Document Revision: February 6, 2006 Cyberlogic Technologies, Inc. 5480 Corporate Drive Troy, Michigan 48098 USA (248) 631.2200/tel (248) 631.2201/fax www.cyberlogic.com Copyright 1994-2006, Cyberlogic Technologies Inc. All rights reserved. Cyberlogic, DHX, MBX, WinConX and IntelligentPowerfulReliable are registered trademarks and DirectAccess is a trademark of Cyberlogic Technologies Inc. All other trademarks and registered trademarks belong to their respective owners. Cyberlogic Technologies, Inc. -2-
INTRODUCTION
The OPC client/server architecture is based on the Microsoft COM (Component Object Model) technology. The distributed version of this technology is called DCOM, and it allows OPC clients to interface to remote OPC servers over a network connection. In a networked environment, a key concern of Windows operating systems is security, including the protection of the system against malicious attacks. As part of this security, DCOM function calls between OPC client and server systems are checked for correct security permissions by the operating system. If the security settings are incorrect, DCOM communication will not work. In particular, this is a problem for systems running under Windows XP Service Pack 2, because the default SP2 settings disable DCOM, preventing remote OPC communications. Note This document is primarily concerned with OPC communications using DCOM. This is an issue when the OPC server and OPC client reside on different systems. However, even if both applications are on the same system, users without Administrator privileges may run into similar issues and therefore should follow the recommendations in this document.
Caution!
The procedures in this document will affect the security settings of the systems and networks involved. They include changes to the Windows firewall, permissions, user accounts and other security-related features. Before you implement any of these recommendations, be sure that you understand how they will affect your system and network security, including increased risk of malicious attacks. In addition, be sure to discuss any proposed changes with your System Administrator or IT department. BECAUSE EVERY NETWORK SITUATION IS UNIQUE, ONLY YOUR IT PROFESSIONALS CAN DETERMINE WHAT SECURITY MEASURES ARE APPROPRIATE FOR YOUR SYSTEMS. CYBERLOGIC TECHNOLOGIES INC. MAKES NO REPRESENTATION THAT THE INFORMATION OR RECOMMENDATIONS IN THIS PAPER ARE SUITABLE FOR A PARTICULAR INSTALLATION AND CANNOT ACCEPT RESPONSIBILITY FOR ANY PROBLEMS, DAMAGES OR LOSS OF SERVICE, WHICH MAY BE INCURRED. It is important to understand that the OPC callback mechanism causes the OPC client to function as a DCOM server and the OPC server to function as a DCOM client. Because of this, the configuration issues in this document affect both the client and server systems.
Note
You must have Administrator privileges to perform the configuration changes described in this document.
-3-
The issues covered are divided into four areas of concern: Network Configuration Issues Operating System Specific Issues
-4-
Domain
Domains have a Domain controller that authenticates Users across the Domain. Having a central point for authentication greatly simplifies Users and User Groups identification. Therefore, this is the preferred network architecture. Some considerations: Ideally, the client and server systems should be members of the same Domain. If they are in different Domains, the Domains must be configured to trust each other.
Authentication of Users and User Groups is handled by the Domain controller. These Users and Groups can then be used in the DCOM settings of the client and server. It is preferable that all systems have the same operating system.
Workgroup
Workgroups have no central point for user authentication. This means that each machine in the Workgroup must have all the information on all of the Users that will access the node remotely. This, of course, can dramatically increase the administrative effort when adding new Users. Some considerations: It is preferable to have the client and server systems as members of the same Workgroup.
Each User account that will be used with DCOM must exist on both the client and server systems and use identical usernames and passwords on both systems. Refer to the section Using Run As... for help in testing this requirement. It is preferable that all systems have the same operating system.
Mixed Configuration
If one system is a member of a Workgroup and the other is a member of a Domain, you must use double identification. This means that you must add User accounts to the Workgroup machine that are identical (username and password) to the User accounts in
Cyberlogic Technologies, Inc. -5-
the Domain. This will allow function calls to the Workgroup machine to be identified and granted locally, without asking the Domain controller. In some situations, it may be inconvenient to login as a new User. For those cases, the next section, Using Run As..., provides a useful workaround for testing purposes.
2. From the Run As dialog box, select The following user: option. 3. Enter the User name and password for the account you want to run as, and then click OK.
-6-
Shortcut Method
This method will require the user to enter only a password each time the application is run. 1. Create a new shortcut for the desired application or make a copy of an existing shortcut. 2. Right-click on the shortcut and select Properties.
-7-
3. Edit the Target field to add the following ahead of the existing path and program name:
runas.exe /user:OPCUSER
In place of OPCUSER in the above string, enter the username of the account you wish to run as. Be sure to include a space before the / and after the username. The result will look like the string below, but it will use the path and file name for the application you want to run.
-8-
4. Any user may now run the application by double-clicking the shortcut. Windows will request the password associated with the username.
-9-
Windows 2000
There is a known bug that affects systems running Windows 2000 with Service Pack 1. DCOM servers on these machines may stop sending callbacks after a few days or weeks, preventing function calls such as OnDataChange from completing. In these cases, the DCOM server will return the error code 0x80010108 RPC_E_DISCONNECTED. All other types of calls from the client to the server will continue to work. There are three ways to deal with this problem: Recommended: Install Windows 2000 Service Pack 3 or higher. Install COM + Rollup Package 18.1 (Post Service Pack 2). As a workaround, stop and restart the client application.
Windows XP
There are two concerns in Windows XP systems: the network access setting and the Windows firewall configuration.
Network Access
By default, Windows XP forces remote users to authenticate as Guest. This setting simplifies the setup of home and small business networks that are not configured as Domains. However, this can create problems for OPC servers and clients. When an OPC server is running on an XP machine with its default network access security setting, the Guest account must be enabled and have enough rights to launch the server, or the clients will not be allowed to connect. In addition, if an OPC server sends a callback to a remote client installed on an XP machine, the server will authenticate as Guest and the callback may not get through to the client. Finally, the Guest-authentication default restricts the tools that are available for administering permissions for various users. Due to the above complications, we do not recommend using the default network access security setting on XP machines. Instead, we recommend changing the Network Access setting from Guest Only to Classic. The Classic setting forces Windows XP to behave
- 10 -
like Windows 2000, forcing remote users to authenticate as themselves rather than as Guests. To change this setting: 1. Open the Start menu, then select Control Panel, Administrative Tools and then Local Security Policy. 2. From the tree, select Local Policies and then Security Options. 3. Locate the entry called Network access: Sharing and security model for local accounts. 4. Double-click on it and change the setting to Classic users authenticate as themselves.
Windows Firewall
By default, the Windows Firewall allows traffic across the network when the traffic is initiated locally, but stops most incoming unsolicited traffic. However, administrators can specify exceptions to this rule, allowing responses to unsolicited requests. Firewall exceptions can be specified at two main levels: the application level, and the port-and-protocol level. At the application level, you specify which applications are able to respond to unsolicited requests. At the port-and-protocol level, you specify that the firewall should allow or disallow traffic on a specific port for either TCP or UDP traffic. To make any OPC client/server application work via DCOM, changes must be made on both
Cyberlogic Technologies, Inc. - 11 -
levels. The Cyberlogic OPC Server (CybOpcRuntimeService.exe), the Microsoft Management Console (mmc.exe), and the OPC utility (OPCEnum.exe) must be added to the exceptions list at the application level, and the DCOM port 135 must be enabled at the port-and-protocol level. The following procedure will guide you through the process of making these changes. 1. To edit the firewall settings, open the Start menu, select Control Panel, then Security Center and finally Windows Firewall.
2. Select On to enable the firewall. This is the default setting and is recommended to protect your machine from outside security threats. For troubleshooting purposes, you may want to set the firewall to Off temporarily. This will help you to determine if the firewall configuration is the cause of the communication problems you are experiencing. After the tests, be sure to turn the firewall back on.
- 12 -
Note
If the computer is protected by a corporate firewall or the network is otherwise secured, it may be safe to turn the firewall off permanently. In that case, the rest of the firewall settings in this section are not necessary. 3. Select the Exceptions tab and add all OPC clients and servers to the exception list.
4. To add a program, click Add Program... and select the desired program from the list.
- 13 -
5. If Cyberlogics OPC Server is not on the list, click Browse... and navigate to C:\Program Files\Common Files\Cyberlogic Shared\OPC. There you will find CybOpcRuntimeService.exe, the program you must add to the exception list.
- 14 -
6. You must also add the Microsoft Management Console (mmc.exe) and the OPC utility OPCEnum.exe, both of which are found in the Windows\System32 directory. The mmc.exe application is needed to run the DCOM configuration editor. OPC client applications use OPCEnum.exe to obtain a list of available servers on the local or remote machines. 7. Click Add Port... and enter the information shown in the figure below to add TCP port 135 to the exceptions list. This port is needed to permit DCOM communications.
- 15 -
- 16 -
3. In the tree on the left side, open Console Root, then Component Services and then Computers. 4. Right-click on My Computer and select Properties.
- 17 -
- 18 -
TCP/IP is the most commonly used transport protocol with DCOM. We recommend that you configure all of your client and server machines to use only TCP/IP, and remove other protocols from their DCOM Protocols lists. Doing so will reduce connection timeouts. 7. Select each protocol you want to remove and click the Remove button.
- 19 -
The Default Distributed COM Communication Properties settings will depend on your network configuration. A Domain configuration will have different settings than a Workgroup or mixed configuration. Note Cyberlogics OPC Server and Client allow you to select preconfigured DCOM security settings that override the Default Distributed COM Communication Properties settings. If you decide to use one of these settings, it will not be necessary for you to change the Default Authentication Level or Default Impersonation Level here. Refer to Appendix A: Cyberlogic OPC Product DCOM Configuration for details.
Domain
If the client and server are both members of a Domain, use the following configuration: 9. Select Connect for the Default Authentication Level With Connect authentication, the server authenticates the credentials of the client only when the client connects to the server. Higher levels of authentication could be used, but performance might suffer.
- 20 -
10. Select Identify for the Default Impersonation Level. With the Identify impersonation, the server can obtain the client's identity. The server can impersonate the client to do access-control list (ACL) checks, but it cannot access system objects as the client. This level of impersonation is sufficient for most servers.
Caution!
Remember that the client and server systems must both have User accounts with identical usernames and passwords.
Note
In Windows 2000, the Network Configuration icon will disappear if you set the DCOM security levels to None and Anonymous. The network will still work, but you will have no way to change the IP address of the network card. If you need to edit the IP address, temporarily change the DCOM settings to None and Delegate.
- 21 -
Note
Access permissions specify a list of Users who are granted or denied access to COM applications. Access permissions are divided into local access permission and remote access permission. Users with local access permission may access a COM application running on the same machine as the calling client. Users with remote access permission may access a COM application from other computers across a network connection.
Note
Launch permission is required to start a new COM application. Activation permission is required for a new client to use a COM application, even if the application has already been launched. Launch and activation permissions are divided into local and remote launch and activation permissions. Users with local launch or activation permission can start or use a COM application running on the same machine as the calling client. Users with remote launch or activation permission can start or use a COM application from other computers across a network connection.
- 22 -
Default Permissions
13. In the Access Permissions section, click the Edit Default... button. Note Cyberlogics OPC Server and Client allow you to select preconfigured DCOM security settings that override the Default Access Permissions settings. If you decide to use one of these settings, you need not modify the Default Access Permissions in this section. Refer to Appendix A: Cyberlogic OPC Product DCOM Configuration for details. 14. For each user or group that will participate in OPC communication, check the Allow box for both Local Access and Remote Access. When you are finished, click OK. If the User or Group you want to edit is not listed, refer to Appendix B: Adding Users or Groups for instructions on how to add to the listing.
Caution!
The example shown grants these permissions to Everyone, which includes all authenticated users. You may wish to restrict this to a smaller group. The recommended way to do this is to create a group called OPC Users and add to this group all Users that will execute any OPC server or client. You would then grant the access, launch and activation permissions to the OPC Users group instead of Everyone.
Cyberlogic Technologies, Inc. - 23 -
15. If the tab has a Launch and Activation Permissions section, click its Edit Default... button. Some systems have a Launch Permissions section instead of Launch and Activation Permissions. In such a case, you cannot edit the default Activation Permissions and you can skip this step. 16. For each user or group that will participate in OPC communication, check the Allow box for both Local Activation and Remote Activation. When you are finished, click OK. If the User or Group you want to edit is not listed, refer to Appendix B: Adding Users or Groups for instructions on how to add to the listing. Note The Local Launch and Remote Launch permissions need not be changed because the server-specific settings will provide their own custom permissions.
- 24 -
- 25 -
Caution!
The example above grants these permissions to Everyone, which includes all authenticated users. You may wish to restrict this to a smaller group. The recommended way to do this is to create a group called OPC Users and add to this group all Users that will execute any OPC server or client. You would then grant the access, launch and activation permissions to the OPC Users group instead of Everyone.
- 26 -
3. In the tree on the left side, open Console Root, then Component Services, then Computers, and then DCOM Config. 4. In the right pane, locate the OPC server. For the Cyberlogic OPC Server find CybOpcRuntimeDA and CybOpcServerAE. 5. Right-click on the server and select Properties from the context menu.
- 27 -
Security Tab
This tab allows you to change the launch, activation and access permissions for the server. The settings must be configured to grant these permissions for client applications using this server. No changes are needed for the Configuration Permissions.
- 28 -
- 29 -
8. For each User or Group that will participate in OPC communication, check the Allow box for all permission types: Local Launch, Remote Launch, Local Activation and Remote Activation. When you are finished, click OK. If the User or Group you want to edit is not listed, refer to Appendix B: Adding Users or Groups for instructions on how to add to the listing.
Caution!
The example shown grants these permissions to Everyone, which includes all authenticated users. You may wish to restrict this to a smaller group. The recommended way to do this is to create a group called OPC Users and add to this group all Users that will execute any OPC server or client. You would then grant the access, launch and activation permissions to the OPC Users group instead of Everyone.
- 30 -
Access Permissions
Access permission grants a User or Group the right to communicate to an application. Access permissions are divided into local access permission and remote access permission. Users with local access permission may access a COM application running on the same machine as the calling client. Users with remote access permission may access a COM application from other computers across a network connection. Because the OPC client application will call functions on the OPC server, the security context of the client must permit this. Note Cyberlogics OPC server allow you to select preconfigured DCOM security settings that override the Access Permissions settings. If you decide to use one of these settings, you need not modify the Access Permissions here. Refer to Appendix A: Cyberlogic OPC Product DCOM Configuration for details. 9. In the Access Permissions group, select the Customize option. 10. Click the Edit... button.
11. For each user or group that will participate in OPC communication, check the Allow box for Local Access and Remote Access. When you are finished, click OK. If the User or Group you want to edit is not listed, refer to Appendix B: Adding Users or Groups for instructions on how to add to the listing.
- 31 -
Caution!
The example above grants these permissions to Everyone, which includes all authenticated Users. You may wish to restrict this to a smaller group. The recommended way to do this is to create a group called OPC Users and add to this group all Users that will execute any OPC server or client. You would then grant the access, launch and activation permissions to the OPC Users group instead of Everyone.
Identity Tab
This tab allows you to specify the User account that will provide the security context for the server. There are four options: Recommended: System Account. Most OPC servers, including the Cyberlogic OPC Server run as a service, so the system account is selected by default. In most cases, this setting works well and should not be changed. Alternative: This User. If you have a special situation and need to set the exact security context to be used for the server, select This User. You must specify the desired User and that accounts password in the Password and Confirm Password boxes.
- 32 -
Caution!
The User account you specify for this option must have access to the OPC server configuration file. Do not use: Interactive User and Launching User. The account that will actually be used with these selections is unpredictable, making it impossible to create a reliable configuration.
- 33 -
Caution!
The preconfigured settings selected in the Cyberlogic editors will apply only to the Cyberlogic product. All non-Cyberlogic products must be configured separately. If the other product you are using does not conform to either of the preconfigured settings in the Cyberlogic products, you can choose the Custom selection. This prevents the Cyberlogic software from overriding the system settings. You must then use the DCOM configuration editor to set the appropriate security levels. Refer to the System-Wide DCOM Configuration Issues and Server-Specific DCOM Configuration Issues sections for more information.
- 34 -
Caution!
If you change the selection on this tab, you must restart the Cyberlogic OPC Server for the new settings to take effect. To restart the Server, open the Windows Control Panel, go to Administrative Tools and then Services. Right-click on Cyberlogic OPC Server and select Restart. 3. If the Low or Medium security settings match your client applications settings, select the appropriate radio option. Refer to the Low and Medium sections for details on these settings. 4. If neither of the preconfigured settings are suitable for your installation, you must choose Custom. When the selection is Custom, the server does not override the default security values. Instead, the settings you edit with DCOMCNFG are used. 5. Click the Launch DCOMCNFG... button to edit the security settings manually. If you selected Custom, you must use DCOMCNFG to configure all of the security settings. If you selected Low or Medium, you must use DCOMCNFG to configure all
Cyberlogic Technologies, Inc. - 35 -
of the security settings except for the Cyberlogic OPC Servers access permissions, authentication level and impersonation level. 6. When you are finished, click OK.
Low
The Low selection overrides the default server-specific security values, giving them the following settings: Security Parameter Access Permissions Authentication Level Setting None Description
Impersonation Level
No authentication occurs.
The server can obtain the client's identity. The server can impersonate the client to do access control list (ACL) checks, but it cannot access system objects as the client.
Note
When the Server starts, it will set the security level with the following call: CoInitializeSecurity( NULL, -1, NULL, NULL, RPC_C_AUTHN_LEVEL_NONE, RPC_C_IMP_LEVEL_IDENTIFY, NULL, EOAC_NONE, NULL);
Medium
The Medium selection overrides the default server-specific security values, giving them the following settings:
- 36 -
Setting Packet
All users
Description
Impersonate
Authenticates credentials and verifies that all call data received is from the expected client. The server can impersonate the client while acting on its behalf, but with restrictions. The server can access resources on the same computer as the client. If the server is on the same computer as the client, it can access network resources as the client. If the server is a computer different from the client, it can access only resources that are on the same computer as the server.
Note
When the Server starts, it will set the security level with the following call: CSecurityDescriptor cSecurity; cSecurity.InitializeFromThreadToken( ); CoInitializeSecurity( cSecurity, -1, NULL, NULL, RPC_C_AUTHN_LEVEL_PKT, RPC_C_IMP_LEVEL_IMPERSONATE, NULL, EOAC_NONE, NULL);
- 37 -
Caution!
If you change the selection on this tab, you must restart the Cyberlogic OPC Client for the new settings to take effect. 3. If the Low or Medium security settings match your servers settings, select the appropriate radio option. Refer to the servers Low and Medium sections for details on these settings. 4. If neither of the preconfigured settings are suitable for your installation, you must choose Custom. When the selection is Custom, the client does not override the default security values. Instead, the settings you edit with DCOMCNFG are used. 5. Click the Launch DCOMCNFG... button to edit the security settings manually. If you selected Custom, you must use DCOMCNFG to configure all of the security settings. If you selected Low or Medium, you must use DCOMCNFG to configure all of the security settings except for the Cyberlogic OPC Clients access permissions, authentication level and impersonation level. 6. When you are finished, click OK.
- 38 -
The Select Users, Computers, or Groups dialog box will open. 2. Click the Advanced... button.
The advanced functions will then be available. 3. Click Find Now. 4. Select the desired User or Group from the list at the bottom of the dialog box
- 39 -
5. If you still do not see the User or Group you wish to add, you may need to look in a different location. Click the Locations... button to select the desired location, then repeat the Find Now operation. 6. When you have made your selection, click OK twice to return to the permissions edit screen.
- 40 -
Network Issues
Domain: All systems in the same Domain or have Domains trust each other.
Workgroup: All systems in the same Workgroup; identical user accounts on all systems. Mixed: Workgroup systems must have user accounts identical to those in the Domain. Windows 2000: Install SP3.
Windows XP: Set network access local security setting to Classic. Add TCP port 135, mmc.exe, OPCEnum.exe, CybOpcRuntimeService.exe, and all other OPC clients and servers to the firewall exceptions list. Make TCP/IP the preferred or only DCOM protocol. Enable DCOM. Set Default Authentication and Impersonation to Connect / Identify for Domain configurations, or None / Anonymous for Workgroup and Mixed configurations. For all Users or Groups that will use OPC communication, set defaults to allow Local and Remote Access and Local and Remote Activation.
If Limit editing is available, set limits to allow Local and Remote Access for ANONYMOUS LOGON, and allow Local and Remote Launch and Activation for all Users and Groups that will use OPC communication. For all OPC servers, set Security Permissions to allow Local and Remote Launch, Activation and Access for all Users and Groups that will use OPC communication. Set the Identity to the System account.
- 41 -