SF6 insulated Ring Main Units and

Compact Switchgear SafeRing and SafePlus


For safe and reliable power distribution
2
Indoor three function RMU
Extensible / Non-extensible
Outdoor four function RMU
IP-54 Enclosure
Extensible / Non-extensible
The ABB advantage

120 years of pioneering technology

Unparalleled domain competence

Vast global experience

Total solution provider

Large installed base across the world

In-depth knowledge of international &


local electrical and safety standards

Environment-friendly technologies
ABB is a global leader in power and automation
technologies that enable industrial and utility
customers to improve performance while lowering
environmental impact. The ABB Group of companies
operates in around 100 countries across the world.
ABBs Power Technologies division offers electric, gas
and water utilities as well as industrial and commercial
customers a wide range of products, systems and
service solutions for power generation, transmission
and distribution including complete electrics,
generation plants, utility automation and bulk
power transmission.
ABBs power technologies cover the entire voltage range
including indoor and outdoor circuit breakers, air and gas
insulated switchgear, disconnectors, capacitor banks,
reactive power compensators, power and distribution
transformers as well as instrument transformers.
ABB a global leader
In India, ABB serves customers with the complete
range of power and automation technologies. The
company has a vast installed base, extensive
manufacturing and a countrywide marketing and
service presence.
3
ABB offers a complete solution for 12/24 kV distribution
networks. This consists of SafeRing,
a Ring Main Unit (RMU) that can be supplied in various
configurations and SafePlus, a compact switchgear with
unique flexibility. SafePlus offers extendibility and fully /
semi modular configuration possibilities. Both the units
have identical user interfaces.
SafeRing / SafePlus are delivered as a completely
sealed system with a stainless steel tank containing
SF6 insulated Ring Main Units and Compact Switchgear
SafeRing and SafePlus
Standard equipment supplied with SafeRing / SafePlus
Earthing switches
Operating mechanism with integral mechanical
interlocking
Operating handle
Facilities for padlocks on all switching equipment
Bushing for cable connections in front with arc-
resistant cable covers for utmost operator safety
Manometer for SF6 gas pressure monitoring
Lifting lug for easy handling
All units are designed so that an integrated remote
control and monitoring unit can be fitted when required
Applications
Wind turbines City power distribution,
hotels, shopping
centres, office
buildings, business
centres, etc.
Small industries Compact secondary
substations
Light mining
applications, tunnels
and underground
railways
all the live parts and the switching equipment.
Constant atmospheric conditions in the sealed tank
ensures a high level of reliability, safety and a
virtually maintenance-free system. As an option in
SafePlus, an external busbar can be provided to
enable a completely modular configuration.
SafeRing and SafePlus can also be fitted with a
remote control and monitoring unit and are suitable
for both indoor and outdoor applications.
Key features
Compact and robust design
Minimal moving parts

Virtually maintenance free

High degree of functionality with integrated


features
High flexibility
Multiple configuration options

Enhanced safety

Complete solutions including applications


for remote control and monitoring
4
Remote control & monitoring unit (optional)
The use of an integrated remote control and
monitoring unit offers many advantages including
reduction in downtime and increased efficiency.
The unit can be connected to the motor control and
monitoring equipment.
A standard interface allows easy retrofit installation
of the unit.
The functions include:
Remote control and position indicators for
switches and circuit breakers
Monitoring of short circuit indicators
Monitoring of SF6 gas pressure/density
Additional equipment that can be supplied
includes Direct Process Interface (DPI)
board for:
Monitoring of current on the high voltage
side with ring core transformers and
Monitoring of current and voltage on the low
voltage side of the distribution transformer.
(Power Quality Monitoring)
Communication
The unit can be equipped with different types of
communication media. External communication
such as radio and GSM is connected via an
RS232 interface.
Voltage and short circuit indicators
As an option these units can be equipped with fixed type
or plug-in type voltage indicators as well as electronic
short circuit indicators for simple fault indication.
Circuit breaker with relay
When vacuum circuit breakers are used for transformer
protection, self powered microprocessor based over
current and earth fault relay are used. The protection
system does not require an external power supply, as the
power is taken from the current transformers.
SafePlus and SafeRing
C
o
m
m
u
n
ica
tio
n
s
5
Transformer protection
A choice is offered between a switch fuse
combination and circuit breaker with relay for
transformer protection. The switch fuse
combination offers optimal protection against
short circuits, while the circuit breaker with
relay option offers better protection against
low overcurrents. A circuit breaker with relay
is recommended for larger transformers.
Key interlocking
As an option the units can be supplied with a
key interlocking system for circuit breakers,
switches and earthing switches.
Modularity and external busbar
All modules except the metering panel are only
325 mm wide. The metering panel is 650 mm
wide including bus riser. SafePlus can be
configured with a maximum of 5 modules in
one SF6 tank with an internal busbar. To
configure switchgear with more than 5 modules
as many tanks as needed can be joined
together with use of an external busbar.
Alternatively the whole switchgear can be
configured fully modular using an external
busbar between all modules. The external
busbar is fully insulated in order to maintain
climatic independence and ensures
maintenance-free operation. The internal busbar
supports a maximum current of 630 A, while
the external busbar has a rating of 1250 A.
Manual / Motorised operation
Manually operated mechanisms for cable and
transformer switches are part of standard equipment.
As an option, they can also be motorised.
Fuses
When switch fuse combinations are used
for transformer protection, the fuse
canisters are positioned behind a
separately interlocked cover in front of
the unit. To facilitate fuse replacement,
the operating handle is used to remove
the fuse canister covers. The fuse
tripping system is located at the front,
ensuring a waterproof solution.
Arc suppressor
As an option the units can be supplied with an arc
suppressor which closes automatically on the feeder
bushings if an internal arc fault occurs.
Cable connections
The units are fitted with standardised bushings that comply
with DIN 47636. All the bushings are the same height from the
ground and are protected by a cable cover. The cable covers
are supplied with an interlocking mechanism with the earthing
switches. It is also possible to connect parallel cables with a
special double cable cover. Cable covers are designed to
accommodate both single core and three core cables.
6
Busbar extension LHS/RHS
External busbar
Metering
LV compartment
Manometer and signal (1 NO) from pressure
indicator wired to terminals
Voltage tester
Auxiliary switch for vacuum circuit breaker
position 2 NO + 2NC
Auxiliary switch for disconnected position
2NO + 2NC
Auxiliary switch for earth switch position
2NO + 2NC
Vacuum circuit breaker tripped signal 1NO
Auxiliary switch for load break switch position
2NO + 2NC
Optional equipment
Auxiliary switch for fuse blown 1NO
Cable test bushings
Cable support bars, non-magnetic
Extra base frame (h=450 mm)
Ronis interlocking system, EL 11 AP
Current measuring
Arc suppressor
Integrated control and monitoring
Trip coil open
Trip coil open and close
Motorised operation
Capacitive voltage indicator
Short circuit indicator
C- module F- module V- module
Switch Downstream Vacuum circuit
disconnector Earthing switch Switch fuse earthing switch breaker Earthing switch
Rated voltage kV 12 / 17,5 / 24 12 / 17,5 / 24 12 / 17,5 / 24 12 / 17,5 / 24 12/15,2/17,5/24 12/15,2/17,5/24
Power frequency withstand voltage kV 28 / 38 / 50 28 / 38 / 50 28 / 38 / 50 28 / 38 / 50 28 / 38 / 38 / 50 28 / 38 / 38 / 50
Impulse withstand voltage kV 95 / 95 / 125 95 / 95 / 125 95 / 95 / 125 95 / 95 / 125 95 / 95 / 95 / 125 95 / 95 / 95 / 125
Rated current A 630 / 630 / 630 Ver
1)
630/630/630/630
Breaking capacities:
closed loop A 630 / 630 / 630
of load cable charging A 135 / 135 / 135
of load transformer A 20 / 20 / 20
earth fault A 200 / 150 / 150
earth fault cable charging A 115 / 87 / 87
short circuit breaking current kA Ver
2)
21 / 21 / 16 / 16
Making capacity kA 62,5 / 52,5 / 52,5 62,5 / 52,5 / 52,5 Ver
2)
12,5 / 12,5 / 12,5 52,5/52,5/40/40 52,5/52,5/40/40
Short time current 1 sec. kA 25 / - / - 25 / - / - 5 / 5 / 5
Short time current 3 sec. kA 21 / 21 / 21 21 / 21 / 21 21 / 21 / 16 / 16 21 / 21 / 16 / 16
Technical specifications
1) Depending on the current rating of the fuse 2) Limited by high voltage fuse links
SafeRing and SafePlus are tested according to IEC publications IEC 60265, IEC 60129, IEC 60056, IEC 60420, IEC 60694 and IEC 60298.
7
Similar versions with switch fuse are also available.
Available configurations of SafeRing
Available modules of SafePlus
DV
* Busrise needed when Sl on right side of SF6 tank
** Sv always together with Busrise (Total width=650 mm)
C De D F V Be Sl* Sv** M
200/
630A
CCV CCCC
CCCV CCVV
C Cable Switch
F Switch fuse disconnector
D Direct cable connection
De Direct cable connection with earthing
V Vacuum circuit breaker
S1 Busbar sectionaliser,
load break switch
Be Busbar earthing
Sv Busbar sectionaliser, vacuum
circuit breaker
M Metering cubicle
Dimensional drawing
* NB Fixing bracket
CSG A B C
1-way 371 297 336
2-way 696 622 661
3-way 1021 947 986
4-way 1346 1272 1311
5-way 1671 1597 1636
AB B Lim ited
M edium Voltage Technologies
Street N o. 17
M ID C , Satpur
N ashik 422 007
Tel: +91 253-2351095 98
Fax:+91 253-2350644
R egional M arketing O ffices:
N B C C Tow er
4th Floor
N o. 15, B hikaji C am a Place
N ew D elhi 110 066
Tel: +91 11 26186000
Fax: +91 11 26197592/84035
4th Floor
N o. 9
Elgin R oad
Kolkata 700 020
Tel: +91 33 22832911/906
Fax:+91 33 22832990
AB B H ouse
D r. S B Path
B allard Estate
M um bai 400 038
Tel: +91 22 56318231 39
Fax:+91 22 56318276/77
Em bassy Star, 1st Floor
N o. 8, Palace R oad
Vasanth N agar
B angalore 560 052
Tel: +91 80 22949779
Fax: +91 80 22949808
C entury Plaza
N o. 3C , 3D , 3F, 3rd Floor
561 / 562, Anna Salai
Teynam pet
C hennai 600 018
Tel: +91 44 24340201/203
Fax:+91 44 24340282
Vandana H ouse
1st Floor
G E R oad, R am kund
R aipur 492 001
Tel: +91 771 5060816-8
Fax:+91 771 5023051
www.abb.com
N orth East W est South C entral
All products are manufactured in accordance with
ISO9001. The latest edition of relevant IEC standards
will always apply to our continuous test programme.
SafeRing/SafePlus are designed for highest levels of
personal safety and type tested for internal arc as per
IEC standards.

You might also like