Single-Phase Transformers: 6. Insulating DC Circuits From AC Circuits
Single-Phase Transformers: 6. Insulating DC Circuits From AC Circuits
It should be mentioned here that the electric power is generated at voltage in the range of the 11-30KV.
Transmitting a given amount of power requires a fixed product of voltage and current. Thus the higher
the voltage, the lower the current can be. Lower line currents are associated with lower losses (I2Z). -
Transmitting the power in low voltage range for long distance is not feasible since all the power will be
lost as a voltage drop on the transmission line.
An obvious solution to this problem is to raise the voltage level to some hundred KV (ranging from 110
to 700 KV). Here comes the function of the transformer. This device is one of the most important
inventions of all times. Without a doubt, they are the most important piece of equipment along the
power transmission and distribution systems. Transformers make it possible to convert the energy taken
from generators into usable, transmittable form. Without them, it would be next to impossible to use
the energy produced by the utility companies.
Transformer Construction
A single-phase transformer consists basically from two or more windings coupled by magnetic core.
When one of the windings (primary) is connected to an AC source, a time varying flux is produced in
the core. This flux is confined within the magnetic core and it links the second winding (secondary).
When any electric load is connected to the secondary winding, a current will flow.
10
φ
I1 I2
+ +
E1 N1 N2 E2 V2 Load
V1
- -
Ideal Transformer
1. No leakage flux (all the flux produced by the primary winding links the secondary)
2. No winding resistance (V1= E1 and V21= E2)
3. The core reluctance is zero ( ℜ = 0, and µ = ∞ )
4. No core losses (eddy + hysteresis)
11
Let the mutual flux linking both windings φ m be sinusoidal, such that: φ m = φ p sin ω t . According to
Faraday's law, the induced emf can be expressed as:
dλ 1 dφ m
e1 = = N1 = ωφ p N1 cos ω t
dt dt
dλ 2 dφ m
e2 = = N2 = ωφ p N 2 cos ω t
dt dt
1
E1 = ωφ p N1 = 4.44 fφ p N1
2
1
E2 = ωφ p N 2 = 4.44 fφ p N 2
2
The polarities of the induced emf are given by Lenz's law, that is, the emfs produces currents that tend
to oppose the flux change.
E1 N1 V1
The ration between the primary and secondary induced emf is: = = = a , which is known as
E2 N 2 V2
the transformer Turns Ratio. Since the transformer is ideal and there is no losses, then the input power
equals the output power, V1 I1 = V2 I 2 , then:
E1 N1 V1 I 2
= = = =a
E2 N 2 V2 I1
1
V1 = aV2 and I1 = I2
a
12
Z 2\ is known as the secondary winding impedance referred to the primary winding. In addition, both
the current and the voltage in the secondary circuit can be referred to the primary circuit as follows:
V1
= a , then V1 = aV2 = V2\
V2
I1 1 1
= , then I1 = I 2 = I 2\
I2 a a
The equivalent circuit of the transformer Referred to the primary is given as follows:
I2
I1 I 2\ =
a
V2\ = aV 2
V1 z 2\ = a 2 Z 2
E1 E2\ = aE2
The equivalent circuit of the transformer Referred to the secondary is given as follows:
I1\ = aI 1 I2
V1
V1\ = E1 V2
a E1\ = E2
a
13
Example
Solution:
N1 V1 240
a) a = = = =2
N 2 V2 120
5000
b) I1rated = = 20.83 A
240
5000
I 2rated = = 41.67 A
120
I N
or 2 = 1 = a = 2
I1 N 2
3200
c) For the given load, I 2 = = 33.33 A
120 × 0.8
I 2 33.33
And I1 = = = 16.67 A
a 2
The assumptions made in the previous section for ideal transformer are no longer applicable when
analyzing the performance of an actual transformer.
14
φm
R1 I1 R2 I2
+ +
V1 E1
φ11 φ12 E2 V2 Load
- -
N1 N2
Where:
For the primary winding, the flux linking the winding is given as:
φ 1 = φ m + φ 11
The voltage equation for the primary loop can be written as:
dλ 1 dφ 1
V1 = R1i1 + = R1i1 + N1
dt dt
dφ m dφ
Thus V1 = R1i1 + N1 + N1
11
dt dt
dφ di1
Since N1φ 11= i1 L1 , ∴ N1 = L1
11
dt dt
di1 dφ m di
∴ V1 = R1i1 + L1 + N1 = R1i1 + L1 1 + e1 (A)
dt dt dt
In the secondary circuit, the voltage equation may be written as follows:
15
dλ dφ 2
V1 = − R2i2 + = − R2 i2 + N 2
2
dt dt
From the flux direction, φ 2 = φ m − φ 12 ,
dφ m dφ
Thus: V2 = − R2i2 + N 2 − N2
12
dt dt
di2 dφ m di
And ∴ V2 = − R2 i2 − L2 + N2 = − R2 i2 − L2 2 + e2 (B)
dt dt dt
Where e1 and e2 are the induced emf in the primary and the secondary windings, respectively. It can be
shown that:
e1 N1
= =a
e2 N 2
Equations A & B can be written in frequency domain as follows:
∴ V1 = R1i1 + jω L1i1 + E1
V2 = − R2 i2 − jω L2i2 + E2
To model the core losses of the transformer a parallel circuit consists of an inductor Lm and a resistor
Rc is added usually to the primary side of the transformer equivalent circuit, where:
The core related circuit elements Lm & Rc are usually determined at the rated voltage and referred to the
primary. They are assumed constant when the transformer is operating at or near the rated conditions.
16
I1 R1 L1 R2 L2 I2
Ie
Ic Im Load
V1
Rc Lm E1 E2 V2
N1 N2
Ideal Transformer
The equivalent circuit of the transformer in the frequency domain is given as:
I1 R1 jX 1 I 2\ = I 2 a R2 jX 2 I2
Ie
Load
V1
Rc jX m E1 E2 V2
Ic Im
N1 N2
Ideal Transformer
Where:
17
I2 = Secondary current
Ie = Excitation current
Im = Magnetizing current
Ic = Core loss current
Xm =Magnetizing reactance
X1 =Primary leakage reactance
X2 =Secondary leakage reactance
Rc = Core loss resistance
R1 = Primary winding resistance
R2 = Secondary winding resistance
V1 = R1i1 + jX 1i1 + E1
V2 = − R2i2 − jX 2 i2 + E2
Ie = Ic + Im
I1 = I e + I 2\
I 2\ = I 2 a
a = N1 N 2
I c // E1
I m ⊥ E1
V1
jI 1 X 1
E1
E2
Ic I1 R1
V2 jI 2 X 2
θ2 I 2 R2
Im Ie \
I 2
I2
I1
18
Referred Transformer Equivalent Circuit
1. Referred to primary side
I1 R1 jX 1 a 2 R2 a 2 jX 2 I 2\ I2 a I2
R2\ jX 2\
Ie
Ic Im
V1 jX m
Rc V2\ aV2 V2
N1 N2
Ideal Transformer
R2\ = a 2 R2
X 2\ = a 2 X 2
I 2\ = I 2 a
E 2\ = aE 2
V 2\ = aV 2
a = N1 N 2
E 2\ = E1
V1
E1 = E 2\ jI 1 X 1
Ic
I1 R1
\ \ \
V 2 jI X
2 2
θ2 I 2\ R2\
Im Ie
I 2\
I1
19
2. Referred to secondary side
R1 jX 1
I1 aI1 a2 a2 R2 jX 2 I2
I e\
I c\ I m\
V1 Rc jX m
V1 V1\ V1 a V2
a2 a2
N1 N2
Ideal Transformer
R1
R1\ =
a2
X
X 1\ = 21
a
I1\ = aI1
E1
E1\ =
a
V
V1\ = 1
a
a = N1 N 2
Example
Solution
Step #1
Determine the load voltage and current:
The voltage across the load is taken as a reference in this case and is equal to V2 = 220∠0 V .
For a load of 20 kW at power factor of 0.8 lag, the load current is equal to:
20
P2 20,000
I2 = = ∠ − cos −1 0.8 = 113.64∠ − 36.9 A
V2 cosθ 2 220 × 0.8
Step #2
X 2\ = a 2 X 2 = 0.32 Ω
Step #3
Solve the equivalent circuit
I1
R1 jX 1 R2\ jX 2\ I 2\ I2 a
Ie
Ic Im
V1 jX m
Rc V2\ aV2
E1 = V2\ + I 2\ (R2\ + jX 2\ )
E1 = 440∠0 + 56.82∠ − 36.9(0.16 + j 0.32) = 458.2∠1 = 458.2 + j 9.07
The shunt branch current is:
E1 458.3∠1
Ic = = = 1.7 + j 0.03
Rc 270
21
E1 458.3∠1
Im = = = 0.09 − j 4.58
jX m j100
I e = I c + I m = 1.79 − j 4.55
Thus the primary current is given as:
I1 = I e + I 2\ = 61.04∠ − 39.3 A
The primary voltage is:
V1 = E1 + I1 (R1 + jX 1 ) = (458.2 + j 9.07 ) + (61.04∠ − 39.3)(0.16 + j 0.32) = 478.4∠2.2 V
the full load primary input current. In practice I e = 3 − 5% I1 . Moreover, since the primary and the
secondary winding resistances and leakage reactances are very small, then the internal voltage drop is
very small such that ∆V1 = I1 (R1 + jX 1 ) ≤ 3 − 5%V1 .
V1 = E1 + I1 (R1 + jX 1 )
Since I1 = I e + I 2\ , then:
V1 = E1 + I e (R1 + jX 1 ) + I 2\ (R1 + jX 1 )
If I e is very small compared to I1 and R1 & X 1 are also very small, then I e (R1 + jX 1 ) is very small
and neglecting it will have negligible effect on both E1 and V2 . The approximate equivalent circuit can
thus be given in the form:
I1 I 2\ I2 a R1 jX 1 R2\ jX 2\
Ie
Ic Im
V1 jX m
Rc V2\ aV2
22
I1 I 2\ I2 a Req jX eq
Ie
Ic Im
V1 jX m
Rc V2\ aV2
Where:
Req = R1 + R2\ = R1 + a 2 R2
X eq = X 1 + X 2\ = X 1 + a 2 X 2
V1
Ic
V2\ jI 2\ X eq1
θ2 \
I Req1
2
Im Ie \
I 2
I1
23
Second Approximation
If the current I e can be neglected, then the circuit is reduced to the second approximation as shown in
I1 I 2\ = I 2 a Req jX eq
V1
V2\ = aV2
Req and X eq are the equivalent resistance and reactance referred to the primary side. The phasor
V2\ jI 2\ X eq1
θ2 \
I Req1
2
I = I1
\
2
I1
Voltage Regulation
Distribution and power transformers are often used to supply loads that are designed to operate at
essentially constant voltage. The amount of the secondary current drawn by the load depends on the
load magnitude. As this current change, the load voltage will change consequently. This change is due
to the voltage drop on the transformer internal impedance. A measure of how much the voltage will
change as the load is varied is called “voltage regulation”
Definition
The voltage regulation is defined as the change in the magnitude of the secondary voltage as the current
changes from full load to no load with the primary voltage held constant.
24
V2 nd no−load − V2 nd full −load
Voltage regulation ε =
V2 nd full −load
V1 − V2\ V1\ − V2
ε= =
V2\ V2
Efficiency
The percentage efficiency of the transformer is defined as the ratio of the power output to the power
input.
Poutput
η= × 100
Pinput
Poutput
η= × 100
Poutput + losses
å losses = P NL + Psc − fl
For any loading percentage x, I x2 Req1 = x 2 I 2fl Req1 . The output power at any percentage x of the full load
25
Maximum Efficiency
∂η
For maximum efficiency, = 0 . This will lead to PNL = x 2 Psc . In other words, for the maximum
dx
efficiency will occur at the loading level where the no-load losses is equal to the copper losses.
Consequently, the loading level at which the maximum efficiency occurs is given by:
PNL
x=
Psc
φm
W
I1
A
+ +
V1 V E1 V2 V
- -
N1 N2
The equivalent circuit of the transformer will be as shown in the figure below. Measuring the voltage,
current and power, then:
26
I1 I 2\ = 0 R1 jX 1 R2\ jX 2\
Ie
Ic Im
V1 Rc jX m V2\ = aV2
I1 I 2\ = 0
Ie
Ic Im
jX m V2 = aV2
\
V1 Rc
The measured values are: PNL , I NL and V1 . From the above circuit:
V12 I
RC = and Yo = NL
PNL V1
1 1
Yo = −j
Rc Xm
1
∴Xm =
æ 1 ö
Yo2 − çç 2 ÷÷
è Rc ø
27
Short circuit test
This test provides the values of the total leakage impedances and the value of the losses in the winding
at full load.
In short circuit test, we short-circuit the low voltage winding and we put the input voltage on the high
voltage winding. Increase the input voltage in steps until we reach the full load current (about 20-30%
of input voltage) and measure the voltage, current and power. The circuit connection and the equivalent
circuits will be as shown:
LV
HV
φm
W
I1
A
+ +
V1 V E1 V2
- -
N1 N2
I1 I 2\ = I 2 a R1 jX 1 R2\ jX 2\
V1
Psc
Req =
I12
V1
Z eq =
I1
X eq = Z eq2 − Req2
If the transformer is designed to have equal losses on the primary and secondary circuits, then:
Req
R1 = R2\ =
2
X eq
X 1 = X 2\ =
2
28
Example
A 50 KVA, 2400/240, 60 Hz, single-phase transformer has a short circuit and open circuit tests
performed on the high-voltage and low-voltage sides respectively, and the following results were
obtained:
Voltage (V) Current (A) Power (W)
Open circuit test 240 5.4 186
Short circuit test 48 20.8 620
Solution
a) The parameters of the transformer referred to the primary side are: R1 , R2\ , X 1 , X 2\ , Rc and X m .
From the short circuit test
Vsc 48
Z eq = = = 2.3Ω
I sc 20.8
Psc 620
Req = = = 1.43Ω
I sc (20.8)2
2
æ P ö
θ oc = cos −1 çç NL ÷÷ = 81.8 Lagging
è Voc I NL ø
Yo\ = 0.0225 ∠ − 81.8 ° S
29
1
Rc\ = = 309.6Ω
Gc
1
X m\ = = 44.8Ω
Bm
1
Rc\ = = 309.6Ω
Gc
30