Power System Reliability Analysis With Distributed Generators
Power System Reliability Analysis With Distributed Generators
by
Dan Zhu
Thesis submitted to the faculty of
Virginia Polytechnic Institute and State University
in partial fulfillment of the requirements for the degree of
Master of Science
In
Electrical Engineering
Approved:
Dr. Robert P. Broadwater, Chairman
Abstract
Reliability is a key aspect of power system design and planning. In this
research we present a reliability analysis algorithm for large scale, radially
operated (with respect to substation), reconfigurable, electrical distribution
systems. The algorithm takes into account equipment power handling constraints
and converges in a matter of seconds on systems containing thousands of
components.
Acknowledgements
I would like to acknowledge the invaluable guidance, concern and support
of my advisor, Dr. Robert Broadwater. During this research, he always accepted
my ideas with an open mind and gave me the maximum opportunity to contribute
to the program. His advice really helped me to refine the application.
I would like to thank Electric Distribution Design (EDD) Inc. for providing
facilities to finish this research work, and Electric Power Research Institute (EPRI)
Distribution Engineering Workstation (DEW) for benchmark analysis of the power
flow calculations.
Thanks are also due to Dr. Jacobs and Dr. Pratt for serving on my
committee. They both helped to review my thesis paper.
My husband, Max, deserves special thanks. His unselfish support and
encouragement has allowed me to keep my perspective during this time.
iii
Table of Contents
1. Introduction ... 1
1.1. Introduction ..... 1
1.2. Objective of the Research 1
1.3. Distributed Generators.. 2
1.4. Literature Review . 3
1.5. Definition of Power System Reliability 4
1.6. Reliability Assessment Techniques.. 5
2. Measuring Service Quality.. 7
2.1. Definitions of Performance Indices.. 7
3. Comparison of Different System Designs.. 9
3.1. Simple Radial Distribution System 9
3.2. Alternative Feed Distribution Arrangement..10
3.3. Alternative Feed Arrangement with DR .. 10
4. Switching Operations....... 12
5. Reliability Analysis Sets... 14
5.1. Segment..... 14
5.2. Reliability Analysis Sets............... 15
6. Pointer and Circuit Traces...................... 21
6.1. Workstation Circuit Model............21
6.2. Pointers...... 22
6.3. Circuit Traces............................... 24
7. Computer Algorithm............................... 28
7.1 Introduction .. 28
7.2 Algorithm...28
iv
List of Figures
Figure 1.1 Subdivision of System Reliability.....5
Figure 3.1 Simple Radial Distribution System.......9
Figure 3.2 Alternative Feed Distribution Arrangement ...10
Figure 3.3 Alternative Feed Arrangement with DR .....11
Figure 4.1 Sample Circuit.............13
Figure 5.1. Sample segment .........15
Figure 5.2. Reliability Analysis Sets .......16
Figure 6.1 Sample Circuit ............25
Figure 7.1 Illustrating Selection of Alternative Feed ...34
Figure 7.2 Reliability Analysis Algorithm Sequence Diagram 39
Figure 8.1 Example Circuit for Relative_CAIDI .........46
Figure 10.1 System 1 for Case Study One ...................50
Figure 10.2 System 2 for Case Study One: Adding an Alternative Feed .53
Figure 10.3 System 3 for Case Study One: Adding a Distributed
Generator .............56
Figure 10.4 System for Case Study Two .....58
Figure 10.5 Addition of Substation and DG to System Shown
in Figure 10.4 .......... 59
Figure 10.6 DG at the End of Circuit .......60
Figure 10.7 Circuit for Case Study Three ....................62
Figure 10.8 Down Time Variation with Varying Load of L_C32 .. 63
Figure 10.9 Down Time with Varying Load of L_C32 ...64
vi
List of Tables
Table 6.1 DEW Component Trace Structure Element 23
Table 7.1 Summary of Traces Used to Develop the RA Sets ..36
Table 7.2 Summary of Messages in the RA Sequence Diagram .40
Table 10.1 Equipment Index Table ..51
Table 10.2 Improvement of Reliability ....55
Table 10.3 Comparison of Reliability Improvements ..57
Table 10.4 System Reliability Improvement for Case Study Two .. 61
vii
1. Introduction
1.1. Introduction
The economic and social effects of loss of electric service have
significant impacts on both the utility supplying electric energy and the end
users of electric service. The cost of a major power outage confined to one
state can be on the order of tens of millions of dollars. If a major power
outage affects multiple states, then the cost can exceed 100 million dollars.
The power system is vulnerable
[1]
1. 4. Literature Review
Prior to the 1960s, the reliability of proposed power systems was
often estimated by extrapolating the experience obtained from existing
systems and using rule-of-thumb methods to forecast the reliability of new
systems[3].
During the 1960s considerable work was performed in the field of
power system reliability and some excellent papers were published. The
most significant publications were two company papers by a group of
Westinghouse Electric Corporation and Public Service and Gas Company
authors[3],[4]. These papers introduced the concept of a fluctuation
environment to describe the failure rate of transmission system components.
The techniques presented in these papers were approximations which
provided results within a few percent of those obtained using more
theoretical techniques, such as Markov processes. The application of
Markov Chains in the power system reliability field was illustrated in
Reference [5]. The Markov approach is limited in application because of
computer storage requirements and the rounding errors which occur in the
solution of large systems.
Most previous publications have focused on transmission system
reliability. This research focuses on distribution system reliability. This work
extends previous research[5], which demonstrated sets used in describing
power system reliability calculations. Reference [6] presented the first
application to apply linked lists and pointer concepts to reliability analysis. It
took into account constraints associated with switching operations, but it was
relatively slow due to running numerous power flow calculations.
One aspect investigated h ere is the effect of Distributed Generators
(DG) on power system reliability. Standards for connecting DGs into
distribution systems are just being developed. Reference [7] deals with
issues related to existing DG interconnection practices. An investigation of
eleven utilities and industry interconnection standards was performed to
identify the key requirements for a DG connection. The results of this
investigation led to the development of a unified approach for determining
interconnection requirements. Reference [8] considers many aspects of DGs
in distribution systems, including protection, harmonics, transients, voltage
and frequency control. A Power flow calculation based on the positive
sequence model of the distribution circuits was presented.
1.5. Definition of Power System Reliability
The function of an electric power system is to satisfy the system load
requirement with a reasonable assurance of continuity and quality. The
ability of the system to provide an adequate supply of electrical energy is
usually designated by the term of reliability. The concept of power-system
reliability is extremely broad and covers all aspects of the ability of the
system to satisfy the customer requirements. There is a reasonable
subdivision of the concern designated as system reliability, which is
shown in Figure 1.
Quantitative
methodologies
use
statistical
approaches
to
reinforce
SAIDI =
CAIDI =
10
the left hand side of SW0, we can open SW0 and close SW3, so that the DR
can pick up the rest of the circuit, which was originally fed by S0. Without
the DR, we have to draw the power from S1. Such operation might violate
system constraints or degrade the quality of the power supply, especially
when the customer load reaches a peak value.
11
4. Switching Operations
Reliability analysis for a power system also leads to more reliable and
cost-effective operation, since power restoration analysis is a subset of the
calculations performed for reliability analysis. Here we assume switch
operation time is less than repair time, so loads that have lost power may be
restored faster by appropriate switching operations, or reconfiguration of the
system.
There are two kinds of switching operations of interest. One is
isolating the failure point so that a load point of interest which has lost
power may be re-supplied from the original source. The other is to again
isolate the failure point and to feed a load point of interest from an alternate
source, if an alternate source is available. For example, in Figure 4.1, if a
fault happens in component 5, we can open switch SW4 to isolate
component 5 from the rest of the system. The original source S0 can still
supply power to all the customers, except those on the downstream of switch
SW4.
12
13
14
[11]
reliability of a given load point. Figure 5.2 illustrates the relation among
these sets.
15
16
The L set shown in Figure 5.2 contains all segments within a circuit
whose failure can cause loss of power to the segment of interest S. This L set
includes all segments that are not separated from the continuous path
between the source (substation, generator, etc.) and the segment of interest S
by an automatic protection device.
Now we partition the L set into the sets SSL and NSSL:
The SSL set consists of the segments that may be isolated from the
continuous path between S and the original source
The NSSL set consists of the segments that cannot be switched away
from the continuous path between S and the original source.
The SSL set contains any segments separated from the continuous
path by manually operated switches. If any element of this set fails, the
segment of interest S can be temporarily restored from the original source
before the failed component is repaired or replaced.
Examining those segments that cannot be separated from the
continuous path, we can further partition the set NSSL into SL and NSL:
The SL set consists of the segments that can be switched away from
the segment of interest S, so that if the failure occurs in the SL set, S
may be fed by an alternate source
17
The NSL set consists of the segments that cannot be switched away
from the segment of interest S. That is the segment of interest itself,
so this set only contains the element {S}.
If any thing fails in the NSL set, all the components within that
segment have to experience the full repair or replacement time of the failed
component. Temporary restoration is not possible.
Considering the SL set, we can divide it into SAF and NSAF:
For the SAF set, if the failed component lies in these segments, it is
possible to restore power to S by an alternate source
For the NSAF set, if the failed segment belongs to this set, the
segment of interest S cannot be temporarily restored from an alternate
feed.
The set SAF contains the segments that can be isolated from both the
segment of interest S and the alternative source, which make the temporary
restoration topologically possible. Sometimes, system constraints may limit
the restoration options; the alternate source might not have the capacity to
support the particular load point that of interest. So the set SAF is partitioned
into SF and NSF:
The SF set consists of all segments that can be isolated from S and an
alternative source, allowing power to be restored to S from the
18
(5.1)
NSSL=SL {S};
(5.2)
(5.3)
SAF= SF NSF
(5.4)
(5.5)
To sum up, if the failed component from the L set is placed in the SSL
set, it is possible to restore power to the load point of interest S from the
original source. If the failure occurs in the SF set, the power can be restored
to S from an alternative source without violating system constrains. But if
19
the failed component locates in either {s}, NSAF or NSF sets, then the failed
component must be completely repaired before power can be restored to S.
We use several additional reliability analysis (RA) sets to calculate the
sets of Equation (5.5), as given by
SIC = a set of all the segments in the circuit
SW = a set of all the sectionalizing devices in the circuit
AF = a set of available alternate sources
IS = a set of sectionalizing devices that will isolate the segment of interest S
from the original sources
NIS = a set of switches that do not isolate the original source from the
segment of interest
EC = a set of ending components for the circuit
PD = a set of protective devices in the circuit that isolate a load point of
interest from its source.
20
Power
Research
Institutes
Distribution
Engineering
21
6.2. Pointers
With large amounts of data in active memory, data structure
manipulation is a primary concern. A feature of the C language which has a
significant impact on this problem is the pointer. The pointer is a variable
that holds the address of a data element. Pointers permit the construction of
linked lists of data elements in computer memory [14]. In DEWorkstation,
pointers are used for all data objects. Applications share circuit information
via pointers, and also use pointers to manipulate data objects hidden inside
the applications.
In distribution systems, a single circuit model may contain over 5000
components, and an entire system model consisting of hundreds of circuits
may contain over a million components. With such large systems, modeling
methods have a direct impact on the ability to perform engineering analysis.
Use of pointers in linked lists allows system interconnects and equipment
parameters to be directly available for analysis without repetitive search
algorithms. Intrinsic in the graphical creation of the circuits is the creation of
linked lists. The DEWorkstation memory model links together sources and
components of each circuit[15]. In this way, it is possible to trace from circuit
to circuit, through an individual circuit, or through a particular branch of a
circuit.
Application programmers work with DEWorkstation defined objects.
These objects are manipulated and accessed via pointers and indices into
arrays of pointers. The links provided that pertain to component traces
involved in reliability analysis are:
22
Data Type
Circuit number
Short integer
Substation number
Short integer
Short integer
Short integer
Component name
String
Forward Pointer
Pointer
23
Backward Pointer
Pointer
Pointer
Brother Pointer
Pointer
Pointer
Pointer
Pointer
Pointer
.
Due to the large size of the trace structure, only the elements which
are employed by the reliability analysis module are listed in Table 1. Several
segment trace pointers are included in the structure. The Segment Pointer is
used to find the primary sectionalizing device for a component.
Sectionalizing devices in a circuit are linked in a doubly linked list via the
Forward Segment Pointer and the Backward Segment Pointer. Sectionalizing
devices are also linked with the Feeder Path Segment Pointer, which is
similar to the Feeder path pointer for components, except that only
sectionalizing devices are processed.
24
25
traces. These traces along with the notation used to indicate the trace, are
defined as follows:
FTm = forward component trace beginning with component m (if m is not
specified, FT begins from the substation). FT in the example circuit is
given by
FT= B1 2 3 SW4 5 6
(6.1)
(6.2)
(6.3)
ECT = ending component trace, here for the example circuit is given by
ECT=5 9 13 17 18 19
(6.4)
The circuit traces discussed above are basic circuit traces. For reliability
analysis, it is more efficient to work with pointers to segments and to
perform traces based on these pointers. The segment circuit traces used in
this research are as follows:
26
FSTm = forward segment trace from segment m, (if m is not specified, the
forward trace will begin with the substation). In the example circuit,
FST is given by
FST= B1 SW4 Fu7 SW14
(6.5)
(6.6)
AFT = alternative feed trace. In the example circuit, there is only one
alternative source, so AFT is given by
AFT = SW25
(6.7)
If there is more than one alternative feed for the circuit, then AFT would
consist of the linked list of all alternative feeds.
27
7. Computer Algorithm
7.1 Introduction
This chapter presents the computer algorithm used to develop the
reliability analysis (RA) sets. The algorithm is implemented with linked lists.
A notation in terms of linked lists is introduced to describe the algorithm. A
software design for implementing the algorithm is also discussed. Along
with the presentation of the algorithm, the example circuit illustrated in
Figure 6.1, is used to explain the development of the RA sets.
7.2 Algorithm
In what follows, we assume for the example circuit that the segment
of interest is given by
{S} = {SW16}
(7.1)
(7.2)
where
pFSeg = pointer to forward segment (in the example circuit, segment B1s
pFSeg pointer is pointed to segment SW14)
pBSeg = pointer to backward segment (in the example circuit, segment
SW14s pBseg pointer is pointed to segment B1)
28
pSeg = pointer to segment device for component (In the example circuit,
all the components in segment SW16, components 17, 18 and 19,
have their pSeg pointed to SW16)
The expression (7.2) is read as the Forward Component Trace (FCT) yields
the SW set and sets the pointers pFSeg, pBSeg, and pSeg. Note that the
notation used here is always to have pointers begin with a small p.
For the example circuit,
SW = {B1, SW4, Fu7, SW11, SW14, SW16, SW23, Fu26, SW25}
(7.3)
In the FCT, we can also find the ending components that make up the
EC set, by using the following condition
If a components forward pointer points to its brother pointer[6], then
this component is an ending component.
Thus,
FCT EC
(7.4)
29
be traced via a FPST. In this way, we can collect all the available alternate
sources. Thus
FCT AF
(7.5)
Note that for each segment stored in the AF set, there are two ending
components. One corresponds to a component in the EC set, and the other
component exists in the adjacent circuit.
Since IS consists of all the sectionalizing devices in the feeder path of
S, we can use a FPSTs to obtain the IS set, as well as the PD (protective
device) set, as given by
FPSTs IS, PD
(7.6)
(7.7)
(7.8)
30
Thus,
FST L
(7.9)
Following the steps described above, we obtain the L set for the segment of
interest S
L= {B1, SW4, SW11, SW14, SW16, SW23}
(7.10)
The segments in the SSL set may be isolated from S and the original source,
so that the power can be restored from the original source. SSL is given by
the following set operations
SSL=L NIS
(7.11)
(7.12)
The NSL set has only one element the segment of interest S. All the failed
components in the segment of interest must be completely repaired before
power can be restored to S.
31
The segments in the SL set can be switched away from the segment of
interest S, so that if the failure occurs in the SL set, S may be fed from an
alternative source. The SL set is given by the following set operation
SL= L IS {S}
(7.12)
(7.13)
32
SAF
(7.14)
(7.15)
The NSAF set includes all the segments for which it is not possible to
restore power to S from an alternative source. All the failed components in
these segments must be completely repaired before restoring power to S.
The NSAF set is given by set operation:
NASF = SL SAF
(7.16)
(7.17)
33
from the alternative feed (AF). If there is more than one alternative feed in
the system, the minimum capacities encountered in the feeder path
component traces FPTAF for all the available sources in the AF set must be
compared. For instance, there are n alternative feeds in the system. Let
CAFk = minimum remaining component power capacity in the FPTAF for the
kth alternative feed, k =1, 2, 3 n
CAFm = max
{CAFk}
k
(7.18)
(7.19)
34
(7.20)
Even though the minimum remaining capacity on the feeder path from
AF1 is equal to the required power in S, pulling the power from AF1 to S will
fully utilize component AF12. Thus AF2 is chosen since it has more
remaining capacity on the feeder path.
In the general case, the segment of interest is not directly connected to
the alternative feeds as shown in Figure 9. So FPT traces in the circuit of
interest are also required to determine remaining power handling capabilities.
In essence, component traces from the segment of interest to all alternative
sources are required to check power handling capacities.
In summary, the Circuit traces which yield the reliability analysis (RA)
sets are shown in Table 7.1
35
Step 1
FCT
Step 2
FPSTs IS, PD
Step 3
FST L
Step 4
FPSTAF, FPSTS
Step 5
FPTAF
SAF
SF or NSF
V j = Vi I j Z j
36
(7.21)
(7.22)
where
Ij = current through element j
Im = current through directly connected downstream element fed by
elements j
Sload = load attached to element j
Vj = voltage at downstream port of element j
Vi = voltage at upstream port of element j
Zj = the impedance of element j.
The sequential algorithm for the Radial Power Flow is given as follows:
1.
2.
3.
SF or NSF
(7.23)
(7.24)
38
39
Return Value
FCT ( )
Component pointer
FPST ( )
Component pointer
FST ( )
Component pointer
Min_Cap ( )
Max_Cap( )
GetCus ( )
Get_Sets( )
Get Data ( )
40
41
8. Reliability Indices
This analysis relies on two general classes of information to estimate
the reliability: component reliability parameters and system structure. Using
system structure and component performance data, we can evaluate the
reliability of specific load points or the whole distribution system. The
structure information is achieved by the circuit traces presented previously.
In the following paragraphs the performance data is discussed.
Predictive reliability techniques suffer from data collection difficulties.
Simplifying assumptions (default values) are required for practical analysis
of distribution systems.
8.1. Functional characterization
The availability of component functionally is characterized by the
following indices:
Annual Failure Rate = the annual average frequency of failure
Annual Down Time = the annual outage duration experienced
at a load point.
The failure rate for segment i, FRi , is the sum of the failure rates of all the
components contained in the segment i as given by
n
FRi = Fr j
j =1
where
Frj = the failure rate for component j
42
(8.1)
REPi =
Fr
j =1
Re p j
(8.2)
Fr
j =1
where
Frj = the failure rate for component j
Repj = the average repair time for component j
n = the number of components in segment i.
These indices are computed for each segment in the feeder. All load
points within a segment experience the same failure rate and down time.
In the reliability analysis program, failure rates and repair times from
field data are preferred. When this data is not available, default values are
fetched from a table in the relational database which has generic average
failure rates and repair times for each type of device.
8.2. Reliability Indices Calculation
After finding the reliability analysis sets for the segment of interest S,
we can calculate the reliability indices. First assume there is a single failure
incident.
43
FR REP + FR SOT
iNSL ,
NSAF ,
NSF
iSSL ,
SF
(8.3)
where
SOTi = switch operation time to re-supply segment S due to the failure of
segment i.
Note that the reliability analysis algorithm presented here assumes that
switch operations can always be performed faster than repairs.
The customer average interruption duration index (CAIDI) for a
segment is the same as DTs
CAIDI = DTs
(8.4)
Once the down time for each segment is calculated, and given the
number of customers attached to each segment, the total customer down
time, DTC, for a given circuit can be calculated by
DTC =
DT C
icircuit
44
(8.5)
Since the failure rate and down time is known at each segment on the
feeder, the system index SAIDI (system average interruption duration index)
is then given by
SAIDI =
DTC
Ci
(8.6)
icircuit
RTs =
DTs
FRi
(8.7)
iL
Relative _ CAIDI j =
CAIDI ckt
CAIDI j
where
CAIDIckt = average CAIDI for the circuit of interest
CAIDIj = CAIDI for segment j.
45
(8.8)
Thus
If Relative_CAIDIj = 1, then the customers in segment j have average
reliability
If Relative_CAIDIj < 1, then the reliability of the customers in
segment j is less than average
If Relative_CAIDIj > 1, then customers in segment j have reliability
better than average.
46
C1, while segments such as P52, P71, P72, P63, have reliabilities poorer
than the average value.
47
48
49
Lp611
31
50
Component Type
Substation
0.1
Disconnect switch
0.001
0.001
Supervisory switch
0.001
Cutout Switch
0.001
Fuse
0.001
Recloser
0.001
Electronic recloser
0.001
Index
51
(Hrs/Yr)
0.001
Sectionalizer
0.001
10
Breaker
0.001
11
Network protector
0.001
13
14
Reclosing device
0.001
15
0.01
16
Distribution transformer
0.01
17
Network transformer
0.01
18
Regulating transformer
0.01
19
Voltage regulator
0.01
20
0.01
21
0.01
33
3-Phase line
0.01
34
2-Phase line
0.01
35
1-phase line
0.01
37
3-Phase cable
0.01
38
2-Phase cable
0.01
39
1-Phase cable
0.01
41
0.01
42
0.01
43
0.01
44
Arrester
0.001
45
Current transformer
46
Potential transformer
47
Communication transmitter
48
Communication receiver
49
Combination switch
0.001
50
Motor operator
52
52
Ground relay
53
54
Elbow Switch
0.001
56
0.001
59
60
0.001
In Figure 10.2, an adjacent circuit C2 is added to the system. This circuit has
some remaining capacity, which means it is possible for it to supply some
power to circuit C1.
31
L68
Figure 10.2 System 2 for Case Study One: Adding an Alternative Feed
53
54
The significant drop comes from power being restored from Sub2, and p62
does not need to wait for the failing component to be completely repaired. In
this case, the down time will be the switch operation time instead of the
repair time for the failing component. The alternate source also improves the
reliability of the entire system. Table 10.2 shows a comparison of reliability
indices for System 1 and System 2.
Table 10.2 Improvement of Reliability
Reliability
System1 without
System 2 with
Percent
Indices
Alternate Feed
Alternate Feed
Improvement
SAIDI(Hrs/yr)
0.002
0.001
50%
CAIDI(Hrs/yr)
0.305
0.176
42%
If the load on circuit C2 becomes heavier, substation Sub2 might lose the
capacity to pick up the load on C1. For example, when we lengthen line L68
or add 5600kw load to it, pushing the load near to the overload point for the
line, the annual down time for segment p62 will jump back to 0.355 Hrs/yr,
and the system CAIDI will also go back to 0.305 Hrs/yr. It means the load
point of interest cannot be restored from the alternate source because system
constraints will be violated. Now we can see how the availability of alternate
feeds and the change of the system loading impact the system reliability.
Next we will illustrate how a distributed generator enhances the reliability of
the system. As it is illustrated in Figure 10.3, a distributed generator DR0 is
added near to the point where circuits C1 and C2 have their tie switch.
55
31
9
L68
56
Improvement
Without DR0
With DR0
p63
0.405
0.095
77%
p62
0.355
0.085
76%
p61
0.31
0.13
58%
p71
0.36
0.18
50%
p72
0.41
0.23
44%
p12
0.22
0.13
41%
p8
0.46
0.28
39%
p31
0.265
0.175
34%
p4
0.27
0.18
33%
p2
0.27
0.18
33%
p51
0.28
0.19
32%
p52
0.37
0.28
24%
p32
0.465
0.375
19%
P11
0.13
0.13
0%
From Table 10.3, we notice that the segments close to DR0 (etc. P62, P63)
have more improvement than those (etc. P52, P32) far from DR0. The
segment P11, which is next to source Sub1, has no improvement at all. This
is because as the distance between the segment of interest and the alternative
feed increases, the alternative source needs to supply more and more power
to its adjacent circuit in order to restore the segment of interest, and its
remaining capacity becomes less and less. When it reaches the point that the
alternative source has no spare capacity to pick up any more load, the
57
58
L_C1
Sub 2
DG
C3
L_C32
L_C31
locating the DG in Sub2 does not improve the reliability of L_C1 at all.
From Case Study One, we can predict that placing the DG in Sub2 will not
increase the reliability of the rest of the original system either (the segments
further away from the adjacent circuit have less improvement).
L_C1
Sub 2
DG
C3
L_C32
L_C31
60
increases. Table 10.4 shows the system reliability improvement after adding
the alternative source Sub2 and distributed generator DG.
Table 10.4 System Reliability Improvement for Case Study Two
Without Alternate
With Alternate
Feed
Feed and DG
SAIDI(Hrs/yr)
0.72
0.54
25%
CAIDI(Hrs/yr)
9.12
6.03
34%
System indices
Improvement
61
Sub 2
L_C1
C3
L_C32
62
0.8
0.6
0.5
0.4
0.7
0.3
0.2
0.1
Estimated Load
Down Time
63
0.4
0.2
0.1
Estimated Load
Down Time
0.3
65
66
12. Reference
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
67
[9]
68
Appendix A: Reliability Analysis Report for the System Shown in Figure 10.4
=========================================
====== Reliability Analysis Report ======
=========================================
Report created at Mon Apr 07 10:28:39 2003
==========================================
Reliability Indices Of The system Analyzed
==========================================
System Name
=============
SUB_A1_001
SAIDI
=======
0.54
CAIDI
=======
6.03
============================================
Reliability Indices Of The Circuits Analyzed
============================================
Circuit Local Name
====================
F9818_C1
F9786_C2
no local name
GLN_X
GLN_Y
========== ==========
180481
261676
180384
261614
185831
248589
SAIDI
=======
0.17
1.25
0.20
CAIDI
=======
3.49
14.52
0.07
69
============================================
Reliability Indices for all the Segments
============================================
Circuit :
F9818_C1
=================================================================================================================
Segment Local Name
GLN_X
GLN_Y
CAIDI_Rel
# of Customers
DownTime
CustomerDownTime
RestorationTime
---------Hrs
---Hrs
=================== ======== ======== =========== ================ ========== ================== ================
F9818_C1
180481
261676
0.000
0
0.000
0.000
0.000
CB1
180505
261736
2.830
0
1.235
0.000
1.153
hPF_J324
182021
262866
2.138
96
1.635
156.960
1.527
NO
181254
262970
2.138
0
1.635
0.000
1.527
hPF_J202
182326
263081
1.864
124
1.875
232.500
1.751
NO
181209
263506
1.864
0
1.875
0.000
1.751
f_25K
183922
263853
2.523
0
1.385
0.000
1.258
R3_560A_2A2D_
185601
264352
1.363
0
2.565
0.000
1.187
hPF_J784
193816
264539
1.228
0
2.845
0.000
1.317
no local name
195047
264544
1.211
0
2.885
0.000
1.335
no local name
193814
264778
1.302
0
2.685
0.000
1.242
hPF_J931
193808
265595
1.179
0
2.965
0.000
1.372
DscSw_192544:265150 192560
265168
1.179
0
2.965
0.000
1.372
DscSw_192544:265150 192539
265135
1.133
0
3.085
0.000
1.428
DscSw_192544:265150 192509
265152
1.163
0
3.005
0.000
1.391
NO
192424
265123
1.163
0
3.005
0.000
1.391
f_65K
192683
266154
0.923
94
3.785
355.790
1.590
hPF_2698
191455
265912
1.077
60
3.245
194.700
1.502
NO
190839
266018
1.077
0
3.245
0.000
1.502
hPF_1642
191254
266519
1.133
59
3.085
182.015
1.428
NO
190670
266297
1.133
70
3.085
0.000
1.428
R3_200A_2A2D_K2
f_65K
hPF_3292
NO
hPF_3199
hPF_3135
NO
hPF_3204
(NO)
iPS_J172
f_100K_K3
jCF_J716
jCF_J529
R3_200A_2A2D_R
hPF_J049
NO
f_100K_R6
jCF_J1125
jCF_J1460
hPF_J959
hPF_J773
hPF_J1590
hPF_J1334
jCF_J1445
hPF_J3371
f_80K_R5
hPF_3144
hPF_J1031
hPF_3296
NO
hPF_3189
hPF_3268
191727
193050
193356
193801
193363
193726
193558
193747
193885
193959
192414
192853
192264
191243
191212
190529
190225
188786
188992
189012
189261
189374
189938
190007
190256
188742
188500
188666
189107
188759
188460
266675
267149
268085
267769
267715
267334
267708
267334
267735
267517
266904
267895
267670
266593
266710
266865
266632
265519
265583
265619
265664
265784
265865
265885
266516
268071
268180
267806
268378
268436
268864
1.039
0.893
0.948
0.948
0.928
0.959
0.959
0.928
1.039
1.003
0.756
0.737
0.737
0.991
0.928
0.928
0.793
0.772
0.772
0.752
0.733
0.752
0.746
0.772
0.752
0.959
0.890
0.721
0.919
0.919
0.948
0
56
37
0
46
36
0
29
0
0
91
1
1
0
0
0
0
1
2
1
6
2
1
1
3
0
57
110
68
0
34
3.365
3.915
3.685
3.685
3.765
3.645
3.645
3.765
3.365
3.485
4.625
4.745
4.745
3.525
3.765
3.765
4.405
4.525
4.525
4.645
4.765
4.645
4.685
4.525
4.645
3.645
3.925
4.845
3.805
3.805
3.685
0.000
219.240
136.345
0.000
173.190
131.220
0.000
109.185
0.000
0.000
420.875
4.745
4.745
0.000
0.000
0.000
0.000
4.525
9.050
4.645
28.590
9.290
4.685
4.525
13.935
0.000
223.725
532.950
258.740
0.000
125.290
1.294
1.444
1.417
1.417
1.448
1.401
1.401
1.448
1.294
1.340
1.594
1.636
1.636
1.207
1.289
1.289
1.280
1.315
1.315
1.350
1.385
1.350
1.362
1.315
1.350
1.215
1.308
1.659
1.303
1.303
1.262
188435
268876
0.919
41
3.805
156.005
1.303
71
hPF_3223
NO
f_65K_R1
(DS)
jCF_J1524
(NO)
jCF_J1712
f_50K_R7
hPF_J050
hPF_J1640
jCF_J1144
hPF_J1626
hPF_2655
hPF_2630
hPF_J930
DscSw_191924:264803
DscSw_191924:264803
DscSw_191924:264803
jCF_J875
hPF_J774
NO
R3_200A_2A2D_L
f_65K_L1
f_10K
f_10K
jCF_J962
jCF_J1193
jCF_J173
f_8OK_K1
hPF_J325
hPF_J723
NO
188908
188819
189406
190136
190128
190796
190679
189769
190307
189497
189662
189945
191313
191372
193121
191890
191917
191942
194039
193787
195410
193643
193157
193344
193034
192954
193366
193628
185916
181266
180874
268937
268888
268063
268587
270064
269062
268962
268288
267212
267479
267049
266715
266318
266145
265824
264796
264829
264804
265657
264306
264687
263158
261239
260335
260907
261404
261853
262768
264389
262368
262515
0.969
0.969
0.609
0.457
0.450
0.457
0.457
0.578
0.523
0.928
0.959
0.928
1.014
1.133
1.039
1.039
1.026
1.003
1.246
1.283
1.283
1.179
1.104
1.039
1.054
1.118
1.133
1.133
0.860
2.138
1.991
0
0
43
102
1
0
0
0
41
0
2
2
85
38
1
0
0
0
0
0
0
0
0
3
2
1
0
1
48
75
81
3.605
3.605
5.735
7.655
7.775
7.655
7.655
6.045
6.685
3.765
3.645
3.765
3.445
3.085
3.365
3.365
3.405
3.485
2.805
2.725
2.725
2.965
3.165
3.365
3.315
3.125
3.085
3.085
4.065
1.635
1.755
0.000
0.000
246.605
780.810
7.775
0.000
0.000
0.000
274.085
0.000
7.290
7.530
292.825
117.230
3.365
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
10.095
6.630
3.125
0.000
3.085
195.120
122.625
142.155
1.234
1.234
1.521
2.030
2.062
2.030
2.030
1.526
1.688
1.289
1.248
1.289
1.594
1.428
1.557
1.557
1.576
1.613
1.298
1.261
1.261
1.277
1.341
1.401
1.386
1.346
1.329
1.329
1.652
1.527
1.639
180624
262450
1.991
1.755
0.000
1.639
72
hPF_J634
hPF_J633
NO
hPF_J635
NO
hPF_J636
hPF_J722
180875
180862
180539
180892
180414
180912
180866
262913
262895
264296
263000
263470
262981
262334
2.138
1.947
1.947
2.138
2.138
2.138
2.138
70
82
0
34
0
89
62
1.635
1.795
1.795
1.635
1.635
1.635
1.635
114.450
147.190
0.000
55.590
0.000
145.515
101.370
1.527
1.676
1.676
1.527
1.527
1.527
1.527
Circuit :
F9786_C2
=================================================================================================================
Segment Local Name
GLN_X
GLN_Y
CAIDI_Rel
# of Customers
DownTime
CustomerDownTime
RestorationTime
---------Hrs
---Hrs
=================== ======== ======== =========== ================ ========== ================== ================
F9786_C2
180384
261614
0.000
0
0.000
0.000
0.000
CB2
180321
261620
1.123
0
12.925
0.000
1.010
hPF_J1594
179665
260846
1.058
25
13.725
343.125
1.072
NO
180129
260782
1.058
0
13.725
0.000
1.072
no local name
179553
260754
1.127
0
12.881
0.000
1.006
f_100K
179396
260609
1.041
0
13.941
0.000
1.009
hPF_J743
179060
260222
0.906
61
16.021
977.281
1.159
NO
179105
258904
0.906
0
16.021
0.000
1.159
hPF_J742
178961
260125
0.913
85
15.901
1351.585
1.150
hPF_J820
179509
258517
1.028
37
14.121
522.477
1.103
NO
178402
258403
1.000
0
14.521
0.000
1.134
hPF_J819
179438
258765
1.000
0
14.521
0.000
1.134
hPF_J1426
179746
257632
1.011
56
14.361
804.216
1.122
NO
181605
258344
1.011
0
14.361
0.000
1.122
hPF_J327
179718
256941
1.064
52
13.641
709.332
1.066
NO
178606
257875
1.043
0
13.921
0.000
1.087
hPF_J328
179689
258095
1.043
73
13.921
0.000
1.087
hPF_J1226
NO
f_25K
f_80K
hPF_J1045
NO
f_65K
(NO)
f_65K
f_65K
jCF_J1749
f_65K
f_65K
hPF_J029
NO
f_65K
(DS)
Sect_L1
hPF_J1420
jCF_J1128
f_100K_L7
f_65K
Sect_L2
hPF_J3344
hPF_J3345
NO
(DS)-BA
f_65K
hPF_J288
hPF_J289
hPF_J287
NO
180497
181011
181566
184676
184907
185280
185481
186165
186672
187084
187101
188299
188718
189090
189177
189283
192270
192138
189685
189726
190089
193362
193832
194513
194499
195191
194165
196336
197790
198014
197271
256315
258103
256304
256512
255449
254494
256542
263497
256555
256696
257018
256620
256583
256631
258814
256627
256608
256341
253519
252750
253913
256429
256351
256309
256391
254911
256420
256765
257111
257133
257008
0.963
0.963
1.114
1.098
1.072
1.069
1.089
1.127
1.038
1.060
1.057
1.077
1.101
0.978
0.978
1.101
1.117
1.049
1.031
1.040
1.045
1.079
1.087
0.970
1.043
1.043
1.017
0.969
0.965
0.950
0.997
70
0
4
8
0
0
5
0
10
5
0
7
2
41
0
4
0
9
2
1
0
7
5
48
0
0
12
8
97
84
0
15.081
15.081
13.031
13.221
13.541
13.581
13.331
12.881
13.981
13.691
13.731
13.481
13.181
14.841
14.841
13.181
13.001
13.841
14.081
13.961
13.891
13.451
13.361
14.961
13.921
13.921
14.281
14.981
15.041
15.281
14.561
1055.670
0.000
52.124
105.768
0.000
0.000
66.655
0.000
139.810
68.455
0.000
94.367
26.362
608.481
0.000
52.724
0.000
124.569
28.162
13.961
0.000
94.157
66.805
718.128
0.000
0.000
171.372
119.848
1458.977
1283.604
0.000
1.178
1.178
1.016
1.022
1.046
1.049
1.034
1.006
1.074
1.056
1.059
1.043
1.025
1.159
1.159
1.025
1.016
1.081
1.100
1.091
1.084
1.043
1.044
1.169
1.087
1.087
1.116
1.158
1.175
1.194
1.137
197155
258029
0.997
14.561
0.000
1.137
74
hPF_J286
NO
f_25K
f_25K
jCF_J886
f_65K
jCF_J414
(NO)-BA
Sect_L3
hPF_J910
hPF_J611
jCF_JO30
jCF_J187
hPF_J3347
NO
jCF_J777
hPF_J3360
hPF_J1402
hPF_J1180
hPF_J1357
hPF_J1358
hPF_J1427
hPF_J1428
hPF_J1471
NO
hPF_J1472
NO
hPF_J1181
OpenSwtDev_4_1
hPF_J1179
196960
196891
195565
195355
195186
194944
194158
193825
193056
192975
193021
194250
194246
193007
193034
194287
192801
193878
194195
195667
197076
196887
195852
195805
195760
196946
195729
197864
195886
196207
194686
256944
258465
253759
257717
257919
258085
258802
259165
257105
257621
258383
260251
260455
258955
254880
254440
251459
251296
251334
251476
251187
251295
253722
253530
253327
253401
253134
254245
251498
249831
251389
0.994
0.994
0.935
1.006
1.008
0.996
1.008
1.017
1.103
1.074
1.040
1.022
1.031
1.031
0.978
0.978
1.106
0.970
0.994
1.002
0.963
1.037
0.914
1.002
1.043
1.043
1.034
1.028
1.093
1.093
1.074
0
0
14
2
0
3
1
0
0
1
4
1
1
1
48
0
1
88
74
51
78
20
86
51
21
0
0
6
0
0
0
14.601
14.601
15.531
14.431
14.401
14.581
14.401
14.281
13.161
13.521
13.961
14.201
14.081
14.081
14.841
14.841
13.121
14.961
14.601
14.481
15.081
14.001
15.881
14.481
13.921
13.921
14.041
14.121
13.281
13.281
13.521
0.000
0.000
217.434
28.862
0.000
43.743
14.401
0.000
0.000
13.521
55.844
14.201
14.081
14.081
712.368
0.000
13.121
1316.568
1080.474
738.531
1176.318
280.020
1365.766
738.531
292.341
0.000
0.000
84.726
0.000
0.000
0.000
1.141
1.141
1.190
1.125
1.125
1.134
1.125
1.116
1.028
1.056
1.091
1.109
1.100
1.100
1.159
1.159
1.025
1.169
1.141
1.131
1.178
1.094
1.241
1.131
1.087
1.087
1.097
1.103
1.037
1.037
1.056
NO
195965
249755
1.074
13.521
0.000
1.056
75
hPF_J1178
hPF_J1401
NO
OpenSwtDev_4_2
NO
hPF_J3361
NO
no local name
hPF_J3346
jCF_J1374
jCF_J1023
hPF_J1067
jCF_J585
hPF_J028
f_65K
jCF_J1293
f_80K
f_65K
jCF_J1657
R3_140A_2A2D_K
f_10K
f_65K
f_65K
f_65K
f_40K
hPF_J1554
NO
(DS)
f_40K
f_65K
hPF_J1055
f_65K
194513
194536
195332
196178
196307
194085
194051
192853
193024
191328
190568
190170
189971
188566
187845
188061
184119
183789
183408
182751
182717
182414
182478
182528
180334
182566
182353
182633
182699
182611
182591
251371
251365
250996
249793
248871
251321
249806
253908
255164
256614
256372
256657
256610
256636
256738
258484
256590
256512
256545
256315
253681
251751
251321
250604
249969
248692
249013
247634
247416
246991
246781
0.992
1.043
1.002
1.002
1.002
1.061
1.061
1.117
0.970
1.117
1.117
1.087
1.117
0.916
1.074
1.065
1.085
1.027
1.117
1.005
0.995
0.992
0.965
0.916
0.899
0.970
0.970
1.011
0.990
0.951
0.912
72
0
0
0
0
0
0
0
61
1
0
12
1
69
5
4
10
16
1
0
1
2
13
10
1
0
0
0
6
7
5
14.641
13.921
14.481
14.481
14.481
13.681
13.681
13.001
14.961
13.001
13.001
13.361
13.001
15.841
13.511
13.631
13.381
14.131
13.001
14.441
14.591
14.641
15.041
15.841
16.141
14.961
14.961
14.361
14.661
15.271
15.911
1054.152
0.000
0.000
0.000
0.000
0.000
0.000
0.000
912.621
13.001
0.000
160.332
13.001
1093.029
67.555
54.524
133.810
226.096
13.001
0.000
14.591
29.282
195.533
158.410
16.141
0.000
0.000
0.000
87.966
106.897
79.555
1.144
1.087
1.131
1.131
1.131
1.069
1.069
1.016
1.169
1.016
1.016
1.044
1.016
1.237
1.043
1.053
1.037
1.083
1.016
1.017
1.025
1.028
1.050
1.094
1.110
1.054
1.054
1.011
1.028
1.052
1.096
183088
246426
0.980
14.811
74.055
1.036
76
f_65K
Sect_K1
(DS)
f_65K
f_65K
jCF_J545
f_65K_K6
(NO)
jCF_J1141
jCF_J180
jCF_J442
f_65K_K5
f_40K
(NO)
f_40K
hPF_J985
hPF_J610
NO
f_65K_K8
f_40K
f_25K
hPF_J609
(NO)
f_65K
f_65K
hPF_J1555
f_65K
f_65K
hPF_J1070
f_65K
hPF_J1553
(DS)
183232
183202
182613
183830
185184
184413
184190
184554
183083
184196
184374
184538
190600
190791
190617
184750
186768
187257
188179
192893
193377
187738
187554
186628
185773
186979
185615
184724
184121
182545
182547
246017
245624
245625
245502
243814
237521
237422
232668
236052
239887
240293
240273
240019
234982
240058
240866
245476
244649
245916
246124
246126
245639
247735
245584
243408
243496
243030
242553
245743
248543
249756
0.980
1.014
0.992
0.960
0.993
1.005
0.872
0.872
0.866
1.005
1.005
0.884
0.792
0.792
0.797
0.983
0.994
0.994
0.954
0.935
0.926
0.970
1.014
0.941
0.965
0.957
0.948
0.938
1.014
0.995
0.986
6
0
1
6
0
1
25
0
1
1
4
10
11
0
22
5
0
0
3
0
1
20
0
12
7
2
16
32
1
2
1
14.811
14.321
14.641
15.121
14.621
14.441
16.651
16.651
16.771
14.441
14.441
16.421
18.321
18.321
18.221
14.761
14.601
14.601
15.221
15.521
15.671
14.961
14.321
15.421
15.051
15.171
15.321
15.471
14.321
14.591
14.721
88.866
0.000
14.641
90.726
0.000
14.441
416.275
0.000
16.771
14.441
57.764
164.210
201.531
0.000
400.862
73.805
0.000
0.000
45.663
0.000
15.671
299.220
0.000
185.052
105.357
30.342
245.136
495.072
14.321
29.182
14.721
1.036
1.008
1.031
1.053
1.025
1.017
1.133
1.133
1.142
1.017
1.017
1.123
1.221
1.221
1.216
1.039
1.028
1.028
1.058
1.075
1.083
1.054
1.008
1.069
1.047
1.056
1.064
1.072
1.008
1.025
1.037
183121
251251
0.968
15.001
45.003
1.056
77
f_40K
jCF_J879
jCF_J948
hPF_J825
jCF_J1247
(NO)
hPF_J1143
hPF_J1071
hPF_J1389
hPF_J1237
f_65K
f_100K
f_100K
hPF_J1225
jCF_J1285
PTS
hPF_J432
hPF_J431
jCF_J1250
f_80K_H3
f_40K
f_40K
R3_70A_2A2D_R
f_40K
f_40K_R1
jCF_J1022
jCF_J1050
jCF_J1068
hPF_J964
(NO)
f_25K
jCF_J516
184241
190695
190089
188516
187107
189473
186186
184768
183680
182780
182804
182751
182500
180295
180171
177599
178140
178392
179032
179341
179452
179589
179636
179897
179677
182023
181613
179953
180008
177518
178435
251255
248868
249115
249758
248078
252523
251300
251276
250833
252614
253846
256586
256475
256310
256331
256325
256344
256358
256353
256097
253930
251116
250890
247918
245736
245669
245614
244043
244494
246849
246905
0.958
0.960
0.960
0.952
0.960
0.968
0.952
0.952
0.952
0.989
0.975
1.050
1.006
0.963
1.117
1.127
1.067
1.096
1.117
1.007
1.004
0.977
0.922
0.888
0.803
0.798
0.798
0.798
0.788
0.922
0.914
1
2
0
6
0
0
2
4
4
2
4
12
18
78
2
0
26
16
0
10
0
10
8
6
10
1
3
2
9
0
1
15.151
15.121
15.121
15.241
15.121
15.001
15.241
15.241
15.241
14.681
14.891
13.831
14.431
15.081
13.001
12.881
13.601
13.241
13.001
14.411
14.461
14.861
15.741
16.341
18.071
18.191
18.191
18.191
18.431
15.741
15.891
15.151
30.242
0.000
91.446
0.000
0.000
30.482
60.964
60.964
29.362
59.564
165.972
259.758
1176.318
26.002
0.000
353.626
211.856
0.000
144.110
0.000
148.610
125.928
98.046
180.710
18.191
54.573
36.382
165.879
0.000
15.891
1.065
1.065
1.065
1.073
1.065
1.056
1.073
1.073
1.073
1.034
1.042
1.065
1.101
1.178
1.016
1.006
1.062
1.034
1.016
1.097
1.100
1.124
1.173
1.207
1.288
1.296
1.296
1.296
1.314
1.173
1.181
180165
247327
0.915
15.861
63.444
1.182
78
jCF_J904
hPF_J1425
f_25K
f_65K
hPF_J1593
179289
179744
179524
179501
179718
255367
257875
258788
259522
261024
0.999
1.019
1.114
1.101
1.052
3
57
1
6
17
14.531
14.241
13.031
13.181
13.805
43.593
811.737
13.031
79.086
234.685
1.107
1.112
1.016
1.025
1.078
Circuit :
no local name
=================================================================================================================
Segment Local Name
GLN_X
GLN_Y
CAIDI_Rel
# of Customers
DownTime
CustomerDownTime
RestorationTime
---------Hrs
---Hrs
=================== ======== ======== =========== ================ ========== ================== ================
no local name
185831
248589
0.000
0
0.000
0.000
0.000
no local name
186059
248471
0.667
1
0.100
0.100
5.000
no local name
185811
247887
0.667
0
0.100
0.000
5.000
79
Vita
Dan Zhu was born on September 4, 1977 in Jiangmen, Guangdong
Province, China. She received her BSEE degrees from South China Normal
University, Guangzhou, Guangdong Province, China, in June 2000.
Before she came to Virginia Tech to pursue her master degree, she was
employed as a Communication Engineer by Electric Power Bureau of
Jiangmen, Guangdong, China.
80