Easypact Catalouge 10-11-2011 V1
Easypact Catalouge 10-11-2011 V1
EasyPact CVS
Moulded-case circuit breakers from 100 to 800 A
Catalogue 2011
Do you strain to find a high quality circuit breaker that is simple, flexible, and safe? Have tight project budgets restricted you from choosing the best technology products? Do you need the reach, support and accessibility of a global leader, with the value of a local supplier?
Buildings
2
Industry
Residential
Compact CVS has helped our customers with a value system focused on
Schneider Electric has always believed in customer satisfaction and ensures that we renovate our offers to meet the changing needs of our customers. Now Schneider Electric is happy to announce that
Compact CVS is now EasyPact CVS More Safe , Simple & Reliable
A global environment friendly range from Schneider Electric.
3
EasyPact CVS
Environmentally responsible
n EasyPact CVS is part of the Schneider Electric energy efficiency approach. Designed for easy disassembly and recycling at end of life, EasyPact CVS complies with environmental directives RoHS* and WEEE**, and with ISO 14001 standards, thanks to non - polluting factories. Schneider Electric fully takes into account environmental requirements, starting right from the design phase of every product through to the end of its service life: the materials used for EasyPact CVS are not potentially dangerous to the environment the production facilities are non-polluting in compliance with the ISO 14001 standard the energy dissipated per pole is low, making energy losses insignificant the materials are marked to facilitate sorting for recycling at the end of product service life.
@ @ @ @
Plastic
Copper
Decomposition
EasyPact CVS moulded case circuit breakers and accessories can be recycled and reused optimally.
Energy resources
Recyling center
* RoHS = Restriction of Hazardous Substances ** WEEE = Waste Electrical and Electronic Equipment
EasyPact CVS
from 100 to 800A
Safe
Reliable
Simple
7
Isolation
* 100 to 630 A
Reliable accessories
n Continuous rated shunt coils n Multifunctional Aux./Alarm contact n Unique electrical fault trip indication (SDE)
Current limitation technology
Line load reversibility for entire EasyPact CVS range System upgradeability
n Compact NSX/EasyPact CVS upto 630A have the same foot print & mounting dimensions, helps easy retrofitting and system upgradeability.
* Auxiliaries and accessories are common for MCCBs upto 630A.
Electrical auxiliaries
Compact NSX
EasyPact CVS
Rotary Operating handles
Insulation Monitoring
Control accessories
Earth fault protection (UMGFP)
10
n Only two frame sizes up to 630A n Common accessories for complete range (ON/OFF/Trip Auxiliaries/Shunt/UV etc) n Line load reversibility for entire range n Suitable for class II switchboards
Panel builders
n Isolation as a standard feature enhances safety n Excellent current limiting capability reduces stresses on cables, busbars and loads n Continuous rated accessories increase system reliability n Moduler earth leakage and earth fault protection ensure human/installation protection
End Users
OEMs
n High endurances and maintenance free operation assure continuous performance of machines n Unique common accessories help standardisation of components
Contractors
n Sufficient pole pitch helps to terminate Copper and Aluminum busbars or cables n Easy availability of the product due to less number of frame size n Designed to perform in demanding applications
11
EasyPact CVS
12
EasyPact CVS
General contents
A-1
Installation recommendations
B-1
C-1
Additional characteristics
D-1
Catalogue numbers
E-1
13
TM-D thermal-magnetic trip units ETS 2.3 Microprocessor trip unit and accessories
A-3 A-4
A-5
A-6
A-7
A-8
A-10
A-1
Introduction
General characteristics
DB400000
EasyPact CVS circuit breakers and auxiliaries comply with the following international recommendations: b IEC 60947-1: general rules b IEC 60947-2: circuit breakers b IEC 60947-3: switch-disconnectors
Pollution degree
EasyPact CVS circuit breakers are certified for operation in pollution-degree III environments as defined by IEC standards 60947-1 and 60664-1 (industrial environments).
9
Standardised characteristics indicated on the rating plate: 1 Type of device: frame size and breaking capacity class 2 Ui: rated insulation voltage. 3 Uimp: rated impulse withstand voltage. 4 Ics: service breaking capacity. 5 Icu: ultimate breaking capacity for various values of the rated operational voltage Ue 6 Ue: operational voltage. 7 Colour label indicating the breaking capacity class. 8 Suitable for Isolation symbol. 9 Reference standard. Note: when the circuit breaker is equipped with an extended rotary handle, the door must be opened to access the rating plate.
Frame 1 CVS 100 CVS 160 CVS 250 Frame 2 CVS 400 CVS 630 Frame 3 CVS 800*
Climatic withstand
EasyPact CVS circuit breakers have successfully passed the tests defined by the following standards for extreme atmospheric conditions: b IEC 60068-2-1: dry cold (-55C) b IEC 60068-2-2: dry heat (+85C) b IEC 60068-2-30: damp heat (95 % relative humidity at 55C) b IEC 60068-2-52 severity level 2: salt mist.
Environment
EasyPact CVS respects the European environment directive EC/2002/95 concerning the restriction of hazardous substances (RoHS). All EasyPact CVS production sites have set up an ISO 14001 certified environmental management system.
Ambient temperature
EasyPact CVS circuit breakers can be used between -25C and +70C. For temperatures higher than 40C (65C for circuit breakers used to protect motor feeders), devices must be derated (see page B-2). b Circuit breakers should be put into service under normal ambient, operatingtemperature conditions. Exceptionally, the circuit breaker can be put into service when the ambient temperature is between -35C and -25C. b The permissible storage-temperature range for EasyPact CVS circuit breakers in the original packing is -50C and +85C.
All EasyPact CVS circuit breakers are suitable for isolation as defined in IEC standard 60947-2: b The isolation position corresponds to the O (OFF) position. b The operating handle cannot indicate the OFF position unless the contacts are effectively open. b Padlocks cannot be installed unless the contacts are open. Installation of a rotary handle does not alter the reliability of the position-indication system. The isolation function is certified by tests guaranteeing: b The mechanical reliability of the position-indication system b The absence of leakage currents b Over voltage withstand capacity between upstream and downstream connections. The tripped position does not ensure isolation with positive contact indication. Only the OFF position guarantees isolation.
IEC 60947-2
All EasyPact CVS circuit breakers are class II front face devices. They can be installed through the door of class II switchboards (as per IEC standards 61140 and 60664-1) without downgrading switchboard insulation. Installation requires no special operations, even when the circuit breaker is equipped with a rotary handle.
Degree of protection
The following indications are in accordance with standards IEC 60529 (IP degree of protection) and IEC 62262 (IK protection against external mechanical impacts). Bare circuit breaker: b with toggle: IP40, IK07 front face b with extended rotary handle: IP 55, IK08 Circuit breaker installed in a switchboard: b with toggle: IP40, IK07 front face b with extended rotary handle: IP 55, IK08 A-2
Protection ...........................................................................................
TM-D trip units are used mainly in electrical distribution applications for protection of cables supplied by transformers.
Short-circuit protection with a fixed or adjustable pick-up Im that initiates instantaneous tripping if exceeded. b TM-D: fixed pick-up, Im, for 16 to 250 A ratings and adjustable from 5 to 10 x In for 400 A ratings, 4 to 8 x In for 600 A rating.
Protection versions
b v b v v
DB400003
TM-D thermal-magnetic trip units can be used on EasyPact CVS100-630 circuit breakers with performance levels B/F/N.
3-pole: 3P 3D: 3-pole frame (3P) with detection on all 3 poles (3D) 4-pole: 4P 3D: 4-pole frame (4P) with detection on 3 poles (3D). 4P 4D: 4-pole frame (4P) with detection on all 4 poles (same threshold for phases and neutral).
TM16D to 250D
16
b -
TM320D to 630D
50
b -
In at 40 C (1)
CVS100 CVS160 CVS250 CVS400 CVS630
25
b -
32
b -
40
b -
63
b -
80 100
b b b -
125
b -
160
b b
200
b
250
b
b fixed 190 300 400 500 500 500 640 800 800 1250 1250 2000 2500
b -
Magnetic protection
Pick-up (A) accuracy 20 % Im CVS100 CVS160/250 CVS400 CVS630 adjustable
Thermal protection
Pick-up (A) tripping between 1.05 and 1.20 Ir Ir = In x ...
Neutral protection
Unprotected neutral Fully protected neutral 4P 3D 4P 4D no detection 1 x Ir
(1) For temperatures greater than 40C, the thermal protection characteristics are modified. See the temperature derating table on page B-2. * 630 A @ 30C Note: All the trip units have a transparent lead-sealable cover that protects access to the adjustment dials.
A-3
Protection ...........................................................................................
The protection functions can be set using the adjustment dials.
Overload protection
Long-time protection with an adjustable threshold and fixed tripping delay: b Ir base setting (6-position dial from 0.5 to 1)
Short-circuit protection
Short-time and instantaneous protection: b short-time protection with an adjustable pick-up and fixed tripping delay b instantaneous protection with fixed pick-up.
On 4-pole circuit breakers, neutral protection is set using a three-position switch to 4P 3D (neutral unprotected), 4P 3D + N/2 (neutral protection at 0.5 In) or 4P 4D (neutral protection at In).
Trip units
Ratings (A) of circuit breaker Circuit breaker In 20 to 70 C CVS400 F/N CVS630 F/N Ir = In x
ETS 2.3
400 b 630 b
at 1.5 x Ir at 6 x Ir at 7.2 Ir
0.5...1 adj., 6 settings xed 90...180 5...7.5 3.2...5.0 2... 10 adj, 8 settings xed y 40 y 60 11 no protection 0.5 x Ir 1 x Ir Yes Yes
Thermal memory
Test equipment for ETS electronic trip unit Mini test kit
The mini test kit is a portable unit requiring no external power supply, used to check operation of the electronic trip unit and circuit breaker tripping. It connects to the test connector on the front of the circuit breaker. Required power source: five 9 V alkaline batteries (not supplied).
The portable test kit is used to check all aspects of the protection functions: b long time protection b short time protection b instantaneous protection b earth-fault protection. Required power source: 110 or 220 V AC, 50/60 Hz.
A spare test plug and wiring kit are available for this offer.
Earth-leakage protection
PB106449
Vigi CVS100/160/250
105 x 236 x 86 140 x 236 x 86 2.5 3.2
Vigi CVS400/630
135 x 355 x 110 180 x 355 x 110 8.8 10.8
PB103580-36
Type
Number of poles CVS100 CVS160 CVS250 CVS400 CVS630 Sensitivity In (A)
Vigi ME
3, 4 (1) b b fixed fixed < 40 < 40 200...440
Vigi MH
3, 4 (1) b b b adjustable 0.3 0.03 - 0.3 - 1 - 3 - 10 adjustable 0 - 60 (2) - 150 (2) - 310 (2) < 40 < 140 < 300 < 800 200... 440 - 440...550
Vigi MB
3, 4 (1) b b adjustable 0.3 - 1 - 3 - 10 - 30 adjustable 0 - 60 - 150 - 310 < 40 < 140 < 300 < 800 200...440 - 440...550
Protection characteristics
1 2 3 4 Sensitivity setting Time-delay setting (for selective earth-leakage protection). Lead-seal fixture for controlled access to settings. Test button simulating an earth-fault for regular checks on the tripping function 5 Reset button (reset required after earth-fault tripping). 6 Rating plate
Time delay Intentional delay (ms) Max. break time (ms) Rated voltage V AC 50/60 Hz
(1) Vigi 3P modules may also be used on 3P circuit breakers used for two-phase protection. (2) If the sensitivity is set to 30 mA, there is no time delay, whatever the time-delay setting.
Operating safety
The Vigi module is a user safety device. It must be tested at regular intervals (every 6 months) via the test button.
A-5
EasyPact CVS Ground Fault Protection is meant for human safety and to prevent fires due to low level f aults resulting from a deterioration of electrical insulation or high resistive faults.
Building housing inflammable or explosive material Line voltage to ground exceeds 150V AC Electrical equipments like welding sets Electrical equipments used in close Proximity of water/other liquids and metallic object b Cable protection when distance between source and load is high Current sensitivity required Rated voltage, Rated current and frequency Operation time Detection device and protection device co-ordination
n n n n n n
Adjustable earth fault sensitivity selection 10 to 60% Adjustable time delay lnst / 0.5 - 3 Sec. System healthiness check through LED indication Individual fault indication for OL, SC, EF when used with Compact NSX (Optional) Individual fault indication for OL/SC, EF when used with EasyPact CVS (Optional) Test facility to check healthiness of earth fault protection system without tripping MCCB n Suitable for 3P3W & 3P4W electrical distribution network
Unique Modular Ground Fault (UMGFP) system is suitable for EasyPact CVS / Compact NSX MCCBs
Ir selection in RM
32, 40, 50, 63, 80, 100 125, 160, 200, 250 400, 630 800
0.5 to 3 Sec. /Instantaneous 0.5 to 3 Sec. /Instantaneous 0.5 to 3 Sec. /Instantaneous 0.5 to 3 Sec. /Instantaneous
Overload setting
Ground Fault Protection Sealing Stud Time Delay Selector switch (2 step setting)
CT details
A-6
Motor protection
DB400006
Circuit breakers with an MA trip unit are combined with a thermal relay and a contactor or a starter.
Protection
Short-circuit protection with an adjustable pick-up Im that initiates instantaneous tripping if exceeded. b Im = In x ... is set on an adjustment dial in multiples of the rating: v 6 to 14 x In (2.5 to 100 A ratings) v 9 to 14 x In (150 to 220 A ratings) v 6 to 13 x In (320 to 500 A ratings) CVS100 to 630 circuit breakers, equipped with an MA magnetic trip unit with adjustable thresholds, offer: - short-circuit protection - suitability for isolation. CVS100 to 630 circuit breakers with trip unit are supplied ready-assembled.
Protection version
b 3-pole (3P 3D): 3-pole frame (3P) equipped with detection on all 3 poles (3D).
50
MA trip units
Ratings (A)
Circuit breaker
In at 65 C
CVS100 CVS160 CVS250 CVS400 CVS630
2.5
b setting 6...14 x ln -
6.3
b -
12.5
b -
25
b -
50
b -
100
b b -
150
b b setting 9...14 x ln -
220
b -
320
b setting 6...13 x ln
500
b
A-7
Introduction
PB106447
Common characteristics
Rated voltages Insulation voltage (V) Impulse withstand voltage (kV) Operational voltage (V) Suitability for isolation Utilisation category Pollution degree Ui Uimp Ue 690 8 415 yes A 3
Circuit breakers
Rated current (A)
EasyPact CVS100/160/250
lcu
PB106448
In/2 In
Protection
Short-circuit protection Overload/short-circuit protection Magnetic only Thermal magnetic electronic Micro processor with neutral protection (Off-0.5-1) By UMGFP By Vigi module
Connections
Connection terminals Large Cu or Al cables * 630 A @ 30C Pitch Cross-section
A-8
CVS100
100 3, 4 B F 40 25 70 36
CVS160
160 3, 4 B F 40 25 70 36
CVS250
250 3, 4 B F 40 25 70 36
CVS400
400 3, 4 F N 40 36 70 50
CVS630
630 3, 4 F N 40 36 70 50
b b b b
b b b b
b b b b
b b b b b b
b b* b b b b
140 x 255 x 110 185 x 255 x 110 6.05 7.90 45/52.5 mm 45/70 mm 4 x 240
140 x 255 x 110 185 x 255 x 110 6.2 8.13 45/52.5 mm 45/70 mm 4 x 240
A-9
EasyPact CVS 800A MCCBs are available in 3P/4P version with 35/50kA
breaking performances with Ics = 100% Icu. EasyPact CVS comes with host of features including adjustable overload, short circuit setting, line load reversibility. b Ics=100% Icu. b Adjustable over load setting (0.8 to 1 x In) b Adjustable short circuit setting for individual phase (3.5 to 10 In) b Line load reversibility
CVS 800
Overload protection (thermal)
Tripping threshold (A) In Adjustable 0.8...1 x In Adjustable 3.5...10 In
Auxiliary contact with 1C/O & 2 C/O options. Alarm contact with 1C/O & 2 C/O options. Shunt trip coil. Under voltage coil. Direct and Extended Rotary Handle. Unique modular ground fault protection for 3 phase 3 wire and 3 phase 4 wire systems. Protection of distribution system EasyPact CVS 800 A
CVS 800 3/4 b b 800 690 8 415
AC 50/60 Hz
F
35 100% A 8000 2500
N 50
In
Protection
Overload release setting (A) Adjustable Ir(In x ...) Short Circuit Protection Short Circuit Release setting Earth Fault Protection* By UMGFP GFP Release setting = 10-60% of In Time Delay Setting (0.5 - 3 Sec./Inst.) Isd (Ir x...)
Thermal Magnetic
b Centralised 0.8..1 b 3.5 to 10 (independent adjustment of each phase) b b b b b b b b b b 40 300*2 b b WXHXD Weight(kg) (mm) (mm) 3 /4Pole 3Pole 4Pole 210 x 274 x 103 280 x 274 x 103 10.3/13.7
Installation Accessories
Spreaders Phase Barriers
A-10
Connection
Interphase barriers
Cable connectors
Rear connectors
Electrical auxiliaries
Indication contact
Voltage release
cat.A
Insulation Monitoring
Control accessories
Earth leakage protection (VigiCVS) Direct rotary handle Extended rotary handle
A-11
CVS circuit breakers may be installed horizontally, vertically or flat on their back, without derating performance levels.
Fixed circuit breakers are designed for standard connection using bars or cables with lugs. Bare-cable connectors are available for connection to bare copper or aluminium cables.
DB400009 DB400010 DB400011
DB400012
Mounting on a backplate.
Mounting on rails.
Front connection
Fixed circuit breakers are designed for standard front connection using bars or cables with lugs. Cable connectors are available for bare cables. Rear connection is also possible.
DB400013
DB112169
EasyPact CVS100 to 630 come with terminals comprising snap-in nuts with screws: b EasyPact CVS100: M6 nuts and screws. b EasyPact CVS160/250: M8 nuts and screws b EasyPact CVS400/630: M10 nuts and screws. These terminals may be used for: b direct connection of insulated bars or cables with lugs b terminal extensions. Interphase barriers or terminal shields are recommended. They are mandatory for certain connection accessories (in which case the interphase barriers are provided).
Bars
Insulated bar.
DB112170
When the switchboard configuration has not been tested, insulated bars are mandatory.
Crimp lugs
DB112171
There are two modules of lugs, for aluminium and copper cables. Interphase barriers or long terminal shields must be used with narrow lugs. The lugs are supplied with interphase barriers.
Small lug for Al cables. EasyPact CVS circuit breaker Copper cables size (mm2) crimping Aluminium cables size (mm2) crimping 100/160/250 400/630 150, 185 240, 300 hexagonal barrels or punching 150, 185 240, 300 hexagonal barrels
DB112172
DB112173
DB112177
Terminal extensions
Spreaders.
Extensions with anti-rotation ribs can be attached to the standard terminals to provide numerous connection possibilities in little space: b straight terminal extensions b right-angle terminal extensions
Spreaders
Spreaders may be used to increase the pitch: b CVS100 to 250: the 35 mm pitch can be increased to 45 mm b CVS400/630: the 45 mm pitch can be increased to 52 or 70 mm. Bars, cable lugs or cable connectors can be attached to the ends.
A-12
DB400014
DB112314
Bare cables
Bare-cable connectors may be used for both copper and aluminium cables. 1-cable connectors for EasyPact CVS100 to 250 The connectors snap directly on to the device terminals or are secured by clips to right-angle and straight terminal extensions as well as spreaders.
Bare cable.
1-cable connectors for EasyPact CVS400 to 630 The connectors are screwed directly to the device terminals. 2-cable connectors for EasyPact CVS100 to 250 and 400/630 The connectors are screwed to device terminals or right-angle terminal extensions. Maximum size of cables depending on the type of connector
EasyPact CVS circuit breaker Steel connectors 1.5 to 95 mm2 120 to 185 mm2 2 cables 50 to 120 mm2 2 cables 35 to 240 mm2 Aluminium connectors 25 to 95 mm2 100/160 b b b b b b b b b b b 250 400 630
DB112316
DB112317
DB112315
DB111326
35 to 300 mm2
CVS400/630.
DB400015
DB111330
Four positions.
Two lengths.
Rear connection
Escutcheons are an optional feature mounted on the switchboard door. They increase the degree of protection to IP40, IK07. Protection collars maintain the degree of protection, whatever the position of the device (connected, disconnected).
DB400030
Escutcheon for toggle without and with access to the trip unit.
DB400031
A-13
EasyPact CVS100/160/250
DB115583
Rotary handle
Standard
OF1 SD MN / MX
OF2 SDE
All EasyPact CVS100/160/250 circuit breakers have slots for the electrical auxiliaries listed below. 5 indication contacts (see page A-15) b 2 ON/OFF (OF1 and OF2) b 1 trip indication (SD) b 1 fault-trip indication (SDE) b 1 earth-fault indication (SDV), when the device is equipped with a Vigi module. 1 remote-tripping release (see page A-16) b either 1 MN undervoltage release b or 1 MX shunt release. All these auxiliaries can be installed with a rotary handle. The illustration shown (TMD, MA standard) indicates auxiliary possibilities depending on the type of trip unit.
SDV
EasyPact CVS400/630
DB115590
Rotary handle
Standard
SD SDE
OF4
All EasyPact CVS400/630 circuit breakers have slots for the electrical auxiliaries listed below. 6 indication contacts (see page A-15) b 4 ON/OFF (OF4) b 1 trip indication (SD) b 1 fault-trip indication (SDE) b 1 earth-fault indication (SDV), when the device is equipped with a Vigi module. 1 remote-tripping release (see page A-16) b either 1 MN undervoltage release b or 1 MX shunt release. All these auxiliaries can be installed with a rotary handle. The illustration shown (TMD, MA and ETS 2.3 standard) indicates auxiliary possibilities depending on the type of trip unit.
SDV
A-14
One contact model provides circuit-breaker status indications (OF - SD - SDE - SDV).
These common-point changeover contacts provide remote circuit-breaker status information. They can be used for indications, electrical locking, relaying, etc. They comply with the IEC 60947-5 international recommendation.
Functions
Breaker-status indications, during normal operation or after a fault A single type of contact provides all the different indication functions: b OF (ON/OFF) indicates the position of the circuit breaker contacts b SD (trip indication) indicates that the circuit breaker has tripped due to: v an overload v a short-circuit v an earth fault (Vigi) v operation of a voltage release v operation of the push to trip button v disconnection when the device is ON. The SD contact returns to de-energised state when the circuit breaker is reset. b SDE (fault-trip indication) indicates that the circuit breaker has tripped due to: v an overload v a short-circuit v an earth fault (Vigi) b SDV indicates that the circuit breaker has tripped due to an earth fault. It returns de-energised state when the Vigi module is reset.
DB125549
Indication contacts.
Installation
b OF, SD, SDE and SDV functions: a single type of contact provides all these different indication functions, depending on where it is inserted in the device. The contacts clip into slots behind the front cover of the circuit breaker (or the Vigi module for the SDV function). The SDE function on a CVS100 - 630 A equipped with a magnetic, thermal-magnetic or ETS2.3 trip unit requires the SDE adaptor.
Standard
All 6 100 mA at 24 V DC AC12 AC15 DC12 DC14 6 6 6 6 6 6 6 5 4 2 6 2.5 0.6 0.3 1 0.2 0.05 0.03 -
Low level
OF, SD, SDE, SDV 5 1 mA at 4 V DC AC12 AC15 DC12 DC14 5 5 5 5 5 5 3 3 2.5 2 1.5 5 2.5 0.6 0.3 1 0.2 0.05 0.03 -
220/240 V AC 380/440 V AC
A-15
DB125550
MN undervoltage release
b This release trips the circuit breaker when the control voltage drops below a tripping threshold b The tripping threshold is between 0.35 and 0.7 times the rated voltage b Circuit breaker closing is possible only if the voltage exceeds 0.85 times the rated voltage.
MX or MN voltage release.
Characteristics
Power supply V AC V DC Opening Closing 50/60 Hz: 24 - 48 - 100/130 - 200/240 50 Hz: 380/415 60 Hz: 208/277 12 - 24 - 30 - 48 - 60 - 125 -250 0.35 to 0.7 Un 0.85 Un 0.85 to 1.1 Un Pick-up: 10 - Hold: 5 50
DB115605
Failsafe opening 0
0.35
Failsafe closing 0
Closing conditions of the MN release.
0.85
1.1 Un
A time delay unit for the MN release eliminates the risk of nuisance tripping due to a transient voltage dip lasting y 200 ms. For shorter micro-outages, a system of capacitors provides temporary supply to the MN at U > 0.7 to ensure non tripping. The correspondence between MN releases and time-delay units is shown below.
Power supply Unit with fixed delay 200 ms 48 V AC 220 / 240 V AC Unit with adjustable delay y 200 ms 48 - 60 V AC/DC 100 - 130 V AC/DC 220 - 250 V AC/DC Corresponding MN release 48 V DC 250 V DC 48 V DC 125 V DC 250 V DC
PB103752-32
DB115607
MX shunt release
The MX release opens the circuit breaker via an impulse-type (u 20 ms) or maintained order.
D2 MN D1 MN release with a time-delay unit. Wiring diagram for emergency-off function with MN + time-delay unit.
When the MX release is supplied, it automatically opens the circuit breaker. Opening is ensured for a voltage U u 0.7 x Un.
V AC V DC Operating range Consumption (VA or W) Response time (ms) 50/60 Hz: 24 - 48 - 100/130 - 200/240 50 Hz: 380/415 60 Hz: 208/277 12 - 24 - 30 - 48 - 60 - 125 -250 0.7 to 1.1 Un Pick-up: 10 50
Possible opening 0
When the circuit breaker has been tripped by an MN or MX release, it must be reset before it can be reclosed. MN or MX tripping takes priority over manual closing. In the presence of a standing trip order, closing of the contacts, even temporary, is not possible. Connection using wires up to 1.5mm2 to integrated terminal blocks.
Note: circuit breaker opening using an MN or MX release must be reserved for safety functions. This type of tripping increases wear on the opening mechanism. Repeated use reduces the mechanical endurance of the circuit breaker by 50 %.
A-16
There are two types of rotary handle: b direct rotary handle b extended rotary handle.
PB106453
Degree of protection IP40, IK07. The direct rotary handle maintains: visibility of and access to trip-unit settings suitability for isolation indication of the three positions O (OFF), I (ON) and tripped access to the "push to trip" button.
Device locking The rotary handle facilitates circuit-breaker locking. b Padlocking: v standard situation, in the OFF position, using 1 to 3 padlocks, shackle diameter 5 to 8 mm, not supplied
EasyPact CVS with a rotary handle.
Degree of protection IP56, IK08. The extended rotary handle makes it possible to operate circuit breakers installed at the back of switchboards, from the switchboard front. It maintains: b visibility of and access to trip-unit settings b suitability for isolation b indication of the three positions O (OFF), I (ON) and tripped.
Padlocking locks the circuit-breaker handle and disables door opening: b standard situation, in the OFF position, using 1 to 3 padlocks, shackle diameter 5 to 8 mm, not supplied
b A unit that replaces the front cover of the circuit breaker (secured by screws). b An assembly (handle and front plate) on the door that is always secured in the same position, whether the circuit breaker is installed vertically or horizontally. b An extension shaft that must be adjusted to the distance. The min/max distance between the back of circuit breaker and door is: v 185600 mm for EasyPact CVS100 to 250 v 209600 mm for EasyPact CVS 400/630.
PB106455
An additional accessory interlocks two devices with rotary handles to create a sourcechangeover system. Closing of one device is possible only if the second is open. This function is compatible with direct or extended rotary handles. Up to three padlocks can be used to lock in the OFF or ON position.
PB106456
A-17
DB400025
DB400026
Locks
Locking in the OFF position guarantees isolation as per IEC 60947-2. Padlocking systems can receive up to three padlocks with shackle diameters ranging from 5 to 8 mm (padlocks not supplied). Certain locking systems require an additional accessory. Control device
Toggle
Function
Lock in OFF position
Lock in OFF or ON Padlock position Direct handle rotaryStandard Lock in b OFF position b OFF or ON position (1) Padlock Keylock
Padlock Lock in b OFF position (1) b OFF or ON position with door opening prevented (2) Lock in OFF position
b OFF or ON position (1)
Padlock Keylock
inside the switchboard (1) Following a simple modification of the mechanism. (2) Unless door locking has been voluntarily disabled. Rotary-handle locking using a keylock.
DB400028
DB400029
Sealing accessories
DB400017 DB400019 DB400018
Toggle control
DB115033
Sealing accessories.
Rotary handle
A-18
Installation recommendations
EasyPact CVS
Installation recommendations
Contents
Functions and characteristics A-1 B-2
B-3 B-4
B-1
Installation recommendations
100 to 630A
When thermal-magnetic trip units are used at ambient temperatures other than 40 C, the Ir pick-up is modified.
DB400035
(m) 2000
Altitude does not significantly affect the characteristics of EasyPact CVS circuit breakers up to 2000 m. Above this altitude, it is necessary to take into account the decrease in the dielectric strength and cooling capacity of air.
Vibrations
CVS devices resist electromagnetic or mechanical vibrations. Tests are carried out in compliance with standard IEC 60068-2-6 for the levels required by merchant-marine inspection organisations (Veritas, Lloyds, etc.): b 2 to 13.2 Hz: amplitude 1 mm b 13.2 to 100 Hz: constant acceleration 0.7 g. Excessive vibration may cause tripping, breaks in connections or damage to mechanical parts.
Degree of protection
CVS circuit breakers have been tested for degree of protection (IP) and mechanical impact protection (IK). See page A-2. Electronic trip units are not affected by variations in temperature. If the trip units are used in hightemperature environments, the ETS setting must nevertheless take into account the temperature limits of the circuit breaker.
DB115053
(A)
110 100 90
The overload protection is calibrated at 40 C in the lab. This means that when the ambient temperature is less than or greater than 40 C, the Ir protection pick-up is slightly modified. To obtain the tripping time for a given temperature: b see the tripping curves for 40 C (see pages D-2 and D-3) b determine tripping times corresponding to the Ir value (thermal setting on the device), corrected for the ambient temperature as indicated in the tables below.
Settings of CVS100 to 630 equipped with TM-D trip units as a function of the temperature
The table indicates the real Ir (A) value for a given rating and temperature. Rat. Temperature (C) (A) 10 15 20 25
16
10 20 30 40 50 60 70 (C)
80
30
17 26.3 33.6 42 53 67 84 105 131 168 210 263
35
16.6 25.6 32.8 41 51 65 82 128 164 205 256
40
16 25 32 40 50 63 80 125 160 200 250 400
45
15.6
50
55
23.5 30 37 46 57 92.0 116 148 185 231
60
23 36 44 55 70.7 89 113 144 180 225
65
22 35 43 53 68 86
70
13.8 21 28.5 33.5 41 50 65 83
15.2 14.8
14.5 14 29.5 29
25 32 40 50 63 80
24.5 24 31.3 30.5 39 49 61 78 97 122 156 195 244 390 38 47 59 95 119 152 190 238
DB400102
DB400102
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1 TM80D/100D : Im = 8 x In
75.5 73
100 114 125 144 160 184 200 230 250 288
102.5 100
320 364.9 357.8 350.5 343.2 335.6 327.9 320 400 456.6 447.7 438.6 429.2 419.7 410 600 672 660.5 648.9 637 630 500 558.6 549.2 539.7 530.1 520.3 510.2 500 612.6 600
t < 10 ms
The table below indicates the maximum long-time (LT) protection setting Ir (A) depending on the ambient temperature. Type of Rating (A) Temperature (C) device 40 45 50 55 60 65 70
CVS400 Fixed CVS630 Fixed 400 630 400 630 400 615 400 600 390 585 380 570 370 550 360 535
values.
B-2
Installation in switchboards
General rules
When installing a circuit breaker, minimum distances (safety clearances) must be maintained between the device and panels, bars and other protection devices installed nearby. These distances, which depend on the ultimate breaking capacity, are defined by tests carried out in accordance with standard IEC 60947-2. If installation conformity is not checked by type tests, it is also necessary to: b use insulated bars for circuit-breaker connections b segregate the busbars using insulating screens. For CVS100 to 630 devices, terminal shields and interphase barriers are recommended and may be mandatory depending on the operating voltage of the device and type of installation (fixed, withdrawable, etc.).
Power connections
The table below indicates the rules to be respected for CVS100 to 630 devices to ensure insulation of live parts for fixed devices.
DB400039
No insulating accessory
DB115059
Interphase barriers
DB115060
With:
Insulated bars
Possible (instead of ph. Recommended barriers) Possible for CVS100 to 250 Possible (instead of ph. barriers)
Recommended
(1) Long terminal shields provide a degree of protection of IP40 (ingress) and IK07 (mechanical impact).
B-3
Installation recommendations
100 to 630A
Installation in switchboards
Installation example
Safety clearance
Minimum distance between two adjacent circuit breakers
DB400046 DB400047
A1
Minimum distance between circuit breaker and top, bottom or side panels
DB400048 DB400049 DB400050
D1
D1 D1
D1
D2
C1
Clearance (mm) Between Between device and sheet metal devices Painted sheet metal Bare sheet metal
A1 C1 0 0 0 D1 30 0 0 D2 30 0 0 C1 5 5 0 D1 40 0 0 D2 40 0 0
U y 440 V for devices equipped with: b no accessories b interphase barriers b long terminal shields
0 0 0
DB400051
Spacing y 60 mm
F1
F2
F2 Bars
F1 F2 F1 F2 U < 440 V 350 350 80 80 These clearances can be reduced for special installations as long as the configuration is checked by tests.
Live busbars.
B-4
C-2 C-3
Front-panel accessories
EasyPact CVS100 to 630
C-4
Front-panel cutouts
EasyPact CVS100 to 630
C-5
Power connections
EasyPact and Vigi CVS100 to 630 Connection of insulated bars or cables with lugs to EasyPact and Vigi CVS100 to 630 Connection of bare cables to EasyPact and Vigi CVS100 to 630
C-11
C-12
D-1 E-1
C-1
Dimensions
DB400055 DB400056
3P
DB400057
4P
DB400058
A4 A3 A A1 X A A2 A3 A4 A2 X X
C1 C2
C3
B1
B B2
Y Y Long terminal shields (also available for CVS400/630 spreaders with 52.5 mm pitch: B1 = 157.5 mm, B2 = 210 mm).
Mounting
On backplate
DB400059
CVS100 to 250
3P
DB111411
CVS400/630
3P
DB112066
CVS100 to 630
4P
DB112067
F1
F1 F2
F1
F1 F2
F1
F1 F1 F2 F3
F1
F1
E4 E2 E1 E3 X
2 6
T(1)
4 6
4 6
On rails
DB400063
3P
DB111412
3P
DB112069
4P
DB112070
F1 F2 U E2 E1 X
F1 F2
F3 F2
2 6
4 6
4 6
G4 G5
G3 G2 G1 Z
C-2
Dimensions
DB400067 DB400068
3/4P
DB400069
3/4P
DB400070
CVS100 to 250
CVS400/630
A4 A A3 A2 X X X
A6 A5
A8 A7 A9
C1 C2 C3 Z
B1 B2 Y
B B1 B2 Y
Mounting
On backplate
DB400071
CVS100 to 250
3P
F1 F1 F2 F1
DB111420
CVS400/630
3P
F1 F1 F2 F1
DB112078 DB112079
CVS100 to 630
4P
F1 F1
F3
F1 F2
X E6 E1 E8 E7
E5
T(1) (1) The T holes are required for rear connection only.
3 6
6 6 Y
6 6
On rails
DB400075
3P
DB111421
3P
DB112081 DB112082
4P
F1 F2 F3 F2
F1 F2 U X E6 E5 E1
Y Type CVS100/160/250 CVS400/630 Type CVS100/160/250 CVS400/630 A A1 80.5 161 127.5 255 E2 E3 125 70 200 113.5 A2 94 142.5 E4 140 227 A3 A4 145 178.5 200 237 E5 E6 137.5 200 200 300 A5 155.5 227.5 E7 145 213.5
3 6 A6 236 355 E8 215 327 A7 169 242.5 F1 35 45 A8 220 300 F2 17.5 22.5 A9 253.5 337 F3 70 90
6 6
6 6
B 52.5 70 G1 95 -
B1 105 140 G2 75 -
C1 81 95.5 G4 23 -
C2 86 110 G5 17.5 -
C3 126 168 T 24 32
E1 62.5 100 U y 32 y 35
C-3
Front-panel accessories
EasyPact CVS100 to 630
M2 M3
A1 D1 D2
A2
DB115012
A3 B1 Y 3.5
6.5
For Vigi
DB400097 DB115018 DB115019
79 X
DB115020
64
69 Y
3.5
6.5
Type
CVS100/160/250 CVS400/630
A1
91 123
A2
114 164
A3
101 151
B1
157 189
M2
115 155
M3
102 142
C-4
Front-panel cutouts
EasyPact CVS100 to 630
CVS100 to 250
DB400117
CVS400/630
76 29
116 41.5
P3 Z
Y R1
Y R1
102 54.5
X 90
175
P3 Z
47.5 95 Y
63.5 127
Y
Type
CVS100/160/250 CVS400/630
P3
88 112
R
14.5 31.5
R1
29 63
CVS100 to 250
DB400124 DB400125
CVS400/630
X 85.5
148 38 38 P3 Z 29 Y 14.5 29 32 Y
X 85.5
148 38 38 P3 Z 29 Y 14.5 29 32 Y
C-5
Power connections
Connection locations
DB400134 DB400135
C1
B1
B1
B1
A1 X A2 A3 X
C2 Z
Type
CVS100/160 CVS250 CVS400/630
A1
A2
B1
35 35 45
C1
19.5 21.5 26
C2
19.5 19.5 26
Type
CVS100/160 + Vigi CVS250 + Vigi CVS400/630 + Vigi
A1
A3
B1
35 35 45
C1
19.5 21.5 26
C2
21.5 21.5 26
CVS400/630
DB400138
10.5
14
113.5 X
DB400137
13
70 6
20
CVS400/630
DB116108
30
14
113.5 8 X
C-6
Power connections
CVS100 to 250
63
22
70
DB400139
70 X X
DB115455
CVS400/630
DB115454
Z 46.5
14
113.5 X
113.5 X
X 70
41
CVS400/630
DB115460
4 20.5
61
34
70
113.5 X X
(b) CVS250.
4 Z 30 41
70 X
C-7
Power connections
3P
DB400143
4P CVS100 to 250
DB400144
E3 E2 E2 E2
E2
E2
F2
DB400145
E1
C3
F1
X
Z
CVS400/630
Y Y
C4
Type
CVS100/160 CVS250 CVS400/630
C3
23.5 25.5 -
C4
44
E1
114 114 135 170
E2
45 45 52.5 70
E3
159 159 187.5 240
F1
100 100
F2
11 11
X Z
152.5 15 166 15
C-8
Power connections
Connection of insulated bars or cables with lugs to EasyPact and Vigi CVS100 to 630
DB400013 DB115653
Dimensions
Bars L (mm) I (mm) d (mm) e (mm) (mm) L (mm) (mm)
CVS100
y 25 d + 10 y 10 y6 6.5 y 25 6.5 10 5/5
CVS160/250
y 25 d + 10 y 10 y6 8.5 y 25 8.5 15 5/5
CVS400/630
y 32 d + 15 y 15 3 y e y 10 10.5 y 32 10.5 50 20/11
DB115654
(1) Tightening torque on the circuit breaker for lugs or bars. (2) Tightening torque on fixed devices for rear connectors. L Lug.
terminal
DB115655
Dimensions
L (mm) l (mm) d (mm) e (mm) (mm) L (mm) Lugs (mm) Torque (Nm) (1) Bars
Tinned copper
400 I L e
d L
(1) Tightening torque on the circuit breaker for spreaders or terminal extensions.
Tinned copper
Spreaders and straight, right-angle, 45, double-L and edgewise terminal extensions are supplied with flexible interphase barriers.
Connection with accessories to CVS400 and 630 (IEC 228) Accessories for CVS400 and 630
DB115657
45 mm 52.5 or 70 mm With spreaders Bars L (mm) l (mm) d (mm) e (mm) (mm) L (mm) (mm) Torque (Nm) (1) y 40 d + 15 y 20 3 y e y 10 12.5 y 40 12.5 50 With terminal extensions y 32 30 y I y 34 y 15 3 y e y 10 10.5 y 32 10.5 50
Tinned copper
400 I L e
d L
Lugs
(1) Tightening torque on the circuit breaker for spreaders or terminal extensions. Tinned copper To be mounted on upstream side.
Spreaders and right-angle, 45 and edgewise terminal extensions are supplied with flexible interphase barriers.
DB115658
C-9
Power connections
DB400149
1-cable connector
2-cable connector
Aluminium y 250 A
25 25 to 50 20 70 to 95 26 120 to 185 150 max. flex. 26
25 1.5 to 95 (1) 12 25 or 50
2-cable connector
L (mm) S (mm2) Cu/Al Torque (Nm) 2 x 50 to 2 x 120 22
(1) For flexible cables from 1.5 to 4 mm2, connection with crimped or self-crimping ferrules.
1-cable connector
2-cable connector
1-cable connector
DB115663
2-cable connector
30 or 60 2 x 35 to 2 x 240 rigid 240 max. flex. 31
C-10
MCB Type A
CVS 800 129
Dimension B
114
MCB Type
2- 4.5
A
CVS 800
Dimension B C
114 70
129
Rating
800 A
Dimn. 't'
8.0 mm
Dimensions (mm)
Type CVS100/160/200/250 CVS400/630 G26 30 52.5 G27 41 67.5 K8 45 70 K9 159 240 K10 114 170
C-11
b Supply to RELAY UNIT & UNDER VOLTAGE RELEASE shall be taken from SUPPLY SIDE of MCCB.
b Control Voltage supply to RELAY UNIT shall be taken from LINE SIDE of MCCB. b Supply to SHUNT RELEASE shall be taken form LOAD SIDE of MCCB.
Notes: 1. Connections shown in dotted lines shall be made by customer. 2. HRC fises are not in SEIPLs scope of supply. 3. Remove BOTTOM SIDE SPREADERS (if Fitted) of MCCB before mounting CT on MCCB.
Ground Fault Protection Sealing Stud Time Delay Selector switch (2 step setting)
CT details
1. To change any setting switch OFF the MCCB. Remove protective cover from Relay Module. Replace cover after changing setting. 2. To test E/F relay press test Push Button. E/F relay will operate according to the time delay selection. Keep the Test Push Button pressed till the relay trips (indicated by red lamp).
C-12
Additional characteristics
EasyPact CVS
Additional characteristics
Contents
Functions and characteristics Installation recommendations Dimensions and connection A-1 B-1 C-1
Tripping curves
EasyPact CVS100 to 800A Protection of distribution systems EasyPact CVS100 to 250 Motor protection Current and energy limiting curves
Catalogue numbers
E-1
D-1
Additional characteristics
Tripping curves
TM32D
DB400095
10 000 5 000 2 000 1 000 500 200 100 50 20 10 t(s) 5 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1 TM16D/25D : Im = 12 x In
10 000 5 000 2 000 1 000 500 200 100 50 20 10 t(s) 5 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1 TM32D : Im = 12.5 x In
t < 10 ms
t < 10 ms
3 4 5 7 10 I / Ir
20 30
50 70 100
200 300
3 4 5 7 10 I / Ir
20 30
50 70 100
200 300
TM40D/50D
DB400096
TM63D
DB400101
10 000 5 000 2 000 1 000 500 200 100 50 20 10 t(s) 5 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1 TM50D : Im = 10 x In
10 000 5 000 2 000 1 000 500 200 100 50 20 10 t(s) 5 2 1 .5 .2 .1 .05 TM63D : Im = 8 x In
TM40D : Im = 12.5 x In
t < 10 ms
t < 10 ms
3 4 5 7 10 I / Ir
20 30
50 70 100
200 300
3 4 5 7 10 I / Ir
20 30
50 70 100
200 300
D-2
Tripping curves
TM125D/160D
DB400103
10 000 5 000 2 000 1 000 500 200 100 50 20 10 t(s) 5 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
10 000 5 000 2 000 1 000 500 200 100 50 20 10 t(s) 5 2 1 .5 .2 .1 .05 TM160D : Im = 8 x In TM125D : Im = 10 x In
TM80D/100D : Im = 8 x In
t < 10 ms
t < 10 ms
3 4 5 7 10 I / Ir
20 30
50 70 100
200 300
3 4 5 7 10 I / Ir
20 30
50 70 100
200 300
TM200D/250D
DB400104
TM320D/400D
DB400106
10 000 5 000 2 000 1 000 500 200 100 50 20 10 t(s) 5 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1 TM200D/250D : Im = 10 x In
10 000 5 000 2 000 1 000 500 200 100 50 20 10 t(s) 5 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1 TM320D/400D : Im = 510 x In
t < 10 ms
t < 10 ms
3 4 5 7 10 I / Ir
20 30
50 70 100
200 300
3 4 5 7 10 I / Ir
20 30
50 70 100
200 300
D-3
Additional characteristics
Tripping curves
TM500D
DB400107
10 000 5 000 2 000 1 000 500 200 100 50 20 10 t(s) 5 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
10 000 5 000 2 000 1 000 500 200 100 50 20 10 t(s) 5 2 1 .5 .2 .1 .05 TM600D : Im = 48 x In
TM500D : Im = 510 x In
t < 10 ms
t < 10 ms
3 4 5 7 10 I / Ir
20 30
50 70 100
200 300
3 4 5 7 10 I / Ir
20 30
50 70 100
200 300
10 000 5 000 2 000 1 000 500 200 100 50 20 10 t(s) 5 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1 Reflex tripping : t < 10 ms I = 11 x In 2 3 4 5 7 10 I / Ir 20 30 50 70 100 200 300 Isd = 2...10 x Ir Ir = 0.5...1 x In
D-4
Tripping curves
10 000 5 000 2 000 1 000 500 200 100 50 20 10 t(s) 5 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1 Reflex tripping.
t < 10 ms
t < 10 ms
3 4 5 7 10 I / Ir
20 30
50 70 100
200 300
3 4 5 7 10 I / Ir
20 30
50 70 100
200 300
MA320
DB400110 DB400111
MA500
10 000 5 000 2 000 1 000 500 200
Thermal withstand
10 000 5 000 2 000 1 000 500 200 100 50 20 10 5 t(s) 2 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1
Im = 6 ...13 x In
Thermal withstand
Im = 6 ...13 x In
t < 10 ms
t < 10 ms
3 4 5 7 10 I / In
20 30
50 70 100
200 300
3 4 5 7 10 I / In
20 30
50 70 100
200 300
D-5
Additional characteristics
100 to 800A
The limiting capacity of a circuit breaker is its aptitude to let through a current, during a short-circuit, that is less than the prospective short-circuit current.
Tripping curves
DB115719
(Isc)
Prospective Isc peak Prospective current Prospective Isc Limited Isc peak
The exceptional limiting capacity of the EasyPact CVS range greatly reduces the forces created by fault currents in devices. The result is a major increase in breaking performance. In particular, the service breaking capacity Ics is equal to 100 % of Icu. The Ics value, defined by IEC standard 60947-2, is guaranteed by tests comprising the following steps: b break three times consecutively a fault current equal to 100% of Icu b check that the device continues to function normally, that is: v it conducts the rated current without abnormal temperature rise v protection functions perform within the limits specified by the standard v suitability for isolation is not impaired.
Current-limiting circuit breakers greatly reduce the negative effects of short-circuits on installations. Thermal effects Less temperature rise in conductors, therefore longer service life for cables. Mechanical effects Reduced electrodynamic forces, therefore less risk of electrical contacts or busbars being deformed or broken. Electromagnetic effects Fewer disturbances for measuring devices located near electrical circuits.
The exceptional limiting capacity of the EasyPact CVS range is due to the rotating double-break technique (very rapid natural repulsion of contacts and the appearance of two arc voltages in-series with a very steep wave front).
300
The limiting capacity of a circuit breaker is expressed by two curves which are a 200 function of the prospective short-circuit current (the current which would flow if no 146 protection devices were installed): 100 b the actual peak current (limited current) 80 b thermal stress (A270 s), i.e. the energy dissipated by the short-circuit in a conductor 60 with a resistance of 1 50.
30 Maximum permissible cable stresses k 40 F N CVS630
CVS400
The table below indicates the maximum permissible thermal stresses for cables F CVS250 20 depending on their insulation, conductor (CuBor Al)CVS100 and their cross-sectional area CVS160 (CSA). CSA values are given in mm2 and thermal stresses in A2s.
CSA PVC PRC CSA PVC PRC Cu Al Cu Al Cu Al Cu Al 16 mm2 3.4x106 1.39x106 4.69x106
10 6 1.93x10 5 3 2
8 9
1.5 8 mm2
5 4 2
10
7 4 2.97x10 6 3 4 4
4 mm2 2.12x105
20
4.10x10
kA rms
2.92x10 35 mm2
30 40 50 5 70 100
Current-limiting curves
DB116369
300
5 3 2 10 As
2 7
5 3 2
CVS630 CVS400
N CVS630
CVS400
10
5 3 2 10
5
F CVS250
CVS100 CVS160
10 8 7 6 5 4 2
5 3 2
10
20
30 40 50 70 100
200 300
10
20
kA rms
kA rms
D-6
Catalogue numbers
EasyPact CVS
Catalogue numbers
Contents
Functions and characteristics Installation recommendations Dimensions and connection Additional characteristics A-1 B-1 C-1 D-1
E-1
Catalogue numbers
EasyPact CVS100/160/250B
With TM-D thermal-magnetic trip unit
EasyPact CVS100B (25 kA at 380/415 V) Rating TM16D TM25D TM32D TM40D TM50D TM63D TM80D TM100D EasyPact CVS160B (25 kA at 380/415 V) Rating TM100D TM125D TM160D EasyPact CVS250B (25 kA at 380/415 V) Rating TM160D TM200D TM250D
DB400150
3P LV510300 LV510301 LV510302 LV510303 LV510304 LV510305 LV510306 LV510307 3P LV516301 LV516302 LV516303 3P LV525301 LV525302 LV525303
4P LV510310 LV510311 LV510312 LV510313 LV510314 LV510315 LV510316 LV510317 4P LV516311 LV516312 LV516313 4P LV525311 LV525312 LV525313
EasyPact CVS100/160/250F
With TM-D thermal-magnetic trip unit
DB400150
EasyPact CVS100F (36 kA at 380/415 V) Rating TM16D TM25D TM32D TM40D TM50D TM63D TM80D TM100D EasyPact CVS160F (36 kA at 380/415 V) Rating TM100D TM125D TM160D EasyPact CVS250F (36 kA at 380/415 V) Rating TM160D TM200D TM250D
3P LV510330 LV510331 LV510332 LV510333 LV510334 LV510335 LV510336 LV510337 3P LV516331 LV516332 LV516333 3P LV525331 LV525332 LV525333
4P LV510340 LV510341 LV510342 LV510343 LV510344 LV510345 LV510346 LV510347 4P LV516341 LV516342 LV516343 4P LV525341 LV525342 LV525343
3P ME type for CVS/NSX100/160 (200 to 440 V) MH type for CVS/NSX100/160 (200 to 440 V) MH type for CVS/NSX250 (200 to 440 V) MH type for CVS/NSX100/160 (440 to 550 V) MH type for CVS/NSX250 (440 to 550 V) Connection for a 4P Vigi on a 3P breaker LV429212 LV429210 LV431535 LV429215 LV431533
4P LV429460 LV429214
E-2
EasyPact CVS100N (50 kA at 380/415 V) Rating MA2.5 MA6.3 MA12.5 MA25 MA50 MA100 EasyPact CVS160N (50 kA at 380/415 V) Rating MA150 EasyPact CVS250N (50 kA at 380/415 V) Rating MA220
Ref. 125/160/200/250
GFP12CT23P GFP12CT24P
Note: Kindly order one nos. shunt coil along with one Ground Fault Protection
E-3
Catalogue numbers
Accessories
EasyPact CVS100/160/250
2 short 2 long
LV429235 LV429236
Steel connectors
DB112225
Aluminium connectors
DB112726
DB112227
Set of 3 Set of 4
LV429218 LV429219
DB112724
Set of 10
LV429348
Terminal extensions
DB112231
Set of 4
LV429309
DB112232
DB112233
DB112235
3P 4P
LV431563 LV431564
E-4
Accessories
EasyPact CVS100/160/250
For cable 120 mm2 For cable 150 mm2 For cable 185 mm2
Set of 3 Set of 4 Set of 3 Set of 4 Set of 3 Set of 4 Set of 3 Set of 4 Set of 3 Set of 4 3P 4P
LV429252 LV429256 LV429253 LV429257 LV429254 LV429258 LV429504 LV429505 LV429506 LV429507 LV429515 LV429516
Insulation accessories
DB400161
DB400162
3P 4P
LV429517 LV429518
DB112241
Set of 6
LV429329
DB400163
3P 4P
LV429330 LV429331
E-5
Catalogue numbers
Accessories
EasyPact CVS100/160/250
Electrical auxiliaries
Auxiliary contacts (changeover)
OF or SD or SDE or SDV OF or SD or SDE or SDV low level SDE adaptor, mandatory for trip unit TM, MA 29450 29452 LV429451
DB112254
Voltage releases
Voltage 24 V 50/60 Hz 48 V 50/60 Hz 110-130 V 50/60 Hz 220-240 V 50/60 Hz and 208-277 V 60 Hz 380-415 V 50 Hz and 440-480 V 60 Hz DC 12 V 24 V 30 V 48 V 60 V 125 V 250 V MN 48 V 50/60 Hz with fixed time delay Composed of: MN 48 V DC Delay unit 48 V 50/60 Hz MN 220-240 V 50/60 Hz with fixed time delay Composed of: MN 250 V DC Delay unit 220-240 V 50/60 Hz AC
DB111454
MX LV429384 LV429385 LV429386 LV429387 LV429388 LV429382 LV429390 LV429391 LV429392 LV429383 LV429393 LV429394
MN LV429404 LV429405 LV429406 LV429407 LV429408 LV429402 LV429410 LV429411 LV429412 LV429403 LV429413 LV429414 LV429412 LV429426 LV429414 LV429427
E-6
DB115631
Accessories
EasyPact CVS100/160/250
Rotary handles
Direct rotary handle
DB112259
LV429337
LV429338
Locks
Toggle locking device for 1 to 3 padlocks
DB400164
By removable device
29370
DB400165
By fixed device
29371
Keylock adaptor (keylock not included) Keylock (keylock adaptor not included)
E-7
Catalogue numbers
Accessories
EasyPact CVS100/160/250
Interlocking
Mechanical interlocking for circuit breakers
DB111486
With toggles
29354
DB111487
LV429369
Installation accessories
Front-panel escutcheons
IP40 toogle escutcheon (small cut-out) IP40 escutcheon for Rotary handle IP40 escutcheon for Vigi module 29315 LV429317 LV429316
E21641
E21641
IP40
Lead-sealing accessories
DB115615
Bag of accessories
LV429375
1 adaptor
LV429305
Spare parts
10 toggle extensions Bag of screws 12 snap-in nuts (fixed/FC) 1 set of 10 identification labels M6 for CVS100B/F M8 for CVS160/250B/F LV429313 LV429312 LV510100 LV516060 LV429226
E18624
E-8
EasyPact CVS400F (36 kA at 380/415 V) Rating TM320D TM400D EasyPact CVS630F (36 kA at 380/415 V) Rating TM500D TM600D
EasyPact CVS400/630N
With TM-D thermal-magnetic trip unit
DB400008
EasyPact CVS400N (50 kA at 380/415 V) Rating TM320D TM400D EasyPact CVS630N (50 kA at 380/415 V) Rating TM500D TM600D
EasyPact CVS400/630N
With MA magnetic trip unit
EasyPact CVS400N (50 kA at 380/415 V) Rating MA320 EasyPact CVS630N (50 kA at 380/415 V) Rating MA500 3P LV540552
DB400020
LV563552
EasyPact CVS400/630F
ETS 2.3 electronic trip unit (protection)
EasyPact CVS400F (36 kA at 380/415 V) EasyPact CVS630F (36 kA at 380/415 V) 400 A 630 A 3P LV540505 LV563505 4P LV540506 LV563506
DB400021
7 8 10
EasyPact CVS400/630N
ETS 2.3 electronic trip unit (protection)
DB400021
400 A 630 A
3P LV540510 LV563510
4P LV540511 LV563511
7 8 10
E-9
Catalogue numbers
3P Type MB Connection for a 4P Vigi on a 3P breaker 200 to 440 V 440 to 550 V LV432455 LV432453
4P LV432660 LV432457
Ref. 400/630
3 PH 3W 3 PH 4W GFP13CT33P GFP13CT34P
Note: Kindly order one nos. shunt coil along with one Ground Fault Protection
E-10
Accessories
EasyPact CVS400/630
2 short 2 long
LV432475 LV432476
E22041
Set of 10
LV429348
E21276
E21012
Spreaders
For cable 240 mm2 For cable 300 mm2 Supplied with 2 (or 3) interphase barriers
For cable 240 mm2 For cable 300 mm2 Supplied with 2 (or 3) interphase barriers
Insulation accessories
E18618
Short terminal shield, 45 mm (1 piece) Long terminal shield, 45 mm (1 piece) Interphase barriers 2 insulating screens (70 mm pitch)
3P 4P 3P 4P Set of 6 52,5 mm 3P 4P 70 mm 3P 4P
E18606
E-11
Catalogue numbers
Accessories
EasyPact CVS400/630
Electrical auxiliaries
Auxiliary contacts (changeover)
OF or SD or SDE or SDV OF or SD or SDE or SDV low level SDE adaptor mandatory for trip unit TM, MA and ETS2.3 29450 29452 LV540050
E18608
Voltage releases
E18609
Voltage 24 V 50/60 Hz 48 V 50/60 Hz 110-130 V 50/60 Hz 220-240 V 50/60 Hz and 208-277 V 60 Hz 380-415 V 50 Hz and 440-480 V 60 Hz DC Voltage 12 V 24 V 30 V 48 V 60 V 125 V 250 V MN 48 V 50/60 Hz with fixed time delay Composed of: MN 48 V DC Delay unit 48 V 50/60 Hz MN 220-240 V 50/60 Hz with fixed time delay Composed of: MN 250 V DC Delay unit 220-240 V 50/60 Hz AC
MX LV429384 LV429385 LV429386 LV429387 LV429388 LV429382 LV429390 LV429391 LV429392 LV429383 LV429393 LV429394
MN LV429404 LV429405 LV429406 LV429407 LV429408 LV429402 LV429410 LV429411 LV429412 LV429403 LV429413 LV429414 LV429412 LV429426 LV429414 LV429427
E-12
Accessories
EasyPact CVS400/630
Rotary handle
Direct rotary handle
E18611
LV432597
LV432598
Locks
Toggle locking device for 1 to 3 padlocks
E18621
By removable device
29370
E18613
By fixed device
32631
E-13
Catalogue numbers
Accessories
EasyPact CVS400/630
Interlocking
Mechanical interlocking for circuit breakers
E21288
With toggles
32614
E18780
LV432621
Keylock kit (keylock not included) (1) 1 set of 2 keylocks (1 key only, keylock kit not included) (1) for only 1 device Ronis 1351B.500 Profalux KS5 B24 D4Z
Installation accessories
Front-panel escutcheons
E21641
IP40 Toggle escutcheon (small cut-out) IP40 escutcheon for rotary handle IP40 escutcheon for Vigi module
Lead-sealing accessories
LV429375
Spare parts
Front-panel escutcheons
Toggle extension Bag of screws 1 set of 10 identification labels LV432553 LV432552 LV429226
Test
Test kits
E21290
43362
E36271
Portable test kit for STR trip units Spare test plug for portable test kit 34547 Wiring kit (spare part)
E-14
AC 50Hz
voltage
24 V DC 48 V 110 V 220 V
Reference
LV580064 LV580065 LV580066 LV580067
Rotary handles
Direct rotary handles Ref.
LV580080
Ref.
LV580081
Note: Kindly order one nos. shunt coil along with one Ground Fault Protection Order one auxilliary contact alongwith shunt coil for CVS800.
E-15
For more information visit our website at: www.schneider-electric.co.in Schneider Electric India Pvt. Ltd. (A 100% subsidiary of Schneider Electric Industries SAS) Corporate office : 9th Floor, DLF Building No.10, Tower C, DLF Cyber City, Phase II, Gurgaon - 122002, Haryana, Tel: 0124 3940400, Fax: 0124 4222036 Customer Care Centre : Toll-free numbers: 1800 180 1707, 1800 103 0011, General number: 0124 4222040, Email: [email protected]