Fuel Oil Sizing Program Overview - Pps
Fuel Oil Sizing Program Overview - Pps
Introduction
PC
Based Program Sizes Typical Fuel Oil Piping Systems Helps to determine workability of overall application Helps to sizing suction and discharge piping
rate of use vs. duty cycle determines pump flow length of time without power determines tank size E-Gen sets RULE of THUMB 7 GPH / 100kw E-Gen sets - RULE of THUMB 4:1 , pump runs 25% of time. parallel loop, total burning rate plus total return flow series loop, total burning rate plus return flow of last burner only Motor HP based on PSI required
pressure (30" Hg) provides the force to get oil into the pump Most pumps can produce a 20" Hg vacuum Good practice limits suction to a 15" vacuum or less Typical piping loss is 5" Hg This leaves 10" Hg for static lift, or 12' of oil Pump should not be located more than 12' above the bottom of the tank
at pump inlet
Friction
convert fittings, valves, etc. to equivalent diameters add total length of pipe to equivalent for fittings add loss through strainer
Increase
Equivalent Diameters
ball valve, full ported check valve, lift type check valve, swing type foot valve, poppet type globe valve gate valve, full ported plug valve 90 degree elbow 45 degree elbow Tee, through run Tee, through branch 3 600 100 420 340 8 18 30 16 20 60
both pumps in a duplex set may be run together, use total flow in calculations Figure static lift from bottom of tank Use a 100% safety factor for strainer drop Use a 40 or 100 mesh strainer for #2 oil Use worst case viscosity in figuring loss
to keep pump close to tank Eliminate up and over lifts Add a priming funnel to the high point Do not allow pumps to run dry If possible, always use a foot valve to hold prime Pressure test all suction piping
Some Terminology
Operating Pump Suction: This value is displayed on the screen at the suction side of the pump. This value is the total summation of all losses encountered on the suction side of the pump. Priming Pump Suction: This value takes into account the vertical lift of a dry system, and may also be referred to as the priming static lift. If a pump looses its prime, and the piping system is dry, the static lift may not be the same as the priming static lift. Therefore, the Priming Pump Suction must be examined as well as the Operating Pump Suction. This value takes into account the vertical distance of piping that might go above the centerline of the pump, before connecting with the pump. S.G: Density of a fluid compared to the density of water.
Discharge Piping
Pressure
at pump discharge
Add pressure needed at point of use plus total gravity head and pipe losses
Generally,
discharge piping is smaller than suction piping A Back Pressure Regulating Valve may be used to regulate pressure at point of use (boilers)
Miscellaneous Cautions
Avoid high lifts and traps Allow for easy priming of pumps Provide adequate vent lines Provide properly sized day tank overflow lines Design the system so it can be tested regularly Dont overlook controls
Pop Up Windows
Report Printing
Example
Rule of THUMB
Exercise 1 For No. 2 Fuel Oil Determine: P1 and P2 Select Pump Set
Required 5 psi
P1
P2
100 feet
10 feet
300 gph
Storage Tank
10 feet
Example
Rule of THUMB
Exercise 2 For No. 2 Fuel Oil Determine: P1 running and priming, P2 ASV Spring Size Select Pump Set
Required 5 psi
ASV 15 feet
400 gph