Profiled Metal Roofing The Metal Cladding & Roofing Manufacturers Association Limited PDF
Profiled Metal Roofing The Metal Cladding & Roofing Manufacturers Association Limited PDF
MACE
On
29/05/2016
Nh2
JUNE 2004
Contents
Page
1
1
1
1
1
1
1
2
2.0 Components
2.1 Profiled sheets
2.2 Coatings
2.3 Spacer systems
2.4 Fasteners
2.5 Insulation
2
2
2
3
3
5
3.0 Weathertightness
3.1 Performance requirements
3.2 Roof pitch
3.3 End laps
3.4 Side laps
5
5
5
5
6
7
7
7
9
11
13
13
14
14
15
6.0 Acoustics
6.1 Sound reduction
6.2 Sound absorption
15
15
15
16
16
16
17
17
17
17
17
18
18
18
9.0 Durability
9.1 Introduction
9.2 Materials
9.3 Design details
9.4 Maintenance
Page
19
19
19
20
20
10.0 Sustainability
10.1 Sustainable construction
10.2 Life Cycle Assessment
10.3 ISO 14001
21
21
21
22
23
23
24
24
24
24
25
26
26
26
26
26
27
14.0 References
28
For up to date information on metal roof and wall cladding, including downloadable construction
details, visit www.mcrma.co.uk.
The Metal Cladding & Roofing Manufacturers Association Limited. June 2004
Components
STEEL
ALUMINIUM
Weather sheet
0.7
0.9
Liner sheet
0.4
0.5
0.7
0.9
2.2
Coatings
Type
Substrate
Typical thickness:
microns
Application
Plastisol
steel
200
weathersheet
Pvf2
25
weathersheet
Multicoat
100
weathersheet
ARS
aluminium
28
weathersheet
Polyester
22
liner
Full details of the range of available coatings can be obtained from the individual manufacturers.
2.3
Spacer systems
Traditional
zed spacer
and ferrule
2.4
Fasteners
a) Primary
These fasteners are designed to transfer all loads
on the cladding system back to the supporting
structure so their strength is particularly important.
If the fasteners are exposed they must also
provide a weathertight seal. They are normally
used in the valley of the profile. If crown fixing
is recommended by the manufacturers, saddle
washers are usually required.
Bracket
to purlin
Outer sheet
to spacer
Mini-zed to
purlin
through
ferrule
Composite
and siteassembled
composite
Self tapping
Metal
sheet to
hot rolled
steel
Metal sheet
to timber
Rivets
Weathertightness
2.5 Insulation
The majority of site-assembled double skin roof
constructions use mineral fibre (glass or rock)
quilt insulation supplied in rolls. When unrolled on
site the material expands to at least its required
thickness and normally fills the cavity created by
the spacer system between the liner and weather
sheet. The material is normally quite soft and
deforms around the small profiled ribs on the liner,
and under and around the spacer system.
Rigid mineral fibre insulation slabs are also used
in some circumstances but this is less deformable
than the quilt and the roofing system has to be
designed and installed with this in mind so that no
gaps are left in the insulation layer.
Site-assembled composite constructions do not
use spacer systems and rely on the rigidity of the
insulation and special fasteners to support the
outer sheet. In this case rigid profiled polyurethane,
polyisocyanurate, and mineral fibre insulation are
used.
150mm
m
m
15
Two runs
of sealant
Fig 12: End lap detail for roof pitches greater than 4
Aluminium weather sheets may require a slightly
different end lap arrangement to allow for the
coefficient of linear expansion, which is twice that
of steel. The actual arrangement will depend on
the length and colour of the sheets. The colour
determines the maximum temperature that the
sheets reach and therefore the maximum degree
of expansion.
Fig 13 shows a typical detail, which allows some
movement at the end lap joint without affecting
the fasteners. Special sealants need to be used
to provide a suitable sliding joint, and the overlap
may be increased to 200mm. When aluminium
profiles are being considered the manufacturers
recommendations should be followed.
200mm
Two runs
of sealant
3.4
Side laps
Thermal Performance
4.1 Regulations
The thermal performance of the roof cladding is
important because it affects the amount of energy
required to heat the building and will influence the
running costs and the comfort of the occupants.
Approved Document L2 to the Building Regulations
(2002 Edition) Conservation of Fuel and Power
defines the required levels of performance in
terms of U values, thermal bridging, and air
tightness, and explains how the requirements can
be achieved. Site testing of the completed building
is required in many cases, to ensure the design
performance has been achieved. It means that the
building designer and cladding contractor need to
pay more attention to the thermal performance of
individual details of the construction, which were
not previously defined.
The Approved Document refers to MCRMA
technical paper No 14 Guidance for the design
of metal roofing and cladding to comply with
Approved Document L2:2001, for further more
detailed information.
4.2 U-values
4.2.1 Methods of determining U-values
The elemental U-value or thermal transmittance
specified in Approved Document L2 for industrial
and commercial roofs is 0.25 W/m2K.
Approved Document L2 requires that profile
shapes, and repeating thermal bridges, such as
metal spacers and other fixings, are taken into
account when a U-value is calculated using the
combined method, which is specified in BS EN
ISO 69461 and CIBSE Guide A32. However, this
method is designed to deal with the type of thermal
bridges such as timber studs, which distort the
heat flow relatively little, and it specifically excludes
elements in which the insulation layer is crossed by
thin metal components.
Ultimately, the U-value of this type of element
has to be calculated by developing a full two- or
three-dimensional thermal model of the structure
to calculate the heat flows. This is a complex task
requiring software, which complies with BS EN
ISO 10211:19963, and is usually carried out only
Purlin spacing : m
Insulation
conductivity : W/mK
Bracket
spacing : m
0.9
1.4
1.8
0.035
0.5
175
160
155
1.0
160
150
150
0.5
210
195
185
1.0
190
180
175
0.5
220
210
200
1.0
205
200
195
0.04
0.045
Ts - Te
Ti - Te
Humidity
class
Building type
Minimum
f-value
Storage areas
0.30
Offices, shops
0.50
0.65
0.80
Special buildings,
e.g. laundry, brewery,
swimming pool
0.90
10
The fact that the heat loss from the real building
is compared with that from the notional building
means that, provided that the surface temperature
criteria in Fig 16 are met, it is possible to trade off
areas and U-values against thermal bridges. So
that if it was not possible to design out a severe
thermal bridge, the criterion could, for example, be
met by reducing the rooflight area from 20%, while
retaining the rooflight U-value at 2.2 W/m2K. (See
example in MCRMA technical bulletin No 11).
11
12
Interstitial condensation
4.4.3
Important leakage routes
To minimise air leakage through twin skin metal
roofing, the liner side of the construction must be
sealed as effectively as possible. This involves
sealing:
13
5.2.2. Ventilation
No matter how well the vapour control layer is
constructed, some moisture vapour may get into
the construction and there must be provision in the
design to deal with it. The smaller the roof voids
and the insulation cavity the less moisture there is
likely to be present to condense. The roof voids
should therefore be the minimum required and the
weathersheet should be in contact with the insulation.
In site-assembled double skin constructions with
standard trapezoidal sheets ventilated fillers
must be used at the ridge and eaves to allow
some breathing through the ribs in the profiled
weathersheet. This helps to disperse any moisture
vapour which is in the construction.
Other types of profiled sheets, such as secret fix,
use different methods of ventilation. See individual
manufacturers details.
14
Acoustics
5.4 Rooflights
Ensuring continuity of the vapour control layer and
ventilation through profiled ribs normally means
that site-assembled rooflights should be used
with site-assembled double skin cladding systems.
Factory-assembled rooflights are used with
composite panels.
15
Performance in fire
7.1 Introduction
The manner in which all elements of building
construction perform in the event of a fire is of
prime concern to the designer, the occupant,
the building owner and the building insurance
company. Profiled metal cladding constructions
must therefore conform to specific requirements
which are defined in the Building Regulations
Approved Document B. They may also have
to comply with other requirements defined by
building insurance organisations, such as the Loss
Prevention Council (LPC).
The purpose of the Building Regulations is to
ensure the health and safety of people in or about
the building. The main requirements are:
16
Structural performance
8.1
Dead + imposed
Dead + snow drift
Dead + wind
Dead wind
1.4 Wd + 1.6 Wi
1.4 Wd + 1.05 Wsnow
1.4 Wd + 1.4 Wind
1.0Wd 1.4 Wind
Attachment(3)
Notes:
1. Wd = deadload
Wi = imposed load (BS6399:Part 3)
Wsnow = snowdrift load (BS6399:Part 3)
Wind = wind load (BS6399:Part 2)
2. These load factors are mostly from BS5950:
Part 5 and are also adopted in BS5427. They
apply to the metal profile.
3. Attachment refers to the fixing assembly
(fasteners or clips). A minimum factor of 2
should be used and may be increased for timber
and other non-steel substances.
Fig 20: Load factors
17
Design loading
Foot traffic:
For many roof constructions point loading due
to foot traffic is one of the critical load cases.
The minimum thicknesses specified in section
2 are generally required to enable the roof to
withstand foot traffic during assembly, but even
these are not immune from damage, if care is
not taken. Metal roof cladding is normally only
designed for cleaning and maintenance loading.
If regular access is required special walkways
should be provided. The appearance of some
roofs, particularly if made of aluminium, may be
impaired by excessive foot traffic.
18
Durability
9.1 Introduction
Durability is the ability of a building and its parts
to perform its required function over a period
of time (see BS7543). Virtually all materials will
change physically when subjected to UV radiation,
moisture and atmospheric pollution, and this will
affect their performance. The designer must
therefore ensure not only that the materials and
details used are suitable initially but also that they
will have a satisfactory life, given the necessary
maintenance.
9.2 Materials
The materials selected for the roof can have a
significant effect on its durability and the amount of
maintenance that will be necessary during its life.
The components which are exposed to the weather
are particularly important.
The type of sheeting material, coating and colour
must all be considered. The performance might
also depend on the shape and orientation of the
building and the environment. Generally, light
coloured coatings are preferable because they do
not absorb as much sunlight as dark colours, and
they are therefore cooler. This means they tend to
have the best life and they optimise the thermal
performance of the roof.
The table in Fig 21 gives an indication of the life
of some coated sheets on a typical 5 roof slope,
in an inland, non-polluted environment. The
life-in-years shown concern the appearance
and the condition of the coating and it can be
extended by repainting. The data has been taken
from manufacturers literature and is for general
guidance only.
Material
Coating
Life-in-years
Steel
Plastisol - light
Plastisol - dark
Pvf2
Multicoat
23
10
15
20
Aluminium
Pvf2
ARS
20
15
19
9.4 Maintenance
The coating life shown above, and therefore the
durability of the roof, is always dependent on
regular maintenance. This will involve inspection,
removal of debris, cleaning and repair of any
damage found. Gutters are likely to require the
most frequent attention because debris tends to
collect in them and can restrict their capacity, whilst
increasing the potential for corrosion.
20
Sustainability
21
Climate change.
Ozone depletion.
Summer smog.
Mineral extraction.
22
23
11.2 Rooflights
Rooflights are used in many industrial and
commercial buildings. Typically a rooflight area of
approximately 10% of the total roof area is used.
Great care should be taken in their specification
and installation, and the manufacturers guidance
should always be followed. See also MCRMA
technical paper No 1 Recommended good practice
for daylighting in metal clad buildings.
24
11.6 Flashings
Flashings are normally manufactured in the same
material and thickness as the cladding, at least
0.7mm for steel and 0.9mm for aluminium. Where
the leg length of a flashing exceeds approximately
200mm, it will be difficult to maintain a flat
appearance and it is advisable to introduce a
bend or stiffener to straighten and strengthen the
material. See examples in section 11.1)
Exposed edges should be stiffened using one of
the details shown in Fig 28.
Lock roll
Welt
Stiffened edge
Fig 28
25
Site work
12.1 General
26
Inspection and
maintenance
27
References
1.
2.
3.
4.
5.
6.
7.
8.
9.
Other publications
The Complete Package CDROM
Manufacturing tolerances for profiled metal roof
and wall cladding
CladSafe latent defects insurance scheme: basic
guide
Liability
Whilst the information contained in this design guide is believed
to be correct at the time of going to press, the Metal Cladding and
Roofing Manufacturers Association and its member companies
cannot be held responsible for any errors or inaccuracies and, in
particular, the specification of any application must be checked
with the individual manufacturer concerned for a given installation.
28
12.00
incl. P&P