Synchronous Generator
Synchronous Generator
Laboratory Practice V
Synchronous Generator
Name
Index No.
Group
Field
Date of Performance
Date of Submission
:
:
:
:
:
:
S.P.M Sudasinghe
100523G
G - 12
EE
2013/08/28
2013/09/20
OBSERVATIONS
Name: S.P.M Sudasinghe
Index no: 100523G
Group: G 12
Date: 2013/08/28
Instructed by: Mr K.K.M.S Kariyawasam
If (A)
20
0.01
40
0.04
60
0.05
80
0.07
100
0.10
120
0.12
140
0.14
160
0.17
180
0.20
200
0.24
220
0.30
240
0.38
260
0.51
270
0.59
Is/c (A)
If (A)
0.02
0.04
0.05
0.08
0.10
0.12
IL (A)
VL (V)
3.5
220
4.0
216
4.5
212
5.0
206
5.5
202
6.0
196
IL (A)
VL (V)
0.38
218
0.76
216
1.16
216
1.48
214
CALCULATIONS
1. Calculations of Synchronous Reactance
Synchronous Reactance= X S =
V O/C
I S/C
60
=25
2.5
Similarly XS can be calculated for other values of field currents using the graph 1
Observations from graph 1
If (A)
VO/C (V)
IO/C (A)
Calculated XS
()
0.05
60
2.5
25.00
0.10
106
5.0
21.20
0.15
145
7.5
19.33
0.20
176
10.0
17.60
0.25
202
12.5
16.16
0.30
220
15.0
14.67
0.35
235
17.5
13.43
0.40
246
20.0
12.30
0.45
254
22.5
11.29
0.50
260
25.0
10.40
0.55
265
27.5
9.64
0.60
270
30.0
9.00
If Ia
SCR=
SCR=
18
6.6
= 2.7
1
SCR
1
2.7
X S ( SAT ) , pu=
= 0.37 pu
In ohms,
X S(SAT ) =X S ( SAT ) , pu
V rated
I rated
X S (SAT )=
0.37
240
6.66
= 13.33
cos + j sin jX s
E=V + I
-------------- (1)
V o /c 220
=
=14.67
I s / c 15
cos =1 =0
From equation 1,
V 22 V 1 14.67 0+12 14.672=2202
V = 219.51
V = 219.51V
a) For cos = 0
cos =0 =90 0
For =900,
2
V 229.34 V 48184.79=0
V =234.67V =205.33
V= 234.67 V
For =-900,
V 22 V 1 14.67 sin (900 ) +12 14.672 =2202
V 2 +29.34 V 48184.79=0
V =205.33V =234.67
V= 205.33
V= 225.99 V
For =-25.840,
V 22 V 1 14.67 sin (25.840 ) +12 14.672 =2202
V 2 +12.79V 48184.79=0
V =213.21V =225.99
V= 213.21V
IL (A)
1
2
4
6
8
10
12
cos=1
219.51
218.03
212.03
201.62
186.08
163.95
131.95
DISCUSSION
SCR for low speed generators is 1.0 to 1.5 and for modern turbo-generators is 0.5 to 0.6
V o/c
I s/ c
It may be seen from graph 2 that the synchronous reactance decrease with the increase in field
current. This is due to magnetic saturation effect. As long as the resultant flux density due to the
effect of armature and field currents, is below the knee point of the saturation curve the flux
produced per ampere of armature current is approximately constant. Therefore the synchronous
reactance is constant. For higher flux densities the flux produced per ampere decreases and
consequently the synchronous reactance decreases.
Synchronous generators field current depends on the connected load. Similarly in a current
transformer, the primary current depends on the load connected to the secondary winding.
Hence the armature winding of the synchronous generator act as secondary winding of the current
transformer and the field winding of the synchronous generator is similar to the primary winding of a
current transformer.
4. Variation of terminal Voltage with Load current for various power factor loads
For unity power factor, and for lagging power factors Terminal voltage always decrease when the
load current increase. But for leading power factors terminal voltage increases first and begin to fall
after some point when the load current increases. From the graph 5 we can see that load having 90
leading power factor angle (zero leading power factor) is approximately a straight load characteristic
and always increase with load. Zero lagging power factor load has also a straight load characteristic
and it decrease always.
Normally the terminal voltage falls with the increase in load current. Reason is the increase in
voltage drop through synchronous impedance due to increasing load current.
When the power factor is leading (highly capacitive load) the effect of armature flux is to help the
main flux, hence to generate more emf. This causes the terminal voltage to increase first. But after
some value of load current effect of voltage drop through synchronous impedance becomes higher
than the increase in generated emf. Then terminal voltage starts to decrease after some value of load
current.
When power factor is lagging (highly inductive load) the effect of armature flux is to oppose the
main flux, hence to reduce generate emf. Hence terminal voltage falls rapidly with load current for
lagging power factors. Reduction of voltage with load current for lagging power factors is more than
unity and leading power factors.