Recommended LabVIEW Architectures and Development Practices
for Control and Monitoring Applications
This document provides an overview of recommended architectures and development practices when designing control
and monitoring applications using LabVIEW Real-Time and LabVIEW FPGA software with NI CompactRIO controllers.
Contents
Overview and Background ........................................................................................................1
CompactRIO Architecture...............................................................................................................1
LabVIEW..........................................................................................................................................1
Real-Time Controller.......................................................................................................................1
Reconfigurable I/O FPGA ..............................................................................................................3
I/O Modules.....................................................................................................................................3
SystemConfigurations....................................................................................................................4
CHAPTER 1
Designing a CompactRIO SoftwareArchitecture.............................................................6
CompactRIO Reference Architectures ......................................................................................6
Processes........................................................................................................................................7
Data Communication .....................................................................................................................7
Typical CompactRIO Architecture.................................................................................................9
Common Variant Architectures.....................................................................................................9
ExampleTurbine Testing System............................................................................................. 11
CHAPTER 2
Choosing a CompactRIO ProgrammingMode................................................................14
When to Use LabVIEW FPGA ....................................................................................................15
Using LabVIEW FPGA Interface Mode ..................................................................................... 17
CHAPTER 3
Designing a LabVIEW Real-Time Application...................................................................23
Designing a Top-Level RTOS VI ..................................................................................................23
Deterministic and Nondeterministic Processes ...................................................................24
Implementing Deterministic Processes...................................................................................25
Setting the Priority of a Deterministic Task...............................................................................25
CHAPTER 4
Best Practices for Network Communication.....................................................................52
Network Communication ............................................................................................................52
Selecting a Networking Protocol................................................................................................52
Communication Model ................................................................................................................52
Network Configuration ................................................................................................................53
Interfacing to OSs and Third-Party Applications........................................................................53
LabVIEW Version...........................................................................................................................54
Security .........................................................................................................................................54
Ease of Use Versus Performance and Reliability......................................................................54
Network Streams............................................................................................................................62
Using Network Streams to Send Messages and Commands................................................65
Installing Network Stream Support to CompactRIO................................................................66
ii
CHAPTER 5
Customizing Hardware ThroughLabVIEWFPGA...........................................................78
FPGA Technology ...........................................................................................................................78
Establishing a Design Flow..........................................................................................................79
Best Practices for Implementing LabVIEW FPGA Code ....................................................80
Reading and Writing I/O ..............................................................................................................80
Data Communication.....................................................................................................................87
Interprocess Data Communication.............................................................................................87
Intertarget Communication.........................................................................................................89
CHAPTER 6
Timing and Synchronization of I/O....................................................................................... 111
LabVIEW FPGA Communication Nodes..................................................................................111
I/O Nodes..................................................................................................................................... 112
Method Nodes............................................................................................................................ 112
Property Nodes........................................................................................................................... 112
iii
Synchronizing Modules...............................................................................................................122
Synchronizing Delta-Sigma Modules........................................................................................122
Synchronizing Simultaneous On-Demand Modules .............................................................123
Synchronizing Multiplexed Modules .......................................................................................123
Synchronizing Delta-Sigma and Scanned (SAR) Modules.....................................................123
CHAPTER 7
Adding I/O to the CompactRIO System............................................................................125
Adding I/O to CompactRIO .......................................................................................................125
MXI-Express RIO .........................................................................................................................126
Ethernet RIO .................................................................................................................................127
EtherCAT RIO.................................................................................................................................128
Tutorial: Accessing I/O Using the EtherCAT RIO Chassis ....................................................129
CHAPTER 8
Communicating With Third-Party Devices.......................................................................135
Serial Communication From CompactRIO.............................................................................135
Serial Communications From LabVIEW...................................................................................137
CHAPTER 9
Designing a Touch Panel HMI...............................................................................................153
Building User Interfaces and HMIs Using LabVIEW..........................................................153
Basic HMI Architecture Background.........................................................................................153
iv
CHAPTER 10
Adding Vision and Motion.......................................................................................................158
Machine Vision/Inspection..........................................................................................................158
Machine Vision Using LabVIEW Real-Time.............................................................................161
Example Configurations..............................................................................................................202
Ethernet RIO With C Series Motion Modules........................................................................202
EtherCAT-Based System............................................................................................................203
Mixed-Axis Systems...................................................................................................................204
CHAPTER 11
Deploying and Replicating Systems...................................................................................208
Application Deployment..............................................................................................................208
Deploying Applications to CompactRIO..................................................................................208
Deploying LabVIEW FPGA Applications..................................................................................213
Method 2: Storing the Application in Nonvolatile Flash Memory on the FPGA Target.....214
Deploying Applications That Use Network-Published Shared Variables..............................216
Recommended Software Stacks for CompactRIO................................................................219
Imaging.........................................................................................................................................220
Application Components............................................................................................................221
The Replication and Deployment Utility (RAD).......................................................................221
CHAPTER 12
Security on NI RIO Systems..................................................................................................248
Security Concerns on RIO Systems........................................................................................248
The Nature of Security on RIO Systems.................................................................................248
Layers of Security.......................................................................................................................249
Security Vectors on RIO Systems.............................................................................................249
Best Practices for Security on RIO Systems..........................................................................250
CHAPTER 13
Using the LabVIEW for CompactRIO SampleProjects..............................................251
Overview of Sample Projects....................................................................................................251
Walk-Through of the LabVIEW FPGA Control on CompactRIO Sample Project........256
Create a New Sample Project...................................................................................................256
UI Main VI........................................................................................................................................270
Event Handling Loop..................................................................................................................270
UI Message Loop.......................................................................................................................272
Monitoring Loop..........................................................................................................................273
vi
CompactRIO Architecture
CompactRIO is a rugged, reconfigurable embedded system containing three components: a processor running a
real-time operating system (RTOS), a reconfigurable FPGA, and interchangeable industrial I/O modules. The realtime
processor offers reliable, predictable behavior and excels at floating-point math and analysis, while the FPGA excels at
smaller tasks that require high-speed logic and precise timing. Often CompactRIO applications incorporate a human
machine interface (HMI), which provides the operator with a graphical user interface (GUI) for monitoring the systems
state and setting operating parameters.
Sensors and
Actuators
I/O Modules
Real-Time
Processor
ADC
Signal
Conditioning
Signal
Conditioning
DAC
Signal
Conditioning
Signal
Conditioning
DI
Signal
Conditioning
Signal
Conditioning
DO
Signal
Conditioning
Signal
Conditioning
FPGA
PCI Bus
LabVIEW
LabVIEW is a graphical programming environment used by thousands of engineers and scientists to develop
sophisticated control systems using graphical icons and wires that resemble a flowchart. It offers integration with
thousands of hardware devices and provides hundreds of built-in libraries for advanced control, analysis, and data
visualizationall for creating user-defined systems more quickly. The LabVIEW platform is scalable across multiple
targets and OSs, and, in the case of CompactRIO, LabVIEW can be used to access and integrate all of the components
of the LabVIEW reconfigurable I/O (RIO) architecture.
Real-Time Controller
The real-time controller contains a processor that reliably and deterministically executes LabVIEW Real-Time applications
and offers multirate control, execution tracing, onboard data logging, and communication with peripherals. Additional
options include redundant 9 VDC to 30 VDC supply inputs, a real-time clock, hardware watchdog timers, dual Ethernet
ports, up to 2 GB of data storage, and built-in USB and RS232 support.
Run loops with nearly the same timing on each iteration (typically within microseconds)
Reliability
In addition to offering precise timing, RTOSs can be set up torun reliably for days, months, or yearswithout stopping.
This is important not only for engineers building systems that need 24/7 operation but also for any application where
downtime is costly. A watchdog feature is also typically included in real-time systems to automatically restart an
entire computer if the user program stops running. Furthermore, hardware used in a real-time system is often designed
to be rugged to sustain harsh conditions for long periods.
RTOSs on NI hardware
Each series of NI real-time targets runs on one of three different RTOSs. LabVIEW Real-Time provides a level of
abstraction that helps programmers largely ignore the details of the underlying RTOS. However, to offer context to
more advanced users, note that RTOSs on NI real-time targets include Phar Lap/ETS, VxWorks, and NI Linux Real-Time.
Learn more about the new Linux-based RTOS at ni.com/linux.
I/O Modules
I/O modules contain isolation, conversion circuitry, signal conditioning, and built-in connectivity for direct connection
to industrial sensors/actuators. By offering a variety of wiring options and integrating the connector junction box into
the modules, the CompactRIO system significantly reduces space requirements and field-wiring costs. You can choose
from more than 70 NIC Series I/O modules for CompactRIO to connect to almost any sensor or actuator. Module
types include thermocouple inputs; 10 V simultaneous sampling, 24-bit analog I/O; 24 V industrial digital I/O with up
to 1 A current drive; differential/TTL digital inputs; 24-bit IEPE accelerometer inputs; strain measurements; RTD
measurements; analog outputs; power measurements; controller area network (CAN) connectivity; and secure digital
(SD) cards for logging. Additionally, you can build your own modules or purchase modules from third-party vendors.
With the NIcRIO-9951 CompactRIO Module Development Kit, you can develop custom modules to meet applicationspecific needs. The kit provides access to the low-level electrical CompactRIO embedded system architecture for
designing specialized I/O, communication, and control modules. It includes LabVIEW FPGA libraries to interface with
your custom module circuitry.
Figure 4. You can choose from more than 50 NIC Series I/O modules for CompactRIO
to connect to almost any sensor or actuator.
SystemConfigurations
The simplest embeddedsystem consists of a single controller running in a headless configuration.This configuration
isused in applications that do not need an HMI except for maintenance or diagnostic purposes. However, most
control and monitoring applications require an HMI to display data to the operator or allow the operator to send
commands to the embedded system. A common configuration is 1:1, or 1 host to 1 target, as shown in Figure5.
The HMI communicates to the CompactRIO hardware over Ethernet through either a direct connection, hub, or
wireless router.
NI Touch Panel
Tablet
NI CompactRIO
PC
The next level of system capability and complexity is either a 1:N (1 host to N targets) or N:1 (N hosts to 1 target)
configuration. The host is typically either a desktop PC or an industrial touch panel device. The 1:N configuration,
shown in Figure 6, is typical for systems controlled by a local operator. The N:1 configuration is common when
multiple operators use an HMI to check on the system state from different locations.
NI Touch Panel
NI CompactRIO
NI CompactRIO
Complex machine control applications may have an N:N configuration with many controllers and HMIs (Figure 7).
They often involve a high-end server that acts as a data-logging and forwarding engine. This system configuration
works for physically large or complex machines. Using it, you can interact with the machine from various locations or
distribute specific monitoring and control responsibilities among a group of operators.
This guide walks through recommended implementations for a variety of FPGA, controller, and HMI architecture
components. It also offers example code and, in some cases, alternative implementations and the trade-offs
between implementations.
CHAPTER 1
Designing a CompactRIO
SoftwareArchitecture
Almost all CompactRIO systems have a minimum of three top-level VIs executing asynchronously across three
different targets: the FPGA, the real-time operating system (RTOS), and a host PC. If you begin your software
development without having some sort of architecture or flowchart to refer to, you may find keeping track of all of
the software components and communication paths to be challenging. Having a diagram that describes all of the
system pieces at a high level helps guide development and communication about the design with stakeholders. This
section describes several common CompactRIO architectures that you can use as a starting point for many
applications. You also can use them as a guide for creating your own architecture.
The example architectures in the following sections were created using a vector-based drawing program called the
yEd Graph Editor, which is a free design tool downloadable from yworks.com.
Processes
The first step in identifying the processes that your application will contain is to create a list of tasks that your application
needs to accomplish. Common tasks include PID control, data logging, communication to an HMI, communication to
I/O, and safety logic or fault handling. The next step is deciding how the tasks are divided into processes. An application
with a large number of processes requires more time to be spent on interprocess data communication. At the same
time, breaking your tasks into individual processes makes your program more scalable. For example, you might have a
real-time application during the first phase of a project that is communicating across the network to a user interface (UI)
built with LabVIEW, but later on the application needs to communicate to a web browser. If you separate the network
communication task from other tasks within the application, you can redesign your network communication process
without impacting your control process. More information on designing processes in LabVIEW Real-Time can be found
in Chapter 3: Designing a LabVIEW Real-Time Application.
Data Communication
Once youve diagrammed your processes, the next step is to identify data communication paths. Data communication
is one of the most important factors to consider when designing an embedded system. LabVIEW, LabVIEW Real-Time,
and LabVIEW FPGA include many different mechanisms for transferring data between processes on a single target
as well as processes that communicate across targets.
Choosing a data communication mechanism depends on several factors, with the primary factor being the data
communication model. Most CompactRIO applications can contain at least two or more of the data communication
models listed below:
Message/Command
Stream
Each model has different data transfer requirements. These models apply to both interprocess communication and
intertarget communication. Later chapters refer to these data communication types when recommending LabVIEW
mechanisms for data transfer between processes on a Windows target, real-time target, or FPGA target in addition
to communication between the CompactRIO device and a host PC.
Message/Command
Command- or message-based communication is something that happens relatively infrequently and is triggered by
some specific event. An example is a user pushing a button on an HMI to stop a conveyor belt. In message-based
communication, it is important to guarantee delivery of the message in a timely manner or with low latency. In the
previous example, when the operator pushes the stop button, the operator expects an immediate response (a
humans perception of immediate is on the order of tenths of a second). It is often desirable to synchronize a
process to the incoming message or command to conserve processor resources. This involves blocking until a
message is received or a timeout occurs.
Stream
Streaming communication is buffered and involves the high-throughput transfer of every data point, where throughput
is more important than latency. Typically, one process writes data to another process that reads, displays, or processes
that data. An example is an in-vehicle data logger that sends data from the FPGA to the RTOS for data logging.
Streaming often requires multilayer buffering, during which each end (the sender and the receiver) has its own uniquely
sized buffer. This is ideal when you have a processor loop that wants to read large chunks of data at a time and a DAQ
loop that writes smaller chunks of data at shorter intervals.
A summary of the different types of data communication models and their features is shown in Table 1.1. Keep these
features in mind when selecting a data communication model.
Communication Type
Fundamental Features
Optional Features
Performance
Message/Command
Low latency
Dynamic lookup,
group management
Low latency,
high-channel count
Stream
Multilayer buffering
High throughput
On the RTOS_Main.vi, the communication task and control task are designed as two separate loops. This is generally
a good practice since the network communication could impact the determinism of the control algorithm if the tasks
are executed within a single loop. Also, the modularity makes it easier to simulate parts of the system. For example,
you could easily swap out the actual control loop with a simulated control loop to test the network communication.
Embedded Monitoring
Embedded monitoring applications typically require data to be streamed at high rates from the C Series I/O modules
up to a host user interface where the data is displayed to an operator. The user interface also allows the operator to
configure the hardware, which requires a mechanism for sending commands from the host down to the RTOS.
10
The turbine testing system used in this example has the following software requirements:
Monitor the revolutions per minute (rpm) of the turbine using a tachometer
11
Display the temperature, tachometer velocity (rpm), accelerometer data, and frequency of the accelerometer
data to the UI
To create an architecture for the turbine testing system, start with the control and monitoring architecture shown in
Figure 1.8.
Figure 1.8. Common Software Architecture for Control and Monitoring Applications
This application was implemented in Hybrid Mode, and uses both the RIO Scan Interface and LabVIEW FPGA
Module. LabVIEW FPGA is used for the following tasks:
Turbine Speed ControlThis loop generates a PWM signal to control the turbine speed based on the duty
cycle (%) and period (mS) communicated from the LabVIEW Real-Time VI.
Accelerometer and Tachometer AcquisitionThis loop takes in the start trigger and acquires data from the
tachometer and accelerometer until it reaches the specified number of samples. It also streams the sensor
data to the LabVIEW Real-Time VI using a DMA first-in-first-out (FIFO) memory buffer.
Data Acquisition and Analysis (High Priority)This loop communicates with the Accelerometer &
Tachometer Acquisition Loop in the LabVIEW FPGA VI. It sends a trigger to begin the finite acquisition,
retrieves accelerometer data from the DMA FIFO, and sends the collected and analyzed data to the user
interface for display. It also retrieves tachometer data and converts it to revolutions per minute.
Turbine PWM CharacteristicsThis loop monitors the temperature, and if it rises above the maximum limit,
it shuts down the turbine.
Message HandlerThis loop receives any UI commands and distributes them to the appropriate real-time or
FPGA process.
12
Command ParserThis loop uses a Network Stream to receive commands from the user interface over
Ethernet. The commands are placed into a Queue and sent to the Message Handler loop for distribution.
The User Interface VI runs on a Windows machine and allows the user to view data and interact with the
CompactRIO system. It has the following tasks:
UI Event HandlerThis process handles user events with Event Structures such as Stop and
TriggerAcquisition.
Command SenderThis process sends any commands received from the UI Event Handler to
theCompactRIO controller using a Network Stream.
UI UpdateThis process receives the latest temperature value, accelerometer value, accelerometer
frequency, and tachometer velocity and displays them to the user interface.
To view the actual turbine testing application, download the Turbine Testing Example from Section 1 Downloads.
Chapter3: Designing a LabVIEW Real-Time Application describes the real-time VI within the application in
moredetail.
In addition to the turbine testing example, LabVIEW 2012 and later includes several architectures similar to the ones
discussed in this guide that you can use as starting points for your application. These architectures are called
CompactRIO sample projects and they are listed below.
LabVIEW Supervisory Control and Data Acquisition Sample Project (LabVIEW 2013 and later)
13
CHAPTER 2
Choosing a CompactRIO ProgrammingMode
The CompactRIO architectures presented in Chapter 1 provide you with the option to implement your I/O by customizing
the FPGA hardware through LabVIEW FPGA or by using NI CompactRIO Scan Mode. If you have LabVIEW Real-Time
and LabVIEW FPGA on your development computer, you are prompted to select which programming mode you would
like to use when you add a CompactRIO target to your LabVIEW project. Upon selecting a mode, you can also go into
Hybrid Mode if you want to use a hybrid of LabVIEW FPGA and CompactRIO Scan Mode for your application.
Figure 2.1. If you have LabVIEW FPGA installed, you are prompted to select a programming
mode
when adding a CompactRIO system to your LabVIEW project.
14
Hybrid Mode
Using the CompactRIO Scan Mode and LabVIEW FPGA at the same time on a target is known as Hybrid Mode. With
this approach, the modules you select to program directly with LabVIEW FPGA are removed from the I/O scan, and
the remaining modules communicate with the RIO Scan Interface. Note that the RIO Scan Interface uses two of the
three DMA channels that are normally available for use in LabVIEW FPGA.
This section offers tips on choosing a programming mode for your CompactRIO application. You should choose a
programming mode based on your application requirements for performance, reliability, customization, and I/O. The
NI LabVIEW for CompactRIO Developers Guide discusses programming techniques and best practices for both
LabVIEW FPGA programming and the RIO Scan Interface use.
Figure 2.2. With LabVIEW FPGA, you can create custom FPGA VIs for high-speed data
acquisition,
control loops, or custom timing and triggering.
15
hardware circuitry. Because there is no OS on the FPGA chip, the code is implemented in a way that ensures
maximum performance and reliability.
High-Speed Waveform Acquisition/Generation (>500 Hz)
The RIO Scan Interface is optimized for control loops running at less than 500 Hz, but many C Series I/O modules are
capable of acquiring and generating at much higher rates. If you need to take full advantage of these module features
and acquire or generate at speeds higher than 500 Hz, you can use LabVIEW FPGA to acquire at a user-defined rate
tailored to your application.
Custom Triggering/Timing/Synchronization
With the reconfigurable FPGA, you can create simple, advanced, or otherwise custom implementations of triggers,
timing schemes, and I/O or chassis synchronization. These can be as elaborate as triggering a custom CAN message
based on the rise of an analog acquisition exceeding a threshold or as simple as acquiring input values on the rising
edge of an external clock source.
Hardware-Based Analysis/Generation and Coprocessing
Many sensors output more data than can be reasonably processed on the real-time processor alone. You can use the
FPGA as a valuable coprocessor to analyze or generate complex signals while freeing the processor for other critical
threads. This type of FPGA-based coprocessing is commonly used in applications such as:
Encoding/decoding sensors
Tachometers
Data reduction
Third-party IP integration
Sensor simulation
Hardware-in-the-loop simulation
16
I/O Variables
LabVIEW
Real-Time VI
FPGA
NI Scan Engine
I/O Memory
Table
RIO Scan
Interface
I/O Modules
LabVIEW Real-Time
I/O Modules
Figure 2.3. Block Diagram Description of the RIO Scan Interface Software Components
When deciding to use Scan Mode for a CompactRIO application, you should consider the required performance or
loop rates and channel count. The graph in Figure 2.4 shows benchmarking that was completed using Scan Mode for
a PID control loop, including one analog input and one analog output. The data shows that PID loop rates higher than
100 Hz combined with a high-channel count have a significant impact on CPU usage. Generally, you should not use
Scan Mode when you require loop rates faster than 500 Hz.
17
Figure 2.4. When using the RIO Scan Interface, high-channel counts combined with
high-loop rates have a significant impact on CPU.
Although you should not use Scan Mode for high-speed data acquisition or control loops, it does offer several benefits:
Ease of ProgrammingDrag and drop your I/O variables directly into your LabVIEW Real-Time VI during
development.
Ability to Dynamically Detect I/O ModulesSlots not configured through the project automatically detect
inserted modules. You can then configure these modules through the variable API.
Fault EngineThe NIScan Engine features the built-in NIFault Engine that throws errors deterministically.
Diagnostics and DebuggingWith the Distributed System Manager, you can view current values and faults
as well as override current I/O values while your program is running.
Not all CompactRIO hardware works with NI Scan Mode. For a list of C Series I/O modules that feature Scan Mode
support, see C Series Modules Supported by CompactRIO Scan Mode. CompactRIO targets with 1M gate FPGAs
cannot fully support the scan interface. You can implement some scan interface features on unsupported targets,
but you must use LabVIEW FPGA.
18
Figure 2.5. Drag and drop I/O variables onto your Real-Time VI block diagram.
The Scan Engine also provides a Timed-Loop timing source, so you can synchronize code with I/O updates for low-jitter
control applications.
Figure 2.6. Use a Timed Loop with the clock source set to Synchronize to Scan Engine
to synchronize the loop to I/O updates.
You can find example programs for using Scan Mode at \LabVIEW\examples\ScanEngine.
19
When programming in Scan Mode, another option for interfacing to I/O variables is through the I/O Variable
programmatic API, shown in the Figure 2.7. The programmatic API offers several benefits over the static I/O Variable
Node API:
You can iterate through multiple variables at once without dropping down a large number of I/O Variable Nodes
Deployment to a CompactRIO target is less complicated since the items are not bound to a LabVIEW project
You can change I/O variable configuration settings while running an application, and configuration settings are
viewable on the block diagram
While the programmatic API offers several advantages, it does require more programming. The I/O Variable programmatic
API can be found in the LabVIEW functions palette under Data CommunicationShared VariableI/O Variable.
When deploying Scan Engine I/O variables to a CompactRIO controller, note that these variables have the potential
to take up a significant portion of the CPU bandwidth. If you deploy a chassis in Scan Mode that physically contains
all the modules you want to use, it publishes a variable called PercentHWScanUtilization. This value tells you what
percentage of CPU bandwidth is dedicated to reading or writing I/O variables based on your scan time and deployed
hardware. Based on this, you have an idea of how much time can be dedicated to other processes.
Figure 2.8. Monitor the CPU bandwidth that is used for reading and writing to Scan Engine I/O
variables.
20
Figure 2.9. After activating Hybrid Mode, write an FPGA VI to interface with the module
and pass data to the real-time host.
In Hybrid Mode, you can continue using the RIO Scan Interface on some modules while programming others directly
on the FPGA. You can use the FPGA programming model to handle high-speed operations, inline processing,
waveform buffered acquisition, and certain modules that do not feature Scan Mode support. Activate FPGA
programming for a particular module by dragging and dropping the module project item from under the CompactRIO
chassis to under the FPGA target. By doing this, you can program the FPGA for custom code running in parallel with
the scan interface for other modules. You can access the FPGA I/O from the real-time VI by using either the FPGA
Host Interface Functions or User-Defined Variables.
21
Figure 2.10. Activate FPGA programming for a particular module by dragging and dropping the
module project item from under the CompactRIO chassis to under the FPGA target.
You need to note a few important limitations when using Hybrid Mode. First, the compile time significantly increases
because the compiler has to combine the default RIO Scan Interface bitfile as well as the FPGA code that was
created into one bitfile. Secondly, the number of DMA channels that you can use in the FPGA code is reduced since
the Scan Engine uses two channels. Most FPGAs have three DMA channels, so most applications have only one
DMA channel left to use in the FPGA code.
22
CHAPTER 3
Designing a LabVIEW Real-Time Application
When creating a LabVIEW Real-Time application for CompactRIO, start with a design diagram as described in
Chapter 1: Designing a CompactRIO Software Architecture. If you begin your software development without having
some sort of architecture or flowchart to refer to, you may have difficulty keeping track of all software components
and communication paths. Once you have created a design diagram, the next step is to implement your LabVIEW
Real-Time code.
Figure 3.1. Creating a top-level VI with the general structure of the program filled out is
a good starting point for developing a LabVIEW Real-Time application.
Once you have designed your top-level RTOS VI, the next step is to implement each of your processes. This chapter
provides best practices for designing processes in LabVIEW Real-Time, including deterministic versus nondeterministic
processes, interprocess data communication, design patterns, and memory management.
23
Figure 3.2. Jitter is the measure of how much the execution time of
a task differs over subsequent iterations.
CompactRIO helps you bound the amount of jitter, which may be a requirement for mission-critical applications. You
can choose from two options for designing a deterministic application with one or more processes that require a
hard bound on the amount of jitter:
1. Implement critical tasks using LabVIEW FPGASince your LabVIEW FPGA code is running in hardware
rather than within an OS, you can guarantee that a critical task does not crash or hang. An RTOS is more
deterministic and reliable than a general-purpose OS, but it is still subject to software crashes if not
programmed correctly.
2. Implement critical tasks using Timed Loops in LabVIEW Real-TimeSlightly more complex than a While
Loop, a Timed Loop is designed to execute deterministic tasks with minimal jitter.
The next section describes implementing deterministic processes using Timed Loops and VI priorities. If your
application does not contain any tasks that require bounded jitter, use While Loops with timing functions instead of
Timed Loops. Timed Loops offer many useful built-in features but also involve more overhead and complexities than
While Loops. You can benefit from the reliability of an RTOS without using Timed Loops, but you cannot place a
bound on or minimize jitter.
24
Nondeterministic Tasks
Closed-loop control
File I/O
Decision-making logic
Safety logic
25
Timed Loops
A Timed Loop is similar to a While Loop but includes additional features for executing code deterministically. With a
Timed Loop, you can specify the period and priority at which your code executes. The higher the priority of a Timed
Loop, the greater the priority the structure has relative to other timed structures on the block diagram. The Timed
Loop on your block diagram with the highest priority is referred to as your time-critical loop. You can configure the
priority and period dynamically on the block diagram or through a configuration window that you launch when you
double-click the left input node on the Timed Loop.
Figure 3.3. You can specify the period and priority of a Timed Loop through
the Timed Loop configuration dialog.
When using Timed Loops on an RTOS, timing is important. When a time-critical loop is called, it is the only loop on
the block diagram that executes. If a time-critical loop is set to run 100 percent of the time and never go to sleep, it
completely monopolizes one core of your system. Be sure to specify a period that is reasonable for your time-critical
loop but allows other background tasks within your application to execute.
One way to prevent undesired timing behavior is to create a time budget for your application. Time budgeting involves
determining the amount of time required to execute each loop in the application and setting the rates of the loops
accordingly. Your timing budget should restrict your application to using no more than 80 percent of the available CPU.
Find instructions for creating a time budget in the LabVIEW Real-Time Help file Avoid Jitter (Real-Time Module).
26
VI Priorities
You can also set the priority of a deterministic section of code by placing it within a subVI and modifying the VI
priority through the VI Properties dialog as shown in the Figure 3.4.
Figure 3.4. You can specify the priority of a VI through the VI Properties dialog
under the Execution category.
Try to avoid using Timed Loops and VI priorities in the same application. If you must use both, you should have a solid
understanding of how they relate. If you have a VI with a priority that contains a Timed Loop with a priority, the Timed
Loop ignores the VI priority. In comparison to the VI priorities shown in Figure 3.4, Timed Loops execute at just below
time-critical priority (highest) and at just above VIs with high priority. VIs with time-critical priority settings take
precedence over Timed Loops. The While Loop executes at normal priority.
To understand how LabVIEW schedules parallel tasks based on priority, Figure 3.5 summarizes the priorities and
execution systems available. An execution system is a pool of related threads. More information can be found in the
LabVIEW Real-Time Help document Understand the Priority-Based Scheduling Model.
27
Above
Time-Critical
NI Scan
Engine
Thread
Execution Systems
1 Thread
Per CPU
Time-Critical
1 Thread
Per CPU
1 Thread
Per CPU
1 Thread
Per CPU
1 Thread
Per CPU
1 Thread
Per Timed
Structure
Priority
Timed
Structure
High
Above
Normal
Normal
Numerous
Threads of
Various
Priorities
1 Thread
Per CPU
Background
System
Threads
User
Interface
4 Threads
Per CPU
4 Threads
Per CPU
4 Threads
Per CPU
4 Threads
Per CPU
1 Thread
Per CPU
4 Threads
Per CPU
4 Threads
Per CPU
4 Threads
Per CPU
4 Threads
Per CPU
1 Thread
Per CPU
4 Threads
Per CPU
4 Threads
Per CPU
4 Threads
Per CPU
4 Threads
Per CPU
1 Thread
Per CPU
4 Threads
Per CPU
4 Threads
Per CPU
4 Threads
Per CPU
4 Threads
Per CPU
1 Thread
Per CPU
Standard
Instrument
I/O
Data
Acquisition
Other 1
Other 2
Timed
Structure Threads
For more information on creating subVIs, see the video Creating SubVIs in NI LabVIEW.
28
Description
Current Value
(Tag)
Streaming
RT FIFOs
RT FIFOs
Command-/
Message-Based
Queues
RT FIFOs
Note that the transfer type is only one of the considerations when choosing a data communication mechanism. You
may have valid use cases for implementing an update using a command-based mechanism or vice versa based on
the other considerations mentioned such as ease of implementation, scalability, or performance. The next section
offers best practices for implementing each type of communication model in LabVIEW Real-Time.
Figure 3.7. You can use single-process shared variables for variable communication
between multiple processes.
29
To create a single-process shared variable, right-click a real-time target in the Project Explorer window and select
New Variable from the shortcut menu. In the Shared Variable Properties dialog box, you can set the variable type
as Single Process (a single-process shared variable is a global variable).
If your application contains a relatively large number of variables and you require tag management features such as
dynamic tag lookup, you should consider the current value table described below, which is designed to handle a
large number of tags efficiently.
Since single-process shared variables are based on global variables, they act as a shared resource, which can
introduce jitter if used within a time-critical loop. If you are interested in using single-process shared variables within
a time-critical loop, be sure to enable RT FIFOs in the variable properties dialog. Single-process shared variables with
RT FIFOs enabled are discussed in the upcoming section titled RT FIFOs.
30
The basic API writer example is shown in Figure 3.10. In the API call, the variable name is used to look up the index
of the variable, and then the value is accessed from the CVT using the index. This example assigns random number
data to Var0Var4 tags and writes to the Stop and Index tags. You can initialize the tags using a cluster array, as
shown in Figure 3.10, or load them from a file using the CVT Load Tag List VI.
The Basic CVT Reader example in Figure 3.11 reads the current value of the tags within another instance of the
application. Both examples use the Format Into String function to dynamically look up Var0Var4 tags.
You can find more information on the CVT in the NIDeveloper Zone document Current Value Lookup Table
Reference Library.
Instructions for Installing the CVT Library
Step 1: Navigate to ni.com/labviewtools
Step 2: Download and install the VI Package Manager
Step 3: Within VI Package Manager, search for CVT
31
Queues
Queues are the recommended protocol for command- or message-based communication between two nondeterministic
processes because they are flexible, easy to use, and allow you to transfer buffered data. When sending messages,
you might need to send multiple data types within a single packet. Queues support the Cluster data type, which you
can use to bundle together different data types, both fixed size and variable size such as strings. You can use queues
on both real-time and Windows OSs.
The block diagram in Figure 3.12 shows a loop that performs a data acquisition task. The data acquisition loop shares
the acquired data with the second loop using queues. The second loop logs the acquired data that it reads from the
queueto disk on the real-time target.
Figure 3.12. You can use queues to transfer buffered data between two nondeterministic loops.
The Queue Operations palette is included in LabVIEW on the Functions palette under SynchronizationQueue
Operations. You can find example programs using queues in the NIExample Finder.
RT FIFOs
RT FIFOs are first-in-first-out memory buffers that behave deterministically. You can implement them using RT FIFO
functions that are similar to the Queue functions, or with an RT FIFO-enabled shared variable. Both mechanisms are
the same under the hood. While RT FIFO-enabled shared variables have a simpler implementation than RT FIFO
functions, RT FIFO functions give you more control. For example, with RT FIFO functions, you can decide when the
FIFOs are created and when they are shut down. A shared variable is automatically created when it is first called, and
it is shut down when the application is stopped. You also have control over configuration options such as polling versus
blocking for optimizing performance, and you can use more complex data types such as clusters (as long as they
contain fixed-size elements). This section discusses both RT FIFO functions and RT FIFO-enabled shared variables.
32
RT FIFO Functions
RT FIFO functions are similar to Queue functions but are less flexible and more deterministic. They are recommended for
streaming data between any two processes on an RTOS because they always preallocate memory and have a maximum
buffer size. RT FIFOs are also recommended for transferring commands or messages to or from a time-critical loop. They
provide a deterministic data transfer method that does not add jitter. Queues and RT FIFOs differ in the following ways:
Queues can handle string, variant, and other variable size data types, but RT FIFOs cannot.
RT FIFOs are fixed in size, so they can communicate data between Timed Loops without dynamically allocating
new memory. Queues can grow as elements are added to them.
Queues use blocking calls when reading/writing to a shared resource, which can block another loop from
running and impact determinism. RT FIFOs do not use blocking calls.
RT FIFOs execute regardless of errors at input to maintain determinism; queues do not execute on error.
The block diagram in Figure 3.13 is similar to the previous example using queues, but since the data acquisition loop
is now deterministic, you use RT FIFO functions to share data. The deterministic loop with a priority of 100 shares
the acquired data with the nondeterministic loop using an RT FIFO function. The nondeterministic loop logs the
acquired data that it reads from the RT FIFOto disk on the real-time target. You can download a more advanced
example of RT FIFOs from Chapter 4: Best Practices for Network Communication.
Figure 3.13. You can use RT FIFOs to transfer buffered data to or from a time-critical loop.
Because of the fixed-size restriction, an RT FIFO can be a lossy communication method. Writing data to an RT FIFO
when the FIFO is full overwrites the oldest element. You must read data stored in an RT FIFO before the FIFO is full
to ensure the transfer of every element without losing data. Check the overwrite output of the RT FIFO Write
function to ensure that you did not overwrite data. If the RT FIFO overwrites data, the overwrite output returns a
TRUE value.
The RT FIFO palette is included in LabVIEW Real-Time on the Functions palette under LabVIEW Real-TimeRT FIFO.
You can find example programs featuring RT FIFOs in the NIExample Finder.
33
Figure 3.14. You can use RT FIFO-enabled shared variables to transfer buffered data
to or from a time-critical loop.
To enable the RT FIFO on a shared variable, navigate to the RT FIFO page of the Shared Variable Properties dialog
box and place a checkmark in the Enable Real-Time FIFO checkbox.
34
Figure 3.15. By enabling the RT FIFO, you can read and write to a shared variable
from multiple parallel loops without inducing jitter.
Use a single-element RT FIFO to transfer the latest values (tags or updates) and use a multi-element RT FIFO to
transfer the buffered values (messages or streams). A multi-element FIFO features a buffer for which each write adds
another element to the buffer and each read removes an element from the buffer. As long as the consumer loop checks
the FIFO frequently, you can leave the buffer at the default of two elements and not miss any triggers/commands.
To check the FIFO, the consumer task must read the shared variable and check the error status. If the FIFO is empty,
the shared variable returns the warning -2220. If this warning is not returned, then the FIFO was not empty and the
returned value is a valid command.
Each time the shared variable is read, one element is removed from the FIFO (assuming the FIFO is not empty).
Because of this, you cannot have multiple consumers receive a command from the same FIFO, but you can have
multiple commanders putting commands into the FIFO.
Greater reliability
Easier debugging
Enhanced maintainability
Before viewing some common design patterns, you need to understand your options for synchronizing loops in
LabVIEW Real-Time. Synchronization is the foundation of any design pattern.
35
Periodic Loop
A periodic loop runs continuously at a defined period. The Turbine PWM Characteristics loop in the turbine testing
application is periodic. This loop, shown in Figure 3.16, executes at a period of 100 ms or 10 Hz. It uses variables for
communication. Be careful not to add any functions that would introduce blocking or other types of synchronization
(for example, queues with no timeout) when designing period loops.
Figure 3.16. The Turbine PWM Characteristics loop in the turbine testing application executes
periodically.
You also can implement periodic loops for a higher priority task by using a Timed Loop, similar to the Data Acquisition and
Analysis loop. You generally should use Timed Loops only when implementing a periodic task since any type of blocking
introduces jitter.
Event-Driven Loop
An event-driven loop executes only when an event occurs. Often the event is receiving a message from another
process. The message loop in the turbine testing application is event driven. In the command parser example, the
synchronization source is the Dequeue Element function. The timeout is set to default (-1), which means the function
never times out and the loop executes only when a command is received from the host. Other commonly used
functions that force an event-driven architecture include the following:
Queues
Notifiers
RT FIFOs
Network Streams
36
When using an event-driven design pattern, you can block until a message is received or until a timeout occurs.
When blocking with no timeout, you are efficiently using the CPU, but you are also preventing any background tasks
from running. If you add a timeout to any of these functions, you can have a timeout state during which you can
execute background tasks while waiting on messages.
Scheduled Loop
A scheduled loop executes at an absolute time. An example is a maintenance routine that executes every day at
midnight. This type of synchronization is less common.
Design Patterns
The design patterns common in LabVIEW Real-Time applications are similar to those used in LabVIEW for Windows
applications. This section examines two design patterns: state machine and producer consumer.
State Machine
A state machine is a common and useful design pattern. You can use a state machine to implement any algorithm that
can be explicitly described by a state diagram or flowchart. A state machine usually illustrates a moderately complex
decision-making algorithm, such as a diagnostic routine or a process monitor. To learn the basics of the state machine
architecture in LabVIEW, see the NIDeveloper Zone document Application Design Patterns: State Machine.
Producer Consumer
A producer consumer design pattern is used to transfer data between processes that produce and consume data at
different rates. On Windows OSs, a producer consumer is commonly implemented with Queue functions. In
LabVIEW Real-Time, it can be implemented with Queues or RT FIFOs. You can implement a producer consumer
design pattern so that it shares data between two loops or it shares events.
Data-Sharing Producer Consumer
Use a data-sharing producer consumer design pattern when you need to execute a process such as data analysis,
when a data source, such as a triggered acquisition, produces data at an uneven rate and you need to execute the
process when the data becomes available.
37
38
EFFECT
Embedded hardware targets are typically much more resource constrained than desktop PCs. Disk space, RAM, and
CPU bandwidth are typically limited. Because of this, you need to monitor these resources when developing and
testing applications to ensure that you do not run into limits that introduce negative side effects. This section
discusses tools and techniques to help you overcome constrained hardware resource issues.
Disk Space
Lost Data
RAM
RAM
CPU Bandwidth
Starvation
Figure 3.19. Disk space, RAM, and CPU bandwidth are typically limited in embedded
application design.
39
Figure 3.20. Check free disk space and memory within MAX.
To programmatically obtain the free disk space, use the Get Volume Info function when targeted to the controller.
You can find this function on the Advanced File Functions palette (ProgrammingFile I/OAdvanced File
FunctionsGet Volume Info).
Memory Preallocation
One type of memory preallocation occurs when memory is allocated for memory stored in the data space of your VI. If
you attempt to preallocate more memory than what is available, you receive an error message during deployment or your
VI terminates at the beginning of execution.
40
Fixed-size memory that is allocated during initialization is also included in this category since it does not affect
fragmentation or engage the memory manager after the first call. A common example of a fixed-size memory allocation is
the allocation of a large array, similar to the block diagram shown in Figure 3.22.
If your LabVIEW code does not fit onto your real-time target, or you find that you are allocating more fixed-size
memory than what is available during initialization, you can take one of the following actions:
Once you know where LabVIEW creates buffers, you might be able toedit the VI to reduce the amount of
memoryLabVIEW requires to run the VI. For tips on reducing memory copies, see the NIHelp document
VI Memory Usage starting at the section Determining When Outputs Can Reuse Input Buffers.
41
Figure 3.24. Uninstall software drivers that you are not using to increase memory.
42
Avoid memory leaks by closing all of the references that you open during initialization. It is also a safe practice to
replace the terminals of any reference with shift registers.
Avoid Overallocation by Using Fixed-Size Data
Overallocation occurs when the program tries to store too much data in RAM. It typically results from a queue or
buffer without a fixed size. The graph in Figure 3.25 shows a situation where a buffer is expanding. Note that once a
buffer expands, it generally does not contract. The buffer could be getting periodically emptied as the code runs, but
it still retains the size of its largest value.
Variable-sized strings
Variants
Two methods for sharing data between processes on a real-time target are discussed in this chapter. By default,
queues have a variable-sized buffer. Even with a fixed number of elements, a queue that contains variable-sized data
(strings, variants) is still variable sized. This is also true for Network Streams and shared variables. If you are working on
an application for which dynamic memory allocation is a concern, use RT FIFOs for transferring data between
processes. RT FIFOs limit you to a fixed-sized buffer and fixed-sized data types.
43
Figure 3.26. Memory on an RTOS becomes fragmented over time, making it difficult for the
memory manager to locate a large block of contiguous memory.
You can keep your contiguous memory healthy by minimizing dynamic memory allocations and preallocating space
for arrays equal to the largest expected array size. Figure 3.27 shows how you can preallocate memory for an array
by using the Initialize Array and Replace Array Subset functions. The array is created only once and Replace Array
Subset can reuse the input buffer for the output buffer. You should preallocate an array if you can determine the
upper size limit of the array.
44
Figure 3.28. Programmatically monitor memory with the NI System Configuration API.
You should also include a safe shutdown routine that performs the following functions:
Check out the NIDeveloper Zone document Fail-Safe Control Reference Design for more information on this topic.
You can also monitor the memory usage using the NIDistributed System Manager in LabVIEW under the Tools menu.
45
Figure 3.29. Monitor CompactRIO memory usage with the NIDistributed System Manager.
Figure 3.30. Monitor CPU usage with the RT Get CPU Loads VI.
46
47
Figure 3.31. An application periodically resets the watchdog timer when the application
responds on time.
If a software failure prevents the application from resetting the timer, the timeout eventually expires because the
hardware counter is independent of the software and thus continues to count down until it reaches zero. When the
watchdog timer expires, the hardware triggers the recovery procedure, as shown in Figure 3.32.
Figure 3.32. The hardware timer triggers a recovery procedure when the watchdog timer
expires.
When preparing your embedded system for deployment, you can choose from two options for implementing a
hardware-based watchdog timer within LabVIEW. You can access the built-in watchdog hardware that is available in
all CompactRIO and NI Single-Board RIO controllers using the LabVIEW Real-Time Module, or you can implement
your own watchdog timer using the LabVIEW FPGA Module. If you are writing to any hardware outputs from your
LabVIEW FPGA VI, it may be beneficial to implement your watchdog timer in LabVIEW FPGA. If something goes
48
wrong, you can immediately and reliably put all of your hardware outputs into a safe state. Each option is described
in more detail in the following sections.
Figure 3.33. The RT Watchdog API interfaces with a hardware counter that is built-in to
CompactRIO and NISingle-Board RIO controllers.
When programming with the RT Watchdog API, you first need to configure the watchdog and set a timeout value.
The appropriate range of timeout values depends on the specific performance characteristics and uptime requirements
of the embedded application. You must set the timeout long enough so that it does not expire due to acceptable
levels of system jitter. However, you must set the timeout short enough so that the system can recover from failure
quickly enough to meet system uptime requirements. In Figure 3.34, the watchdog timeout is set to 10 seconds.
Next you need to configure the expiration actions. Specifically, you must determine how you want the system to
respond to a watchdog timeout. You have the option to reset the target or trigger an occurrence, which can be used
to execute another piece of code if your watchdog loop becomes unresponsive. More information can be found in the
LabVIEW Real-Time Help File titled Watchdog Configure VI.
Figure 3.34. Configure the timeout value and expiration actions with the Watchdog Configure.
vi.
Finally you want to whack or pet the watchdog periodically. Every time you whack the watchdog, you are resetting
the watchdog timer. If something in your system causes the watchdog loop to become unresponsive (low memory,
49
low CPU bandwidth, and so on), the watchdog timer does not reset and you can recover your system based on the
expiration actions that you defined during initialization. It is important to note that the watchdog timer does not start
until the Watchdog Pet.vi or the Watchdog Start.vi has been executed.
Figure 3.35. Configure the timeout value and expiration actions with the Watchdog Configure.vi
Figure 3.36. Define failure conditions within LabVIEW FPGA when implementing safe states.
You can use the following two reference designs to help you implement a LabVIEW FPGA based watchdog timer and
safe states:
The Fail-Safe Control Reference Design for CompactRIO white paperThis reference design written by
NISystems Engineering provides a framework that demonstrates FPGA safe states and FPGA-monitored
watchdogs for the real-time controller.
The LabVIEW FPGA Control Sample ProjectThis Sample Project included in LabVIEW 2012 is based on the
Fail-Safe Control Reference Design linked above.
50
Software Watchdogs
Along with implementing hardware-based watchdogs, you can implement software-based watchdogs. The Fail-Safe
Control Reference design has multiple software loops check-in with a software watchdog loop in addition to a LabVIEW
FPGA-based watchdog. If any of these loops becomes unresponsive, the software watchdog can take action to fix it or
reboot the system. This software watchdog loop then checks in with the hardware watchdog in case something happens
to it or to the entire system.
Figure 3.37. A software watchdog can take action if any loops become unresponsive and check
in with the hardware watchdog in case something happens to the entire system.
51
CHAPTER 4
Best Practices for Network Communication
Network Communication
For embedded CompactRIO applications, communication with a remote client is often a critical part of the project.
Embedded applications typically function as data servers because their primary role is to report information (status,
acquired data, analyzed data, and so on) to the client. They are also usually capable of responding to commands from
the client to perform application-specific activities.
Ethernet
Host PCs
Communication Model
The communication models discussed in chapters 1 and 3 pertain to both interprocess communication and network
communication. These models are current value data (tags), updates, streaming, and command-/message-based
communication. Understanding the type of data transfer you need is the most important consideration when choosing
a networking mechanism. Table 4.1 provides examples of when you might use current value data (tags), updates,
streaming, or command-based data communication for networked applications.
52
Communication
Model
Description
Example
Updates
Streaming
Message/
Command
Network Configuration
The network configuration is another important consideration. In multiclient applications, clients may connect and
disconnect at random times. The TCP/IP protocol requires you to implement a connection manager to dynamically
accept and service any number of incoming connections in addition to tracking client requirements and servicing
each client individually. While this is possible, it requires a decent amount of work on the development side. On the
other hand, network-published shared variables feature the Shared Variable Engine with a built-in connection manager,
which handles any incoming client connections for you. Since TCP/IP Messaging (STM) and CVT Client Communication
(CCC) are both based on TCP, they also require you to develop a connection manager.
Network Streams also require some additional development when using them within a 1:N or N:1 configuration
because they are implemented as a point-to-point communication model. This means that an application based on
Network Streams that connects to 10 clients requires at least 10 streams. However, since Network Streams are the
most reliable and easy-to-use mechanism for streaming data, they are still a good choice for streaming. For
messages and commands, consider using shared variables over Network Streams.
Figure 4.2. Consider your system configuration when choosing a networking protocol.
Shared Variables
No
NILabWindows/CVI and
Measurement Studio only
No
Yes
53
LabVIEW Version
Several of the data transfer mechanisms recommended in Table 4.3 do not work in all versions of LabVIEW:
If you have selected one of these three mechanisms but are not using a compatible version of LabVIEW, use the
mechanism recommended for the same communication model and network configuration that can communicate
with a third-party UI.
Security
If you require security features such as built-in encryption and authentication, use HTTPS-based web services to
implement communication. Web services support data communication to LabVIEW UIs, third-party UIs, and web
browsers. If you are using the web server on NIs real-time targets to implement HTTPS communication, consider
enabling the web services API keys for added security. To learn more about security with LabVIEW web services,
refer to the Configuring Web Services Security LabVIEW Help document.
54
Network Configuration
Message or
Command
Update
Stream
Network Streams
(flushed)
Shared Variable
(blocking)
Network
Streams
Network-Published Shared
Variable or CCC
1:1 (CompactRIO to
Third-Party UI)
Simple TCP/IP
Messaging (STM)
UDP
TCP/IP
Network Streams
(flushed)
Shared Variable
(blocking)
Network
Streams
Network-Published Shared
Variable or CCC
Simple TCP/IP
Messaging (STM)
UDP
TCP/IP
Web Services
Web Services
Web Services
Web Services
The next section explains how to implement each of the networking protocols described in Table 4.3 and features
instructions for downloading and installing the protocols that are not included in LabVIEW.
Figure 4.3. Network shared variables are ideal for tag communication in a 1:N or N:1
configuration.
Three important pieces make the network variable work in LabVIEW: network variable nodes, the Shared Variable
Engine, and the NIPublish-Subscribe Protocol.
55
56
Figure 4.6. Ensure that buffering is disabled when using shared variables for tag
communication.
Determinism
Network-published shared variables are extremely flexible and configurable. You can create a variable that features a
real-time FIFO to include a network communication task within a time-critical loop. When you do this, LabVIEW
automatically runs a background loop to copy the network data into a real-time FIFO, as shown in Figure 4.7. Keep in
mind that this prevents jitter from occurring within the time-critical loop while performing network communication,
but it does not mean that the network communication itself is deterministic.
57
Figure 4.7. When you enable the real-time FIFO for network-published shared variables, a
hidden background loop runs on the real-time target to copy the network value into a real-time
FIFO.
This feature can simplify your program, but it has some limitations:
Some capabilities of network-published shared variables are not available when you enable the real-time FIFO
Error management is more difficult because network errors are propagated to the individual nodes throughout
the program
Future modification of the program to use different network communications is more difficult
Another option for applications that involve both network communication and a time-critical loop is to use regular
network-published shared variables for network communications and maintain a separate loop for network
communication tasks. You can communicate between these two loops using the interprocess communication
mechanisms discussed in Chapter 3: Designing a LabVIEW Real-Time Application.
Lifetime
All shared variables are part of a project library. By default, the Shared Variable Engine deploys and publishes that
entire library of shared variables as soon as you run a VI that references any of the contained variables. Stopping a VI
does not remove the variable from the network. Additionally, if you reboot a machine that hosts the shared variable,
the variable is available on the network again as soon as the machine finishes booting. If you need to remove the
shared variable from the network, you must explicitly undeploy the variable or library from the Project Explorer
window or the NIDistributed System Manager.
SCADA Features
The LabVIEW Datalogging and Supervisory Control (DSC) Module provides a suite of additional SCADA functionality
on top of the network-published shared variables including the following:
User-based security
Scaling
58
Published I/O variables are optimized for I/O monitoring. They do not work with all network-published shared variable
features and all LabVIEW devices. For maximum flexibility when sharing data between LabVIEW applications, you
should use network-published shared variables.
59
Reliability
Some of the hosted process variables may be critical to the distributed application, so they benefit from running on a
reliable embedded OS such as LabVIEW Real-Time to increase the overall reliability of the system.
Determinism
If you want to use network variables to send data directly to or from a time-critical loop on a real-time target, you
must have the RT FIFO enabled to ensure deterministic data transfer. You can only host RT FIFO-enabled network
variables on the real-time target.
The path name used to dynamically access network variables is similar to a Windows network share name, such as
//machine/myprocess/item. Below are additional examples of network variable references:
//localhost/my_process/my_variable
//test_machine/my_process/my_folder/my_variable
//192.168.1.100/my_process/my_variable
60
Monitoring Variables
The NIDistributed System Manager offers a central location for monitoring systems on the network and managing
published data. From the system manager, you can access network-published shared variables and I/O variables
without the LabVIEW development environment.
With the NIDistributed System Manager, you can write to network-published shared variables so you can remotely
tune and adjust process settings without the explicit need for a dedicated HMI. You can also use the NIDistributed
System Manager to monitor and manage controller faults and system resources on real-time targets. From LabVIEW,
select ToolsDistributed System Manager to launch the system manager.
61
Figure 4.11. Initialize variables to known values and serialize variable execution.
There are also times when you may not want to serialize your variables. When multiple variables are serialized and an
error occurs within the first variable, the variables further down the chain do not execute. If you want to ensure that
every variable is processed, even if an error occurs within one variable, you should avoid serializing them.
Figure 4.12. Use a timeout to prevent reading the same value repeatedly in a loop.
Network Streams
Network Streams are similar to Queue functions in that they are FIFO based, but unlike Queue functions, Network
Streams have network scope. They were designed and optimized for lossless, high-throughput data communication
over Ethernet, and they feature enhanced connection management that automatically restores network connectivity
if a disconnection occurs due to a network outage or other system failure. Streams use a buffered, lossless
communication strategy that ensures data written to the stream is never lost, even in environments that have intermittent
network connectivity.
Because Network Streams were built with throughput characteristics comparable to those of raw TCP, they are ideal
for high-throughput applications for which the programmer wants to avoid TCP complexity. You also can use streams
for lossless, low-throughput communication such as sending and receiving commands.
Network Streams use a one-way, point-to-point buffered communication model to transmit data between applications.
This means that one of the endpoints is the writer of data and the other is the reader. Your application might require
multiple streams to communicate multiple types of data, as shown in Figure 4.13.
62
Figure 4.13. Network Streams use a one-way, point-to-point buffered communication model.
Figure 4.13 shows a basic Network Streams implementation. One process executes on the real-time target, and the
other process executes on the host computer. You can follow three basic steps to set up a Network Stream:
1. Create the endpoints and establish the stream connection
2. Read or write data
3. Destroy the endpoints
If a disconnection occurs and one endpoint becomes inactive, a reconnection is performed automatically by the
protocol in the background. This protocol retries forever, preserving the lossless nature of the data stream. While the
protocol is trying to reconnect, the active endpoint outputs an error message notifying the user that the endpoints
cannot resynchronize. You can also monitor whether the stream is connected by using the Network Stream Endpoint
Property Node shown in Figure 4.15.
Figure 4.15. Monitor the Network Stream Endpoint connection status with a property node.
63
Figure 4.16. Basic Implementation of Network Streams to Stream Data Across a Network
Figure 4.17. Use the Flush Stream.vi to shut down a Network Stream.
64
When using Network Streams to send commands, do the following to ensure low latency:
1. Specify a small buffer size (the example uses a buffer size of 10 elements)
2. Use the Flush Stream VI to flush the buffer immediately after a command is sent
You can implement the commander architecture for events that originate on a UI by using the standard LabVIEW
UI-handling templates. Translate the UI event into the appropriate command by building the command message and
writing it to the Network Stream. Be sure to flush the buffer after the command is sent to ensure low latency.
65
66
You can find more information on Network Streams in the NIDeveloper Zone white paper Lossless Communication
with Network Streams: Components, Architecture, and Performance.
67
Metadata
Metadata is implemented as an array of clusters. Each array element contains the data properties necessary to
package and decode one variable value. Even if you have defined only the Name property, you can use a cluster to
customize the STM by adding metaproperties (such as data type) according to your application requirements. The
metadata cluster is a typedef, so adding properties should not break your code.
Figure 4.22 shows an example of the metadata cluster configured for two variables: Iteration and RandomData.
Before each data variable is transmitted, a packet is created that includes fields for the data size, the metadata ID,
and the data itself. Figure 4.23 shows the packet format.
The metadata ID field is populated with the index of the metadata array element corresponding to the data variable.
The receiving host uses the metadata ID to index the metadata array to get the properties of the message data.
API
The STM API is shown in Figure 4.24. For basic operation, it consists of a Read VI and a Write VI. It also features two
supplemental VIs to help with the transmission of the metadata, but their use is not mandatory. Each of the main VIs
is polymorphic, which means you can use them with different transport layers. This document discusses STM
communication based on the TCP/IP protocol, but STM also works with UDPand serial as transport layers.The API
for each layer is similar.
68
69
Also note that the application flattens the data to a string before it is sent. For simple data types it is possible to use
a typecast, which is slightly faster than the Flatten to String function. However, the Flatten to String function also
works with complex data types such as clusters and waveforms.
As you can see, you can customize the protocol and expand it to fit your application requirements. As you add
variables, simply add an entry to the metadata array and a corresponding STM Write Message VI for that variable.
Receiving data is also simple. The design pattern shown in Figure 4.26 waits for the metadata when the connection
is established with the server. It then uses the STM Read Message VI to wait for incoming messages. When it
receives a message, it converts the data and assigns it to a local value according to the metadata name.
The Case structure driven by the data name provides an expandable method for handling data conversion. As you add
variables, simply create a case with the code to convert the variable to the right type and send it to the right destination.
Note that an outer Case structure handles timeout events.
One advantage of this design pattern is that it centralizes the code that receives data and assigns it to local values.
Another advantage is that the STM Read Message VI sleeps until it receives data (or a timeout occurs), so the loop is
driven at the rate of incoming data. This guarantees that no data is lost and no CPU time is wasted polling for
incoming data.
70
Note:Since the client has no knowledge of the metadata until run time, you must be sure that the application
handles all possible incoming variables. It is a good practice to implement a default case to trap any unknown
variables as an error condition.
For more information on STM, view the following white papers on ni.com:
LabVIEW Simple Messaging Reference Library (STM)
Command-Based Communication Using Simple TCP/IP Messaging
A Multiclient Server Design Pattern Using Simple TCP/IP Messaging
If you attempt to resume the connection immediately after termination, you see an error dialog with error code 60
from the TCP Listen.vi that is similar to the error dialog in Figure 4.27. This inability to reestablish the listening TCP
socket is caused by an orphaned socket. The orphaned socket is the socket that initiated the termination. If you wait
for 60 seconds before attempting to reestablish the connection, the error message goes away. However, many
systems cannot afford to be down for 60 seconds.
Figure 4.27. Error Code 60 is generated when the client/server connection is terminated.
71
The 60 second timeout is intentional. When an orphaned socket is identified, TCP/IP makes the socket unavailable for
60 seconds so that no other sockets can communicate with it. If you compare TCP/IP to a postal service, a termination
is equivalent to a family moving out of its home. The postal service temporarily takes down that mailbox so that if new
people move in, they do not receive mail that does not belong to them. TCP/IP makes the socket unavailable intentionally
so that it can send data reliably over the network.
Preventing Orphaned Sockets
This section provides two methods for preventing orphaned sockets.
Design your application so that only the client can terminate the connection
In most cases, the orphaned socket issue is more severe on the server side. Typically, the client port is assigned
dynamically but the server port is fixed. When the server closes the connection, the server port becomes locked out. If
the connection is always terminated from the client side, you can significantly reduce the risk of dealing with error 60.
When designing your server application, you need to follow three rules:
1. Do not close the connection in the event of a timeout by ignoring the timeout error.
2. If you want to stop the server application, send a message to the client and let the client terminate the
connection. Wait for a non-timeout error (62 or 56) and close the server application upon error.
3. Do not close the server application upon an event. If an event occurs that should stop the application, send a
message to the client and have the client terminate the connection. Then close the server application upon error.
Figure 4.28. This example VI prevents the server from closing the network connection.
72
Implementation
The underlying implementation of CCC is TCP/IP. Specifically, it is an adaptation of STM, which offers a platformindependent way of sending messages by name while maintaining the performance and throughput of raw TCP
communication. In applications involving hundreds or perhaps thousands of tags, the importance of efficient
communication is obvious.
TheCCC interface is made up of two separate elements. Theserver portion of the interface acts as a TCP server and
consists of a command parser that processes requests for data from the client. Theclient portion of the interface
acts as the TCP client and initiates the communication with the server. It then sends commands to theserver for
configuring and sending/receiving data.
Host PC
CompactRIO RT Target
TheCCC protocol implementation emphasizes performance optimization by configuring as much as possible on the
first call, leaving the repetitive operations with less work to do. Accordingly, the protocol is implemented in such a
way that theclient must first identify all of the tags of interest using the Bound Address parameter. On the first
execution, theserver looks up the tags by their index in the CVT. From that point forward, only the CVT index API is
used to ensure the highest possible performance.
73
On both theclient andserver components, all of the repetitive operations are implemented with determinism in mind.
They allocate all of the necessary resources on the first call of each function and use a functional global variable to
store blocks of data between iterations. This ensures that no memory allocation takes place after the first iteration.
In the corresponding client application, shown in Figure 4.32, the CCC write and read operations are implemented in
series with the rest of the HMI code. This ensures that the values for both the read and write tags are updated on
each iteration. The client application includes the following steps:
1. Initialize the client-side CVT
2. Initiate a connection with the server
3. Use the CVT API functions (tags) to read and write data to and from the client-side CVT
4. Use the CCC Client Read and Write VIs to transfer data between the client-side CVT and the server-side CVT
5. End a connection with the server
74
For more information on CCC, see the NIDeveloper Zone white paper
CVT Client Communication (CCC) Reference Library.
Web Services
LabVIEW web services, introduced in LabVIEW 8.6, offer an open and standard way to communicate with VIs over
the web. Consider a LabVIEW application deployed across a distributed system. LabVIEW provides features such as
Network Streams for establishing communication, but many developers need a way to communicate with these
applications from devices that do not have LabVIEW using standard web-based communication. With LabVIEW web
services, you can:
Remotely monitor and control LabVIEW applications using custom thin clients
Stream any standard MIME data types, such as text, images, and videos
75
Client Machines
Remote System
Web
Figure 4.33. You can use web services to communicate data over the web.
Web services act as a web API to any type of software, whether that software is controlling a complex embedded
system or simply a database store. To use a web service, a client sends a request to the remote system hosting the
service, which then processes the request and sends back a response (typically an XML, or eXtensible Markup
Language, message). The client can choose to display the raw XML data, but it is more common to parse the data
and display it to the user as part of a GUI.
Using this approach, you can create one or more VIs for your CompactRIO LabVIEW Real-Time target and build them
as web services. These web service VIs provide a standard interface for exchanging data between your embedded
devices and any computer connected via a network.
HTTP Request
Web
Client Machine
Thin Client
Application
XML Response
Figure 4.34. You can host and execute web services on a remote system
and access them via the standard HTTP protocol.
76
The bioreactor application uses Network Streams to send commands from the host PC to the CompactRIO
controller. Since this application uses the RIO Scan Interface to handle I/O, network-published I/O variables are used
to send raw I/O data to the UI update process.
77
CHAPTER 5
Customizing Hardware
ThroughLabVIEWFPGA
This chapter covers several best practices in addition to advanced tips and tricks for developing high-performance
control and monitoring systems with the LabVIEW FPGA Module and CompactRIO. It examines recommended
programming practices, ways to avoid common mistakes, and numerous methods to create fast, efficient, and reliable
LabVIEW FPGA applications.
FPGA Technology
FPGAs offer a highly parallel and customizable platform that you can use to perform advanced processing and control
tasks at hardware speeds. An FPGA is a programmable chip composed of three basic components: logic blocks,
programmable interconnects, and I/O blocks.
The logic blocks are a collection of digital components such as lookup tables, multipliers, and multiplexers where
digital values and signals are processed to generate the desired logical output. These logic blocks are connected with
programmable interconnects that route signals from one logic block to the next. The programmable interconnect can
also route signals to the I/O blocks for two-way communication to surrounding circuitry. For more information on
FPGA hardware components, see the LabVIEW FPGA Help Document: Introduction to FPGA Hardware Concepts.
FPGAs are clocked at relatively lower rates than CPUs and GPUs, but they make up for this difference in clock rate by
allowing you to create specialized circuitry that can perform multiple operations within a clock cycle. Combine this
with their tight integration with I/O on NI reconfigurable I/O (RIO) devices and you can achieve much higher
throughput and determinism as well as faster response times than with a processor-only solution. This helps you
tackle high-speed streaming, digital signal processing (DSP), control, and digital protocol applications.
Because LabVIEW FPGA VIs are synthesized down to physical hardware, the FPGA compile process is different from the
compile process for a traditional LabVIEW for Windows or LabVIEW Real-Time application. When writing code for the
78
FPGA, you write the same LabVIEW code as you do for any other target, but when you select the Run button, LabVIEW
internally goes through a different process. First, LabVIEW FPGA generates VHDL code and passes it to the Xilinx compiler.
Then the Xilinx compiler synthesizes the VHDL and places and routes all synthesized components into a bitfile. Finally,
the bitfile is downloaded to the FPGA and the FPGA assumes the personality you have programmed. This process, which
is more complicated than other LabVIEW compiles, can take up to several hours depending on how intricate your design
is. Later in the chapter, learn more about debugging and simulating your FPGA VI so that you can compile less often.
Figure 5.2. Behind the scenes, the LabVIEW FPGA compiler translates LabVIEW code into
VHDL and invokes the Xilinx compile tools to generate a bitfile, which runs directly on the FPGA.
79
Figure 5.3. Drag and drop an I/O node to the FPGA block diagram.
The FPGA I/O Node returns single-point data when called. For most NI R Series devices and C Series I/O modules,
you can use LabVIEW structures and logic to specify the sample rate and triggering. High-speed analog input
modules that use delta-sigma converters and have their own onboard clock are an exception. For these modules, you
control the sample rate with a Property Node. Table 6.2 in Chapter 6: Timing and Synchronization of I/O provides a
list of NI C Series I/O modules that use delta-sigma modulation.
80
For most I/O nodes, you can use a loop with a Loop Timer Express VI to set the sample rate. The Sample Delay
control sets the rate in ticks. Ticks are the pulses on the FPGA clock, which by default is 40 MHz for most
CompactRIO targets. For example, implementing a sample delay of 20,000 ticks of the 40 MHz clock renders a
sample rate of 2 kHz. You can also specify the sample delay in microseconds or milliseconds by double-clicking the
Loop Timer and adjusting the configuration panel. Of course, no matter what rate you specify, the module samples
up to only the maximum rate specified in the module documentation.
You also have an option to use a Sequence structure, as shown in Figure 5.4. A Sequence structure can be used to
guarantee that every time the LabVIEW FPGA VI is compiled, the timer and I/O Node are executed in the same sequence.
Figure 5.4. The Acquisition Scheme for a Standard Analog Input Module
To implement a triggered application, use a Case structure gated on the trigger condition. This trigger condition can
be an input from the host processor or it can be derived from logic directly on the FPGA. With LabVIEW FPGA, you
can implement basic or complex triggering schemes such as retriggering, pause triggering, or any type of custom
triggering. Figure 5.5 shows an example of an application that takes in a start trigger and monitors the number of
samples being collected until it reaches the number specified by the user. The code used in this example can be
found in the Turbine Tester project, which can be downloaded from the Introduction and Basic Architectures
section at ni.com/compactriodevguide.
81
Figure 5.6. Motor Control Example With Two Different Clock Signals
Now consider the LabVIEW FPGA code used to monitor these signals and trigger on either the rising or falling edge.
Typically triggering a loop based on a Boolean clock signal works like this: first wait for the rising or falling edge to
occur and then execute the LabVIEW FPGA code that you want to run when the trigger condition occurs. This is
often implemented with a Sequence structure that uses the first frame to wait for the trigger and the second frame
to execute the triggered code, as shown in Figure 5.7.
Rising Edge Trigger: In this case, you are looking for the trigger signal to transition from False (or 0) to True (or 1). This
is done by holding the value in a shift register and using the Greater Than? function. (Note: A True constant is wired
to the iteration terminal to initialize the value and avoid an early trigger on the first iteration.)
Falling Edge Trigger: In this case, use a Less Than? function to detect the transition from True (or 1) to False (or 0).
(Note: A False constant is wired to the iteration terminal to initialize the value.)
82
Analog Level Trigger: Use a Greater Than? function to detect when the analog signal is greater than your analog
threshold level, and then use the Boolean output of the function as your trigger signal. This case actually is a rising or
falling edge detector because you are using the Not Equal? function to detect any transition.
Now examine another common triggering use caselatching the value of a signal when a trigger event occurs.
Tip: Latch Values
In this case, you use a rising edge trigger to latch the Analog Input value from another loop into the Latched Analog
Input register. This value is held constant until the next trigger event occurs. In this example, the actual analog input
operation is occurring in another loop, and you are using a local variable for communication between the loops.
(Note: Local variables are a good way to share data between asynchronous loops in LabVIEW FPGA.)
Figure 5.10. In this example, the actual analog input operation is occurring in another loop,
and you are using a local variable for communication between the loops.
83
Figure 5.11. A subVI is used to count the number of samples acquired once a trigger condition is met.
84
The left side of Figure 5.13 shows how you can adapt PWM code to use a Tick Count function rather than a Loop Timer
function. Using a feedback node to hold an elapsed time count value, you turn the output on and off at the appropriate
times and reset the elapsed time counter at the end of the PWM cycle. The code may look a bit more complicated, but
you can drop it inside a top-level loop without affecting the overall timing of the loopit is more portable.
85
Figure 5.14. A subVI is set to reentrant, so all four of these loops run simultaneously, and any
VI-scoped memory data, internal shift registers, or local variables are unique to each instance.
In the case of LabVIEW FPGA, this also means that each copy of the function uses its own FPGA slices, so
reentrancy is effective for code portability but has the potential to use more gates. If you are trying to save FPGA
resources, you may want to change the execution properties to nonreentrant execution. However, for small subVIs,
you could potentially use more FPGA fabric in this case because the compiler adds more logic to the FPGA fabric to
handle arbitration. The section below describes techniques for avoiding arbitration.
Avoiding Arbitration
Arbitration occurs when your LabVIEW FPGA code contains a shared resource, such as an I/O node or a nonreentrant
subVI, that has multiple readers or writers. In these situations, the compiler adds more logic to the FPGA fabric to handle
this arbitration. If you are concerned about minimizing the amount of FPGA fabric you are using, try to avoid arbitration.
Find more information on how arbitration works in the LabVIEW FPGA Help Document: Managing Shared Resources.
You can avoid arbitration by changing the arbitration settings within LabVIEW as described in the help document above,
but a more reliable technique is designing your application in a way that prevents arbitration. Some of these techniques
are listed below:
Another technique is to create multiple global or local variables when you are in a situation that requires multiple writers.
For example, consider having a LabVIEW FPGA VI that uses one loop for reading from an analog input node and two
additional loops for processing the analog data. In this situation, you can create two separate global or local variables,
say A and B, to write to inside your analog input loop. In your first processing loop, you can read from variable A, and
in your second processing loop, you can read from variable B.
86
Figure 5.15. Use the Tick Count function to measure elapsed time.
Because you use an unsigned integer for the counter value, your elapsed time calculations remain correct when the
counter rolls over. This is because if you subtract one count value from another using unsigned integers, you still get
the correct answer even if the counter overflows.
Another common type of counter is an iteration counter that measures the number of times a loop has executed.
Unsigned integers are typically preferred for iteration counters because they give the largest range before rolling
over. The unsigned 64-bit integer data type you are using for the counter provides a huge counting rangeequivalent
to about 18 billion-billion. Even with the FPGA clock running at 40 MHz, this counter will not overflow for more than
14,000 years.
Figure 5.16. Unsigned integers are typically preferred for iteration counters
because they give the largest range before rolling over.
Data Communication
Data communication in LabVIEW FPGA falls into two categories: interprocess and intertarget. Interprocess
communication generally corresponds to sharing data between two or more loops on the FPGA target. Intertarget
data communication is sharing data between the FPGA target and host processor. For both cases, you should
consider whether you are communicating current value data, messages, or commands or are streaming data before
deciding which mechanism to use. These data communication types are described in more detail in the Introduction
and Basic Architectures chapter.
Variables
LabVIEW FPGA features local and global variables for sharing current values or tags between two or more loops.
With variables, you can access or store data in the flip-flops of the FPGA. Variables store only the latest data that is
written. They are a good choice if you do not need to use every data value you acquire.
Memory Items
Another method for sharing the latest values is to use available memory items. Taking advantage of memory items
consumes few logic blocks but uses the onboard memory. LabVIEW FPGA devices have two types of memory
87
items: target scoped and VI defined. You can access target-scoped memory items through all VIs under the FPGA
target. VI-defined memory items are scoped to the VI that defines them. Figure 5.17 shows a block diagram using a
Memory Method Node configured for a target-scoped memory item. This VI reads data from memory, increments
the data, and then overwrites the same memory location with the new data.
Figure 5.17. Read and write to a memory item using a Memory Method Node.
VI-scoped memory is a powerful tool for applications that need to store arrays of data. In general, you should always
avoid using large front panel arrays as a data storage mechanismuse VI-scoped memory instead. For more information
on using memory items on an FPGA target, see the LabVIEW Help document Storing Data on an FPGA Target.
FIFOs
If you are communicating messages or updates, or streaming data between two or more loops, consider using
FIFOs for data transfer. A FIFO is a data structure that holds elements in the order they are received and provides
access to those elements using a first-in-first-out access policy.
Figure 5.18. Use FIFOs to share buffered data between two parallel loops.
Similar to memory items, you have two types of FIFOs to choose from: target scoped or VI defined. You can access
target-scoped FIFOs through all VIs under the FPGA target, and VI-defined FIFOs are scoped to the VI that defines them.
When you configure a FIFO, you must specify the implementation that determines which FPGA resources hold and
transfer data in the FIFO. The following recommendations can help you choose one implementation over another.
88
Flip-flopsFlip-flops use gates on the FPGA to provide the fastest performance. They are recommended only
for very small FIFOs (fewer than 100 bytes).
Lookup tableYou can store data to two lookup tables per slice on the FPGA. Lookup tables are
recommended only for small FIFOs (fewer than 300 bytes).
Block memoryIf you are trying to preserve FPGA gates and lookup tables for other parts of your application,
you can store data in block memory.
For more information on using FIFOs on an FPGA target, see the LabVIEW Help document Transferring Data
Between Devices or Structures Using FIFOs.
Intertarget Communication
You can choose from two methods for communicating data between an FPGA VI and a VI running on the real-time
processor: front panel controls and indicators or DMA FIFOs. You can use front panel controls and indicators to
transfer the latest values or tags and DMA FIFOs to stream data or send messages and commands. Both methods
require using the FPGA Interface functions on the host VI to interact with the FPGA.
Figure 5.19. Read and write to front panel controls and indicators
to share the latest values between targets.
Programmatic front panel communication has low overhead relative to other methods for transferring data between
the FPGA and host processor. Read/Write nodes are good candidates for transferring multiple pieces of information
between the FPGA and host processor given their relatively low overhead. DMA FIFOs, shown in Figure 5.20, can
provide better throughput when streaming large amounts of data, but they are not as efficient for smaller and
infrequent data transfers.
89
Transferring data between the FPGA and host processor using front panel controls and indicators requires involving
the host processor more than the DMA FIFOs. As a result, the speed of data transfer is highly dependent on the
speed and availability of the host processor. A slower processor or the lack of processor availability results in slower
data transfer from the FPGA target to the host. A disadvantage of programmatic front panel communication is that
this method transfers only the most current data stored on the control or indicator of the FPGA VI. For example, data
could be lost if the FPGA VI writes data to an indicator faster than the host VI can read the data. Also, each control or
indicator on the FPGA VI uses resources on the FPGA. Best practices in FPGA programming recommend limiting the
number of front panel objects in FPGA VIs.
Additional LabVIEW Help Reference
DMA FIFOs
If you need to stream large amounts of data between the FPGA and real-time processor, or if you require a small
buffer for command- or message-based communication, consider using DMA FIFOs for data transfer. DMA does not
involve the host processor when reading data off the FPGA; therefore, it is the fastest method for transferring large
amounts of data between the FPGA target and the host.
Figure 5.20. DMA uses FPGA memory to store data and then transfer it at a high speed
to host processor memory with very little processor involvement.
The following list highlights the benefits of using DMA communication to transfer data between an FPGA target and
a host computer:
Frees the host processor to perform other calculations during data transfer
Reduces the use of front panel controls and indicators, which helps save FPGA resources, especially when
transferring arrays of data
Automatically synchronizes data transfers between the host and the FPGA target
Though DMA FIFOs are a great mechanism for streaming data, they quickly become complicated when streaming
data from more than one channel, optimizing your throughput, or scaling your data on the real-time host VI. If your
application requires streaming analog data from one or more analog channels, you should use the NICompactRIO
Waveform Acquisition Reference Library discussed at the end of this section as a starting point. This library
90
features an FPGA template and an NI-DAQmx-like API for streaming data and offers many benefits including
optimized performance and built-in scaling.
Using DMA FIFOs in LabVIEW FPGA
To create a DMA buffer for streaming data, right-click on the FPGA target and select New...FIFO. Give the FIFO
structure a descriptive name and choose target to host as the type. This means that data should flow through this
DMA FIFO from the FPGA target to the real-time host. You can also set data type and FPGA FIFO depths. Clicking
OK puts this new FIFO into your project, which you can drag and drop to the FPGA block diagram.
Tip: In LabVIEW 2012 FPGA and later, you can convert fixed-point data to single precision floating-point data.
Offloading this conversion to the FPGA can save significant processor resources. For earlier LabVIEW versions, you
can obtain a similar conversion function through the downloadable example or the NI Developer Zone document
Fixed-Point (FXP) to Single (SGL) Conversion on LabVIEW FPGA.
You can use the same DMA channel to transfer multiple streams of data, such as that collected from I/O channels.
Most CompactRIO systems have three DMA channels. In Hybrid Mode, CompactRIO systems have only one DMA
channel. To pack multiple data streams or I/O channels into one DMA FIFO, use the interleaving technique shown in
Figure 5.22, and unpack using decimation on the host.
Figure 5.22. You can use build array and indexing on a For Loop to implement
an interleaved multichannel data stream.
When passing multiple analog input channels into one DMA FIFO, the channels are stored in an arrangement similar
to that shown in Table 5.1. This table assumes that four analog input channels are being interleaved into one DMA
91
FIFO. The unpacking algorithm on the host VI is expecting the elements to arrive in this specific order. If the FIFO
overflows and elements are lost, then the unpacking algorithm on the host VI fails to assign data points to their
correct analog input channels. Therefore, it is extremely important to ensure lossless data transfer when reading
from multiple analog input channels.
Array Index
Element
AI 0
AI 1
AI 2
AI 3
AI 0
AI 1
AI 2
Table 5.1. When writing multiple channels to one DMA FIFO, the host VI expects
the elements to arrive in a specific order.
92
Whenever you are reading data from a DMA FIFO, you must be able to detect and recover from buffer overflows, or
timeout cases, to maintain data correctness. The next section provides a recommended architecture for ensuring
lossless data transfer when using DMA FIFOs.
Ensuring Lossless Data Transfer
If lossless data transfer is important, or if you are transferring data from multiple I/O channels into the same DMA
FIFO, you must be able to monitor the state of the DMA mechanism and react to any faults that occur. On the FPGA
DMA Write Node, a timeout usually indicates that the DMA buffer is full. You should monitor and latch it when it
becomes true. You must do this from the FPGA side because simply sampling this register from the host is not
sufficient to catch quick transitions. Once you detect a timeout event, you also need to recover from it. Figure 5.24
provides an example of detecting and handling a DMA FIFO timeout case.
93
FPGA VI
RT Host VI
In this figure, the timeout event of the DMA FIFO is being monitored on the FPGA VI. When a timeout event occurs,
the Timed Out? register is set to True. Once the Timed Out? register is set to True, it is latched until the host VI clears
the buffer and sets the Reset register to True. The timeout case on the RT Host VI flushes the buffer by reading the
remaining elements. Once the buffer is cleared, the Reset register is set to true and the acquisition on the FPGA VI
resumes. By using this method of dealing with the DMA FIFO timeout event, you can detect and recover from buffer
overflow so that you can avoid bugs created from missing data points.
Avoiding Buffer Overflows
If you are receiving buffer overflows, you need to either increase the DMA FIFO buffer size on the host, read larger
amounts on the host, or read more often on the host. Keep in mind that many control and monitoring applications
need only the most up-to-date data, so losing data may not be an issue for a system as long as it returns the most
recent data when called.
If you are experiencing buffer overflows, you can increase the host FIFO buffer by using a DMA Configure call as
shown in Figure 5.25. For FPGA to RT transfers, an overflow often occurs because the host FIFO buffer, not the
FPGA FIFO buffer, is not large enough. The size of the DMA FIFO set through the FIFO properties page determines
94
only the size of the FPGA FIFO buffer that uses up FPGA memory. By default, the host FIFO buffer size is 10,000
elements or twice the size of the FPGA FIFO buffer, whichever is greater.
Figure 5.25. Increasing the DMA FIFO size on the host is one way of eliminating
buffer overflow issues (DMA RT.vi).
Increasing the size of the buffers can help reduce buffer overflow conditions caused by sporadic events such as
contention for buses and the host processor. But if the average transfer rate is higher than what the system can
sustain, the data eventually overflows the buffer regardless of the buffers size. One way to reduce buffer overflow
conditions with appropriately sized buffers is to try to read larger amounts of data at a time, which leads to lower
overhead per data unit and therefore increases overall throughput.
The CompactRIO Waveform Reference Library includes an NI-DAQmx-like API that executes in LabVIEW Real-Time
and converts raw analog data into the waveform data type. The waveform data type makes it easy to display multiple
channels of I/O to a UI as well as to interface with common data-logging APIs such as Technical Data Management
Streaming (TDMS). The API also converts your data to the appropriate engineering units depending on the scale that
you configure.
95
Figure 5.27. When using the CompactRIO Waveform Reference API, you can quickly stream
data and display multiple channels of I/O to a user interface.
This library includes an FPGA VI that you need to slightly modify for the VI to reference the I/O modules used in your
system. For most applications, you only need to modify the FPGA VI. This VI, designed to offer optimal streaming
performance when using DMA FIFOs, includes mechanisms for monitoring and handling buffer overflow conditions.
Use this FPGA VI template as a starting point whenever you are streaming data from one or more analog channels
using DMA FIFOs.
You can find more information including installation files in the NIDeveloper Zone white paper
NICompactRIO Waveform Reference Library.
For more information on using DMA FIFOs on an FPGA target, see the LabVIEW Help document
Transferring Data Using Direct Memory Access.
96
might implement an interrupt on the FPGA. This example is called the Interrupt Method for Synchronization and can
be found in the NIExample Finder.
Figure 5.28. Basic LabVIEW FPGA Programming Structure for Sending an Interrupt
Interrupts offer simple code with a straightforward API, but you should be aware of the following caveats:
Handling the interrupt on the host side involves overhead usually on the order of 5 s to 50 s. This response
latency may be acceptable depending on the application or the frequency of the event.
If you do not want the FPGA VI to block until the interrupt is acknowledged, you should add a separate FPGA
loop for sending the interrupt.
Interrupts are not the lowest latency option on multicore targets. The fastest response time is obtained by
dedicating a CPU core to continuously monitor an FPGA register (no sleep).
Additional References
97
Unit
Unit is the most fundamental level of IP you can build in the sense that it maps to a specific processing
function or algorithm. You would not split it and test it as a set of smaller functional units.
You want to keep these simple, so you would call it a unit if:
It can be encapsulated as a subVI you may want to reuse in other parts of your design
It is functional in natureyou can provide some known inputs and test for expected outputs
It may hold state, in which case you may need to call it multiple times to verify it, but its behavior should not
rely on the explicit specific passing or control of time
Component
Components are more complex pieces of logic that include elements that can exhibit side effects or focus
more on the timing in the system. They are composable by definition, and usually have a clear task or objective
to accomplish. An FPGA application can often be broken down into multiple components, and verification at this
level ensures that the components interact as expected when integrated into a larger component. You may also
want to make sure that a subcomponent is interacting properly with the I/O or host (through the host interface)
without waiting until the whole system is assembled.
System
You can think of the system level as the top-most component. It is represented by your top-level FPGA VI plus
any additional HDL IP imported through the Component-Level IP (CLIP) Node. It is somewhat different from
other components in that its interface is exposed to the host application, so verification tests are either similar
to running your host app or they are your host app. Verification therefore requires using the host interface API
as well as connecting real I/O signals to your system. A system usually contains multiple While Loops or SCTLs.
Table 5.2 provides guidance on which execution mode you should use for verification and debugging. Keep in mind
that if you can perform extensive debugging and verification at the unit and component levels, then you decrease
your verification work at the system level.
Verify
Functional
Performance
Execution Mode
Verify Timing
Verify
Integration
of HDL IP
Good for
Unit Testing
Good for
Component
Testing
Windows PC
X (only code
contained in SCTL)
FPGA Hardware
Advanced:
Third-Party Simulator
Good for
System Testing
X
X
Table 5.2. This table provides a comparison of different execution modes for verifying and
debugging your LabVIEW FPGA code.
98
Figure 5.29. You can change the execution mode of your LabVIEW FPGA VI by right-clicking
theFPGAtarget in the LabVIEW project.
99
Figure 5.30. View signals in relation to each other with respect to time using the new
LabVIEWFPGAsampling probe.
The window also includes functions for locating the next rising edge or previous rising edge on a signal, and zoom
capabilities to navigate through the data. For information on how to use the Sampling Probe, see the
LabVIEWFPGA Help Document: Debugging Using Sampling Probes.
100
Figure 5.31. A typical test bench consists of several components, all of which can
beimplemented in the LabVIEW graphical development environment.
In the LabVIEW FPGA Module Version 2013 and later, you can test LabVIEW FPGA components using the Desktop
Execution Node. With the Desktop Execution Node, you can perform verification on a LabVIEW FPGA VI without
making changes to your LabVIEW FPGA code to accommodate the testing. The Desktop Execution Node uses
simulated time to reflect timing in hardware. You can provide stimuli to controls, indicators, and I/O before time
advances; force time to advance a set number of ticks; and then read the values of the controls, indicators, and I/O
before providing additional stimuli to the VI.
Figure 5.32. The Desktop Execution Node can be used to create a test bench
foryourLabVIEWFPGA VI
101
The following nodes tie into simulated time and announce time steps or return a simulated time value:
While Loop
Wait Express VI
For specifics on individual node timing or execution behavior, read the NI white paper Using the LabVIEW FPGA
Desktop Execution Node.
Using the Desktop Execution Node
The Desktop Execution Node is generally recommended for validating components. Since it executes the FPGA VI in
simulation mode, you can develop tests for VIs that contain target resources such as I/O and memory items. This
section describes the steps to set up the Desktop Execution Node for component testing.
Consider an example featuring a LabVIEW FPGA component that has been designed to read tachometer and
accelerometer data from an analog input node (NI 9234) and then convert the tachometer reading into revolutions
per minute (rpm) before sending it to the host. Since the NI 9234 uses delta-sigma modulation, you are specifying
the sample rate of the module using a property node. The goal of your test is to verify the tachometer IP (Tach_
FPGA.vi) that you downloaded from ni.com/ipnet.
Figure 5.33. This section references an example FPGA VI that acquires tachometer data
and converts it to rpm.
102
Figure 5.34. The Desktop Execution Node is on the FPGA Interface palette.
Most components contain a single loop. If your component contains multiple loops, select the fastest clock
referenced in your VI.
If you are performing unit testing and your code is not contained within a loop, encompass your unit code
within a While Loop for the purpose of testing. Otherwise, the Desktop Execution Node stops after completing
the first iteration.
103
Figure 5.35. The first step to configuring the Desktop Execution Node is to select your FPGA VI.
Ticks = 400
Therefore, you would configure your Clock Ticks input in the Desktop Execution Node to 400 ticks.
While Loop With No Loop Timer
If you are using a While Loop that does not contain any analog I/O (it may contain digital I/O), the easiest way to
measure the number of ticks is by using the Sampling Probe. To do this, create an indicator off the While Loop
iteration terminal. Right-click the wire and select Sampling ProbeFPGA. Run the VI in simulation mode for a
second or two, stop, and view the Sampling Probe window. In the example below, you can see that the While Loop
104
takes two ticks of the 40 MHz clock to execute, according to the Sampling Probe window (each tick equals 25 ns).
For this case, you would set the Clock Ticks input to two ticks.
Note: Because this is a While Loop, the number of ticks measured in simulation does not necessarily equal the
number of ticks that result when executing the same code in hardware. Any code inside an SCTL, however, is
guaranteed to be cycle accurate.
Figure 5.36. If your While Loop does not contain a timing source, you can measure the number
of clock ticks per iteration by using a Sampling Probe.
105
Figure 5.37. When the timing source of your loop is the onboard clock of a delta-sigma analog
input module, you need to specify the simulated time by adding a conditional Loop Timer.
You can put the Loop Timer inside a Conditional Disable structure so that it is called only when the VI is executing in
simulation mode. Configure the Conditional Disable structure with the following values:
FPGA_EXECUTION_MODE == DEV_COMPUTER_SIM_IO
The Loop Timer should be placed inside this conditional case, and the default case should be empty.
Figure 5.38. Configure a Conditional Disable structure to execute the Loop Timer
onlywheninsimulationmode.
Finally, the last step is to set the Clock Ticks input in the Desktop Configuration Node. In this example, 488 s is
equal to 19,531 ticks, so you set the Clock Ticks input to 19,531 ticks.
To learn more about using the Desktop Execution Node, see the NI white paper Using the LabVIEW FPGA Desktop
Execution Node.
Step 3: Build Your Test Bench
Once you have successfully configured the Desktop Execution Node, you can begin building your test bench. In the
example shown below, logged tachometer data is being read from a TDMS file and written to the analog input I/O
node called Tach. The FPGA VI is executed in simulation mode, and the resulting rpm is displayed on a chart. To verify
the tachometer IP, you can view the tachometer data read from the file and the rpm data plotted to the chart.
106
Figure 5.39. Once the Desktop Execution Node is configured, you can create a test VI
andverifyyourFPGAcode.
Figure 5.40. The NI FPGA Debug Library contains VIs that you can use for common simple
tasks, oradvanced debugging structures like the advanced I/O counters shown here.
107
Performance
Throughput
Timing
Control
Resource
Utilization
Numerical
Precision
Figure 5.41. With LabVIEW FPGA programming techniques, you can push your system further
for throughput, timing control, resource utilization, or numerical precision.
These dimensions are often interconnected, so improving your design with one of them affects the others
sometimes positively but more often at their expense. It is important to understand these dimensions and how they
relate to each other, so this guide lists some basic definitions below and explores related techniques in later
chapters.
Throughput
Throughput is a key concern for DSP and data processing applications. It is measured as work per unit of time. In the
majority of applications using NI RIO hardware, work refers to the processing or transfer of samples, so their
throughput is usually measured in samples per second or some equivalent form such as bytes, pixels, images,
frames, or operations per second. The fast Fourier transform (FFT) is an example of a processing function with
throughput that can be measured in FFTs, frames, or sample per second.
The High-Performance RIO Developers Guide offers a more in-depth discussion of the factors that affect
throughput as well as a set of techniques that can help you achieve higher throughput when creating LabVIEW FPGA
applications.
Timing Control
Timing control refers to the ability to prescribe and measure the amount of time between events of interest in the
system. When you use LabVIEW FPGA, your designs are translated to a hardware circuit so you can create designs
that have fast timing responses with little jitter. Control applications usually require a guaranteed maximum response
time between system sampling and control signal updating. This amount of time is referred to as latency. In digital
protocol applications, timing specifications may refer to the target, minimum, or maximum time between events
related to the data or signals being transmitted. Precise timing control is important to both the control and digital
protocol application areas.
The High-Performance RIO Developers Guide for a more in-depth discussion of latency as well as a set of
techniques that can help you achieve lower or more precise timing responses when using LabVIEW FPGA.
Resource Utilization
An FPGA has a finite number of resources and is usually much more constrained in storage and memory elements
than a processor or microcontroller. Being able to fit your design into the FPGA is a hard constraint on the whole
development process. FPGAs are also made up of different types of resources, so running out of one type of
resource can keep you from progressing in your applications.
108
More importantly, resource utilization can have a dramatic impact on the other performance dimensions, especially
throughput and meeting timing constraints. Refer to the High-Performance RIO Developers Guide for descriptions
of the different resources that compose the FPGA and how you can balance them to make your design fit and
increase its performance.
Numerical Precision
Numerical precision concerns revolve around having enough digits or bits so your application can work correctly.
Inadequate numerical precision is considered a functional problem that must be avoided and tested against. The
number of bits used to represent system variables, including the number of bits used for integers, the integer and
fractional parts of fixed-point numbers, and the dynamic range of floating-point numbers, can have a substantial
impact on the performance and resource utilization of your application, so you should consider this.
Figure 5.42. You have several options for selecting a compile server when compiling your
LabVIEW FPGA VI.
Use the local compile serverBy default you can compile on your local development PC. This is a viable solution for
compiling small VIs, but if you are concerned about long compile times, you should consider the other options below.
Connect to a network compile server (single server)You can choose to offload your compiles to a single
Windows- or Linux-based machine on the network. Compilation times are proven to be reduced when compiling on a
Linux machine versus a Windows machine.
Connect to a network compile server (farm)If you are working on a team, you can use the LabVIEW FPGA
Compile Farm Toolkit to set up a compile farm with multiple workers. This toolkit helps you create an on-site server
to manage FPGA compilations. You can connect as many worker computers as you need, and the central server
software manages the farming out of parallel compilations and queuing. This is an effective way to reduce compile
times if you cannot use cloud technology for your project.
Connect to the LabVIEW FPGA Compile Cloud ServiceThis service helps you compile your FPGA VIs on Linux
with the latest dedicated high-RAM high-end computers. Depending on the size of your LabVIEW FPGA VI, you may
notice substantial reductions in your compile times compared to compiling on your Windows desktop. Compiling in
109
the cloud also adds the capability to compile many VIs in parallel. To try a 30-day trial of the LabVIEW FPGA Compile
Cloud Service, visit ni.com/trycompilecloud.
Reading the Compile Report
After compiling an FPGA VI, LabVIEW displays a Compile Report that contains information about the overall size and
speed of the application. This information can help you decide how to optimize your code if necessary.
Note that the compiler algorithm is not deterministic, and you might get different results from one compile to the
next even if you do not change the VI or the compiler settings. You can change the compiler settings if the compile
fails by right-clicking the build specification in the LabVIEW project and selecting Properties from the context menu.
In the Properties page, select the category Xilinx Options.
VI Size
The Final device utilization (map) report shown in the dialog of a successful compile offers information about the
number of slice registers, slice lookup tables, and multipliers used as well as the amount of block RAM used. A
recommended best practice is to keep your overall FPGA usage below 90 percent in your final application. If you
upgrade your software in the future and need to recompile your VI, you may find that a different version of the Xilinx
compilation tool chain uses more or less fabric. In this case, you need some extra room to work with.
VI Speed
The Successful Compile Report dialog box also contains information about the clock rates of the application.
RequestedDisplays the clock rate at which the compiled FPGA VI runs. The default setting is 40 MHz.
MaximumDisplays the theoretical maximum compile rate for the FPGA VI.
If the maximum rate is slower than the requested rate, an error results and the compile process stops. You must
modify the application to the point where the maximum rate is equal to or greater than the requested rate. A common
problem when you use SCTLs is that the Requested Rate exceeds the Theoretical Maximum. Refer to the SingleCycle Timed Loop section of this chapter for more information about optimizing FPGA applications using SCTLs.
110
CHAPTER 6
Timing and Synchronization of I/O
Understanding how data travels between module hardware components and the LabVIEW FPGA block diagram can
help you develop better programs and debug faster. This section introduces you to the different hardware architectures
of analog and digital C Series I/O modules and how to communicate with each one. These modules are typically used
for measurement or control signals and feature model numbers that follow this style: NI92xx, NI93xx, or NI94xx.
Some basic terminology used in this section is listed below.
ADCAnalog-to-digital converter. Discrete component that converts an input analog signal (usually voltage)
into a digital representation. Front-end circuitry, also known as signal conditioning, is used to convert real-world
analog signals into voltage levels within the set range of the ADC.
DACDigital-to-analog converter. Discrete component that converts a digital value into an analog value.
Analog output is usually a voltage, but, if you add circuitry, you can convert it into a current value.
ArbitrationThe process of providing one request priority while causing all other requests to wait.
JitterInconsistent periods between multiple iterations of a looping program structure. Measured as the
difference between the longest period experienced and the nominal period requested.
Figure 6.1. The I/O node, method node, and property node for LabVIEW FPGA
visually have subtle differences.
111
I/O Nodes
Are designed to be thin interfaces to the module (in other words, minimal data or timing manipulation)
Cannot be used in SCTLs (except I/O nodes for parallel digital lines)
Figure 6.2. I/O Node Selection Menu (left) and an I/O Node Set to Channel AI0 (right)
Method Nodes
Examples include
Property Nodes
Examples include
Calibration constants
Serial number
Module ID
Vendor ID
112
Figure 6.4. Property nodes for some modules feature several options.
113
Module Classifications
This section describes the different types of C Series I/O modules. You need to understand how these modules are
designed to properly implement timing and synchronization. The basic types of module classifications are presented
in Figure 6.6.
Parallel Digital
Because each of the digital lines on a direct FPGA communication module is programmed as a separate entity, digital
modules with eight or fewer channels are also referred to as parallel digital modules. The parallel design of these
modules makes them the easiest to program in LabVIEW. I/O nodes for parallel digital modules can be called from
SCTLs, which make programming more efficient, and individual channel lines can be called simultaneously from
separate loops, as seen in Figure 6.7, with no concern for arbitration.
Figure 6.7. You can call lines on the same parallel digital module from separate loops.
114
Be aware that a call for direction change, at any time, on the DIO lines of an 8-channel parallel module causes an
interrupt that you must handle appropriately on the LabVIEW block diagram to prevent a glitch or jitter on other lines
in use at the time of direction change. The NI9402 does not have this problem. Four lines are used for DIO and the
other four lines are used to control the direction. Direction changes can happen independently of data transfer. The
NI9401, one of the most popular DIO modules, uses all eight DIO lines and must switch modes to communicate
line states. This mode change affects all DIO lines regardless of which ones are changing state.
As you continue to read about the different classifications of modules, note that all
modules that use SPI communication must adhere to the same caveat of hardware
arbitration.Simultaneous Modules
Modules that are simultaneous have one ADC per channel and acquire data with no appreciable skew between
channels. The two subcategories of simultaneous modules, on-demand and delta-sigma, transfer data via the SPI
bus and are subject to all of the specifications and challenges of other SPI bus modules.
115
On-Demand Conversion
NIC Series On-Demand Simultaneous Modules
Model Number
Description
NI9215
NI9263
NI9265
NI9219
NI92221
NI92231
1These
modules are simultaneous modules and can be programmed with FPGA I/O nodes, similar to other
modules listed in this table. However, to run at higher speeds, you need to program them with the usercontrolled I/O sampling API as outlined in the Data on Demand section below. The maximum sampling
rates achievable when using both FPGA I/O nodes and the user-controlled I/O sampling API can be found
in the Maximum Sampling Rate section of the user manual.
On-demand modules, like the ones listed in Table 6.1, have few specific challenges when it comes to programming
with LabVIEW FPGA. This makes them some of the easiest modules to program. The biggest caveat involves
arbitration, which is shared by all modules that use SPI communication.
Data on Demand
Data on demand is less of a caveat and more of a feature. On-demand simultaneous C Series modules have the
ability to return data when the I/O node is called at any interval down to the minimum conversion time as listed in
the manual. This means that the acquisition can be clocked by external, irregular clocks. The t does not need to be a
constant for an acquisition with an on-demand simultaneous module.
Pipelined Simultaneous Data or User-Controlled I/O Sampling
he NI 9223 User-Controlled IO Sampling.lvpj
T
is in the NI Example Finder.
Some modules designed for high-speed measurements exceed the data throughput capabilities of the FPGA I/O
node. In these situations, you can apply user-controlled I/O sampling functions to communicate with a module. These
add complexity to the program but dramatically increase the bandwidth from the module.
Figure 6.8. You can use the User-Controlled I/O Sampling palette for higher
bandwidth communication to some modules.
116
When programming with the user-controlled sample method, you may find it easier to start with an existing example
program that is shipped with LabVIEW. Figure 6.9 is the block diagram from the NI9223 User-Controlled IO
Sampling.lvproj, which you can find in the NIExample Finder.
To program with the user-controlled I/O sample method, follow these steps that reference the example program in
Figure 6.9.
Initialize the Process
1. Call the Reset I/O function. When this call completes, the module is ready to perform an acquisition using the
user-controlled I/O sampling functions. You must call the Reset I/O function first to prepare the NI9223 to use
the other user-controlled I/O sampling functions.
2. Set the Stopped Boolean to false. This Boolean provides synchronization between the While Loops in the last
sequence frame. If any loop stops, it causes the others to stop as well.
3. Use an interrupt to signal the host that the FPGA is ready to begin acquiring data and wait to start the
acquisition until the host acknowledges it. This is necessary to ensure that the DMA FIFO has been started
prior to acquiring data.
Loop 1
4. Call the Generate I/O Sample Pulse function to begin acquiring data. The rate at which this function is called
determines the sample rate for the acquisition, so a loop timer is used to enforce the desired sample period.
117
Loop 2
5. Call the Read I/O function to read data acquired from the module. This function is configured to read a single
sample from each channel on the module. Because this function waits for data to become available, a generous
but noninfinite timeout is provided. In the case of the default 40 MHz top-level clock, the timeout is 1 second.
6. Write the acquired data into the DMA FIFO.
7. If a timeout occurred either while waiting for data from the module or waiting to write the data to the DMA
FIFO, then report the timeout to the host and stop the VI.
Loop 3
8. Call the Get Read I/O Status function at the same rate you call the Generate I/O Sample Pulse function. This
checks the status of every sample you acquire. If an overwrite or sample gated occur (output = true), then
report the status to the host and stop the VI. In the example, this loop is encased in a diagram disable
structure to make it easily removable from the application. Calling the Get Read I/O Status function is useful
for development and debugging but not strictly necessary for deployment if the application does not feature
variable timing in the application. In the Figure 6.9 example, you cannot obtain a sample gated status unless
the top loops sample period is less than the minimum sample period supported by the module. However, this
application could produce an overwrite status if the host VI cannot read from the DMA FIFO fast enough.
Delta-Sigma Modulation
he NI 9234 Getting Started.lvpj
T
is in the NI Example Finder.
NIC Series Simultaneous Modules With Delta-Sigma Modulation
Model Number
Description
NI9229
NI9239
NI9233
NI9234
NI9235
NI9236
NI9237
NI9225
NI9227
Many C Series modules designed for high-speed, dynamic measurements use delta-sigma () converters. To better
understand how these modules work, you must first know the fundamentals of delta-sigma modulation. The Greek
letters delta and sigma are mathematical symbols for difference and sum, respectively. The modulation circuit of a
delta-sigma converter compares the running sum of differences between the desired voltage input, Vin, and a known
reference voltage, Vref. The output from the comparator becomes a bitstream that is sent into a digital filter and a
1-bit DAC. Because of this negative feedback, the differences oscillate around 0 V, or ground. The digital filter
effectively keeps track of how many times the difference is above 0 V, and, based on this count along with the
reference voltage, you can determine the input voltage. This modulation loop runs at a much higher frequency than
the actual output frequency of the converter.
118
C Series modules with delta-sigma converters feature an oversample clock that runs the modulation circuitry.
Oversample clocks, which run at 12 MHz or faster, affect timing, synchronization, and programming paradigms. The
following list provides insight into the specific challenges of C Series modules that use delta-sigma modulation.
Need a Sync Pulse to ResetOversample clocks need to be reset before they are used. This is why there
is a LabVIEW FPGA I/O node to send a start event to the module.
Time to Data Ready Is Non-ZeroThe time between the start event and data availability is specified as
time to first data. This time may vary slightly between different delta-sigma-based modules and greatly
between modules of other types. On-demand modules have a time to first data of zero. You can find
documentation on how to align the data sets in KnowledgeBase 4DAEUNNQ: How Do I Compensate for
Different Group Delays With C Series Modules in LabVIEW FPGA? and KnowledgeBase 53CHLD6C: What
Is the Best Method to Synchronize Two Different DSA Modules in LabVIEW FPGA?
Sample Rates Are Discrete and SpecificBecause of the oversample clock and the digital filter, delta-sigma
modules can run only at discrete sample rates. These sample rates are a function of a divisor and the oversample
clock. This is why the rate input for a delta-sigma module is an enumerated data type of predetermined sample
rates. If you try to input a sample rate that is not supported, it is rounded to the next highest available sample rate.
Minimum Sample Rates Are Greater Than 1 kHzThe minimum sample rate for delta-sigma modules is
often over 1 kHz. Use averaging, filtering, or some form of decimation to further reduce your data set beyond
the rate the digital filter on the module outputs.
No Irregular or External ClocksDelta-sigma modules cannot report data on demand and thus do not work
with irregularly timed I/O node calls because the iterative process must complete a large number of loops before
returning accurate data. The I/O node for a delta-sigma module always blocks for the exact (t) for which the
module has been set to acquire. An I/O node call at an interval less than t must wait until the full sample period
is complete. This gives the oversample circuitry enough time to calculate an accurate value. To compensate for
this, implement a resampling algorithm on the FPGA before processing your data or using it in a control loop.
Physically Share Oversample Clock to Synchronize ModulesTwo delta-sigma modules that need to be
synchronized must share the same oversample clock. To synchronize modules, the oversample clock from one
module must be exported from the right-click properties menu as the source module in the LabVIEW project.
It must be imported from the same menu of the other client modules. Any module can be a source or a
client moduleit is up to the programmers discretion. Remember, changes made to a module property window
from the project view cause a recompile and cannot be changed at run time.
You can see many of these caveats in the block diagram of the example program NI9234 Getting Started.lvprj shown
in Figure 6.10.
You can find example programs for all of the delta-sigma modules in the NIExample Finder.
119
Multiplexed
One of the more expensive components of a module is the ADC. By using a multiplexer, also known as a mux, to
route multiple channels through a single ADC, multiplexed modules offer higher channel counts at lower per channel
prices than simultaneous modules.
Before learning how to program these modules, you need to know some specification-level details. First, the sample
rates are often listed as the total rate of all channels put together, also known as an aggregate rate. From the module
hardware standpoint, all channels selected must run at the same rate (aggregate rate divided by number of channels),
but from the program standpoint, you can remove samples from select channels with FPGA processing. Second, it is
important to note that there is an interchannel delay, or skew, between all channels in a multiplexed module. You can
implement processing in the FPGA to compensate for this skew via shifting or data resampling, but most systems that
incorporate multiplexed modules are not impacted by this small offset. If hardware-based phase alignment is important
to your system, you should select a module with multiple ADCs.
You can choose from two main subsets of multiplexed modules: high speed and low speed.
High Speed
High-speed multiplexed modules implement a double pipeline to increase the throughput of data to the chassis. With
a double pipeline, the first valid data cannot be returned until the process has run two complete iterations. Once the
first two iterations have run to prime the pipeline, the subsequent iterations begin to yield valid data. When using an
I/O node to sample channels, the pipeline is automatically managed by the FPGA I/O node, and the channels within
the FPGA I/O node are sampled in numerical order regardless of the order they appear in the node. If the first two
channel requests in the FPGA I/O node do not match the two channel requests stored in the module pipeline, there is
a delay before the first channel sample occurs. This delay is caused by the FPGA I/O node automatically updating the
module channel sample pipeline, which takes two channel sample cycles. This situation could happen if you have I/O
nodes addressing the same module from different parts of the block diagram. For example, if in an init case of a
Case structure, you read channels 0, 1, and 2 from an I/O node and then in the acquire case, you read from
channels 5, 6, and 8, you incur the pipeline updating penalty because the module is already primed for channels 0, 1,
and 2 and needs to flush the pipeline. If this delay causes problems, the workaround is to acquire all of the channels in
the same step and place data from channels 5, 6, and 8 into a FIFO to be called upon later.
NIC Series High-Speed Multiplexed Modules
Model Number
Description
NI9205
NI9206
NI9201
NI9221
NI9203
120
Description
NI9211
NI9213
NI9214
NI9217
NI9207
NI9208
SPI Digital
Digital modules that feature more than eight lines exceed the number of pins allowed for direct FPGA communication
and, thus, communicate over the SPI bus. These modules operate with a convert pulse, and they latch inputs and
update outputs simultaneously with each convert. As with any other SPI bus module, all of the lines on a 32-channel
digital I/O module are routed through the same communication lines to the backplane. You should control the I/O
node calls to SPI bus modules with dataflow to prevent simultaneous calls resulting in jitter. These calls include normal
I/O calls as well as commands to change line direction from input to output.
121
Synchronizing Modules
Some applications, such as vibration or sound measurement, require a high level (sub 100 nS) of synchronization
between channels. This section discusses timing and synchronization of both delta-sigma-based modules and
scanned (SAR) modules. Any NIC Series I/O module that is not classified as delta sigma is classified as SAR.
Figure 6.11. Export the clock from the chosen master module (left) and then select it
from all subsequent modules to be synchronized (right).
2. On the block diagram, create a property node for each I/O module and use the Data Rate enum to specify the
rate, as shown in Figure 6.12. Note that even though the I/O modules share the same sampling rate, you must
create a unique Data Rate enum for each property node (right-click on the property node for each module and
select create constant). This ensures that the enum integer is properly matched to the expected rate for the
specific I/O module.
3. Create a Start Trigger for each I/O module and place them into the same I/O node. This ensures the start
triggers are properly routed.
122
4. Place all channel reads from all synchronized modules in the same I/O node as seen in Figure 6.12. Using this
process, you can mix and match any of the existing simultaneous delta-sigma modules.
The best method for synchronizing different delta-sigma modules in LabVIEW FPGA is to have the I/O nodes for each
module in the same While Loop. If you place the I/O nodes for the different modules in parallel While Loops, you must
address additional startup delays. You also need to take into account thegroup delayfor each module because the
modules acquire data at the same time when in the same loop. View KnowledgeBase 4DAEUNNQ: How to Compensate
for Different Group Delays With C Series Modules in LabVIEW FPGA for tips on this topic.
123
An application becomes more complicated when it requires multirate synchronization between delta-sigma and SAR
modules. Since these modules have different timebases, they cannot share a clock when they are separated into two
or more loops executing at multiple rates. The best option is to separate them into multiple loops and then expect
some drift between the timebases over time, in addition to a phase offset caused by the varying startup times.
124
CHAPTER 7
Adding I/O to the CompactRIO System
Adding I/O to CompactRIO
NIproducts based on the LabVIEW reconfigurable I/O (RIO) architecture are increasingly adopted for system-level
applications that require high-channel counts, intensive processing, and distributed I/O. Adding RIO expansion I/O to
the NIRIO product offering enables a 1:N system topology with one controller and many FPGA I/O nodes for flexible,
high-channel-count systems that can perform both distributed control and centralized processing.
NIoffers three types of expansion chassis systems for expanding your I/O. Each expansion chassis features an FPGA
and is based on the same C Series module architecture. The main differences between expansion I/O options stem
from the choice of bus, with each bus being best suited for a subset of expansion I/O applications. The NII/O expansion
chassis systems include the following:
MXI-Express RIO
Ethernet RIO
EtherCAT RIO
Each expansion chassis has unique capabilities. Choose an expansion chassis depending on your application
requirements. Table 7.1 provides a quick comparison of the three different types of expansion chassis.
125
MXI-Express RIO
Ethernet RIO
EtherCAT RIO
NI9157, 9159
NI9148
NI9144
Slots
14
FPGA
Spartan 2M
Spartan 2M
Daisy chain
Same as Ethernet
Daisy chain
7 m between nodes
FPGA-based DIO
FPGA-based DIO
<10 s
No Spec
<1 s
250 MB/s
100 Mbit/s
100 Mbit/s
API Support
Host
Windows/Real-Time
Windows/Real-Time
Real-Time Only
Network Topology
Distance
Multichassis Synchronization
Communication Jitter
Bus Throughput
MXI-Express RIO
Featuring a high-performance Xilinx Virtex-5 FPGA and a PCI Express x1 cabled interface, an NI9157/9159
MXIExpress RIO 14-slot chassis for C Series I/O expands the RIO platform for large applications requiring high-channel
counts and a variety of signal conditioning and custom processing and control algorithms. You can use these
MXIExpress RIO expansion chassis with high-performance NIcRIO-9081/9082 CompactRIO systems in addition to
industrial controller and PXI systems. When using a MXI-Express RIO expansion chassis, you interface to the expansion
chassis I/O within your main controller VI using LabVIEW FPGA Host Interface functions.
NIcRIO-9081/9082 Systems
126
Ethernet RIO
When expanding your I/O using the standard Ethernet protocol, you can use the NI9148 Ethernet RIO expansion
chassis. Programmers can take advantage of the existing network infrastructure such as switches and routers.
Although full duplex switch networks eliminate packet collisions, switches introduce jitter, and you should use
general Ethernet only in applications that do not require deterministic communication. If you need synchronization
between the local I/O and expansion I/O, see the EtherCAT RIO section for more information.
When using the Ethernet RIO expansion chassis, the main controller is responsible for running the real-time control
loop using I/O from its own chassis in addition to the I/O from one or more Ethernet RIO chassis. The expansion
chassis provides expansion or distributed I/O for the main controller.
The Ethernet RIO expansion chassis works with both LabVIEW FPGA and the Scan Engine. If you use LabVIEW
FPGA with the expansion chassis, you can embed decision-making capabilities to quickly react to the environment
without host interaction. The FPGA can also offload processing from the main controller by conducting inline analysis,
custom triggering, and signal manipulation.
When using LabVIEW FPGA, you should create a regular While Loop or a Timed Loop with a lower priority to handle
the communication since Ethernet is nondeterministic (see Figure 7.4). This allows your control task to run
deterministically and reliably because it is not affected by the possibly high-jitter I/O device. When using LabVIEW
FPGA, you interface to the I/O within your real-time VI using the FPGA Host Interface functions.
Figure 7.4. Add a new process to handle the I/O expansion task when using LabVIEW FPGA
Interface Mode.
127
The Ethernet RIO expansion chassis also works with the Scan Engine. You have the option to choose Scan Mode or
FPGA Interface Mode when adding the Ethernet RIO chassis to your LabVIEW project. When using Scan Mode, your
design diagram might look like Figure 7.5, where you have all of your system I/O accessible from the Scan Engine.
When using Scan Mode, you interface to the I/O within your real-time VI using the Scan Engine I/O variables.
Figure 7.5. You can use the NIScan Engine to handle I/O with the NI9148 Ethernet RIO chassis.
To get started with the NI9148 Ethernet RIO expansion chassis, see the NIDeveloper Zone tutorial Getting Started
With the NI9148 Ethernet RIO Expansion Chassis.
EtherCAT RIO
In certain applications, the main I/O and expansion I/O systems require tight synchronizationall of the inputs and
outputs must be updated at the same time. Using a deterministic bus allows the main controller to know not only
when the expansion I/O is updated but also exactly how long the data takes to arrive. You can easily distribute
CompactRIO systems with deterministic Ethernet technology using the NI9144 expansion chassis.
The NI9144 is a rugged expansion chassis for expanding CompactRIO systems using a deterministic Ethernet
protocol called EtherCAT. With a master-slave architecture, you can use any CompactRIO controller with two
Ethernet ports as the master device and the NI9144 as the slave device. The NI9144 also has two ports that permit
daisy chaining from the controller to expand time-critical applications.
Host Computer
NI cRIO-9074
(TCP/IP)
(EtherCAT)
NI 9144
Figure 7.6. The CompactRIO hardware architecture expands time-critical systems
using the NI9144 deterministic Ethernet chassis.
128
NI cRIO-9074
NI 9144
(EtherCAT)
(TCP/IP)
Figure 7.7. Hardware Setup for Ethernet RIO Tutorial
129
5. If the controller already has LabVIEW Real-Time and NI-RIO installed on it, select Custom software
installation and click Next. Click Yes if a warning dialog box appears. Click the box next to NI-Industrial
Communications for EtherCAT. The required dependencies are automatically checked. Click Next to continue
installing software on the controller.
6. Once the software installation is finished, select the controller under Remote Systems in the Configuration
pane. Navigate to the Network Settings tab in the bottom right portion of the window. In the Network Adapters
window, select the secondary Ethernet Adapter (the one that does not say primary). Next to Adapter Mode, select
EtherCAT in the pull-down box and hit the Save button at the top of the window.
130
Figure 7.9. Select EtherCAT as the mode for the second Ethernet port of the CompactRIO
controller.
131
3. By default, the I/O channels show up in the project as Scan Engine I/O variables. The Scan Engine
automatically manages I/O synchronization so that all modules are read and updated at the same time once
each scan cycle.
Note: For high-channel-count systems, you can streamline the creation of multiple I/O aliases by exporting and
importing .csv spreadsheet files using the Multiple Variable Editor.
Step 2: Add Deterministic I/O (Option 2LabVIEW FPGA)
1. In the LabVIEW Project Explorer window, right-click on the CompactRIO controller and select NewTargets
and Devices.
2. In the Add Targets and Devices dialog window, expand the category EtherCAT Master Device to autodiscover
the EtherCAT port on the master controller. Select your EtherCAT device and click OK. The LabVIEW project
now lists the master controller, the NI9144 chassis, their I/O modules, and the physical I/O on each module.
By default the I/O channels show up in the project as Scan Engine I/O variables.
3. Right-click the EtherCAT device in the LabVIEW project and select NewFPGA Target. You can now create a
LabVIEW FPGA VI to run on the EtherCAT target. By default the chassis I/O is added to the FPGA target but
not the I/O modules. To program the C Series module I/O using LabVIEW FPGA, drag the C Series modules
from the EtherCAT device target onto the FPGA target in the LabVIEW Project Explorer window.
132
Figure 7.11. Drag C Series I/O modules under the FPGA target
to access them with LabVIEW FPGA.
4. Create an FPGA VI under the EtherCAT device target and program using the EtherCAT I/O. The Figure 7.12
example uses the FPGA on an EtherCAT chassis to output a PWM signal.
Note: There is a limit to the number of user-defined I/O variables that you can create in FPGA Interface Mode. The
NI9144 can hold a total of 512 bytes of input data and 512 bytes of output data for both I/O variables in Scan Mode
and user-defined I/O variables in FPGA Interface Mode. For example, if you are using four 32-channel modules in Scan
Mode and each channel takes up 32 bits of data, then Scan Mode I/O variables are using 256 bytes of input data.
With the remaining 256 bytes of input data, you can create up to 64 input user-defined I/O variables (also of 32-bit
length) in FPGA Interface Mode.
5. The next step is creating an interface that allows the Real-Time VI to communicate to the FPGA VI on the EtherCAT
expansion chassis. For example, you need the user to be able to control the pulse width of the PWM signal,
along with the invert pulse input. To transfer data to or from an FPGA on an EtherCAT chassis to a Real-Time VI,
you use a new mechanism called user-defined I/O variables. To create a user-defined I/O variable, right-click the
EtherCAT device target and select NewUser-Defined Variable.
133
6. In the Properties dialog box, specify the variable name, data type, and direction (FPGA to host or host to
FPGA). Drag and drop the user-defined I/O variables onto your FPGA VI.
Figure 7.14. Drag and drop user-defined I/O variables onto the FPGA VI.
Note: These user-defined I/O variables transfer single-point data to and from the master controller at each scan cycle,
so they are best used for passing processed data from the NI9144 FPGA.
7. Drag and drop the same variables onto your Real-Time VI to communicate between the two targets.
134
CHAPTER 8
Communicating With Third-Party Devices
This section examines different methods for communicating with third-party devices from a CompactRIO
controller. Because CompactRIO has built-in serial and Ethernet ports, it can easily work with Modbus TCP, Modbus
Serial, and EtherNet/IP protocols. You can find information on using the Ethernet port to communicate to an HMI
in Chapter 4: Best Practices for Network Communication.
When interfacing to a third-party device in LabVIEW Real-Time using RS232, USB, or Ethernet ports, you should
consider adding a separate process for handling the communication since these protocols are nondeterministic.
This allows the control task to run deterministically and reliably because it is not affected by the possibly high-jitter
I/O device.
Figure 8.1. Add a separate process for handling any nondeterministic communication to a
third-party device over serial or Ethernet.
135
As a single-ended bus, RS232 is ideal for shorter-distance communications (under 10 m). Shielded cables reduce
noise over longer runs. For longer distances and higher speeds, RS485 is preferred because it uses differential
signals to reduce noise. Unlike buses such as USB and IEEE 1394, RS232 is not designed to power end devices.
CompactRIO controllers have an RS232 port that features the standard D-SUB 9-pin male connector (also known as
a DE-9 or DB-9). You can use this port to monitor diagnostic messages from a CompactRIO controller when the
console out switch is engaged or to communicate with low-cost RS232 devices in your application.
RS232 Wiring and Cabling
RS232 ports feature two standard pinouts. You can classify RS232 devices as data terminal equipment (DTE), which
is like a master or host, and data communications equipment (DCE), which is similar to slaves. DCE ports have
inverted wiring so that DCE input pins connect to DTE output pins and vice versa. The serial port on CompactRIO
controllers is a DTE port, and the serial port on a device such as a GPS, bar code scanner, modem, or printer is a
DCE port.
When connecting a CompactRIO DTE RS232 port to a typical end device with a DCE RS232 port, you use a regular
straight-through cable. When connecting two DTE or DCE devices together, such as a CompactRIO controller to a
PC, you need to use a null modem cable, which swaps the transmit and receive signals in the cabling.
136
Device 1
Device 2
Cable Type
DTE
DTE
DTE
DCE
Straight-through cable
DCE
DTE
Straight-through cable
DCE
DCE
Loopback Testing
A common technique for troubleshooting and verifying serial port functionality is loopback testing. At a basic level, all
you need to do is connect the TXD to the RXD pin. Use a standard RS232 straight-through or loopback cable and a
small bent paper clip to short pins 2 and 3. With the loopback cable installed, bytes sent from the read function can
be read by the read function. You can verify that software, serial port settings, and drivers are working correctly with
this technique.
137
For most simple instrument applications, you need only two VISA functions, VISA Write and VISA Read. Refer to the
Basic Serial Write and Read VI in the labview\examples\instr\smplserl.llb for an example of how to use VISA functions.
Most devices require you to send information in the form of a command or query before you can read information
back from the device. Therefore, the VISA Write function is usually followed by a VISA Read function. Because serial
communication requires you to configure extra parameters such as baud rate, you must start the serial port
communication with the VISA Configure Serial Port VI. The VISA Configure Serial Port VI initializes the port identified
by the VISA resource name.
It is important to note that the VISA resource name refers to resources on the machine for which the VI is targeted.
Figure 8.5. You can directly browse to the VISA resource name from
the VISA resource control in LabVIEW or from MAX.
Check the bottom left corner of the VI to determine which target the VI is linked to. For CompactRIO, use COM1 to use
the built-in port. COM 1 on a CompactRIO controller is ASRL1::INSTR. If you are connected to the CompactRIO
controller, you can directly browse to the VISA resource name from the VISA resource control in LabVIEW or from MAX.
Timeout sets the timeout value for the serial communication. Baud rate, data bits, parity, and flow control specify
those particular serial port parameters. The error in and error out clusters maintain the error conditions for this VI.
Though the ports work at the byte level, the interfaces to the read and write functions are strings. In memory, a
string is simply a collection of bytes with a length attached to it, which makes working with many bytes easier to
program. The string functions in LabVIEW provide tools to break up, manipulate, and combine data received from a
serial port. You can also convert string data to an array of bytes for using LabVIEW array functions to work with lowlevel serial data.
Because serial operations deal with varying-length strings, these tasks are nondeterministic. Additionally, serial
interfaces by nature are asynchronous and do not have any mechanisms to guarantee timely delivery of data. To
maintain the determinism of your control loops, when programming serial applications keep any communications
code in a separate loop from the control code.
138
The VISA Read function waits until the number of bytes requested arrives at the serial port or until it times out. For
applications where this is known, this behavior is acceptable, but some applications have different lengths of data
arriving. In this case, you should read the number of bytes available to be read, and read only those bytes. You can
accomplish this with the Bytes at Serial port property accessible from the Serial palette.
You can access serial port parameters, variables, and states using property nodes. If you open the VISA Configure
Serial Port VI and examine the code, you see that this VI simply makes a call to many property nodes to configure the
port. You can use these nodes to access advanced serial port features, including the auxiliary data lines, bytes
waiting to be read/written, and memory buffer sizes. Figure 8.7 shows an example of using a property node to check
the number of bytes available at the port before reading.
Figure 8.7. Using a VISA Property Node to Read the Number of Bytes
In general, working with devices can range from simply reading periodically broadcasted bytes such as GPS data to
working with complex command structures. For some devices and instruments, you can find preprogrammed
instrument drivers on ni.com/idnet, which can simplify development. Because these drivers use NI-VISA functions,
they work with the onboard CompactRIO serial port.
139
In LabVIEW, place aVISA Configure Serial PortVI or aVisa Property Nodeto configure the settings of your individual ports.
140
Figure 8.9. Program an NI987x with the VISA API when using Scan Mode.
Once you have set the serial port to match that of the connected device, use theVISA APIas you would when using
any other VISA device.
Note: This maximum nonstandard baud rate for the NI9871 module (3.6864 Mbit/s) can be achieved only while using
the FPGA interface. The maximum baud rate while using either module with the RIO Scan Interface is 115.2kbit/s.
Using NI987x Serial Modules With LabVIEW FPGA
You also can access NI987x serial modules with LabVIEW FPGA. See the Figure 8.10 example titled NI987x Serial
Loopback.lvproj in the NIExample Finder. This example demonstrates communication to the NI987x serial port and
streaming serial data to a real-time VI.
141
Figure 8.10. You can find the NI987x serial loopback example for LabVIEW FPGA in the
NIExample Finder.
142
Industrial Communications
OPC
Figure 8.11. Three Methods for Connecting a CompactRIO Controller to an Industrial Device
143
Industrial protocols take a low-level bus like RS232 or TCP/IP and add predefined techniques for communication on
top. This is similar to how HTTP, the protocol for web content delivery, sits on top of TCP/IP. It is possible to write
your own HTTP client like Internet Explorer or Firefox, but it takes a large amount of effort and may not accurately
connect to all servers without hours of testing and verification. Similarly, devices and controllers that support
industrial networking standards are much easier to integrate at the program level and to use for abstracting the lowlevel communication details from end users, so engineers can focus on the application.
Because CompactRIO has built-in serial and Ethernet ports, it can easily work with many protocols including Modbus
TCP, Modbus Serial, and EtherNet/IP. You also can use plug-in modules for communication with most common
industrial protocols such as PROFIBUS and CANopen.
When you cannot use native communication, another option is gateways. Gateways are protocol translators that can
convert between different industrial protocols. For example, you can connect to a CC-Link network by using a
gateway. The gateway can talk Modbus TCP on the PAC end and translate that to CC-Link on the other end.
Modbus Communications
Modbus is the most common industrial protocol in use today. Developed in 1979, it supports both serial and
Ethernet physical layers. Modbus is an application layer messaging protocol for client/server communication
between devices connected on a bus or network. You can implement it using asynchronous serial transmission to
communicate with touch screens, PLCs, and gateways to support other types of industrial buses. Modbus works
with a CompactRIO controller and its onboard serial or Ethernet modules. Note that the onboard serial port of
CompactRIO hardware uses RS232 though some Modbus devices may use the RS485 electrical layer. In this case,
you can use a common RS485-to-RS232 adapter.
144
The Modbus serial protocol is based on a master/slave architecture. An address, ranging from 1 to 247, is assigned to
each slave device. Only one master is connected to the bus at any given time. Slave devices do not transmit information
unless a request is made by the master device, and slave devices cannot communicate to other slave devices.
Information is passed between master and slave devices by reading and writing to registers located on the slave device.
The Modbus specification distinguishes the use of four register tables, each capable of 65,536 items and differentiated
by register type and read-write access. Register address tables do not overlap in this implementation of LabVIEW.
Tables
Object Type
Type of Access
Comments
Discrete Inputs
Single-Bit
Read Only
Coils
Single-Bit
Read-Write
Input Registers
16-Bit Word
Read Only
Holding Registers
16-Bit Word
Read-Write
Table 8.2. Information is passed between master and slave devices by reading
and writing to registers located on the slave device.
Before starting with Modbus programming, you must determine several important parameters of your Modbus
device by consulting its documentation:
1. Master or slave? If your Modbus device is a slave, configure your CompactRIO controller as a master.
This is the most common configuration. Likewise, connecting to a Modbus master (such as another PLC)
requires configuring the CompactRIO controller as a slave.
2. Serial or Ethernet? Modbus Ethernet devices are sometimes called Modbus TCP devices.
3. For Modbus serial
RS232 or RS485? Many Modbus devices are RS232, but some use the higher power RS485 bus for
longer distances. RS232 devices can plug directly into a CompactRIO system, but an RS485 device
needs an RS232-to-RS485 converter to function properly.
RTU or ASCII mode? RTU/ASCII refers to the way data is represented on the serial bus. RTU data is in
a raw binary form, whereas ASCII data is human readable on the raw bus. This parameter is required
by the Modbus VIs.
4. What are the register addresses? Every Modbus device has a mapping of its I/O to registers, coils, and
discrete inputs for reading and writing that is represented by a numerical address. Per Modbus convention,
a register address is always one less than the register name. This is similar to the first element of an array
being element 0. The Modbus LabVIEW Library requires register addresses, not register names.
Modbus Tutorial
The NIDeveloper Zone document How to Turn an RT Target Into a Modbus Slave Using I/O Servers walks you
through the steps of turning your CompactRIO controller into a Modbus slave. It also shows you how to read from
this server with LabVIEW for Windows if you do not have a third-party Modbus server. Before starting the tutorial,
install the Modbus I/O Server onto your CompactRIO target through MAX.
Additionally, with the LabVIEW Real-Time and LabVIEW Datalogging and Supervisory Control (DSC) modules, you
can configure Modbus I/O servers on the development computer to communicate with Modbus devices. If you do
not have the LabVIEW Real-Time or LabVIEW DSC modules, you can use the free LabVIEW Modbus Library to
create Modbus master or slave applications with any Ethernet or serial ports on your development computer. This
145
library provides a set of lower-level VIs for greater flexibility, performance, and customization. Download the
LabVIEW Modbus Library to begin programming your Modbus applications today.
Figure 8.14.The LabVIEW Modbus Library provides low-level functions for greater flexibility
and performance.
Modbus Serial- and TCP-based communications are also available as a third-party add-on on the LabVIEW Tools
Network calledModBusVIEW over TCP.
EtherNet/IP
EtherNet/IP is a protocol built on the Common Industrial Protocol (CIP) for communications with EtherNet/IP devices.
This protocol, developed and commonly found on Rockwell Automation (Allen-Bradley) PLCs, uses standard Ethernet
cabling for communications with industrial I/O. EtherNet/IP is an application layer protocol that uses TCP for general
messages and User Datagram Protocol (UDP) for I/O messaging and control.
Figure 8.15. With EtherNet/IP, you can directly read and write to tags on a Rockwell PLC from
CompactRIO.
The LabVIEW Driver for EtherNet/IP provides both explicit messaging API and implicit I/O data communication with a
wide range of PLCs and other EtherNet/IP devices. With this driver, the CompactRIO controller supports direct
communication to Rockwell Automation PLCs, allowing for easy integration into a new or an existing system.
146
You can use the LabVIEW Driver for DNP3 Outstation Support to program a real-time target, such as a CompactRIO
system, as an outstation device with advanced functionality like power quality monitoring, phasor measurements, and
other smart grid-related analysis. The DNP3 software driver supports Ethernet and serial communication, file transfer,
and time synchronization between the master and outstation. Multiple communication channels per outstation and
multiple sessions (logical devices) per channel also work with this driver.
OPC
OPC, or Open Platform Communications, is a common protocol used in many applications with high channel counts
and low update rates, which are common in process industries such as oil and gas and pharmaceutical
manufacturing. OPC is designed for connecting HMI and SCADA systems to controllersit is not generally used for
communication between controllers. A common use for OPC is to integrate a CompactRIO controller into a thirdparty system for HMI and SCADA applications.
The OPC specification is a large collection of standards that span many applications. This section covers OPC Data Access
(DA), the core specification that defines how to universally move data around using common Windows technologies
and OPC Unified Architecture (UA), a cross-platform standard optimized for security and with extended functionality.
147
Figure 8.17. Communicate OPC data items with network-published shared variables.
OPC DA is a Windows-only technology and the CompactRIO controller cannot directly communicate using the OPC
DA protocol. Instead, a Windows PC can communicate to the CompactRIO controller using the NI-PSP protocol and
can translate and republish the information via OPC. When running on a Windows machine, the Shared Variable
Engine functions as an OPC server and performs this translation and republishing automatically. This means other
OPC DA clients, such as third-party SCADA packages or process control software, can access and retrieve data from
the CompactRIO device.
148
2. To publish the variables as OPC DA data items, bind each variable hosted on the CompactRIO controller to a
variable hosted on the Windows PC. To create variables hosted on a Windows PC, right-click My Computer in
the LabVIEW Project and select NewVariable.
3. In the Shared Variable Properties window, give the variable a useful name such as SV_PID_SetPoint_OPC.
Check the Enable Aliasing box and click the Browse button to browse to the SV_PID_SetPoint variable on the
CompactRIO controller.
149
4. Save the new library you create with a useful name, such as OPC Library.lvlib.
5. Deploy the variables to the Shared Variable Engine by right-clicking the library and selecting Deploy.
6. The shared variable is now published as an OPC DA item. Other OPC DA clients can now connect to the
Windows PC and use the data for display, HMI, and so on. You can verify that the variable is working correctly
by launching an OPC DA client such as the NIDistributed System Manager
(StartProgramsNationalInstrumentsNIDistributed System Manager).
Figure 8.21. The OPC clients, such as the NIDistributed System Manager,
can read and write to the OPC item.
150
7. If you have an OPC DA client, such as the LabVIEW DSC Module, you can verify that the variable is working
from that client as well. NIshared variable OPC DA items are published under the National Instruments.
Variable Engine.1 server name.
8. Once variables are deployed in the Shared Variable Engine, they stay deployed with subsequent reboots of the
OPC DA server machine.
9. Find more information on the Shared Variable Engine and OPC DA in the LabVIEW Help file Connecting to
OPC Systems Using LabVIEW (Windows Only).
Figure 8.22.The OPC UA VIs support both nonsecure connections and secure connections
between an OPC UA server and an OPC UA client.
To learn more about the OPC UA standard, read the white paper Why OPC UA Matters. For example code on how
to use the OPC UA API, review the project C:\Program Files\National Instruments\LabVIEW XXXX\examples\
comm\OPCUA\OPC UA Demo.lvproj.
OPC Servers
In addition to OPC DA I/O servers and the OPC UA API, National Instruments provides an OPC Server solution that
contains a list of drivers for many of the industrys PLCs. For a list of supported PLCs, refer to the NI Developer Zone
articleSupported Device & Driver Plug-in List for NI-OPC Servers.
151
152
CHAPTER 9
Designing a Touch Panel HMI
Building User Interfaces and HMIs Using LabVIEW
This chapter examines one software design architecture for building an operator interface with a scalable navigation
engine for cycling through different human machine interface (HMI) pages.
You can use this architecture to build an HMI based on LabVIEW for any HMI hardware targets including the
NITPC2212 touch panel computer running the Windows Embedded Standard 7 (WES7) OS or the NITPC-2206
running the Windows XP Embedded (XPe) OS. LabVIEW is a full programming language that provides one solution for
a variety of development tasks ranging from HMI/SCADA systems to reliable and deterministic control applications.
The LabVIEW Touch Panel Module offers a graphical programming interface that you can use to develop an HMI in
a Windows development environment and then deploy it to an NItouch panel computer (TPC) or any HMIs running
Windows Embedded Standard 7 or Windows XP Embedded.
153
Navigation Loop
The navigation loop handles the management and organization of different UIs in your application. You can implement
a navigation loop as a simple state machine built with a While Loop and a Case structure. Each case encloses an
HMIpage VI that, when called, is displayed on the HMI screen. Figure 9.2 is an example of a navigation loop.
154
This example uses the HMI Navigation Engine (HNE) Reference Library, which was created for HMI page
management and navigation. The HNE is based on VIs included with the LabVIEW Touch Panel Module, but it
features an additional history cache so the user can define a button to jump backward toward the previously viewed
screen. The HNE also includes basic templates and examples for getting started. Refer to theNIDeveloper Zone
documentHMI Navigation Engine (HNE) Reference Libraryto download the HNE library.
The HNE installs a page manager APIpalette named HNE to the User Libraries palette in LabVIEW.
HNE Page Manager (Init)This VI initializes the HNE by setting the navigation history depth and setting the
name of the first page to be displayed.
HNE Page Manager (Next)This VI returns the name of the next page and passes it to the Case structure in
the HNE.
HNE Page Manager (Set)This VI sets the name of the next page to be displayed. It is used within HMI
pages to support navigation buttons.
HNE Page Manager (Back)This VI returns the name of the previous page from the page history. It is used
within HMI pages to support the operation of a back navigation button.
Examples subpaletteThis is a subpalette that contains the example VI for the HNE API.
Templates subpaletteThis is a subpalette that contains two template VIs for the HNE API. The first is a
template VI for the navigation loop called HMI_NavigationEngine VI and the second is a template for an
HMIpage called HMI_Page VI.
155
The navigation engine uses VIs from the Touch Panel Navigation palette.
TPC Initialize NavigationThis VI initializes the navigation engine by setting the navigation history depth and
the name of the first page to be displayed.
TPC Get Next PageThis VI returns the name of the next page and passes it to the Case structure in the HMI
navigation engine.
TPC Set Next PageThis VI sets the name of the next page to be displayed. Use it within HMI pages to
support navigation buttons.
TPC Set Previous Navigation PageThis VI returns the name of the previous page from the page history.
Use it within HMI pages to support the operation of a back navigation button.
The page state and history are stored in a functional global variable that each of these VIs accesses.
UI Pages
As stated above, the navigation loop contains all of the HMI pages for an application. Each HMI page is a LabVIEW VI
created to monitor and configure a specific process or subprocess in the machine. The most common elements on a
page front panel are navigation buttons, action buttons, numeric indicators, graphs, images, and Boolean controls
and indicators. Figure 9.5 shows an example page containing a typical set of front panel elements.
156
The page block diagram uses the event-based producer consumer design pattern to implement a responsive, eventdriven UI. The example in Figure 9.6 uses the Asynchronous Message Communication (AMC) reference library for
interprocess communication. You can download the AMC reference library, which uses queues for interprocess
communication, from the NIDeveloper Zone document Asynchronous Message Communication (AMC)
Reference Library. The AMC library also has an API based on UDP that you can use to send messages across the
network. You can implement the Figure 9.6 example using queue functions for communicating between the Event
Handler process and the Message process.
For more information on creating UI pages, see the NIDeveloper Zone document Creating HMI Pages for the
LabVIEW Touch Panel Module.
157
CHAPTER 10
Adding Vision and Motion
Machine Vision/Inspection
Machine vision is a combination of image acquisition from one or more industrial cameras and the processing of the
images acquired. These images are usually processed using a library of image processing functions that range from
simply detecting the edge of an object to reading various types of text or complex codes.
Often more than one of these measurements is made on one vision system from one or more images. You can use
this for many applications including verifying that the contents of a container match the text on the front of the bottle
or ensuring that a code has printed in the right place on a sticker.
The information from these processed images is fed into the control system for data logging, defect detection,
motion guidance, process control, and so on.
For information on the algorithms in NIvision tools, see the Vision Concepts Manual.
158
to 5MP with color and monochrome options. These cameras feature dual Gigabit Ethernet ports, digital inputs and
outputs, and a built-in lighting controller.
NIalso offers plug-in image acquisition devices called frame grabbers that provide connectivity between industrial
cameras and PCI, PCI Express, PXI, and PXI Express slots. These devices are commonly used for scientific and
automated test applications, but you also can use them to prototype a vision application on a PC before you
purchase any industrial vision systems or smart cameras.
All NIimage acquisition hardware uses the same driver software called NIVision Acquisition Software. With this
software, you can design and prototype your application on the hardware platform of your choice and then deploy it
to the industrial platform that best suits your application requirements with minimal code changes.
Where
159
Working distance is the distance from the front element (external glass) of the lens to the object
under inspection
Focal length measures how strongly a lens converges (focuses) or diverges (diffuses) light
For example, if the working distance of your imaging setup is 100 mm, and the focal length of the lens is 8 mm, then
the FOV in the horizontal direction of an NISmart Camera using the VGA sensor in full Scan Mode is
Based on the result, you can see that you may need to adjust the various parameters in the FOV equation until you
achieve the right combination of components that match your inspection needs. This may include increasing your
working distance, choosing a lens with a shorter focal length, or changing to a high-resolution camera.
Software Options
Once you have chosen the hardware platform for your machine vision project, you need to select the software
platform you want to use. NIoffers two application development environments (ADEs) for machine vision. Both
NICompact Vision Systems and NISmart Cameras are LabVIEW Real-Time targets, so you can develop your
machine vision application using the LabVIEW Real-Time Module and the NIVision Development Module.
The Vision Development Module is a library of machine vision functions that range from basic filtering to pattern
matching and optical character recognition. This library also includes the NIVision Assistant and the Vision Assistant
Express VI. The Vision Assistant is a rapid prototyping tool for machine vision applications. With this tool, you can use
160
click-and-drag, configurable menus to set up most of your application. With the Vision Assistant Express VI, you can
use this same prototyping tool directly within LabVIEW Real-Time.
Another software platform option is NIVision Builder for Automated Inspection (AI). Vision Builder AI is a configurable
machine vision ADE based on a state diagram model, so looping and decision making are extremely simple. Vision
Builder AI features many of the high-level tools found in the Vision Development Module. Both hardware targets work
with Vision Builder AI as well, giving you the flexibility to choose the software you are most comfortable with and the
hardware that best suits your application.
NI Vision Application
Programming
Configuration
Vision Builder AI
Figure 10.4. NIoffers both configuration software and a full programming environment
for machine vision application development.
161
Figure 10.5. You can add NISmart Camera systems to the same LabVIEW project as
CompactRIO systems.
162
Figure 10.6. Adding a VI on Your NISmart Camera to Your Project in LabVIEW Real-Time
Upon deployment, this VI resides in smart camera storage and runs on the smart camera during run time.
To simplify the process of acquiring and processing images, NIincludes Express VIs in the Vision palette. Use these
Express VIs in this example to acquire images from the smart camera (or vision system) as well as process the
images. To access these Express VIs, right-click on the block diagram and choose VisionVision Express.
The first step is to set up an acquisition from your camera. If your camera is not available or not fixtured correctly yet,
you also can set up a simulated acquisition by opening images stored on your hard drive.
Start by dropping the Vision Acquisition Express VI onto the block diagram. This menu-driven interface is designed so
that you can quickly acquire your first image. If you have any recognized image acquisition hardware connected to
your computer, it shows up as an option. If not, you have the option on the first menu to open images from disk.
163
Figure 10.8. The Vision Acquisition Express VI guides you through creating a vision application
in LabVIEW.
Next, choose which type of acquisition you are implementing. For this example, select Continuous Acquisition with
inline processing so you can sit in a loop and process images. Next, test your input source and verify that it looks
right. If it does, then click the finish button at the bottom.
Once this Express VI generates the LabVIEW code behind the scenes, the block diagram appears again. Now drop
the Vision Assistant Express VI just to the right of the Vision Acquisition Express VI.
With the Vision Assistant, you can prototype your vision processing quickly. You can deploy this same tool to realtime systems, although traditional LabVIEW VIs are usually implemented to provide greater efficiency in real-time
systems. For an overview of the tools in this assistant, view the NIVision Assistant Tutorial.
Step 3. Communicate With the CompactRIO System
Once you have set up the machine vision you plan to conduct with the Vision Assistant Express VI, the last thing
to do is communicate the data with the CompactRIO system. You can use network-published shared variables
to pass data between the two systems. Network communication between LabVIEW systems is covered in depth
in an earlier section in this document. In this example, you are examining a battery clamp, and you want to return
the condition of the holes (if they are drilled correctly) and the current gap shown in the clamp.
164
As you can see in Figure 10.9, the results of the inspection are passed as current values to the CompactRIO system
via shared variables hosted on the CompactRIO system. You can also pass the data as commands to the
CompactRIO system.
165
Figure 10.10. Choose your execution target from the Vision Builder AI splash screen.
With this emulator, you can set up lighting and trigger options, arrange I/O to communicate to the CompactRIO hardware,
and complete many of the other actions required to configure the smart camera without having one available for your
development system. Once you have selected your execution target, click on New Inspection under Configure Inspection.
This takes you into the development environment, which features four main windows. Use the largest window, the
Image Display Window, to see the image you have acquired as well as any overlays you have placed on the image. Use
the window to the upper right, the State Diagram Window, to show the states of your inspection (with your current state
highlighted). The bottom right window, the Inspection Step palette, displays all the inspection steps for your application.
Lastly, the thin bar at the bottom is the Step Display Window, where you see all of the steps that are in the current state.
This example implements the same inspection as the LabVIEW example that inspected battery clamps and returned
the number of holes and the gap of the clamp back to CompactRIO via the two shared variables hosted on the
CompactRIO hardware.
166
From here, set up pattern matching, edge detection, object detection, code reading, or any other algorithms you need.
For example, implement a pattern match to set the overall rotation of the object, a detect objects to see if both of the
holes were in the clamp, and a caliper tool to detect the distance between the clamp prongs. This generates a few
pass/fail results that you can use to set the overall inspection status, which you can display on the overlay to the user.
167
Now create two new states by clicking the toggle main window view button (circled in red). Create a pass state and a fail
state. In both states, report the values back to CompactRIO but, in the fail state, also reject the part using some digital I/O.
Step 3. Communicate With the CompactRIO System
Vision Builder AI provides access to many of the I/O types discussed previously, including network-published shared
variables, RS232, Modbus, Modbus TCP, and raw TCP/IP. In this example, use the variable manager to access the
shared variables hosted on CompactRIO. Access the variable manager by navigating to Tools Variable Manager.
Here you can discover the variables on the CompactRIO system by navigating to the Network Variables tab. From
there, select and add the variables and bind them to variables within the inspection.
Now these results are sent back to the CompactRIO system, and the inspection waits on the next camera trigger.
As you can see, both methods (programmable and configurable) offer the user a way to acquire images, process
them, and then use the pertinent information to report results back to a CompactRIO control system or to directly
control I/O from a real-time vision system.
Motion Control
The term motion control is applied to applications ranging from simple on-off or open-loop control of rotary equipment
like fans and pumps to high-precision multiaxis position or velocity control synchronized to measurement and control
I/O. You can implement simple motion control through industrial control I/O: a standard digital output to a motor
starter or a PWM signal to a motor drive. Complex motion control applications, on the other hand, require specialized
software and hardware: supervisory control, cascaded control loops, motor commutation schemes, advanced tuning
algorithms, specialized sensors, actuators, feedback devices, and high-speed/high-precision I/O.
You can use CompactRIO for both simple and complex motion applications. For simple applications like standard
pump or fan control, generic analog or digital I/O modules and user-defined logic are sufficient. For more complex
applications that require precise position or velocity control, multiaxis coordination, or synchronization with I/O, NI
offers the LabVIEW NI SoftMotion Module.
168
NI SoftMotion turns a CompactRIO controller into a configurable custom motion controller by providing modular
motion control components that run on the CompactRIO real-time controller and user-configurable FPGA.
Components include APIs for motion programming in LabVIEW or in C, a motion engine that handles supervisory
control and trajectory generation, and motion control IP blocks for control loops and motion I/O. The modular
components of NI SoftMotion are combined differently depending on the system architecture and motion I/O
selection. Because NI SoftMotion is implemented in the LabVIEW Real-Time and LabVIEW FPGA modules with useraccessible components, it provides direct integration with all the other capabilities of CompactRIO at both the
LabVIEW Real-Time and LabVIEW FPGA levels.
Motion
Supervisory
Control
User Program
PC
Trajectory
Generator
Interpolation
Position Loop
Velocity Loop
Torque Loop
User-Programmable
FPGA
Real-Time Controller
Motion I/O
Motion Drive
Machine
Vision
Data
Acquisition
Process
Control
Control Design
and Simulation
Filtering and
Signal
Processing
Figure 10.15. The LabVIEW NI SoftMotion Module turns a CompactRIO controller into
aconfigurable custom motion controller.
You can choose from three versions of NI SoftMotion: Lite, Standard, and Premium.
169
Lite
Standard
Premium
Point-to-point motion
Motion I/O
Coordinated motion
Gearing/camming
Customization
Visit the LabVIEW NI SoftMotion Module page on ni.com for more information and for the option to download an
evaluation copy. This evaluation copy contains all the features of LabVIEW NI SoftMotion Premium for the evaluation
period and then defaults to LabVIEW NI SoftMotion Lite until you provide an activation code for Standard or Premium.
Motion controllerThe processing element that runs software algorithms and closed control loops to
generate the motion profile commands based on the move constraints from the user-defined application
software and I/O feedback.
Communication interfaceConverts the command signals from a motion controller to actual digital or analog
values that the drive can interpret.
DriveReceives the digital or analog data from a motion controller after conversion in the communication
interface and converts it to real current/voltage that it applies to the motor to perform the commanded motion.
In many cases, it also has a processing element that closes high-speed control loops. Some advanced drives
can offload the position and velocity control loops from the motion controller and run them on board the drive.
MotorConverts the electrical energy from the drive/amplifier into mechanical energy. The motor torque
constant, kt, and the motor efficiency define the ratio between motor current and mechanical torque output.
Mechanical transmissionConsists of the components connected to the motor that direct the rotary motion
of the motor to do work. This typically involves mechanical devices such as gearboxes or pulleys and lead
screws that convert the rotary motion at the motor shaft to a linear movement at the payload with a certain
transmission gear ratio. Common examples are belts, conveyors, and stages.
Feedback sensorsHelp close the control loops to provide instantaneous position and velocity information to
the drive/amplifier and the motion controller.
Motion I/ORelays information such as limit switches, drive status, and other synchronization information
back to the motion controller through the communication interface.
170
The motion controller component of the system is divided into four components:
Supervisory controlThis top control loop executes command sequencing and passes commands to the
trajectory generation loops. This loop performs the following:
Trajectory generatorThis loop receives commands from the supervisory control loop and generates path
planning based on the profile specified by the user. It provides new location setpoints to the control loop in a
deterministic fashion. As a rule of thumb, this loop should execute with a 5 ms or faster loop rate.
Control loop(s)These are fast control loops that execute every 50 s. They use position and velocity sensor
feedback and the setpoint from the trajectory generator to create the commands to the drive. Because these
loops run faster than the trajectory generator, they also generate intermediate setpoints based on time with a
routine called spline interpolation. For stepper systems, one of the control loops is replaced with a step
generation component.
Feedback devicesThese are sensors such as encoders and limit switches that provide instantaneous
position and velocity information to the drive/amplifier and the motion controller.
171
The LabVIEW NI SoftMotion Module provides these motion controller components implemented in the LabVIEW
Real-Time and LabVIEW FPGA modules as well as an API in LabVIEW and C for creating motion control applications
on top of these core components.
Figure 10.18. Simplified Motion System Diagram Showing Which Components Are
Implemented in the LabVIEW RIO Architecture (in this case, with a CompactRIO controller)
172
NI SoftMotion Architecture
The LabVIEW NI SoftMotion Module contains components that run in LabVIEW for Windows, LabVIEW Real-Time,
and LabVIEW FPGA. It also contains interfaces to a variety of motion specific devices and generic I/O.
Figure 10.19. LabVIEW NI SoftMotion Components and Motion I/O Hardware Options
NI SoftMotion provides an architectural framework and common API that are hardware agnostic; it can be used to
control a variety of different motion hardware configurations. NI SoftMotion is also implemented with open IP in the
LabVIEW Real-Time and LabVIEW FPGA modules, so you can modify specific components as necessary but still use
custom components with the other parts of the NI SoftMotion architecture. Because NI SoftMotion is designed to
be hardware agnostic and open, it provides
Tight integration with other components running in LabVIEW Real-Time or LabVIEW FPGA
Examples of application-specific customization include FPGA triggering and timing based on other C Series I/O in the
system, changing the trajectory generation method, or modifying the control-loop algorithms to implement a
sensorless startup routine.
This section of the guide examines LabVIEW NI SoftMotion Module components and the motion-specific hardware
with which they interface.
173
Figure 10.20. NI SoftMotion Resource Items Available From the LabVIEW Project
An NI SoftMotion axis is a resource that contains the settings and configuration for a specific motion drive, motor, or
feedback device. You use axis resources on the block diagram to specify which resources interact with the
NISoftMotion API. An axis is bound to a specific hardware type to give it the necessary characteristics to configure
and operate with that physical hardware. Axes are bound from the Axis Manager, which you access by right-clicking
on an axis in the LabVIEW project.
Figure 10.21. Access the Axis Manager by right-clicking on an axis in the LabVIEW project.
174
Figure 10.22. Use the NI SoftMotion Axis Manager and Resource Binding Dialog to associate
an axis with a specific type of hardware.
Simulated axisConfigure axes and create and execute motion applications even if you do not have hardware
installed. This is useful for simple prototyping and setup, or for advanced applications as a trajectory master for
electronic gearing and camming operations. However, because you are not connected to actual hardware, you
cannot test control-loop settings or any I/O. The simulated axis, which is available only as a servo axis, features
the following characteristics.
I/O Type
Value
Encoder 0 position
Encoder 0 velocity
Analog input
Sine wave
Steps generated
High or On
FALSE
Digital input
Pulse
Table 10.2. A simulated axis returns simulated data for testing NI SoftMotion
applications without requiring a physical drive and motor in the system.
SolidWorks axisThe SolidWorks axis type provides a connection to a motor defined in the SolidWorks
Motion Analysis add-on. With this axis type, you can synchronize Dassault Systemes SolidWorks assemblies
for motion system simulation. Using NI SoftMotion with SolidWorks to simulate your system with actual
motion profiles, you can design motion profiles; detect collisions; simulate the mechanical dynamics of your
machine including mass and friction effects; estimate machine cycle time performance; validate component
selections for motors, drives, and mechanical transmissions; and evaluate engineering trade-offs between
the mechanical, electrical, control, and embedded system aspects of the design. For more details, see the
Virtual Prototyping Training Series.
175
Figure 10.23. Interface NI SoftMotion with a SolidWorks assembly through the LabVIEW
project to control the model with LabVIEW code.
NI 951x axisUse NI 951x C Series modules directly from LabVIEW Real-Time with the NI Scan Engine, or
use these modules in FPGA mode with the FPGA I/O nodes for the modules.
EtherCAT driveConfigure and use an EtherCAT AKD servo drive completely through NI SoftMotion. You do
not need to use the I/O variables under the EtherCAT device when using the EtherCAT AKD drive with NI
SoftMotion.
Unbound axesCreate custom motion applications in situations where the system requires features or
functionality not available in other motion controllers. This may be a non-supported communication interface,
specialized I/O, or customized control algorithms for precise control. If you use unbound axes with the Axis
Interface nodes, your main application VI can use the same NI SoftMotion APIs for all axis types, which means
that you can have unbound axes and axes bound to other resources in the same application. Unbound axes are
used with most NI 950x C Series drive modules and when implementing motion control with generic C Series
I/O modules.
User-defined variable axesUse user-defined variable (UDV) axes to implement an interface for
communication between the NI SoftMotion Engine and the LabVIEW FPGA Module. UDV axes allow your
main application VI to use the same NI SoftMotion API for all axis types, which means that you can have UDV
axes and axes bound to other resources in the same application. The UDV communication module handles
communication between the NI SoftMotion Engine and the LabVIEW FPGA VI using user-defined variables that
you add to the project. NI SoftMotion supports the following UDV axis types:
176
Generic user-defined variable axisWorks with UDV axes not associated with a currently supported
C Series module. When you use a generic UDV axis, the axis configuration dialog box contains all
available configuration options.
NI 9501 user-defined variable axisWorks with UDV axes associated with an NI 9501 C Series
stepper drive module. When you use an NI 9501 UDV axis, the axis configuration dialog box contains
configuration options customized for the NI 9501 properties.
As the above list attests, the axis is an abstraction that you can use to bind various types of hardware to it. The
benefit to this is the ability to combine dissimilar axis types in the same VI using a consistent high-level programming
API. You can prototype a program using a simulated axis and then deploy it to a real-time system, change the axis
binding to the real hardware, and run the code on the real-time system without changing anything about the way the
high-level code is written.
Right-click on each axis to bind that axis to a specific physical interface or drive in the system, and to configure the
settings and properties for that axis.
Figure 10.24. Right-click on an axis in the LabVIEW project to bind it to a physical resource,
change its properties, or test the settings with the interactive test panel.
177
Figure 10.25. The items and settings on the Axis Configuration panel change depending on the
axis type.
You can use the Interactive Test Panel to test and debug your motion system. With the Interactive Test Panel, you can
perform a simple straight line move and monitor move and I/O status information, change move constraints, obtain
information about errors and faults in the system, and view the position or velocity plots of the move. If you have a
feedback device connected to your system, you can also obtain feedback position and position error information.
Figure 10.26. Perform test moves, check limit switch settings, enable/disable drives, and see
any errors from the Interactive Test Panel.
178
To open the interactive window, right-click the axis in the LabVIEW Project Explorer window and select Interactive
Test Panel. Set the desired position, move mode, and move constraints using the tabs. Click the Start button on the
bottom of the dialog box to start the move with the configured options. Use the Status and Plots tabs to monitor the
move while it is in progress.
Once you configure an axis, you use it on the LabVIEW block diagram as a reference to tell the NI SoftMotion API
which axis to use when executing functions. You can drag and drop axes from the project to the block diagram or
place them from the NI SoftMotion palette.
Figure 10.27. You can drag an Axis resource from the LabVIEW project to the block diagram or
drop it from the palette and associate it with an item in the LabVIEW project.
When you install LabVIEW NI SoftMotion, you get a palette of motion VIs that includes two APIs: the Property/Invoke
node API and the Express VI API.
179
Figure 10.30. Axis 2 is geared to Axis 1 with a 1:2 gear ratio for the two straight line moves
shown.
The Express VI API contains Express configuration dialogs with visualizations that help you quickly put together an
application. Double-clicking on an Express VI opens up the properties dialog where you can configure the Express VI
node, see the visualizations, and set parameter values.
Figure 10.31. Use the Straight Line Move Express VI Properties Page to configure settings,
change values, and see the resulting profiles.
180
Palette
Object
Palette
Symbol
Line
Arc
Performs a straight-line move using an axis or coordinate resource. A straight-line move connects two
points using one or more axes. The behavior of the move changes based on the Straight-Line Move Mode.
Performs a circular, spherical, or helical arc move. An arc move produces motion in a circular shape using a
radius you specify. The type of arc to perform changes based on the Arc Move Mode.
Performs a contour move using an axis or coordinate resource. A contour move is a move expressed as a
series of positions that the software uses to extrapolate a smooth curve. These positions are stored in a
table. Each point in the move is interpreted as an absolute position using the starting point of the move as a
temporary zero position. The type of contour move changes based on the Contour Mode.
Performs a reference move, such as locating a home or limit position, on an axis resource. Reference
moves are used to initialize the motion system and establish a repeatable reference position. The behavior
of the move changes based on the Reference Move Mode.
Records encoder position based on an external input, such as the state of a sensor. You can use the
captured position to execute a move relative to a captured position, or simply record the encoder position
when the capture event occurs.
Synchronizes the motor with external activities and specified encoder positions. When the specified
position is reached, a user-configurable pulse is executed. The behavior of the position compare operation
changes based on the Compare Mode.
Contour
Reference
Capture
Compare
Gearing
Camming
Read
Write
Reset
Position
Description
Configures the specified axis for gearing operations. Gearing synchronizes the movement of a slave axis
to the movement of a master device, which can be an encoder or the trajectory of another axis. The
movement of the slave axes may be at a higher or lower gear ratio than the master. For example, every turn
of the master axis may cause a slave axis to turn twice. The type of gearing operation to perform changes
based on the Gearing Mode.
Configures the specified axis for camming operations. These ratios are handled automatically by LabVIEW
NISoftMotion, allowing precise switching of the gear ratios. Camming is used in applications where the
slave axis follows a nonlinear profile from a master device. The type of camming operation changes based
on the Camming Mode.
Reads status and data information from axes, coordinates, feedback, and other resources. Use the read
methods to obtain information from different resources.
Writes data information to axes, coordinates, or feedback resources. Use the write methods to write
information to different resources.
Stops the current motion on an axis or coordinate. The behavior of the move changes based on the Stop Mode.
Stop
Enables and disables axes and/or drives on the specified axes or coordinate resources.
Power
Clear Faults
You can configure NI SoftMotion Express VIs for either synchronous or asynchronous operation by right-clicking and
selecting Timing Model from the menu.
181
Figure 10.32. Select the timing model for each Express VI by right-clicking and selecting Timing
Model.
When configured for synchronous operation, Express VIs wait until the node finishes executing before returning, and
you can use standard LabVIEW programming methods (dataflow).
When configured for asynchronous operation, the Express VIs return immediately, and you must control execution by
using the status parameters provided: execute, error out, done, aborted, busy, and active.
These two programming methods are very different, as illustrated from the two versions of a simple straight line
move example shown in figures 10.33 and 10.34.
Figure 10.33. Straight Line Move Example Using Synchronous Express VIs
182
Figure 10.34. Straight Line Move Example Using Asynchronous Express VIs
You can convert Express VIs to subVIs that uses the Property/Invoke node API by right-clicking on the Express VI and
selecting Convert ToSubVI.
183
Figure 10.36. Resulting Block Diagram After Converting the Straight Line Move Express VI
to a SubVI
See examples of using both the Express VI and Property/Invoke node APIs in the NI Example Finder.
The Property/Invoke node API provides functionality similar to the Express VI API but with a more granular level of
control over how NI SoftMotion processes and executes commands. In addition to the axis resource, the Property/
Invoke node API uses the concept of a motion resource, which creates a reference to specific NI SoftMotion
interface objects.
Figure 10.37. The NI SoftMotion Property/Invoke node API uses motion resources as well as
axis resources.
With this property node, you can configure all of the same properties and settings available from the Express VI
configuration dialog. But where the Express VI execution is determined by dataflow in the synchronous case and by the
done terminal in the asynchronous case, the Property/Invoke node API execution is controlled through the Invoke node.
184
You can also use the Property/Invoke node API to programmatically configure settings for all axes in the
LabVIEWproject.
185
Figure 10.40. All the same settings that you can configure through the axis in the LabVIEW
project can also be configured programmatically through the Property/Invoke node API.
Which API to use is largely determined by your application architecture. Use the Property/Invoke node API when you
need tight synchronization with the rest of your application or when you use a state machine architecture. In all other
cases, use the NI SoftMotion Express VI API, which is lean and efficient.
You can program VIs written using these motion APIs and deploy them to the Windows machine, or you can run
them in LabVIEW Real-Time on a CompactRIO controller. If you deploy and run the VIs on a Windows system while
using resources deployed to a CompactRIO controller, then use Web Service APIs to act on those resources
remotely. Typically, it is best to deploy the code to LabVIEW Real-Time and then implement a communications
protocol back to a high-level API to execute certain move sequences and interact with the application.
186
When you open a VI targeted to the CompactRIO FPGA, you can see an NI SoftMotion palette that includes the
following motor control IP:
PID/PI
PWM
FOC
I2T
Motion I/O
Feedback
Filters
Stepper
Use this IP to build all the necessary components to control a motion axis. There are two basic elements to
controlling a torque amplifier: control and feedback. The control loop provides a current setpoint and the feedback
loop provides an encoder position.
187
Figure 10.42. Spline Interpolation and PID Loop Executed in LabVIEW FPGA With
NISoftMotion IP
To control the NI 9505 brushed DC motor drive module, you also need current control and PWM control of H-bridges.
188
To control a brushless servo drive, you need to use two new elements: field oriented control and Hall effect sensors.
This additional complexity is necessary because a brushless motor is electrically commutated by the drive instead of
mechanically commutated due to the inherent construction of the motor.
189
Figure 10.46. Field Oriented Control (FOC) Algorithm Implemented in LabVIEW FPGA
Figure 10.47. Three PWM Generators, One for Each Motor Phase
Use Hall effect sensor inputs to determine the angle of the motor shaft, and use the angle upon startup to eliminate
a jump in rotor position.
190
191
Consider an example application for which you need to trigger gripper action based on multiple conditions:
Figure 10.52. You can read position from the quadrature decoder loop.
You can determine the force of the gripper from the sampled quad current in the FOC algorithm every 1.4 s.
192
You can then define this information in a user-defined trigger running in a single-cycle Timed Loop on the FPGA and
executing as fast as every 25 ns.
NI SoftMotion has IP for triggering, including position compare, position capture, and periodic position compare
functionality. These functions are full featured with enable/disable, pulse width, periodic trigger, digital filter, and trigger
window capabilities. They are single-cycle Timed Loop compatible and open so that you can modify them if needed.
193
Figure 10.55. Any CompactRIO controller with two Ethernet ports can act as an EtherCAT
master to control multiple daisy-chained AKD drives from the second Ethernet port.
All NI real-time targets with two Ethernet ports and supported by the NI-Industrial Communications for EtherCAT
driver are configurable as NI EtherCAT masters. This includes PXI controllers, NI industrial controllers, the NI 9792
programmable wireless sensor network gateway, and CompactRIO controllers.
You can add coordinated high-performance multiaxis servo control to any system based on these NI real-time
controllers. Which controller to select depends on the number of axes in the system (amount of data being
processed each scan cycle on the EtherCAT bus) and on your desired control-loop rate. The higher the axis count, the
more data that must be processed within a scan cycle. The faster the control-loop rate, the less time the controller
has to complete that processing. These amount of data on the bus and control-loop rate determine the practical limit
on the number of slave devices allowed in a particular system.
194
(TCP/IP)
EtherCAT Master
NI AKD EtherCAT
Servo Drive
NI 9144
EtherCAT Slave
(EtherCAT)
Figure 10.56. CompactRIO acts as the EtherCAT master. You can add multiple NI 9144 and
EtherCAT AKD slaves to extend this system up to the practical limit imposed by the processing
power of the EtherCAT master.
When added to the system, EtherCAT drives show up under the EtherCAT master in the system. Then you can bind
them to an axis.
Figure 10.57. EtherCAT devices show up under the EtherCAT master adapter (second Ethernet
port of the CompactRIO system). You can bind EtherCAT AKD drives to an NI SoftMotion axis
as shown.
Once bound to an axis, NI SoftMotion takes care of all drive communication over EtherCAT, and you can use that axis
with the high-level motion APIs. This is because NI SoftMotion includes a specific drive interface and LabVIEW
project integration for the AKD drive. This drive interface abstracts all the EtherCAT programming and variables; just
use the axis bound to the AKD with the high-level NI SoftMotion API.
195
Figure 10.58. AKD EtherCAT Drives can be bound to an axis, and then directly used with the
NISoftMotion API
NI SoftMotion runs on the NI EtherCAT master (CompactRIO), generates trajectory information (setpoints), and
sends them to the EtherCAT AKD slave drive, which runs the position, velocity, and torque control loops. You can
configure the AKD drive for position mode, velocity mode, or torque mode. In the standard use case, the AKD is
configured for position mode when operating with NI SoftMotion over EtherCAT.
PC
Real-Time
(EtherCAT)
Motion Drive
Motor
Figure 10.59. In the most common configuration, NI SoftMotion sends trajectory information
(position commands) to the AKD, which then closes the control loops.
Benefits of building a motion system with CompactRIO and EtherCAT AKD drives:
Fault code can be read from the AKD drive across the network
Disadvantages:
196
See the video NI SoftMotion and AKD EtherCAT Brushless Servo Drives for a demonstration of the AKD
setupexperience.
Read the case study Master Machinery Builds Semiconductor Pick and Place Machine With CompactRIO and
LabVIEW for an industry example of this configuration.
NI 9512 single-axis stepper or position command (P-command) drive interface with incremental
encoderfeedback
NI 9516 single-axis servo drive interface with dual incremental encoder feedback
NI951x modules were designed to simplify wiring by providing the flexibility to hook up all the I/O for motion control
to a single module. To further ease connectivity, the digital I/O is software configurable to connect to either sinking or
sourcing devices. The modules offer the following:
Digital input signals for home, limits, and general digital I/O; all software configurable as sinking or
sourcing (24 V)
197
Digital input and digital output for high-speed position capture/compare functions (5 V)
LEDs to provide quick debugging for encoder states, limit status, and axis faults
To further simplify wiring, NIoffers several options for connecting NI951x drive interface modules to external
stepper drives or servo amplifiers including the following:
NI951x Cable and Terminal Block BundleConnects an NI951x module with 37-pin spring or screw
terminal blocks
D-SUB to pigtails cable and MDR to pigtails cableSimplify custom cable creation
Figure 10.61. Directly connect cables between an NI 951x module and the analog AKD
servodrive.
NI C Series drive interface modules are supported in NI Scan Mode and in FPGA mode. In NI Scan Mode, you do not
need LabVIEW FPGA to configure and run the module. This configuration is the easiest to set up and use, and it
provides all the necessary functionality for standard use cases. If you need to add custom triggering and timing with
other C Series I/O or modify the control, then use the modules in FPGA mode.
By default in LabVIEW 2013 and earlier, you can use only NI 951x modules in the first four slots in a CompactRIO
chassis because these are the only slots compiled with the high-speed interface (HSI). See the KnowledgeBase
article How Do I Use the NI 951x Motion Control Modules in Slots 5-8 (Non High Speed Interface Slots) of My
CompactRIO Chassis? for instructions on compiling the entire chassis with HSI support. Some older CompactRIO
chassis such as the NI cRIO-9072, NI cRIO-9073, and NI cRIO-9074 have FPGAs that are not big enough to support
HSI for all slots.
The NI 9512 drive interface module can control stepper drives that accept step and direction signals as well as
control brushless servo drives that accept P-commands. Thus, you can use this module to interface to brushless
servo axes as well as take advantage of the tuning features of those servo drives.
When a servo drive is connected to an NI 9514 or an NI 9516, it is configured in torque mode, which means position
and velocity loop moved from the drive and executed in the NI 951x module. Torque loop always runs in the drive.
198
Quad
Encoder
Limits
DIO
Triggering
PC
Real-Time
Scan Mode
951x Module
Step/Dir
Motion Drive
Motor
10 V Analog
Figure 10.62. Using NI 951x modules in NI Scan Mode, spline interpolation, position, and
velocity loopsareexecuted on the module. Using NI 951x modules in FPGA mode, these loops
are executed inLabVIEWFPGA in the backplane FPGA.
Figure 10.63. All that you need to run this system is an external power supply. An NI 9502 and
NI 9411 are connected to the AKM brushless servo motor (left). An NI 9503 is connected to the
stepper motor (center), and an NI 9505 is connected to the brushed DC motor (right). You can
control all three motor types and organize them in different combinations from the same
CompactRIO chassis.
All drive firmware for these modules is implemented on the backplane FPGA using NI SoftMotion motor control IP
blocks. These modules open up the ability to customize pretty much anything in an application because you implement
all the control, including the torque loop, in LabVIEW FPGA. This means these drives require substantial FPGA
resources and LabVIEW Real-Time/LabVIEW FPGA knowledge. Because all the control is open, the NI 950x drive
modules provide a configurable off-the-shelf alternative to custom drive development. They save on cabling costs, so
you can implement a configurable motion drive with a user-defined axis mix and I/O in a compact form factor.
199
Figure 10.64. NI 9503 (Stepper), NI 9502 (Brushless Servo), and NI 9505 (Brushed DC)
DriveModules
Because these drives are implemented in the CompactRIO C Series form factor, power dissipation is limited to 1.5
W. This spec is important because it says you have no limits on the other modules you can use in the CompactRIO
chassis next to these drive modules. For instance, there are no thermal issues putting a high-accuracy 24-bit analog
input module next to an NI 950x motion drive. However, this limits the power output of these drives, so they can
control only small to mid-size motors. When selecting a platform, make sure that the drive modules can provide
enough power with your selected motor to give you the torque you need in your application.
Figure 10.65. Connect motors directly to a CompactRIO system with NI 950x Drive Modules
200
Quad
Encoder
Limits
DIO
Triggering
C Series I/O
PC
Real-Time
Scan Mode
950x Module
Motor
Figure 10.66. In the NI 950x drive module architecture, all control is implemented in
NISoftMotion onLabVIEWFPGA.
When using NI 950x drive modules, components that are typically executed on external drive firmware are pulled in
from the drive and implemented in LabVIEW FPGA on the CompactRIO backplane instead. The NI SoftMotion
shipping examples provide working starting points for NI 950x modules, and can be used with little modification to
the motion IP and control loops for many motion applications.
201
Example Configurations
The following are some common/interesting ways to configure a CompactRIO motion system. They illustrate the
flexibility and possibilities in assembling a configurable off-the-shelf system to meet a variety of application needs.
Figure 10.67. When using Ethernet RIO chassis and NI 951x drive interface modules, no
software is needed beyond LabVIEW with the LabVIEW NI SoftMotion Module installed on the
development machine.
When you run a high-level VI containing an application built with the NI SoftMotion API on the development PC,
NISoftMotion uses web services to deploy the necessary code to the Ethernet RIO chassis, where it runs all the
necessary supervisory and trajectory tasks locally to maintain the determinism and performance needed for motion
control applications.
Figure 10.68. This 4-axis stepper motion controller was built using the NI 9076 Ethernet RIO
chassis andfour NI 9512 drive interface modules.
Axes within the chassis are coordinated. Axes across multiple Ethernet RIO chassis on the same Ethernet network
are not coordinated.
202
Figure 10.69. You can use the Ethernet RIO chassis to add a modular motion control unit to
anyapplicationover an Ethernet network. This example shows an integrated vision and motion
system foraninspection and positioning application.
In Figure 10.69, the NI 950x drive modules are used in the Ethernet chassis to create an embedded motion drive.
This configuration requires the correct LabVIEW FPGA code to be running on the backplane to implement the drive
firmware for these modules. However, once you develop the bitfile, you do not need LabVIEW FPGA to run or
interact with the Ethernet RIO motion controller except to change the functionality of the drive firmware
implemented in LabVIEW FPGA.
EtherCAT-Based System
The EtherCAT-based system can include EtherCAT AKD drives and any motion C Series module in the NI 9144
EtherCAT slave chassis. Any CompactRIO controller with two Ethernet ports can act as the EtherCAT master.
Because of the determinism of EtherCAT, you can synchronize motion axes across multiple chassis at the scan rate
of the EtherCAT master. EtherCAT provides for high-axis-count and mixed-axis systems. The axis count is limited only
by the processing power of the EtherCAT master and the desired scan rate. Its fairly common to have more than a
dozen axes in an EtherCAT system with an appropriate CompactRIO controller (NI cRIO-9024/9025/9068/9081/9082)
as the EtherCAT master.
203
Figure 10.70. System Setup Used on the NI 3D Gears Demonstration System (The NI cRIO-9068
is controlling eight AKD servo drives over EtherCAT, two USB cameras, anda variety of I/O from
the C Series slots including two stepper drives, four electromagnets, and a custom digital
protocol controlling 96 RGB LEDs with a custom FPGA-based digital protocol.
In the Figure 10.70 setup, if there were insufficient slots in the CompactRIO chassis and more motion axes or I/O
channels were required, you can add an NI 9144 chassis with the right mix of NI 951x drive interfaces, NI 950x
drives, and C Series I/O modules.
Mixed-Axis Systems
Figure 10.70 features mixed-axis systems. With NI SoftMotion, you can synchronize axes of different types as long
as they all use the same motion controller. For example, using an NI 9024 EtherCAT master, you could perform
synchronized moves using NI 9512 stepper axes, NI 9514 servo axes, EtherCAT AKD axes, NI 9502 servo axes, or
any other axis type. Axes in NI SoftMotion, though often bound to a particular hardware type, are not associated with
hardware when using the high-level NI SoftMotion API. A straight line move is the same on an AKD axis as it is on an
NI 9512 axis. It is only when the straight line move command gets to the communication interface that it is
transformed into the signals that are expected by the hardware.
204
NI offers a full suite of stepper products including integrated motors, DC and AC stepper drives, and NEMA 834
frame-sized stepper motors with integrated encoder options.
These industry-leading drives and motors are fully compatible with NI controllers and drive interfaces.
Controllers (number of axes, processing power, I/O count and synchronization, communication strategy)
Motor and drive (comparison of motor types, power ranges, typical application uses)
Start by selecting the right mechanical components and motors for your system. One of the most common
applications involves moving an object from one position to another. A typical way to change the rotary motion of a
rotary motor to a useful linear motion is by connecting the motor to a stage and using a leadscrew mechanism to
move the payload. Stages are mechanical devices that provide linear or rotary motion useful in positioning and
moving objects. They come in a variety of types and sizes, so you can use them in many different applications. To
find the correct stage for your application, you need to be familiar with some of the common terminology used when
describing stages. Some of the key items to consider when selecting a stage include the following:
Transmission gear ratioDetermines the linear travel distance of the stage per rotary revolution
ofthemotor.
AccuracyHow closely the length of a commanded move compares to a standard length.
ResolutionThe smallest length of travel that a system is capable of implementing can be as small as
afewnanometers.
205
Travel distanceThe maximum length the system is capable of moving in one direction.
RepeatabilityThe repeated motion to a commanded position under the same conditions. Often this is
specified in unidirectional repeatability, which is the ability to return to the same point from one direction, and
bidirectional repeatability, which specifies the ability to return from either direction.
Maximum loadThe maximum weight the stage is physically designed to carry, given accuracy
andrepeatability.
Stage Selection
You can choose from a variety of stages to meet your application needs. You can narrow down these stages to two
main typeslinear and rotary. Linear stages move in a straight line and are often stacked on each other to provide
travel in multiple directions. A three-axis system with an x, y, and z component is a common setup used to position
an object anywhere in a 3D space. A rotary stage is a stage that rotates about an axis (usually at the center). Linear
stages are used to position an object in space, but rotary stages are used to orient objects in space and adjust the
roll, pitch, and yaw of an object. Many applications, such as high-precision alignment, require both position and
orientation to perform accurate alignment. The resolution for a rotary stage is often measured in degrees or arc
minutes (1 degree equals 60 arc minutes). Special types of stages include the goniometer, which looks like a linear
stage that moves in an arc rather than a straight line, or a hexapod, which is a parallel mechanism that gives you
movement in six axes to controlx, y, z, roll, pitch, and yaw. With a hexapod, you can define a virtual point in space
about which the stage can rotate. While that is a benefit, the disadvantage is that hexapods are parallel and the
kinematics involved are much more complex than those for simple stacked stages.
Backlash
Another stage attribute to consider when choosing a stage for your precision motion system is backlash. Backlash is
the lag created when one gear in a system changes direction and moves a small distance before making contact with
a companion gear. It can lead to significant inaccuracies especially in systems using many gears in the drive train.
When moving on a nanometer scale, even a small amount of backlash can introduce major inaccuracy in the system.
Effective mechanical design minimizes backlash but may not be able to eliminate it completely. You can compensate
for this problem by implementing dual-loop feedback in software. The NI9516 C Series servo drive interface module
supports dual-encoder feedback and accepts feedback from two different sources for a single axis. To understand the
circumstances for which you need to use this feature, consider a stage. If you monitor the stage position directly (as
opposed to the position of the motor driving the stage), you can tell if a move you have commanded has reached the
target location. However, because the motion controller is providing input signals to the motor and not to the stage,
which is the primary source of feedback, the difference in the expected output relative to the input can cause the
system to become unstable. To make the fine adjustments necessary to help the system stay stable, you can monitor
the feedback directly from the encoder on the motor as a secondary feedback source. Using this method, you can
monitor the real position of your stage and account for the inaccuracies in the drive train.
Motor Selection
A motor provides the stage movement. Some high-precision stages and mechanical components feature a built-in
motor to minimize backlash and increase repeatability, but most stages and components use a mechanical coupling
to connect to a standard rotary motor. To make connectivity easier, the National Electrical Manufacturers Association
(NEMA) has standardized motor dimensions. For fractional horsepower motors, the frame sizes have a two-digit
designation such as NEMA 17 or NEMA 23. For these motors, the frame size designates a particular shaft height,
shaft diameter, and mounting hole pattern. Frame designations are not based on torque and speed, so you have a
range of torque and speed combinations in one frame size.
206
The proper motor must be paired with the mechanical system to provide the performance required. You can choose
from the following four main motor technologies:
Stepper motorA stepper motor is less expensive than a servo motor of a similar size and is typically easier
to use. These devices are called stepper motors because they move in discrete steps. Controlling a stepper
motor requires a stepper drive, which receives step and direction signals from the controller. You can run
stepper motors, which are effective for low-cost applications, in an open-loop configuration (no encoder
feedback). In general, a stepper motor has high torque at low speeds and good holding torque but low torque
at high speeds and a lower maximum speed. Movement at low speeds can also be choppy, but most stepper
drives feature a microstepping capability to minimize this problem.
Brushed servo motorThis is a simple motor on which electrical contacts pass power to the armature
through a mechanical rotary switch called a commutator. These motors provide a 2-wire connection and are
controlled by varying the current to the motor, often through PWM control. The motor drive converts a control
signal, normally a 10 V analog command signal, to a current output to the motor and may require tuning.
These motors are fairly easy to control and provide good torque across their ranges. However, they do require
periodic brush maintenance, and, compared to brushless servo motors, they have a limited speed range and
offer less efficiency due to the mechanical limitations of the brushes.
Brushless servo motorThese motors use a permanent magnet rotor, three phases of driving coils, and Hall
effect sensors to determine the position of the rotor. A specialized drive converts the 10 V analog signal from
the controller into three-phase power for the motor. The drive contains intelligence to perform electronic
commutation and requires tuning. These efficient motors deliver high torque and speed and require less
maintenance. However, they are more complex to set up and tune, and the motor and drive are more expensive.
Stage Drive
Technology
Stepper
Brushed Servo
Brushless Servo
Speed
Maximum
Load
Travel Distance
Repeatability
Relative
Complexity
Relative Cost
Medium/Low
Medium/Low
High
Medium/Low
Low
Low
High
High
High
Medium
Medium
Low
Very High
High
High
High
High/Medium
High
Because the motor and drive are so closely coupled, you should use a motor and drive combination from one vendor.
Though this is not a requirement, it makes tuning and selection easier.
207
CHAPTER 11
Deploying and Replicating Systems
Application Deployment
All LabVIEW development for real-time targets and touch panel targets is done on a Windows PC. To run the code
embedded on the targets, you need to deploy the applications. Real-time controllers and touch panels, much like a
PC, have both volatile memory (RAM) and nonvolatile memory (hard drive). When you deploy your code, you have
the option to deploy to either the volatile memory or nonvolatile memory on a target.
Deploy to Volatile Memory
If you deploy the application to the volatile memory on a target, the application does not remain on the target after
you cycle power. This is useful when iteratively developing your application and testing your code.
Deploy to Nonvolatile Memory
If you deploy the application to the nonvolatile memory on a target, the application remains after you cycle the power
on the target. You can set applications stored on nonvolatile memory to start up automatically when the real-time
target boots. This is useful when you have finished development and want to create a stand-alone embedded system.
LabVIEW verifies that the VI and all subVIs are saved, deploys the code to the nonvolatile memory on the
CompactRIO controller, and starts embedded execution of the code. Use the ability to deploy to volatile memory to
quickly iterate through application development.
208
After selecting Real-Time Application, you see a dialog box featuring two main categories that are most commonly
used when building a real-time application: Information and Source Files.
The Information category contains the build specification name, executable filename, and destination directory for both
the real-time target and host PC. You can change the build specification name and local destination directory to match your
nomenclature and file organization. You normally do not need to change the target filename or target destination directory.
209
The Source Files category is used to set the startup VIs and include additional VIs or support files. You need to select
the top-level VI from your Project Files and set it as a Startup VI. For most applications, a single VI is chosen to be a
Startup VI. You do not need to include lvlib or set subVIs as Startup VIs or Always Included unless they are called
dynamically in your application.
210
Figure 11.4. Source Files Category in the Real-Time Application Properties (In this example,
the cRIOEmbeddedDataLogger (Host).vi was selected to be a Startup VI.)
After all of the options have been entered on the required category tabs, you can click OK to save the build
specification or you can directly build the application by clicking the Build button. You can also right-click on a saved
build specification and select Build to build the application.
When you build the application, an executable is created and saved on the hard drive of your development machine
in the local destination directory.
Setting an Executable Real-Time Application to Run On Startup
After an application has been built, you can set the executable to automatically start up as soon as the controller
boots. To set an executable application to start up, you should right-click the Real-Time Application option (under
Build Specifications) and select Set as startup. When you deploy the executable to the real-time controller, the
controller is also configured to run the application automatically when you power on or reboot the real-time target.
You can select Unset as Startup to disable automatic startup.
211
212
213
One caveat to relying solely on the Open FPGA VI Reference function to download and run the FPGA application is
that the host application must first initialize before the FPGA application can be loaded. This causes a delay from
device power up to the configuration and operation of the FPGA. On device power, the input and output lines on the
FPGA are in an indeterminate state until the host application loads and executes the Open FPGA VI Reference
function. The delay in loading and executing the host application can easily be on the order of a minute, posing a
potential safety and reliability risk as the FPGA I/O states remain uncontrolled. Therefore, its recommended that the
FPGA bitfile implements safe states and be stored on the onboard FPGA flash memory.
Method 2: Storing the Application in Nonvolatile Flash Memory on the FPGA Target
In addition to relying solely on the Open FPGA VI Reference, you can download the FPGA bitfile to flash memory on
the target device using the RIO Device Setup that is included with the NI-RIO driver as shown in Figure 11.9. You can
then configure the bitfile downloaded to flash memory to load and run the personality onto the FPGA as well as
load independently of the Open FPGA VI Reference function. To learn more about this download process, reference
the KnowledgeBase article How Do I Download a Bitfile to My Target Without LabVIEW FPGA? You should
download an FPGA bitfile implementing safe states to the flash memory and set it to run on device power up, or
reboot, so that all of the input and output lines are immediately driven to a known state.
214
Figure 11.9. You can download the FPGA bitfile to the FPGAs onboard flash memory
using the RIO Device Setup.
If you have downloaded an FPGA application to flash memory and set it to run on device power or device reboot, you
can still use the Open FPGA VI Reference to communicate between the FPGA and host applications. The Open
FPGA VI Reference simply generates a reference if the FPGA bitfile running on the device matches the FPGA bitfile
stored within the Open FPGA VI Reference node. If, however, the bitfile stored in the Open FPGA VI Reference
function differs from the bitfile running on the FPGA, note that the Run the FPGA VI replaces the bitfile running on
the FPGA with the bitfile contained in the Open FPGA VI Reference function. For more information, refer to the
Open FPGA VI Reference function documentation in the LabVIEW Help.
Figure 11.10. The Run the FPGA VI option in the Open FPGA VI Reference configuration window
toggles whether the Open FPGA VI Reference function overwrites the bitfile loaded to the FPGA
in cases where the bitfile running on the FPGA doesnt match the bitfile embedded in the Open
FPGA VI Reference function.
It is generally recommended that you embed the same FPGA personality referenced in the host application into
flash memory. This is to enable greater safety and reliability by having the I/O state immediately controlled on device
215
power or reboot. For more information on managing FPGA deployments, see the NIDeveloper Zone document
Managing FPGA Deployments.
Beginning in LabVIEW 2013, the System Configuration API, Measurement & Automation Explorer (MAX), and the
Web-Based Configuration and Monitoring interface all provide support for managing FPGA bitfiles for targets that
run NI Linux Real-Time, such as the NI cRIO-9068.
Figure 11.11. In LabVIEW 2013, FPGA flash deployment on NI Linux Real-Time targets is supported through the System Configuration API, MAX,
and the Web-Based Configuration and Monitoring interface.
216
2. You can programmatically deploy the library from a LabVIEW application running on Windows using the Application
Invoke Node.
Use the Path input of the Deploy Library Invoke Node to point to the library(s) containing your shared
variables. Also specify the IP address of the real-time target using the Target IP Address input.
217
To provide scalability, this information is not hard-coded into the executable. Instead, this information is stored in a
file on the target called an alias file. An alias file is a human-readable file that lists the logical name of a target
(CompactRIO) and the IP address for the target (10.0.62.67). When the executable runs, it reads the alias file and
replaces the logical name with the IP address. If you later change the IP addresses of deployed systems, you need
to edit only the alias file to relink the two devices. For real-time and Windows XP Embedded targets, the build
specification for each system deployment automatically downloads the alias file. For Windows CE targets, you need
to configure the build specification to download the alias file.
If you are deploying systems with dynamic IP addresses using DHCP, you can use the domain name system (DNS) name
instead of the IP address. In the LabVIEW project, you can type the DNS name instead of the IP address in the
properties page of the target.
Figure 11.16. For systems using DHCP, you can enter the DNS name instead of the IP address.
218
One good approach if you need scalability is to develop using a generic target machine (you can develop for remote
machines that do not exist) with a name indicating its purpose in the application. Then as part of the installer, you can
run an executable that either prompts the user for the IP addresses for the remote machine and My Computer or pulls
them from another source such as a database. Then the executable can modify the aliases file to reflect these changes.
Recommended software sets guarantee that an application has the same set of underlying drivers for every real-time
system that has the same software set. In general, there is a minimal and full software set.
219
Imaging
An image in the context of NI embedded hardware and software is a single file which can contain, at a maximum, a
copy of all of the files on an embedded targets disk. Given that the RTEXE, system drivers, network settings, shared
variables, scan engine settings, web services, and any application configurations or plug-ins are all stored as files on
disk for an embedded system, Imaging is an effective way to create a backup of a system and to replicate a given
embedded system.
In order to leverage imaging, a fully configured embedded system is required. Often, this means relying on LabVIEW
Project based deployment to properly deploy to the first embedded system, after which imaging can be used to setup
additional systems. Given that Imaging relies on copying all the files on a properly configured embedded target, there
are a few key caveats to be aware of.
The most significant caveat is that imaging can only be used to deploy/replicate to other embedded targets that are of
the same model. For example, if a cRIO 9074 is used to get an image, when applying the image to setup subsequent
systems, only cRIO 9074s can be used. The image from a cRIO 9074 cannot be applied to a different model cRIO, such
an NI 9024. Beyond being restricted to the same model, imaging doesnt copy the FPGA flash settings between
controllers as it only copies the disk that belongs to the real-time operating system on the embedded device. When
applying an image, users need to take precautions to configure the imaging settings properly to preserve existing
configuration or log files on the embedded target, as there is a risk overwriting existing files on the target.
Imaging is recommended when deploying to multiple targets, and is especially recommended when initially setting up
large numbers of embedded targets for field deployment. Imaging is also recommended for creating restore points or
backups for embedded applications. To begin using imaging to manage large numbers of embedded deployments,
please refer to the following Systems Engineering utility: Replication and Deployment (RAD) Utility. The RAD utility
makes use of the System Configuration API which can be used to create and deploy images. Its recommended to use
the source code provided for the RAD as a starting point when attempting to create a custom imaging utility as
opposed to starting from a blank VI.
Figure 11.18. By relying on the System Configuration API and the imaging tools it provides, you
can deploy images to multiple real-time targets.
220
Starting in LabVIEW 2013, system deployment with system images has been improved greatly on NI Linux RealTime targets such as the cRIO-9068. These targets have the ability to run the Set Image function from the System
Configuration API directly, allowing for intelligent self-updating. Targets can be programmed to pull system images
down from a network or locally attached storage and allow you to more securely manage larger scale deployments.
Application Components
Application components, unlike images, only encapsulate the real-time application (RTEXE) and associated driver
dependencies. To better understand application components, its useful to first cover driver components. When going
through the Add/Remove Software dialog for a real-time target such as a CompactRIO, the list of options that appear
both under the Recommended Software Set and the Custom Software Installation are known as components.
Example components for the CompactRIO are System State Publisher, Network Variable Engine, and NI-RIO I/O Scan.
Application components are similar to the driver components, but encapsulate the RTEXE, and can have driver
components listed as dependencies.
Since application components only encapsulate the RTEXE and do not contain other configuration information about
the embedded target, they are not a reliable way to define a backup or restore point for an embedded target. However,
this same characteristic allows for them to install across any real-time target, much like driver components. Key
benefits of application components are that they can be installed to other targets, and deploy much more quickly than
images. For example, a real-time application developed on a cRIO 9074 can be built into an application component and
deployed to an NI 9024. Application components can also be built directly from the LabVIEW Project, and unlike
images, do not require an initial deployment and retrieval. To learn more about configuring and using application
components, please refer to: Using Application Components to Deploy LabVIEW Real-Time Applications.
221
Figure 11.19. With the NI Replication and Deployment Utility, you can
quickly and easily deploy images to multiple real-time targets.
The Real-Time Targets table shows all of the targets on the local subnet as well as any network targets manually
added to the list. You can use these targets for both image retrieval and image deployment. The Application Images
table shows all of the images that are stored on the local hard drive that can be deployed to target systems.
222
In addition to retrieving and deploying an image on the real-time hard drive, the utility can deploy bitfiles to FPGA
flash memory. Saving a bitfile in flash memory has some advantages over deploying the bitfile from the RTEXE. For
example, the host application is required to initialize before the FPGA application is loaded and, as a result, there is a
delay from device power up to the configuration of the FPGA. In addition, on power up, the state of the input and
output lines of your target is unknown since the FPGA has not yet been configured. Therefore, if the FPGA is
completely independent of the host application, its personality should be stored in the onboard FPGA flash memory.
Using the RTAD utility, you can now save bitfiles with an image during retrieval and then later deploy them to flash
memory when you deploy the image. Click Configure Bitfile(s) for FPGA Flash Deployment to edit your FPGA flash
deployment settings.
223
Click the Start button to begin the comparison process. Once the comparison begins, each file on both images is
compared for changes. Files that are found in one image and not the other are also identified. This process may take
several minutes to complete, and a progress dialog is displayed until completion. If the tool completes with no
differences found, the Figure 11.23 dialog appears.
However, if any differences are identified, they are listed in Table 11.1. You can then log the results to a TSV file.
224
Figure 11.24. Include the USB Deploy Image VI in your deployed real-time application
to enable updates from a USB memory stick.
Once you have added this code, you can build the main application into an executable and deploy it to a CompactRIO
controller. The deployed application executable, together with all of the other files on the CompactRIO controller hard
drive, becomes the application image. For more information on this utility including downloadable files, see the
NIDeveloper Zone document Reference Design for Deploying CompactRIO Application Updates Using a
USB Memory Device.
Another useful API discussed in this section is the CompactRIO Information Library (CRI), which you can use with
the three APIs listed above to return information about the current hardware configuration of a CompactRIO system.
System Configuration API
The System Configuration API exposes MAX features programmatically. For example, you can use this API to
programmatically install software sets, run self-tests, and apply network settings in addition to image retrieval
225
and deployment. This API is located in the Functions palette under Measurement I/OSystem ConfigurationRealTime Software.
RT Utilities API
The RT Utilities API also includes VIs for image retrieval and deployment. It was deprecated in LabVIEW 2011 and is not
recommended for new designs. The functionality it offers has been fully absorbed into the System Configuration API
Figure 11.26.You also can use the RT Utilities VIs in LabVIEW 2009 or later
to programmatically deploy and retrieve a system image.
226
You can download this library from the NIDeveloper Zone document
Reference Library for Reading CompactRIO System Configuration Information.
IP Protection
Intellectual property (IP) in this context refers to any unique software or application algorithm(s) that you have or your
company has independently developed. This can be a specific control algorithm or a full-scale deployed application.
IPnormally takes a lot of time to develop and gives companies a way to differentiate from the competition;
therefore, protecting this software IP is important. LabVIEW development tools and CompactRIO provide the ability
to protect and lock your IP. In general, you can implement two levels of IP protection:
Lock Algorithms or Code to Prevent IP From Being Copied or Modified
If you have created algorithms for a specific function, such as performing advanced control functions, implementing
custom filtering, and so on, you may want to distribute the algorithm as a subVI but prevent someone from viewing
or modifying that actual algorithm. This may be to achieve IP protection or to reduce a support burden by preventing
other parties from modifying and breaking your algorithms.
Lock Code to Specific Hardware to Prevent IP From Being Replicated
Use this method if you want to ensure that a competitor cannot replicate your system by running your code on another
CompactRIO system or if you want your customers to come back to you for service and support.
227
To password protect a VI, go to FileVI Properties. Choose Protection for the category. This gives you three options:
unlocked (the default state of a VI), locked (no password), and password-protected. When you click on password-protected,
a window appears for you to enter your password. The password takes effect the next time you launch LabVIEW.
The LabVIEW password mechanism is quite difficult to defeat, but no password algorithm is 100 percent secure
from attack. If you need total assurance that someone cannot gain access to your source code, you should consider
removing the block diagram.
Method 2: Removing the Block Diagram
To go beyond the protection offered by password protecting a VI and to guarantee that a VI cannot be modified or
opened, you can remove the block diagram completely. Much like an executable, the code you distributed no longer
contains the original editable code. Do not forget to make a backup of your files if you use this technique because
the block diagram cannot be recreated. Removing the block diagram is an option you can select when creating a
source distribution. A source distribution is a collection of files that you can package and send to other developers to
use in LabVIEW. You can configure settings for specified VIs to add passwords, remove block diagrams, or apply
other settings.
Complete the following steps to build a source distribution.
In the LabVIEW project, right-click Build Specifications and select NewSource Distribution from the
shortcut menu to display the Source Distribution Properties dialog box. Add your VI(s) to the distribution.
On the Source File Settings page of the Source Distribution Properties dialog box, remove the checkmark
from the Use default save settings checkbox and place a checkmark in the Remove block diagram checkbox
to ensure that LabVIEW removes the block diagram.
Build the source distribution to create a copy of the VI without its block diagram.
228
Note: If you save VIs without block diagrams, do not overwrite the original versions of the VIs. Save the VIs in
different directories or use different names.
229
You can use the following steps as guidelines to programmatically lock any application to any of the above mentioned
hardware parameters and thus prevent users from replicating application code:
1. Obtain the hardware information for the device. Refer to the following procedures for more guidance on
programmatically obtaining this information.
2. Compare the values obtained to a predetermined set of values that the application code is designed for using
the Equal? function from the Comparison palette.
3. Wire the results of the comparison to the selectorinputof a Case structure.
4. Place the application code in the true case and leave the false case blank.
Performing these steps ensures that the application is not replicated or usable on any other CompactRIO hardware.
License Key
Adding licensing to a LabVIEW Real-Time application can protect a deployed application from being copied and run
on another similar or identical set of hardware without obtaining a license from the vendor or distributor of the
application. Most modern-day applications running on desktop computers are protected by a license key that is
necessary to either install the application or run it in its normal operational mode. Many vendors use license keys to
determine if an application runs in demo mode or is fully functional. License keys may also be used to differentiate
between versions of an application or to enable/disable specific features.
You can add this behavior to a LabVIEW Real-Time application using the reference design and example code
developed by NISystems Engineering. You can download this code from the NIDeveloper Zone document
Reference Design for Adding Licensing to LabVIEW Real-Time Applications. The main modification is how you
create a unique system ID for a specific hardware target. In the case of CompactRIO, you use the controller,
backplane, and module serial numbers. For other targets, you may use the serial number or Ethernet MAC address
of a given target to create a unique system ID.
230
Figure 11.30. Block Diagram Showing the Process of Creating the License Key
Figure 11.31 shows one possible example of generating a system ID for a 4-slotCompactRIOsystem using these
VIs. The serial numbers for all six system components are added together. While this is not a truly unique value for a
given CompactRIO system, it is unlikely that after replacing one or more system components, the sum of all the
serial numbers will be the same as when the license key was generated.
231
The encryption VI provides two versions of the license key. The default algorithm returns a stream of bytes that can
have any value between 0 and 255; therefore, these bytes may not represent printable characters and may not be
easily stored in a text file or passed along using other mechanisms such as email. To simplify the process of storing
and transferring the license key, the VI provides a hexadecimal version of the encrypted string made up of the ASCII
representation of the hexadecimal value of each of the byte values in the original string. This string is stored in a file
as the license key.
Store the License Key on the Hardware Target
The reference example stores the license key in a simple INIfile on theCompactRIOcontroller hard drive.
232
Figure 11.33. Storing the License Key in an INIFile on the CompactRIO Controller
If the license key and file are generated away from the actual CompactRIO system, then you must copy the license
file to the CompactRIO system when you deploy the application to the controller.
Verify the License Key During Application Startup
When the deployed application is starting up, it needs to verify the license key and, based on the results of the
verification process, adjust its behavior according to the license model. If the license key is verified correctly, the
application runs normally, but if the key is not verified, it may not run at all or run in an evaluation mode.
The reference example provides a basic verification VI that is added before the actual application.
You can choose from two different methods to verify a license key. The first and preferred method is to re-create the
license key on the target system (described in this section). The second method, which consists of decrypting the
license key, is described in the NIDeveloper Zone white paper Reference Design for Adding Licensing to
LabVIEW Real-Time Applications under the section titled Enabling Features based on the License Key.
The more basic and more secure method to verify the license key is to run the same algorithm you use to create the
license key on the target system and then compare the new license key with the license key stored in the license
file. If the two match, then the license key is verified and the application may run.
233
Figure 11.35. Block Diagram to Verify the License Key Stored in the File on the System
Figure 11.35 shows that this process is almost identical to the process of generating the license key. Instead of
writing the license file, however, the license file is read and compared to the newly generated license key.
This method of verifying the license key works well if you do not need any partial information from the license key such
as information about enabling or disabling individual features or the individual serial numbers of system components.
For licensing models that require more detailed information about the license key, the key itself must be decrypted.
For more information on this type of licensing, see the NIDeveloper Zone document Reference Design for Adding
Licensing to LabVIEW Real-Time Applications.
Figure 11.36. Connect to a touch panel through Ethernet using the NITPC Service.
You can find the IP address of the touch panel by going to the command prompt on the TPC and typing ipconfig. To get
to the command prompt, go to the Start menu and select Run In the pop-up window, enter cmd.
234
After selecting the Touch Panel Application, you are presented with a dialog box. The two most commonly used
categories when building a touch panel application are Information and Source Files. The other categories are rarely
changed when building touch panel applications.
The Information category contains the build specification name, executable filename, and destination directory for
both the touch panel target and host PC. You can change the build specification name and local destination directory
to match your nomenclature and file organization. You normally do not need to change the target filename or target
destination directory.
235
Figure 11.38. The Information Category in the Touch Panel Application Properties
You use the Source Files category to set the startup VIs and obtain additional VIs or support files. You need to select
the top-level VI from your Project Files and set it as a Startup VI. For most applications, a single VI is chosen to be a
Startup VI. You do not need to include lvlib or set subVIs as Startup VIs or Always Included unless they are called
dynamically in your application.
Figure 11.39. Source Files Category in the Touch Panel Application Properties
(In this example, the HMI_SV.vi was selected to be a Startup VI.)
After you have entered all of the information on the required category tabs, you can click OK to save the build
specification or you can directly build the application by clicking the Build button. You can also right-click on a saved
build specification and select Build to build the application.
236
When you build the application, an executable is created and saved on the hard drive of your development machine
in the local destination directory.
Building an Executable From a VI for a Windows CE Touch Panel
The LabVIEW project provides the ability to build an executable touch panel application from a VI. To build this
application, you create a build specification under the touch panel target in the LabVIEW Project Explorer. By rightclicking on Build Specifications, you can select the option of creating a Touch Panel Application, Source Distribution,
Zip File, and so on.
After selecting Touch Panel Application, you see a dialog box with the three main categories that are most commonly
used when building a touch panel application for a Windows CE target: Application Information, Source Files, and
Machine Aliases. The other categories are rarely changed when building Windows CE touch panel applications.
The Application Information category contains the build specification name, executable filename, and destination
directory for both the touch panel target and host PC. You can change the build specification name and local
destination directory to match your nomenclature and file organization. You normally do not need to change the
target filename. The target destination determines if the deployed executable runs in volatile or nonvolatile memory.
On a Windows CE device
\My Documents folder is volatile memory. If you deploy the executable to this memory location, it does not
persist through power cycles.
\HardDisk is nonvolatile memory. If you want your application to remain on the Windows CE device after a
power cycle, you should set your remote path for target application to a directory on the \HardDisk such as
\HardDisk\Documents and Settings.
237
Figure 11.41. The Information Category in the Touch Panel Application Properties
Use the Source Files category to set the startup VI and obtain additional VIs or support files. You need to select the
top-level VI from your Project File. The top-level VI is the startup VI. For Windows CE touch panel applications, you can
select only a single VI to be the top-level VI. You do not need to include lvlib or subVIs as Always Included.
Figure 11.42. The Source Files Category in the Touch Panel Application Properties
(In this example, the HMI_SV.vi was selected to be the top-level VI.)
The Machine Aliases category is used to deploy an alias file. This is required if you are using network-published
shared variables for communication to any devices. Be sure to check the Deploy alias file checkbox. The alias list
238
should include your network-published shared variable servers and their IP addresses (normally CompactRIO or
Windows PCs). You can find more information on alias files and application deployment using network-published
shared variables in the section titled Deploying Applications That Use Network-Published Shared Variables.
Figure 11.43. The Machine Aliases Category in the Touch Panel Application Properties
(Be sure to check the deploy aliases file checkbox if you are using network-published shared
variables.)
After you have entered all of your information on the required category tabs, you can click OK to save the build
specification or you can directly build the application by clicking the Build button. You can also right-click on a saved
build specification and select Build to build the application.
When you build the application, an executable is created and saved on the hard drive of your development machine
in the local destination directory.
239
PXI/NI FlexRIO
PC RIO/R Series
NI Single-Board RIO
NI CompactRIO
(Value)
NI CompactRIO
(Performance)
Figure 11.44. With LabVIEW, you can use the same architecture for applications ranging from
CompactRIO to high-performance PXI to board-level NISingle-Board RIO.
NISingle-Board RIO
NISingle-Board RIO is a board-only version of CompactRIO designed for applications requiring a bare board form
factor. While it is physically a different design, NISingle-Board RIO uses the processor and FPGA, and most models
240
accept up to three C Series modules. NISingle-Board RIO differs from CompactRIO because it includes I/O built
directly into the board. NIoffers two families of NI-Single-Board RIO products:
Digital I/O With RIO Mezzanine Card Connector
The smallest option for NISingle-Board RIO combines the highest performance real-time processor with a Xilinx
Spartan-6 FPGA and built-in peripherals such as USB, RS232, CAN, and Ethernet. In addition to the peripherals, the
system includes 96 FPGA digital I/O lines that are accessed through the RIO Mezzanine Card (RMC) connector,
which is a high-density, high-bandwidth connector that allows for direct access to the FPGA and processor. With this
type of NISingle-Board RIO, you can create a customized daughter card designed specifically for your application
that accesses the digital I/O lines and processor I/O including CAN and USB. This NISingle-Board RIO family
currently does not support C Series connectivity.
Digital I/O Only or Digital and Analog I/O With Direct C Series Connectivity
NIalso offers NISingle-Board RIO devices with both built-in digital and analog I/O on a single board. All I/O is
connected directly to the FPGA, providing low-level customization of timing and I/O signal processing. These devices
feature 110 3.3 V bidirectional digital I/O lines and up to 32 analog inputs, 4 analog outputs, and 32 24 V digital input
and output lines, depending on the model used. They can directly connect up to three C Series I/O and
communication modules for further I/O expansion and flexibility.
LabVIEW FPGA Programming
Not all NISingle-Board RIO products currently support Scan Mode. Specifically, the NISingle-Board RIO products
with a 1 million gate FPGA (sbRIO-9601, sbRIO-9611, sbRIO-9631, and sbRIO-9641) are not supported, in addition to
the NISingle-Board RIO products with the RMC connector (sbRIO-9605 and sbRIO-9606). Instead of using Scan
Mode to read I/O, you need to write a LabVIEW program to read the I/O from the FPGA and insert it into an I/O
memory table. This section examines an effective FPGA architecture for single-point I/O communication similar to
Scan Mode and shows how to convert an application using Scan Mode.
Built-In I/O and I/O Modules
Depending on your application I/O requirements, you may be able to create your entire application to use only the
NISingle-Board RIO onboard I/O, or you may need to add modules. When possible, design your application to use
the I/O modules available onboard NISingle-Board RIO. The I/O available on NISingle-Board RIO with direct C Series
connectivity and the module equivalents are listed below:
110 general-purpose, 3.3 V (5 V tolerant, TTL compatible) digital I/O (no module equivalent)
32 single-ended/16 differential channels, 16-bit analog input, 250 kS/s aggregate (NI9205)
This NISingle-Board RIO family accepts up to three additional C Series modules. Applications that need more than
three additional I/O modules are not good candidates for NISingle-Board RIO, and you should consider CompactRIO
integrated systems as a deployment target.
FPGA Size
The largest FPGA available on NISingle-Board RIO is the Spartan-6 LX45. CompactRIO targets offer versions using
both the Virtex-5 FPGAs and the Spartan-6 FPGAs as large as the LX150. To test if code fits on hardware you do not
241
own, you can add a target to your LabVIEW project and, as you develop your FPGA application, you can periodically
benchmark the application by compiling the FPGA code for a simulated RIO target. This gives you a good understanding
of how much of your FPGA application will fit on the Spartan-6 LX45.
Build LabVIEW FPGA I/O scan (analog in, analog out, digital I/O, specialty digital I/O).
Convert I/O variable aliases to single-process shared variables with real-time FIFO enabled.
Build a real-time I/O scan with scaling and a shared variable-based current value table.
242
Figure 11.45. The first step in porting an application from CompactRIO to an alternate target
is finding replacement I/O on the future target.
243
Figure 11.46. Develop a simple FPGA application to act as an FPGA scan engine.
After you have implemented a simple scan engine in the FPGA, you need to port the real-time portion of the application
to communicate with the custom FPGA scan engine rather than the scan engine I/O variables. To accomplish this,
you need to first convert all I/O variable aliases to single-process shared variables with the real-time FIFO enabled.
The main difference between the two variables is while I/O variables are automatically updated by a driver to reflect
the state of the input or output channel, single-process shared variables are not updated by a driver. You can change
the type by going to the properties page for each I/O variable alias and changing it to single-process.
Tip: If you have numerous variables to convert, you can easily convert a library of I/O variable aliases to shared
variables by exporting to a text editor and changing the properties. To make sure you get the properties correct, you
should first create one dummy single-process shared variable with the single-element real-time FIFO enabled in
the library and then export the library to a spreadsheet editor. While in the spreadsheet editor, delete the columns
exclusive to I/O variables and copy the data exclusive to the shared variables to the I/O variable rows. Then import
the modified library into your new project. The I/O variable aliases are imported as single-process shared variables.
Because LabVIEW references shared variables and I/O variable aliases by the name of the library and the name of
the variable, all instances of I/O variable aliases in your VI are automatically updated. Finally, delete the dummy
shared variable that you created before the migration process.
244
Figure 11.47. You can easily convert an I/O variable (IOV) alias library to shared variables by
exporting the variables to a spreadsheet, modifying the parameters, and importing them into
your new target.
The final step for implementing an FPGA scan engine is adding a real-time process to read data from the FPGA and
constantly update the current value table. The FPGA I/O you are adding to the shared variables is deterministic, so
you can use a Timed Loop for implementing this process.
To read data from the FPGA scan engine, create a Timed Loop task set to the desired scan rate in your top-level RT VI.
This Timed Loop is the deterministic I/O loop, so you should set it to the highest priority. To match the control loop
speed of your previous Scan Mode application, set the period of this loop to match the period previously set for Scan
Mode. You also need to change the timing sources of any other task loops in your application that were previously
synchronized to the Scan Mode to the 1 kHz clock and set them to the same rate as the I/O scan loop.
The I/O scan loop pushes new data to the FPGA and then pulls updated input values. The specific write and read VIs
are also responsible for the scaling and calibration of analog and specialty digital I/O.
245
Figure 11.48. The FPGA I/O scan loop mimics the RIO Scan Interface feature by
deterministically communicating the most recent input and output values to and from the
FPGA I/O and inserting the data into a current value table.
Figure 11.49. The RT Write FPGA Scan IO VI pulls current data using a real-time FIFO singleprocess shared variable, scales values with appropriate conversion for the FPGA Scan VI, and
pushes values to the FPGA VI.
246
Figure 11.50. The RT Read FPGA Scan IO VI pulls all updates from the FPGA Scan IO VI,
performs applicable conversions and scaling, and publishes data to a current value table using
a real-time FIFO single-process shared variable.
After building the host interface portion of a custom FPGA I/O scan to replace Scan Mode, you are ready to test and
validate your ported application on the new target. Ensure the FPGA VI is compiled and the real-time and FPGA
targets in the project are configured correctly with a valid IP address and RIO resource name. After the FPGA VI is
compiled, connect to the real-time target and run the application.
Because the RIO architecture is common across NISingle-Board RIO, CompactRIO, and R Series FPGA I/O devices,
LabVIEW code written on each of these targets is easily portable to the others. As demonstrated in this section, with
proper planning, you can migrate applications between all targets with no code changes at all. When you use the
specialized features of one platform, such as the RIO Scan Interface, the porting process is more involved, but only
the I/O portions of the code require change for migration. In both situations, all of the LabVIEW processing and
control algorithms are completely portable and reusable across RIO hardware platforms.
247
CHAPTER 12
Security on NI RIO Systems
Security Concerns on RIO Systems
Reconfigurable I/O (RIO) systems (NI Single-Board RIO, NI CompactRIO, and so on) are often used in critical applications.
While the application space for the RIO platform is expansive, security concerns with RIO systems can be more
narrowly defined.
One key security concern is functional correctness, wherein the I/O of the RIO device is proper. This is a security
concern because if functional correctness is compromised, the hardware that the RIO device is connected to can get
damaged or malfunction. For example, failed products on an assembly line may pass if the I/O of the RIO device has
been compromised, or alternatively, motors and centrifuges controlled by the RIO device may get permanently
damaged if they are ramped improperly.
In addition to functional correctness, a key security concern is sensitive data protection. RIO devices often compute,
carry, or transmit sensitive data. Its important to ensure that this data is properly protected. Besides the data itself,
valuable algorithms are often programmed onto RIO devices as well. Keeping these algorithms safe from theft is
also crucial.
The three key security concerns, functional correctness, sensitive data protection, and algorithm protection are
seldom considered independently on a RIO system. Often, a compromise in one of these areas leads to a
compromise in another.
Figure 12.1. The Trade-Off Between Security and Time, Cost, and Ease of Use
248
Given this trade-off, you need to evaluate the proper investment in security for each application. The security required
by an application depends on the liability and scope of the application. National Instruments provides best practices
and open channels of communication to help you overcome the challenges that security presents.
Layers of Security
Security can be defined at several different levels in most systems. For a RIO system, security is defined at the following
key levels; physical, network, operating system, and application. Its important to have some protection at each level,
otherwise, a compromise in one layer can easily lead to a compromise in another. If you invest a lot of time and effort
protecting one layer and fail to consider other layers, an intruder may find a way around the well-protected layer and
manage to compromise your system with little effort.
First, you need to understand how the four RIO system layers are related. The layers farthest away from the application
are the physical and network layers. Security threats to a RIO system can emerge from these two layers. The next
affected layer is the operating system layer, which is closest to the application. Lastly, the application layer, which
resides at the core, requires the most protection. Steps can be taken at each of the layers to ensure that the overall
application is not compromised.
249
(Ethernet
Development and/or
Deployment PC
250
CHAPTER 13
Using the LabVIEW for CompactRIO
SampleProjects
LabVIEW 2012 and later provides several fully functioning project templates and sample projects to use as starting
points for your own applications. All of the sample projects are built on existing LabVIEW project templates, like the
Simple State Machine or the Queued Message Handler. You can spend less time developing your own application by
using one of the sample projects that already has a lot of the application written for you. Using a sample project also
ensures that the design your application is based on is an architecture recommended by NationalInstruments.
LabVIEW 2012 and later includes three sample projects that were written for CompactRIO and NI Single-Board RIO targets:
LabVIEW 2013 and later includes an additional sample project designed for SCADA systems:
High-performance controlThe control loop can run faster than 10 kHz and features four control algorithms
operating in parallel, all with minimal jitter.
Hardware-based controlRunning the control algorithm and safety logic on the FPGA provides maximum
reliability.
User interface with headless optionThe user interface VI interacts with the CompactRIO device and
displays data. This VI can connect and disconnect from the device at any time without affecting the control loop.
Error handlingThe application reports and logs all errors from the CompactRIO device and then shuts down
on critical errors.
251
Headless operation with optional user interfaceThe user interface VI interacts with the CompactRIO
device and displays data. This VI can connect and disconnect from the device at any time without affecting the
acquisition and logging loop.
252
Triggered data loggingThe real-time VI logs acquired data to disk as TDMS files when a trigger condition is
met. This sample project also manages the amount of disk space being used.
Error handlingThe application reports and logs all errors from the CompactRIO device, shutting down on
any critical error.
Figure 13.3. LabVIEW Waveform Acquisition and Logging Sample Project Architecture
Deterministic, software-based controlThe real-time controller executes parallel control algorithms that run
at different rates.
RIO Scan InterfaceThe RIO Scan Interface provides single-point updates to I/O variables at rates up to a few
hundred hertz without requiring FPGA programming.
User interfaceThe user interface VI interacts with the CompactRIO device and displays data. This VI can
disconnect from the device and reconnect at any time without affecting the control loop.
Error handlingThe application reports and logs all errors from the CompactRIO device and shuts down on
critical errors.
253
Figure 13.4. LabVIEW Real-Time Control (RIO Scan Interface) on CompactRIO Sample Project
Architecture
SCADA serverThe SCADA server manages I/O points in the system, logs data and alarms in the historical
database, and regularly archives data from the logging database to the archive database.
Administrator consoleThe administrator console allows the system administrator to configure and manage
the SCADA server.
ClientThe client allows the operators to monitor the system status and I/O points. The operator can view the
values of the I/O points, alarms, and historical trends in different detailed views.
Simulated CompactRIO system and simulated PLC-based systemA simulated CompactRIO system and
a simulated PLC-based system are included in this sample project. The systems demonstrate how to connect
to third-party devices. You can replace the simulated systems with a real CompactRIO system and a real PLCbased system.
ScalabilityYou can use this sample project as a starting point to scale to a large system by adding a large
number of I/O points or adding many subsystems in this sample project.
254
Figure 13.5. LabVIEW Supervisory Control and Data Acquisition Sample Project Architecture
255
Figure 13.6. Data Communication Diagram for the LabVIEW FPGA Control on CompactRIO
Sample Project
For an introduction to creating data communication diagrams for CompactRIO applications, see
Chapter 1: Designing a CompactRIO Software Architecture.
256
Figure 13.7. Create a sample project by clicking the Create Project button.
If you choose the CompactRIO filter under the Sample Projects heading, you can see the LabVIEW FPGA Control on
CompactRIO sample project. Follow the More Information link to launch the documentation for this sample project.
Before opening the documentation, start the process of creating your own copy of this project by clicking Next in the
Create Project dialog.
You can see several options for customizing your own copy of the LabVIEW FPGA Control on CompactRIO sample
project. In this case, change Project Name to My Control Application. Specify a new folder titled My Control
Application within your preferred directory. Leave all the other options as default. Click the Finish button to start
copying the project. While the project is being made, examine the documentation.
257
Review Documentation
You can see in the overview of this documentation that the sample project is based on the Simple State Machine
and Queued Message Handler project templates. You can also see a list of features, including the high-performance
and hardware-based control of this application, because the control loop is running on the FPGA target.
If you scroll down, you can see the system requirements for this sample project, the required software and
hardware, and an overview of all the parallel tasks running across the execution targets in this application.
Further down, a diagram illustrates what happens when you change a control setpoint on the user interface of this
application. You can see that a message is sent over the network to the real-time target containing the new
setpoints, and the real-time target sends those setpoints via read/write controls to the FPGA target. Explore how
this works later when you open up the VIs.
258
The documentation also contains instructions on how to modify the sample project to include your own hardware
under Modifying this Sample ProjectAdapting the Sample Project to Your Hardware.
Now look at the completed project.
259
FPGA Main VI
The front panel of the FPGA Main VI features many controls and indicators. The Real-Time Main VI uses read/write
controls to set and get the values of these controls and indicators. Now look at the block diagram.
Note: This FPGA VI was written to be loaded to flash memory using the NI RIO Device Setup utility and configured
to reload the FPGA bitfile only upon cycling the power. After reviewing the LabVIEW FPGA code, see instructions for
properly configuring the FPGA bitfile in the section Downloading the FPGA Bitfile to Flash Memory.
Control Loop
Right away, you see multiple blue labels indicating places where you are required to add your own code for your
specific application. You can see the control loop is a state machine that is initialized in the safe state. The only way
for the control loop to move out of the safe state is by receiving a command from the Real-Time Main VI. While in
the safe state, a safe state value is sent to all of the output controls for your control algorithm.
If the user moves the control algorithm into the Manual state on the user interface, then the Manual state runs. In this
state, users can specify which manual values they wish to write to each of the output channels.
Figure 13.13. Move into Manual state to manually control the hardware outputs.
260
If users run this application in the Control state (see Figure 13.14), then they are required to add a function, like the
PID block that is available with the LabVIEW PID and Fuzzy Logic Toolkit, to actually perform the control algorithm
because this code has no control function. The PID block installs with the LabVIEW Real-Time Module, and can be
easily dropped into this VI. You can also create your own custom control algorithm.
Figure 13.14. Move into the Control state to execute PID control on all four channels.
Watchdog Loop
In addition to the control loop, you can use the Watchdog Loop. This loop, once enabled by the RT Main VI,
periodically pets the watchdog and resets the system if a timeout occurs. The timeout occurs when the real-time
Watchdog Loop does not execute within a timeout period defined by the user. The Watchdog Loop runs on the FPGA
VI instead of the real-time target because this code allows the FPGA to switch into a safe state and write known
values to the outputs before resetting the system. For more information on watchdog timers, see the Ensuring
Reliability With Watchdog Timers section of Chapter 3: Designing a LabVIEW Real-Time Application.
More information on configuring the watchdog timer is included in the real-time Watchdog Loop discussion later in
the chapter.
Note: If the FPGA bitfile is loaded to flash and set to reload only upon cycling the power, then when you call the
System Reset node, the real-time controller reboots, but the FPGA bitfile continues to run. This ensures that the
FPGA hardware outputs immediately go into a safe state and stay there until the real-time controller is back online.
After reviewing the LabVIEW FPGA code, see instructions for properly configuring the FPGA bitfile in the section
Downloading the FPGA Bitfile to Flash Memory.
261
If you choose to not download the FPGA bitfile to flash memory, or if you choose to download it to flash but with the
option to autoload upon a device reboot, then you need to add some logic to this TRUE case to ensure that the
hardware outputs go into a safe state prior to calling the System Reset node. Otherwise, a race condition could
occur and you could end up resetting the FPGA prior to putting the hardware outputs into a safe state.
RT Main VI
Now look at the RT Main VI, which features several loops running in parallel. A comment on the diagram explains the
functionality of each of the parallel loops. This VI opens with a broken run arrow since the FPGA VI is not compiled.
UI Commands Loop
The top loop is the UI Commands VI. Open this VI.
This VI is based on the Simple State Machine project template that is available with LabVIEW. You can see that this VI
is using Network Streams to communicate with the user interface VI under My Computer. The main purpose of this
loop is to receive UI commands and manage the connection of any Network Streams that are used within the
application. This sample project uses two streams:
Network Streams are used for this type of data transfer because when sending commands from a user interface to
an embedded system, you need a reliable data communication mechanism. Network Streams were designed and
optimized for lossless, high-throughput data communication. They feature enhanced connection management that
automatically restores network connectivity if a disconnection occurs due to a network outage or other system
failure. Streams use a buffered, lossless communication strategy that ensures data written to the stream is never
lost, even in environments that have intermittent network connectivity.
262
The VI initializes by going into the Listen for UI Writer state and waits until it makes a connection with the UI, at
which point it moves into the Receive UI Commands state.
Figure 13.18. The UI Commands loop receives UI commands and manages the
network connection of Network Streams.
Upon receiving an error in both the Listen for UI Writer and Receive UI Commands cases, destroy the Network
Stream and attempt to create a new one. This allows the client to disconnect and reconnect at any time while the RT
application continues to run. When the client disconnects, the reference is no longer valid, so you need to create a
new one.
You write data received from the Network Stream into the Enqueue Message VI shown in Figure 13.20. The Enqueue
Message VI passes all messages or commands to the Message Handling Loop shown in Figure 13.21. This VI is borrowed
from the Queued Message Handler Template available for the LabVIEW Core software option. The Message Queue
API is basically a wrapper around Queue functions with usability tweaks for communicating messages between two
or more loops. You can double-click the Enqueue Message VI to see how it works. This function forces the user to
send messages as a cluster consisting of a string (the message or command) and a variant (any associated data). For
example, the command might be Change Setpoint and the associated data might be 27 C. This is a scalable and
efficient method for communicating messages within a large application. You use the variant data type so that you
can use the same API to send multiple data types.
263
Figure 13.20. The Message Queue API is a wrapper around Queue functions.
The Message Handling Loop is part of the RT Main VI. The RT Main VI was built from the Queued Message Handler
project template and thus uses a Queued Message Handler architecture for receiving and sending messages. The RT
Main VI is set up to handle different messages like updating the state on the FPGA, handling errors, and sending
data to the UI.
Note that every parallel loop on the RT Main VI has its own unique error handler VI, shown in Figure 13.22.
264
Figure 13.22. Each loop has its own error handler subVI.
By using its own error handler, each loop can specify unique errors that the particular loop wants to handle in a
certain way. Any error message that is generated within the real-time application can be classified by the user as
critical, log-only, and ignore. Any error that isnt classified by the user is automatically classified as non-critical. All
error messages are sent to the Message Handling Loop and are processed within the Critical Error, Log-Only
Error, Non-Critical Error case, which is shown in Figure 13.23. Note that a feature of the Queued Message
Handler is that in addition to receiving messages from the producer loop (UI Command Loop), the consumer loop
can send messages to itself and make decisions on which state executes next.
In Figure 13.23, all error messages are logged to the local drive on the real-time controller and sent to the UI for
display. In addition, upon a non-critical error, the FPGA goes into a safe state. Send a message to the UI notifying the
user that the FPGA state has changed. Upon a critical error, exit the application.
Figure 13.23. All error messages are processed in the Message Handling Loop.
265
Watchdog Loop
The next VI on the RT Main VI is the Watchdog Loop.
The only purpose of this VI is to use a read/write control to periodically pet the watchdog in the Watchdog Loop on
the FPGA that you already looked at.
Figure 13.25. The RT Watchdog Loop periodically pets the watchdog loop on the FPGA
to ensure that RT to FPGA communication is present.
Several global variables are referenced throughout the RT Main VI. The RT Main VI includes one global variable that
stores all configuration options titled Global-Configuration Options.vi. This global variable is located in the LabVIEW
project under the RT TargetGlobals folder and is shown in Figure 13.26. This is where users can specify whether
they are in debugging mode, in addition to timeouts and loop rates.
266
Figure 13.26. Configuration options used within the RT Main VI are stored as a global variable.
The watchdog timeout by default is set to 40,000,000 ticks of the FPGA clock or 1 second. This means that if the
Watchdog Loop fails to execute within 1 second on a given iteration, a watchdog timeout occurs and the FPGA goes
into a safe state. Keep in mind that a real-time OS is extremely reliable and the only reason a loop might not finish on
time is typically because of CPU starvationyour system runs out of memory and the software is hanging or is
about to crash. You can ensure that the CPU bandwidth stays low and that the largest block of contiguous memory
does not decrease by monitoring them in the System Health and FPGA Monitoring Loop.
You should disable the watchdog timer in debugging mode since debugging tools such as highlight execution cause
the application to run much slower.
267
This loop uses network-published shared variables to send monitoring information to the UI Main VI. You monitor
input values (analog input) and output values (analog output) from the FPGA VI by using read/write controls and
monitor some real-time system data, such as largest contiguous memory block and CPU usage percentage.
You need to keep the CPU usage percentage below 80 percent. If the CPU usage reaches 100 percent, you probably
have loops that are running slower than your specified rate. If a high-priority Timed Loop is active, the other loops
may not be executing at all. If you find that the CPU usage is higher than 80 percent, you should review the LabVIEW
Real-Time Help document Minimize CPU Usage for tips and tricks on how to reduce it.
You also should closely monitor the largest block of contiguous memory. The largest block of contiguous memory
should be fairly constant because LabVIEW allocates and releases memory throughout the execution of the RT Main
VI. If you see that the contiguous memory falls below a certain limit, go into a safe state and restart the system.
When you restart the real-time controller, the memory is defragmented. Often an embedded software application
crashes not because it ran out of memory but because the available memory is very fragmented. This is caused by
dynamic memory allocations. Some applications cannot be restarted while they are deployed out in the field, and for
these applications, the developer should spend extra time removing a majority if not all of the dynamic memory
allocations. Some common sources of dynamic memory allocation include Queues without a fixed-sized buffer,
variable-sized arrays (and waveforms), variable-sized strings, and variants.
268
Finally, note that any input or output errors from the LabVIEW FPGA VI are also handled in this loop. If an error
occurs on either the analog input node or the analog output node in the LabVIEW FPGA VI, a custom error message
is sent to the UI for display.
Figure 13.30. A custom error message is sent to the UI if an error occurs on the LabVIEW
FPGA I/O nodes.
Figure 13.31. The RT Main VI stops if the user presses the Exit button on UI Main VI
or if a critical error occurs within the RT Main VI.
269
UI Main VI
Open the UI Main VI. This is the user interface that your user interacts with when operating the LabVIEW FPGA
Control on CompactRIO application. In the upper-left corner of the user interface, you see the Connection Settings.
When this application first runs, these are the only settings that the user can change. All other controls are disabled.
The user can now change the IP address of the controller and choose to connect to that IP address. Once
connected, the rest of the user interface enables.
If you want to run the FPGA control algorithm in the Control state, you can click the Run Control button.
Once the control is running, you can set setpoint values, which are sent to the target automatically. Note that the
setpoints automatically coerce to the range of the input module being used for the PID control task.
You typically want to tweak the Control Configuration settings while the control loop is running. To send the updated
Control Configuration settings to the target, you can click the Update Control Configurations button.
On the Manual tab, you can set the values of all the FPGA outputs directly. When you click the Run Manual button,
the FPGA Main VI switches into the Manual state.
The Data Monitoring tab features the raw channel values of the inputs and the outputs on the FPGA.
Finally, the System Monitoring tab shows monitoring information like CPU usage, largest continuous memory, and
the loop period of the VI running on the FPGA. If any errors occur while running this application, they appear in the
System Status string on the front panel.
Now look at the block diagram. The UI Main VI has three parallel loops.
270
Note that this loop is registered for the user event Stop. You use the user event so the Message Handling Loop is
in charge of shutting everything down. If an error (as opposed to a UI event) is what causes the UI Main VI to exit,
you need a way for the Message Handling Loop to tell the Event Handling Loop to stop. The user event is the NIrecommended way.
When designing applications involving a UI, ensure that the loop handling front panel events is the last one to shut
down. In this sample project, when you press the Exit button, you immediately send an Exit command down to the UI
Message Loop, as shown in Figure 13.34. Once the Event Handling Loop has received an acknowledgement that the
UI Message Loop has stopped (or is executing the Exit case), stop the Event Handling Loop. You send this
acknowledgment by sending a user event called Stop from the UI Message Loop to the Event Handling Loop.
Figure 13.34. The Event Handling Loop sends messages to the UI Message Loop that
are generated from front panel events.
271
UI Message Loop
The UI Message Loop, which is based on the Queued Message Handler project template, handles messages from
the user interface and any error messages received from the real-time target via Network Streams.
Figure 13.35. The UI Message Loop sends messages to the CompactRIO device using
Network Streams
and handles the configuration of front panel controls.
Connect
Closes network connections upon an error in the UI Message Loop and/or the UI Monitoring Loop.
Disconnect UI
Updates the Connected? indicator if both the Network Streams and network-published shared variables
are successfully created.
Close Connections
Enables and disables front panel controls based on the connection status.
Disconnects the UI after closing network connections (if something went wrong). User needs to attempt
to reconnect and address any networking issues.
272
Initial UI Values
Identifies any incoming errors as RT or UI and displays the error message to the System Status
indicator on the front panel.
Exits upon a critical error.
Enables/disables controls depending on the state of the FPGA (this case is called when the FPGA state
changes).
When the user modifies the value of any setpoint control or manual value control on the front panel, the
new value is sent to the FPGA control loop.
Sends the control configuration on the user interface to the FPGA Main Control Loop when the user hits
the Update Control Configuration button.
Sends any of the commands listed above to the RT Main VI, which then sends the commands to the FPGA
Main VI.
Initializes the UI with the current values of the FPGA Main VIs read/write controls upon successful
connection to the real-time target.
Run Control, Run Manual, Run Safe State, Stop Control, Stop Manual
Once the connection is established within the Connect case, a command is sent to the RT Main VI to
retrieve all current FPGA Main VI parameter values and send them back to the UI. This is important since
the FPGA Main VI control loop continues to run even when the client disconnects and reconnects.
Adds a new string to the beginning of the System Status string on the UI.
Exit
Fires the user event to stop the Event Handling Loop and toggles the local variable to stop the Monitoring
Loop. This message alone causes all three loops to stop.
Monitoring Loop
The Monitoring Loop runs periodically when connected and uses network-published shared variables to display the
monitored values from the real-time target. You use network-published shared variables instead of Network Streams
because you are concerned only with the current value of the data, and you are OK with missing a few data points
here and there.
Note that you use the Dynamic Shared Variable API instead of the static shared variable nodes. This is because you
can dynamically change the IP address of the real-time target from the front panel. To ensure that you connect to the
Shared Variable Library that is hosted on the real-time target corresponding to the IP address on the front panel, use
the IP address on the front panel when opening a connection to each variable.
273
When you use static shared variable nodes, the IP address is statically configured in the LabVIEW project. If you
change the IP address on the front panel, the UI Main VI continues to connect to the IP address defined in the
LabVIEW project.
The shared variable connection is created in the UI-Initiate Connection.vi found in the Connect state of the UI
Message Loop.
For more information on the LabVIEW FPGA Control on CompactRIO sample project, view the documentation in the
created project or follow the More Information link in the Create Project window.
Figure 13.36. The Monitoring Loop receives current value data from
the CompactRIO device and displays it to the UI.
274
275
2. On the Information page, ensure that Run when loaded to FPGA is checked. If its not checked, check it and
rebuild the bitfile.
3. To load your FPGA bitfile to flash memory, launch the RIO Device Setup utility by right-clicking your FPGA target.
Figure 13.39. Launch the RIO Device Setup Utility from the LabVIEW project.
4. On the Download Bitfile to Flash tab, select the bitfile you want to use and click the Download Bitfile button.
276
5. On the Device Settings tab, select Autoload VI on device powerup and press the Apply Settings button.
Figure 13.40. Configure your FPGA bitfile to load to your device every time you cycle the
power.
6. Now your FPGA bitfile loads to your device every time you cycle the power. If you perform a system reset, the
FPGA bitfile stays loaded, and the real-time OS restarts.
277
7. Finally, open the Initialize and Run FPGA subVI within the RT Main VI and ensure that the Open FPGA VI
Reference is configured to not run the FPGA VI when called. Since the FPGA bitfile already is loaded, calling
this function resets the FPGA bitfile, which is not necessary.
Figure 13.41. Uncheck the Run the FPGA VI option in the Configure Open FPGA VI Reference
dialog.
2014 National Instruments. All rights reserved. CompactRIO, CVI, LabVIEW, Measurement Studio, National Instruments, NI, ni.com, NI FlexRIO, NI SoftMotion, the National Instruments
corporate logo, and the Eagle logo are trademarks of NationalInstruments. For other National Instruments trademarks see ni.com/trademarks. The mark LabWindows is used under a license
from Microsoft Corporation. Windows is a registered trademark of Microsoft Corporation in the United States and other countries. Other product and company names listed are trademarks or
trade names of their respective companies.
278