The document analyzes the design of a grating support structure for a hanging platform. It summarizes that: 1) A STAAD model was created to analyze the grating and support structure according to BS5950 codes. 2) The grating, made of 30x3mm flats at 30mm pitch, was found to be structurally safe and have deflections within allowable limits under all load combinations. 3) The connections between the support columns and concrete roof using chemical anchor bolts, between the columns and secondary members using bolts, and of the end plates were all found to have sufficient capacity.

Uploaded by

vj8584
Copyright
© © All Rights Reserved
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
Download as xls, pdf, or txt
100% found this document useful (2 votes)
1K views5 pages

Design of Grating For Platform

The document analyzes the design of a grating support structure for a hanging platform. It summarizes that: 1) A STAAD model was created to analyze the grating and support structure according to BS5950 codes. 2) The grating, made of 30x3mm flats at 30mm pitch, was found to be structurally safe and have deflections within allowable limits under all load combinations. 3) The connections between the support columns and concrete roof using chemical anchor bolts, between the columns and secondary members using bolts, and of the end plates were all found to have sufficient capacity.

Uploaded by

vj8584
Copyright
© © All Rights Reserved
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1/ 5

( Rev 0 , 05.12.

10 )
AL ROSTAMANI PEGEL L.L.C
Link Middle east Ltd , J ebel Ali , Dubai
Design of Grating Support Structure for Hanging Platform
231796391.xls.ms_office
1 . Introduction
The purpose of following calculations is as listed below;
(A) To check proposed grating support system for the platform.
(B) To check the adequacy of the grating for live load of personnel as 5 kN/m
Reference Documents and drawings ::
LME drawing # EN-1563-101 Dt. 01.12.10 - " Plan Layout for Grating ".
Reference codes::
* BS 5950 - Part 1:2000 -Structural use of steelwork in building.
* BS 8110-1997 - Structural use of concrete.
* Chemical anchor bolts - HILTI or equivalent.
2 .STAAD model and Loads
Staad model- Isometric view
3D- View
Analysis and Design of the grating has been done using Staad Pro as per BS5950 code.
Proposed Grating is Lionweld grating as below made of 30 x 3 thk flats at pitch 30x100.
231796391.xls.ms_office
900
1300
30
Main load bearing flats 30 x 3 thk ,are at 30 mm C/c.
Dead load ( DL)
self weight of steel structure is calculated by STAAD programme.
Consider Ladder load = 1 kN/m being exerted on the platform respective member.
self weight of grating members 24 kg/m = 0.24 kN/m
Live load .( LL)
Platform load- 5.0 kN/m As required by the client
Load combinations:
Design Load combinations
1.4DL+1.6LL
* Service Load combinations ( For deflection check)
1.0DL+1.0LL
3 . Analysis and Design
3.1 - Grating design
Refer grating diagram above.
Total design load = 1.4DL+1.6LL
= 1.4 x 0.24 + 1.6 x 5.0
= 8.34 kN/m
Grating length = 1300 mm
\ no. of load bearing flat bars = 1300 / 30 = 43.34
Max bending moment in the grating panel =
consider this UDL full on the grating span 8.34 x 1.3 = 11 kN/m
900
Bending moment = 11 x 0.9 / 8 = 0.11 kNm
Moment capacity = 43.34 x (1.2 py.Z) = 43.34 (1.2 x 275 x 3 x 30 / 6)
= 6.45 kNm > actual moment
Hence safe
Deflection check :
231796391.xls.ms_office
max deflection = 5 WL
4
/ 384 E I I = 67 x 3 x 30
3
/ 12 = 0.45 x 10
6
mm
4
= 5 x 11 x 900
4
/ ( 384 x 203000 x 0.45 x 10
6
)

= 1.03 mm
Allowable deflection = span / 200 = 1300 / 200 = 6.5 mm
Actual deflection < allowable deflection
Hence safe
3.2 Chemical Anchor Connection between UC 152X152X23 & concrete roof.
Fx = 6 kN
Fy = 78 kN
Fz = 1 kN
Use 152x152 x20 thk base plate for columns.
It is proposed to use 8 no. M20 HILTI chemical anchor bolts
max tension in bolt due to Fz = 25 /4 = 6.25 kN
Max shear in bolt = Fy / 8 = 78 /4 = 19.5 kN
Refer HILTI chemical anchor bolt catalogue :: HVU adhesive with HAS rod.
Tensile capacity: ( for 20 dia bolts) Refer catalogue:
N
Rd,c
= N
o
Rd,c
.f
B,N
.f
T
.f
A,N
.f
R,N
N
o
Rd,c
.= 52.4 kN
f
B,N
. = 1.16 for C40 grade concrete
\ N
Rd,c
= 52.4 * 1.16 * 1.0 * 0.68 * 1.0 f
T
.= 1.0 full recommended anchor depth
= 41.3 kN > actual tension in bolt f
A,N
.= 0.68 for 120 mm spacing
f
R,N
= 1.0 no edge distance influence
Hence safe
(egde distance > 180 mm)
Shear capacity: (for 20 dia bolts) Refer catalogue:
V
Rd,c
= V
o
Rd,c
.f
B,V
.f
AR,V
.f
b,V
V
o
Rd,c
.= 10.3 kN
min edge distance required C
min
= 85 mm f
B,V
.= 1.28 for C40 concrete grade
actual edge distance C = 200 mm f
AR,V
.= 1.89 C/C
min
= 2.35
spacing between bolts S = 120 mm S/C
min
= 1.4
\ V
Rd,c
= 10.3 * 1.28 * 1.89 *1.0 f
b,V
= 1.0
= 25 kN > actual shear in bolt
Hence safe
Combined capacity = 6.25/41.3 + 19.5 / 25 = 0.94 < 1.4
Hence safe
End plate :
max moment in end plate = 2 x 6.25 x 0.05 = 0.62kNm
Moment capacity of end plate per unit width = p
y
.t
p
/4 ..cl.6.3.4.3, BS5950-1:2000
\Moment capacity of end plate = p
y
.b.t
p
/4
= 275 x 152 x 20 /4 = 4.18 kNm > actual moment in end plate
hence safe
Hence provided 4no. M20 chemical HILTI anchor bolts/rod and the end plate are safe.
231796391.xls.ms_office
3.3 Bolted connection between main member UC 152x152x23 to secondary members CH 125x65x15.
max axial force in hanger members = 10kN
provide 2M12 through bolts, BS grade 8.8
max tension per bolt = 10/2 = 5 kN
capacity of M12 bolt in tension = 37.8 kN > actual design tension
Provide 12 thk end plate .. Hence safe
4. Conclusion :
The proposed grating made of 30 x 3 thk flat at pitch 30 mm c/c and the support system
is structurally safe.
Deflections are within allowable limit.
The proposed connections are structurally safe.