PROII91 GettingStartedGuide
PROII91 GettingStartedGuide
August 1, 2011
All rights reserved. No part of this documentation shall be reproduced, stored in a retrieval system, or transmitted by any means, electronic, mechanical, photocopying, recording, or otherwise, without the prior written permission of Invensys Systems, Inc. No copyright or patent liability is assumed with respect to the use of the information contained herein. Although every precaution has been taken in the preparation of this documentation, the publisher and the author assume no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained herein.
The information in this documentation is subject to change without notice and does not represent a commitment on the part of Invensys Systems, Inc. The software described in this documentation is furnished under a license or nondisclosure agreement. This software may be used or copied only in accordance with the terms of these agreements.
2011 by Invensys Systems, Inc. All rights reserved. Invensys Systems, Inc. 26561 Rancho Parkway South Lake Forest, CA 92630 U.S.A. (949) 727-3200 http://www.simsci-esscor.com/ For comments or suggestions about the product documentation, send an e-mail message to ProductDocumentationComments@invensys.com.
All terms mentioned in this documentation that are known to be trademarks or service marks have been appropriately capitalized. Invensys Systems, Inc. cannot attest to the accuracy of this information. Use of a term in this documentation should not be regarded as affecting the validity of any trademark or service mark. Invensys, Pro/II, SimSci-Esscor are trademark of Invensys plc, its subsidiaries and affiliates. All other brands may be trademarks of their respective owners.
Contents
Introduction
About this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vii About PRO/II Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .viii About SimSci-Esscor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .viii Where to Find PRO/II Software Documentation. . . . . . . . . . . . . . .ix Online Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ix Online Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . x Where to Find Additional Help. . . . . . . . . . . . . . . . . . . . . . . . . x Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .xi Authorized SimSci-Esscor Technical Support Centers. . . . . . xii
Testing PRO/II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6 Reviewing the Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6 Generate an Output Report . . . . . . . . . . . . . . . . . . . . . . . . 2-6 Converting Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6 Modifying/Repairing/Removing PRO/II Software . . . . . . . . . . 2-7
Reviewing the Simulation Results . . . . . . . . . . . . . . . . . . . . . . . .5-21 Viewing the Output Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-22 Using the Flash Tool (optional) . . . . . . . . . . . . . . . . . . . . . . . . . .5-23
Index
vi
Contents
Introduction
About this Manual
This manual will guide you through the installation of the PRO/II family of software products and provides you with three sample sessions on using PRO/II Software.
Chapter 5 Session 1: Separator Step-by-step instructions to enable you to simulate a minimal set of process units in a gas processing application. Chapter 6 Session 2: Complete Additonal process units are added to Expander Plant complete an entire demethanizer/ expander plant simulation. Chapter 7 Session 3: Presentation of Output Introduces tools provided by PRO/II Software to organize, format and review results.
vii
The PRO/II Software process simulation program is designed with both the beginner and the expert in mind. It is based on a foundation of comprehensive, reliable, and accurate simulation capabilities. It is easy to use, and the input language is an extension of the universal language of chemical engineering. Expert systems, extensive input processing, and error checking allow even an inexperienced user to be instantly productive. These features have made PRO/II Software an industry standard.
About SimSci-Esscor
For 40 years, SimSci-Esscor has been a leader in the development and deployment of process simulation software, services, and complete solutions for oil and gas production, hydrocarbon and specialty chemical processing and refining, and fossil and nuclear power. Benefit from products that minimize capital requirements, optimize facility performance, maximize ROI, and produce assets for: Plant engineering design and simulation:
Integrated process engineering (FEED) Pipeline production analysis, asset model management Operational analysis, optimization, process control Dynamic simulation, operator training
Design-Operate-Optimize a safe and profitable plant subject to ever more stringent market and regulatory constraints. SimSci-Esscor software solutions are indispensable tools in solving these three increasingly complex challenges simultaneously. SimSci-Esscor is business unit of Invensys Process Systems, owned by Invensys, plc.
viii Introduction
-ix
Online Help
PRO/II Software incorporates an online Help system, a comprehensive reference tool that quickly accesses information. Online answers are instantly available while you work. In the Help system, commands, features, and data fields are explained in easy steps. You can access the electronic Contents for the Help system by selecting Help/Contents from the PRO/II menu bar. Contextsensitive help is accessed using the <F1> key or the Whats This? button by placing the cursor in the area in question.
Quickly learn how to simulate a simple PRO/II Getting Started Guide flowsheet using PRO/II Software Obtain detailed information on the PRO/II Users Guide capabilities and use of PRO/II Software Obtain basic information on PRO/II keywords Obtain basic information on PRO/II Software calculation methods Obtain more detailed information on PRO/II Software calculation methods Obtain detailed information of component and thermodynamic properties See simulation examples PRO/II Keyword Manual Online Help PRO/II Online Reference Manual SIMSCI Component and Thermodynamic Data Input Manual PRO/II Keyword Manual
See simulation examples for chemical, PRO/II Application Briefs solid processing, petrochemical, batch, Manual and electrolyte applications Demonstrates the use of PRO/II Software with process industry examples Learn how to create a custom component databank using the LIBMGR utility PRO/II Casebooks
Learn about PRO/II batch reactor and PRO/II Add-on Modules distillation, electrolytes, Profimatics or Users Guide polymers modules
Introduction
Learn about PRO/II-HTRI , PRO/IIHTFS or Linnhoff March ColumnTarget Interface modules Learn about PRO/II User-added Subroutines or the PRO/II Data Transfer System Learn to write applications (input and calculated) to access data in PRO/II simulation databases Information on APIs to the PRO/II COM Server with examples Learn about Ternary Mixture Plots
PRO/II Interface Modules Users Guide PRO/II Data Transfer System and User-added Subroutines Users Guide COM Server Programmers Guide and Tutorial COM Server Reference Guide Ternary Mixture Plots Help Manual
Technical Support
SimSci-Esscor and its agents around the world provide technical support and service for PES products. If you have any questions regarding the use of the program or the interpretation of output produced by the program, contact your local SimSci-Esscor representative for advice or consultation. When calling one of the Technical Support Centers, be prepared to describe your problem or the type of assistance required. Also, to expedite your call, complete the following steps before calling Technical Support:
Have the installation DVD and all the provided documentation available. Determine the type of computer you are using. Determine the amount of free disk space available on the disk on which the product is installed. Note the exact actions you were taking when the problem occurred, as well as the steps you took leading up to that point. Note the exact error messages that appear on your screen, as well as any other symptoms.
Both new and experienced users will benefit significantly from attending one of SimSci-Esscors regularly scheduled training courses on PES products. If you would like to obtain a list of courses available, or if you have any questions relating to the use of a PES product, its methods, data, or technology, please call your
PRO/II 9.1 Getting Started Guide -xi
Tel: ++ 1 800 SIMSCI 1 Invensys SimSci-Esscor, 26561 Rancho Parkway South, Suite Fax: + 1949 455 8154 100, E-mail: support.simsci@invensys.com Lake Forest, CA 92630 Invensys Systems Mexico S.A Amargura # 60 Col. Parques de la Herradura, Huixquilucan, Edo.de, 52786 Invensys SIMSCI-ESSCOR, 7665 - 10th Street NE, Calgary T2E8X2 Tel: + 52 55 52 63 01 76 Fax:+ 52 55 52 63 01 60 Email: mexico.simsci@invensys.com Tel: + 403-617-6220 (Cell) Fax: + 403-274-8651 E-mail: support.simsci@invensys.com
Mexico
Canada
Argentina
Invensys Systems Argentina Inc. Tel: + 54 11 6345 2100 Fax: + 54 11 6345 2111 Nunez 4334 Buenos Aires (Argentina) C1430AND E-mail:simsci.latino@invensys.com Invensys Systems Italia S.p.A Tel: + 39 02 262 9293 Fax: + 39 02 262 9200 Via Carducci, 126 Sesto San Giovanni (MI) 20100, Italia E-mail:simsci.eura@invensys.com Tel: + 58 212 267 5868 ext. 282 Invensys Systems Venezuela Torre Delta Piso 12, Av.Francisco de Fax: + 58 212 2670964 E-mail:simscilat@invensys.com Miranda Altamira, Caracas 1060 Invensys Systems Brasil Ltda. Av. Chibaras, 75 - Moema Sao Paulo, SP O 4076 - 000 Tel:+ 55 11 2844 0201/291 Fax: + 55 11 2844 0341 E-mail: suporte.simsciesscorbrasil@invensys.c om
Italy
Venezuela
Brazil
xii
Introduction
Address Invensys Systems GmbH & Wonderware GmbH Hermann Klammt Str. 1-3 D- 41460 Neuss
Australia and Invensys Performance Solutions New Zealand Level 2-4, 810 Elizabeth Street Sydney 2017, Australia Japan
Invensys Process Systems Japan, Inc. Tel: + 81 3 6450 1095 8th Fl. Suzuebaydium, 1-15-1 Kaigan, Fax:+ 81 3 5408 9220 Minato-ku, Tokyo 105-0022 Japan E-mail: ipsjp.support@invensys.com Invensys ME Dubai PO Box 61495 Jebel Ali Free Zone, Dubai Tel: + 971 4 88 11440 Fax: + 971 4 88 11426 E-mail: simsci.eura@invensys.com Tel: + 65 6829 8643 Fax: + 65 6829 8202 E-mail: simsci.apac@invensys.com
Middle East
Asia - Pacific Invensys Software Systems (s) Pte. Ltd. 15, Changi Business Park Central 1 Singapore 486057 United Kingdom Invensys Systems (UK) Limited The Genesis Centre, Birchwood Science Park, Birchwood, Warrington United Kingdom WA3 7BH Invensys Process Systems (China), No. 211, Huancheng Road East, Fengpu Industrial Park, Shanghai 201400 Invensys Systems LA Colombia Calle 100 # 36-39 Int. 4-203, Bucaramanga, SDER Invensys Korea Simsci-Esscor 6F, Dongsung B/D, 17-8, Yeouidodong, Seoul, 150-874
Tel: + 44 (0) 1925 811469 Fax: + 44 (0) 1925 838509 E-mail: simsci.eura@invensys.com
China
Tel: + 86 21 3718 0000 ext. 5912 Fax: + 86 10 8458 4521 E-mail: simsci.apac@invensys.com Tel: + 57 1 3136360 E-mail: support.co@simsci.com Tel: + 82-22-090-0822 Fax: + 82-32-542-3778 E-mail: support.kr@invensys.com
Colombia
Korea
-xiii
xiv
Introduction
Documentation
A partial list of available PRO/II online documents is:
PRO/II Keyword Manual SIMSCI Component and Thermodynamic Data Input Manuals PRO/II User Guide PRO/II Getting Started Guide (this document) PRO/II Interface Modules User Guide PRO/II Data Transfer System User Guide PRO/II User-Added Subroutines User Guide
1-1
Software Requirements
PRO/II 9.1 Requirements
The minimum software requirements are listed below. PRO/II 9.1 Software functions properly only on the operating systems in the lists.: Operating System Windows XP SP3, Windows VISTA SP2 (Business / Enterprise), Windows 7 (Business / Enterprise), Windows 7 Enterprise(64 Bit), or Windows 2008 Server SP2 Proper installation of PRO/II Software under all operating systems requires administrator rights. Microsoft Office Compilers Office 2010, Office 2007, Office 2003, Office XP.
User-Added Subroutines and PDTS applications require the following programs: Microsoft Visual Studio Net 2003 (or .NET 2005 or .NET 2007) Intel Visual FORTRAN version 10.x for Windows (Standard or Professional Edition). Newer versions (such as version 11.x) are compatible.
UAS and PDTS sample projects shipped with PRO/II 9.1 Software are built using .NET Framework 2003. Newer versions (.NET 2005 and .NET 2007) may be used, but require the end user to upgrade UAS and PDTS projects themselves. Conversion utilities and instructions automatically are invoked when a project needing conversion is opened in Microsoft Visual Studio.NET with Intel Visual Fortran installed.
Note:
User-added subroutines and PDTS applications built under Windows 2000 will run under Windows XP, Windows 2003, and Windows VISTA.
1-2
Installation Requirements
Acrobat Reader
Most PRO/II 9.1 documentation is delivered using Portable Document Format (i.e., as .pdf files). A recent version of Acrobat Reader is included on the PRO/II installation DVD. The latest free version also may be downloaded from an Adobe web site. As of this writing one such Adobe web site is: http://get.adobe.com/reader/
Microsoft Office
Click the Settings button under Performance. Select the Advance tab. Click on the Change... button in the Virtual Memory section. If desired, change the size in the paging file size for selected drive section; then click the Set button.
To set virtual memory in Windows 2003 Server and Windows VISTA: From the Vista Start menu, select Settings/Control Panel. Open the System item and access the Advanced tab. Click the Settings button under Performance. Select the Advance tab. Click the Change... button in the Virtual Memory section. If desired, change the size in the paging file size for selected drive section, and click the Set button.
Security Options
USB Security
SimSci-Esscor provides USB hardware security, in which you insert key specially coded to allow use of PRO/II Software. During installation, the USB key should not be plugged in. After installation, simply plug the security hardware device directly into one of the computers USB ports to start running PRO/II Software.
FLEXlm Security
SimSci-Esscor provides three different FLEXlm security options on the FLEXlm Server Application installation DVD.
FLEXNET 11 Security Single license option FLEXlm 9.5 Security Single license option TOKEN Security Multi-user license sharing option
1-4
Installation Requirements
The FLEXlm License Manager is a third-party concurrent-user software licensing tool from Macrovision Corporation. It is a client/ server-based tool that has been customized by Invensys Operations Management personnel. FLEXlm Server can run under Windows XP. The server must have at least 5 MB of available disk space. To install, learn, and troubleshoot FLEXlm security, follow the instructions provided in the FLEXlm Security Guide included in the standard release package.
1-5
restart PRO/II 9.1 Software and manually attempt to recover as much work as possible. FLEXlm security is managed by a proprietary client program that interacts with PRO/II 9.1 but executes independently. Security in PRO/II 9.1 is monitored periodically on-demand, not continually. A crash requires a delay of at least three minutes to re-establish communicaction with the FLEXlm security client.
Note: A crash of the PRO/II 9.1 program results in a delay of at least three minutes to re-establish communication with the FLEXlm security client. There is no need to attempt to reconfigure PRO/II 9.1 or the FLEXlm client. However, security will fail if an attempt is made to restart PRO/II Software too soon.
1-6
Installation Requirements
The main PRO/II application PRO/II Data Transfer System (PDTS) PRO/II User-Added Subroutines (UAS) Chemistry Wizard (from OLI) Thermo Data Manager (TDM). The TDM is a silent install. SIM4ME Portal/ Reports also is a silent install. CFI (Common Framework Install) module also is a silent install. PFE Editor Notepad ++ NIST REFPROP
To begin the install procedure: Insert the PRO/II DVD into the DVD drive. Browse to the root of the DVD and read release notes. Open PROII91 folder and double-click on the setup.exe to begin the installation. The first screen you will see in the installation process is the prerequisites for the PRO/II installation. To continue, click Install. Preparing to Install appears where Windows Installer Configures. The Welcome to InstallShield Wizard dialog box appears
PRO/II 9.1 Getting Started Guide 2-1
Click Next > to continue. The License Agreement dialog box appears. Choose I agree and click Next > to continue. The Destination Folder dialog box appears This box shows the default destination directory (C:\SIMSCI) of the PRO/II files and for shared SIMSCI components, like CFI, SIM4MEPortal (C:\Program Files/Common Files/ SIMSCI).
To install to these folder, click Next >. To install to a different folder, click Change > and select another folder. . in the SIMSCI directory, place PRO/II version 9.1 in another directory (e.g., \P2v91) to avoid any conflicts.
Click Next > to continue. The Setup Type dialog box appears. Choose Typical or Custom.
Windows 2003/XP and Windows VISTA must have system administration privileges for the install to proceed properly. Select one of the two available local installation options:
Typical
Installs only the PRO/II program, TDM, SIM4ME Portal and Reports, PFE Editor and Notepad++. Installs components based on your selection.You can install the Standalone option from this option as well as the individual components including the Translator, PRO/II program, Chemistry Wizard module, UAS, PDTS, PFE Editor, Notepad++, NIST REFPROP and Multi Simulation Manager.
Custom
The Custom Setup dialog box appears to allow you to select the components you want to install. The list box shows all possible components. Click on the components you want to install and note the change in required disk space. Click Next >.
If you are installing a Standalone option (directly or through the Custom installation), the Security Option dialog box appears. Select one of the four security options:
FLEXlm 9.5 Allows PRO/II Software to go beyond the cur-
rent machine to obtain licenses from another machine (FLEXlm 9.5 security server machine) on the network.
FLEXNET 11
Allows PRO/II Software to go beyond the current machine to obtain licenses from another machine (FLEXNET 11 security server machine) on the network. Utilizes a USB hardware key attached to the USB port on the back of the current machine for licensing purposes. Using this type, PRO/II Software will only search this hardware key for license(s). Allows PRO/II Software to go beyond the current machine to obtain licenses from a Token server on the network. Allows PRO/II Software to go beyond the current machine to obtain licenses from a Tokennet server on the network.
USB
Token
Tokennet
If you chose FLEXNET 11, FLEXlm 9.5, Token or Tokennet, specify the prospective IPASSI FLEXlm server(s) (e.g., @server1; @server2) to guide PRO/II to find the FLEXlm server. Click Next > to continue.
A dialog box appears to select the options of creating a Shortcut on the Desktop and/or the Quick Launch bar. Click Next > to continue.
2-3
If you are installing the Standalone option, the Shortcut Options Folder dialog box appears. By default, the setup program adds PRO/II icons in the SIMSCI program folder. Also select the options of creating a Shortcut on the Desktop and/or the Quick Launch bar. Click Next > to continue. The Ready to Install Program dialog box appears. If you want to review or change any settings, click < Back. If you are satisfied with the settings, click Install> to begin copying files. When your installation is complete, the InstallShield Wizard Complete Installation dialog box appears. Click Finish to complete the Local installation.
Note: Setup determines if it is necessary to restart the computer. If
so, it asks whether you want to restart the system now or later. You should now test your PRO/II installation. Proceed to the Testing PRO/II section for more information.
2-4
C:\SIMSCI\PROII91\Manual C:\SIMSCI\PROII91\HLP C:\SIMSCI\OLI_for_PRO_9.x C:\Program Files\PFE32 C:\Program Files\Notepad++ C:\SIMSCI\PROII91\TDM C:\Program Files\Common Files\SIMSCI\SIM4MEPortal211 C:\SIMSCI\ MultiSimulationManager10 C:\Program Files\Common Files\SIMSCI\ SIMSCICFI40
[Main PRO/II directory] [PRO/II users directory] [Binary files] [System files] [Resource files] [PRO/II Documentation] [Online help files] [Chemistry Wizard] [PFE32 file editor files] Notepad ++ [TDM files]
PRO/II 9.1 PRO/II Documentation PRO/II Re-Initialization Utility (PRU) LM ColumnTarget Interface PROII 9.1 PDTS Applications Command Prompt Ternary Plots SIM4ME Portal 2.1.1
Other icons may appear depending upon the install options chosen. For example, installing the OLI Chemistry Wizard adds an icon.
2-5
Testing PRO/II
As a simple test of your PRO/II system, open PRO/II Software, import the input file G3 and run it. This will let you utilize PRO/IIs flowsheet capability and give you a sense of how PRO/II will run. To test the PRO/II system: Click Start and select Programs/SIMSCI/PROII91/PROII 9.1. A Welcome to PRO/II screen appears which provides you with basic information on the user interface.
Note: SIMSCI is the default directory and is used for illustrative
purposes in the remainder of the chapter. If you chose another directory (e.g., P2v91), use that directory name in place of SIMSCI. Click OK to continue. Select File/Import from the menu bar. Select G3.INP in the Import Keyword File window and click Open. A window will appear showing the import of problem G3 PRO/II Main Window. Click the Run button on the toolbar to begin calculations. Click Run Simulation on the Flowsheet Status dialog box to continue.
Converting Files
This version of PRO/II Software automatically detects the file version and runs the PRO/II converter for upgrades. To convert simulation files:
2-6 Installing PRO/II Software
Launch PRO/II Software with PROVISION On the File menu, use the Open item to display the Open dialog. Enter the name of a file to convert. Click Open. The designated file will be converted to the new version PRO/II 9.1 Software.
Note: Several processing methods, such as the order of searching
component data banks, or methods for characterizing assays, change over time with the release of newer versions of PRO/ II. Running in key word mode usually does not inform the user of such changes. The PROVISION Graphical User Interface traps these changes and displays dialogs. This allows users to choose options that either (a) retain the older options or (b) updates the simulation to use current defaults. These choices of necessity require user interaction with the dialogs.
SimSci-Esscor PRO/II 9.1. Selecting the option (listed above) and clicking on the Change/ Remove button will give you the opportunity to remove or add components, repair or modify the PRO/II configuration, or even uninstall the whole product.
Note: The order of uninstalling components and/or creating files
under the PRO/II tree may cause certain single files to remain on the disk. After uninstalling a component, check the corresponding installation directory for remaining files and delete them manually.
2-7
2-8
file field on the Config Services tab (See figure below). Carefully go through the log file to see if there are any errors recorded in this log file.
Figure 3-1 : LMTools Configuration Service
Alternatively, after attempting to start the FLEXlm server, start the lmtools.exe utility, click on the Server Status button on the Server Status tab, and then click the Perform Status Enquiry button (as shown in the Figure below). Again, carefully go through the output text to find any error messages. Note that if you need to perform the server status enquiry multiple times, you can use Edit->Clear Window from the menu bar as this will clear the output text box for easy reading.
3-2
Installation Troubleshooting
If there are any error messages in the FLEXlm server log file or in the lmtool.exe Server Status output text window, try and take appropriate action to resolve the problem yourself. Examples:
Attempting to start the FLEXlm server using a license file not intended for the license server causes an authentication error. In this case, you need to install the correct license (and FLEXlm server) on the machine for which the license was generated. Alternatively, contact your SimSci-Esscor representative to issue a license file for the machine on which the FLEXlm server is installed. Another issue could be that the licenses themselves have expired. The expiration date can be found by looking at the license file, ipassi.lic, or by clicking the Perform Diagnostics button on the Server Diags tab. If the licenses have expired, then contact your SimSci-Esscor sales representative to renew your licenses. A further common error is that the FLEXlm server machine name, the second item on the SERVER line in the FLEXlm
3-3
license file, is not stated correctly. An example of the server line, from a permanent license, is as follows:
SERVER miawa2ca 000874fe5ea8
Note for a temporary license, the ANY entry must be retained as the third item on the SERVER line.
If the machine name is correct in the SERVER line but the FLEXlm server is still not starting correctly, then use the IP address of the server machine instead of the machine name.
For errors that you cannot resolve yourself, contact SimSci-Esscor technical support for assistance. When doing so, have the server log file available to send as an aid in troubleshooting the problem. Step 2 - Ensure that the application is using FLEXlm/TOKEN security If the FLEXlm server is up and running with the correct license, but there is still a problem launching the application due to a FLEXlm/ TOKEN security error, then the focus should switch to the SimSci-Esscor application side. The second step in troubleshooting FLEXlm/TOKEN security is to verify if FLEXlm/TOKEN is indeed the active license security type. This selection of license security type is made in the main initialization file (*.ini) of the application. These files are usually named after the applications they control, such as PROII.ini, PipePhase.ini, Datacon.ini, etc. The easiest way to locate these ini files is to search the application directory for the *.ini file that contains the string [wss_Security]. Once you identify the ini file, you need to open the file (NotePad will work fine for this) to see what the active security type is. Search for the Type statement in the [wss_Security] section. The active security Type statement is the one that does not have a semicolon (;) in front of it. If FLEXlm/TOKEN is not the current active security type, you will need to comment out the current active type by placing a semi-colon at the beginning of that line, and uncomment the ;Type=FLEXlm or the ;Type=TOKEN line. For example:
[wss_Security]
Type=FLXLM95 Type=USB
3-4
Installation Troubleshooting
Or
[wss_Security] Type= TOKEN Type=TOKENNET Type=USB Type= FLXNET11 Type=FLXLM95
If FLEXlm/TOKEN security was previously not the active security type and has now been made the active security type, the user should test the application to verify that the change has corrected the problem. If the FLEXlm/TOKEN security still does not work, proceed to Step 3 for further diagnosis. Step 3 - Ensure that the application is using the correct set of security files This step involves checking the security files at two levels. At the first level, the user needs to make sure that the application is actually using its own set of security files (scintf.dll, token.dll, tokennet.dll, flxnet11.dll, and flxlm95.dll). Sometimes multiple copies of the security files exist on the machine and the application may be using the file(s) somewhere on the paths specified in the PATH environment variable, not the ones under its own directory. Since this will create significant confusion during security troubleshooting, it is highly recommended that all security files that are not part of any SimSci-Esscor application file systems be deleted, especially the ones on the PATH environment variable. When this is done, the user can be sure exactly which security files the application is using. The second level is only applicable to the FLEXlm security. The SimSci-Esscor FLEXlm security comes in two versions, 7.2 and 9.5. Because these two versions are not completely compatible with each other, it is critical that the FLEXlm client (the flxlm.dll on the application side), the license file, and the FLEXlm server be of the same FLEXlm version. The symptom of this incompatibility is that the application fails and in the server debug file you see the license is checked out and back in almost at the same time. The FLEXlm server version can be found in the server log file (ipassi.log) and the
PRO/II 9.1 Getting Started Guide 3-5
license file version can be found in the license file itself. If the version cannot be found in the license file, then the license file should be FLEXlm version 7.2. The version of the flxlm.dll can be found by right-clicking the file, selecting Properties, and then selecting the Version tab. From 2006, we are moving towards using the FLEXlm version in FLEXlm dll file names. For instance, flxlm72.dll means the file is version 7.2 and flxlm95.dll means version 9.5. Moreover, the value of the Type statement in the application ini file also uses flxlm95 and flxlm72 to reflect the FLEXlm version it is using. Step 4 - Ensure that the FLEXlm communications are functioning properly If the FLEXlm server is running correctly and the application's licensing configuration is appropriate, but there is still a FLEXlm/ TOKEN licensing problem, turn the focus to the communications between the application machine and the FLEXlm server machine. To do this, first ping the FLEXlm server machine from the application machine to see if the communications between them are enabled. If not, the user should contact their IT personnel to resolve this issue first. After the fundamental communications problem is resolved, examine the value of the environment variable IPASSI_LICENSE_FILE on the application machine to see if the value points to the intended FLEXlm server machine. If this value has been set multiple times, examining and editing the value in the registry may be necessary because the old value may be cached in the registry location. Figure 3-3 shows the registry entry for server @cms4m0ca:
Figure 3-3: Registry Entry for Server @cms4m0ca
The user can directly delete or edit the value of the IPASSI_LICENSE_FILE from here or run lmpath.exe to accomplish the same result.
3-6
Installation Troubleshooting
Another issue with this environment variable is that sometimes the application machine system has a problem resolving the FLEXlm server machine name into the IP address. In this case, instead of using the FLEXlm server machine name for value of IPASSI_LICENSE_FILE, use the FLEXlm server machine's IP address, such as @123.12.10.100. If the environment variable is managed correctly and the problem still persists, the user may resolve the problem based on any error messages rendered on the application side. The user should examine the contents of the FLEXlm server log file ipassi.log to see if there are any records about the license request. If there are no records at all in the server log file about this license request, then the communication between the FLEXlm client and FLEXlm server have not been established. In this case, the user needs to examine the firewall on the FLEXlm server machine to ensure that the port numbers used by the FLEXlm server (lmgrd.exe) are enabled for the communication. The port numbers used by the FLEXlm server can be found in the FLEXlm server log file ipassi.log. Example:
10:21:59 (lmgrd) lmgrd tcp-port 27000 10:22:10 (lmgrd) IPASSI using TCP-port 2601
Another possible FLEXlm communication issue may be encountered accessing FLEXlm licenses over the internet, as it may take longer for the application to connect to the FLEXlm server machine. If this takes too long, the application may prematurely timeout the connection attempt and return an error. To overcome this problem, set the environment variable FLEXLM_TIMEOUT on the application machine. The usage of this variable is as follows: Set the timeout value of a FLEXlm-licensed application when attempting to connect to a license server port in the range 2700027009. Values are in microseconds, within the range 0 through 2147483647. The default setting is 100000 microseconds. The other thing the user can do to reduce the connection time is to explicitly set the FLEXlm server ports such that the application knows exactly what ports to talk to. Please refer to Table 3-1 for details on setting up explicit FLEXlm server ports.
3-7
Problem Fix
Problem Fix
3-8
Installation Troubleshooting
Problem Fix
How can I make FLEXlm security work with firewall on the FLEXlm server machine? To make FLEXlm security work with firewalls, the following three components must be configured correctly. 1. Use a port number on the SERVER line in the license file as follows:
Fix
SERVER host hostid [port] Example: SERVER ips-sol07 0002b303df80 27000 2. Use another port number on the VENDOR line in the license file: VENDOR vendor [port=]port Example: VENDOR IPASSI port=27001 3. On the application machine, set the value of the environment variable IPASSI_LICENSE_FILE to be 27000@ips-sol07. The port number here is the port number from the SERVER line. Make sure both the ports are enabled on the FLEXlm server machine.
4. 5. Problem Fix
Ensure that the port numbers for the SERVER line and for the VENDOR line are not used by other applications on the FLEXlm server machine, and are different from each other. How do I automatically launch my FLEXlm server when I reboot my FLEXlm server machines?
For FLEXlm servers on Windows NT/2000/XP/2003 machines, this is possible through the Config Services tab. On this tab, check the Use Services and the Start Server at Power Up checkboxes and save the server configuration. Why does FLEXlm security fail when I try to reboot immediately after a PRO/II crash? The FLEXlm server runs independently of PRO/II. A crash of PRO/II requires a delay of about 3 minutes to restore communication with the FLEXlm server. Wait a few minutes and then try rebooting PRO/II. No re-configuration and no further other action should be required. How do I prevent my FLEXlm server from being manipulated by users on other machines? Beginning with FLEXlm 9.x, when you are starting the FLEXlm server, you can specify that users on other machine cannot shut down the FLEXlm server. To do this, go to the Start/Stop/Reread tab, select the service you are about to start, click the Advanced settings, and check lmdown will only work from node where lmgrd is running. Then, click Start Server. Refer to the following screen image.
Problem Fix
Problem Fix
3-9
Problem
If I get the message below when launching a SimSci-Esscor application, what could be going wrong?
Fix
A common cause of this error is that the FLEXlm dll on the application is of version 7.2, but the FLEXlm server is 9.5. In this case, run the FLEXlm 9.5 Client Retrofit program to update the application and this should resolve the problem.
3-10
Installation Troubleshooting
Problem Fix
How do I obtain the system information about the machine, including the host ID? The FLEXlm utility, lmtools.exe System Settings tab, is always the most accurate for checking the host ID. Note that when issuing a FLEXlm/TOKEN license, SimSci-Esscor uses Ethernet Address or Disk Volume Serial Number to bind the license. If your FLEXlm cannot start correctly, you may want to verify that the Ethernet address or disk volume serial number in the license file is consistent with that on the machine. In addition, you may check the Computer/ Hostname to verify that this value is the same as the second item on the SERVER line in your license file. An example of lmtools System Settings tab display:
Problem Fix
How do I configure the usage of my license(s)? Use a FLEXlm options file to specify how the license(s) should be used. For detailed information, please refer to the Options File documentation. How do I include a FLEXlm options file and how would I know if the FLEXlm server is using the options file? If you use ipassi.opt for the name of the options file, then simply put this options file in the FLEXlm server folder (where the lmgrd.exe and IPASSI.EXE are). When the next time the IPASSI FLEXlm server starts, it will automatically read and apply the rules in this file. If the options file does not have the default file name or is not located in the FLEXlm server folder, then you'll need to explicitly specify the options file on the VENDOR line in the license file as follows:
Problem Fix
3-11
Problem Fix
Can I use a regular FLEXlm license file and a TOKEN license file under the same IPASSI FLEXlm server? Technically, this configuration should work. However, this is not recommended as the logging and reporting functionalities work differently for FLEXlm and for TOKEN security. For clarity, it is highly recommended that FLEXlm and TOKEN be installed on different license server machines. We're using FLEXlm over a wide-area network. What can we do to improve the FLEXlm licensing performance? To shorten the initial connection time between the FLEXlm Client and the FLEXlm Server over a wide-area network, you can specify the FLEXlm server port numbers in the FLEXlm license file. In this case, the Client will know exactly what ports on the Server machine to use when trying to connect to the Server. We're using FLEXlm over a slow wide-area network. What can we do to allow longer FLEXlm Client/Server initial connection time? You can set the environment variable FLEXLM_TIMEOUT to a larger value on the Client machine. This value sets the timeout period of a FLEXlm-licensed application when attempting to connect to a license server port in the range 27000-27009. Values are in microseconds, within the range 0 through 2147483647. The default setting is 100000 microseconds.
Problem Fix
Problem Fix
3-12
Installation Troubleshooting
After changing the security type to USB (or after making any change to the security options)be sure to test the application to verify that the change has corrected the problem. If the USB security still does not work, proceed to Step 2 for further diagnosis. Step 2 - Examine the USB environment on the machine For the USB security to work, the machine itself must be able to correctly detect the USB key. This step is to determine if this is the case. With the USB key plugged in, go to the Device Manager and open the Universal Serial Bus Controllers to see whether the entry for the USB key is listed correctly as illustrated in Figure 3-4:
Figure 3-4: Device Manager
If there is a conflict or problem, the USB SuperPro controller (shown as Rainbow USB SuperPro) will show up with a yellow exclamation mark or a red X (or may not show up at all). Figure 3-5 shows an example of a USB driver issue, i.e. a yellow exclamation mark displayed by the USB SuperPro entry:
Figure 3-5: Device Manager > USB SuperPro
3-13
When the machine is not detecting the USB entry correctly, please unplug the USB key from the machine and uninstall the existing USB driver using the Add/Remove Programs function (Figure 3-6):
Figure 3-6: Add/Remove Programs
After un-installing the existing USB driver, install the USB 7.0 driver. The install program for USB 7.0 driver is available from the SimSci-Esscor application install DVD or from the SimSci-Esscor ESD web site. After installing the driver successfully, the Sentinel Protection Installer 7.0.0 entry should appear in the Add/Remove Programs window as follows:
Figure 3-7: Sentinel Protection Installer 7.6.3
Now, plug the USB key back into the machine and go to the Device Manager again to verify that the system is correctly detecting the USB key. If the problem persists, then either the key is damaged or the computer, including the USB port, may be malfunctioning. In this case, the user will either have to try the key on another machine
3-14 Installation Troubleshooting
that has working USB environment to determine if the key is good; or alternatively, the user can try another USB key that is known to be working on another machine to try on this problem machine and verify if its USB environment is functioning correctly. If the result indicates that the USB key is not functioning properly, please return the key to SimSci-Esscor technical support for further diagnosis. If the USB environment on the machine is not working correctly, the user will have to resolve the machine problem first. Another method for examining the USB environment is to use the SuperproMedic utility program (SproMedic.exe) from Rainbow Technology. The install program (SuperproMedic.exe) for this utility is available in the Utility folder in the USB 5.0 Retrofit program, which can be found in the SimSci-Esscor ESD web site. The default install location for this program is C:\Program Files\ Rainbow Technologies\SuperPro\Medic. This program displays the version of the current Sentinel System Driver on the machine. Note that not all versions of Sentinel System Driver work with the SimSci-Esscor USB key. If the existing USB driver is not a good one, the SuperproMedic utility program will indicate the problem as shown below (Version 5.39.2 - Unknown S):
Figure 3-8: SuperproMedic
In this case, the user will have to unplug the USB key from the machine, un-install the current USB driver, and then re-install the USB 7.0 driver. When the utility program shows no error in the Sentinel System Driver, the user can click on the Find SuperPro button to see if it can detect the USB key. If it finds the key, the output should look similar to Figure 3-9 (1 Hard limit of first key found):
3-15
If no keys are detected, the output is as follows (0 Hard limit of first key found):
Figure 3-10: USB Key Not Found
Step 3 - Examine the SimSci-Esscor USB key and the USB.DLL If the SproMedic.exe utility can correctly detect the USB key, the next thing to look at is the usb.dll and the USB key. A potential problem with the USB.DLL is that it may not be recent enough to recognize the applications turned on in the USB key. To eliminate this problem, the user simply downloads the USB 5.0 Retrofit program from the Update area in the SimSci-Esscor ESD web site, and then retrofits the application accordingly to update the USB.DLL. After the retrofitting, the user can run the
3-16 Installation Troubleshooting
USBKeyCheck.exe utility program first to see if the USB key is good. If the USBKeycheck.exe program indicates that the USB key has already expired or does not contain the license to run the application, please contact the SimSci-Esscor sales representative to resolve this issue. Step 4 - Examine the copies of USB.DLL on the machine Sometimes there are multiple copies of USB.DLL existing on the machine. In this case, the application may or may not be using the newly updated USB.DLL obtained from the previous step. The SimSci-Esscor security files, including USB.DLL, should only exist inside the application folder and the application should only use its own set of security files. Should there be any SimSci-Esscor security files existing outside of all SimSci-Esscor application folders, it is highly recommended that they be deleted to eliminate the confusion, especially those that exist on the paths specified in the PATH environment variable.
Problem
Fix 1 Fix 2
3-17
Invalid ;path of access failures: You receive messages that files could not be copied and that the installation failed. If you are installing to a network, ensure that you have adequate read/ write access privileges. Ensure that you have enough disk space in the specified directory. PRO/II is installed on a system running Windows NT. When it runs, it produces errors relating to security. Ensure that whoever installed PRO/II had system administration rights/privileges. Security chip missing errors. The security device must be the first item in parallel port. Make sure that the security installation has been completed correctly and that you have the security device listed in the installation instructions. Make sure that the security device is firmly inserted into the parallel port. Check the 25 connector pins on the security device for damage. If a printer is attached, make sure it is turned on. Some laptop computers do not put out enough voltage to the parallel port to return an answer to the program. You can test this by attaching a printer, turning it on, and executing the program. If it works with a printer attached, then you can use that as a solution, move the program to another computer, or contact Technical Support for a special battery adapter to increase voltage directly to the security device number. Something to try: Some laptop problems have been resolved by attaching a cable at least two feet long to the printer side of the security device (no printer). Make sure only similar security devices are piggybacked.
Fix 6
3-18
Installation Troubleshooting
Obtain a new serial number from OLI, Inc. Invensys cannot provide full licenses for all the OLI products that can be used by PRO/II. Refer to the Chemistry Wizard User Guide for instructions. Create a .dbs file using the MSE option. Start the OLI Chemistry Wizard application and choose the MSE option. Give the database file a name and add some components. Save the database file, being sure to remember the file name and the location where it is stored. Close Chemistry Wizard application. Run PRO/II Software to change the serial number. Start PRO/II. On the Input menu, select Thermodynamic Data... Set up PRO/II Software to use the MSE data base. In the Thermodynamic Data dialog, highlight a system in the Defined Systems: dialogue; then clock the Modify... button. Highlight Electrolyte in the Category field and User-Added Models 7.0 in the Electrolyte System: field. Press the Add button add it to the simulation. It should show up as a User method
3-19
in the Defined Systems: list box. This should activate the Modify button, typically bordered in red. Click the Modify... button to open the Thermodynamic Data - Modification data entry window. Near the bottom of the window should be a field labelled DBS File Name:. Near it should be a Browse... button.
To select the .dbs file (created above using the MSE option): Click the Browse... button and navigate to the directory where the data file is stored. Select the data file. Close all Thermodynamic data DEWs to return to the main PFD window of PRO/II Software. Ther probably will be some messages about generating lists of electrolyte components. These may be ignored for now.
Run the simulation in PRO/II Software. Press the RUN button (either on the RUN palette or on the main tool bar).
At this point PRO/II should request the serial number. Enter the new serial number as requested. Press OK repeatedly to exit all dialogue windows. Close PRO/II and restart the application for the change to take effect. If the serial number is not requested, contact a PRO/II support representative.
3-20
Installation Troubleshooting
Required data. Actions or data required. Optional or default data. Data you have supplied
4-21
Questionable data. A warning that a data value you supplied is outside the normal range. Data field is not available to you Data entry is not required
In Session 2: Complete Expander Plant, additional process units are added to complete an entire demethanizer/expander plant simulation. In each session, step-by-step instructions enable you to build the simulation, use the Process Flow Diagram (PFD) drawing tools to manipulate the flowsheet, run the simulation, and review the results. At each step, an illustration of the PROVISION display screen is provided. Session 3: Presentation of Output; is designed to introduce some of the many tools that PRO/II Software provides, to organize, format, and review results from the first two sessions. Many features are new or improved in version 9.1.
Where to Start?
PRO/II Software users, at all levels of experience, will benefit greatly from working with this tutorial. If you are a first-time user, you should work using this Getting Started Guide. Although not recommended, experienced users may skip the Getting Started Guide and move on to the Users Guide.
Briefs Manual. The PRO/II Reference Manual provides details on the basic equations and calculation methods used in the program. If you cannot find an answer to your problem in these documents, please contact your local PRO/II sales or support representative.
The process flowsheet is shown in Figure 4-1, and the feed composition is presented in Table 4-2.
Note: Both Sessions 1 and 2 assume that ENGLISH units of
measure were selected as the default units for input and output data.
Figure 4-1: Expander Plant Flowsheet
4-23
Flow rate (m3/s) 8.0 Temperature (F) 120.0 Pressure (psia) 602.7
How to Proceed?
Lets get started with using PRO/II Software. Session 1 simulates only three process units of the flowsheet shown in Figure 4-1. By working through this exercise, you will gain familiarity with the basic features of the simulator. You can complete the simulation of the entire flowsheet by continuing with Session 2, which demonstrates advanced features of PRO/II Software and introduces some of the PFD tools. Finally, Session 3 explores some of the tools to analyze the results of the simulation. Some users may wish to jump right in and skip some (or all) of this tutorial. At any time, whenever you are comfortable using the program, feel free to leave the tutorial and begin working on your own simulations.
4-24
Tutorial : Introduction
5-1
An empty Untitled [Flowsheet] process flow diagram (PFD) window appears for laying down your process simulation as shown in Figure 5-2. The toolbar appears below the menu bar and above the main PFD window. Using the toolbar icons reduces the number of mouse actions required for a selection.
The floating PFD palette, for adding streams and units, appears first at the right of the flowsheet window. The floating PFD palette may be moved anywhere on the desktop by clicking on its title bar, holding the left mouse button down, and dragging it to its new
5-2 Session 1: Separator
location. The floating Run palette can be relocated in the same manner.
Process Units
Start building the process flowsheet for this session by laying down each process unit and stream, one by one, on the PFD. Use Figure 5-3 as a guide. 5. 6. 7. 8. For separator F1, move the mouse cursor to the floating PFD palette and click Flash icon. To add the unit, click anywhere on the main PFD window. Scroll down the PFD palette to select an expander (EX1) and place it on the PFD. Repeat the procedure for valve (V1).
Moving icons around on the main PFD window is easy. 9. Place the cursor on an icon, press and hold the left mouse button, and drag it to a new location.
10. Release the mouse button to drop the icon at the position of the mouse cursor.
5-3
11. Connect the unit operations by adding process streams to the PFD. Process streams define the heat and material flow of the simulation.
Process Streams
To add process streams: 12. Click Streams on the floating PFD palette. The cursor changes to an arrow with an S attached. You can now add streams to your flowsheet. Notice that all possible OUTLET ports appear on each unit as soon as Streams is selected. The required outlet ports are colored red, while the optional ones are green.
Figure 5-4: The PFD: Process Units and Streams
13. Add streams by clicking at the origin of the stream (often an outlet port). To lay down an external feed stream, click on an unoccupied part of the PFD. The cursor remains attached to the stream, which is now anchored to the origin point. 14. Click again at the destination of the stream (often an inlet port on a unit icon). Continue until all streams have been added to the PFD as shown in Figure 5-4.
Note: As soon as you click a streams origin point, the OUTLET
ports disappear. Only the valid INLET ports appear and are colored red.
5-4 Session 1: Separator
15. Click Streams again or press the ESC key to exit the streams mode.
Note: By default, the names of the process units and streams are
automatically assigned by the program. For example, S1 for the first stream, F1 for the first flash drum unit, V1 for the first valve, and so on. At this point, it is worth noting that the unsatisfied data are indicated on the PFD. Units that have unsatisfied internal data (all of them in this flowsheet, at this point) have red identification strings, F1, bordered in red. Streams for which data must be supplied (external feed streams) also have red identifiers, S1, bordered in red. Internal (connecting) and product streams have black identifiers, S2, bordered in black.
Note: Units that have unsatisfied connectivity requirements (i.e.,
missing feeds or an insufficient number of product streams) also have red identifiers bordered in red.
Note: The red color of the icon border indicates that data entry is required.
21. Click Input at the top of the screen. 22. Next, click Component Selection. (see Figure 5-5). The Component Selection window is displayed.
Figure 5-5: Selecting Components
23. Enter the first component, Nitrogen, in the Component field. This is illustrated in Figure 5-6.
5-6
Session 1: Separator
24. Click Add -> to move this component to the Component Name/ Alias field (see Figure 5-7).
Figure 5-7: Component Selection Window
25. Repeat the previous two steps for each of the other components: METHANE, ETHANE, PROPANE, IBUTANE, NBU-
5-7
TANE, IPENTANE, PENTANE, HEXANE, and HEPTANE (these are the valid library component names). Figure 5-8 illustrates the display after all the components are added.
Figure 5-8: Component Selection Window
Note: The border of the Component Name/Alias is now blue. This color indicates that data requirements were satisfied with usersupplied data.
26. There are no red-bordered fields, indicating no additional required entries. Click OK to exit this window.
Note: It is possible to select components without typing their
names. 27. Click Select from Lists in the Component Selection window. This opens another dialog box that groups various components into lists. 28. Choose a list, highlight the desired components in the Component Full Name field, and click Add Components. The highlighted components are added to the simulation. All the components in this example are included in the Most Commonly Used list.
(EOS). It provides good results for systems of similar components such as all the paraffins system in this exercise. The noncondensable component Nitrogen should not be a problem at the anticipated operating conditions. To select the thermodynamic method, open the Thermodynamic Data dialog box using one of the following procedures: 29. Click the equilibrium diagram icon outlined in red, on the toolbar, to select from a list of common thermodynamic methods, generalized correlations, liquid activity methods, special packages, user-added, or equation of state methods. Or 30. Select Input at the top of the screen and choose Thermodynamic Data as shown in Figure 5-9.
Figure 5-9: Defining Thermodynamic Methods
This opens the Thermodynamic Data dialog box illustrated in Figure 5-10. It offers many systems of thermodynamic calculation methods. For example, the predefined Peng-Robinson thermodynamic system uses the Peng-Robinson cubic equation of state to calculate K-values, liquid and vapor phase enthalpies and entropies, and vapor phase densities. It uses API methods to calculate liquid densities. To select a predefined thermodynamic system of methods within the Thermodynamic Data window:
5-9
31. Select Most Commonly Used option from the list labeled Category. 32. Select Peng-Robinson from the Primary Method list box, as shown in Figure 5-10.
Figure 5-10: Thermodynamic Data Entry Window
33. Click Add-> to include this method set in the list of Defined Systems (see Figure 5-11).
Note: Since we have included only a single method set, it serves
as the Default System (see Figure 5-11). You may set or change the default system whenever more than one method set is included in a simulation.
5-10
Session 1: Separator
predefined method sets. The rather well behaved system of components in the current exercise will be adequately modeled using an unmodified, predefined method set. The Modify button in Figure 5-11 opens up a cascading series of dialog boxes that allow you to customize any predefined system. The options are extensive, but are beyond the scope of this tutorial. To use this feature, highlight a thermodynamic set in the Defined Systems list and click Modify to open the Modification dialog box. To delete a method set from the simulation, highlight it in the Defined Systems list and click Delete. Remember that every simulation requires at least one thermodynamic method set to be listed in the Defined Systems list.
computed automatically as the simulation solves. To open the main data entry window of any icon, use any one of the following procedures: 35. Position the cursor on an icon and double-click the left mouse button. The main data entry window for the icon opens. 36. Position the cursor on an icon and single-click the right mouse button to display the options menu. Left-click Data Entry on the menu to open the icons main data entry window. 37. To select a unit or stream, left-click the icon. The selected unit or stream will be highlighted in green. At the top of the screen, select Input and click Data Entry to open the main data entry window of the icon. There is no particular order necessary for data entry; start at any unit operation or stream. When specifying stream data for this example problem, only feed stream S1 requires data to be supplied.
Stream Data
As noted above, stream S1 must be adjusted to work properly in our simplified flowsheet. Table 5-1 shows the adjusted data for stream S1.
5-12
Session 1: Separator
Double-click stream S1 to open the Stream Data dialog box (Figure 5-12).
Figure 5-12: The Stream Data Entry Window
38. Enter data in the red-bordered data entry fields. Optionally, you may enter the description FEED for this stream. To enter flow rate and composition data: Click Flowrate and composition. Select Total Fluid Flowrate in the Fluid Flowrate Specification group box, and specify value 8 for the total stream flow rate as shown in Figure 5-13.
5-13
The rate we have entered has the units of pound-moles per hour. However, Table 5-1 indicates that the rate should be eight cubic meters per second. It is simple to change the dimensional units of this field. To change the dimensional units: 39. Click to highlight the rate field (where 8.0000 are displayed). 40. Click UOM (upper-left in this DEW) to open the Convert Units-of-Measure window as shown in Figure 5-14.
Figure 5-14: Convert Units-of-Measure Window
41. Select Vapor Volume (Vap. Vol.) from the Basis list box. Select m3 from the second column, and sec from the third column. 42. Click Change Units to return to the Stream Data Flowrate and Composition window.
5-14 Session 1: Separator
43. Fill in the fields for each component in the Composition Mole list, using the mole percentages listed in Table 5-1 (see Figure 5-15).
Figure 5-15: Stream Data-Flowrate and Composition DEW
44. Press TAB to move to the next field. For example, enter 7.91 for Nitrogen. Press TAB and enter 73.05 for methane, and so on. Figure 5-15 shows the filled-in values through Pentane. If desired, use the scroll bar to move through the list. 45. After the composition data has been entered, click OK to return to the main Stream Data window. To specify the feed stream temperature and pressure: 46. For the First Specification data field, select Temperature option, as shown in Figure 5-16. 47. Enter the temperature value of 84.
Note: The UOM is F.
5-15
48. Choose Pressure from the Second Specification drop-down list box and enter a value of 587.7 (psia). The completed Stream Data window should appear as in Figure 5-17.
Figure 5-17: The Completed Stream Data Entry Window
49. No fields remain bordered in red, so, click OK to return to the PFD view.
5-16
Session 1: Separator
An entry here is not required because PRO/II automatically assumes a default pressure drop of 0.0 psi if you do not enter either a pressure or a pressure drop value. 51. Click Unit Specification and select Duty as the second specification for the flash drum. A default value of 0.0 is provided by PRO/II Software for this duty. Note the green border.
Figure 5-18: The Flash Drum Data Entry Window
Figure 5-18 illustrates the completed Flash Drum main DEW. There are no red-bordered areas left that require data. 52. Click OK to continue.
55. Supply a name for the simulation data file by typing SESSION1. 56. If desired, use the drop-down navigation window to select a storage directory. 57. Click OK to continue. The main PRO/II PFD window now should look similar to Figure 5-20.
Figure 5-20: The Main PRO/II with PROVISION Window
Note: The unit identifier for the flash drum unit, F1, is no longer
bordered in red. This means that all process data required for this unit has been specified.
5-18 Session 1: Separator
58. Continue entering data for the other process units. To provide data for the Valve: 59. Double-click the valve icon on the PFD to bring up the Valve data entry window.
Figure 5-21: The Valve Data Entry Window
Optionally, you may enter a description for the unit. For e.g., VALVE. 60. Select the Outlet Pressure option in the Operating Parameter field and enter the value of 125 psia. 61. Click OK to return to the main window. The completed Valve data entry window is shown in Figure 5-21. To provide data for the Expander: 62. Double-click the expander icon to open the Expander unit data entry window. Optionally, you may enter a description for the unit, e.g., EXPANDER. 63. Select the Outlet Pressure option in the Pressure and Work Specifications field and input a value of 125 psia. 64. Change the Adiabatic Efficiency entry from its default value of 100% to 80% as shown in Figure 5-22. 65. Click OK to continue.
5-19
The main PRO/II window will now look like Figure 5-23
Note: There are no remaining toolbar icons, unit identifiers, or stream identifiers bordered in red. That means all process data required for this flowsheet have been specified.
66. Save the simulation data file again under the name SESSION1 by selecting Save under the File menu. 67. Run the simulation.
5-20
Session 1: Separator
Alternatively, you can more closely control the simulation via the Run palette. To display the Run palette, go to the View menu, highlight Palettes, and click Run. From the Run palette, you can: 68. Click Check Data on the floating Run palette to check if there are any errors in your flowsheet. If there are errors or warnings, the Status button on the Run palette will be outlined in red or yellow. 69. Click Status to bring up the Flowsheet Status window. This window displays the errors or warning messages generated by the flowsheet data. 70. Correct the errors in your flowsheet. If there are no errors or warnings, the Status button will be outlined in black. To continue to run the simulation from this point:
5-21
Note: The Programmers File Editor program is the default editor for viewing output reports. Use the scroll bar to view the output.
74. While in the Programmers File Editor window, select the Print option from the File menu to print the output, if desired. 75. Select the Exit option from the File menu in the Programmers File Editor to close the output report.
5-22
Session 1: Separator
A window displaying the stream condition, including the vapor and liquid mole fraction, enthalpy, and the composition in each phase (see Figure 5-25) appears. This information is saved in a file each time the flash tool executes.
Figure 5-25: Flash Results for Stream S1
viewing output reports. The Editor item on the Options menu provides a convenient way to change this. Simply enter the full directory path and file name of any other installed text editor, such as Notepad or WordPad.
PRO/II 9.1 Getting Started Guide 5-23
This completes Session 1 of the tutorial. You may take a break if you want to. If you continue with Session 2, you will learn about other interesting PRO/II features, including the following: 78. Displaying different views of a single flowsheet (e.g., full and magnified views) in multiple viewport windows. 79. Using the Specification and Define features. 80. Entering data for a column. 81. Changing the default dimensional units. 82. Modifying the thermodynamic property calculation methods. Taking Session 2 is not a prerequisite for using PRO/II Software. You could end your tutorial session here and begin working on your own simulations. On the other hand, you can come back to the tutorial any time, if you decide to continue later.
5-24
Session 1: Separator
PRO/II loads this database file and displays the flowsheet from Session 1 on the PFD. All the data previously entered in all the Data Entry Windows is still there. If the PFD palette is not displayed:
on the toolbar.
To hide or display the Run palette: 3. Select Palettes from the View menu and uncheck the Run option. To bring the Run palette back into view, recheck the Run option from ViewPalettes menu.
6-1
4. 5.
With Figure 6-1 as a guide, add the missing unit operations to the PFD. Select the additional process units - two heat exchangers, a compressor and a column - and place them on the PFD.
unit icon on the PFD palette. Then, hold down the <Shift> key while clicking the PFD. 6. When the column is placed on the PFD, PRO/II Software displays an additional window that requires you to specify the number of trays. Specify 10 trays. Include a reboiler by making sure a check mark appears in the Reboiler check box. Omit the condenser by clicking the Condenser check box to remove the check mark. The complete window is illustrated in Figure 6-2.
7. 8.
Your PFD should now appear similar to Figure 6-2. The placement of the unit operation icons that you added probably will be different from shown. If you previously ran Session 1 successfully, the unit operations and streams (that already have been solved) appear in dark blue.
but PRO/II Software allows you to change it. Position the cursor anywhere in the PFD window. Click the right mouse button to display Set Title... Click Set Title... to open the Set Window Title DEW. Enter your new title and press OK. For this tutorial, we will leave the name unchanged.
6-2
PRO/II Software allows you to open multiple view windows of the simulation PFD drawing. This feature allows you to view the process units easily on large flowsheets. To open a second view of the flowsheet PFD, and to tile both windows horizontally, either: 9. or 10. Click on the main PRO/II toolbar to bring up the Flowsheet:2 window. 11. Next, open the Window menu on the main PRO/II menu bar and select Tile Horizontally. Select New View from the Window menu on the main PRO/II menu bar to bring up the Flowsheet:2 window.
6-3
may not be visible on the toolbar, since not all the available icons will fit if the window has been resized or the toolbar has been modified. It is simple to add, remove, or rearrange items on the tool bar. Click the View menu Toolbar item to open the Toolbar Customization dialog box. Make sure New View is in the Selected Items list box. Use the Up, Down, Top, and Bottom buttons to rearrange the items. Toolbar icons display left-to-right, corresponding to the top-to-bottom order of entries in the Selected Items list box. To view the entire PFD in the Flowsheet:1 window, and to focus on the two heat exchangers in the Flowsheet:2 window, follow the steps below: 12. To select the Flowsheet:1 window, click on its title bar. 13. Click on the toolbar to view the entire flowsheet in window Flowsheet:1. 14. Select the Flowsheet:2 window by clicking on its title bar. 15. Click on the toolbar of the main PRO/II window. The cursor changes to a magnifying glass. 16. Move the (magnifying glass) cursor to the Flowsheet:2 window. 17. Click and hold down the left mouse button near the two heat exchangers. 18. While holding down the left mouse button, drag the mouse until the two heat exchangers are enclosed in a blue selection rectangle. 19. Release the mouse button. The area bounded by the selection rectangle zooms to fill the entire Flowsheet:2 window (see Figure 6-3).
6-4
20. Click Streams on the floating PFD palette and lay down the following streams: 1. 1. 1. 1. 1. 1. A connector stream from the top of the demethanizer column to the inlet of one side of the first heat exchanger. A connector stream from the outlet of this side of the heat exchanger to the inlet of the compressor unit. A product stream from the outlet of the compressor unit. A connector stream from the second outlet of the first heat exchanger to the inlet of the second heat exchanger. A product stream from the outlet of the second heat exchanger. A product stream from the reboiler of the column unit.
Note: Lay down streams that connect units visible in the different
view windows by pulling the stream from one view to the other. This is especially helpful for large flowsheets. You can now close the second window, Flowsheet:2, and maximize the Flowsheet:1 window. 2. Double-click the control-menu box of Flowsheet:2 to close it.
6-5
3.
The PFD should look similar to Figure 6-4 after all the units and streams have been added.
As mentioned in Session 1, the composition of the feed stream to the first unit (the gasgas heat exchanger) is identical in composition to the stream already laid down as the feed to the flash drum, S1. To avoid repeating all data entry steps for the feed to the first process unit, we disconnect this stream from the flash drum unit, and reconnect it to the first heat exchanger by following these steps: 4. Move the mouse to the end of stream S1 attached to the flash drum. The mouse pointer should change from a left arrow to a right arrow when the pointer is very close to the end of the stream. Click and hold the left mouse button, and move the end of stream S1 to the inlet of the first heat exchanger E1. Release the mouse button. The feed stream should now be reconnected to the heat exchanger E1.
5. 6.
6-6
example), click on the arrow for that stream. Hold the left mouse button down and pull the stream to its new horizontal position before releasing the mouse button. 7. Repeat the steps above to connect the outlet stream from the expander EX1 to tray 1 of the column unit. Again, repeat the same steps to connect the outlet stream from the valve unit to tray 3 of the column, and to connect the outlet of the second heat exchanger to the inlet of the flash drum.
We have now completely built the flowsheet for the total demethanizer/ expander plant as shown in Figure 6-5 below.
have merely reconnected the previously defined flash drum feed to the gasgas heat exchanger. Before you can run this simulation, you need to provide data for the four units whose identifiers are bordered in red the two heat exchangers, the compressor, and the column and change the temperature and pressure of stream S1.
6-7
10. Change the pressure in the Second Specification field from 587.7 psia to 602.7 psia. The modified Stream Data window appears as shown in Figure 6-6.
Figure 6-6: Modified Stream Data Window for Stream S1
6-8
14. Use Process Stream to specify whether the process inlet and outlet streams are on the cold or hot side. 15. Click Process Stream in the Hot Side field. The Heat Exchanger-Process Streams data entry window appears as in Figure 6-8.
Figure 6-8: HX-Process Streams
16. Select stream S1 (the reconnected feed stream) to feed the hot side, and stream S9 (the feed to the second heat exchanger) as the hot side product. 17. Select stream S6 (the column overhead) as the feed to the cold side, and stream S7 (the compressor feed) as the cold side product. 18. Return to the main data entry window for unit E1. The hot side inletcold side outlet stream temperature approach is required to be 10F.
PRO/II 9.1 Getting Started Guide 6-9
19. Select Specificationon the Heat Exchanger data entry window. The Heat Exchanger Specifications window shown in Figure 6-9 appears. 20. Select the Hot InletCold Outlet Temperature Approach specification option from the Specification drop-down list box and enter a value of 10F.
Figure 6-9: The Heat Exchanger-Specifications Window
21. Return to the main Heat Exchanger data entry window and input a hot side pressure drop value of 10 psi and a cold side pressure drop value of 5 psi in the appropriate Pressure Drop data entry fields (see Figure 6-10).
Figure 6-10: The Heat Exchanger Data Entry Window
22. After returning to the PFD, enter data for the second heat exchanger, E2, by repeating the steps above (see Figure 6-10 and Figure 6-11).
6-10
23. Optionally, give this heat exchanger the description CHILLER This heat exchanger is required to further cool the gas feed S9 down to 84F with a pressure drop of 5 psi across the hot side of the exchanger (see Figure 6-11 and Figure 6-12.
After all the required data has been entered, the data entry window for this exchanger should appear as shown in Figure 6-13.
6-11
Compressor
24. Double-click the compressor icon (C1) to open the main data entry window for this unit (see Figure 6-14). 25. Enter the compressor adiabatic efficiency as 75% in the Efficiency or Temperature Specification field.
Figure 6-14: Compressor Main Data Entry Window
The work done on the compressed gas in unit C1 should equal the work done by the gas in the expander EX1. This specification may be made through the DEFINE feature of PRO/II Software: 26. Select Work from the Pressure, Work, or Head Specification drop-down list box.
6-12
27. Click once in the data entry field directly beside the Pressure, Work or Head Specification drop-down list box. 28. Click Define (see Figure 6-14), which is now active on the data entry window toolbar. This brings up the Definition data entry window (see Figure 6-15).
Figure 6-15: Compressor Definition Window
29. Click the check box for Set Up Definition for Compressor Work. 30. Click the red-linked text Parameter to bring up the Parameter window. 31. Select Expander unit EX1 the Constant/Stream/Unit drop-down list box in the Parameter window (see Figure 6-16).
Figure 6-16: Parameter Window
32. Click the red-linked text Parameter... in the Parameter window to bring up the Parameter Selection window (see Figure 6-17). 33. Select Actual Work from the Parameter data entry field (see Figure 6-17).
6-13
Figure 6-16 through Figure 6-19 show the completed Parameter, Definition, and Compressor data entry windows.
6-14
35. Click OK to return to the main Compressor data entry window shown in Figure 6-20.
Figure 6-20: Completed Compressor Data Entry Window
36. Click OK to save the data and return to the main PFD window.
Column
The red label T1 of the column indicates data entry is required. 37. Double-click any part of the column icon on the PFD to open the main data entry window for this unit.
Note: The Pressure Profile, Feeds and Products, and Performance
Specifications buttons on the icon are red, indicating required user input.
6-15
38. Click to specify the phase and tray location of the feed and product streams. The Column Feeds and Products data entry window should appear. 39. Specify that stream S4 (the expander product) is fed to tray 1 and S5 (the valve product) fed to tray 3. 40. Enter a rate of 2000 lb-mol/hr for the overhead vapor product S6 from tray 1. Refer Figure 6-22, which shows this window with all the data filled in.
Figure 6-22: Column-Feeds and Products Data Entry Window
41. As soon as you click OK, PRO/II displays the Transfer to Specification dialog box (see Figure 6-23).
6-16
This gives you the option to use the overhead rate just entered for stream S6 as a performance specification. We are more interested in the purity of the (liquid) bottoms product (stream S11 in this example). We will enter a performance specification on that stream very soon.
42. Click NO to reject the option and return to the main Column data entry window.
43. Click in the main Column data entry window to specify the pressure of the top tray. The Column-Pressure Profile window appears (see Figure 6-24).
Figure 6-24: Column Pressure Profile Data Entry Window
44. Specify a value of 125 psia for the top tray pressure in the Overall Specification field. By accepting the default setting of no pressure drop per tray, no other data is required. Figure 6-24 shows the complete window. 45. Click OK to return to the main Column data entry window. We now need to specify that the methane (C1) to ethane (C2) ratio in the bottoms product equals 0.015.
6-17
46. Click on the main Column data entry window. This opens the Column-Specifications and Variables window.
Figure 6-25: Column-Specifications and Variables Window
47. Click the check box for Add Specifications and Variables and the Active check box on the right (see Figure 6-25). 48. Click the red-linked text Parameter... in the Specifications field to bring up the Parameter window (see Figure 6-26). 49. Select Stream from the Stream/Unit drop-down list box. Select the column bottoms product stream (S11) as in Figure 6-26.
Figure 6-26: Parameter Window
50. Click the red-linked text Parameter... to open the Parameter Selection window. 51. Select Flowrate from the Parameter field and choose Selected Components from the Flowrate field. 52. Select METHANE from both the Starting Component and Ending Component drop-down list boxes (see Figure 6-27).
6-18
53. The completed Parameter window is shown in Figure 6-28. Click OK to continue.
Figure 6-28: Completed Parameter Window
54. Click the green-linked text = sign in the Specifications field of the Column Specifications and Variables window as shown in Figure 6-29
6-19
55. Click the division sign / in the pop-up box. The resulting window should now appear as shown in Figure 6-30.
Figure 6-30: Column Specifications and Variables Window
56. Click the red-linked text Parameter in the Specifications field to open the Parameter window. 57. Select Stream from the Constant/Stream/Unit drop-down list box. 58. Next, select stream S11 (the bottom product) from the Stream Name drop-down list box as shown in Figure 6-31.
6-20 Session 2: Complete Expander Plant
59. Click the red-linked text Parameter... to open the Parameter Selection window. 60. Select Flowrate from the Parameter field, Selected Components from the Flowrate field, and ETHANE from both the Starting Component and Ending Component drop-down list boxes.
Figure 6-32: Completed Parameter Selection Window
61. Click OK to return to the Parameter window, which is now complete (see Figure 6-33).
Figure 6-33: Completed Parameter Window
6-21
63. Click the red-linked text value in the Specifications field of the Column Specifications and Variables window. Enter a value of 0.015 in the data entry field that appears. Press ENTER or Return (on your keyboard). Figure 6-35 shows the completed column purity specification on the bottoms product.
Note: No elements of the specification are red. Figure 6-35: Completed Specification
The column model in PRO/II Software requires a specific number of degrees of freedom before it can solve successfully. Too many degrees of freedom result in an indeterminate problem that cannot be solved uniquely. Too few degrees of freedom indicate that the problem is over-specified, and cannot solve because not all the specifications can be met simultaneously. The PROVISION input
6-22
windows are designed to help ensure that the number of degrees of freedom is correct, so that the model is properly defined. Each specification that is declared removes one degree of freedom. Each variable that is declared adds one degree of freedom. When the number of variables equals the number of specifications, the model is properly defined and can solve to a unique solution. Since this column has one specification, it also requires one variable. Looking at Figure 6-36, we see that PRO/II Software has (by default) added the reboiler duty as a variable. This is an acceptable choice for the needs of this simulation, and we will not alter it in this tutorial. If you wish to explore the available variables, click the blue-linked text Column T1 Duty of Heater REBOILER in the Variables field. This opens the Variable window shown in Figure 6-36.
64. Click the blue-linked text Duty of Heater REBOILER to view the Parameter Selection window. PRO/II Software has already selected Heat Duty from the Parameter list and has entered the REBOILER in the Heater field by default (see Figure 6-37).
6-23
65. Press Cancel to return to the Variable window. 66. Press Cancel to return to the Specifications and Variables window. 67. Press Cancel to return to the main column data entry window, as illustrated above in Figure 6-31. No elements are displayed in red, so the column does not require more data. 68. Click OK to save the data and exit the column. The main PRO/II window now is illustrated in Figure 6-38.
6-24
stream identifiers bordered in red. This means that all process data required for this flowsheet have been supplied. 69. Save the completed data file under the new name SESSION 2. Use the Save As option from the File menu. Run the simulation.
71. When there are errors, warnings or messages to report a message box will pop up to inform prior to executing the simulation. Should that occur, correct your flowsheet if necessary, or, if there are no errors and you determine the messages to be acceptable, click Continue to proceed with the simulation.
on the toolbar.
6-25
menu item to bring up the Messages window. You may have to resize the main PFD window if the Messages window is hidden. This window will contain a scrolling history of the calculation steps completed. To view the output report,
Click on the toolbar to bring up the Generate Report for Session 2 window.
The stream and process unit results are automatically shown in a Programmers File Editor window. They have been written to disk storage in the file SESSION2.OUT.
6-26
7-1
7.
Right-click a stream. This displays the pop-up actions menu shown in Figure 8-1
8. 9.
Choose Display... from the pop-up actions menu to open the Stream Style window (Figure 7-2) Choose Circle from the drop-down list box for the Stream Label Border.
10. Click OK to return to the PFD. You will see the style of the stream label change for the selected stream.
Note: You may select each stream individually or several streams at once. To make changes to multiple streams, simply drag a selection rectangle around the area containing the desired streams before right-clicking. 7-2 Session 3: Presentation of Output
To use the circle border as the default border for subsequent streams on the PDF: 11. Choose OptionsDrawing Defaults Stream Display... on the main menu bar. This opens the Stream Style window (Figure 7-3). 12. Choose Circle from the drop-down list box for the Stream Label Border. This option is available only when the Name option for Stream Label Type is selected.
The default Property List is the Property Label List, which displays the stream name, the temperature, the pressure, and the flow rate of the stream.
Figure 7-5 illustrates the PFD drawing after applying the Property Label List to streams S1 and S8.
Figure 7-5: The PFD Using Stream Property Lists for Stream Labels
7-4
about a dozen predefined stream property lists that can be displayed for streams. These lists should be used selectively, since they can occupy a lot of PFD real estate If the resolution of the display makes it difficult to read the property lists, use PRO/IIs Zoom feature to enlarge the table. Simply press PgUp to increase the resolution until the size of the text is comfortable to read.
Choose Stream Property Lists from the Options menu on the main PRO/II menu bar. This opens the Define Stream Property List dialog box. Analogous tools are available for displaying properties of unit operations.
To export the PFD to the clipboard: 17. Choose FileExport from the main PRO/II menu bar. 18. Click the radio button for Flowsheet Drawing. 19. Click OK. PRO/II Software displays a dialog box confirming that the flowsheet has been exported to the clipboard.
7-5
rendering of the PFD drawing. Only the contents of the PFD window are captured. This is superior to the standard Windows Alt+PrtSc screen capture, which is limited to the display terminal resolution and captures the entire PRO/II program window.
7-6
Note: Microsoft Excel Workbook must be configured to allow macros before this export feature will work. In Excel Workbook , navigate to ToolsMacroSecurity and ensure the security level is set to Medium (preferred) or Low. Next, close Excel WOrkbook to force the change to take effect.
7-7
You can resize this page or make this page one cell in a grid of pages. To make changes to the page style: 24. Double-click the left mouse button on the page boundary to bring up the Page Setup window, as shown in Figure 7-9.
Figure 7-9: Page Setup window
7-8
As you did for the entire PFD, you can also select pages of the flowsheet PFD and export them to the clipboard. Choose the radio button Selected Page of Flowsheet Drawing from the Export window (see Figure 7-6). Figure 7-10 shows the result of exporting the page from the PFD and pasting it in MS Word.
7-9
Creating Plots
PRO/II Software has built-in plotting capability, which can be used to paste Excel plots directly into your reports. In the demethanizer flowsheet, you may want to view the column profiles. To set up your plot options: 25. Select the OptionsPlot Setup... from the main PRO/II window. 26. Choose the running Excel version from the drop-down list box. 27. Click OK to return to the PFD. To create a plot: 28. Select the OutputGenerate Plot from the main PRO/II window to display the PRO/II - Generate Plot window, as shown in Figure 7-12. 29. Select column T1 from the list displayed in the Units for Selection group box. 30. Select the type of plot you want to generate from the Available Plots list.
7-10 Session 3: Presentation of Output
31. Click Plot... to create the Excel plot. Output is shown in Figure 7-12.
Figure 7-12: Generate Plot Window
7-11
33. Click the radio button Viewer in the Display Results Using: group box and click OK to return to the PFD. 34. Select the stream for which you want to view the results. 35. Right-click on the stream and choose View Results from the menu. On the other hand, you can select the stream and click View on the toolbar. An HTML viewer window containing the stream results similar to Figure 7-15 will appear. The HTML files are written to the C:\Windows\Temp directory. Your default browser may also allow you to print, save, or export the results to other formats.
7-12
Block Diagrams
For large flowsheets, you may want to organize the flowsheet with subflowsheets. This is done using the PRO/II block diagram feature. To create a block diagram: 36. Drag a selection rectangle around the section of the flowsheet containing the heat exchangers and the compressor, as illustrated in Figure 7-16. 37. Right-click and select the Collapse item from the right mouse menu. The selection will be collapsed into a block diagram (called BD1 by default) as shown in Figure 7-17. 38. Use the View 2 option, as described in Session 2, to view the unit operations within the block diagram in a separate view. Simply double-click on the block diagram to expand the icon. Block diagrams can also be nested.
7-13
7-14
Figure 7-18: View 1 is the top level PFD. BD1-View 1 is the block diagram BD1
This completes Session 3 of the tutorial. In this session, you have learnt some of the features that allow you to transfer your PRO/II results to reports and other applications. Your tutorial session ends here. Good luck working on your own flowsheets.
7-15
7-16
Index
A
Adding units, 5-3, 5-4 work, 6-12 Connect units, 5-4 Connectivity unsatisfied, 5-5 Converting older simulation databases, 2-6 Custom installation PRO/II, 2-2
B
Bordered items color coded, 4-21, 5-5, 5-13, 6-7, 6-25 Building the Flowsheet units, 5-3, 5-4
D
Data bases Converting older, 2-6 Desktop Icons, 2-5 Dimensional units setting local units, 5-14 Directory Structure, 2-5 Directory structure PRO/II, 2-5 Disk space PRO/II Requirements, 1-3 Documentation online Help system, 1-ix online PDF files, 1-ix
C
Chemistry Wizard OLI, 2-1, 2-5, 3-19 Colors color coded items, 4-21, 5-5, 5-13, 6-7, 6-25 Column condenser, 6-2 feeds and products, 6-16 overhead, 6-16 pressure profile, 6-17 reboiler, 6-2 trays, 6-2 Compatability Security license files, 3-12 Compiler Requirements, 1-2 Composition defining stream, 5-13 composition, 5-1 Compressor adiabatic efficiency, 6-12 define, 6-13 main data entry window, 6-12
E
Electrolytes Chemistry Wizard, 2-1 Errors Security, 3-18 Expander adiabatic efficiency, 5-19
I-1
F
Feed stream composition, 5-13 main data entry window, 5-13 Feeds, 5-5 File Opening, 6-1 FLEXlm 9.5, 2-3 multiple license FAQ, 3-8 multiple server FAQs, 3-8 multiple server security, 3-9 performance on WAN, 3-12 Restricting Server access, 3-9 Security, 1-4 security, 1-4 Security FAQs, 3-8 Security options file, 3-11 Switching Security, 1-5 FLEXNET 11, 1-5, 2-3 Floating PFD palette, 5-2 Flow rate modifying units of measure, 5-14 Flowsheet, 5-2 connectivity, 5-5 Flowsheet errors, 5-21
I
Icons desktop, 2-5 PRO/II, 2-5 Install Default directory, 2-5 Local Version of PRO/II, 2-2 Installation Custom, 2-2 media, 1-1 Testing PRO/II, 2-6 troubleshooting, 3-1 Installation Requirements, 1-1 Installing PRO/II, 2-1
L
Library components, 5-7 Licenses invalid Security, 3-10 Security multiple, 3-8 Linked text, 6-13
G
Gas-gas heat exchanger, 6-8 GUI color coded items, 4-21, 5-5, 5-13, 6-7, 6-25
M
Maintenance Modify, repair, remove, 2-7 Messages window, 5-21, 6-25 Modify PRO/II, 2-7
H
Hardware Requirements, 1-3 Hardware requirements, 1-2 Heat exchangers hot product temperature, 6-10 specifications, 6-10 specifying process streams, 6-9 Help
N
Notepad, 5-23
O
OLI
Index
I-2
Chemistry Wizard, 2-1, 2-5, 3-19 Online documentation, 1-x Opening a file, 6-1 Operating System Requirements, 1-2, 1-3 Options PRO/II Selecting security, 2-3 Security, 1-4 Switching Security, 1-5 Output Report generation, 2-6 sample problem, 2-6
R
Reconnecting streams, 6-6 Remove PRO/II, 2-7 Repair PRO/II, 2-7 Report Output generation, 2-6 Sample problem output, 2-6 Reqirements Operating System, 1-2 Requirements Fortran Compiler, 1-2 PRO/II Disk Space, 1-3 Results Reviewing, 2-6 results, 4-24
P
Package contents, 1-1 PaletteSee PFD palette, 6-5 PFD palette, 6-5 PRO/II color coded items, 4-21, 5-5, 5-13, 6-7, 6-25 Custom installation, 2-2 default directory structure, 2-5 FLEXln options, 3-11 icons, 2-5 Install Local Version, 2-2 Installation testing, 2-6 Installing, 2-1 Modify, repair. remove, 2-7 Output Report generation, 2-6 Reviewing results, 2-6 Sample output, 2-6 Security troubleshooting, 3-1 Security FAQs, 3-8, 3-12 Security, Selecting, 2-3 PRO/II Requirements Disk Space, 1-3 Process flow diagram, 4-22 Process unit description, 5-17 program, 4-24 PROVISION color coded items, 4-21, 5-5, 5-13, 6-7, 6-25
S
Security FLEXlm, 1-4 installation
troubleshooting, 3-1 OLI Chem Wizard, 3-19 options, 1-4 Selecting for PRO/II, 2-3 Switching, 1-5 Security FAQs downloading license security software, 3-17 drive read failure, 3-17 errors running Win NT, 3-18 finding host IDs, 3-11 FLEXlm options file, 3-11 FLEXlm performance on WAN, 3-12 invalid license keys, 3-10 launching FLEXlm server, 3-9 license file compatibility, 3-12 license usage configuration Configuration Security license FAQ, 3-11
multiple FLEXlm servers, 3-8 multiple license files, 3-8 restricting access to FLEXlm server, 3-9 security and firewalls, 3-8, 3-12 security chip missing, 3-18
I-3
using mixed security types, 3-17 Server restricting access, 3-9 Software Requirements, 1-3 Software requirements, 1-2 Streams mode, 5-4 products, 5-11 Structure Default directory, 2-5 Directory, 2-5
U
Unsatisfied connectivity, 5-5 USB security, 1-4 Security FAQs, 3-12
T
Technical support centers, 1-xii Testing PRO/II installation, 2-6 Token, 2-3 Tokennet, 2-3 Troubelshooting Security failure, 3-17 Troubleshooting installation problems, 3-1
V
Valve outlet pressure, 5-19 Viewing output reports, 6-26 Viewports multiple windows, 6-3
W
Wizard OLI Chemistry, 2-1, 2-5, 3-19
Index
I-4