . . . . . . . . . . . . . . . . . . . . .
Replacement Instructions and Labels. . . . . . . . . . . . . . .
Location of Safety Labels. . . . . . . . . . . . . . . . . . . . . . . .
Section
5
5
6
6
6
7
7
7
Specifications
Port Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CT Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Steady State Accuracy. . . . . . . . . . . . . . . . . . . . . . . . .
Time-Overcurrent Pickup Accuracy. . . . . . . . . . . . . . . .
Time-Overcurrent Response. . . . . . . . . . . . . . . . . . . . .
Instantaneous Pickup Accuracy . . . . . . . . . . . . . . . . . .
Instantaneous Response . . . . . . . . . . . . . . . . . . . . . . .
Definite-Time Response. . . . . . . . . . . . . . . . . . . . . . . .
Appendix A
External Connections. . . . . . . . . . . . . . . . . . . . . . . . . . 25
Appendix B
Communication Parameters. . . . . . . . . . . . . . . . . . . . . 29
Appendix C
Using Terminal Emulator Programs. . . . . . . . . . . . . . . . 30
HyperTerminal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
AcSELerator QuickSet 5030. . . . . . . . . . . . . . . . . . 31
Appendix D
Coordination. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Appendix E
Overcurrent Control Settings. . . . . . . . . . . . . . . . . . . . . 37
Programming
Factory-Default Settings. . . . . . . . . . . . . . . . . . . . . . . . 14
Fault Interrupters 1 and 2. . . . . . . . . . . . . . . . . . . . . . . 14
Passwords. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
View Menu 1 or 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Configure Menu 1 or 2 . . . . . . . . . . . . . . . . . . . . . . . . . 17
Change User Password . . . . . . . . . . . . . . . . . . . . . . . . 19
Group Configure Menu. . . . . . . . . . . . . . . . . . . . . . . . . 19
Test Trip Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
June 1, 2015
S&C Electric Company 2000-2015, all rights reserved
24
24
24
24
24
24
24
24
Introduction
Qualified Persons
WARNING
The equipment covered by this publication must be operated and maintained by qualified
persons who understand any hazards involved and are thoroughly trained in the operation
and maintenance of electronic control devices which are used in conjunction with power distribution equipment. These instructions are intended only for such qualified persons. They
are not intended to be a substitute for adequate training and experience in safety procedures for this type of equipment.
Read this
Instruction Sheet
Thoroughly and carefully read this instruction sheet before programming, operating,
or maintaining your S&C Overcurrent Control. Familiarize yourself with the safety
information on page 3. The latest version of this instruction sheet is available online in
PDF format at sandc.com/Support/Product-Literature.asp
Retain this
Instruction Sheet
This instruction sheet is a permanent part of your S&C Vista Underground Distribu
tion Switchgear. Designate a location where you can easily retrieve and refer to this
publication.
Warranty
Safety Information
Understanding
Safety-Alert
Messages
There are several types of safety-alert messages which may appear throughout this
instruction sheet as well as on labels attached to the S&C Overcurrent Control. Famil
iarize yourself with these types of messages and the importance of the various signal
words, as explained below.
DANGER
DANGER identifies the most serious and immediate hazards which will likely
result in serious personal injury or death if instructions, including recommended pre
cautions, are not followed.
WARNING
WARNING identifies hazards or unsafe practices which can result in serious personal injury or death if instructions, including recommended precautions, are
not followed.
CAUTION
CAUTION identifies hazards or unsafe practices which can result in minor
personal injury or product or property damage if instructions, including recommended
precautions, are not followed.
NOTICE
NOTICE identifies important procedures or requirements that, if not followed, can result in
product or property damage if instructions are not followed.
Following Safety
Instructions
If you do not understand any portion of this instruction sheet and need assistance,
con
tact your nearest S&C Sales Office or S&C Authorized Distributor. Their telephone numbers are listed on S&Cs website sandc.com Or call S&C Headquarters
at (773) 338-1000; in Canada, call S&C Electric Canada Ltd. at (416) 249-9171.
NOTICE
Thoroughly and carefully read this
instruction sheet before programming
your S&C Overcurrent Control.
Replacement
Instructions
and Labels
If you need additional copies of this instruction sheet, contact your nearest S&C Sales
Office, S&C Headquarters, or S&C Electric Canada Ltd.
It is important that any missing, damaged, or faded labels on the equipment be
replaced immediately. Replacement labels are available by contacting your nearest S&C
Sales Office, S&C Headquarters, or S&C Electric Canada Ltd.
Safety Information
Location of Safety Labels
WARNING
Hazardous voltage inside can shock, burn,
or cause death.
Electronics module
Enclosure for overcurrent control with cover removed to show electronics module.
Burden-board module
DANGER
Never disconnect current transformer
secondary circuits without de-energizing
the switchgear. Hazardous voltage will
shock, burn, or cause death.
Description
General
The following instructions are for field and shop programming of the S&C Overcurrent
Control. This microprocessor-based control is designed for use on S&C Vista Under
ground Distribution Switchgear to provide fault detection and operation of the resettable,
vacuum fault interrupters. Each overcurrent control operates up to six single-pole fault
interrupters or two three-pole fault interrupters. The control is housed in an enclosure
which is mounted on the operation side of the switchgear. For UnderCover and Wet-VaultMounted Style Vista units, the enclosure is fully submersible. The electronics module is
removable for programming in the shop.
Programming
A personal computer furnished by the user is to be used to input settings, review set
tings, and interrogate the event recorder. The software for programming the overcurrent
control is contained within the control. Two data ports are providedone on the
enclosure for programming in the field, and another on the electronics module for
programming in the shop. Adapter cables are available from S&C (see Instruction Sheet
681-515A) to connect the computer to the control.
An external power source is required for programming and interrogating the control.
A source of dc power is available from the mouse or USB port on the personal computer.
The adapter cables contain connectors for data and power to utilize the power available
from the computer.
Description
Power and Sensing
Current transformers are provided inside the switchgear tank for each set of three singlepole fault interrupters or each three-pole fault interrupter. These current transformers
provide primary current sensing ranging from 50 to 12,500 amperes (100 to 25,000 amperes
for 900-ampere and 1200-ampere models). Vista UDS rated above 12.5 kA short circuit
will respond to fault currents above 12.5 kA, but the event log will only record that a fault
above 12.5 kA has occurred (or 25 kA for 900-ampere and 1200-ampere models). The
overcurrent control is capable of sensing and responding to both phase overcurrents and
ground overcurrents.
The power derived from the current transformers is used to operate the control and
to charge the trip capacitors which discharge into magnetic latching solenoids to trip the
fault interrupters during a fault. No external power is required for operation of the control
in the field.
Time-Current
Characteristics
Settings
(See Appendix E for a
complete list of settings)
The definite-time delay setting will override the instantaneous setting when the definite-time delay setting is activated before the instantaneous
setting.
Description
Event Recording
The overcurrent control features an internal event recorder that captures the last
twelve fault operations for each fault interrupter. The event log indicates which poles
have experienced a fault, the magnitude of the fault, and whether or not a ground
overcurrent was involved. This information can be accessed via a personal computer
connected to the data port of the control.
Self Testing
Single-Pole or
Three-Pole Tripping
Data port
DANGER
Never disconnect CT secondary circuits without de-energizing the switchgear. Hazardous
voltage will shock, burn, or cause death.
CAUTION
When the electronics module is removed from its enclosure, the associated fault interrupters will not provide fault protection
Removing the
Electronics Module
CAUTION
ALWAYS disconnect the trip connectors from the electronics module before removing the
module from the base plate. Failure to follow this precaution may result in the unexpected operation of a fault interrupter.
Electronics module
2. Disconnect the two trip connectors from the front of the electronics module.
4. Grasp the electronics module by the handle and lift it upward slightly away from
the base plate. This raises the stand-off attached to the inside of the cover of the
electronics module, allowing the CT shorting clip to make its connection to the
power CT secondaries and short circuit the secondaries. After the CT secondar
ies are short circuited, the connection between the electronics module and the
burden-board module breaks.
Blind-mate
connector on
main board
Electronics module
Stand off
Blind-mate
connector
on burden
board
Shorting
clip
Burden-board module
5. Slide the electronics module a short distance away from the rear wall of the base
plate, lift the module up, and remove it from the base plate.
Electronics module
Data port
1. Hold the electronics module by the handle at the front of the module.
2. Place the rear of the electronics module onto the base plate of the burden-board module
while holding the front of the electronics module away from the base plate at a slight
angle. Slide the electronics module back until it engages the rear wall of the base plate.
Two slots at the back of the electronics module will engage with the tabs in the base
plate which hold the electronics module in place.
3. Lower the front of the electronics module onto the base plate. This connects the elec
tronics module to the burden-board module. It also lowers the stand-off which pushes
the CT shorting clip away from the burden board removing the short circuit from the
power CT secondaries. The control will power up if sufficient current is flowing through
the Vista switchgear.
Blind-mate connectors on main board and burden board
Electronics module
Stand off
Shorting
clip
Burden board
Base plate
5. Connect the two trip connectors to the front of the electronics module. The trip
connectors are keyed and cannot be swapped or installed incorrectly.
6. Place the cover on the controls enclosure and tighten the captive screws or bolts
that secure the cover in place.
Four captive screws secure cover to Pad-Mounted or Dry-VaultMounted Style enclosures; 22 bolts secure cover to submersible
enclosures (tightened to 15 foot-pounds)
Programming
Factory-Default
Settings
The overcurrent control is provided with the factory-default settings shown here.
Fault Interrupters 1
and 2
Passwords
Factory-Default Passwords
Type of Password
User
Group Configure
Password
6601
4731
Two passwordsthe User and Group Configure Passwordscontrol access to the sensi
tive areas of the menu system. The User Password must be entered to change control
settings, test trip the solenoids, and change the User Password.
The Group Configure Password is required to change the global settings, download
firmware, and change the Group Configure Password.
Passwords must contain four numeric characters. Each control is provided with
factory- default passwords. The User and Group Configure Passwords can be changed, but
the default passwords will always allow access.
Main Menu
1. To begin communications, open the terminal emulator program and press <ENTER>
(refer to Appendix C for additional instructions regarding terminal emulation). The
control will respond with the Main Menu and = prompt.
2. Select the desired option from the Main Menu and input the corresponding number
after the = prompt. Press <ENTER>. (Option 1 is shown as an example.)
Main Menu: <select number>
1. View Menu 1
2. Configure Menu 1
3. View Menu 2
4. Configure Menu 2
5. Change User Password
6. Switch to Group Configure
7. Test Trip Menu
=1
INTERRUPTER 1
INTERRUPTER 1
INTERRUPTER 2
INTERRUPTER 2
Programming
View Menu 1 or 2
The View Menu allows review of the settings and status of the control. (The View Menu
shown at right is for Fault Interrupter 1.)
1. Select the desired option from the View Menu and input the corresponding number
after the > prompt. Press <ENTER>. (Option 1 is shown as an example.)
2. Refer to the appropriate subsection below for further information on the selected option.
3. To return to the Main Menu, input 9 after the > prompt and press <ENTER>.
View Menu INTERRUPTER 1: <select number>
1. View event report (last 12 events)
2. View load current
3. View relay settings
4. View relay self-test
9. Switch to Main Menu
= View FI 1 > 1
Elapsed
**Time**
(Seconds)
2040
1829
1908
0.019
24
1926
18
1908
2010
22
18
1992
1
2
3
X
X
***** Amperes*****
Programming
3. Target the ground faulted pole if ground current is greater than the ground pickup
setting or if ground current is greater than or equal to 50A and greater than 10% of the
maximum phase current.
4. If only one target is declared from the previous logic, target the faulted pole (of the
remaining three with the highest current.
The primary RMS magnitude of each pole and ground current. Current greater than
14,500 ampere will be reported as >14500 (>29000 for 900-ampere and 1200-ampere
models).
The event report is reset when the fault interrupter settings are changed and saved.
50
49
48
GROUND
NA
Curve Selection
200E
NA
N/A
N/A
N/A
N/A
Trip Mode
Frequency
60
Programming
4. View Relay Self-Test
The View Relay Self-Test option allows viewing of the self-test status report for the
selected fault interrupter. This report includes the status of the trip capacitors, supply
voltage, RAM, integrity of the data, CR-RAM, EEPROM, and voltage control. See SELFTEST REPORT on page 23 for more information.
INTERRUPTER 1
FID = S&C1000R100970317
SELF TESTS
W = Warn F = Fail
Pole #
Trip Caps
OK
OK
OK
Supply
+ 5V
+ 12V
Voltage
4.99
12.26
RAM
OK
FLASH
CR_RAM
EEPROM
V_CONTROL
OK
OK
OK
OK
Configure Menu 1 or 2
The Configure Menu allows review and changes to the time-current characteristic curve
settings for the selected fault interrupter. (The Configure Menu shown at right is for Fault
Interrupter 1.)
1. Select the desired option from the Configure Menu and input the corresponding
number after the > prompt. Press <ENTER>. (Option 1 is shown as an example.)
2. Refer to the appropriate subsection below for further information on the selected
option.
3. To return to the Main Menu, input 9 after the > prompt and press <ENTER>.
Configure Menu INTERRUPTER 1: <select number>
1. Change relay settings
2. View relay settings
9. Switch to Main Menu
= Config FI 1 > 1
Programming
1. Change Relay Settings
The Change Relay Settings option allows changes to the time-current characteristic
curve settings for the selected fault interrupter. There is a prompt for the input for each
setting.
1. After each prompt, enter the new setting and press <ENTER>. The available choices are
shown in parenthesis. To retain the previous selection shown after the =, press <ENTER>.
2. After all of the settings have been entered, the new settings will be displayed in a table. Enter
Y for yes or N for no after the Save Changes (Y/N)? prompt. A confirmation of the choice
will be shown and the settings will be displayed. Note that when new settings are saved, the
event report discussed on page 15 will be reset.
PHASE
GROUND
TAP
TAP
200
200
32
32
GROUND
TAP
TAP
200
200
32
32
Programming
2. View Relay Settings
The View Relay Settings option allows viewing of the current control settings for the
selected fault interrupter. The trip mode and frequency settings are included.
INTERRUPTER 1
PHASE
GROUND
TAP
TAP
200
200
32
32
Trip Mode
Frequency
60
Change User
Password
The Change User Password option allows changing of the User Password. After the new
password has been entered, the control will return to the Main Menu.
1. Enter the current User Password after the first prompt.
2. Enter the new password after the second prompt. The password must have four
numeric characters.
3. To confirm the new password, re-enter it after the third prompt.
USER PASSWORD: ? *****
CHANGE USER PASSWORD
Enter new password (four digits, blank for no change) *****
Re-enter new password *****
The Group Configure option allows viewing and changing of the global settings, changing
of the Group Configure Password, and downloading of firmware.
1. Select the desired option from the Group Configure Menu and input the corresponding
number after the > prompt. Press <ENTER>. (Option 1 is shown as an e xample.)
2. Refer to the appropriate subsection below for further information on the selected
option.
3. To return to the Main Menu, input 9 after the > prompt and press <ENTER>.
Group Configure Menu: <select number>
1. Change global settings
2. View global settings
3. Change Group Configure Password
4. Download Firmware
9. Switch to Main Menu
=Group Config > 1
Programming
1. Change Global Settings
The Change Global Settings option allows changing of the fault interrupter ID, trip mode,
and frequency.
CAUTION
Do not program three-pole fault interrupters to operate in single-pole trip mode. Single-pole
tripping is not possible with three-pole fault interrupters.
1. After each prompt, enter the new setting and press <ENTER>. The available choices
are shown in parenthesis. To retain the previous selection shown after the =, press
<ENTER>.
2. After all of the settings have been entered, the new settings will be displayed in a table.
Enter Y for yes or N for no after the Save Changes (Y/N)? prompt. A confirmation
of the choice will be shown and the settings will be displayed.
<Press Q to return to menu>
ID for Interrupter 1 (20 characters) = INTERRUPTER 1
?interrupter pole 1
ID for Interrupter 2 (20 characters) = INTERRUPTER 2
?interrupter pole 2
1-pole or 3-pole trip mode for Interrupter 1 (1,3) = 1 ?3
1-pole or 3-pole trip mode for interrupter 2 (1, 3) = 1 ?3
50 Hz or 60 Hz Operation (50, 60) = 60 ?
ID Interrupter 1
INTERRUPTER POLE 1
ID Interrupter 2
INTERRUPTER POLE 2
Nominal Frequency
60
INTERRUPTER 1
INTERRUPTER 2
Nominal Frequency
60
INTERRUPTER 1
ID Interrupter 2
INTERRUPTER 2
Nominal Frequency
60
Programming
3. Change Group Configure Password
The Change Group Configure Password allows changing of the Group Configure Pass
word. After the new password has been entered, the control will return to the Group
Configure Menu.
1. Enter the current Group Configure Password after the first prompt.
2. Enter the new password after the second prompt. The password must have four numeric
characters.
3. To confirm the new password, re-enter it after the third prompt.
CHANGE GROUP PASSWORD
Enter new password (four digits, blank for no change) ****
Re-enter new password ****
4. Download Firmware
The Download Firmware option allows the control to be disabled for downloading and
uploading of firmware. Refer to the nearest S&C Sales Office for instructions.
The Test Trip Menu option allows test tripping of the fault interrupters; all three poles or
single poles.
1. Select the desired option from the Test Trip Menu and input the corresponding num
ber after the = prompt. Press <ENTER>. The selected pole(s) will trip. (Option 1
is shown as an example.)
2. To return to the Main Menu, input 9 after the = prompt and press <ENTER>.
Test Trip Menu
1. Trip Mode 3 FI1 All Poles
INTERRUPTER 1
INTERRUPTER 2
INTERRUPTER 1
INTERRUPTER 1
INTERRUPTER 1
INTERRUPTER 2
INTERRUPTER 2
INTERRUPTER 2
Self-Test Report
Viewing of Self-Test
Report
The overcurrent control tests vital subsystems upon power up and periodically thereafter
to ensure proper operation. To view the self-test report, select View Relay Self-Test from
the View Menu for the selected fault interrupter.
INTERRUPTER 1
FID=S&C1000R100970317
SELF TESTS
W = Warn F = Fail
Pole #
Trip Caps
OK
OK
OK
Supply
+ 5V + 12V
Voltage
4.99
12.26
RAM
FLASH
CR_RAM
EEPROM
V_CONTROL
OK
OK
OK
OK
OK
Response to Self-Test
Failure
The following defines each of the self tests and the controls response to a self-test
failure. The control displays the above screen when none of the self-tests have failed.
Actual values may vary.
FID
The FID indicates the model, firmware version, and firmware date code.
Trip Caps
The status of the trip capacitors is reported for each fault-interrupter pole. If the trip
capacitors are not charged to at least 50 volts, a low condition is reported. The control
cannot issue a trip until the capacitors are fully charged. The capacitors charge from
either the CTs or port power. If the control indicates low when no trip condition exists,
the voltage supplied to the communication port is less than 4 volts, or the control is defec
tive and should be replaced.
Supply Voltage
The control periodically checks the voltage of each power supply and compares the
results with failure thresholds. The self-test report displays the measured values.
Protection is disabled and an F is placed next to the displayed value if it falls outside the
failure threshold. This self-test also detects gross A/D converter failures.
Threshold Values
Supply
Low Fail
High Fail
+ 5V
+ 12V
4.5
11.00
5.35
14.00
Self-Test Report
RAM
The RAM self-test verifies proper operation of the read/write memory. This test periodi
cally performs a nondestructive write/read to successive blocks of RAM to determine if a
RAM failure has occurred. A failure occurs if the expected data is not read back from the
RAM. In this case, protection is disabled and fail is reported.
Flash
The Flash self-test verifies the integrity of the data contained in system program Flash. If
Flash is corrupted, protection is disabled and fail is reported.
CR-RAM
Areas of RAM containing constant data that have been copied from EEPROM are periodi
cally examined to verify their integrity. If this critical RAM has been corrupted, protection
is disabled and fail is reported.
EEPROM
The EEPROM self-test verifies the integrity of data contained in EEPROM. EEPROM selftest failures are handled differently because self-test failures and control settings are both
stored in EEPROM. Following an EEPROM self-test failure, factory-default settings are
restored and protection is enabled. The message Relay enabled using default settings is
displayed at the top of each menu. If the EEPROM failure persists (i.e., if default settings
cannot be stored in EEPROM), a self-test failure is also generated.
Voltage Control
This logic monitors the power shunt circuitry in the power supply. On power up, each
phase magnitude is averaged for 0.5 seconds. If the average is greater than or equal to 50
amperes and the associated trip capacitor is not charged, the CT power circuit is defec
tive and a failure is declared.
Self-Test Failures
and Warnings
The following screen is an example of a self-test failure. The +5-volt power supply voltage
is flagged with an F, and Relay Disabled appears above each menu.
The control records self-test failures in EEPROM and remains disabled until power
is removed and restored. When power is restored, the self-test is repeated. If no failure
occurs, the failure indication changes to warnor W in the case of a power supply
and protection is enabled.
INTERRUPTER 1
FID=S&C1000R100970317
SELF TESTS
W = Warn F = Fail
Pole #
Trip Caps
OK
OK
OK
Supply
+ 5V + 12V
Voltage
5.35F 12.12
RAM
FLASH
CR_RAM
EEPROM
V_CONTROL
OK
OK
OK
OK
OK
Specifications
Port Power
CT Power
45 A RMS
90 A RMS
720 A continuous
12 kA for 1 s
25 kA for 0.25 s
1440 A continuous
25 kA for 1 s
50 kA for 0.25 s
14.5 kA
29 kA
CT:
Burden Board:
Main Board:
0.2% typical
0.3% typical
0.2% typical
Time-Overcurrent
Pickup Accuracy
Time-Overcurrent
Response
Instantaneous Pickup
Accuracy
600-A models:
900-A and 1200-A models:
Instantaneous
Response
Definite-Time
Response
0 to +8 ms
0 to 10%
0 to 10% 12 A
Appendix A
External Connections
This section describes each of the external connections to the control. Included in
the fol
lowing tables are terminal numbers, terminal names, mating-connector
part numbers (where applicable), and the pin-out of the data port connectors.
Terminal numbers are identified by labels on the electronics module or terminal block.
Electronics module
Trip outputs
Trip Outputs
Terminal Number (1,2)
Pole
1, 2
3, 4
5, 6
7, 8
9, 10
11, 12
Trips
Phoenix 1783999
Phoenix 1876194
are polarized.
Appendix A
Burden-board
module
Signal
inputs
Burden
board
Power
inputs
Signal Inputs
TerminalNumber
Signal Pole
13
14
15
16
17
18
19
20
Power Inputs
TerminalNumber
Power Pole
21
22
23
24
25
26
27
28
Appendix A
Electronics
module
Function
Power In
No Connection
Signal Reference
No Connection
No Connection
No Connection
Power Return
Appendix A
Overcurrent-control enclosure
(Pad-Mounted and Dry-VaultMounted Style shown)
Data port
1
5
4
FACE
VIEW
Function
Power Return
Power In
Signal Reference
Appendix B
Communication
Parameters
NOTICE
Before using any Microsoft terminal emulator program, disable any PDA synchronizing
software programs. Failure to do so may cause communication problems when connecting
to the Vista Overcurrent Control.
HyperTerminal
Parameter
Setting
Baud Rate
9600
Parity
None
Data Bits
Stop Bits
Flow Control
XON/XOFF
The overcurrent control does not use hardware flow control (RTS, CTS).
Setting
Device
Data Speed
9600
Data Bits
Stop Bits
Parity
None
RTS/CTS
OFF
DRT
ON
RST
ON
Specify the assigned COM # from the drop down list. The assigned COM # can be found under Control Panel,
System, Hardware, Device Manager. Expand the Ports menu. The COM # will be adjacent to SEL to UART
Bridge Controller.
Appendix C
NOTICE
Due to the nature of the internal connections of some secondary injection style relay test
sets, a ground loop condition can develop when both the test set and a PC are connected
to an ac wall outlet. The ground loop condition may damage the PC data port. Always isolate the PC by running it on an isolated ac supply or by running the PC on its battery packs.
Using Terminal
Emulator Programs
The procedures for starting and using terminal emulator program will vary depending
on the specific terminal emulator program. A simple terminal emulator program was
included with every copy of Microsoft Windows.
NOTICE
Windows Vista, Windows 7, and Windows 8 do not include a terminal emulation program.
Users must select and install a terminal emulator program to be able to communicate with
the Vista Overcurrent Control. S&C recommends downloading one of two terminal emulator programs listed below.
Appendix C
HyperTerminal
For Windows 95, 98, 2000, NT, ME, XP, and Microsoft Vista:
1. Click on the Start button.
a. For Windows 95, 98, and ME select Programs and then Accessories. In the
Accessories folder, select the HyperTerminal icon. Then double-click on
Hypertrm.exe.
b. For Windows 2000, NT, and XP select Programs, then Accessories, then Commu
nications (or HyperTerminal). Then select the HyperTerminal icon.
c. For Microsoft Vista open the HyperTerminal program from its file location
(probably on the desktop).
2. A dialog box will then ask for a connection description. This is a file that will be saved
in the HyperTerminal folder with its own name and icon. It stores the appropriate
settings for connecting to the Vista Overcurrent Control so that they do not have to be
entered each and every time. In the connection description dialog box, enter a name
for this file (for example, Vista).
3. The next dialog box asks for a phone number to dial. Ignore this and go to the
Connect Using list at the bottom of the dialog box. With the relay connected, select
the correct COM # from the drop down menu. The assigned COM # can be found
under Control Panel, System, Hardware, Device Manager. Expand the Ports menu.
The COM # assignment is adjacent to SEL to UART Bridge Controller. Click
on OK.
4. The next dialog box asks for the connection parameters. Enter the settings listed in
Appendix B and click on OK.
5. HyperTerminal should now be connected to the Vista Overcurrent Control. To
initiate the data flow between the computer and the control, press the <Enter> key
on the computer. Until the <Enter> key on the computer is pressed, nothing
will come up on the screen. It may be necessary to click on the Disconnect button
on the toolbar. This function is also located under the Call menu. After disconnecting,
click on the Reconnect button on the toolbar. Again, this function is located under
the Call menu.
6. To exit this session, select File:Exit or click on the X button in the upper righthand corner of the window. Hyperterminal will ask if you want to save the session
settings. Click on Yes so that, in the future, all of the above instructions can be bypassed
by simply clicking on the icon that you just created.
AcSELerator
QuickSet 5030
Appendix D
Coordination
The Vista Overcurrent Control provides the flexibility required to meet the critical needs
of protective device coordination between upstream and downstream devices such as cir
cuit breakers and fuses. The example below shows how well the U.S. U4 time-overcurrent
curve coordinates with both an upstream protective relay and downstream power fuse.
The reference document used for these curve families and their equations is IEEE Stan
dard C37.112-1996 IEEE Standard Inverse-Time Characteristic Equations for Overcurrent
Relays.
As shown in this instruction sheet and, as seen on the overcurrent controls user inter
face, all pickup-current settings selections for E, K, Coordinating-Tap, Coordinating-Main,
ANSI/U.S. U1 through U5, and IEC C1 through C5 are expressed in terms of primary amperes.
However, in IEEE Standard C37.112-1996, U.S. and IEC curve families are expressed in
terms of multiples of pickup where 1.0 on this axis represents the pickup setting. The
standard uses this method of illustrating time versus current response because different
current transformer ratios may be used for each specific application. In Vista, the CT ratio
is fixed at either 660:1 or 1320:1. Consequently, we will refer to the multiples-of-pickup
nomenclature for this example.
Based on the desired application, any of the ten curve families can be selected to
meet the coordination requirements. Adjusting the minimum pickup setting in terms
of primary amperes moves the desired time-overcurrent curve to the left or right on
the TCC coordination plot. In addition to the minimum pickup setting, a time dial
feature is used to move the desired time-overcurrent curve up or down in time (in
seconds) to meet the specific coordination requirements.
Example:
Referring to the coordination plot in Figure 2, a Vista unit with 600-ampere fault
interrupters is placed into an electrical system where the upstream protective device
is controlled by an overcurrent relay whose phase time-overcurrent curve family
is set for a CO-9 Very Inverse curve. The relays phase overcurrent pickup is set for
960 amperes with a time dial setting of 2. There are two curves shown which take into
account the operating time tolerance of the CO-9 overcurrent relay. Downstream of the
Vista unit is an S&C SMU-20 power fuse with a 200K-ampere rating. Its minimum melt and
total clearing curves are shown on the TCC coordination plot.
It is desired to coordinate the Vista unit with the upstream and downstream devices. A
review of the ANSI/U.S. and IEC curve families resulted in the selection of the ANSI/U.S.
U4 curve. See Figure 3. Its curve shape is similar to the other two devices curves. Using
a TCC coordination program, it is possible to fit a time-overcurrent curve between the
curves of the upstream source-side and downstream load-side devices. Note that the Vista
curve selected is shown starting at 150% of the actual pickup setting in primary amperes
(880 amperes 1.5 = 1320 amperes). The time dial setting selection of 0.8 was selected
to maintain an acceptable coordinating time interval (CTI) between the upstream protec
tive relay phase setting, the power fuse, and the Vista unit. Due to the extremely fine
resolution of pickup current and time dial settings selections within the ANSI/U.S. and
IEC curve families, it is obvious that there are other pickup current and time dial settings
within the U4 family that could accomplish proper device coordination; in this example
the Vista Overcurrent Controls time-overcurrent curves are placed equidistant between
the upstream and downstream device time-overcurrent curves.
Appendix D
One final consideration in the selection of ANSI/US and IEC curve families to achieve
proper power system coordination is the I2t security characteristic of the Vista Overcur
rent Control, included with controls having firmware version R300 or later. The control will
self-protect its internal power supply and current sensing circuitry when a pickup setting (in
amperes) and/or a time dial setting exceeds the thermal limits of the electronic circuitry (in
both the electronics module and burden board assemblies). Figure 1 shows the I2t security
characteristic of the Vista Overcurrent Control. When the I2t security characteristic is
enabled, the control may implement a definite-time response characteristic of 0.25 seconds
for any current magnitude above 14.5 kA (above 29 kA for 900-ampere and 1200-ampere Vista
models). This matches the performance ratings of the control listed in the Specifications
section. The I2t security characteristic does not apply to the E, K, Coordinating-Tap, and
Coordinating-Main curve families under all settings.
Time(s)
Maximum Rating
0
0
10
15
20
25
Current (kA)
Figure 1. Vista Overcurrent Control maximum current rating adjusted for C.T. saturation.
The following table should be used to determine if the I2t security characteristic will
become enabled during the maximum calculated fault levels. In most cases, the pickup
current and time dial settings selected will be well below the values listed in the table.
To prevent the I2t security characteristic from becoming enabled, the pickup current and
time dial settings must be less than the limits listed in the following table.
The operation time of the U.S. and IEC curves is a function of three variables: the
pickup setting, the time-dial setting, and the fault current (measured in multiples
of the pickup setting). With this information, the overcurrent control calculates the
curve operation time and the I2t security characteristic operation time, compares the
two, and operates according to the faster time. The table provides example curve
settings at sample fault current levels that would cause the curve operation time to
be slower than the I2t security characteristic operation time for a 660:1 CT.
Appendix D
I2t Security Characteristic Settings Limits (660:1 CT)
Curve
U1
U2
U3
U4
U5
Not applicable
C1
C2
C3
Not applicable
Not applicable
C4
C5
Not applicable
Not applicable
For our sample coordination study, with a U4 curve selected to have an 880ampere pickup and a 0.8 time dial setting, we are well below the limits shown
for the operation of the I2t security characteristic during fault levels up to 14.5
kA. The time dial setting is below the threshold of 10.0 at a pickup setting of
1200 amperes.
If the setting was above the limit for the I2t security characteristic, a warning message
would be displayed with the calculation of the cross over point in primary amperes of the
selected US or IEC curve with the I2t security characteristic curve. A sample warning
message is shown below.
Phase overcurrent control will operate on the TOC curve for faults up to 18476 A.
Phase overcurrent control will operate on its maximum I2t (thermal) limit curve for
faults above 18476 A. Refer to S&C Instruction Sheet 681-515 Appendix D.
When this occurs, the user must consider the following:
If the fault level displayed in the warning message is higher than the maximum
available fault current level at the Vista unit, the I2t security characteristic will not
become enabled. If the fault level displayed in the warning message is lower than
the maximum available fault current level, then the I 2t security characteristic will
become enabled resulting in a faster time to operate. To prevent this from occurring,
new settings selections should be considered to prevent miscoordination between
upstream source-side and downstream load-side devices. Contact S&C Electric
CompanyPower Systems Services for application assistance.
Appendix D
1000
100
Time in Seconds
10
Fuse
S&C SMU20 K 14.4kV
Rating: 200.0 [A]
12.47[kV]
Phase Relay
Relay WEST CO-9
Tap Range: [-] Tap: 0
Pick Up: 960.00 [A] TD: 2
CT: 600:5 at 12.47 [kV]
Phase
Relay
51
600: 5
0.1
Vista
51
200K fuse
0.01
0.4
10
100
1000
10000
Appendix D
6000 (5000)
100
90
80
70
60
3000 (2500)
50
40
30
1500 (1250)
20
600 (500)
10
9
8
7
6
300 (250)
5
4
Time in Seconds
150 (125)
2
60 (50)
1
.9
.8
.7
15.0
.6
12.0
10.0
.5
.4
30 (25)
8.00
.3
6.00
15 (12.5)
5.00
.2
4.00
3.00
6 (5)
.1
.09
.08
2.00
.07
.06
3 (2.5)
.05
1.00
.04
.03
8 9
80
90
100
70
60
40
30
.6 .7 .8 .9 1
20
.5
10
.01
50
0.50
.02
Appendix E
Overcurrent Control
Settings
The Vista Overcurrent Control can be programmed to provide a wide variety of settings
combinations. Listed below are the setting ranges that are displayed when the control is
connected to a personal computer.
For C.T. ratio of 660:1:
Phase TCC Curve (E, K, TAP, MAIN, U1, U2, U3, U4, U5, C1, C2, C3, C4, C5)
For E-Speed Curves:
Curve Selection (25E, 30E, 40E, 50E, 65E, 80E, 100E, 125E, 150E, 175E, 200E, 250E,
300E, 400E)
For K-Speed Curves:
Curve Selection (25K, 30K, 40K, 50K, 65K, 80K, 100K, 125K, 150K, 175K, 200K)
For Coordinating-Tap Curves:
Minimum Pickup (Amperes) (50, 65, 80, 100, 150, 200, 250, 300, 350, 400)
For Coordinating-Main Curves:
Minimum Pickup (Amperes) (100, 150, 200, 250, 300, 350, 400, 450, 500, 600, 700, 800)
For Curves U1-U5 and C1-C5:
Minimum Pickup (Amperes) (50-1200, 1 A steps)
Time-Dial Multiplier U Curves (0.5 15.0, 0.1 steps)
Time-Dial Multiplier C Curves (0.05 1.0, 0.01 steps)
For Coordinating-Tap and Coordinating-Main Curves:
Instantaneous Pickup (kA) (OFF, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1, 2, 3, 4, 5, 6)
For Curves U1-U5 and C1-C5:
Instantaneous Pickup (Amperes) (OFF, 200 13200, 20 A steps)
For Coordinating-Tap and U1-U5 and C1-C5 Curves:
Definite Time Delay (ms) @ 60 Hz (OFF, 32, 48, 64, 80, 96)
Definite Time Delay (ms) @ 50 Hz (OFF, 40, 60, 80, 100, 120)
For Coordinating-Main Curves:
Definite Time Delay (ms) @ 60 Hz (OFF, 64, 80, 96, 112, 128)
Definite Time Delay (ms) @ 50 Hz (OFF, 80, 100, 120, 140, 160)
Appendix E
Ground TCC Curve (OFF, TAP, MAIN) or (OFF, U1, U2, U3, U4, U5, C1, C2, C3, C4, C5
See Notes 1 and 2
For Coordinating-Tap Curves:
Minimum Pickup (Amperes) (50, 65, 80, 100, 150, 200, 250, 300, 350, 400)
For Coordinating-Main Curves:
Minimum Pickup (Amperes) (100, 150, 200, 250, 300, 350, 400)
For Curves U1-U5 and C1-C5:
Minimum Pickup (Amperes) (50 400, 1 A steps)
Time-Dial Multiplier U Curves (0.5 15.0, 0.1 steps)
Time-Dial Multiplier C Curves (0.05 1.0, 0.01 steps)
For Coordinating-Tap and Coordinating-Main Curves:
Instantaneous Pickup (kA) (OFF, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1, 2, 3, 4, 5, 6)
For Curves U1-U5 and C1-C5:
Instantaneous Pickup (Amperes) (OFF, 200 13200, 20 A steps)
For Coordinating-Tap and U1-U5 and C1-C5 Curves:
Definite Time Delay (ms) @ 60 Hz (OFF, 32, 48, 64, 80, 96)
Definite Time Delay (ms) @ 50 Hz (OFF, 40, 60, 80, 100, 120)
For Coordinating-Main Curves:
Definite Time Delay (ms) @ 60 Hz (OFF, 64, 80, 96, 112, 128)
Definite Time Delay (ms) @ 50 Hz (OFF, 80, 100, 120, 140, 160)
Note 1: Ground settings are not displayed and are disabled if the Trip Mode setting is set
for 1-pole trip or if the Phase TCC curve selected is either E-speed or K-speed.
Note 2: Ground curves can be selected to provide a different TCC curve than the phase
setting. However, when TAP or MAIN is used for the phase TCC, only MAIN and TAP TCC
curves can be selected for the ground TCC setting. When a U or C curve is selected for the
Phase TCC, only the U and C families can be selected for the ground TCC setting.
For a C.T. ratio of 1320:1:
Phase TCC Curve (E, K, TAP, MAIN, U1, U2, U3, U4, U5, C1, C2, C3, C4, C5)
For E-Speed Curves:
Curve Selection (50E, 65E, 80E, 100E, 125E, 150E, 175E, 200E, 250E, 300E, 400E)
For K-Speed Curves:
Curve Selection (50K, 65K, 80K, 100K, 125K, 150K, 175K, 200K)
For Coordinating-Tap Curves:
Minimum Pickup (Amperes) (100, 150, 200, 250, 300, 350, 400)
For Coordinating-Main Curves:
Minimum Pickup (Amperes) (200, 250, 300, 350, 400, 450, 500, 600, 700, 800)
For Curves U1-U5 and C1-C5:
Minimum Pickup (Amperes) (100-2400, 1 A steps)
Time-Dial Multiplier U Curves (0.5 15.0, 0.1 steps)
Time-Dial Multiplier C Curves (0.05 1.0, 0.01 steps)
Appendix E
For Coordinating-Tap and Coordinating-Main Curves:
Instantaneous Pickup (kA) (OFF, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1, 2, 3, 4, 5, 6)
For Curves U1-U5 and C1-C5:
Instantaneous Pickup (Amperes) (OFF, 200 13200, 20 A steps)
For Coordinating-Tap and U1-U5 and C1-C5 Curves:
Definite Time Delay (ms) @ 60 Hz (OFF, 32, 48, 64, 80, 96)
Definite Time Delay (ms) @ 50 Hz (OFF, 40, 60, 80, 100, 120)
For Coordinating-Main Curves:
Definite Time Delay (ms) @ 60 Hz (OFF, 64, 80, 96, 112, 128)
Definite Time Delay (ms) @ 50 Hz (OFF, 80, 100, 120, 140, 160)
Ground TCC Curve (OFF, TAP, MAIN) or (OFF, U1, U2, U3, U4, U5, C1, C2, C3, C4, C5)
See Notes 1 and 2
For Coordinating-Tap Curves:
Minimum Pickup (Amperes) (100, 150, 200, 250, 300, 350, 400)
For Coordinating-Main Curves:
Minnimum Pickup (Amperes) (200, 250, 300, 350, 400)
For Curves U1-U5 and C1-C5:
Minimum Pickup (Amperes) (100 800, 1 A steps)
Time-Dial Multiplier U Curves (0.5 15.0, 0.1 steps)
Time-Dial Multiplier C Curves (0.05 1.0, 0.01 steps)
For Coordinating-Tap and Coordinating-Main Curves:
Instantaneous Pickup (kA) (OFF, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1, 2, 3, 4, 5, 6)
For Curves U1-U5 and C1-C5:
Instantaneous Pickup (Amperes) (OFF, 200 13200, 20 A steps)
For Coordinating-Tap and U1-U5 and C1-C5 Curves:
Definite Time Delay (ms) @ 60 Hz (OFF, 32, 48, 64, 80, 96)
Definite Time Delay (ms) @ 50 Hz (OFF, 40, 60, 80, 100, 120)
For Coordinating-Main Curves:
Definite Time Delay (ms) @ 60 Hz. (OFF, 64, 80, 96, 112, 128)
Definite Time Delay (ms) @ 50 Hz. (OFF, 80, 100, 120, 140, 160)
Note 1: Ground settings are not displayed and are disabled if the Trip Mode setting is set
for 1-pole trip or if the Phase TCC curve selected is either E-speed or K-speed.
Note 2: Ground curves can be selected to provide a different TCC curve than the phase
setting. However, when TAP or MAIN is used for the phase TCC, only MAIN and TAP TCC
curves can be selected for the ground TCC setting. When a U or C curve is selected for the
Phase TCC, only the U and C families can be selected for the ground TCC setting.