MV 3000 Getting Started Manual
MV 3000 Getting Started Manual
SAFETY INSTRUCTIONS
Care has been taken with the design of this product to ensure that it is safe. However, in
common with all products of this type, misuse can result in injury or death. Therefore, it is very
important that the instructions in this manual and on the product are observed during
transportation, commissioning, operation, maintenance and disposal.
This technical manual must be regarded as part of the product. It should be stored with the
product and must be passed on to any subsequent owner or user.
Local safety laws and regulations must always be observed.
Persons working on the product must be suitably skilled and should have been trained in that
work for these products.
The product is a component designed for incorporation in installations, apparatus and
machines.
The product must not be used as a single item safety system. In applications where
maloperation of the product could cause danger, additional means must be used to prevent
danger to persons.
Product approvals and certifications will be invalidated if the product is transported, used or
stored outside its ratings or if the instructions in this manual are not observed.
Third party approvals to safety standards UL 508C and CSA C22.2 No 14 are marked on the
product.
In the European Union:
Products within the scope of the Low Voltage Directive, 73/23/EEC as amended are CE
marked.
The product complies with the essential protection requirements of the EMC directive
89/336/EEC as amended, when installed and used as described in this manual. The
requirements of the EMC Directive should be established before any installation, apparatus
or machine which incorporates the product is taken into service.
A machine must not be taken into service until the machine has been declared in conformity
with the provisions of the Machinery (Safety) Directive, 98/37/EEC.
Acknowledgements
Microsoft Windows is a registered trademark of the Microsoft Corporation.
CHANGES FROM PREVIOUS EDITION
Previous edition: Rev. 0005 (01/03) ratings in Tables 2-1 and 2-2 updated
Options in Section 9 updated to include EMC Filters and
ferrites, 2
nd
CAN port and new PROFIBUS module
This edition: Rev. 0006 (06/06) New Control Diagrams and Company
name change. In Section 9 Ethernet Module added and
FIP modules deleted.
See over for default input/output diagram
Getting Started Manual
ALSPA MV3000e
Active Energy Management Drives (MicroCubicle Style Products Only)
Publication No. T2002EN Rev. 0006 (06/06)
Page i
SAFETY INSTRUCTIONS
Care has been taken with the design of this product to ensure that it is safe. However, in
common with all products of this type, misuse can result in injury or death. Therefore, it is very
important that the instructions in this manual and on the product are observed during
transportation, commissioning, operation, maintenance and disposal.
This technical manual must be regarded as part of the product. It should be stored with the
product and must be passed on to any subsequent owner or user.
Local safety laws and regulations must always be observed.
Persons working on the product must be suitably skilled and should have been trained in that
work for these products.
The product is a component designed for incorporation in installations, apparatus and
machines.
The product must not be used as a single item safety system. In applications where
maloperation of the product could cause danger, additional means must be used to prevent
danger to persons.
Product approvals and certifications will be invalidated if the product is transported, used or
stored outside its ratings or if the instructions in this manual are not observed.
Third party approvals to safety standards UL 508C and CSA C22.2 No 14 are marked on the
product.
In the European Union:
Products within the scope of the Low Voltage Directive, 73/23/EEC as amended are CE
marked.
The product complies with the essential protection requirements of the EMC directive
89/336/EEC as amended, when installed and used as described in this manual. The
requirements of the EMC Directive should be established before any installation, apparatus
or machine which incorporates the product is taken into service.
A machine must not be taken into service until the machine has been declared in conformity
with the provisions of the Machinery (Safety) Directive, 98/37/EEC.
Acknowledgements
Microsoft Windows is a registered trademark of the Microsoft Corporation.
CHANGES FROM PREVIOUS EDITION
Previous edition: Rev. 0005 (01/03) ratings in Tables 2-1 and 2-2 updated
Options in Section 9 updated to include EMC Filters and
ferrites, 2
nd
CAN port and new PROFIBUS module
This edition: Rev. 0006 (06/06) New Control Diagrams and Company
name change. In Section 9 Ethernet Module added and
FIP modules deleted.
See over for default input/output diagram
Getting Started Manual
ALSPA MV3000e
Active Energy Management Drives (MicroCubicle Style Products Only)
Publication No. T2002EN Rev. 0006 (06/06)
Page ii
TB7
1
2
CLOSE
LCN
TB1
9
8 DIGOUT1
7
6
5 DIGOUT2
4
3
2 DIGOUT3
1
TB2
2 +24V Aux Input
1 0V AuxInput
TB3
10 +24V O/P
9 INTERLOCK
8 DIGIN 1
7 DIGIN 2
6 DIGIN 3
5 DIGIN 4
4 DIGIN 5
3 DIGIN 6
2 +24 V O/P
1 0 Volts (digital)
TB4
9 HSIO -
8 HSIO +
7 CAN LO
6 CAN HI
5 GND
4 RS485 Rx-
3 RS485 Rx+
2 RS485 Tx-
1 RS485 Tx+
TB5
12 A +
11 A -
10 B +
9 B -
8 Z +
7 Z -
6 +24V
5 FB+
4 +5V
3 0V
2 FB-
1 M_PTC
TB6
9 +10V
8 AN I/P 1+
7 AN I/P 1 -
6 AN I/P 2 +
5 AN I/P 2 -
4 -10V
3 AN GND
2 AN O/P 1
1 AN O/P 2
4 D AN I/P 1
3 C AN I/P 2
AN O/P 1
1 C
AN O/P 2
20 mA 10 V
Set the DIP switches to
Configure the analogue
I/O for Current or Voltage
operation. Then refer to
menu 7, to configure the
relevant parameters.
PLANT INTERLOCK
TRIP RESET
KEYPAD/REMOTE
STOP
RUN
To run drive, INTERLOCK
must be connected to +24V
HEALTHY
SFE
RUNNING
AT VOLTS
0 V
Lamps on
cabinet door
AUX R
EARTH
(GROUND)
DC+
Internal
Dynamic
Braking
Unit
(Optional)
Switch
settings
shown in their
factory default
state.
AUX S
AUX T
To Programmable
logic controller...etc.
(Optional)
A
L
S
P
A
M
V
3
0
0
0
e
2 B
RS232 link for Keypad, PC
and PLC connection, on
harbour.
(Update time 100 ms)
(open =Keypad)
DC-
TB22
2
4
R/U
S/V
T/W
FAN
LOAD POWER FEEDFORWARD
fromMachine Bridge
MAINS BRIDGE INPUT/OUTPUT DIAGRAM
SFE RUNNING
Lamp supply
RUN PERMIT
LCN AUX
See Ancillary Components
(Figure 2) for details of
LCN AUX wiring
M
a
i
n
s
B
r
i
d
g
e
SW1
X
X
FromPWM
filter fuse
indicator and
thermostat
(Figure 2)
Fromline reactor
thermistors
(Figure 2)
TB1
DIGOUT 1
DIGOUT 2
DIGOUT 3
TB2
2 +24V AuxInput
1 0V Aux Input
TB3
10 +24V O/P
9 INTERLOCK
8 DIGIN 1
7 DIGIN 2
6 DIGIN 3
5 DIGIN 4
4 DIGIN 5
3 DIGIN 6
2 +24 V O/P
1 0 Volts (digital)
TB4
9 HSIO -
8 HSIO +
7 CAN LO
6 CAN HI
5 GND
4 RS485 Rx-
3 RS485 Rx+
2 RS485 Tx-
1 RS485 Tx+
TB5
12 A +
11 A -
10 B +
9 B -
8 Z +
7 Z -
6 +24V
5 FB+
4 +5V
3 0V
2 FB-
1 M_PTC
TB6
9 +10V
8 AN I/P 1+
7 AN I/P 1 -
6 AN I/P 2 +
5 AN I/P 2 -
4 -10V
3 AN GND
2 AN O/P 1
1 AN O/P 2
4 D AN I/P 1
3 C AN I/P 2
AN O/P 1
1 A AN O/P 2
20 mA 10 V
Set the DIP switches to
Configure the analogue
I/O for Current or Voltage
operation. Then refer to
menu 7, to configure the
relevant parameters.
REF2:
4 - 20 mA
LOOP
METER
Speed Feedback
20K
PLANT INTERLOCK
REVERSE
ANALOGUE REF1/2
TRIP RESET
KEYPAD/REMOTE
STOP
RUN
To run drive, INTERLOCK
must be connected to +24V
HEALTHY
RUNNING
AT SPEED
0 V
Lamps on
cabinet door
R/U
T/W
FromEncoder
and motor PTC
(Figure 2)
S/V
To Programmable
logic controller...etc.
(Optional)
A
L
S
P
A
M
V
3
0
0
0
e
2 B
REF1: +/-10V
At factory default state,
Analogue References are only
available in REMOTE mode
High Speed Digital I/O
(open =Keypad)
(open =Ref. 1)
AUX R
DC-
DC+
Internal
Dynamic
Braking
Unit
(Optional)
AUX S
AUX T
TB22
2
4
FAN
9
8
7
6
5
4
3
2
1
MACHINE BRIDGE INPUT/OUTPUT DIAGRAM
EARTH
(GROUND)
TB7
1
2
LOAD POWER FEEDFORWARD
to the Mains Bridge
Screened (shielded) twisted pair must be used.
Observe polarity +,
*
*
AN O/P 2 switch shown in the AEM Drive
position, NOT in the Default position. The other
three switches are shown in Default position.
M
a
c
h
i
n
e
B
r
i
d
g
e
SW1
Figure 1 Bi-directional converter input/output diagram (default)
Lamp supply
(24V Lamp)
See Figure 2 for Power Wiring
Screened (shielded) twisted pair must be
used.
Observe polarity +,
At each end of cable,
connect screen (shield) to
chassis as shown
Alternative RUN/STOP control for single
switch operation, Mains or Machine
bridge:
CLOSE THE "STOP" SWITCH =RUN
OPEN THE "STOP" SWITCH =STOP
DIGIN 1
DIGIN 2
STOP
RUN
+24 V
0 V
RS232 link for Keypad, PC
and PLC connection, on
harbour.
(Update time 100 ms)
Lamp supply:
A 24 V supply is available
for this purpose, at TB3/2
or TB3/10 (+) with
respect to TB2/1 (0 V).
For ratings, see Table 1
on page iv.
Page iii
110 V supply for
customer use
AC Line Reactor
Part /01
AC Line Reactor
Part /02
PWM Filter
Pre-charge
Circuit
+
Mains
Voltage
Monitor
+
Mains
Network
ALSPA MV3000e
SINUSOIDAL FRONT END (SFE)
230 V fan supply for frame sizes 4, 6 and 7,
not frame size 3
TB5
R/U
DC
DC
S/V
T/W
AUX R
AUX S
AUX T
2
4
TB22
Fan
DC
Link
Fan Transformer
Isolator
(Disconnect)
Auxiliary
fuses
Main
Fuses
Close LCN
+ DC
DC
2
4
TB22
Fan
1
3
TB1
TB6
TB1
TB6
Load Power Feed Forward
User Control
R/U
S/V
T/W
Pre-charge
Circuit
+
Mains
Voltage
Monitor
AUX R
AUX S
AUX T
(Not
connected)
R1
S1
T1
SFE Running
1
2
TB7
R5
S5
T5
R4
S4
T4
R5
S5
T5
1
2
TB7
TB3
6
10
RUN PERMIT
+24 V
LCN
AUX
To
AA
N
(Not required)
to to
Figure 2 Interconnection diagram for an AEM drive
1 2 3 4 5 6 7 TB24
Mains Bridge Machine Bridge
230 V
110 V
X
INTERLOCK
M_PTC
0 V
*
* See SFE default input/output
diagramat Figure 1
INTERLOCK
X X
F
e
r
r
it
e
R
i
n
g
s
(
o
p
t
io
n
a
l)
U
V
W
E
OPTIONAL
ENCODER
PTC
Motor Thermistor
Connect PTC
between:
TB5/1 and TB5/3
G
L
A
N
D
Cabinet
Boundary
To TB5
FB+
FB-
+5 V
0 V
Note: a motor
thermostat can
be
accommodated
by re-
programming a
digital input
ALSPA MV3000
Internal
Dynamic
Braking
Unit
(optional)
Externally fitted
DB Resistor
(optional)
BR
(See Figure 1
inside front cover)
Bi-directional converter Bi-directional converter
Line Contactor (LCN)
1 6
1 6
A A
X
INTERLOCK *
From Encoder
and motor PTC
TB5
See Figure 1 for
connection details
PWM filter
fuses and
"fuse blown"
indicator
A1 A2
R7
S7
T7
Suppressor
EMC Capacitors
(option)
See Section 3.3
EMC Capacitors
(option)
See Section 3.3
Fromfan
transformer
Ancillary Components
Fan Transformer
primary fuses
R2
S2
T2
R3
S3
T3
R4
S4
T4
R6
S6
T6
(See Figure 1
inside front cover)
Cabinet
Boundary
G
L
A
N
D
Cabinet
Earth (Ground)
E
M
C
F
ilt
e
r
(
o
p
t
io
n
a
l
Thermistor
connections
Cable sizes are designated by
numbers, e.g. . These numbers
cross-refer to cable sizes given in
Tables 3-3 to 3-5 in Section 3
(Installation).
The specifications of other components
are given in Section 2.
Basic configuration
Bi-directional converter (2 off)
Line reactor (parts /01 and /02)
PWM filter + protection
Line contactor
Fan transformer
EMC capacitors (optional)
EMC filter (optional)
Page iv
Table 1 I/O panel, connector specifications
TB1 Digital Outputs Specifications
DIGOUT 1 to 3 Volt-free changeover relay outputs Max volts : 250 Vac, 30 Vdc
Max current : 3 A (resistive load)
TB2 Auxiliary Input Supply Specifications
+24 V Aux input Allows monitoring and programming
with main power switched off.
Current, nominal (Keypad+Controller) : 500 mA
Current, max (all versions) : 2.2 A
TB3 Digital Inputs Specifications
Pin Signal Menu 7
3 to 8 DIGIN 1-6 For remote control of drive default
functions are shown in the default I/O
diagram (Figure 1).
Impedance: 15 k
Active: +12 V to +50 V
Inactive: Open circuit or <7 V
9 INTERLOCK Hardware interlock must be made
to enable drive.
Impedance: 15 k
Healthy: +12 V to +50 V
Unhealthy: Open circuit or <7 V
2 & 10 +24 V O/P User supply for peripheral equipment. Volts range: +22.8 V to +25.3 V
Max load: 500 mA
1 0 V (digital) 0 V reference of digital inputs. Connected to earth (ground) internally
TB4 TB4A TB4B Communications Specifications
Pin Pin Pin Signal
1/2 1/2 RS485 Tx +/
3/4 3/4 RS485 Rx +/
Differential link for improved noise
immunity (Menu 32).
0 - 2 km range. Update time 10 ms.
5 5/6 GND
1 CAN 0 V
Common ground for communications
links.
Connected to earth (ground) internally.
6/7 4/2 CAN HI/LO
3 SCN
Connection to CANopen or to
expanded I/O.
Future
8/9 7/8 HSIO +/ High speed digital link (Menu 20).
(Not available in SFE mode)
RS422 protocol, signal differential with respect
to GND pin. Common mode 15 V
TB5 Encoder/PTC Specifications
Pin Signal Menu 13
1 M_PTC Input from motor thermistor (machine
bridge)
Input from line reactor (mains bridge).
Resistive: Trip: 0 to 10 k (P2.13 motor
PTC, P52.19 SFE choke PTC)
Reset: (Value in parameter) 0.1 k
2/5 FB /FB+ Encoder power supply feedback for
accurate setting.
4/6 +5 V/+24 V Power supply outputs for the
encoder.
+5 V: Adjustable, 4.5 - 6.5 V, 350 mA
maximum
+24 V: Fixed, 350 mA maximum
3 0 V Common return line for encoder
power supply and the PTC.
Connected to earth (ground) internally.
7/8 Z/Z+
9 - 12 B/B+, A/A+
Marker signal from encoder.
Encoder position signals.
EIA RS422A, Max edge freq 1.5 MHz,
see Section 3.9
TB6 Analogue Inputs/Outputs Specifications
Pin Signal Menu 7
1/2 ANOP 1 and 2 Analogue outputs 1 and 2, V or I as
selected by SW1.
V or I: (11 bit +sign), 5% full scale accuracy, ..
V: 10 V to +10 V, 5 mA load
I: 20 mA to +20 mA, 500 load
3 AN GND Analogue ground (earth) for inputs
and outputs.
Connected to earth (ground) internally.
4/9 10 V/+10 V to ......... Reference supplies for analogue
inputs.
Maximum Load : 5 mA current limited
5/6 AN I/P 2 /+
7/8 AN I/P 1 /+
Differential analogue input 2
Differential analogue input 1
V or I as selected by SW1 (11 bit +sign), 5% full
scale accuracy:
V: 10 V to +10 V, 100 k load input
impedance.
I: 20 mA to +20 mA, 235 load input
impedance.
Common mode volts =2.5 V maximum.
TB7 (pre-charge pcb) Relay Output Specifications
Pin Signal
1/2 CLOSE LCN
Line contactor pilot relay output
(volts free)
D.1.1 Maximum volts : 500 Vac
Maximum current : 8 A
ALSPA MV3000e AEM Drives Documentation Structure
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page v
OVERVIEW
&
SPECIFICATIONS
(SECTIONS 1&2)
OPTIONS AVAILABLE
(SECTION 9)
PLANNING
+
PRODUCT SELECTION
DELTA DRIVE?
OPTIONAL EXTRAS?
BUYER'S GUIDE
DELTA MANUALS
(T1689, T1693)
INSTALLATION INSTRUCTIONS
FOR MAINS BRIDGE,
SINUSOIDAL FRONT END
AND
MACHINE BRIDGE
(SECTION 3)
EVERY OPTION HAS
INDIVIDUAL
INSTALLATION
INSTRUCTIONS
DELTA MANUALS
(T1689, T1693)
INSTALLATION OF
MODULAR DRIVES
HOW TO USE THE KEYPAD
+
DEFAULT SET-UP
+
FLOWCHARTS FOR
GUIDED COMMISSIONING
+
SIMPLE
APPLICATION EXAMPLES
(SECTIONS 4, 5A, 5B)
FULL SYSTEM SOFTWARE
DIAGRAMS
(SECTION 5C)
SOFTWARE MANUAL
(T1679EN)
DETAILED
DESCRIPTION OF
DRIVE PARAMETERS
+
USEFUL APPLICATION
PROGRAMMING
EXAMPLES
SIMPLE MAINTENANCE
(SECTION 6)
DIAGNOSTICS AND USE OF
ON-LINE HELP
(SECTION 7)
MAINTENANCE
+
DIAGNOSTICS
SOFTWARE MANUAL
(T1679EN)
DIAGNOSTIC
FLOWCHARTS
+
EXTRA DIAGNOSTIC
INFORMATION
BASIC SPARES
(SECTION 8)
+
AVAILABLE OPTIONS
(SECTION 9)
+
DISPOSAL INSTRUCTIONS
(SECTION 10)
SPARES
+
OPTIONS
+
DISPOSAL
THIS MANUAL
(T2002EN)
STAGES OF USE
OPTIONAL
MANUALS
OPTION MANUALS
INSTALLATION
COMMISSIONING
PROGRAMMING
FOR FINAL
APPLICATION
SOLUTIONS
ALSPA MV3000e AEM Drives
Page vi ALSPA MV3000e Getting Started Manual for AEM Drives (06/06)
This page intentionally left blank
ALSPA MV3000e AEM Drives Overview
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page vii
OVERVIEW
Section Page
1. Introduction...................................................................................................................... 1-1
Introduces the Getting Started Manual and the concept of Active Energy Management (AEM).
Explains the terminology used to describe the components of AEM drives.
2. Product Data .................................................................................................................... 2-1
Lists the complete range of Converteam MicroCubicle bi-directional converters. Provides
electrical and mechanical data for the bi-directional converter, configured either as a Mains
Bridge in a Sinusoidal Front End (SFE), or as a Machine Bridge; also provides physical
dimensions and miscellaneous data common to all the converters, such as derating
information.
3. Installation........................................................................................................................ 3-1
Explains how to properly install a MicroCubicle bi-directional converter, ready for
commissioning, either as part of a SFE or as a machine bridge. Mechanical aspects include
the illustrated layout of components with regard to ventilation and EMC requirements.
Electrical installation instructions include the layout of cables for EMC requirements,
segregation, access to drive connectors and cable connection.
4. Using Menus and Parameters ........................................................................................ 4-1
Explains the system of menus and parameters which is used to configure the converter
during commissioning. Shows how to use the Drive Data Manager to navigate the menus
and enter parameter values. Shows how to get on-line help.
5A. Commissioning a Mains Bridge....................................................................................5A-1
Explains how to configure a mains bridge as part of a SFE, to generate a controlled DC
voltage, using factory default settings. Explains how to configure the converter in more detail
using Guided Commissioning (simple flowcharts) and the Control Block Diagrams supplied
in Section 5C.
5B. Commissioning a Machine Bridge................................................................................5B-1
Explains how to configure a machine bridge to turn a motor, using factory default settings,
also how to configure the drive in more detail using Guided Commissioning (simple
flowcharts) and shows how to set up the drive for more advanced applications, using the
Control Block Diagrams supplied in Section 5C.
5C. Control Block Diagrams................................................................................................ 5C-1
Provides a graphic representation of the converter parameters. Explains how to use these
diagrams to design customised applications.
6. Preventive Maintenance.................................................................................................. 6-1
Simple maintenance procedures for keeping MicroCubicle bi-directional converters
serviceable.
7. Diagnostics ...................................................................................................................... 7-1
What to do if the MicroCubicle bi-directional converter displays a WARNING or if it TRIPS.
Shows how to display Warning and Trip codes, and tabulates the meaning of these codes.
Provides many diagnostic hints to help find possible faults, explains how to reset the
converter and how to view a history of any previous incidents which may help with diagnosis.
8. Spare Parts........................................................................................................................ 8-1
Overview ALSPA MV3000e AEM Drives
Page viii ALSPA MV3000e Getting Started Manual for AEM Drives (06/06)
Lists spare parts which may be obtained from the MicroCubicle bi-directional converter
supplier to replace faulty items. Associated Part Nos. are included.
9. Options .............................................................................................................................. 9-1
Lists and briefly describes the optional equipment and manuals which can be obtained from
the MicroCubicle bi-directional converter supplier.
10. Disposal.......................................................................................................................... 10-1
Provides disposal instructions for the MicroCubicle bi-directional converter, and advises of
any toxic materials and special procedures to dispose of them.
ALSPA MV3000e AEM Drives Contents
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page ix
CONTENTS
Section Page
Safety Instructions ................................................................................................................. i
Bi-directional converter input/output diagram (default) ...............................................................ii
Interconnection diagram for an AEM drive ...................................................................................iii
Input/Output panel, connector specifications...............................................................................iv
Documentation Structure.................................................................................................................v
Overview ..........................................................................................................................................vii
Contents............................................................................................................................................ix
1. Introduction............................................................................................................................ 1-1
1.1 About this Manual.................................................................................................................... 1-1
1.2 About ALSPA MV3000e MicroCubicle
TM
Bi-directional Converters........................................ 1-1
1.1 Drive Data Manager (Keypad)............................................................................................. 1-2
1.2 Explanation of Product Code................................................................................................... 1-2
1.3 Terminology............................................................................................................................. 1-2
1.3.1 Bi-directional Converter...................................................................................................... 1-2
1.2.1 Rectifier-fed Drive............................................................................................................... 1-3
1.2.2 Mains Bridge....................................................................................................................... 1-3
1.2.3 Sinusoidal Front End (SFE)................................................................................................ 1-3
1.2.4 Machine Bridge .................................................................................................................. 1-4
1.4 Typical Applications Using Bi-directional Converters.............................................................. 1-5
1.4.1 AEM Drive using two identical Bi-directional Converters................................................... 1-5
1.2.5 AEM Drive using a Bi-directional Converter and a Rectifier-fed Drive............................... 1-5
1.2.6 Common DC Link Scheme with Several Machine Bridges................................................ 1-6
1.3 Use of Metric Units .................................................................................................................. 1-7
1.5 Customer Support and Training.............................................................................................. 1-7
1.6 Associated Publications........................................................................................................... 1-7
2. Product Data .......................................................................................................................... 2-1
2.1 Rating Data for Bi-directional Converters Configured as Machine Bridges............................ 2-1
2.2 Rating Data for Bi-directional Converters Configured as Mains Bridges................................ 2-2
2.3 MicroCubicle Dimensions .................................................................................................... 2-3
2.4 AC Line Reactor...................................................................................................................... 2-4
2.4.1 Physical Dimensions, Inductance and Losses................................................................... 2-4
2.4.2 Fixing Dimensions.............................................................................................................. 2-5
2.5 PWM Filter............................................................................................................................... 2-6
2.5.1 Physical Dimensions and Losses....................................................................................... 2-6
2.5.2 Fixing Dimensions.............................................................................................................. 2-7
2.6 Fan Transformer...................................................................................................................... 2-8
2.6.1 Physical Dimensions and Losses....................................................................................... 2-8
2.6.2 Electrical Data for Fan Transformer................................................................................... 2-9
2.7 Line Contactor LCN................................................................................................................. 2-9
2.8 Electrical and Environmental Specifications ......................................................................... 2-10
2.8.1 Common Specifications.................................................................................................... 2-10
2.8.2 Specifications for Machine Bridges.................................................................................. 2-10
2.8.3 Specifications for Sinusoidal Front End (SFE)................................................................. 2-11
2.9 Product Performance Data.................................................................................................... 2-11
2.9.1 Product performance data for Machine Bridges .............................................................. 2-11
2.9.2 Product performance data for Sinusoidal Front End........................................................ 2-12
2.9.3 Mains Impedance............................................................................................................. 2-12
2.10 DC Link Overvoltage Trip Levels........................................................................................... 2-13
2.11 Acoustic Noise Levels ........................................................................................................... 2-13
2.12 Standards .............................................................................................................................. 2-14
3. Installation.............................................................................................................................. 3-1
3.1 Introduction.............................................................................................................................. 3-1
3.2 Receipt of Equipment.............................................................................................................. 3-1
3.2.1 Inspection and Storage...................................................................................................... 3-1
Contents ALSPA MV3000e AEM Drives
Page x ALSPA MV3000e Getting Started Manual for AEM Drives (06/06)
3.2.2 Handling..............................................................................................................................3-2
3.3 Harmonic Recommendations...................................................................................................3-3
3.3.1 AC Line Reactors................................................................................................................3-3
3.3.2 PWM Filters.........................................................................................................................3-3
3.4 EMC Recommendations ..........................................................................................................3-3
3.4.1 EMC Filter and Capacitors..................................................................................................3-3
3.4.2 Cabinet Layout for EMC Compliance .................................................................................3-4
3.5 Mechanical Installation.............................................................................................................3-6
3.5.1 Cooling and Environment....................................................................................................3-6
3.5.2 Clearances and Mounting Distances..................................................................................3-7
3.5.3 Mounting Checklist..............................................................................................................3-7
3.6 Electrical Installation - General ................................................................................................3-8
3.6.1 Protection devices...............................................................................................................3-8
3.6.2 Cable Lugs and Recommended Torque Settings...............................................................3-9
3.7 Cable Selection......................................................................................................................3-10
3.7.1 AC Power Cable Selection................................................................................................3-10
3.7.2 DC Link Cable Selection...................................................................................................3-11
3.7.3 DC Link Cable Screening and Segregation......................................................................3-12
3.7.4 Ancillary and Control Cable Selection..............................................................................3-12
3.7.5 Cable Segregation............................................................................................................3-13
3.8 Suitability of Motors and Cables ............................................................................................3-13
3.9 Encoders and Encoder Cables ..............................................................................................3-14
3.10 Access to Electrical Connections...........................................................................................3-15
3.11 Control Connections...............................................................................................................3-17
3.12 Cable Connections - Frame Sizes 3 and 4............................................................................3-19
3.12.1 AC Power and Motor Cables ............................................................................................3-19
3.12.2 DC Link and Ancillary Cables ...........................................................................................3-21
3.13 Cable Connections - Frame Size 6........................................................................................3-23
3.13.1 AC Power, Motor and DC Link Cables .............................................................................3-23
3.13.2 Ancillary Cables ................................................................................................................3-25
3.14 Cable Connections - Frame Size 7........................................................................................3-27
3.14.1 AC Power, Motor and DC Link Cables .............................................................................3-27
3.14.2 Ancillary Cables ................................................................................................................3-30
3.15 Ancillary Components ............................................................................................................3-31
4. Using Menus and Parameters............................................................................................... 4-1
4.1 Menu Structure Overview.........................................................................................................4-1
4.1.1 Parameters..........................................................................................................................4-1
4.2 Use of the Drive Data Manager (Keypad)............................................................................4-1
4.2.1 Navigation Key....................................................................................................................4-1
4.2.2 Navigating Menus and Parameters ....................................................................................4-2
4.2.3 Editing Parameters .............................................................................................................4-3
4.2.4 Using the Keypad HELP (?) Key.........................................................................................4-5
4.2.5 SHORTCUT Method of Entering a Parameter Number......................................................4-5
4.2.6 Access to Other Menus (P1.31)..........................................................................................4-5
4.2.7 Keypad Removal.................................................................................................................4-6
4.3 Keypad Harbour Status Indicators...........................................................................................4-7
4.4 Application Programming.........................................................................................................4-8
4.4.1 Control Flags and Status Flags...........................................................................................4-8
4.4.2 Programming Digital I/O......................................................................................................4-9
4.4.3 Programming Analogue I/O..............................................................................................4-10
4.5 Security Attributes and Passwords ........................................................................................4-10
4.5.1 Attributes...........................................................................................................................4-10
4.5.2 Parameter Passwords.......................................................................................................4-11
4.6 Control Block Diagrams .........................................................................................................4-11
5A. Commissioning a Mains Bridge............................................................................................... 1
5A.1 Introduction.................................................................................................................................. 1
5A.2 Installation Assumptions ............................................................................................................. 2
5A.3 Menu Structure Overview............................................................................................................ 3
5A.3.1 Menu Listing........................................................................................................................... 3
ALSPA MV3000e AEM Drives Contents
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page xi
5A.3.2 Menu 1....................................................................................................................................3
5A.3.3 Default Configuration..............................................................................................................6
5A.3.4 Returning to Factory Default Settings ....................................................................................7
5A.4 Commissioning Procedure..........................................................................................................7
5A.4.1 Introduction.............................................................................................................................7
5A.4.2 Simple Start............................................................................................................................8
5A.4.3 Guided Commissioning of a SFE...........................................................................................9
5A.5 Application Programming..........................................................................................................13
5B. Commissioning a Machine Bridge...........................................................................................1
5B.1 Introduction..................................................................................................................................1
5B.2 Installation Assumptions..............................................................................................................2
5B.3 Menu Structure Overview............................................................................................................2
5B.3.1 Menu Listing...........................................................................................................................2
5B.3.2 Menu 1....................................................................................................................................3
5B.3.3 Default Configuration..............................................................................................................6
5B.3.4 Returning to Factory Default Settings ....................................................................................7
5B.4 Commissioning Procedure..........................................................................................................7
5B.4.1 Introduction.............................................................................................................................7
5B.4.2 Simple Start............................................................................................................................8
5B.4.3 Guided Commissioning of a Machine Bridge.........................................................................9
5B.5 Application Programming..........................................................................................................22
5C. Control Block Diagrams............................................................................................................1
6. Preventive Maintenance........................................................................................................ 6-1
6.1 Tools and Equipment Required............................................................................................... 6-1
6.2 Maintenance Schedules.......................................................................................................... 6-1
7. Diagnostics ............................................................................................................................ 7-1
7.1 LED Indicators......................................................................................................................... 7-1
7.1.1 Fault Indication................................................................................................................... 7-1
7.2 Warnings.................................................................................................................................. 7-1
7.3 Trips......................................................................................................................................... 7-1
7.4 Viewing Warnings and Trips.................................................................................................... 7-1
7.4.1 Action in the Event of a Warning........................................................................................ 7-2
7.4.2 Action in the event of a Trip................................................................................................ 7-2
7.4.3 Resetting Trips ................................................................................................................... 7-2
7.4.4 Trip Fault Codes................................................................................................................. 7-2
7.5 Using the HELP Key................................................................................................................ 7-2
7.6 Diagnostic Hints....................................................................................................................... 7-3
7.6.1 Changing Pcb's .................................................................................................................. 7-4
7.6.2 Failure of Converter Firmware ........................................................................................... 7-4
7.6.3 Uploading the Converter Memory Contents to a PC.......................................................... 7-4
8. Spare Parts............................................................................................................................. 8-1
8.1 Pre-charge Fuses.................................................................................................................... 8-1
8.1.1 Replacing Pre-charge Fuses.............................................................................................. 8-1
8.2 Spare Parts Listing.................................................................................................................. 8-3
9. Options ................................................................................................................................... 9-1
9.1 Optional Hardware................................................................................................................... 9-1
9.2 Optional Manuals..................................................................................................................... 9-2
10. Disposal ................................................................................................................................ 10-1
Contents ALSPA MV3000e AEM Drives
Page xii ALSPA MV3000e Getting Started Manual for AEM Drives (06/06)
This page intentionally left blank
ALSPA MV3000e AEM Drives 1. Introduction
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page 1-1
1. Introduction
1.1 About this Manual
This Getting Started Manual provides a competent user trained in electrical installation
practice with sufficient information to safely install, commission, operate, maintain and dispose
of simple Active Energy Management (AEM) systems, based on the MV3000e series of
bi-directional converters.
This manual should be regarded as part of the product. It should be retained for the life of the
product and passed on to any subsequent owner or user.
1.2 About ALSPA MV3000e MicroCubicle
TM
Bi-directional Converters
Active Energy Management systems are based on the MV3000e bi-directional converter,
which is a MicroCubicle style product that can be configured by the user as a mains bridge
or as a machine bridge:
The mains bridge is combined with ancillary components to form a Sinusoidal Front End
(SFE). The SFE accurately controls the bi-directional flow of power between the AC mains
supply and a DC bus (normally referred to as the "DC Link"). The current drawn from, or
regenerated to, the mains supply is at unity power factor and is substantially free from
harmonics.
The machine bridge controls a motor and the bi-directional power flow between the DC bus
and the motor or generator.
When a SFE and a machine bridge are connected at their DC terminals, an AEM drive (Active
Energy Management Drive) is created, also sometimes referred to as a "4-quadrant AC drive".
This is illustrated in Figure 1-1.
For simplicity, in this manual most examples assume a configuration comprising a bi-
directional converter configured as a mains bridge, connected via a DC link to an identical bi-
directional converter configured as a machine bridge.
DC link
Mains Bridge
Machine Bridge
Motor
3
M
Mains
Network
3
Ancillary Componets
Sinusoidal Front End (SFE)
Figure 1-1 AEM Drive arrangement
1. Introduction ALSPA MV3000e AEM Drives
Page 1-2 ALSPA MV3000e Getting Started Manual for AEM Drives (06/06)
1.1 Drive Data Manager (Keypad)
The converter can be configured for use by means of an optional Drive Data Manager
(keypad) and a simple menu system. The keypad can be mounted directly to the front of the
converter, or may be panel mounted using an optional mounting kit and connected to the
converter via a cable.
1.2 Explanation of Product Code
The MicroCubicle bi-directional converters covered by this manual are listed in Tables 2-1
and 2-2 in Section 2. The code used to identify bi-directional converters is illustrated in Figure
1-2, using the code for an ALSPA MV3000e bi-directional converter, rated at 140 A with a
nominal supply voltage of 400 V.
Figure 1-2 ALSPA MV3000eJ bi-directional converter identity code
The voltage and current ratings are given in Section 2, Tables 2-1 and 2-2. Dimensions and
weights are provided in Section 2.3.
1.3 Terminology
1.3.1 Bi-directional Converter
A MicroCubicle style product that can be configured (in both hardware and software) to
operate as a mains bridge (a component of a SFE) or as a machine bridge.
Identifiable by the letter J in the part number, e.g. MV3071J5A1.
Contains mains voltage monitoring circuits to allow synchronisation to the mains when
operating as a mains bridge.
The default software operating mode is SFE mode, in which it functions as a mains bridge.
A simplified representation of the bi-directional converter is illustrated in Figure 1-3.
3-phase AC DC 3-phase AC DC
OR
Figure 1-3 Simplified representation of a Bi-directional converter
MV3140J 5A1
ALSPA
MV3000
Series
Current
Rating (Amps)
Bi-directional
Converter
Overload Rating
Selectable 1.1/1.5
Standard
Fan
Voltage
Rating
ALSPA MV3000e AEM Drives 1. Introduction
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page 1-3
1.2.1 Rectifier-fed Drive
Also sometimes referred to as an "AC in AC out drive" or "AC-fed drive", the Rectifier-fed
drive:
Comprises a MicroCubicle style product which combines the functions of a diode rectifier
bridge and a machine bridge, as shown in Figure 1-4.
Identifiable by the letter A in the part number, e.g. MV3065A5A1
Typically AC-fed and as such provides unidirectional power flow from the mains to an AC
induction motor, but can alternatively be DC-fed to allow bidirectional power flow between DC
and an AC induction machine.
Can form part of an AEM drive or a common DC link scheme.
Covered by manual T1676.
3-phase
mains
3-phase
machine
DC
Rectifier Machine bridge
Figure 1-4 Simplified representation of a rectifier-fed drive
1.2.2 Mains Bridge
The mains bridge forms part of the Sinusoidal Front End (SFE), described in
Section 1.2.3.
1.2.3 Sinusoidal Front End (SFE)
Also sometimes referred to as a "DC feeder", the SFE:
Converts electrical energy from AC mains to DC, or vice versa. Its primary function is to
actively control the voltage at its DC terminals. To achieve this it can sink or source near
sinusoidal current to or from the AC mains.
Consists of a bi-directional converter configured with software to function as a mains bridge,
plus ancillary components as shown in Figure 2 at the front of this manual.
Can form part of an AEM drive or a common DC link scheme, described later.
The DC link is automatically precharged as soon as a voltage is applied to the AUX terminals.
If a "Run" signal is not applied, or if the mains bridge is stopped or tripped, the SFE functions
as a diode rectifier.
Figure 1-5 shows a simplified block diagram of a SFE.
1. Introduction ALSPA MV3000e AEM Drives
Page 1-4 ALSPA MV3000e Getting Started Manual for AEM Drives (06/06)
Figure 1-5 Simplified representation of a Sinusoidal Front End
1.2.4 Machine Bridge
Also sometimes referred to as a "DC-fed drive", the machine bridge:
Converts electrical energy from DC into AC, or vice versa. Its primary function is to perform
speed or torque control of an AC induction motor or generator.
May consist of a bi-directional converter which has been software configured to operate in one
of several possible drive modes, including frequency control (VVVF), vector control (with
or without encoder), or scalar control.
Alternatively may consist of a rectifier-fed drive with its rectifier bridge unused.
Can form part of an AEM drive or a common DC link scheme, described later.
Figure 1-6 shows a simplified block diagram of a machine bridge.
3-phase
machine
DC
Machine Bridge
Figure 1-6 Simplified representation of a bi-directional converter configured as a machine bridge
DC
3-phase
mains
Ancillary
components
Sinusoidal Front End
Mains Bridge
Bi-directional
converter
*
*
Refer to Figure 2 on page iii
ALSPA MV3000e AEM Drives 1. Introduction
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page 1-5
1.4 Typical Applications Using Bi-directional Converters
1.4.1 AEM Drive using two identical Bi-directional Converters
3-phase
mains
3-phase
machine
Ancillary
components
Sinusoidal Front End
Mains Bridge Machine Bridge
AEM Drive
Figure 1-7 Simplified representation of an AEM drive using two identical bi-directional conveters
See Section 2 for rating details.
1.2.5 AEM Drive using a Bi-directional Converter and a Rectifier-fed Drive
Sinusoidal Front End
Mains Bridge Machine Bridge
Rectifier
Rectifier-fed Drive
3-phase
machine
3-phase
mains
AEM Drive
(Not used)
Ancillary
components
Figure 1-8 Simplified representation of an AEM drive using a SFE and a rectifier fed drive
1. Introduction ALSPA MV3000e AEM Drives
Page 1-6 ALSPA MV3000e Getting Started Manual for AEM Drives (06/06)
Table 1-1 shows the model numbers of mains bridges and rectifier-fed drives which may be
used together to make an AEM drive.
Table 1-1 MV3000e Compatibility table for AEM dri ve creation
Mains bridge
Compatible rectifier-fed drives for use as machine bridges *
MV3071J 5A1 MV3065A5A1 MV3052A5A1
MV3140J 5A1 MV3124A5A1 MV3096A5A1 MV3077A5A1
MV3364J 5A1 MV3302A5A1 MV3240A5A1 MV3180A5A1 MV3156A5A1
MV3566J 5A1 MV3477A5A1 MV3414A5A1 MV3361A5A1
MV3099J 6A1 MV3099A6A1 MV3077A6A1 MV3062A6A1
MV3242J 6A1 MV3242A6A1 MV3192A6A1 MV3144A6A1 MV3125A6A1
MV3382J 6A1 MV3382A6A1 MV3336A6A1 MV3289A6A1
* Refer to Converteam manual T1676 for ratings of MV3000e Rectifier-fed products.
1.2.6 Common DC Link Scheme with Several Machine Bridges
The bi-directional converter can be used in a common DC link scheme in which a SFE and
several machine bridges of various ratings drive a number of motors, as shown in Figure 1-9.
These motors may draw or regenerate power independently and thereby increase the system
efficiency by reducing the current drawn from the mains. Further information may be obtained
from the supplier.
Figure 1-9 Common DC link scheme with several machine bridges
Common DC link
Sinusoidal Front End (SFE)
Machine Bridges
Motors
3
3
3
3
M
M
M
M
Mains
Network
3
ALSPA MV3000e AEM Drives 1. Introduction
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page 1-7
1.3 Use of Metric Units
The ALSPA MV3000e range of bi-directional converters has been designed to IEC standards
using SI units. In this manual approximate values for inches, lb and hp are also included for
convenience.
1.5 Customer Support and Training
Converteam provides comprehensive telephone technical support, application planning,
service and trsaining for customers.
Contact Converteam at the address and telephone numbers shown at the end of this manual.
1.6 Associated Publications
1.6.1.1.1 T1676 ALSPA MV3000e Getting Started Manual for AC-fed Drives
This manual provides a competent user trained in electrical installation practice
with sufficient information to safely install, commission, operate, maintain and
dispose of a simple AC-fed drive installation.
1.3.1.1.1 T1679 ALSPA MV3000e Software Technical Manual
This manual includes full descriptions of the menu structure and parameters and
also the serial communications systems.
1.3.1.1.2 T1684 ALSPA MV3000e Dynamic Braking Units
Comprehensive instructions are provided to allow a competent user to install,
commission, maintain the MV3DB series DB Units, and to select and install the
associated braking resistors.
1.3.1.1.3 T2013 ALSPA MV3000e CANopen Fieldbus Facility Technical Manual
This manual enables a competent user trained in drives to use the on-board
CANopen facility to add input/output functions (extended I/O) and to configure
communication between two or more drives, using the CANopen Fieldbus.
1.3.1.1.4 T1689 ALSPA MV DELTA, Technical Manual for MV3000e DELTA
T1693 ALSPA MV DELTA Liquid Cooled Drive System
These manuals include specifications and instructions to allow a competent user
trained in drives to safely install the components of ALSPA MV3000e DELTA
systems to construct DELTA drives.
DELTA drives are a unique system of modular based drive units,150 kW to 1.8 MW
in air-cooled versions, 600 kW to 3.6 MW in liquid cooled versions.
1.3.1.1.5 T1933 ALSPA MV3000e MicroPEC Application Processor
This instruction sheet enables a competent user trained in drives to install the
MicroPEC facility and use it to add complex processor-based functions to the
simple logic functions provided as standard with the drive.
1. Introduction ALSPA MV3000e AEM Drives
Page 1-8 ALSPA MV3000e Getting Started Manual for AEM Drives (06/06)
This page intentionally left blank
ALSPA MV3000e AEM Drives 2. Product Data
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page 2-1
2. Product Data
2.1 Rating Data for Bi-directional Converters Configured as Machine Bridges
Note: The data in Table 2-1 is correct for a PWM switching frequency of 1.25 kHz. For data at other switching frequencies refer to Converteam.
Table 2-1 Rating data for bi-directional converters configured as machine bridges
Converter DC Link Motor Rating Drive Output Current Heat Losses to Cabinet
Ventilation
Fan
Transformer
Fan Transformer
Primary Fuses
Auxiliary Fuses
Approx. Maximum Losses
Model
G
r
a
d
e
Frame
Size
Nominal
Voltage
V
Mains
Current
(1.1/1.5 O/L)
A
IEC Rated
Fuse **
(1.1/1.5 O/L)
A
UL Rated
Fuse **
(1.1/1.5 O/L)
A
Model Number
(Parts
/01 and /02)
Model Number
Rating **
IEC UL/CSA
A A
DC Link *
Voltage
V
Clean Air
Configured
kW
With Dirty
Air Kit Fitted
W
Airflow required
by cabinet
m
3
/h cu ft/min
Model No.
Rating ***
IEC UL/CSA
A A
Rating **
IEC UL/CSA
A A
MV3071J5A1 3 71/58 80/63 90/80 MV3SRL037A5 MV3PWM071A5 16 12 1.1 200 140 85 MV3FTX0350A4 4 3.5 10 8
MV3140J5A1 4 140/105 160/125 175/150 MV3SRL075A5 MV3PWM140A5 20 20 1.6 260 255 150 MV3FTX0350A4 4 3.5 10 8
MV3364J5A1 6 364/292 400/315 500/400 MV3SRL200A5 MV3PWM364A5 40 40 3.3 440 680 400 MV3FTX0750A4 10 6.25 16 12
MV3566J5A1 7 475/374 630/500 750/600 MV3SRL315A5 MV3PWM566A5 80 70 5.1 580 850 500 MV3FTX1306A4 10 10 16 12
MV3071J5A1 3 65/52 80/63 90/70 MV3SRL037A5 MV3PWM071A5 16 12 1.1 200 140 85 MV3FTX0350A4 4 3.5 10 8
MV3140J5A1 4 124/96 125/100 175/125 MV3SRL075A5 MV3PWM140A5 20 20 1.6 260 255 150 MV3FTX0350A4 4 3.5 10 8
MV3364J5A1 6 302/240 315/250 400/300 MV3SRL200A5 MV3PWM364A5 40 40 3.3 440 680 400 MV3FTX0750A4 10 6.25 16 12
MV3566J5A1 7 460/365 500/500 600/600 MV3SRL315A5 MV3PWM566A5 80 70 5.1 580 850 500 MV3FTX1306A4 10 10 16 12
MV3099J6A1 4 99/77 100/80 125/100 MV3SRL090A7 MV3PWM099A6 10 10 1.6 260 255 150 MV3FTX0350A6 4 3 10 8
MV3242J6A1 6 242/192 250/200 350/250 MV3SRL200A7 MV3PWM242A6 32 35 3.3 440 680 400 MV3FTX0750A6 6 5 16 12
MV3382J6A1 7 289/234 400/400 500/450 MV3SRL315A7 MV3PWM382A6 50 50 5.1 580 850 500 MV3FTX1306A6 10 8 16 12
MV3099J6A1 4 98/82 100/100 125/110 MV3SRL090A7 MV3PWM099A6 10 10 1.6 260 255 150 MV3FTX0350A6 4 3 10 8
MV3242J6A1 6 211/170 250/200 300/225 MV3SRL200A7 MV3PWM242A6 32 35 3.3 440 680 400 MV3FTX0750A6 6 5 16 12
MV3382J6A1 7 272/221 400/315 450/400 MV3SRL315A7 MV3PWM382A6 50 50 5.1 580 850 500 MV3FTX1306A6 10 8 16 12
OUTPUT DE-RATING
ALTITUDE: Nominal 0 to 1000 m, above 1000 m de-rate 7.3% per 1000 m to a maximum of 2000 m.
TEMPERATURE: Nominal 0
C to 40
C, above 40
C de-rate 2.5% per
C to a maximum of 50
C.
.Overload (O/L) ratings - Selectable by parameter P99.02 (P1.29)
1.1 rating = 1.1 overload, i.e. 1.1 x full load current (P99.02 = 1)
1.5 rating = 1.5 overload, i.e. 1.5 x full load current (P99.02 = 0)
Section 2.8 gives maximum permitted overload repetition rate.
* DC link volts configured by user and must be
greater than 2 x ac mains voltage.
UL/CSA approval only up to 1100 V.
** For fuse type see Section 3.6.1. These fuses
may not prevent damage to the pre-charge
circuit in the event of short circuits on the
DC link and other components.
*** Fuse type as in Section 3.6.1.
.
LA4-DA2G
LA4-DA2G
MV3140J5A1
LC1-D11500F7
LC1-F115
200
175 LX1-FF110
LA1D
LA1-DN11
LA4-DA
LA9-F980
LA-D09981 LA9-F701
MV3364J5A1
LC1-F400
LC1-F400
430 420
430 420
LX1-FJ110
LX1-FJ110
LA1-DN11
LA1-DN11
LA9-D09980
LA9-D09980
LA-D09981
LA-DO9981
LA9-F703
LA9-F703
MV3566J5A1
LC1-F500
LC1-F500
580 700
580 700
LX1-FK110
LX1-FK110
LA1-DN11
LA1-DN11
LA9-D09980
LA9-D09980
LA-D09981
LA-D09981
LA9-F703
LA9-F703
MV3099J6A1
LC1-D8011F7
LC1-D8011F7
125 110
125 110
LA4-DA2G
LA4-DA2G
MV3242J6A1
LC1-F185
LC1-F265
275 200
300 285
LX1-FG110
LX1-FJ110
LA1-DN11
LA1-DN11
LA9-F980
LA9-F980
LA-D09981
LA-D09981
LA9-F702
LA9-F703
MV3382J6A1
LC1-F400
LC1-F400
430 420
430 420
LX1-FJ110
LX1-FJ110
LA1-DN11
LA1-DN11
LA9-D09980
LA9-D09980
LA-D09981
LA-D09981
LA9-F703
LA9-F703
IEC
UL/CSA
IEC
UL/CSA
IEC
UL/CSA
IEC
UL/CSA
IEC
UL/CSA
IEC
UL/CSA
IEC
UL/CSA
ENTER A VALUE INTO P13.12, E.G. 10Hz TO BEGIN WITH. THE MOTOR SHOULD ROTATE CLOCKWISE.
TO MEASURE THE MAGNETISING CURRENT, THE MOTOR MUST BE OFF LOAD. SET THE
VALUE OF P13.12 TO THE MOTOR BASE FREQUENCY (AS P2.00), WHEN THE RAMP HAS FINISHED
LOOK AT THE VALUE IN P9.05, AND RECORD (typically 1/3 of motor full load current).
CONTINUE
Vector No Encoder
CONTINUE
Vector No Encoder
5B. Commissioning a Machine Bridge ALSPA MV3000e AEM Drives
ALSPA MV3000e Getting Started Manual for AEM Drives (06/06)
Page 5B-16
Vector Control, No Encoder (continued)
NO
CHECK SPEEDS
(MENU 05)
YES
DO YOU
REQUIRE
CONTROL
MODE?
YES
NO
YES
CHECK MOTOR DATA
(see above)
ADJ UST PROPORTIONAL &
INTEGRAL GAINS FOR THE
SPEED AMPLIFIER TO GIVE
THE REQUIRED RESPONSE
TO A STEP SPEED CHANGE.
P14.00 =PROPORTIONAL GAIN
(values =3 to 12 max)
P14.01 = INTEGRAL GAIN
(values =5 to 300 max)
TORQUE CONTROL SET-UP PARAMETERS
THE DRIVE SERVO CAN BE SET TO BE A
TRUE TORQUE CONTROLLER, THIS IS A
SHORT LIST OF THE PARAMETERS FOR A
SIMPLE SET-UP. REFER TO THE CONTROL
REPRESENTATION.
BLOCK DIAGRAMS FOR A PICTORIAL
P15.04 =TORQUE REFERENCE SOURCE
P15.01 =TORQUE REFERENCE SCALE FACTOR
P15.00 =TORQUE REFERENCE MONITOR
P15.02 =1 TO ENABLE TORQUE REFERENCE
P14.08 =1 DISABLE SPEED LOOP?
P14.16 =1 TO ENABLE SPEED DEADBAND
Leave Speed Amplifier enabled and use Deadband
to generate a Speed Catch.
P14.14 =SPEED ERROR DEADBAND?
P8.00 =POSITIVE TORQUE LIMIT 1
P8.01 =NEGATIVE TORQUE LIMIT 1
POOR
STARTING
RESPONSE?
SWITCH OFF
THE RsTRACKER:
SET P12.28 =0
TRY AGAIN.
REDUCE P12.11
(STATOR RESISTANCE)
BY 10% IF REQUIRED.
TRY AGAIN.
NO
YES
DRIVE
PERFORMANCE
OK?
TORQUE
I REQUIRE SPEED CONTROL
STOP!
VECTOR QUICK START IS COMPLETE
NOW BACKUP YOUR EDITS!
(See Hint on page 5B-9)
IF REQUIRED, USE THE CONTROL
DIAGRAMS IN SECTION 5C TO
COMPLETELY CONFIGURE THE DRIVE
FOR FULL APPLICATION OPERATION.
THEN BACKUP YOUR EDITS!
To prevent unauthorised access to
parameters, see Section 4.5
CONTINUE
Vector No Encoder
ALSPA MV3000e AEM Drives 5B. Commissioning a Machine Bridge
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives
Page 5B-17
5B.4.3.4 Vector Control with Encoder
SWITCH THE DRIVE OFF AND CONNECT THE ENCODER.
THE ENCODER IS CONNECTED TO TB5 ON THE I/O PANEL,
SEE DIAGRAM AT THE FRONT OF THE MANUAL.
CABLING RECOMMENDATIONS CAN BE FOUND BY CONSULTING
SECTION 3.9.
THE DEFAULT SET-UP IS FOR SPEED CONTROL,
TORQUE CONTROL WILL BE SELECTED AT THE END OF THIS PROCEDURE.
For encoders supplied from +5 V :
The Encoder sense wires FB+, FB-, connected at the Encoder end of the supply,
allow the drive to sense the voltage. Set P13.06 to the supply volts of the Encoder
and the drive will compensate for cable volts drop.
EDIT THE FOLLOWING PARAMETERS, TO CONFIGURE THE DRIVE
P2.00 MOTOR BASE FREQUENCY Motor nameplate frequency (Hz)
P2.01 MOTOR BASE VOLTAGE Motor nameplate voltage (V)
P2.02 MOTOR Full Load CURRENT Motor nameplate current (A)
P2.03 MOTOR Nominal POWER Motor nameplate power (kW)
P2.04 MOTOR Nominal SPEED Motor nameplate speed (r/min)
P13.00 SPEED FEEDBACK Source SET 1 =ENCODER
P13.01
BACKUP SPEED FEEDBACK
Default Value =1 =Encoder
P13.02 Encoder LOSS ACTION Default value =1 =Warning
P13.04 Encoder LINE COUNT Pulses of your encoder, eg 2500
P13.05
Overall line count =P13.04 +(P13.05 x 10 000) e.g. for 11 000 lines : P13.04 =1000
P13.05 =1
Encoder 10000 LINES X10K pulses for your encoder
CONTINUE
Vector Control
with Encoder
THE ORANGE WARNING LED SHOULD EXTINGUISH AND
THE GREEN STANDBY/HEALTHY LED SHOULD BE LIT
OK?
NO
?
TO VIEW TRIPS,
PRESS
OR VIEW DIAGNOSTICS IN
THIS MANUAL
RESET TRIPS
ENABLE ALL MENUS BY SETTING P1.32 =2.
SELECT VECTOR CONTROL STRUCTURE BY SETTING P99.01 =2
SWITCH THE DRIVE BACK ON
CONTINUE
Vector Control
with Encoder
YES
5B. Commissioning a Machine Bridge ALSPA MV3000e AEM Drives
ALSPA MV3000e Getting Started Manual for AEM Drives (06/06)
Page 5B-18
Vector Control with Encoder (continued)
P12.00 NO LOAD CURRENT Motor magnetising current
IF NOT KNOWN, MEASURE IT DURING AN OPEN LOOP TEST - SEE BELOW
OR ESTIMATE FROM: P12.00 = 0.75 x P2.02 x sin (cos (power factor))
-1
P12.02 Nominal MAINS SUPPLY VOLTS
P5.15 MAXIMUM SPEED FORWARD Default value =1500 r/min *
P5.16 MAXIMUM SPEED REVERSE Default value =1500 r/min
P5.17 MINIMUM SPEED FORWARD Default value =0 r/min
P5.18 MINIMUM SPEED REVERSE Default value =0 r/min
P6.00 ACCELERATION RATE FORWARD Default value =10.0 %/s
P6.02 DECELERATION RATE FORWARD Default value =10.0 %/s
* Maximum speed cannot be set > base until a calibration run
has been performed (page 5B-20). If required, re-edit this
parameter after calibration run.
EDIT THE FOLLOWING DRIVE PARAMETERS
CONTINUE
Vector Control
with Encoder
Set to SFE DC Link reference
2
ON ALL DRIVES, 110 % DUTY IS DEFAULT. 150 % DUTY CAN BE
SELECTED BY SETTING P1.29 =0.
STANDARD VOLTAGE GRADE IS DEFAULT. ALTERNATE VOLTAGE
GRADE CAN BE SELECTED BY SETTING P99.11 =1. SEE TABLE 2-1
SET UP THE LOAD POWER FEEDFORWARD LINK
SET P7.23 ANALOGUE OUTPUT 2 MODE =5 (0-20 mA fast load power feedforward)
SET P7.25 ANALOGUE OUTPUT 2 SCALE =Current rating (Amps) of MV3000 machine bridge.
SET the AN O/P 2 slider on SW1 to its 20 mA position.
NOTE
When parameter P99.11 or
P1.29 is changed, the keypad
will show a Link Failure
momentarily while the
converter re-scales itself.
CONTINUE
Vector Control
with Encoder
MOTOR REGENERATIVE POWER LIMIT Set value =-0.1 kW, unlimited
FORWARD OVERSPEED LEVEL Default value =120 %
P23.05
P29.00
REVERSE OVERSPEED LEVEL Default value =120 % P29.01
ALSPA MV3000e AEM Drives 5B. Commissioning a Machine Bridge
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives
Page 5B-19
Vector Control with Encoder (continued)
OPEN LOOP TESTING
Minimum Control Connections made?
CHECK MOTOR PHASING
FAULT? Press for HELP,
OR SEE DIAGNOSTICS IN THIS MANUAL.
ENSURE REVERSE SWITCH ON
DIGIN 3 IS OPEN.
THE DRIVE REQUIRES AN ACCURATE MODEL OF THE MOTOR TO RUN THE VECTOR CONTROLLER
PROPERLY. IT IS STRONGLY RECOMMENDED THAT A FULL CALIBRATION RUN IS INITIATED TO DO THIS.
THE NEXT CHART EXPLAINS THE CALIBRATION CHOICES.
THIS TEST IS OPTIONAL, BUT IS A SAFE AND PRACTICAL WAY TO CHECK MOTOR INSTALLATIONS AND TO
DETERMINE A VALUE FOR THE MOTOR MAGNETISING CURRENT, REQUIRED FOR P12.00 AND TO CHECK
THE ENCODER. REMOVE AS MUCH LOAD AS POSSIBLE FROM THE MOTOR.
ENABLE OPEN LOOP TEST MODE BY SETTING P13.11 =1
SET OPEN LOOP RAMP RATE BY SETTING P13.13 TO A SUITABLE VALUE
(typically 10 Hz/sec, but lower for high inertia loads).
PRESS THE DRIVE START BUTTON (Drive Running and Standby LEDs on at this point).
ENTER A VALUE INTO P13.12, +2 Hz. THE MOTOR SHOULD ROTATE CLOCKWISE, P9.01 SHOULD BE
THE SAME POLARITY AS P13.12.
ENTER A VALUE INTO P13.12, 2 Hz. THE MOTOR SHOULD ROTATE COUNTERCLOCKWISE, P9.01
SHOULD BE THE SAME POLARITY AS P13.12.
SET P13.12 =0.5 Hz. CHECK THE ENCODER ANGULAR FEEDBACK BY MONITORING P13.10. THE ANGLE
SHOULD CHANGE BY 360
o
FOR ONE SHAFT REVOLUTION.
OK?
NO
YES
CHECK THE ENCODER
CONNECTIONS.
SET P12.3 =2
THE VALUE WILL RETURN
TO 1, INDICATING THAT
ESTIMATION IS COMPLETE.
EXPLICIT ENTRY
DATA FROM THE MOTOR
MANUFACTURER MUST BE
OBTAINED TO BE EDITED
INTO THE FOLLOWING
PARAMETERS:
P12.11 TO P12.16 IN STAR (Y)
EQUIVALENT.
CONTINUE
Vector Control
wi th Encoder
CONTINUE
Vector Control
with Encoder
THESE PARAMETERS ARE
LISTED ON PAGE 5C-12.
ALSPA MV3000e AEM Drives 5B. Commissioning a Machine Bridge
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives
Page 5B-21
Vector Control with Encoder (continued)
POOR
STARTING RESPONSE?
STARTING TORQUE
INSUFFICIENT?
NO CHECK MOTOR DATA (see above)
CHECK RAMPS (MENU 6)
CHECK MAX/MIN SPEEDS (MENU 5)
NO
YES
DO YOU
REQUIRE TORQUE
CONTROL
MODE?
YES
NO, I REQUIRE SPEED CONTROL
YES
ADJ UST PROPORTIONAL AND
INTEGRAL GAINS FOR THE
SPEED AMPLIFIER TO GIVE
THE REQUIRED RESPONSE TO
A STEP SPEED CHANGE.
P14.00 = PROPORTIONAL GAIN
P14.01 = INTEGRAL GAIN
DRIVE
PERFORMANCE
OK?
STOP!
VECTOR COMMISSIONING IS NOW COMPLETE
TORQUE CONTROL SET-UP PARAMETERS
THE DRIVE SERVO CAN BE SET TO BE A
TRUE TORQUE CONTROLLER, THIS IS A
SHORT LIST OF THE PARAMETERS FOR A
SIMPLE SET-UP. REFER TO THE CONTROL
DIAGRAMS IN SECTION 5C FOR A FULL
EXPLANATION.
P15.04 =TORQUE REFERENCE SOURCE
P15.01 =TORQUE REFERENCE SCALE FACTOR
P15.00 =TORQUE REFERENCE MONITOR
P14.08 =1 DISABLE SPEED LOOP
P15.02 =1 TO ENABLE TORQUE REFERENCE
P14.16 =1 TO ENABLE SPEED DEADBAND
P14.14 =SPEED ERROR DEADBAND
P8.00 =POSITIVE TORQUE LIMIT
P8.01 =NEGATIVE TORQUE LIMIT
SET MAXIMUM SPEEDS TO
REQUIRED VALUES IF
GREATER THAN BASE SPEED.
ROTOR TEMPERATURE COMPENSATION
1. IF TORQUE CONTROL IS INADEQUATE AND
LOAD VARIATION IS SLOW, ENABLE
THE TRACKER BY SETTING P12.06 =1.
2. IF TORQUE CONTROL IS INADEQUATE AND
LOAD VARIATION IS FAST, LEAVE P12.06 =0
THEN REDUCE P12.04 (MOTOR TEMPERATURE
COMPENSATION) UNTIL SATISFACTORY,
HOWEVER ENSURE: (P12.04 x P12.15) > P12.10
100
SPEED AMPLIFIER GAINS
AND THAT P12.15 IS APPROXIMATELY =(1.4 x P12.10)
NOW BACKUP YOUR EDITS!
(See Hint on page 5B-9)
IF REQUIRED, USE THE CONTROL
DIAGRAMS IN SECTION 5C TO
COMPLETELY CONFIGURE THE DRIVE
FOR FULL APPLICATION OPERATION.
THEN BACKUP YOUR EDITS!
TO PREVENT UNAUTHORISED ACCESS
TO PARAMETERS, SEE SECTION 4.5.
CONTINUE
Vector Control
with Encoder
3. LOOK AT HINT INSIDE BACK COVER
Leave Speed Amplifier enabled and use Deadband
to generate a "Speed Catch".
5B. Commissioning a Machine Bridge ALSPA MV3000e AEM Drives
ALSPA MV3000e Getting Started Manual for AEM Drives (06/06)
Page 5B-22
5B.5 Application Programming
Once the basic commissioning procedure has been completed, the user may find the need to
customise the drive parameters to accurately satisfy all the needs of the application. Practical
advice, with hints and worked examples, is given in Section 4.4. Together with the Control
Block Diagrams in Section 5C, this will enable the user to design systems for almost any
application.
ALSPA MV3000e AEM Drives 5C. Control Block Diagrams
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page 5C-1
5C. Control Block Diagrams
The Control Block Diagrams for the SFE and the Machine Bridge are shown on the following
pages. Section 4.6 shows how to use the diagrams to configure the bi-directional converters
for specific applications.
The control diagrams are listed in Table 5C-1. The table shows which diagrams are
concerned with each type of converter.
Table 5C-1 Control block diagrams
Sheet No. Description DB SFE
Machine
Bridge
1 Control System Overview
2 Proportional DB Control
3 Machine Bridge Control System Overview
4 Plant I/O and Serial Links
5 Reference Arbitration and Starting/Stopping
6 Motor Frequency Control
7 Motor Vector Control, Part 1
8 Motor Vector Control, Part 2
9 Trips/Warnings and Diagnostic Monitoring
10 Motor Position Controller
11 Pointers
12 Special Monitoring Functions
13 Application Logic, General Purpose Logic Blocks
14
Summing Nodes, Analogue Switches and Square
Roots
15 Comparators, Ramp Function and Brake Logic
16 Motor Scalar Control
17 SFE Control System Overview
18 SFE Vector Control, Part 1
19 SFE Vector Control, Part 2
5C. Control Block Diagrams ALSPA MV3000e AEM Drives
ALSPA MV3000e Getting Started Manual for AEM Drives (06/06) Page 5C-2
This page intentionally left blank
ALSPA MV3000e AEM Drives 5C. Control Block Diagram
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page 5C-3
5C.
Control System Overview
DEFAULT
CONNECTION
DEFAULT
SETTING
CONTROL
FLAG
STATUS
FLAG
xx DIGOUT
DIGIN xx
(A)
MONITOR
POINT
ANALOG
I/O
KEY
DC LINK
OR
R S T
Mains
Network
4
CONTROL MODE SELECTOR
P99.01
0. NO MOTOR CONTROL
1. VVVF CONTROL
2. VECTOR CONTROL
3. SCALAR CONTROL
4. SFE MODE
3
2
REFERENCE SELECTOR
DC LINK VOLTAGE CONTROL
CURRENT CONTROL
MAINS MONITORING
LOAD POWER FEEDFORWARD
ANALOGUE AND DIGITAL INPUTS
ANALOGUE AND DIGITAL OUTPUTS
KEYPAD REFERENCE
STARTING AND STOPPING
TRIPS/WARNINGS
MONITORING
APPLICATION LOGIC
KEYPAD
START/STOP
ANALOGUE INPUTS
DIGITAL INPUTS
SFE CONTROL SYSTEM OVERVIEW
SHEET 17
1. FREQUENCY CONTROL (VVVF) MODE
2. VECTOR CONTROL MODE
3. SCALAR CONTROL MODE
4. SFE MODE
2
3
4
MACHINE CONTROL MODES
SFE MODE (MAINS CONTROL)
R S T
U V W
Mains
Network
M
Note: Option 4 is displayed only if
the bridge is a bi-directional
converter, or a DELTA with a
Mains Voltage Monitor unit
connected.
1
0
1
0
0. NO MOTOR CONTROL (DB MODE)
U V W
DB Resistors
KEYPAD
SPEED REFS
& START/STOP
ANALOGUE INPUTS
DIGITAL INPUTS
REFERENCE SELECTOR
SPEED CONTROL
DIRECTION CONTROL
POSITION CONTROL
ANALOGUE AND DIGITAL INPUTS
ANALOGUE AND DIGITAL OUTPUTS
KEYPAD SPEED REFERENCE
STARTING AND STOPPING
TRIPS/WARNINGS
MONITORING
APPLICATION LOGIC
MACHINE BRIDGE CONTROL SYSTEM OVERVIEW
SHEET 3
KEYPAD REFS
& ON/OFF
ANALOGUE INPUTS
DIGITAL INPUTS
REFERENCE SELECTOR
DB CONTROL MODE
ANALOGUE AND DIGITAL INPUTS
ANALOGUE AND DIGITAL OUTPUTS
KEYPAD REFERENCE
STARTING AND STOPPING
TRIPS/WARNINGS
MONITORING
APPLICATION LOGIC
PROPORTIONAL DB CONTROL OVERVIEW
SHEET 2
DB CONTROL MODE
Sheet
1
Control Block Diagram
5C. Control Block Diagram ALSPA MV3000e AEM Drives
ALSPA MV3000e Getting Started Manual for AEM Drives (06/06) Page 5C-4
Comparator
O/P
Bridge
3 phase
PWM
Motor
Control
Speed Ramp
DB Ramp Limit
Speed
Reference
Selection
Reference
Selection
Max DB
Modulation
Vdc Source
Selection
DB
Threshold
100%
0%
DB Port
PWM
DB Mode
DB Port
on CDC
Control
Mode
Ramp Time
DB Ref. Source
P23.13
P99.01
P23.14
P23.15
P23.17
P23.04
DB O/P
Select
P23.19
Vref Source P23.10
Scale P23.11
>
=
<
Vdc
An1
An2
X
X
DB Reference
P23.16
DB Demand
P23.18
V Reference
P23.12
DB Power
P23.22
DB Current
P23.21
DB
PWM
1 to 4 =Motor control modes
0 =DB control mode
=Monitoring
Point
1
21
1 to 4
0
Motor Control
1
0
1
0
Proportional Braking Control
DB Threshold Control
PROPORTIONAL DB CONTROL
Output Bridge Connections
For Proportional DB Control
DBR A
DBR C
DBR B
DC Link +ve
DC Link -ve
A
B
OUTPUT
BRIDGE
C
Output Bridge Connections
For Threshold DB Control
DBR A
DBR C DBR B
DC Link +ve
DC Link -ve
A
B
OUTPUT
BRIDGE
C
MENU 23
Sheet
2
ALSPA MV3000e AEM Drives 5C. Control Block Diagram
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page 5C-5
SELECT 110% or 150%
OVERLOAD DUTY
P99.02 (P1.29)
CHOOSE MOTOR
CONTROL STRUCTURE
P99.01
USING "NOT" TRIPPEDENSURES THAT WARNINGS DO NOT AFFECT THE HEALTHY OUTPUT
SUMMING NODES, SWITCHES AND POINTERS SHEET 10
MENU 40 PROGRAMMABLE SUMMING NODES, ALLOWING SCALING AND
SUMMATION OF ANY DRIVE PARAMETER.
MENU 42 POINTERS. THESE POINTERS ARE ASSOCIATEDWITH MOST
OF THE DRIVE's REFERENCEC CHOICES, ANDALLOWS THE USER
TO CHOOSE ANY DRIVE PARAMETER FOR THE REQUIRED USE.
APPLICATION LOGIC, SPECIAL MONITORING FUNCTIONS SHEET 8
STATUS FLAG
BINARY GENERATOR
MENU 31
LOGIC GATES
COMPARATORS
DELAYS
MENU 30 &MENU 47
=3, SCALAR
=1, FREQUENCY
STARTING AND STOPPING SHEET 3
AUTO-RESETTING/STARTING
CONFIGURE THE DRIVE TO AUTO-RESET/RESTART AFTER A TRIP
CUSTOMER SELECTABLE RESET ENABLES
NUMBER OF RESETS AND TIMINGS OF RESETS MENU 28
(DEFAULT START MODE P4.00 =LOW FREQUENCY START)
(DEFAULT NORMAL STOP MODE P4.07 =DISABLE ANDCOAST)
(DEFAULT RAPIDSTOP MODE P4.08 =DISABLE ANDCOAST)
TRIPS/WARNINGS/DIAGNOSTIC MONITORS SHEET 7
HISTORY RECORDING
10 CHANNELS
MONITOR ANY
DRIVE PARAMETER
TRIGGER SET-UP
PRE ANDPOST TRIG
MANUAL TRIGGER
MENUS 26and 27
DEFAULT
CONNECTION
DEFAULT
SETTING
TRIPPED
START/STOP
SEQUENCING
START MODE
SYNCROSTART MODE
NORMAL STOP MODE
RAPID STOP MODES
STOP TIME LIMIT
ZERO SPEED
HOLDTIMES
MENU 4
TRIP MONITORING SYSTEM
10PRESENT TRIPS.
10PRESENT WARNINGS.
10TRIP HISTORY STORAGE.
USER CONFIGURABLE TRIPS.
MOTOR PROTECTION
MENU 10
TRIP
RESET
CONTROL
FLAG
STATUS
FLAG
xx DIGOUT
DIGIN xx
(A)
MONITOR
POINT
ANALOG
I/O
KEY
TRIP AVOIDANCE
KEYPAD/
REMOTE
DIGIN 6
TRIP
RESET
DIGIN 4
START
DIGIN 2
STOP
DIGIN 1
KEYPAD
START/STOP
9 5
116
KEYPAD/REMOTE
REMOTE
START/STOP
FLAGS
AND
BACKUP
START/STOP
FLAGS
MENU 4
START
0
1
NORMAL
STOP
MENU 99 SECURITY CODES,
PARAMETER BACKUP
ANDSYSTEM
CONFIGURATIONS
MENU 35 KEYPADREMOVAL,
PARAMETER PRINTING
AND PARAMETER "LOCKING"
OTHER USEFUL MENUS
MONITORING
EXTENSIVE
SYSTEM
MONITORS
TO AID
VIEWING
AND
DIAGNOSTICS
MENU 9 &11
START
AND
STOP
DRIVE
PLANT INTERLOCK (IF THIS INPUT IS OPEN, THE DRIVE WILL TRIP)
SPEED REFERENCE ARBITRATION SHEET 3
MAXIMUMSPEEDS
MINIMUMSPEEDS
DEMANDCLAMPS
DIRECTION INHIBITS
J OG SPEEDS
MENU 5
DIRECTION
0=FORWARD
1=REVERSE
CLAMP
KEYPAD
SPEED REF
4 - 20mA @ DEFAULT
ANALOGUE
REF1/2
DIGIN 5
ANALOG
REF 2
ANALOG
REF 1
+/- 10V @ DEFAULT
SOURCE 3
SPEEDREF
DIRECTION
CONTROL 4 REFERENCE SOURCES
REFERENCE SELECTOR
BACKUP REFERENCE
MENU 5
DETAILS OF ALL
POSSIBLE SPEED
REFERENCE CHOICES
P9.00/P1.00
SOURCE 4
REV
DIRECTION
FWD
SELECT
3
SELECT
2
SELECT
1
?
SOURCE 2
SOURCE 1
4 5 6
LOWEST
FLAG "ON"
WINS
3
"OFF" =REF1
FOR PLANT I/O SEE MENU 7, SHEET 2
INTERLOCK
KEYPAD/
REMOTE
REVERSE
DIGIN 3
DIGIN 4
"OFF" =KEYPAD
MAX/MIN SPEEDS P5.15to P5.18
(P1.15 to P1.18)
J OG SPEEDS P5.14 and P5.27
DIRECTION MODE P5.11
CLAMP
ZERO
REFERENCE
POSITION CONTROL SHEET 9
FULL POSITION CONTROLLER, INCLUDING A
FIXED POSITION MENU, A POSITION TEACHER,
A UNI-DIRECTIONAL APPROACH ANDA
COMPREHENSIVE DATUMMING CONTROLLER
SKIP SPEEDS
MENU 22
TC
SPEED REF
TIME CONST.
MENU 5
RAMP RATES 1/2
SELECT RATES 1/2
RAMP FREEZE
S - SHAPING
MAX RAMP DEVIATIONS
MENU 6
RAMPS SHEETS 4, 5
RAMPS
ADVANCED
MOTOR
MODEL
DATA
MENU 12
OUTPUT
ENABLE/RUN
DRIVE MONITORING MENUS MENUS 9, 11 and 38
MENU 9 BASIC MONITORING OF THE MAIN DRIVE VARIABLES
MENU 11 ADVANCEDNONITORING OF DRIVE VARIABLES, INCLUDING
VECTOR CURRENTS, TEMPERATURES, CONTROL ANDSTATUS FLAGS
HOURS RUN, ENERGY CONSUMED, DIGITAL I/O STATES,
ANALOGUE INPUT ANDOUTPUT VALUES AND OTHERS.
MENU 38 EXCLUSIVELY MONITORS ALL THE VARIABLES IN THE POSITION
CONTROLLER
LOADFAULT
DETECTION
WINDOW
ALLOWS PLANT
CONDITION
MONITORING
MENU 43
PROGRAMMABLE
REFERNCE
SHAPER
ALLOWS THE
USER TO "SHAPE"
ANY OF THE
DRIVES SIGNALS.
MENU 44
TORQUE MONITOR
WINDOW
MENU 29
SPEEDMONITOR
WINDOW
MENU 29 AT SPEED
12
INERTIA
COMPENSATION
MENU 25
SELECT SPEED FEEDBACK SOURCE
P13.00
SPEEDFEEDBACK
THIS IS A SPECIAL CONTROL MODE, FOR VERY SPECIALISED APPLICATIONS.
REFER TO SUPPLIER FOR DETAILS.
BUMPLESS
ENCODER LOSS
RIDETHROUGH
%=P9.01/P1.01
rpm=P9.03
SCALAR CONTROL MODE SHEET 11
SPEED FEEDBACK
SPEED TRIM
SELECTIONS
MENU 24
=1
MENU 13 SHEET 10
BASIC MOTOR DATA
MENU 2
=2
=3
ENCODERLESS
SPEED
FEEDBACK
TACHO
SELECTIONS
ANALOG
O/P 1
ANALOG
O/P 2
(MENU 7)
(MENU 7)
DIGOUT 3
DIGOUT 2
CURRENT FEEDBACK
+/- 10V @ DEFAULT
+/- 10V @ DEFAULT
SPEEDFEEDBACK
AT SPEED
(MENU 7)
OUTPUT RUNNING
(MENU 7)
DIGOUT 1
(MENU 7)
HEALTHY
VECTOR CONTROL MODE SHEETS 5 & 6
VECTOR
CONTROL
CURRENT
CONTROL
CURRENT LIMIT
AND
TORQUE LIMIT
SELECTIONS
MENU 3
SLIP
COMPENSATION
AND
MOTOR
STABILITY
MENU 3
=2, VECTOR
SPEEDCONTROL
AMPLIFIER
DROOP CONTROL
ERROR DEADBAND
MENU 14
SPEED TRIM
SELECTIONS
MENU 24
REGEN POWER
LIMIT P4.12
TORQUE LIMIT
CONTROL
AND
SELECTIONS
MENU 8
MOTOR TEMP.
COMPENSATION +
FLUX LIMIT
MENU 12
FLUXING
CONTROL
AND
VOLTAGE
BOOST
MENU 3
BASIC MOTOR NAMEPLATE DATA
MENU 2
FREQUENCY CONTROL MODE SHEET 4
DC INJ ECTION
BRAKING
SET-UP
MENU 4
REGEN POWER
LIMIT P4.12
SYNCRO-STARTING
MODE SET-UP
MENU 4
F
V
OPTIONAL
DYNAMIC
BRAKE
MENU 23
MOTOR VOLTS
SHEET 7
MOTOR
AND
DRIVE
PROTECTION
P9.09/P1.03
FREQUENCY
P9.05/P1.02
P9.07/P1.04
MOTOR CURRENT
IGBT's +PWM
8
25
(1)
DRIVE
O/P RUNNING
HARDWARE
BRIDGE
INTERLOCK
- +
DC LINK VOLTS
SHEET 7
- +
P11.03
R S T
J OG
ENC
MOTOR
Sheet
3
Machine Bridge Control System Overview
SELECT STANDARD OR
ALTERNATE
VOLTAGE GRADE
P99.11
AC-FED OR DC-FED
- +
(DRIVE MODEL
DEPENDENT)
5C. Control Block Diagram ALSPA MV3000e AEM Drives
ALSPA MV3000e Getting Started Manual for AEM Drives (06/06) Page 5C-6
RS485
SERIAL
LINK
SET-UP
RS485 USER PAGE 2 SIZE P32.65
RS485 USER PAGE ELEMENTS 1 to 20
P32.66
to
P32.85
RS485 CONTROL WORDS @ LOSS ACTION
RS485 DEFAULT FOR WORD0 (after loss)
RS485 DEFAULT FOR WORD1 (after loss)
D-DTx REF 1/2
D-DTx CONTROL 0/1
Tx REF 1/2 SCALE
RS485 LOSS ACTION
RS485 TIME OUT PERIOD
RS485 BAUDRATE
RS485 TRIB. ADDRESS
RS485 PROTOCOL
RS485 PARITY
P32.91
P32.92
P32.64
P32.87
P32.88
P32.89
P32.90
P32.63
P32.62
P32.54
P32.55
P32.50
P32.51
P32.52
P32.53
Tx
DATA
DRIVE
to
DRIVE
Rx
DATA
P32.93
P32.94
Rx REF 1/2 SCALE
Rx REF's 1/2
X
Rx CONTROL WORDS
X
RS485
USER
PAGE 2
SET-UP
Tx and Rx
TO/FROM
USER PAGES
RS485 REFERENCE 1
RS485 REFERENCE 2
RS485. WORD0 BITS 0 to 15 =
RS485. WORD1 BITS 0 to 15 =
RxDATA FROMTHE LINK
RS485 CONTROL WORD 1 P32.61
P32.60 RS485 CONTROL WORD0
CLAMP
CLAMP
RS485
DATA
RS485
HEALTHY 57
+/-100%
INV = -3.015 . . .to . . . -3.000
INV =
3.115 . . .to . . . 3.100
-3.115 . . .to . . . -3.100
3.015 . . .to . . . 3.000
P32.58
P32.59
RS232 SERIAL LINK
RS485 SERIAL LINK
RS232 TIME OUT PERIOD
RS232 LOSS ACTION
SERIAL WRITE ENABLE
SERIAL GLOBAL RESPONSE
RS232 USER PAGE 1 SIZE
RS232 USER PAGE ELEMENTS 1 to 20
RS232 DEFAULT FOR WORD0 (after loss)
RS232 DEFAULT FOR WORD1 (after loss)
RS232 CONTROL WORDS @ LOSS ACTION
P32.24
P32.00
P32.01
P32.26
to
P32.45
P32.25
P32.14
P32.15
P32.22
P32.23
RS232 PROTOCOL
RS232 PARITY
RS232 TRIB. ADDRESS
RS232 BAUDRATE
SERIAL WRITE ENABLE
SERIAL GLOBAL RESPONSE
P32.12
P32.13
P32.00
P32.01
P32.10
P32.11
RS232
SERIAL
LINK
SET-UP
RS232
DATA
RS232 REFERENCE 1
RS232 REFERENCE 2
RS232. WORD 0 BITS 0 to 15 =
RS232. WORD 1 BITS 0 to 15 =
RS485 CRC FAILURES P32.56
RS485 TIME OUTS P32.57
Tx and Rx
TO/FROM
USER PAGES
RS232
USER
PAGE1
SET-UP
RS232 CONTROL WORD 1 P32.21
CLAMP
CLAMP
RS232 CONTROL WORD0 P32.20
INV =
4.115 . . .to . . . 4.100
-4.115 . . .to . . . -4.100
P32.18
P32.19
4.015 . . .to . . . 4.000
INV =
-4.015 . . .to . . . -4.000
RxDATA FROMTHE LINK
RS232 TIME OUTS
RS232 CRC FAILURES
RS232
HEALTHY 58
P32.17
P32.16
+/-100%
50 HS REF ON
HS O/P SCALING
O/P FREQ =Encoder line count x Speed
30 x P20.00
WHEN USING THE O/P SCALERS, SIMPLY EDIT IN THE VALUE THAT IS
REQUIRED TO BE 100%.
O/P 2 POLARITY
O/P 2 MODE
O/P 1 MODE
O/P 1 POLARITY
INPUT
OUTPUT
ANALOG O/P 2 SIGNAL P7.22
O/P 2 SCALE FACTOR P7.25
ANALOG O/P 1 SIGNAL
O/P 1 SCALE FACTOR
P7.17
P7.20
O/P 1 VALUE P7.21
ANALOG
DIGITAL
O/P 2 VALUE P7.26
ANALOG
DIGITAL
HSIO MODE
ANALOG I/P REF 1
ANALOG I/P REF 2
P20.00
HSIO +/- INPUT
TB6/8,7
DIGITAL
ANALOG
DIGITAL
ANALOG
ANALOG REF TIME CONST.
P7.16
TB6/6,5
1 =INPUT
>1 =OUTPUT
HIGH SPEEDDIGITAL
INPUT/OUTPUT
TB4/9,8
ANALOG REF TIME CONST.
P7.16
P7.05 REF 2 OFFSET
ANALOG O/P 1
ANALOG O/P 2
TB6/1
P7.24
P7.23
P7.18
P7.19
TB6/2
27
REF2
4-20mA ON
ENCODER FEEDBACK
SPEEDFEEDBACK
HSIO REF. INPUT
REF 1 VALUE
REF 2 VALUE
REF 1 OFFSET
X +
+
P7.01
MODE
X +
+
MODE
P7.04 REF 2 MODE
REF 2 GAIN P7.06
HS I/P
SCALING
REF 1 GAIN P7.02
REF 1 MODE P7.00
REF1
4-20mA ON
ANALOG REF1
26
P7.03
P7.07
ANALOG REF2
HS INPUT REF.
P20.03
DEFAULT CONNECTIONS TO DIGITAL O/P SHOWN
HS I/P FREQ. FOR 100%SPEED
USE THE FOLLOWING VALUES FOR CONTROL FLAGS ANDDIGITAL O/P's
TO ALLOW CONNECTION TO THE DIGITAL INPUTS
HS I/P FREQ. FOR 0%SPEED
DIGITAL I/P STATES MONITOR P11.21
DIGIN 6
DIGIN 4
DIGIN 5
P20.01
P20.02
TB3/3
TB3/4
TB3/5
DIGIN 3
DIGIN 2
DIGIN 1
TB3/7
TB3/6
TB3/8
12
AT SPEED
DRIVE O/P RUNNING
USING "NOT" TRIPPEDENSURES THAT
WARNINGS DO NOT AFFECT THE HEALTHY OUTPUT
DIGITAL O/P STATES MONITOR P11.22
8
TRIPPED
5
TB1/3,2,1
DIGOUT 3
1.006 for DIGIN 6, -1.006 for INV DIGIN 6
1.005 for DIGIN 5, -1.005 for INV DIGIN 5
1.004 for DIGIN 4, -1.004 for INV DIGIN 4
1.003 for DIGIN 3, -1.003 for INV DIGIN 3
1.002 for DIGIN 2, -1.002 for INV DIGIN 2
1.001 for DIGIN 1, -1.001 for INV DIGIN 1
P7.29 DIGITAL OUTPUT 3 SIGNAL
(2.012)
DIGOUT 1
DRIVE O/P RUNNING
DIGOUT 2
AT SPEED (MOTOR CONTROL)
P7.28 DIGITAL OUTPUT 2 SIGNAL
(2.008)
P7.27 DIGITAL OUTPUT 1 SIGNAL
HEALTHY
(-2.005)
TB1/6,5,4
TB1/9,8,7
Sheet
4
Plant I/O and Serial Links
DIGOUT
DIGIN
MONITOR
POINT
xx
STATUS
FLAG
ANALOG
I/O
KEY
CONTROL
FLAG
xx
DEFAULT
CONNECTION
(A)
DEFAULT
SETTING
100
V dc AT REF
P99.01 =1,2,3
P99.01 =4
(2.100)
V dc AT REF (SFE MODE)
MOTOR
CONTROL
ONLY
1 2 3
1 2 3 4 5 6
INTERLOCK
15 14 13 2 1 0 ...
13 14 15 2 0 1 ...
MENUS 60, 61,
63, 89
MENUS 59,
60, 61, 62, 89
DEVICENET
SEE MANUAL T2017
MENUS 60,
65, 67, 89
MENUS 58,60,
65, 66, 89
CAN OPEN
SEE MANUAL T2013
SECONDCAN PORT
SEE MANUAL T1968
Tx
Rx
Tx
Rx
FROM CAN
PORT 1
FROM CAN
PORT 2
USE THE FOLLOWING VALUES
FOR CONTROL FLAGS AND
DIGITAL O/P's TO ALLOW
CONNECTION TO THE BITS OF
THE CONTROL WORDS
USE THE FOLLOWING VALUES
FOR CONTROL FLAGS AND
DIGITAL O/P's TO ALLOW
CONNECTION TO THE BITS OF
THE CONTROL WORDS
RECEIVED
DATA FROM
ONE OTHER
Tx DRIVE ON
D-DLINK
TRANSMIT
DATA TO ALL
OTHER
DRIVES ON
D-DLINK
ALSPA MV3000e AEM Drives 5C. Control Block Diagram
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page 5C-7
KEYPAD/REMOTE
DIGIN 4
(-1.004)
REF. SRC.
SELECT
MENU 5
REF. SRC. 3
REF. SRC. 4
P5.03=(3)
P5.04 =(1)
REF. SRC. 2
REF. SRC. 1
P5.01 =(1)
BACKUP SRC.
P5.05 =(0)
WARNING ON BACKUP ?
P5.27
RS485 SERIAL
LINK REF 2
SUMMING NODE A
TRIMREF. SCALE FACTOR B
TRIMREF. SCALE FACTOR A
TRIMREF. INPUT B SELECT
SUMMING NODE B
FIXED REF #0(P21.00)
FIXED REF #1(P21.01)
POSITION CONTROL
RS232REF 1
PID CONTROLLER
FIXED REF MENU
MOTORISED POT
REF. SEQUENCER
FIXED VAL OF 0
ANALOG REF2
FIXED VAL OF 0
RS485REF 1
ANALOG REF1
POINTER 6
P18.04
PRESET VALUE
LOWER RATE
RAISE RATE
P18.03
71
P18.06
P18.01
P18.02
P18.00
MODE
PRESET
35
34
P18.05
LOWER
RAISE
15
P19.03
P19.01
P19.02
16
MOTORISED POT
(MENU 18)
14
12
13
10
11
8
9
(0)
5
6
7
(0)
(0)
4
1
2
3
FIXED REF #15
FIXED REF #0
P21.15
SEQUENCER SOURCES
SEQUENCER TIMES
NUMBER POINTS
REF_SELECT.3
REF_SELECT.2
REF_SELECT.0
REF_SELECT.1
P17.08TO
P17.17
P17.03 TO
P17.07
P17.01
P21.16
FIXED
REF
MENU
(MENU 21)
33
(0)
32
(0)
P21.19
P21.18
(0)
30
31
(0)
P21.17
P21.00
TRIM
REFERENCE
(MENU 19)
TRIMREF.
INPUT A SELECT
P19.00
22
POINTER 2
POINTER 1
21
17
SUMMING NODE B
20
SUMMING NODE D
SUMMING NODE C
19
SUMMING NODE A
18
15
HS DIG I/P
POSITION CONTROL
16
P18.07
TRIMREF. OUTPUT P19.04
MOTOR. POT. OUTPUT
FIXED REF. OUTPUT P21.20
REF.SEQUENCER OUTPUT P17.21
13
12
14
FIXED VAL OF 0
FIXED VAL OF 0
TRIMREFERENCE
10
11
FIXED REF
MENU
MOTORISEDPOT
REFERENCE
SEQUENCER
RS232 SERIAL
LINK REF 2
PID CONTROLLER
9
8
7
RS232 SERIAL
LINK REF 1
6
OUTPUT
NOT =
0%REF
SEQUENCER
RUNNING
ERROR TIME CONST.
DIFFERENTIAL TIME
PROPORTIONAL BAND
CURRENT POINT
ERROR DEADBAND
SUMMING NODE B 13
SEQUENCE
RESET
SEQUENCER MODE
SEQUENCE
TRIGGER
SEQUENCE
FREEZE
POINTER 5
FEEDBACK SELECT
SUMMING NODE D
SPEED ERROR
ACTIVE CURRENT
FLUX DEMAND
SUMMING NODE C
RS485REF 2
RS232REF 2
TORQUE DEMAND
SPEED DEMAND
FIXED VAL OF 0
ANALOG REF 2
SETPOINT SELECT
POINTER 4
12
P17.00
P16.01
11
10
9
7
8
2
3
4
5
6
1
P16.00
14
27 33
REFERENCE
SEQUENCER
(MENU 17)
29
(1)
P17.20
(0)
28
P17.19
34
(0)
P17.18
PIDFB SCALE
FACTOR
MOTORISED POT
SUMMING NODE A
TORQUE DEMAND
SPEED DEMAND
RS232REF 1
TRIMREFERENCE
RS485REF 1
FIXED REF #0
ANALOG REF 1
FIXED REF MENU
REF. SEQUENCER
FIXED VAL OF 0
6
12
10
11
9
7
8
3
4
5
1
2
ERROR INVERT P16.08
P16.07
P16.06
P16.05
INTEGRAL TIME P16.04
P16.03
PID
CONTROLLER
(MENU 16) SUICIDE 69
FIXED REF #3 (P21.03) 14
FIXED REF #4 (P21.04)
SUMMING NODE B
SUMMING NODE C
SUMMING NODE D
SUMMING NODE A
18
19
20
15
16
17
POINTER 3
P17.02
FIXED REF #1 (P21.01)
FIXED REF #2 (P21.02)
12
13
FIXED VAL OF 0
FIXED REF #0 (P21.00)
FIXEDVAL OF 0
10
11
9
3 RS485 REF 1
PID CONTROLLER
FIXED REF MENU
MOTORISED POT
TRIMREFERENCE
7
8
4
5
6
RS232 REF 1
1
2
ANALOG REF1
ANALOG REF2
P16.02
RS485 SERIAL
LINK REF 1
5
ANALOG REF2
4
3
ANALOG REF1
2
KEYPAD SPEED
REFERENCE
1
P5.06
PID OUTPUT MONITOR P16.09
INTEGRAL
FREEZE
P16.11
(0)
26
P16.10
(-2.000)
P5.14
STOP TIME LIMIT
SYNCHROSTART MODE
START MODE
SPEED DEMAND
CLAMP ENABLE
P5.25
KEYPAD
START/STOP
STOP TB3/8
DIGIN 2
DIGIN 1
START
TB3/7
TB3/5
P4.11
P4.01
P4.00
START
(0)
P4.18
(0)
123
125
NORMAL
STOP
1
START
P4.04
P4.05
0
P4.20
(1.002)
BACKUP 124
P4.19
(0)
(1.001)
RAPID
STOP
(1)
2
P4.06
DEFAULT CONNECTIONS SHOWN.
DIGIN INVERTS ARE PERFORMED BY SIMPLY
APPLYING A -VE SIGN TO THE SELECTION ENTERED
INTO THE CONTROL FLAG PARAMETER.
REF. #3
SELECT
SPEED REFERENCE
P5.09
REF. #2
SELECT
DIGIN 5
TB3/4
ANALOGUE REF1/2
REF. #1
SELECT
P5.07
4 5
P5.08
6
(-1.005)
SELECT
REF
LOWEST
FLAG "ON"
WINS
(1.005)
KEYPAD/REMOTE
116
(1.004)
P4.09
REF. #4
SELECT 7
P5.10
(0)
P9.00
P5.00
P1.00
ZERO SPEEDHOLD TIME
START/STOP
SEQUENCER
(MENU 4)
REMOTE
START/
STOP
START/STOP
CONTROL
RAPID STOP MODE
NORMAL STOP MODE
P4.08
P4.07
P4.10
SYSTEM
CONTROL
FLAG
OVERRIDES
P5.19 P5.20
FORWARD
INHIBIT
REVERSE
INHIBIT
(0)
117
(0)
11
(0)
12
3
2
STOPPING
STARTING
0
1
RUNNING
STOPPED
48 BRAKING
SPEEDREF
TIME CONST.
P5.26
P5.23, P5.24
SPEED DEMANDCLAMPS
J OG
SPEED 1/2
SELECT
DIRECTION MODE
P5.11
DIGIN 3
DIRECTION
CONTROL
TB3/6
BACKUP CONTROL
REFERENCE LOSS
MONITOR
SERIAL LINK
4-20mA
FIELDBUS
etc.
(1.003)
P5.02 =(2)
3
P5.12
REVERSE
ENABLE
J OGGING
P5.15, P5.16 (0)
CLAMP
CLAMP
P5.17, P5.18
MIN. SPEEDS
MAX. SPEEDS
8
P5.13
J OG SPEED 2
J OG SPEED
121
P5.28
(0)
P22.01, P22.03
P22.05, P22.07
P22.00, P22.02
P22.04, P22.06
SKIP SPEEDS
DIRECTION
INHIBITS
CLAMP
SKIPPING 25
SKIP BAND WIDTHS
SKIP BANDCENTRES
SELECTED
SPEED
REFERENCE
Sheet
5
DIGOUT
DIGIN
MONITOR
POINT
xx
STATUS
FLAG
ANALOG
I/O
KEY
CONTROL
FLAG
xx
DEFAULT
CONNECTION
(A)
DEFAULT
SETTING
Reference Arbitration and Starting/Stopping
ONLY APPLICABLE FOR MOTOR CONTROL MODES, P99.01 =1, 2, 3
P32.19
P32.18
P32.58
P32.59
START/
STOP
STOP
BACKUP
5C. Control Block Diagram ALSPA MV3000e AEM Drives
ALSPA MV3000e Getting Started Manual for AEM Drives (06/06) Page 5C-8
P24.01
P24.02
DC INJ ECTION
BLOCK
P6.05 -
P6.08
P3.05 = REQUIRED MOTOR PEAK I LIMIT x 100%
P99.04
(0)
CURRENT
LIMIT SOURCE
FIXEDVAL OF 0
SUMMING NODE A
SUMMING NODE B
FIXEDVAL OF 0
REF SEQUENCER
MOTORISED POT
TRIM REFERENCE
FIXEDREF MENU
P3.06
POINTER 13 17
16
15
14
13
12
11
10
9
FIXED
CURRENT LIMIT P3.05
PID CONTROLLER
ANALOG REF2
RS485REF 2
RS232REF 2
RS485REF 1
RS232REF 1
ANALOG REF1
P3.07
8
7
FIXED100% 1
6
5
4
3
2
CLAMP
ZERO
REFERENCE
SELECTED
SPEED
REFERENCE
13
P5.21
(0)
CURRENT LIMIT
RESPONSE SPEED
SCALE THE
FIXEDLIMIT
114
P3.08
RAMP
(MENU 6)
CURRENT
LIMIT
(MENU 3)
4
(0)
14-
17
RAMP
FREEZE
UP/DOWN
FWD/REV
(no bypass)
SUMMING NODE C
20
21
SUMMING NODE D
POINTER 7
POSITION CONTROL
FIXED VAL OF 0
FIXED VAL OF 0
17
18
19
16
11
12
13
14
15
4
5
8
9
10
6
7
SUMMING NODE A
SUMMING NODE B
MOTORISEDPOT
TRIMREFERENCE
HS DIG I/P
RS485 REF 2
RS485 REF 1
FIXED REF MENU
PIDCONTROLLER
REF SEQUENCER
RS232 REF 1
RS232 REF 2
SPEEDTRIM
SCALE 1
SPEEDTRIM
SCALE SELECT
(0)
75
P24.04
SPEED TRIM SOURCE
P24.00
CURRENT &
TORQUE
LIMIT
DISABLE
P24.05
2
3
ANALOG REF1
ANALOG REF2
SPEEDTRIM SLEW RATE
KEYPADSPEED REF 1
(0) ENABLE
SPEED
TRIM
70
P24.03
TORQUE
LIMIT
(MENUs 3and 8)
SPEED FEEDBACK
%=P9.01
RPM=P9.03
CUT-IN FREQUENCY
RESPONSE SPEED
P8.02
P8.03
P8.01
P8.00
P8.08
RS485 REF 2 5
2NDRAMP RATES
RAMP RATES
S-SHAPING
P6.12
- P6.15
P6.00
- P6.03
P6.04
REF SEQUENCER
SUMMING NODE A
SUMMING NODE B
POINTER 9
POINTER 10
MOTORISEDPOT
TRIMREFERENCE
FIXED REF MENU
FIXED VAL OF 0
FIXED VAL OF 0
RS232 REF 1
RS232 REF 2
PIDCONTROLLER
9
15
16
17
18
14
13
10
11
12
6
7
8
SELECT
2NDRAMP
RATES 127
REGEN. POWER LIMIT
-VE TORQUE LIMIT SCALE SOURCE 2
P3.10
P3.09
(0)
P6.16
+VE TORQUE LIMIT 2
-VE TORQUE LIMIT SCALE SOURCE 1
-VE TORQUE LIMIT 2
+VE TORQUE LIMIT SCALE SOURCE 2
-VE TORQUE LIMIT 1
X
X
X
RS485 REF 1
ANALOG REF1
ANALOG REF2
FIXED 100%
2
3
4
1
+VE TORQUE LIMIT 1
+VE TORQUE LIMIT SCALE SOURCE 1
X
P4.12
P8.11
(0)
TORQUE
LIMIT
ENABLE
115
P3.11
P8.09
P8.10
TRQ LIM
1/2
(0)
21
P8.07
P3.02
P3.01
P3.24
P3.25 VARIABLE V. BOOST SOURCE
VARIABLE VOLTS BOOST
P3.27
PID CONTROLLER
FIXEDVAL OF 0
FIXEDVAL OF 0
RECTIFICATION MODE
6 RS485REF 1
9 RS232REF 2
10
11 POINTER 19
8 RS232REF 1
7 RS485REF 2
4
5
ANALOG REF2
ANALOG REF1
1
2
3
FIXED100%
SYNCHRO-
STARTING
BLOCK
TRQ LIM
1/2
(0)
21
P8.07
P4.02 SCAN CURRENT
SCAN RATE
P4.03
SYNC'START MODE P4.01
P4.14
DC INJ . DURATION
DC INJ . CURRENT
P4.16
P4.15
DC INJ . DELAY
DC INJ . SPEED P4.13
SLIP
COMPENSATION
MOTOR
STABILITY
SLIP COMP. GAIN
P3.03
STABILITY T.CONST. P3.17
TORQUE &SLIP
DERIVATION
FLUX
CONTROL
P3.04
P2.01
P3.31 ECONOMY FACTOR
BASE VOLTAGE
ABS. MINIMUM FREQUENCY
STABILITY GAIN
P3.16
CLAMP
MOTOR
CALIBRATION
RUN IN
PROGRESS
DRIVE
O/P RUNNING
SWITCHING FREQ.
P35.00
OUTPUT
ENABLE/RUN
P4.17
(1)
25
FREQUENCY FEEDBACK P9.09
8
49
CURRENT
CONTROL
BLOCK
VARIABLE VOLTS BOOST O/P
TAPER WITH
FREQUENCY
ACTIVE CURRENT
AUTO BOOST
FIXED BOOST
P2.00 BASE FREQUENCY
ENABLE
VARIABLE
V.BOOST
X
P3.00 FLUXING CONTROL
P3.26
P3.28
>=0 X
(0)
126
CURRENT MODE
CURRENT REFERENCE ARBITRATION
FROMSTART/STOP SEQUENCER
PULSE
WIDTH
MODULATION
MOTOR VOLTAGE
P9.07
MOTOR
DIGOUT
DIGIN
MONITOR
POINT
xx
STATUS
FLAG
ANALOG
I/O
KEY
CONTROL
FLAG
xx
DEFAULT
CONNECTION
(A)
DEFAULT
SETTING
Motor Frequency Control
Sheet
6
ONLY APPLICABLE FOR MOTOR
FREQUENCY CONTROL, P99.01 =1
P6.17 TRIP AVOIDANCE THRESHOLD
SPEEDTRIM
SCALE 2
OVERVOLTAGE
TRIP AVOIDANCE
107
VOLTAGE/ CURRENT
CONTROL MODE SELECTION
FROMSTART/STOP
SEQUENCER.
MODULATION LIMIT
P3.32
BRIDGE
LINEARISATION
P11.70-P11.77
ALSPA MV3000e AEM Drives 5C. Control Block Diagram
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page 5C-9
Sheet
7
KEYPAD TORQUE REF
SUMMING NODE D
SUMMING NODE C
SUMMING NODE B
POINTER 8
SUMMING NODE A
POSITION CONTROL
P14.06
ANALOG REF1
FIXEDVAL OF 0
FIXEDVAL OF 0
HS DIG I/P
FIXEDREF MENU
REF SEQUENCER
PID CONTROLLER
TRIMREFERENCE
MOTORISEDPOT
RS485 REF 1
RS232 REF 1
RS485 REF 2
RS232 REF 2
ANALOG REF2
INERTIA COMP. SPEEDSRC
SPEED TRIMSOURCE SELECT
RS485REF 1 4
POINTER 7
SUMMING NODE D
21
20
SUMMING NODE B 18
SUMMING NODE C 19
FIXED VAL OF 0
FIXED VAL OF 0
MOTORISED POT
TRIMREFERENCE
FIXED REF MENU
HS DIG I/P
POSITION CONTROL
SUMMING NODE A 17
14
13
12
11
10
16
15
RS232REF 2
PIDCONTROLLER
REF SEQUENCER
RS485REF 2
RS232REF 1
8
9
5
7
6
S-SHAPING
MAX. DEVIATION
FWD/REV
RAMP RATES
2ndRAMP RATES
P6.04
P6.10
P6.12-
P6.15
P6.00-
P6.03
SELECTED
SPEED
REFERENCE
ANALOG REF2 3
KEYPADSPEEDREF
ANALOG REF1
1
2
SPEEDTRIMSLEW RATE P24.05
ENABLE
SPEED
TRIM
P24.03
(0)
70
RAMP
(MENU 6)
P24.02
%=P9.01/P1.01
RPM=P9.03
SPEEDFEEDBACK
P24.00
SPEEDTRIM
SCALE SELECT
SPEEDTRIMSCALE 2
(0)
75
P24.04
SUMMING NODE B
18
17
16
POINTER 9
POINTER 10
FIXEDVAL OF 0
FIXEDVAL OF 0
FIXEDREF MENU
REF SEQUENCER
PIDCONTROLLER
TRIM REFERENCE
MOTORISED POT
SUMMING NODE A
14
15
RS232REF 2
RS232REF 1
8
7
6
12
10
9
13
RS485REF 1
RS485REF 2
ANALOG REF2
ANALOG REF1
4
5
1
3
2
FIXED100%
P24.01
SPEEDDEMAND
SPEEDTRIMSCALE 1
MENU 24
CLAMP
ZERO
SPEED
19
TORQUE
DEMAND
(0)
P14.07
SPEEDFEEDBACK
TIME CONST.
SPEEDDEADBAND
OFFSET
SPEED ERROR
DEADBAND
P14.15
P14.09
P14.14
DROOP TIME CONST.
SPEED DROOP
CLAMP
ZERO
REFERENCE
13
14-
17
(0)
P5.21
4 P6.11
122
(0)
(1)
LIMIT
RAMP
18
RAMP
BYPASS
(0)
P6.09
(0)
P6.05-
P6.08
P14.18
RAMP
FREEZE
UP/DOWN
FWD/REV
P6.16
SELECT
2ND
RAMP 127
P14.17
12
P14.10
MENU 14
SPEEDDEMAND
TIME CONST.
GAIN
SELECT
SPEEDERROR
TIME CONST.
P14.13
MENU 14
P14.04
P14.03
P14.05
SPEEDLOOP I GAIN 2
SPEEDLOOP P GAIN 2
SPEEDLOOP DGAIN 2
P14.00
P14.01
P14.02
SPEEDLOOP P GAIN 1
SPEEDLOOP I GAIN 1
SPEEDLOOP D GAIN 1
21
18
19
20
13
14
15
16
17
2
KEYPADREFERENCE
WHEN CHOSEN
4
5
6
8
9
10
11
7
3
P15.00
1
MENU 8
+VE TORQUE LIMIT SCALE SOURCE 1
-VE TORQUE LIMIT SCALE SOURCE 2
-VE TORQUE LIMIT SCALE SOURCE 1
+VE TORQUE LIMIT SCALE SOURCE 2
-VE TORQUE LIMIT 2
-VE TORQUE LIMIT 1
P8.03
P8.01
+VE TORQUE LIMIT 2
+VE TORQUE LIMIT 1
P8.02
P8.00
X
P8.11
X
(0)
P8.08
21
P8.09
X
P8.10
P8.07
TRQ LIM
1/2
X (0)
P8.07
21
INERTIA COMP.
O/P TIME CONST.
INERTIA
COMP.
ACCEL.
TIME
P25.02
INERTIA COMP.
TIME CONST.
P25.01
MENU 25
INERTIA
COMP.
P14.11
P25.00
ENABLE
SPEED LOOP
DEADBAND
(0)
73
P14.16
SPEED
LOOP
P.I.D
ENABLE
INERTIA
COMP.
SGN
TRQ LIM
1/2
P25.04
(0)
INERTIA
COMP OUTPUT
P25.03
74
P11.48
SPEEDLOOP
OUTPUT
P11.47
SPEED
FEEDBACK
TORQUE
DEMAND
MAX. AVAILABLE TORQUE
P11.49
MONITOR POINT
FOR ANY TORQUE
REFERENCE EXCEPT
KEYPAD
P8.06
REGEN. POWER LIMIT
BACKUP
TORQUE
REFERENCE
SOURCE
X
(0)
P14.12
SPEED ERROR
76
3
3
3
INHIBIT
+VE
TORQUE
P8.05
(0)
22
TORQUE DEMAND
SLEW RATE
23
(0)
INHIBIT
-VE
TORQUE
P4.12
(0)
72
P15.02
ENABLE
TRQ REF
P15.03
P15.01
TORQUE
SCALE
FACTOR
TORQUE
REFERENCE
SOURCE
P15.05
P15.04
MENU 15
TORQUE REFERENCE
P15.00
P9.04
P8.04
(0)
24
DISABLE
TORQUE
TORQUE DEMAND
OVERSPEED ACTION
(SEE P29.02)
TORQUE REFERENCE
11
DIGOUT
DIGIN
MONITOR
POINT
xx
STATUS
FLAG
ANALOG
I/O
KEY
CONTROL
FLAG
xx
DEFAULT
CONNECTION
(A)
DEFAULT
SETTING
Motor Vector Control, Part 1
ONLY APPLICABLE FOR MOTOR VECTOR CONTROL, P99.01 =2
BIAS P14.19
DISABLE
SPEED
LOOP
0 ZERO
(0)
107 20
P14.20
SPEED
INTEGRAL
FREEZE
SPEED
INTEGRAL
SEED
METHOD
P14.21
5C. Control Block Diagram ALSPA MV3000e AEM Drives
ALSPA MV3000e Getting Started Manual for AEM Drives (06/06) Page 5C-10
7
8
9
RS485 REF 1 4
P12.23-FLUX LIMIT 1
ANALOG REF2
ANALOG REF1
3
2
P12.24 FLUX LIMIT SRC.
M
ENC
DIGOUT
DIGIN
MONITOR
POINT
xx
STATUS
FLAG
ANALOG
I/O
KEY
CONTROL
FLAG
xx
DEFAULT
CONNECTION
(A)
DEFAULT
SETTING
ONLY APPLICABLE FOR MOTOR VECTOR
CONTROL, P99.01 =2
MOTOR
MODEL
Motor Vector Control, part 2
Sheet
8
MENU 12
EFFECTIVE ROTOR RESISTANCE =
TEMP. COMP. SCALE
ENCODERLESS
SPEED
ESTIMATION
&SCALING
ENCODER
SPEED
FEEDBACK
&SCALING
TACHO
SPEED
FEEDBACK
&SCALING
ENABLE
MANUAL
TEMPERATURE
COMPENSATION
TORQUE
DEMAND
SELECT
BACKUP
FEEDBACK
SPEED
FEEDBACK
SELECT
118
SGN
SPEED
FEEDBACK
%=P9.01,P1.01
RPM=P9.03
SPEEDFEEDBACK
P11.51 (%)
REVERSE
SPEED
(motor going
in reverse)
ENCODER SPEED
9
MENU 13
P13.00
SPEEDFB BACKUP SRC
SPEEDFB SOURCE
P13.01
(0)
ENCODER
LOSS 59
P13.17
#ENC. REVERSALS
REVERSALS THRESH.
MAX. SPEEDCHANGE
MAX. REVERSALS
ACTION ON LOSS
P13.18
ENCODER
MONITOR
P13.03
(0)
(0)
120
119
ENC. ANGLE 13.10
13.07
13.20
13.19
FORCE ENCODER LOSS
RESET ENCODER LOSS
13.08
13.02
ANALOG REF2 3
AUTO TEMP. COMP.
AUTOMATIC Rr
IDENTIFICATION
Rr >0.5xP12.15
Rr <1.5xP12.15
PID CONTROLLER
SUMMING NODE C
SUMMING NODE D
P12.06 0=DISABLED(MANUAL)
1=ENABLED(AUTO)
FIXEDVAL OF 0
FIXEDVAL OF 0
TEMPERATURE
COMPENSATION GAIN
8
RS232 REF 2
P12.07
9
POINTER 11 13
10
11
12
RS485 REF 1
RS485 REF 2
RS232 REF 1
6
7
4
5
AUTO MANUAL
100%
ESTIMATED TEMPERATURE
COMPENSATION
P12.09
x P12.15-P12.15 x
100%-P12.04
ANALOG REF1
MOTOR TEMP. COMPENSATION
FIXED100%
P12.04
1
2
P12.08 TEMP. COMP. SOURCE
VECTOR
CONTROL
PULSE
WIDTH
MODULATION
RS485REF 2 6
P12.28 ENABLE Rs TRACKER
MATHEMATICAL
MOTOR
MODEL
TACHO FEEDBACK SRC.
TACHO FEEDBACK SCALE
TACHO FEEDBACK T.CONST. P13.16
P13.14
P13.15
HI SPEEDINPUT
POINTER 18
9
10
RS232REF 2 8
RS232REF 1 7
P13.04/P13.05
MAX. SPEEDREV P5.16
MAX. SPEEDFWD P5.15
ENCODER LINE COUNT
FIXEDVAL OF 0
FIXEDVAL OF 0
RS485REF 1
ANALOG REF1
ANALOG REF2
1
2
3
4
5
SWITCHING FREQ.
P35.00
P4.17
OUTPUT
ENABLE/RUN
DRIVE
O/P RUNNING
MOTOR
CALIBRATION
RUN IN
PROGRESS
(1)
25
49
8
OUTPUT FREQUENCY
DC LINK VOLTAGE
MENU 12
(1)
100%
NOTE:
CLAMPED TO
RANGE 20%-100%
MAX. POSSIBLE
MOTOR FLUX
CALCULATION
16 SUMMING NODE B
17 POINTER 12
14
15 SUMMING NODE A
FIXED VAL OF 0
77
P12.05
10
11
12
13
TRIM REFERENCE
FIXED VAL OF 0
RS485 REF 2 5
FIXED REF MENU
MOTORISEDPOT
PIDCONTROLLER
REF SEQUENCER
RS232 REF 1
RS232 REF 2
6
P11.70-
P11.77
BASI C MOTOR
NAMEPLATE
DATA
MENU 2
P12.01
P12.29
P12.30
MOTOR PEAK I @ NOM.
SPEED
MOTOR NOM. POWER
MOTOR NOM. SPEED
MOTOR POWER FACTOR
MOTOR FULL LOADI
MOTOR BASE FREQ.
MOTOR BASE VOLTS
P2.03
P2.04
P2.05
P2.01
P2.02
P2.00
(0)
P12.25
68
FLUX LIMIT
ENABLE
SYNCR-STARTING
BLOCK
SYNCRO-STARTING
SYNCR-START
FLUX
P4.02
P4.01
START MODE
SYNCRO-START MODE
SYNCRO-START RATE
P4.00
P4.03
BRIDGE
LINEARISATION
MOTOR PEAK I @ 0%SPEED
MOTOR PEAK I @ 100%SPEED
THIS PARAMETER IS ACTIVE
IN FREQUENCY CONTROL
MODE TO ALLOW SAFE
ENCODER CHECKING
NOTE: Speed feedback, speed reference etc are in
%of TOP SPEED
TOP SPEED=Max of P5.15
P5.16
P12.22 - LEAKAGE VOLTS
P12.21 - MOTOR MAGNETISING CURRENT @ 90%BASE VOLTS
P12.12- STATOR LEAKAGE INDUCTANCE
P12.15- ROTOR RESISTANCE
P12.16- ROTOR LEAKAGE INDUCTANCE
P12.13 - MAGNETISING RESISTANCE
P12.14- MAGNETISING INDUCTANCE
P12.11- STATOR RESISTANCE
P12.00 - MOTOR MAGNETISING CURRENT
P12.02 - NOMINAL MAINS SUPPLY VOLTS
IF AEMTHEN =Vdc/1.35
ELSE =nominal mains voltage
P12.01- MOTOR PEAK CURRENT @ NOMINAL SPEED
P12.19 - MOTOR MAGNETISING CURRENT @ 70%BASE VOLTS
P12.20- MOTOR MAGNETISING CURRENT @ 80%BASE VOLTS
P12.17 - MOTOR MAGNETISING CURRENT @ 50%BASE VOLTS
P12.18- MOTOR MAGNETISING CURRENT @ 60%BASE VOLTS
HIGH DYNAMIC CURRENT BANDWIDTH
VECTOR FLUXING MODE
OPTIMUMVOLT MOD LIMIT
OPTIMUM VOLT MODE CURRENT
CONTROL BANDWIDTH
P12.27
P12.35
P12.36
P12.37
Vdc FEEDFORWARDFILTER TIME
CONSTANT P12.38
CURRENT CONTROLLER Kp FACTOR P12.39
CURRENT CONTROLLER Ki FACTOR P12.40
ORIENTATION CONTROLLER Kp P12.41
ORIENTATION CONTROLLER Ki P12.42
ALSPA MV3000e AEM Drives 5C. Control Block Diagram
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page 5C-11
AC SUPPLY LOSS RIDETHROUGH
NOMINAL MAINS VOLTS
DC LINK VOLTS
O/P RUNNING
P26.02,
P26.04 .. P26.20
TRIPPED
P26.01,
P26.03 .. P26.19
DIGIN 6
MENU 9 AND MENU 11 CONTAIN MANY
OTHER MONITORING PARMETERS.
INCLUDING....
STATUS FLAG AND CONTROL FLAG
MONITORS
AUTO RESETTING CONTROL
AUTO RESETTING ENABLES
Disable
Auto-resets
Award
P28.00
CONTROL FLAGS 112 - 127
CONTROL FLAGS 80 - 111
INST. OVERCURRENT
TIMED OVERCURRENT
DC LINK UNDERVOLTS
DC LINK OVERVOLTS
ALL MOTOR TRIPS - MOTOR CONTROL MODES ONLY
INTERLOCK TRIP
REFERENCE LOSS
ALL TEMPERATURE TRIPS
SERIAL LINK LOSS
BOTH USER TRIPS
OVERSPEED - MOTOR CONTROL MODES ONLY
LOADFAULT DETECT - MOTOR CONTROL MODES ONLY
INTERLOCK TERMINAL (TB3/9)
AUTO RESET HEALTHY TIME
SUPPLY LOSS TIME-OUT
P28.06
.
.
.
.
to
.
.
.
.
.
P28.19
P28.03
P28.02
DriveHealthy
Healthytime
Time-out
SupplyLoss
No. of AUTO RESET ATTEMPTS
AUTO RESET DELAY
FORCE A MOTOR CONTROLSYNCROSTART
P28.01
P28.00
P28.05
SYNCROSTART
START MODE AS P4.00
Trip
Delaytime
Reset
Delaytime
STATUS FLAGS 96- 111
STATUS FLAGS 0- 15
....to....
CONTROL FLAGS 0 - 15
....to....
No. AUTO RESETS LEFT
IS NOT ZERO
No. AUTO RESET LEFT
7
P28.04
TO
STARTING/STOPPING
OVERRIDE
START MODE
ONLY
DURING
AUTO-RESET
AUTO RESET
AUTO RESET
CONTROL
P38.10, P38.11
P11.35
P11.30
P11.28
P11.23
16 BIT "WORDS" FOR
MONITORING
P11.08
DC LINK VOLTS
MORE MONITORING
110 DB ENABLE
(0)
111
DB RESISTOR
THERMOSTAT
P23.09
(2.008)
P23.08
NON-MV DB UNIT FITTED P23.20
P23.06
DB RESISTOR AVERAGE POWER P23.01
DB RESISTOR MAX POWER TIME P23.03
P23.04 DB VOLTAGE THRESHOLD
DB RES. OVERLOADACTION
P23.02 DB RESISTOR MAXIMUMPOWER
DB RESISTOR VALUE P23.00
RECT BRIDGE TEMP.
RECT-
RECT+
RECTIFIER BRIDGE
(IF FITTED)
CONTROL
PCB
(CDC)
DB RES. OVERLOAD REMAINING
OPTIONAL
DYNAMIC
BRAKE
UNIT
(MENU 23)
P35.12
P35.13
P23.07
HOURS ENERGISED P11.17
DAYS ENERGISED P11.18
MIN EVER ELECTRONICS TEMP. P11.14
MAX EVER ELECTRONICS TEMP. P11.13
DC-
DC+
P11.03 IGBT
BRIDGE
ELECTRONICS TEMP. P11.04
MENU 45 ALL BRIDGE TEMPERATURES
P11.05- P11.11 IGBT BRIDGE TEMPERATURE
DRIVE
TRIP
AVOIDANCE
CONTROL
DRIVE
TRIP MONITORING
SYSTEM
(MENU 10)
ON BOARD DIAGNOSTIC
HISTORY CHART RECORDER
DRIVE OVERLOADREMAINING
8 78
HISTORY
RECORDING
PLAYBACK
(MENU 27)
HISTORY
RECORDING
SET UP
(MENU 26)
P26.23
UPPER TRIGGER LIMIT
P27.01
to
P27.10
P27.00 SAMPLE DISPLAY No.
HISTORY CHANNEL No.
P26.27 HISTORY COMMAND
P26.24 SAMPLES AFTER TRIGGER
P26.22
P26.21
LOWER TRIGGER LIMIT
CHANNELS 1-10MODE
TRIGGER SOURCE
P26.00
CHANNELS 1-10SIGNALS
SAMPLE PERIOD
5
STOP HISTORY
P26.26 (2.005)
79
1SCAN
=5ms
TRIP RESETTING and USER TRIPS (ALL CONTROL MODES)
TRIP RESET
P26.25 (2.008)
RUN HISTORY
RESET
TB3/3
MONITOR DRIVE TEMP.
MONITOR DRIVE OVERLOAD
P35.09
P35.10
AVOID DRIVE TIMED OVERLOAD
AVOID DRIVE OVERTEMPERATURE
P10.33
USER
TRIP 2
112
(0)
USER
TRIP 1
(0)
10
P10.32
INFLUENCE
DRIVE
OUTPUT
FREQUENCY
RESET TRIPS
and
"TIMES SINCE"
9
(1.006)
P10.34
HOURS SINCE TRIP
SECONDS SINCE TRIP
P9.10
P10.31
P10.30
WARNING
TRIPPED
6
5
MOTOR PROTECTION/TRIP AVOIDANCE (MOTOR CONTROL MODES ONLY)
MOTOR OVERLOADREMAINING
MEASUREDPTC RESISTANCE
P9.05
P9.06
P9.07
P9.08
DRIVE TRIP AVOIDANCE (MOTOR CONTROL MODES ONLY)
RIDETHROUGH
ACTIVE
62
AC
LOSS
CONTROL
P2.08 MOTOR COOLING FAN TYPE
P2.09 MOTOR I2T ACTION
ACTION ON MOTOR PTC P2.15
MOTOR CURRENT
P2.07 MOTOR 150%OVERLOADTIME
P2.13 MOTOR PTC TRIP RESISTANCE
TRIPS ANDWARNINGS
FROMTHE DRIVE SYSTEM
MOTOR
PTC
TRIP
MOTOR
OVERLOAD
PROTECTION
ALGORITHMS
TRIPS AND WARNINGS
TRIPS AND WARNINGS
(1)
MTRIP 113
P2.11
P2.10 ACTION ON MTRIP
MOTOR CURRENT (A)
MOTOR POWER (kW)
TRIPS AND WARNINGS MOTOR
THERMOSTAT
TRIP
MOTOR VOLTS (V)
DRIVE CURRENT (%)
P9.11
P2.14
HEALTHY
(NO TRIPS
OR WARNINGS)
4
P11.19/P11.20 kW/MW HOURS
P11.15/P11.16 HOURS/DAYS RUN
M
P9.05
P11.03
Reset
(MENU 28)
Trips/Warnings and Diagnostic Monitoring
DIGOUT
DIGIN
MONITOR
POINT
xx
STATUS
FLAG
ANALOG
I/O
KEY
CONTROL
FLAG
xx
DEFAULT
CONNECTION
(A)
DEFAULT
SETTING
Sheet
9
If the drive is configured to auto-restart, the motor can start rotating without
an operator command. Take precautions to prevent injuryto personnel.
WARNING
MOTOR MONITORING (MOTOR CONTROL MODES ONLY)
(MOTOR
CONTROL MODE
ONLY)
DB RESISTOR - MOTOR CONTROL MODES ONLY
SFE MAINS - SFE MODE ONLY
PRECHARGE
COMPLETE
47
?
5C. Control Block Diagram ALSPA MV3000e AEM Drives
ALSPA MV3000e Getting Started Manual for AEM Drives (06/06) Page 5C-12
Motor Position Controller
Sheet
10
P38.00
P38.01
%=P38.06
ENABLE
INCHING
LEARN
POSN. NOW
POSITION FEEDBACK
POSITION REFERENCE
POSITION VALID
ZERO SPEED
P38.02
P38.03
P38.00
P38.01
P36.54
P36.55
POSITION
MONITOR
TOLERANCE
64
11
SEL.3
SEL.2
SEL.1
SEL.0
0000=FIXED POSN 0
...to...
1111=FIXED POSN 15
POSITION TO LEARN P37.04
FIXED
POSITION
MENU
P37.41
94
(0)
93
P37.38
P37.39
P37.40
92
(0)
(0)
91
(0)
POSITION 15
14
69 BELOW POSITION
68
67
ABOVE POSITION
AT POSITION
POINTER 16
(%POSN)
DOUBLE POINTER
POINTER 17 =high
POINTER 16=low
15
P38.02
P38.03
%=P38.07
POSITION FEEDBACK
P37.01 =(4)
REF. SRC.
SELECT
MENU 37
REF. SRC. 2
P37.00 =(1)
REF. SRC. 1
RS485 LINK
REF1 =%POSN
MOTORISED
POT (%POSN)
RS232 LINK
REF2 =%POSN
PID
(%POSN)
13
11
12
RS232 LINK
REF1 =%POSN
RS485 LINK
REF2 =%POSN
9
10
RS485 LINK
(DOUBLE PARA)
REF2 =high
REF1=low
RS232LINK
(DOUBLE PARA)
REF2 =high
REF1 =low
7
8
6
FIXED VAL OF 0
FIXED VAL OF 0
5
4
P37.03
REF. 1/2
SELECT
(0)
88
DATUM
CONTROL
MODES
MENU 36
DATUM
MOVE
IN
PROGRESS
POSITION
REFERENCE
TEACHER
(MENU 37)
POSITION CONTROL MONITOR,
ALL VALUES AND FLAGS
MENU 38
101
(0)
P37.05
POSITION VALID 64
POSITION FEEDBACK
P38.02
P38.03
POSITION
TEACHER
MENU 36
1
OF
16
P37.06 TO P37.37
POSITION 0
FIXEDPOSITION REF. TABLE
POSITION FEEDBACK
FROMENCODER [ANY MODE]
POSITION CONTROL OVERVIEW
POSITION
INCHER
MENU 36
POSITION
REFERENCE
SELECTIONS,
INCLUDING
15FIXED
POSITIONS
MENU 37
POSITION
REFERENCE
SHAPER
MENU 36
DATUMSPEED
POSITIONING
SPEED
BACKUP SRC.
P37.02 =(0)
ANALOG REF1
ANALOG REF2
FIXED MENU 1
2
3
P36.53
INCH DOWN
P36.49
P36.50
DOWN STEP
UP STEP
P36.47
P36.48
96
(0)
(0)
INCH UP 95
P36.52
89
BACKUP CONTROL
REFERENCE LOSS
MONITOR
SERIAL LINK
4-20mA
FIELDBUS
etc.
(0)
POSITION
INCHER
(MENU 36)
POSITION VALID 64
DATUM
MOVEMENT
SEQUENCER
&CAPTURE
(MENU 36)
POSITION FEEDBACK WRAPPED
TO 0/MAX POSITION WHEN
MODE =TURNTABLE
POSITION CONTROL MODE
85
84
P36.00
80
81
P36.38
P36.39
FORCE POSITION INVALID
FORCE POSITION VALID
P36.43
DATUM
APPROACH
DATUMINPUT
(0)
(0)
POSITION
FEEDBACK
(0)
(0)
82
83
P36.40
P36.41
P36.42
PERFORM
DATUM
MOVEMENT
DATUM
PERMIT
LOW
LIMIT
(0)
HIGH
LIMIT
86
87
P36.08
(0)
P36.09
(0)
(0)
INHIBIT
POSITIVE
INHIBIT
NEGATIVE
P36.32
P36.33
P36.01
Z
A/B
DATUM POSITION
ENCODER LINE COUNT DIVIDER
MIN. POSITION
MAX. POSITION
P36.04
P36.05
P36.02
P36.03
DATUMSPEED 3
DATUMSPEED 2 P36.36
P36.37
EITHER LIMIT
SPEED REFERENCE
TO SPEED CONTROL SYSTEM
DATUM SPEED1 P36.35
DATUMSEQUENCE P36.34
OR
DATUMISING
SPEED
65
DATUMMOVEMENT
IN PROGRESS
64 POSITION
VALID
66
POSITION SHAPER RANGE
CONTROL FLAGS
AND
STATUS FLAGS
-X1P36.12 -Y1P36.13
-X2P36.14 -Y2P36.15
-X3P36.16 -Y3P36.17
-X4P36.18 -Y4P36.19
-X5P36.20 -Y5P36.21
X1P36.22 Y1 P36.23
X2P36.24 Y2 P36.25
X3P36.26 Y3 P36.27
X4P36.28 Y4 P36.29
X5P36.30 Y5 P36.31
POSITION SHAPER
P36.51
POSITION
ERROR
BIAS
FOR
SINGLE
DIRECTION
APPROACH
SPEED REF.
POS.
ERROR
ENABLE
UNIDIRECTIONAL
APPROACH
90
(0)
APPROACH BIAS
P36.46
P36.44
P36.45
POSITION SPEED REF.
POSN. STATUS FLAGS 64- 79
POSN. CONTROL FLAGS 96 - 111
P36.10
P36.11
POSITIONING
SPEED
P38.12
P38.09
P38.11
POSN. CONTROL FLAGS 80- 95 P38.10
P38.04
P38.05
%=P38.08
ENC
DIGOUT
DIGIN
MONITOR
POINT
xx
STATUS
FLAG
ANALOG
I/O
KEY
CONTROL
FLAG
xx
DEFAULT
CONNECTION
(A)
DEFAULT
SETTING
ONLY APPLICABLE FOR MOTOR CONTROL MODES, P99.01 =1, 2, 3
ALSPA MV3000e AEM Drives 5C. Control Block Diagram
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page 5C-13
THE POINTERS BELOW CAN BE USED BY SIMPLY SELECTING THE RELEVANT POINTER
FROM THE LIST OFFERED IN THE RELEVANT REFERENCE CHOICE.
E.G. CHOOSE POINTER 1 FROM THE SPEED REFERENCE CHOICE SELECTION (SHEET 2)
THEN CONFIGURE POINTER 1 BELOW.
THE POINTER SOURCES CAN BE ANY DRIVE PARAMETER.
POSSIBLE SOURCE FOR
TRIM REFERENCE
TORQUE REFERENCE P15.00
POSSIBLE SOURCE FOR
PID SETPOINT
POSSIBLE SOURCE FOR
P42.14
P42.15
P42.11
P42.10
P42.07
P42.06
POINTER 8 SOURCE
POINTER 8 SCALE
POINTER 6 SCALE
POINTER 6 SOURCE
POINTER 4 SOURCE
POINTER 4 SCALE
POSSIBLE SOURCE FOR
PID FEEDBACK
POSSIBLE SOURCE FOR
SPEED TRIM REFERENCE
TORQUE LIMITS
POSSIBLE SOURCE FOR
TEMPERATURE COMPENSATION
SCALE
POSSIBLE SOURCE FOR
CURRENT LIMIT
POSSIBLE SOURCE FOR
TORQUE / MAGNET. CURRENT
POSSIBLE SOURCE FOR
POSSIBLE SOURCE FOR
POSITION REFERENCE
POSSIBLE SOURCE FOR
VARIABLE VOLTS BOOST
REFERENCE SEQUENCER P17.21
POSSIBLE SOURCE FOR
POSSIBLE SOURCE FOR
AEMREACTIVE CURRENT
POSSIBLE SOURCE FOR
AEMREACTIVE CURRENT
POSSIBLE SOURCE FOR
AEMACTIVE CURRENT
AEMVDC REFERENCE
POSSIBLE SOURCE FOR
POSSIBLE SOURCE FOR
SPEED REFERENCE
POINTER 1 SCALE
POINTER 1 SOURCE
POINTER 3 SCALE
POINTER 3 SOURCE
POINTER 5 SCALE
POINTER 5 SOURCE
POINTER 7 SOURCE
POINTER 7 SCALE
POINTER 9 SCALE
POINTER 9 SOURCE
POINTER 11 SCALE
POINTER 11 SOURCE
POINTER 13 SCALE
POINTER 13 SOURCE
POINTER 15 SCALE
POINTER 15 SOURCE
POINTER 17 SCALE
POINTER 17 SOURCE
POINTER 19 SCALE
POINTER 19 SOURCE
POINTER 21 SCALE
POINTER 21 SOURCE
POINTER 23 SCALE
POINTER 23 SOURCE
POINTER 25 SCALE
POINTER 25 SOURCE
POINTER 27 SCALE
POINTER 27 SOURCE
NEGATIVE LIMIT
REFERENCE
NEGATIVE LIMIT
P42.08
P42.09
P42.12
P42.13
P42.17
P42.16
P42.21
P42.20
P42.25
P42.24
P42.29
P42.28
P42.33
P42.32
P42.37
P42.36
P42.05
P42.04
P42.53
P42.52
P42.49
P42.48
P42.45
P42.44
P42.41
P42.40
P42.01
P42.00
SPEED REFERENCE
POSSIBLE SOURCE FOR
P42.03
P42.02
POINTER 2 SCALE
POINTER 2 SOURCE
Sheet
11
DIGOUT
DIGIN
MONITOR
POINT
xx
STATUS
FLAG
ANALOG
I/O
KEY
CONTROL
FLAG
xx
DEFAULT
CONNECTION
(A)
DEFAULT
SETTING
AEMREACTIVE CURRENT POSITIVE LIMIT
TORQUE LIMITS
POSSIBLE SOURCE FOR
FLUX LIMIT
POSSIBLE SOURCE FOR
TORQUE / MAGNET. CURRENT
POSSIBLE SOURCE FOR
POSSIBLE SOURCE FOR
POSITION REFERENCE
POSSIBLE SOURCE FOR
TACHO FEEDBACK
REFERENCE SHAPER
ONLY SOURCE FOR
POSSIBLE SOURCE FOR
POSSIBLE SOURCE FOR
AEMACTIVE CURRENT POSITIVE LIMIT
POSSIBLE SOURCE FOR
AEMACTIVE CURRENT REFERENCE
P42.23
P42.22
P42.27
P42.26
P42.31
P42.30
P42.35
P42.34
P42.39
P42.38
P42.43
P42.42
P42.47
P42.46
P42.51
P42.50
P42.19
P42.18
POINTER 26 SCALE
POINTER 26 SOURCE
POINTER 24 SCALE
POINTER 24 SOURCE
POINTER 22 SOURCE
POINTER 22 SCALE
POINTER 20 SCALE
POINTER 20 SOURCE
POINTER 18 SCALE
POINTER 18 SOURCE
POINTER 16 SOURCE
POINTER 16 SCALE
POINTER 14 SCALE
POINTER 14 SOURCE
POINTER 12 SCALE
POINTER 12 SOURCE
POINTER 10 SCALE
POINTER 10 SOURCE
POINTER 28 SCALE
POINTER 28 SOURCE
POSSIBLE SOURCE FOR
PROPORTIONAL DB REFERENCE
P42.54
P42.55
QPID POSITIVE LIMIT
PPID SETPOINT
POSSIBLE SOURCE FOR
PPID FEEDBACK
POSSIBLE SOURCE FOR
PPID FEEDFORWARD
POSSIBLE SOURCE FOR
POSSIBLE SOURCE FOR
PPID POSITIVE LIMIT
POSSIBLE SOURCE FOR
PPID NEGATIVE LIMIT
QPIDSETPOINT
ONLY SOURCE FOR
POSSIBLE SOURCE FOR
POSSIBLE SOURCE FOR
QPID FEEDFORWARD
POSSIBLE SOURCE FOR
QPID FEEBACK
P42.59
P42.58
P42.61
P42.60
P42.63
P42.62
P42.65
P42.64
P42.67
P42.66
P42.69
P42.68
P42.71
P42.70
P42.73
P42.72
P42.57
P42.56
POINTER 37 SCALE
POINTER 37 SOURCE
POINTER 36 SCALE
POINTER 36 SOURCE
POINTER 35 SOURCE
POINTER 35 SCALE
POINTER 34 SCALE
POINTER 34 SOURCE
POINTER 33 SCALE
POINTER 33 SOURCE
POINTER 32 SOURCE
POINTER 32 SCALE
POINTER 31 SCALE
POINTER 31 SOURCE
POINTER 30 SCALE
POINTER 30 SOURCE
POINTER 29 SCALE
POINTER 29 SOURCE
POINTER 38 SCALE
POINTER 38 SOURCE
POSSIBLE SOURCE FOR
QPIDNEGATIVE LIMIT
P42.74
P42.75
Pointers
5C. Control Block Diagram ALSPA MV3000e AEM Drives
ALSPA MV3000e Getting Started Manual for AEM Drives (06/06) Page 5C-14
Special Monitoring Functions
Sheet
12
DIGOUT
DIGIN
MONITOR
POINT
xx
STATUS
FLAG
ANALOG
I/O
KEY
CONTROL
FLAG
xx
DEFAULT
CONNECTION
(A)
DEFAULT
SETTING
APPLICATION MONITORS AND SPECIAL FUNCTIONS, MOTOR CONTROL MODES ONLY
RESET
SEQUENCE LENGTH
SEQUENCE TIMES
SEQUENCE START POINT
74
MODE
(0)
100
P31.01
P31.02
P31.00
SEQUENCE
RUNNING
SPEEDMONITOR
(MENU 29)
NEXT
FREEZE
PREVIOUS
AT TORQUE LIMIT 28
BELOW TORQUE WINDOW
31
48
OUTSIDE TORQUE WINDOW
29
32
30
ABOVE TORQUE WINDOW
MOTOR BRAKING
IN TORQUE WINDOW
TORQUE
TORQUE WINDOW LEVEL 1
TORQUE WINDOW LEVEL 2
TORQUE
MONITOR
(MENU 29)
HYSTERESIS
P9.04
P29.08
P29.07
P29.06
ABOVE SPEEDWINDOW
BELOW SPEEDWINDOW
OUTSIDE SPEEDWINDOW
ZERO SPEED
IN SPEEDWINDOW
SPEEDFEEDBACK
73
70
72
(0)
(0)
(0)
99
97
98
P31.20
P31.21
P31.22
STATUS FLAG
GENERATOR
(MENU 31)
71
P31.19
16
12
14
AT SPEED
11
13
15
10 OVERSPEED
FLAG GEN 0
FLAG GEN 3
FLAG GEN 1
FLAG GEN 2
P9.01
ACTION ON OVERSPEED
SPEEDWINDOW LEVEL 1
SPEED WINDOW LEVEL 2
HYSTERESIS
FWDOVERSPEED
REV OVERSPEED
P29.02
P29.03
P29.04
P29.05
P29.00
P29.01
P44.19
P44.01
P44.18
P44.00
REFERENCE SHAPER Y10
REFERENCE SHAPER X10
....to....
REFERENCE SHAPER Y1
REFERENCE SHAPER X1
(X1,Y1)
POINTER 20 SCALE
POINTER 20 SOURCE
P42.39
P42.38 INPUT
(X5,Y5)
REFERENCE
SHAPER
(MENU 44)
X
Y
(X8,Y8)
(X10,Y10)
REF. SHAPER OUTPUT P44.20
(INPUT)
(OUTPUT)
LOAD FAULT DETECTION
WINDOW
USEDTO CONDITION
MONITOR THE PLANT
(MENU 43)
REVERSE MAX LOAD3
REVERSE MIN LOAD 3
REVERSE SPEED3
FORWARDMIN LOAD 1
FORWARD MAX LOAD1
...to....
SPEED
FORWARDSPEED 1
LOADFAULT TIME
LOADFAULT INPUT
TORQUE DEMAND
LOADFAULT ACTION
DRIVE CURRENT
LOAD
60
LOADFAULT
LOW
61
LOADFAULT
HIGH
P43.20
P43.19
P43.18
P43.05
P43.04
P43.03
P43.02
P43.01
P43.00
ALSPA MV3000e AEM Drives 5C. Control Block Diagram
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page 5C-15
Application Logic - General Purpose Logic Blocks
Sheet
13
DIGOUT
DIGIN
MONITOR
POINT
xx
STATUS
FLAG
ANALOG
I/O
KEY
CONTROL
FLAG
xx
DEFAULT
CONNECTION
(A)
DEFAULT
SETTING
P30.28
P30.37
SET
RESET
LATCH
C
P30.29 MODE
MENU 30
46
P30.34
P30.30
(0) SOURCE
(0)
(0)
MENU 30
P30.32
P30.31
FUNCTION 50
P30.38
48
(0)
P30.36
49
RESET
SET
LATCH
OUTPUT C
38
DELAY TIME
DELAY TIME
DELAY TIME
COMPARATOR
C
COMPARATOR
B
INPUT C
THRESHOLDC
P30.26
P30.27
HYSTERESIS
THRESHOLDB
INPUT B
P30.13
P30.14
P30.15
P30.16
HYSTERESIS
MODE
DELAY C
COMPARATOR C
OUTPUT
35
P30.17
MENU 30
41
P30.21
DELAY B
(0) SOURCE
COMPARATOR B
OUTPUT
21
MENU 30
COMPARATOR
A
THRESHOLDA
P30.03
P30.01
P30.02 HYSTERESIS
MODE
INPUT A P30.00
DELAY A
36
P30.08
P30.04
(0) SOURCE
COMPARATOR
A
OUTPUT
17
(0)
(0)
(0)
LOGIC
BLOCK
C
47
DELAY C
OUTPUT
36
P30.35
P30.19
P30.25
FUNCTION 45
DELAY B
OUTPUT
P30.18
P30.24
(0)
(0)
42
43
LOGIC
BLOCK
B
P30.22
P30.23
44
22
24
SET
RESET
LATCH
B
LOGIC
BLOCK C
OUTPUT
37
SOURCE P30.33
RESET
LATCH
OUTPUT B
LOGIC
BLOCK B
OUTPUT
SOURCE
SET
P30.20
23
(0)
(0)
P30.06
P30.05
P30.11
P30.12
(0)
FUNCTION
38
(0) LOGIC
BLOCK
A
37
P30.09
P30.10
39
40
DELAY A
OUTPUT
18
P30.07 SOURCE
RESET
SET
LATCH
OUTPUT A
SET
RESET
LATCH
A
20
LOGIC
BLOCK A
OUTPUT
19
DELAY TIME
COMPARATOR
D
P30.42
MODE
P30.41 HYSTERESIS
THRESHOLDD
INPUT D
P30.39
P30.40
P30.43
51
P30.47
(0) SOURCE
COMPARATOR D
OUTPUT
DELAY D
39
(0)
(0)
P30.48
P30.45
P30.51
FUNCTION 55
P30.44
P30.50
53
(0)
(0)
LOGIC
BLOCK
D
52
P30.49
54
DELAY D
OUTPUT
40
SET
RESET
LATCH
D
42
RESET
LATCH
OUTPUT D
SET
41
SOURCE P30.46
LOGIC
BLOCK D
OUTPUT
DELAY TIME
COMPARATOR
I
P47.03
MODE
P47.02 HYSTERESIS
THRESHOLDI
INPUT I
P47.00
P47.01
P47.04
144
P47.07
(0) SOURCE
COMPARATOR I
OUTPUT
DELAY I
112
P47.08
146
P47.06 FUNCTION
P47.05
(0)
(0)
LOGIC
BLOCK
I
P47.09
145
DELAY I
OUTPUT
113
114
LOGIC
BLOCK I
OUTPUT
DELAY TIME
COMPARATOR
J
P47.13
MODE
P47.12 HYSTERESIS
THRESHOLDJ
INPUT J
P47.10
P47.11
P47.14
144
P47.17
(0) SOURCE
COMPARATOR J
OUTPUT
DELAY J
115
P47.18
149
P47.16 FUNCTION
P47.15
(0)
(0)
LOGIC
BLOCK
J
P47.19
148
DELAY J
OUTPUT
116
117
LOGIC
BLOCK J
OUTPUT
DELAY TIME
COMPARATOR
K
P47.23
MODE
P47.22 HYSTERESIS
THRESHOLDK
INPUT K
P47.20
P47.21
P47.24
150
P47.27
(0) SOURCE
COMPARATOR K
OUTPUT
DELAY K
118
P47.28
152
P47.26 FUNCTION
P47.25
(0)
(0)
LOGIC
BLOCK
J
P47.29
151
DELAY K
OUTPUT
119
120
LOGIC
BLOCK K
OUTPUT
DELAY TIME
P47.38
155
P47.36 FUNCTION
P47.35
(0)
(0)
LOGIC
BLOCK
L
P47.39
154
DELAY L
OUTPUT
122
123
LOGIC
BLOCK L
OUTPUT
COMPARATOR
L
P47.33
MODE
P47.32 HYSTERESIS
THRESHOLDL
INPUT L
P47.30
P47.31
P47.34
153
P47.37
(0) SOURCE
COMPARATOR L
OUTPUT
DELAY L
121
MENU 47
MENU 47
MENU 47
MENU 47
(0)
(0)
(0)
LOGIC
BLOCK
H
65
P30.65
66
P30.66
67
P30.67
46
LOGIC
BLOCK H
OUTPUT
P30.64 FUNCTION
LOGIC
BLOCK
E
(0)
(0)
(0)
56
P30.53
57
P30.54
58
P30.55
P30.52 FUNCTION
43
LOGIC
BLOCK E
OUTPUT
(0)
(0)
LOGIC
BLOCK
G
(0)
62
P30.61
63
P30.62
64
P30.63
FUNCTION P30.60
45
LOGIC
BLOCK G
OUTPUT
LOGIC
BLOCK
F
(0)
(0)
(0)
59
P30.57
60
P30.58
61
P30.59
P30.56 FUNCTION
44
LOGIC
BLOCK F
OUTPUT
(0)
(0)
158
P47.43
159
P47.44
P47.40 FUNCTION
LOGIC
BLOCK M
OUTPUT
(0)
157
P47.42
(0)
156
P47.41
LOGIC
BLOCK
M
124
(0)
(0)
170
P47.58
171
P47.59
P47.55 FUNCTION
LOGIC
BLOCK P
OUTPUT
(0)
169
P47.57
(0)
168
P47.56
LOGIC
BLOCK
P
127
(0)
(0)
166
P47.53
167
P47.54
P47.50 FUNCTION
LOGIC
BLOCK O
OUTPUT
(0)
165
P47.52
(0)
164
P47.51
LOGIC
BLOCK
O
126
(0)
(0)
162
P47.48
163
P47.49
P47.45 FUNCTION
LOGIC
BLOCK N
OUTPUT
(0)
161
P47.47
(0)
160
P47.46
LOGIC
BLOCK
N
125
MENU 47
MENU 47
(0)
(0)
174
P47.63
175
P47.64
P47.60 FUNCTION
LOGIC
BLOCK Q
OUTPUT
(0)
173
P47.62
(0)
172
P47.61
LOGIC
BLOCK
Q
128
(0)
(0)
178
P47.68
179
P47.69
P47.65 FUNCTION
LOGIC
BLOCK R
OUTPUT
(0)
177
P47.67
(0)
176
P47.66
LOGIC
BLOCK
R
129
(0)
(0)
182
P47.73
183
P47.74
P47.70 FUNCTION
LOGIC
BLOCK S
OUTPUT
(0)
181
P47.72
(0)
180
P47.71
LOGIC
BLOCK
S
130
(0)
(0)
186
P47.78
187
P47.79
P47.75 FUNCTION
LOGIC
BLOCK T
OUTPUT
(0)
185
P47.77
(0)
184
P47.76
LOGIC
BLOCK
T
131
5C. Control Block Diagram ALSPA MV3000e AEM Drives
ALSPA MV3000e Getting Started Manual for AEM Drives (06/06) Page 5C-16
Summing Nodes, Analogue Switches and Square Roots
DIGOUT
DIGIN
MONITOR
POINT
xx
STATUS
FLAG
ANALOG
I/O
KEY
CONTROL
FLAG
xx
DEFAULT
CONNECTION
(A)
DEFAULT
SETTING
THE EQUATION BELOW SHOWS HOW SUMMING NODES A, B, C, D, E, F, G & H OPERATE.
THE EIGHT DIAGRAMS ARE A LOGICAL REPRESENTATION.
SUMMING NODE INPUT 1
SUMMING NODE SCALE 1
SUMMING NODE INPUT 2
SUMMING NODE SCALE 2
SUMMING NODE OUTPUT = ? X 100.00%
WHERE ? IS THE CHOSEN MODE (+, , x or )
SUMMING NODE A
INPUT PARAMETER #1A
PARAMETER #1A SCALE
INPUT PARAMETER #2A
PARAMETER #2A SCALE P40.03
P40.01
P40.02
P40.00
MENU
40
SUMMING NODE A OUTPUT P40.04 SUMMING NODE A MODE P40.20
(+)
SUMMING NODE B OUTPUT
INPUT PARAMETER #2B
PARAMETER #2B SCALE
P40.06
P40.08
MENU
40
SUMMING NODE B
PARAMETER #1B SCALE
INPUT PARAMETER #1B
P40.07
P40.05
P40.09 SUMMING NODE B MODE P40.21
(+)
SUMMING NODE C
PARAMETER #2C SCALE
INPUT PARAMETER #2C
PARAMETER #1C SCALE
INPUT PARAMETER #1C
P40.13
P40.11
P40.12
P40.10
MENU
40
SUMMING NODE C OUTPUT P40.14 SUMMING NODE C MODE P40.22
(+)
SUMMING NODE D
MENU 40
SUMMING NODE DOUTPUT P40.19
PARAMETER #2DSCALE
INPUT PARAMETER #2D
PARAMETER #1DSCALE
INPUT PARAMETER #1D
P40.18
P40.16
P40.17
P40.15
SUMMING NODE DMODE P40.23
(+)
SUMMING NODE E
INPUT PARAMETER #1E
PARAMETER #1E SCALE
INPUT PARAMETER #2E
PARAMETER #2E SCALE P40.27
P40.25
P40.26
P40.24
MENU
40
SUMMING NODE E OUTPUT P40.28 SUMMING NODE E MODE P40.44
(+)
SUMMING NODE F OUTPUT
INPUT PARAMETER #2F
PARAMETER #2F SCALE
P40.30
P40.32
MENU
40
SUMMING NODE F
PARAMETER #1F SCALE
INPUT PARAMETER #1F
P40.31
P40.29
P40.33 SUMMING NODE F MODE P40.45
(+)
SUMMING NODE G
PARAMETER #2G SCALE
INPUT PARAMETER #2G
PARAMETER #1G SCALE
INPUT PARAMETER #1G
P40.37
P40.35
P40.36
P40.34
MENU
40
SUMMING NODE G OUTPUT P40.38 SUMMING NODE G MODE P40.46
(+)
SUMMING NODE H
MENU 40
SUMMING NODE H OUTPUT P40.43
PARAMETER #2H SCALE
INPUT PARAMETER #2H
PARAMETER #1H SCALE
INPUT PARAMETER #1H
P40.42
P40.40
P40.41
P40.39
SUMMING NODE H MODE P40.47
(+)
P40.49 P40.48 SQROOT OF A SQROOT A INPUT X 10000
P40.51 P40.50 SQROOT OF B SQROOT B INPUT X 10000
P40.77
P40.76 SWITCH A INPUT 1
SWITCH A INPUT 2
FIXEDREF A1 P40.78
FIXEDREF A2 P40.79
140
SWITCH A OUTPUT P40.81
P40.80
SWITCH A STATE
(0.000)
P40.83
P40.82 SWITCH B INPUT 1
SWITCH B INPUT 2
FIXEDREF B1 P40.84
FIXEDREF B2 P40.85
141
SWITCH B OUTPUT P40.87
P40.80
SWITCH B STATE
(0.000)
P40.89
P40.88 SWITCH C INPUT 1
SWITCH C INPUT 2
FIXEDREF C1 P40.90
FIXEDREF C2 P40.91
142
SWITCH C OUTPUT P40.93
P40.92
SWITCH C STATE
(0.000)
P40.95
P40.94 SWITCH DINPUT 1
SWITCH DINPUT 2
FIXEDREF D1 P40.96
FIXEDREF D2 P40.97
143
SWITCH DOUTPUT P40.99
P40.98
SWITCH DSTATE
(0.000)
SQUARE ROOTS
ANALOGUE SWITCHES
MENU 40
MENU 40
MENU 40
MENU 40
MENU 40
Sheet
14
ALSPA MV3000e AEM Drives 5C. Control Block Diagram
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page 5C-17
Comparators, Ramp Function & Brake Logic
Sheet
15
DIGOUT
DIGIN
MONITOR
POINT
xx
STATUS
FLAG
ANALOG
I/O
KEY
CONTROL
FLAG
xx
DEFAULT
CONNECTION
(A)
DEFAULT
SETTING
COMPARATOR
U
P40.55
P40.54
P40.52
P40.53
COMPARATOR U INPUT 1 COMPARATOR U OUTPUT 132
COMPARATOR U INPUT 2
FIXEDREF U
COMPARATOR U HYSTERESIS
COMPARATOR U MODE
COMPARATOR U 0UTPUT
P40.56
P40.57
COMPARATOR
V
P40.61
P40.60
P40.58
P40.59
COMPARATOR V INPUT 1 COMPARATOR V OUTPUT 133
COMPARATOR V INPUT 2
FIXEDREF V
COMPARATOR V HYSTERESIS
COMPARATOR V MODE
COMPARATOR V 0UTPUT
P40.62
P40.63
COMPARATOR
W
P40.67
P40.66
P40.64
P40.65
COMPARATOR W INPUT 1 COMPARATOR W OUTPUT 134
COMPARATOR W INPUT 2
FIXEDREF W
COMPARATOR W HYSTERESIS
COMPARATOR W MODE
COMPARATOR W 0UTPUT
P40.68
P40.69
COMPARATOR
X
P40.73
P40.72
P40.70
P40.71
COMPARATOR X INPUT 1 COMPARATOR X OUTPUT 135
COMPARATOR X INPUT 2
FIXEDREF X
COMPARATOR X HYSTERESIS
COMPARATOR X MODE
COMPARATOR X 0UTPUT
P40.74
P40.75
MENU 40 MENU 40
MENU 40 MENU 40
COMPARATORS
BRAKE LOGIC
RELEASE FAIL TIME P47.90
START RESET TIME P47.89
188
P47.81
(0.000)
TORQUE PROVE THRESHOLD P47.83
189
P47.82
(0.000)
ENABLE BRAKE FUNCTION P47.80
ZERO SPEEDTHRESHOLD P47.84
BRAKE HOLDOFF TIME P47.87
BRAKE RELEASE TIME P47.88
TORQUE PROVE TIME P47.85
RELEASE REF TIMER P47.86
138 LATCHEDRUN
(T222)
137 TORQUE PROVE OK
136 HOLDING TORQUE OK
140 BRAKE RELEASE REQUEST
(T223)
141 AT ZERO SPEED
139 RELEASE REFERENCE
ACTIVE CURRENT
SPEEDFEEDBACK
TORQUE PROVE FAIL
BRAKE RELEASE FAIL
RUN REQUEST
BRAKE RELEASE INPUT
MENU 47
RAMP FUNCTION
P6.20 RAMP OUTPUT
P6.36
134
P6.26
(0.000)
135
P6.27
(0.000)
136
P6.28
(0.000)
137
P6.29
(0.000)
139
P6.30
(0.000)
138
P6.35
(0.000)
INCREASE RATE+VE P6.21
DECREASE RATE +VE P6.22
INCREASE RATE -VE P6.23
DECREASE RATE -VE P6.24
S-SHAPING P6.25
INCREASE RATE 2 +VE P6.31
DECREASE RATE 2 +VE P6.32
INCREASE RATE 2-VE P6.33
DECREASE RATE 2 -VE P6.34
RAMP BYPASS
SELECT RAMP 2
RAMP FREEZE DOWN -VE
RAMP FREEZE DOWN +VE
RAMP FREEZE UP -VE
RAMP FREEZE UP +VE
RAMP INPUT
5C. Control Block Diagram ALSPA MV3000e AEM Drives
ALSPA MV3000e Getting Started Manual for AEM Drives (06/06) Page 5C-18
P24.02
P24.01
SPEED FEEDBACK
SPEEDTRIM SCALE 1
SPEEDTRIM SELECT
SUMMING NODE C 19
SUMMING NODE D
POINTER 7
20
21
FIXED VAL OF 0
POSITION CONTROL
SUMMING NODE A
SUMMING NODE B
HS DIG I/P
17
18
14
15
16
RS485 REF 1 4
MOTORISEDPOT
TRIM REFERENCE
FIXED VAL OF 0
FIXED REF MENU
11
12
13
10
RS232 REF 1
RS232 REF 2
PID CONTROLLER
REF SEQUENCER
RS485 REF 2
6
7
8
9
5
P24.00
75
SPEED TRIM
SCALE SELECT
(0)
SPEED TRIM SCALE 2
P24.04
ANALOG REF1
ANALOG REF2
KEYPADSPEEDREF
2
3
1
SPEEDTRIM SLEW RATE P24.05
(0)
70
ENABLE
SPEED
TRIM
P24.03
13 FIXEDVAL OF 0
%=P9.01
RPM =P9.03
15
16
17
18
14
SUMMING NODE A
SUMMING NODE B
POINTER 14
POINTER 15
FIXEDVAL OF 0
PID CONTROLLER
10
12
8
9
11 MOTORISEDPOT
TRIM REFERENCE
REF SEQUENCER
FIXEDREF MENU
7 RS232 REF 2
1
2 ANALOG REF1
FIXED100%
6
3
4
5
RS232 REF 1
RS485 REF 1
RS485 REF 2
ANALOG REF2
X
TORQUE CURRENT SOURCE
P3.19
MAGNET. CURRENT SOURCE
TORQUE CURRENT SCALE P3.21
P3.18
MAGNET. CURRENT SCALE P3.20
X
MINIMUM FREQUENCY P3.04
FREQUENCY FEEDBACK P9.09
SWITCHING FREQ.
P35.00
CLAMP
(1)
25
OUTPUT
ENABLE/RUN
P4.17
8
DRIVE
O/P RUNNING
PULSE
WIDTH
MODULATION
TORQUE CURRENT REF. P3.23
X = A + B
2 2 P +I
MAGNET. CURRENT REF. P3.22
P9.07
MOTOR VOLTAGE
M
Scalar Control
Sheet
16
SELECTED
SPEED
REFERENCE
X
DIGOUT
DIGIN
MONITOR
POINT
xx
STATUS
FLAG
ANALOG
I/O
KEY
CONTROL
FLAG
xx
DEFAULT
CONNECTION
(A)
DEFAULT
SETTING
ONLY APPLICABLE FOR SCALAR
MOTOR CONTROL, P99.01 =3
ALSPA MV3000e AEM Drives 5C. Control Block Diagram
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page 5C-19
SELECT 110% or 150%
OVERLOAD DUTY
P99.02 (P1.29)
USING "NOT" TRIPPED ENSURES THAT WARNINGS DO NOT AFFECT THE HEALTHY OUTPUT
SUMMING NODES, SWITCHES AND POINTERS SHEET 10
MENU 40 PROGRAMMABLE SUMMING NODES, ALLOWING SCALING AND
SUMMATION OF ANY SFE PARAMETER.
MENU 42 POINTERS. THESE POINTERS ARE ASSOCIATEDWITH MOST
OF THE SFE's REFERENCEC CHOICES, ANDALLOWS THE USER
TO CHOOSE ANY SFE PARAMETER FOR THE REQUIRED USE.
APPLICATION LOGIC, SPECIAL MONITORING FUNCTIONS SHEET 8
STATUS FLAG
BINARY GENERATOR
MENU 31
LOGIC GATES
COMPARATORS
DELAYS
MENU 30
STARTING AND STOPPING SHEET 3
AUTO-RESETTING/STARTING
CONFIGURE THE SFE TO AUTO-RESET/RESTART AFTER A TRIP
CUSTOMER SELECTABLE RESET ENABLES
NUMBER OF RESETS ANDTIMINGS OF RESETS MENU 28
TRIPS/WARNINGS/DIAGNOSTIC MONITORS SHEET 7
HISTORY RECORDING
10 CHANNELS
MONITOR ANY
SFE PARAMETER
TRIGGER SET-UP
PRE ANDPOST TRIG
MANUAL TRIGGER
MENUS 26 and 27
DEFAULT
CONNECTION
DEFAULT
SETTING
TRIPPED
TRIP MONITORING SYSTEM
10PRESENT TRIPS.
10PRESENT WARNINGS.
10TRIP HISTORY STORAGE.
USER CONFIGURABLE TRIPS.
MENU 10
TRIP
RESET
CONTROL
FLAG
STATUS
FLAG
xx DIGOUT
DIGIN xx
(A)
MONITOR
POINT
ANALOG
I/O
KEY
KEYPAD/
REMOTE
DIGIN 6
TRIP
RESET
DIGIN 4
START
DIGIN 2
STOP
DIGIN 1
KEYPAD
START/STOP
9 5
116
KEYPAD/REMOTE
REMOTE
START/STOP
FLAGS
MENU 50
START
0
1
NORMAL
STOP
MENU 99 SECURITY CODES,
PARAMETER BACKUP
AND SYSTEM
CONFIGURATIONS
MENU 35 KEYPAD REMOVAL,
PARAMETER PRINTING
AND PARAMETER "LOCKING"
OTHER USEFUL MENUS
MONITORING
EXTENSIVE
SYSTEM
MONITORS
TO AID
VIEWING
AND
DIAGNOSTICS
MENU 11 &51
PLANT INTERLOCK (IF THIS INPUT IS OPEN, THE SFE WILL TRIP)
SFE VECTOR CONTROL, PART 1 SHEET SFE-3
DC LINK
VOLTAGE
CONTROL
MENUS 50, 52
4 - 20mA @ DEFAULT
ANALOG
REF 2
ANALOG
REF 1
+/- 10V @ DEFAULT
REFERENCE
SOURCE
SELECTION
MENU 53
FOR PLANT I/O SEE MENU 7, SHEET 2
INTERLOCK
RUN
PERMIT
DIGIN 3
OUTPUT
ENABLE/RUN
SFE MONITORING MENUS MENUS 11, 45 and 51
MENU 45 SFE TEMPERATURES
MENU 11 MONITORING OF SFE VARIABLES, INCLUDING
TEMPERATURES, CONTROL AND STATUS FLAGS
HOURS RUN, DIGITAL I/O STATES,
ANALOGUE INPUT AND OUTPUT VALUES ANDOTHERS.
MENU 51 SFE VOLTS, CURRENTS, POWER FEEDBACKS
ANALOG
O/P 1
ANALOG
O/P 2
(MENU 7)
(MENU 7)
DIGOUT 3
DIGOUT 2
+/- 10V @ DEFAULT
+/- 10V @ DEFAULT
V dc AT REF
(MENU 7)
SFE RUNNING
(MENU 7)
DIGOUT 1
(MENU 7)
HEALTHY
VECTOR CONTROL, PART 2 SHEET SFE-4
CURRENT
CONTROL
MENU 52
MAINS
MONITORING
MENU 52
OPTIONAL
DYNAMIC
BRAKE
MENU 23
25
DC LINK VOLTS
SHEET 7
P11.03, P51.00
Sheet
17
SFE Control System Overview
100
V dc AT REF
REACTIVE
CURRENT
REFERENCE
LOAD
POWER
FEEDFORWARD
MENU 52
MENU 52
START AND STOP SFE
8
LCN
MAINS
DC LINK
HARDWARE
BRIDGE
INTERLOCK
+
PRECHARGE
CIRCUIT
47
PRECHARGE
COMPLETE
SELECT STANDARD
OR ALTERNATE
AC VOLTAGE GRADE
P99.11 (P1.28)
MAINS BRIDGE
SFE RUNNING
R/U
S/V
T/W
AuxR
AuxS
AuxT
BI-DIRECTIONAL
CONVERTER
ANCILLARY COMPONENTS
TB7
EDIT PARAMETERS
THESE PARAMETERS MAY
BE ENTERED BY KEYPAD.
THIS DOES NOT MAKE THE
KEYPAD A "REFERENCE
SOURCE", SO KEYPAD
REMOVAL WILL BE
ALLOWED.
MAINS
VOLTAGE
MONITOR
(BDM ONLY)
*
*
DELTA SYSTEM USES SEPARATE
MAINS VOLTAGE MONITOR
5C. Control Block Diagram ALSPA MV3000e AEM Drives
ALSPA MV3000e Getting Started Manual for AEM Drives (06/06) Page 5C-20
Sheet
18
SFE Vector Control, Part 1
ONLY APPLICABLE FOR SFE MODE, P99.01 =4
9
10
11
12
13
14
15
16
17
18
19
2
3
4
5
6
7
8
1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
ANALOG REF1
P50.00
ANALOG REF2
RS485 REF1
RS485 REF2
RS232 REF1
RS232 REF2
PIDCONTROLLER
REF SEQUENCER
FIXED REF MENU
MOTORISEDPOT
TRIMREFERENCE
FIXED VAL OF 0
FIXED VAL OF 0
SUMMING NODE A
SUMMING NODE B
SUMMING NODE C
SUMMING NODE D
POINTER 21
Vdc REF
SOURCE
X
Vdc REF
SCALE
P53.00
CLAMP
P53.01
Vdc AT REF
100
DC LINK
VOLTAGE
PI CONTROL
ANALOG REF1
VDC CONTROLLER
ANALOG REF2
RS485REF1
RS485REF2
RS232REF 1
RS232REF 2
PID CONTROLLER
REF SEQUENCER
FIXEDREF MENU
MOTORISED POT
TRIMREFERENCE
FIXEDVAL OF 0
FIXEDVAL OF 0
SUMMING NODE A
SUMMING NODE B
POINTER 22
ANALOG REF1
P50.03
ANALOG REF2
RS485REF1
RS485REF2
RS232REF1
RS232REF2
PID CONTROLLER
REF SEQUENCER
FIXEDREF MENU
MOTORISED POT
TRIMREFERENCE
FIXEDVAL OF 0
FIXEDVAL OF 0
SUMMING NODE A
SUMMING NODE B
POINTER 24
ANALOG REF1
P50.04
ANALOG REF2
RS485REF1
RS485REF2
RS232REF1
RS232REF2
PID CONTROLLER
REF SEQUENCER
FIXEDREF MENU
MOTORISED POT
TRIMREFERENCE
FIXEDVAL OF 0
FIXEDVAL OF 0
SUMMING NODE A
SUMMING NODE B
POINTER 23
X
ACTIVE
CURRENT
POSITIVE
LIMIT
SOURCE
P53.06
ACTIVE
CURRENT
POSITIVE
LIMIT SCALE
P53.07
X
ACTIVE
CURRENT
DEMAND
SOURCE
P53.04
ACTIVE
CURRENT
DEMAND
SCALE
P53.05
X
ACTIVE
CURRENT
NEGATIVE
LIMIT
SOURCE
P53.08
ACTIVE
CURRENT
NEGATIVE
LIMIT SCALE
P53.09
ACTIVE
CURRENT
POSITIVE LIMIT
CLAMP
ACTIVE
CURRENT
DEMAND
P50.03
ACTIVE
CURRENT
NEGATIVE
LIMIT
P50.04
X -1
ACTIVE CURRENT
DEMAND
P51.11
P51.12
DC LINK
CONTROLLER
CURRENT
DEMAND
P51.09
Vdc Ki
Vdc
Kp
Vdc
P51.00
P11.03
DC LINK
CONTROLLER
GAIN
AUTO
CALCULATION
DISABLE AUTO
CALCULATION
OF GAINS
P52.01
DC LINK
CONTROL
BANDWIDTH
LOAD
CONVERTER
RATING
Vdc REF P50.00
P52.00
P50.02
DC LINK
LOADPOWER FEEDFORWARD
FEEDFORWARDCURRENT
DEMAND
P51.10
FEEDFORWARD POWER
DEMAND
P51.07 ANALOG I/P REF 2
TB6/8,7
LOAD POWER SIGNAL
SOURCE ANDMODE
CURRENT SENSOR
TURNS RATIO
CURRENT SENSOR
BURDEN RESISTOR
P52.15
P53.03
P52.16
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
ANALOG REF 1
P52.05
ANALOG REF 2
RS485 REF 1
RS485 REF 2
RS232 REF 1
RS232 REF 2
PIDCONTROLLER
REF SEQUENCER
FIXEDREF MENU
MOTORISED POT
TRIMREFERENCE
FIXED VAL OF 0
FIXED VAL OF 0
SUMMING NODE A
SUMMING NODE B
POINTER 25
X
REACTIVE
CURRENT
REFERENCE
SOURCE
P53.10
REACTIVE
CURRENT
REFERENCE
SCALE
P53.11
REACTIVE
CURRENT
REFERENCE
P52.05
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
ANALOG REF1
P52.06
ANALOG REF2
RS485REF1
RS485REF2
RS232 REF 1
RS232REF2
PIDCONTROLLER
REF SEQUENCER
FIXEDREF MENU
MOTORISED POT
TRIMREFERENCE
FIXED VALUE OF 0
FIXED VALUE OF 0
SUMMING NODE A
SUMMING NODE B
POINTER 26
X
REACTIVE
CURRENT
POSITIVE
LIMIT
SOURCE
P53.12
REACTIVE
CURRENT
POSITIVE
LIMIT SCALE
P53.13
REACTIVE
CURRENT
POSITIVE
LIMIT
CLAMP
103
104
REACTIVE CURRENT
REF. IN POSITIVE LIMIT
REACTIVE CURRENT
DEMAND
REACTIVE CURRENT REF.
IN NEGATIVE LIMIT
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
ANALOG REF1
P52.07
ANALOG REF2
RS485 REF1
RS485 REF2
RS232 REF1
RS232 REF2
PID CONTROLLER
REF SEQUENCER
FIXED REF MENU
MOTORISEDPOT
TRIMREFERENCE
FIXEDVALUE OF 0
FIXEDVALUE OF 0
SUMMING NODE A
SUMMING NODE B
POINTER 27
X
REACTIVE
CURRENT
NEGATIVE
LIMIT
SOURCE
P53.14
REACTIVE
CURRENT
NEGATIVE
LIMIT SCALE
P53.15
X
-1
REACTIVE
CURRENT
NEGATIVE
LIMIT
P52.07
REACTIVE
CURRENT
DEMAND
P51.15
P51.16
P52.06
ANALOG I/P REF 1
TB6/6,5
KEY
DIGOUT 12
CONTROL
FLAG
ANALOG
I/O
23 DIGIN
STATUS
FLAG
MONITOR
POINT
<A>
DEFAULT
SETTING
DEFAULT
CONNECTION
P52.02 P52.03
TO SHEET SFE-4
TO SHEET SFE-4
101
102
ACTIVE CURRENT DEMAND
IN POSITIVE LIMIT
ACTIVE CURRENT DEMAND
IN NEGATIVE LIMIT
106
SFE REF LOSS
P52.46 18
P52.54 18
ALSPA MV3000e AEM Drives 5C. Control Block Diagram
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page 5C-21
P50.01
P52.13
P35.00
P51.06
P51.01, P51.02
P51.13, P51.14
X
SFE CURRENT CONTROLLER
ACTIVE CURRENT
REACTIVE CURRENT
P51.17, P51.18
P51.08 ESTIMATED DC LINK CURRENT
MAINS CURRENT
MAINS POWER
P52.04
CURRENT CONTROLLER BANDWIDTH
CHOKE INDUCTANCE
SUPPLY INDUCTANCE
PULSE WIDTH
MODULATION
LINE REACTOR
MAINS
MAINS VOLTAGE
MONITORING
X P52.14 MAINS VOLTS SCALING
MAINS SYNC OFFSET
MAINS FREQUENCY
MAINS UNDERFREQ WARNING
MAINS OVERFREQ WARNING
MAINS UNDERFREQ TRIP
MAINS OVERFREQ TRIP
TRIP 93
WARNING 133
P52.12
P51.03
P52.09
P52.10
P52.08
P52.11
MAINS ANGLE
PWMFREQUENCY
PWMVOLTAGE
P51.05
8 RUNNING
MAINS ANGLE
Sheet
19
SFE Vector Control, Part 2
DIGOUT
DIGIN
MONITOR
POINT
xx
STATUS
FLAG
ANALOG
I/O
KEY
CONTROL
FLAG
xx
DEFAULT
CONNECTION
(A)
DEFAULT
SETTING
ACTIVE CURRENT
DEMAND
REACTIVE CURRENT
DEMAND
FROM SHEET SFE-3
FROM SHEET SFE-3
105 MAINS SYNC VALID
ONLY APPLICABLE FOR SFE MODE, P99.01 =4
Note: Negative frequency
indicates negative phase
rotation detected.
P54.06
FREQUENCY METHOD
MAINS FILTER BANDWIDTH
NOMINAL MAINS SUPPLY VOLTAGE
P54.13
P54.01
P54.17
P50.09
TRIP 94
WARNING 134
ACTION ON MAINS LOSS
P53.19
P54.14
MAINS AMPLITUDE
VqMAINS
VdMAINS
Vrms MAINS
P54.03
P54.04
P54.05
P51.04
P54.16
P51.23
WARNING 142
TRIP 210
MAINS UNDERFREQ TRIP
P52.08
MAINS UNDERFREQ TRIP P52.08
MAINS UNDERFREQ TRIP
P52.08
5C. Control Block Diagram ALSPA MV3000e AEM Drives
ALSPA MV3000e Getting Started Manual for AEM Drives (06/06) Page 5C-22
This page intentionally left blank
ALSPA MV3000e AEM Drives 6. Preventive Maintenance
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page 6-1
6. Preventive Maintenance
6.1 Tools and Equipment Required
Torque wrench, of a size suitable for the converter power terminals. The torque range
required is drive size dependent and is shown in Table 3-2, page 3-10.
Terminal screwdriver, suitable for control connectors.
Flat blade screwdriver, suitable for opening the power door (RH door).
Star-head screwdriver, suitable for removing upper and lower fingerguards.
CLIP ON Ammeter to measure 1- 20 Amp AC.
6.2 Maintenance Schedules
Access
1. Switch off the equipment and isolate it from the electrical supply.
2. Gain access to the equipment.
Monthly
1. Ensure all ventilation louvres are unobstructed. They are located at the top and bottom
of the converter, and on the PWM filter.
2. Examine auxiliary and power terminals for signs of overheating (damaged insulation
and discolouration).
3. Check security of mounting bolts.
4. Check the currents in each PWM filter connection from R5, S5 and T5 (see page iii).
The lowest value measured should not be less than 80% of the largest value
measured. If there is a greater discrepancy, change the filter. Note that the nominal
value for any specific filter should be between 1 and 20 Amp.
Annual
1. Carry out the Monthly schedule as above.
2. Check all power and control terminations are secure, refer to Table 3-2 for torque
settings of power terminations.
3. Remove accumulated dust from the equipment, using a suction cleaner with a
soft nozzle.
Note: Periodic checking of the converter bridge temperature (P11.05) can show when cleaning is
required, indicated by a temperature rise.
WARNING
Wait at least 5 minutes after isolating supplies and check that voltage between DC+ and
DC- has reduced to a safe level before working on this equipment.
This equipment may be connected to more than one live circuit. Disconnect all supplies
before working on the equipment.
6. Preventive Maintenance ALSPA MV3000e AEM Drives
Page 6-2 ALSPA MV3000e Getting Started Manual for AEM Drives (06/06)
This page intentionally left blank
ALSPA MV3000e AEM Drives 7. Diagnostics
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page 7-1
7. Diagnostics
7.1 LED Indicators
The four LED indicators on the keypad are repeated on the keypad harbour and give a first
indication of converter status. The keypad harbour indicators are shown in Section 4.3 and the
keypad indicators are shown on the back cover of this manual.
7.1.1 Fault Indication
A fault condition is indicated by illumination of the WARNING or flashing TRIPPED indicator and
extinguishing of the HEALTHY/STANDBY indicator.
If the WARNING indicator is lit a problem has occurred which is not sufficiently serious to trip the
converter. A warning code is stored in one of 10 locations in the Warning Record, parameters
P10.00 to P10.09, the code stored in P10.00 being for the most recent warning.
7.2 Warnings
Note: Warnings are not latched and if the warning condition ceases, the WARNING indicator will
extinguish. (At default configuration, Warning 1 is located at P1.06).
Some of the more common codes for WARNINGS are listed on the inside of the back cover.
7.3 Trips
If the TRIPPED indicator is flashing, a serious fault has occurred which has caused the converter
to shut down. Each time a trip occurs a Fault is stored in one of ten locations in the Active Trip
record, parameters P10.10 to P10.19, the fault stored in P10.10 being for the most recent trip.
Note: Trips are latched and must be reset before the converter can be operated again.
7.4 Viewing Warnings and Trips
Parameters in the converter report the trip or warning currently present, and other parameters
hold a history of the last 10 trips. These parameters display codes and text which describe
particular warnings or trips, the Keypad automatically displays these text messages. Menu 10 is
dedicated to trips and warnings, but at default Menu 1 also has some of these parameters
collected together for easy access.
Available parameters in Menu 01 Available parameters in Menu 10
P1.06 =FIRST WARNING P10.00 - P10.09 =WARNINGS 1 to 10
P1.07 - P1.08 =FIRST 2 TRIPS P10.10 - P10.19 =CURRENT TRIPS 1 to 10
P10.20 - P10.29 =TRIP HISTORY 1 to 10
Viewing using navigation keys
Navigate to one of the above parameters, either a Trip or a Warning.
Viewing using " help" key
1. When the converter is showing either a Trip or Warning, press ? .
2. The keypad will display a menu, depending on the state of the converter, e.g. the Warning
option will not show if there is no Warning present.
7. Diagnostics ALSPA MV3000e AEM Drives
Page 7-2 ALSPA MV3000e Getting Started Manual for AEM Drives (06/06)
7.4.1 Action in the Event of a Warning
1. Press ? and select "2" Display Warnings.
2. Display P10.00 and note the first warning. This is the problem which is causing the warning
indication.
3. In turn, Display P10.01 to P10.09 and note any additional warnings. Any warnings in these
locations will be for secondary problems and will help with diagnosis.
4. Refer to the back cover and check the meaning of each warning. Take corrective action as
necessary.
7.4.2 Action in the event of a Trip
1. Press ? and select "2" Display Trips.
2. Display P10.10 and note the most recent trip. This is the problem which has caused the trip
indication. (For the default configuration, Trips 1/2 are located at P1.07/P1.08).
3. In turn, Display P10.11 to P10.19 and record any additional trips which may be present.
4. Refer to the table inside the back cover and check the meaning of each fault. Take
corrective action as necessary.
5. See Section 7.4.3 for resetting trips.
7.4.3 Resetting Trips
From the Digital Inputs
From Default, press and release the button wired to DIGIN 6.
Note: CF9 (the Reset flag) may have been re-programmed, but at Default it is connected to DIGIN 6.
From the Keypad
Press ? and select option 3 (Attempt Trip Reset).
7.4.4 Trip Fault Codes
Some of the more common Trip fault codes for the SFE and the machine bridge are listed inside
the back cover. A full listing and description is given in the Software Technical Manual T1679.
7.5 Using the HELP Key
If the converter trips, get information on the trip by pressing ? .
A screen appears, giving four choices as shown below:
ALSPA MV3000e AEM Drives 7. Diagnostics
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page 7-3
1. PARAMETER HELP
2. DISPLAY TRIPS
RESET ATTEMPT FAIL
(Trip still present)
3. ATTEMPT RESET
P10.10
(Information about the
most recent trip.)
4. BACK TO PARAMETER
PX.XX
Continue with help on
selected parameter.
See Section 4.4 for
examples.
RETURN WITH NO
FURTHER HELP.
PX.XX
xxxxxx xx xxxx x
=xx xxx
Figure 7-1 Help screen for trips
PRESS
1 If the keypad was connected when the converter tripped, this shows the last screen
displayed before the trip.
2 Displays parameter P10.10 gives information about the trip.
3 Attempts to reset the trip. If the attempt fails, this screen re-appears.
4 If the converter tripped while displaying a parameter, the screen will re-display the
parameter.
If the converter shows a Warning, get information on the warning by pressing ? .
The HELP system works as described for trips, except that P10.00 displays the most recent
Warning, as in Figure 7-2 below:
1. PARAMETER
2. DISPLAY WARNS
3. BACK TO PARAMETER
P10.00
(INFORMATION ABOUT
THE MOST RECENT
WARNING)
Figure 7-2 Help screen for warnings
7.6 Diagnostic Hints
1. There is a list of helpful hints recorded on the inside of the back cover of this manual.
2. Use Sections 7.4 and 7.5 to find out what the problem is. The trip or warning messages
give a clue to the problem, and the lists of trip and warning codes inside the back cover of
this manual will also help.
3. Examine the trip or warning history as shown in Section 7.4.
7. Diagnostics ALSPA MV3000e AEM Drives
Page 7-4 ALSPA MV3000e Getting Started Manual for AEM Drives (06/06)
7.6.1 Changing Pcb's
Before changing pcb's refer to the precautions given in Section 8.2.
7.6.2 Failure of Converter Firmware
Should a fault develop in the converter firmware, normal software operation will stop. If a keypad
is plugged in it will display:
FIRMWARE INTEGRITY
FAILURE
(E000)
SEE USER MANUAL
To assist Converteam personnel in diagnosing the cause of the software malfuncion, the memory
contents of the converter can be uploaded to a PC as shown in Section 7.6.3 and sent to
Converteam at the address shown at the end of this manual.
7.6.3 Uploading the Converter Memory Contents to a PC
7.6.3.1 Using Windows 3.1 or 3.11 Terminal Emulation
1. Start Windows Terminal.
2. From Settings, choose Communications.
3. In the dialogue box, change the baud rate to 9600, change the flow control to Xon/Xoff.
Leave the other settings at default values (8 data, 1 stop, no parity).
4. Choose an available Comm port.
5. Check that in Settings, Emulation is at default (=VT-100 [ANSI]).
6. From Transfers, choose Receive text file.
7. Name the file.
8. Ensure the MV3000e RS232 port is connected to the PC, via the RS232 lead. The keypad
lead can be used but the programming lead GDS1009-4001 (see Section 8) has a
connector more suited for connection to a PC serial port.
9. Press capital G to start the memory contents upload. The upload takes about 10 minutes.
10. When the upload is complete press Stop to terminate. This saves the file.
11. Press the "." key to re-start the MV3000e firmware.
12. See Section 7.6.2 for mailing instructions.
The Terminal connection can be saved as "MV3000e" for next time.
7.6.3.2 Using Windows 95 or NT4
1. Start Windows Hyper Terminal.
2. Follow the " wizard" as presented.
ALSPA MV3000e AEM Drives 7. Diagnostics
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page 7-5
3. Name the new connection "MV3000e" and choose an icon.
4. Choose an available Comm port.
5. Set communications parameters to 9600 baud, no parity, 1 stop, Xon/Xoff flow control.
6. Select File - Properties. From the dialogue box choose the Settings tab. Set the emulation
to VT100.
7. Ensure the MV3000e RS232 port is connected to the PC, via the RS232 lead. The keypad
lead can be used but the programming lead GDS1009-4001 (see Section 8) has a
connector more suited for connection to a PC serial port.
8. From Transfer, choose Capture text.
9. Name the file.
10. Press capital G to start the memory contents upload. The upload takes about 10 minutes.
11. When the upload is complete press Stop to terminate. This saves the file.
12. Press the "." key to re-start the MV3000e firmware.
13. See Section 7.6.2 for mailing instructions.
The Terminal connection can be saved as "MV3000e" for next time.
7. Diagnostics ALSPA MV3000e AEM Drives
Page 7-6 ALSPA MV3000e Getting Started Manual for AEM Drives (06/06)
This page is intentionally left blank
ALSPA MV3000e AEM Drives 8. Spare Parts
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page 8-1
8. Spare Parts
The pre-charge fuses may be obtained from any source, including Converteam. All other
spares, as listed in Table 8-2, must be obtained only from Converteam.
8.1 Pre-charge Fuses
Data for pre-charge fuses is shown in Table 8-1. The data is given here in addition to the part
numbers shown in Section 8.2 to allow local purchase of fuses, which may be helpful during
commissioning. Replacing these fuses with any other rating or type will invalidate safety
approvals.
Table 8-1 Pre-charge fuse data
Frame size Fuse rating
A
Fuse type
(Qty. 3)
3 4 Littelfuse KLKD 4
4 4 Littelfuse KLKD 4
6 6 Littelfuse KLKD 6
7 6 Littelfuse KLKD 6
8.1.1 Replacing Pre-charge Fuses
1. Switch off the converter and isolate all supplies.
2. Gain access to the converter interior as described in Section 3.10.
Procedure for frame sizes 3 and 4
(See Figure 8-1, size 3 shown)
1. Locate the pre-charge fuses mounted on a printed circuit board behind the keypad
harbour. Remove the fuses, taking care that they do not fall inside the converter.
2. Fit replacement fuses of the correct type and rating, (see Table 8-1), close and secure
the keypad harbour, then close the converter doors.
WARNING
Wait at least 5 minutes after isolating supplies and check that voltage between DC+
and DC- has reduced to a safe level before working on this equipment.
This equipment may be connected to more than one live circuit. Disconnect all
supplies before working on the equipment.
8. Spare Parts ALSPA MV3000e AEM Drives
Page 8-2 ALSPA MV3000e Getting Started Manual for AEM Drives (06/06)
Procedure for frame sizes 6 and 7
(See Figure 8-2, size 7 shown)
Figure 8-2 Frame size 6 and 7 pre-charge fuse access
The pre-charge fuses are mounted on a printed circuit board (pcb) behind the pre-charge fuse
cover plate, see Figure 8-2. The transparent plastic shroud protecting the fan terminal block is
attached to the chassis at (X) and to the cover plate.
Figure 8-1 Frame size 3 and 4 pre-charge fuse access
Power Cables
X Z
Z
Y
Pre-charge
fuse cover
plate
Transparent
plastic shroud
removed for
clarity
Pre-charge
fuses
ALSPA MV3000e AEM Drives 8. Spare Parts
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page 8-3
Replace the pre-charge fuses as follows:
1. On frame size 6 converters, remove the two M5 screws (Z) securing the cover plate and
remove the plate, complete with attached plastic shroud.
On frame size 7 converters, release the retained screw (X) securing the plastic shroud
to the chassis, then rotate the shroud upward and clip it behind the metal dowel on the
cover plate. Remove the six M5 screws (Y and Z) (four on some models) securing the
cover plate and remove the plate, complete with attached plastic shroud.
2. Locate the three pre-charge fuses mounted on the printed circuit board (pcb), exposed
when the cover plate is removed. The pcb is similar to that shown for frame size 3 in
Figure 8-1.
3. Remove the three fuses, taking care that they do not fall inside the converter.
4. Fit replacement fuses of the correct type and rating (see Table 8-1).
5. On frame size 6 converters, re-fit the cover plate to the converter chassis and secure
with the two M5 screws (Z).
On frame size 7 converters, use four M5 screws (Y) to fit the pre-charge fuse cover
plate to the pcb mounting metalwork, then use two M5 screws (Z) to secure the plate to
the converter chassis. Secure the shroud to the chassis with the retained screw (X).
6. Close the converter doors.
8.2 Spare Parts Listing
The parts listed in Table 8-2 are available as spares from your local authorised Converteam
dealer.
All spare parts are supplied with documentation explaining the procedure for replacement.
Never remove a pcb from the converter unless carrying out the replacement procedures
supplied with the spare pcb.
Never remove the switch mode power supply (SMPS) and the control board pcb from a
converter at the same time.
The SMPS and the control board have the same identity parameters contained in EEPROM
and must be used as a matched pair. If one pcb is replaced with a spare unprogrammed pcb,
the remaining pcb will copy the converter identity parameters into the new pcb. If both pcbs
are removed, the converter identity will be lost and it will be rendered useless.
Never swap pcbs between converters, not even between apparently identical converter.
Even if the Combination Number of pcbs is identical, the identity parameters
programmed into EEPROM will be different.
Swapping pcbs between converters would move the programmed converter identity between
converters which may have other components with different build standards. This can affect
scaling factors etc.and prevent correct operation.
If pcbs are swapped between converters of different ratings, serious damage is likely to occur.
8. Spare Parts ALSPA MV3000e AEM Drives
Page 8-4 ALSPA MV3000e Getting Started Manual for AEM Drives (06/06)
Table 8-2 Spares listing for ALSPA MV3000 bi-directional converters
MicroCubicle
F
r
a
m
e
Control
Module
Fan
Frame Size 3
& 4 Mains
Voltage
Monitor And
Precharge
Unit
Frame Size 6
& 7 Transistor
- Transistor
Module
Frame Size 6
& 7 Transistor/
Precharge
Module
SMPS (Switch
Mode Power
Suppl y)
Precharge
Fuses
(Qty. 3)
400 V/480 V
MV3071J 5A1 3 S41Y7784/40 S41Y7786/10 S41Y8152/10 S20X4320/20 S82030/370
MV3140J 5A1 4 S41Y7784/40 S98101/153 S41Y8007/70 S20X4320/20 S82030/370
MV3364J 5A1 6 S41Y7784/40 SMV98101/151 S41Y7770/50 S41Y8162/10 S20X4321/30 S82030/372
MV3566J 5A1 7 S41Y7784/40 SMV98101/151 S41Y8081/90 S41Y8169/10 S20X4321/30 S82030/372
600/690 V
MV3099J 6A1 4 S41Y7784/ 40 S98101/ 153 S41Y8007/ 80 S20X4321/ 10 S82030/ 370
MV3242J 6A1 6 S41Y7784/ 40 SMV98101/ 151 S41Y8036/ 10 S41Y8162/ 20 S20X4321/ 10 S82030/372
MV3382J 6A1 7 S41Y7784/ 40 SMV98101/ 151 S41Y8081/ 100 S41Y8169/ 20 S20X4321/ 10 S82030/372
ALSPA MV3000e AEM Drives 9. Options
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page 9-1
9. Options
9.1 Optional Hardware
The following options are available for the complete ALSPA MV3000e range of
MicroCubicle bi-directional converters.
Additional options are being added to the converter range as part of the ongoing development
process. Please contact your authorised Converteam dealer for the latest list of options.
Item Part No. Description
ALSPA MV3000e Drive Data
Manager
MVS3000-4001 A multi-function unit with keypad functionality that can be
used to edit and monitor converter parameters, extract
warnings and trip reports, and provide parameter specific
help. The keypad has a large, easy to read, backlit display
and can be mounted to the converter, held in the hand or
permanently mounted on any suitable surface. The keypad
incorporates special keys to start and stop active control of a
DC voltage (SFE), or to start and stop a motor, and to
control its speed (machine bridge).
ALSPA MV3000e Drive Data
Manager Lead and Door
Mounting Kit
MVS3001-4001 A keypad-to-converter interconnection cable, mounting
gasket and drilling template to allow the keypad to be
mounted on a flat surface, e.g. the cabinet door.
ALSPA Drive Coach
PC Programming Lead
MVS3004-4001
GDS1009-4001
A software program that enables uploading of parameters to
a PC and downloading of parameters to a converter, with full
monitoring facilities and on-line help. The software is
supplied on CD-ROM and runs under Microsoft Windows
3.1, 95, 98 or NT.
Connects a PC serial port to the converter RS232 port.
Dynamic Brakes
MV3071J 5A1
MV3140J 5A1
MV3099J 6A1
MV3364J 5A1
MV3242J 6A1
MV3566J 5A1
MV3382J 6A1
MV3DB045S5
MV3DB092S5
MV3DB061S6
MV3DB247S5
MV3DB185S6
MV3DB391S5
MV3DB246S6
A range of dynamic brake switch modules, fitted within the
machine bridge and rated to suit most applications, allowing
a motor load to be decelerated at the required rate. A range
of compatible resistors is also available. Full fixing kit
supplied.
Drip Proof Canopies (Hood)
MV3071J 5A1; MV3071J 6A1
MV3140J 5A1; MV3099J 6A1
MV3364J 5A1; MV3242J 6A1
MV3566J 5A1; MV3382J 6A1
MVS3003-4003
MVS3003-4004
MVS3003-4006
MVS3003-4007
A cover to prevent foreign bodies and water from
accidentally dropping into the converter from above.
ALSPA MV3000e Ethernet
Interface Single Channel.
ALSPA MV3000e Ethernet
Interface Dual Channel.
MVS3012-4001
MVS3012-4002
A self-contained module that fits within the converter to
provide connectivity to 10 MHz or 100 MHz Ethernet
communications networks. Full fixing kit supplied.
ALSPA MV3000e Profibus Field
Bus Coupler.
Baud rates :
187.5 kbits/s
500 kbits/s
1.5 Mbits/s
12 Mbits/s
MVS3007-4002 A self-contained module that fits within the converter to
provide communications over a PROFIBUS-DP network.
Full fixing kit supplied.
(continued)
9. Options ALSPA MV3000e AEM Drives
Page 9-2 ALSPA MV3000e Getting Started Manual for AEM Drives (06/06)
Item Part No. Description
EMC Filter
MV3071J 5A1
MV3140J 5A1
MV3099J 6A1
MV3364J 5A1
MV3242J 6A1
MV3566J 5A1
MV3382J 6A1
MV3FLT180A5A1
MV3FLT180A5A1
MV3FLT150A6X1
MV3FLT400A5X1
MV3FLT250A6X1
MV3FLT600A5X1
MV3FLT400A6X1
A range of EMC Filters that together with EMC Ferrites (see
below) will assist the inverter installation to meet EMC
requirements. These generally apply when operating in non-
industrial environments or when the inverter is installed in
the proximity of sensitive equipment.
Assuming that provision has already been made for fitting
the PWM filter and associated Input Line Reactors then one
EMC Filter plus one motor cable Ferrite Ring will be required
to meet EMC emission requirements.
EMC Ferrite
MV3071J 5A1
MV3140J 5A1
MV3099J 6A1
MV3364J 5A1
MV3242J 6A1
MV3566J 5A1
MV3382J 6A1
MV3FLT140B6A1
MV3FLT140B6A1
MV3FLT140B6A1
MV3FLT566B6A1
MV3FLT566B6A1
MV3FLT566B6A1
MV3FLT566B6A1
A range of EMC Ferrites that together with EMC Filters (see
above) will assist the inverter installation to meet EMC
requirements. These generally apply when operating in non-
industrial environments or when the inverter is installed in
the proximity of sensitive equipment.
Assuming that provision has already been made for fitting
the PWM filter and associated Input Line Reactors then one
EMC Filter plus one motor cable Ferrite Ring will be required
to meet EMC emission requirements.
ALSPA MV3000e MicroPEC
Applications Processor
MVS3009-4001 A self-contained add-on module that fits onto the control
board (CDC or DELTA) to add Function Block
Programmability to the ALSPA MV3000e drive.
ALSPA MV3000e CAN Port 2
Fieldbus Module
MVS3011-4001 A self contained add-on module that fits onto the control
board (CDC or DELTA) to give a second DeviceNet or
CANopen Fieldbus connection. This allows a drive whose in-
built CAN port is already used for CANopen to have a
DeviceNet connection and vice versa. Alternatively the
module can be used to provide either a second DeviceNet or
CANopen connection.
9.2 Optional Manuals
Details of manuals which may be obtained from Converteam as options are given in Section
1.9.
ALSPA MV3000e AEM Drives 10. Disposal
(06/06) ALSPA MV3000e Getting Started Manual for AEM Drives Page 10-1
10. Disposal
This equipment or any part of the equipment should be disposed of in accordance with the
laws of the country of use.
Modern high technology materials have been used in the manufacture of the equipment to
ensure optimum performance. Care has been taken with the selection of these materials to
minimise risks to health and safety. However, some materials require special consideration
during disposal.
In common with all products of this type, the DC link electrolytic capacitors in the drive contain
an electrolyte which must be disposed of as hazardous waste. The electrolytes are solutions
of organic and/or boric acid. The major solvents in the capacitors are butyrolactone and
ethylene glycol.
The capacitors used in the PWM filters contain a non-toxic mineral oil that has a flash point of
140 C (284 F). Do not incinerate these capacitors. This mineral oil is also an environmental
pollutant and due care should be taken when disposing of the capacitors.
Liquid coolant is subject to special considerations during handling, storage and disposal.
Refer to the manufacturers instructions.
10. Disposal ALSPA MV3000e AEM Drives
Page 10-2 ALSPA MV3000e Getting Started Manual for AEM Drives (06/06)
This page intentionally left blank
Converteam
France
9, rue Ampre
91345 Massy Cedex
Sales Tel: +33 (0) 8 25 02 11 02
Support Tel (International):
+33 (0) 3 84 55 33 33
Support Tel. (National):
08 25 02 11 02
Germany
Culemeyerstrae 1
D-12277 Berlin
Sales Tel: +49 (0) 30 74 96 27 27
Support Tel (International):
+49 (0) 69 66 99 831
Support Tel (National):
01 80 3 23 45 72
UK
West Avenue, Kidsgrove, Stoke-on-Trent
Staffordshire, ST7 1TW
Tel: +44 (0) 1782 1010
Fax: +44 (0) 1782 1133
USA
610 Epsilon Drive
Pittsburgh, PA 15238
Sales Tel: +1 412 967 0765
Support Tel: +1 800 800 5290
C
o
n
v
e
r
t
e
a
m
U
K
L
t
d
2
0
0
6
P
u
b
l
i
c
a
t
i
o
n
N
o
.
T
2
0
0
2
E
N
T
h
e
l
o
g
o
C
o
n
v
e
r
t
e
a
m
a
n
d
t
h
e
i
r
f
r
a
m
e
w
o
r
k
s
a
r
e
t
r
a
d
e
m
a
r
k
s
a
n
d
s
e
r
v
i
c
e
t
r
a
d
e
m
a
r
k
a
p
p
l
i
c
a
t
i
o
n
s
o
f
C
o
n
v
e
r
t
e
a
m
.
O
t
h
e
r
n
a
m
e
s
m
e
n
t
i
o
n
e
d
,
r
e
g
i
s
t
e
r
e
d
o
r
n
o
t
,
a
r
e
t
h
e
p
r
o
p
e
r
t
y
o
f
t
h
e
i
r
r
e
s
p
e
c
t
i
v
e
c
o
m
p
a
n
i
e
s
.
Note: These hints are aimed mainly at the DEFAULT SFE, to help with problems which may be experienced while
working wih this manual. Reference is made to the default input/output diagram (Figure 1), located on Page ii
inside the front cover, and to the interconnection diagram (Figure 2) on Page iii.
Problem Possible solution
Healthy LED is not lit. Is the plant "INTERLOCK" connected? Refer to the default input/output diagram.
SFE failure after frequent
switching on and off.
The SFE has correctly carried out self-protection procedures after frequent switching on
and off in a short period of time. Replace pre-charge fuses, see Section 8.
The SFE will not run from
the Keypad.
The SFE must be in "Keypad control" (i.e. Local control). Check that DIGIN 4 is open.
Use a DVM or view P11.21. DIGIN 4 is connected to CF116 which selects local/remote.
The SFE will not run from
the terminals.
The SFE must be in "Remote control". Check that DIGIN 4 is closed, use a DVM or view
P11.21. DIGIN 4 is connected to CF116 which selects Keypad/Remote.
The SFE will not run from
either Keypad or terminals,
and displays Warning 136
(CF25/ LCN feedback loss).
LCN feedback signal LCN AUX missing.
Check line contactor feedback wiring to TB3/6.
Check that LCN has closed.
If the LCN has not closed:
Check LCN coil supply voltage.
Check wiring to TB7.
Check that DC link volts (P51.00) is greater than pre-charge threshold (P52.17).
Trip code 96 (Aux phase
loss) is displayed and cannot
be reset.
SFE is not detecting the correct phase displacement on its auxiliary terminals.
Check wiring to AUX R, AUX S, AUX T terminals.
Check pre-charge fuses, see Section 8.
All LED's flashing This indicates a major software or hardware fault with the controller. Normal software
operation cannot continue. Refer to Section 7.6.2.
The analogue input
references are not
functioning as expected.
The default setting for ANIN1 is 0 - 10 V (0 - 100%) and the default for ANIN2 is
4 - 20 mA (20% - 100%). The DIP switches (SW1) on the drive I/O board configure the
inputs for current or voltage.
Check the DIP switches against those shown on the default input/output diagram.
Ensure the link TB6/3 to TB6/7 is connected when using the drive's 10.5 V supply
(TB6/9).
Check the analogue input settings in P7.00 to P7.07 against default settings.
Check the values entering the analogue inputs in P7.03, P7.07 respectively.
The analogue outputs are
not functioning as expected.
The default settings for ANOP1 and ANOP2 are 0 - 10 V, 0 - 100%. The DIP switches
(SW1) on the I/O board should both be set for volts.
Check the DIP switch settings against those shown on the default input/output
diagram.
Check the analogue output settings in P7.17 to P7.26 against default settings.
Check the values coming from the analogue outputs in P7.21, P7.26 respectively.
SFE trips on overcurrent or
overvolts when run is
attempted.
Check that the Auxiliary terminals (AUX R, AUX S, AUX T) are consistent with the
power terminals R/U, S/V and T/W, i.e. AUX R is wired to R/U etc.
Check the wiring of ancillary components against the interconnection diagram.
Trip code 93 (Mains Sync
Fault) is displayed when run
is attempted.
Check wiring of ancillary components against the interconnection diagram.
Is there excessive impedance in the mains supply to the SFE? (i.e. is the mains
supply fault level too small?). See performance data in Section 2.9.3.
DIAGNOSTIC HINTS FOR THE SINUSOIDAL FRONT END
Note: These hints are aimed mainly at the DEFAULT machine bridge, to help with problems which may be experienced
while working wih this manual. Reference is made to the default input/output diagram (Figure 1), located on Page ii
inside the front cover, and to the interconnection diagram (Figure 2) on Page iii.
Problem Possible solution
Healthy LED is not lit. Is the plant "INTERLOCK" connected? Refer to the default input/output diagram.
Drive failure after frequent
switching on and off.
The drive has correctly carried out self-protection procedures after frequent switching on
and off in a short period of time. Replace pre-charge fuses, see Section 8.
The drive will not run from
the Keypad.
The drive must be in "Keypad control" (i.e. Local control). Check that DIGIN 4 is open.
Use a DVM or view P11.21. DIGIN 4 is connected to CF116 which selects local/remote.
The drive will not run from
the terminals.
The drive must be in "Remote control". Check that DIGIN 4 is closed, use a DVM or view
P11.21. DIGIN 4 is connected to CF116 which selects local/remote.
Also check that the "SFE Running" output is not inhibiting the "STOP" input on DIGIN 1.
All LED's flashing This indicates a major software or hardware fault with the controller. Normal software
operation cannot continue. Refer to Section 7.6.2.
The speed reference is not
working.
The default drive has 3 speed references programmed:
a) Local (Keypad) reference value entered in P1.00
b) Remote ANIN1, programmed to be 0 - 10 V, view value in P11.36
c) Remote ANIN2, programmed to be 4 - 20 mA, view value in P11.37
Monitor P9.00 whilst operating the required reference.
To achieve Keypad reference, ensure DIGIN 4 is open.
To achieve any Remote reference, ensure DIGIN 4 is closed.
To select between Remote references ANIN1 and ANIN2, toggle DIGIN 5.
The analogue input
references are not
functioning as expected.
The default setting for ANIN1 is 0 - 10 V (0 - 100%) and the default for ANIN2 is
4 - 20 mA (20% - 100%). The DIP switches (SW1) on the drive I/O board configure the
inputs for current or voltage.
Check the DIP switches against those shown on the default input/output diagram.
Ensure the link TB6/3 to TB6/7 is connected when using the drive's 10.5 V supply
(TB6/9).
Check the analogue input settings in P7.00 to P7.07 against default settings.
Check the values entering the analogue inputs in P7.03, P7.07 respectively.
The analogue outputs are
not functioning as expected.
The default DIP switch (SW1) setting for ANOP1 is 0 - 10 V, 0 - 100%. The setting for
ANOP2 is 0 20 mA, 0 100%.
Check the DIP switch settings against those shown on the default input/output
diagram.
Check the analogue output settings in P7.17 to P7.26 against default settings.
Check the values coming from the analogue outputs in P7.21, P7.26 respectively.
Deceleration ramps not
being followed, seems to
take longer than set.
The drive is programmed at the factory to prevent itself tripping on overvoltage trips.
When an AC motor is decelerated, the motor generates voltage back to the drive DC link,
the amount of voltage depends on the speed of the deceleration and the load inertia. If the
time taken to stop the load is too long:
Check the deceleration rates set in P1.23 or P6.02, P6.03 (repeated).
Check the value set in P4.12 (P23.05) and ensure that it is sufficient (note that
0.1 kW limit means "unlimited").
Motor turns slowly and draws
excess current when in
Vector control with an
encoder.
This is known as Wrongly Phased. Check the motor phasing and check the encoder
connections. Refer to the Commissioning flowchart, which suggests tests that can be
made to verify the encoder integrity.
Drive will not complete a
CALIBRATION run.
Although the CAL run should be done off load, for small motors with low inertia it may help
to keep the coupling on the motor shaft. Also check the accuracy of the basic motor data
entered, especially Mag current, it needs to be in the right order of magnitude.
Not enough torque available
after a calibration run.
VECTOR CONTROL WITH
ENCODER.
Check P12.10, this is the measured COLD value of Rr determined by the CAL run.
Check P12.15, this is the calculated HOT value of Rr. The value of P12.15 1.4 x
P12.10. If this is not true simply edit P12.15 =1.4 x P12.10.
Check P12.02, the value of mains voltage, then check the value of P11.49, this is
maximum torque the drive has calculated to be available at the motor.
Check P8.00 to P8.03. Values greater than P11.49 will be unattainable.
Try enabling Auto Temperature Compensation. Set P12.06 =1. Increase P12.07 to
increase the rate of auto-compensation, to achieve required motor torque.
Warnings 134 and 136
displayed, trips on code 94
when "RUN" pressed.
Follow the machine bridge Guided Commissioning procedure in Section 5B.4 to choose
the correct control mode.
WARNING & TRIP CODES DIAGNOSTIC HINTS FOR THE MACHINE BRIDGE
VIEWING WARNINGS AND TRIPS
MENU 10
Parameter View
10.00 - 10.09 Warning Nos. 1 - 10
10.10 - 10.19 Trip Nos. 1 - 10
10.20 - 10.29 Trip History Nos. 1 - 10
10.30 Secs Since Trip
10.31 Hours Since Trip
10.32 CF10 - User Trip 1
10.33 CF112 - User Trip 2
10.34 CF9 - Trip Reset
WARNING CODE DESCRIPTION
100 Excess Current
101 M Motor Thermostat
102 M Motor I
2
t
103 Motor PTC
104 DB Resistor
105 Reference Loss
107 High Temperature
108 Low Temperature
110 Backup Ref Loss
112 RS232 Loss
113 RS485 Loss
114 M Overspeed
115 M Encoder Loss
116 FIP Loss
120 - 125 Internal Software Fault
128 M Load Fault - High
129 M Load Fault Low
130 CAN 1 Loss - see P61.43
131 CAN PDO/sec too high
132 Bad CAN ID - see P61.45
133 SFE Mains Frequency
Warning
134 SFE Mains Sync Loss
135 CAN 1 PDO/IO clash
136 SFE CF25 /LCN F/B Loss
137 SFE Choke PTC
TRIP CODE DESCRIPTION
1 Interlock
2 Reference Loss
3 DC Overvolts
4 DC Undervolts
5 Timed Overload
6 Over Temperature
7 Instantaneous Overcurrent
8 U-Phase - Overcurrent
9 U-Phase - HW Overtemp
10, 11 As 8, 9 for V-Phase
12, 13 As 8, 9 for W-Phase
14 Encoder PS Fail
15 Auxiliary 15 V Fail
16 Auxiliary 24 V Fail
17 Unidentified PIB
18 History Restore Fail
19 New Drive
20 Parameter Edits Lost
21 M Motor Thermostat
22 M Motor I
2
T
23 RS232 Loss
24 RS485 Loss
25 Internal Reference Fail
26 Under Temperature
27 Keypad Loss/Removed
28 M Current Imbalance
29 Precharge Failure
30 Drive ID Violation
57 M Overspeed
58 Current Control Fault
59 M Motor Calibration Failure
60 M Unsuitable Motor
61 M Encoder Loss
62 User Trip 1
63 FIP Loss
64 M Load Fault - High
65 M Load Fault - Low
66 Motor PTC
67 DB Resistor
68 Reserved
70 M Datumize Error
71 M Speed Feedback Loss
72 M Over Frequency
73 User Trip 2
93 SFE Mains Freq Trip
94 SFE Mains Sync Loss
95 SFE Mains Monitor Loss
96 SFE Aux Phase Loss
97 Unknown Trip
98 SFE Choke PTC
99 Unknown Trip
100-149 Reserved
150 PWM Error
151 DB Overcurrent Trip
152 DB Hardware Overtemp Trip
200 CAN,1,Loss, - see P61.43
69 (Relate to DELTA systems.
31-56 Refer to Software Manual
74-92 T1679EN)
153-199
HISTORY
THE DRIVE IS EQUIPPED WITH A 10-
CHANNEL HISTORY RECORDER.
MENU 26 ALLOWS SET-UP OF THE LOG
MENU 27 ALLOWS PLAYBACK OF THE
LOG
WARNING/TRIP code annotations :
M =only if motor control (P99.01 =1, 2 or 3)
SFE =only if SFE control (P99.01 =4)
RUNNING led
(Green)
HEALTHY
(STANDBY) led
(Green)
RAISE and LOWER
keys, used to Raise
and Lower motor
speed when Keypad
Reference is
selected.
*
*
*
ESC key, used whilst
Editing and Navigating.
NAVIGATION key, used
to Navigate around the
SFE/Drive Menus and
Parameters. Also used
for Editing.
Alpha/Numeric keys,
used whilst Editing or
Short Cutting parameters.
Keypad Control is selected via Digital Input 4, which
in turn operates Control Flag 116 see Control
Block Diagrams.
DRIVE DATA MANAGER
KEYPAD FUNCTIONS
HELP key. Press to get
Diagnostic Help in case
of a Trip or Warning, or
to get Help about any
drive or SFE parameter.
See examples of Help
key use in Section 4.2
and Diagnostic Help in
Section 7.
ENTER key. Press to
Enter a menu or Enter
(Load) an edit.
STOP key. Press to
stop the motor or
control of DC link volts
in Keypad Control.
RUN key. Press to start
the motor or control of
DC link volts in Keypad
Control.
TRIPPED led
(Red)
WARNING led
(Yellow)
DISPLAY
4-line, 20-digit
Increment Menu
or Parameter no.
Decrement Menu
or Parameter no.
Go to Menu level
Go to Parameter level
Move Cursor Right
Move Cursor Left
(Delete/Backspace)
Increment Value
Decrement Value
NAVIGATION EDITING
NAVIGATION KEY
See over for Diagnostics and Help