Automatic Fire Detectors SIEMENS
Automatic Fire Detectors SIEMENS
Cerberus PRO
Building Technologies
Fire Systems
Characteristics
Environmental
ecologically processing recyclable materials electronic and synthetic material simply separable
Characteristics
resistant to environment and interference factors such as dust, fibers, insects, humidity, extreme temperatures, electro-magnetic interference, corrosive vapors, vibration insensitive to impact, tamper protection protected electronics, high-quality components integrated short-circuit isolator, which locate the defective part on the detector bus of the control unit and insulates between 2 detectors built-in alarm indicator (AI), visible at 360 up to 2 external alarm indicators of type FDAI91/FDAI92/FDAI93 connectable per detector signal processing with detection algorithms automatic address allocation during commissioning the same detector base type can be used for each detector type, for surface and recess supply wiring
Optional accessories
Detector locking device LP720 as protection against theft Designation plate FDBZ291 Detector base seal RS720 for higher protection category Micro terminal DBZ1190-AA (0.28 0.5 mm2) Connection terminal DBZ1190-AB (1.0 2.5 mm2) Sounder base DBS720
OH720 Multi-sensor smoke detector Multi-sensor smoke detector consist of: Detector Dust cap to cover the detector for protection against dust during construction work Function works according to the scattered light principle with one sensor, optical forward scattering Opto-electronic sampling chamber holds off disturbing extraneous light but optimally detects smoke particles an additional heat sensor increases the fire detectors immunity to deceptive phenomena selectable detection behavior by different parameter sets immunity against transient false alarm causes Application
for the detection of flaming fires caused by the combustion of liquid and solid mat-
OP720 Smoke detector Smoke detector consist of: Detector Dust cap to cover the detector for protection against dust during construction work Function works according to the scattered light principle with one sensor, optical forward scattering Opto-electronic sampling chamber holds off disturbing extraneous light but optimally detects smoke particles selectable detection behavior by different parameter sets Application
for the detection of smoke-generating flaming and smoldering fires
HI720 Heat detector (static+RoR) Heat detector consist of: Detector Dust cap to cover the detector for protection against dust during construction work Function equipped with one heat sensor for high requirements certain response behavior with slow and fast temperature increases, also by depth temperature selectable detection behavior by different parameter sets Application suitable in areas in which occur different environment temperatures where high dust or dirt developments or large humidity which can the impact of conventional alarm units to impair
HI722 Heat detector (static) Heat detector consist of: Detector Dust cap to cover the detector for protection against dust during construction work Function equipped with one heat sensor measures the ambient temperature, when the maximum temperature is exceeded the detector sends a danger signal to the fire control panel Application suitable in areas, in which temporary high variations in temperature arise where high dirt and heat fluctuation which can the impact of conventional alarm units to impair
Detector bases DB721 Function Universal base for all point detectors of the series Cerberus PRO FD720 Application for recess supply wiring for surface supply wiring, cable diameter up to 8 mm By using a detector base with loop contact (DB721) the detector line is not interrupted even if no point detector is mounted. Detector base DB722 Function Universal base with detector base seal and screwless terminals for the OP720 and OH720 point detectors of the series Cerberus PRO FD720 Application for recess supply wiring for surface supply wiring, cable diameter up to 8 mm
Base attachment BA720 Application For the supply of surface-mounted tubes (max. 20 mm) and trunking (max. 25 mm x 15 mm) The detector is fixed with a spring-loaded catch.
Installation
Simple installation
Universal base with 2 break outs on the side for surface supply wiring at max. 8 mm extra large rear opening for easy recess supply wiring extra-large mounting slots facilitate a re-use of existing drill holes resulting from other systems connecting terminals for cable diameter at 1.6 mm2 place for auxiliary terminals 2x DBZ1190-AA and 2x DBZ1190-AB detector can be easily turned into the base by hand, or with the detector exchanger DX791 Place for auxiliary terminals DBZ1190- Connecting terminals AA, DBZ1190-AB detector line and ext. AI Opening for cable entry AI
1a
1b
Threaded pin M3 x 12 mm
Hexagonal wrench
support point for T-branching connection, extern alarm indicators (AI) or cable
shielding
place for max. 2 additional terminals each
1a
1b
117
117 56 59
117
59
Technical data OH720 DC 12 33 V ~230 A 2 -10 +55 C -30 +70 C 95 % rel. C-NET white, ~RAL 9010 IP40 IP42 CEA4021, EN 54-7, EN 54-17 G209064 531d/01 3038424 OP720 DC 12 33 V ~220 A 2 -10 +55 C -30 +70 C 95 % rel. C-NET white, ~RAL 9010 IP40 IP42 EN 54-7, EN 54-17 HI720 / HI722 DC 12 33 V ~200 A 2 -10 +55 C -30 +70 C 95 % rel. C-NET white, ~RAL 9010 IP40 IP42 EN 54-5, EN 54-17
Operating voltage (modulated) Operating current (quiescent) Ext. alarm indicator without sounder base AI connectable and programmable Operating temperature Storage temperature Humidity (short-term moisture condensation permitted) Communication protocol Color Protection category EN60529 / IEC529 with detector base seal RS720 Standards Approvals VdS LPCB FM Marine MED (Marine Equipment directive) GL (Germanischer Llyod) Permissible air speed System compatibility C-NET QS standards
OH720
max. 5 m/s
OP720
HI722
Details for ordering Type OH720 OP720 HI720 HI722 DB721 DB722 BA720 LP720 BA720 FDBZ291 RS720 DBZ1190-AA DBZ1190-AB Part no S54310-F2-A1 S54310-F1-A1 S54310-F4-A1 S54310-F3-A1 S54319-F11-A1 S54319-F19-A1 S54319-F20-A1 S54319-F9-A1 S54319-F20-A1 A5Q00002621 S54319-F8-A1 BPZ:4677080001 BPZ:4942340001 Designation Weight Multi-sensor smoke detector 0.144 kg Smoke detector 0.138 kg Heat detector (static + RoR) 0.130 kg Heat detector (static) 0.130 kg Detector base with loop contact 0.100 kg Detector base 0.140 kg Base attachment 0.050 kg Detector locking device (2 hexagonal 0.040 kg key, 100 hexagonal socket pins) Base attachment 0.100 kg Designation plate (10x) 0.034 kg Detector base seal (10x) 0.014 kg 2 Micro terminal 0.28 ... 0.5 mm 0.001 kg Connection terminal 1.0 ... 2.5 mm2 0.007 kg
Accessories
Siemens Switzerland Ltd Infrastructure & Cities Sector Building Technologies Division International Headquarters Fire Systems Gubelstrasse 22 CH-6301 Zug Tel. +41 41 724 24 24 www.siemens.com/buildingtechnologies Document no. Edition A6V10202198_g_en_-10.2011
2011 Copyright by Siemens Switzerland Ltd Data and design subject to change without notice. Supply subject to availability. Manual FD720 Section 2