Operating Instruction of Surge Arrester
Operating Instruction of Surge Arrester
Operating instructions
Surge arrester
Type POLIM-D
Issued by:
ABB Switzerland Ltd.
High Voltage Products
Surge Arresters
Jurastrasse 45
CH-5430 Wettingen 1
Contact information:
Phone: +41 (0)58 585 29 11
Telefax: +41 (0)58 585 55 70
E-Mail: sales.sa@ch.abb.com
Internet: www.abb.com/arrestersonline
ABB
Table of contents
1.
2.
3.
1.1.
Validity
1.2.
Target group
1.3.
Copyright
SAFETY
2.1.
2.2.
2.2.1.
Product safety
2.2.2.
Personnel-related measures
2.2.3.
Organisational measures
DESCRIPTION
3.1.
Intended use
3.2.
3.3.
Technical data
3.3.1.
3.3.2.
Application guidelines
3.3.3.
3.3.4.
Behaviour in fire
4.
5.
COMMISSIONING
10
5.1.
Safety
10
5.2.
10
5.3.
10
5.4.
Mounting
11
5.4.1.
System voltage
11
5.4.2.
Installation position
11
5.4.3.
12
5.4.4.
Connections
12
5.5.
6.
7.
Earthing
13
MAINTENANCE, UPKEEP
14
6.1.
Disconnecting device
14
6.2.
15
6.3.
15
DISPOSAL
16
EN
Doc. 1HC0010173 AB
ABB
1.
1.1.
Validity
These operating instructions are valid only for the POLIM-D surge arrester.
1.2.
Target group
The target group of these operating instructions is professionals in the field of highvoltage technology.
The POLIM-D may only be commissioned and maintained by persons instructed
in proper use and handling.
1.3.
Copyright
The copyright of these operating instructions belongs to ABB Switzerland Ltd.
These operating instructions are to be handled confidentially and are intended
solely for mounting, operating and monitoring personnel. They contain regulations
and illustrations of a technical nature which may neither be utilized for competitive
purposes nor passed on to others. Handing over to third parties is impermissible
and liable for compensation.
All rights, including those regarding the translation, are reserved.
Language of original document: German
Doc. 1HC0010173 AB
EN
ABB
2.
SAFETY
2.1.
This safety sign warns you of the danger of death or serious injury from electric
shocks. Follow all measures marked with the safety sign to avoid injuries and
death.
Warnings in these operating instructions indicate special dangers and list measures for prevention of the danger. There are three levels of warning:
Warning
word
Meaning
DANGER
WARNING
CAUTION
EN
Doc. 1HC0010173 AB
ABB
2.2.
2.2.1.
Product safety
The POLIM-D has been constructed using state-of-the-art technology and officially recognised safety-related rules. Danger to life and health of the user or third
parties could arise or damage of the POLIM-D and other property could occur
while the POLIM-D is in use, however.
2.2.2.
2.2.3.
Keep the operating instructions intact and fully readable, and store them in
such a way that they are accessible to operating personnel at all times.
Personnel-related measures
X
Train and instruct personnel in working on the POLIM-D using the operating
instructions.
Organisational measures
X
The safety rules of the owner of the high- and medium-voltage system and all
regulations of the respective national safety authorities are to be observed.
Clearly assign areas of responsibility for working with the POLIM-D. Make
them known and adhere to them.
Only personnel who have read and understood the operating instructions, especially the "Basic safety precautions" section may be allowed to carry out activities with the POLIM-D.
Doc. 1HC0010173 AB
EN
ABB
3.
DESCRIPTION
3.1.
Intended use
The POLIM-D is a surge arrester intended for use in high- and medium-voltage
applications. Surge arresters protect the insulation of high voltage and medium
voltage devices against unacceptable overvoltages which are caused by lightning
or switching operations.
The manufacturer is not liable for resulting damages from further, unintended use.
The operator accepts all responsibility for using the POLIM-D outside of its intended application range as specified in this document.
3.2.
transformers
cables
EN
Doc. 1HC0010173 AB
ABB
3.3.
Technical data
The technical data, dimensions, weights and installation distances are specified in
the following documents:
3.3.1.
Drawings of accessories
Meaning
POLIM-D
Type designation
In = .. kA
IEC-P-CL .. kA
Meaning
Uc = .. kV
Ur = .. kV
Rated voltage Ur
xxxxxxxx
Serial number
xx/20xx
Doc. 1HC0010173 AB
EN
ABB
3.3.2.
Application guidelines
The following guidelines apply for the use of POLIM-D surge arresters:
3.3.3.
Position
Torque
[Nm]
Minimum
screw-in depth
[mm]
Maximum
screw-in depth
[mm]
M12
top connection
48
18
25
M12
top connection
without socket
48
18
20.5
M12
bottom
connection
48
18
20.5
M12
bottom connection
without socket
48
12
12.5
The specified values in the table below apply for POLIM-D surge arrester equipped with a disconnecting device
3.3.4.
Thread
Position
Torque
[Nm]
M12
20
M10
20
Behaviour in fire
The silicone housing of the surge arrester is self-extinguishing.
EN
Doc. 1HC0010173 AB
ABB
4.
CAUTION
Unpacking
The surge arresters provided are packaged in stable cardboard boxes or wooden
crates. The accessories, packaged in plastic bags, are either included in the carton
or wooden crate or supplied separately in case of large quantities.
The surge arresters are supplied with accessories installed, unless specifically ordered otherwise. The routine test reports for the final electrical inspection are included in the packaging material.
X
After receiving the shipment, compare the order and delivery documents immediately to check for completeness and accuracy of the shipment. In case of
incompleteness or deviations, inform the supplier and shipper immediately.
Notify the insurance company, the shipper and the supplier of the damage
immediately and create a damage log.
Storage
The original packaging materials can be used for storage.
X
Doc. 1HC0010173 AB
EN
ABB
5.
COMMISSIONING
5.1.
Safety
System uses high voltage
Death, serious bodily harm and damage to the switching gear may result from an
electric shock.
DANGER
5.2.
5.3.
DANGER
When working near the surge arrester, do not wear easily flammable clothing.
Surge arresters only protect medium-voltage apparatuses when they are located
within the protective distance The protective distance is only a few meters.
X
Always mount surge arresters as close as possible to the apparatus to be protected within the protective distance. The length of the connecting cables are
decisive here.
X Use POLIM-D surge arrester equipped with a disconnecting device in outdoor installations, only.
10
EN
Doc. 1HC0010173 AB
ABB
5.4.
Mounting
5.4.1.
System voltage
Incorrect system voltage
Damage to the switching gear and the surge arrester.
CAUTION
5.4.2.
Do not use surge arresters intended for a.c. systems in d.c. systems.
Before mounting, ensure that the characteristic data on the rating plate of the
surge arrester matches the requirements of the power system.
Ensure that system voltage applied at the terminals of the arrester does not
exceed the maximum permissible continuous operating voltage of the surge
arrester.
Installation position
Deposits on the undersides of sheds
Conductivity of deposits hinders protective function of the POLIM-D .
CAUTION
Doc. 1HC0010173 AB
Always mount surge arresters in such a way that the sheds point downward.
EN
11
ABB
5.4.3.
5.4.4.
Connections
The base or foundation for the surge arrester must be flat, clean and suitable for
the loads that arise.
The following materials made of stainless or galvanised steel are to be provided by
the customer depending on the application:
bolts
nuts
bolt locks
The ordered mounting accessory is already mounted to the surge arrester in most
cases. If the mounting accessory hase been ordered and delivered separately, it
shall be mounted according to the enclosed instruction, drawing, data sheet or dimensional drawing.
12
Connect the high voltage connection cable to the head end terminal of the
surge arrester. Use a stranded cable.
When tightening the bolt, the torque shall be countered by a spanner at the
same terminal.
Carefully clean contact surfaces before mounting and lubricate with acid-free
contact grease.
EN
Doc. 1HC0010173 AB
ABB
5.5.
Earthing
X
Connect surge arresters to the system ground via the shortest path.
Doc. 1HC0010173 AB
EN
13
ABB
6.
MAINTENANCE, UPKEEP
System uses high voltage
Death, serious bodily harm and damage to the switching gear may result from an
electric shock.
DANGER
The surge arresters do not contain wearing parts and are therefore maintenancefree. Replacement parts are not needed.
6.1.
Disconnecting device
Tripping of disconnecting device
Risk of injury due to inappropriate handling.
DANGER
Do not connect any voltage/energy source to the terminals of the disconnecting device.
14
EN
Doc. 1HC0010173 AB
ABB
6.2.
6.3.
Check the surge arresters visually on a regular basis to ensure that they are
in sound condition.
Doc. 1HC0010173 AB
EN
15
ABB
7.
DISPOSAL
POLIM-D surge arresters are environmentally-friendly products which must be
disposed of based on the respective applicable regional regulations in an environmentally-friendly manner. The materials should be given up for recycling.
Constituent components are:
metal-oxide varistors
If disconnecting device has not been damaged it can be assumed that the small
propellant charge had not been tripped. In this case disconnecting device shall be
disposed according to the local laws and regulations. Do not open disconnecting
device.
The remaining parts of a disconnecting device, which has tripped, can be recycled.
Metal-oxide varistors
The metal-oxide varistors are sintered ceramics consisting up to 90% of ZnO. The
following additions are also contained within:
percent by weight over 1%: Bi2O3 and Sb2O3, which are considered to be dangerous substances according to EU ordinances
percent by weight between 0.1 and 1%: NiO and Cr2O3, which are considered
poisonous and dangerous materials pursuant to EU guideline 91/689/EEC
Metal-oxide varistors are coated with a thin glass coating containing lead-oxide
(< 0.1% of the weight).
The substances are present as an oxide in metal-oxide varistors. A wash-out test
in accordance with an EPA specification (Federal Register/vol. 45, No 98 /Rules
and regulations) has shown that the sintered metal-oxide varistors can be disposed of as industrial waste without infringing on EEC guidelines.
No danger to personal health or the environment is present during normal operation.