Janitza Manual Prophi 7 GB
Janitza Manual Prophi 7 GB
Manual
Version 2.0 - E
po
w
er
fa
n
ct
ex
or
t
co
ge
n
n
tr
er
ol
at
le
io
r
n
www.janitza.com
Controller
Power Factor
Prophi
7-1
Prophi7-1 (/S485)
Prophi 7
AUTO MODE
------------------
AUTO-MODE
223.0 V
I
268 A
-----------------Q
107 kvar
U
------------------
HARMONICS
[V]
DISPLAY-MODE
BARGRAPH-MODE
2.0%
1.0%
0%
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
UNDERCOMPENSATED
-----------------Q-Diff=
ERROR MESSAGE
82kvar
1 2 3 4 5 6 7 8 9 10 11 12
CAUTIONS:
Prophi 7
2
1. High voltage !
2. The device may only be used indoor !
3. Make sure that the discharge time set in controller
matches capacitor discharge time !
Prophi 7
CONTENTS
Section 1
Section 2
2.1
2.2
2.3
Current measurement
Programming of phase-correction
Error messages: Alarm- / Message relay
Section 3
Operating modes
Section 4
Section 5
Programming
5.1
Automatic initialization
5.2
Manual programming
5.3
Programming lock
10
11
14
Section 6
15
Section 7
16
Section 8
Expert mode
8.1
Expert mode 1
8.2
Expert mode 2
17
Section 9
Control principle
20
Section 10
Display editor
21
Section 11
Initial operation
21
Section 12
21
Section 13
22
Annex:
Annex 1
Annex 2
Annex 3
Troubleshouting
Technical data
Table of control series
Description of control-series editor
Default settings
24
25
26
28
29
31
32
Annex 4
Application
Application
Application
19
27
30
-2-
Prophi 7
3
Prophi 7
Section1 General
The power factor controller Prophi7-1 (single phase) enlarges the product range of power
factor control devices by a useful combination of the features known from the well-proven
series with the advantages of a better visualization.
The big graphic display enables a user-friendly programming and gives further benefits
such as larger display in the Display-mode and the display of various parameters in
bargraph-mode.
With the additional ESCAPE-button a backward navigation in all menus is possible.
The HELP-button
(German/English).
allows
an
interactive
help
in
the
particular
menu
item
The controller is characterized by its user friendly operating interface via menu driven
plain text display. The display of several grid parameters, the storage of different values
as well as the possibility of test run allow a simple error analysis and system monitoring.
If required, an automatic initialization is possible which reduces the start-up operation to
a minimum.
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
additional external input (function programmable), e.g. for 2nd parameter set
additional freely programmable alarm relay, e.g. for fan, status notification
serial interface RS485, for controller coupling, integration into networks
visualization, programming and data processing via PC by enclosed software
-3-
Prophi 7
4
Prophi 7
The controller is supplied as standard for an operating voltage of 110...230 VAC (+-15%),
a measuring voltage of 30...440 V~ (L-N) resp. 50...760V~(L-L) and a measuring current
of 5A or 1A. A voltage converter is required for different operating voltages.
Caution!
Voltages which exceed the specified voltage range can damage the
device !
Front view
Operating mode:
- Automatic
- Program.
- Manual oper.
- Service
- Expert Mode
- Osci - Mode
- Display Editor
Increase
selected
parameter
HELP
opens
Help pages
HELP
ESC
ENTER/ OK
Confirmation
storage of
values
Reduce
selected
parameter
Escape
previous
page/value
in the display
Rear view
L1
(L3)
supply voltage
N
(L2)
meas. voltage
meas. current
Type: Prophi 7-1
meas. voltage:30-440V(L-N),50-760V(L-L)
supply voltage: 110...230VAC 50/60Hz
Ser.No.:
meas.
voltage
Vm
supplyvoltage
Vb
MADE IN GERMANY
meas. current
Im (5A/1A)
k
L1 (R)
L2 (S)
T 6,3A
T 2A
T 2A
L3 (T)
N
PE
L1
1. capacitorbranch
P1
P2
K1
9 10 11 12
13
alarmrelay
capacitorcontactors 1-6
capacitorcontactors 7-12
alarmrelay
P1 K1 K2 K3 K4 K5 K6
K13
-4-
Prophi 7
5
Prophi 7
Connection plan
Power feed
Load side
supply
voltage
Vb
meas. meas.current
voltage Im (5A/1A)
Vm
k
l
1. capacitor
branch
L1 (R)
L2 (S)
T 6,3A
T 2A
T 2A
L3 (T)
N
PE
(L)
(N)
Ub
(L3) (L2)
L1
N
Um
Im
l
P1
P2
K1
power factor
controller
alarm
relay
capacitor
contactors 1-6
9 10 11 12
capacitor
contactors 7-12
-5-
Prophi 7
6
Prophi 7
Feed 2
Example:
C.converter 1: 1000/5A
C.converter 2: 1000/5A
Sum-current converter: 5A+5A/5A
Current
measurement
Prophi 7-1
meas. voltage
L2-L3
Meas.current
k
L1 (R)
Example :
L2 (S)
T 2A
T 2A
L3 (T)
N
PE
Meas.current: L1
Meas. voltage: L3-L2
Phase U/I [ 90]
(L)
(N)
Ub
L3
Um
L2
Im
using
meas. current
meas. voltage
phase-angle
Preset:
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L2
L3
L3
L3
L1
L1
L2
L2
L3
L3
0
30
60
90
120
150
180
210
240
270
300
330
(k<->l)
(k<->l)
(k<->l)
(k<->l)
(k<->l)
N
L2
N
L2
N
L1
N
L2
N
L3
N
L1
-6-
Prophi 7
7
Prophi 7
13th step
OFF
ERROR
ERROR inverse
FAN
Supply
Undercurrent
Harmonics
Overcompensated
Undercompensated
Warning switch. oper.
Modbus-Error
MMI-Error
C-defect
OFF
ERROR
ERROR inverse
FAN
Supply
Undercurrent
Harmonics
Overcompensated
Undercompensated
Warning switch. oper.
Modbus-Error
MMI-Error
C-defect
Fixed step OUT
Remark
Adjustment and masking of all ERRORS is possible in the ExpertMode 2. The adjustment is valid for
both relays.
AUTO MODE
------------------
further messages
compare last cover
page !
Connecting-in
Connecting-out
Active capacitor
branches
Supply display
(for 4-quadrant
operation)
Control direction
(here connected-in)
223.0 V
I
268 A
-----------------Q
107 kvar
U
------------------
Harmonics as bar-diagram
HARMONICS
[V]
2.0%
1.0%
0%
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
By activating the ENTER-button the selected display can be stored as standard main display.
Prophi 7
8
Prophi 7
Repeated pressing of the "Operating Mode key takes the user to the various menus:
Auto operation
Programming
Manual operat.
Service
Expert Mode 1
Expert Mode 2
Display-Editor
INTERFACE
back to 1
Display
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
1
2
3
4
5
6
7
8
9
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
LINE VOLTAGE
in V
/%
APPARENT CURRENT
in A
/%
REACTIVE POWER
in kvar /%
ACTIVE POWER
in kW
/%
APPARENT POWER
in kVA /%
DIFF. kVAR TO TARGET COS
FREQUENCY
in Hz
TEMPERATURE
in C / F
HARMONICS
V / %, I / %
Selection via arrow-keys
10 HARMONICS THD-V/%, THD-I/%
11 Compensation power in kvar
12 ENERGY
(kWh, kvarh, consumption, delivery)
reset in: service / max.value reset
13 DATE - TIME
Software version
Return to: 1
AUTO-MODE
-----------------3 REACTIVE POWER
118 kvar
AUTO-MODE
-----------------10 HARMONICS THD rel.
V
1.7%
0.8%
The power value specifies the total power (3-phase) assuming symmetrical load. If no
key is pressed for 120 seconds, the display automatically returns to the operating status!
Under 13 Date-Time the date format 12h/24h setting can be changed by the arrow
buttons (only version /S).
-8-
Prophi 7
9
Prophi 7
Section 5: Programming
Pressing the
The display always shows the parameter and the set value. Values that can be edited are
generally put into square brackets [ ].
The values are changed by pressing the keys:
Subsequent pressing of the
parameter.
ESC
key stores the value and takes the user to the next
AUTO-INIT
------------------
AUTO-INIT
------------------
AUTO-INIT
------------------
1 CURRENT TRANSF.
4 POWER 1.STAGE
START TEST
[ UNKNOWN ]
[25].00 kvar
3 test-runs will be performed during which all stages are being switched on and off. All
necessary parameters are collected, evaluated and stored. Under certain circumstances
3 additional test-runs may be required for a proper initialization.
After successful finalization of AUTO-INIT the controller will switch to normal operation.
In case of recognition of any discrepancies (plausibility) or of inaccurate connection, the
detected error will be displayed in plain text after finalization of AUTO-INIT and can be
eliminated. (see possible error messages at the end of the manual). AUTO-INIT may be
repeated then.
-9-
Prophi 7
10
Prophi 7
- 10 -
Prophi 7
11
Prophi 7
8 MEASURING VOLTAGE
[ 30 ... 760]V~
Programming the measuring voltage of the system.
The values programmed here always refer to the voltage at the clamps of the
device !
The voltage is selected via the / keys. Save and continue with ENTER.
9 V - CONVERTER RATIO
[ NO / 230V ... 380kV ]
When a measuring-voltage converter (e.g. for HV-measurement) is used, its
conversion ratio should be programmed here.
(Input of prim.voltage is here, sec. voltage is automatically from item 8)
Selection via the / keys. Save and continue with ENTER.
High voltage
Meas. Current
Im (X/1A)
Low voltage
20 kV / 400 V
Meas.
Voltage
Um
Operating
voltage
Ub
L1 (R)
L1 (R)
L2 (S)
L2 (S)
L3 (T)
L3 (T)
N
PE
20000
Im
Prophi 7-1
T 2A
T 2A
100
Um
Ub
10 CONNECTING TIME
This refers to the time between connecting the capacitors to increase the
momentary network capacitance. It should be noted that in practical operation the
real connection time is affected by the discharge time (locking time).
Setting range:
1 sec. ... 20 min. (long time for HV- networks)
Default setting:
40 sec.
Selection is performed via the / keys. Continue with ENTER
11 DISCONNECTING TIME
This refers to the time between disconnecting the capacitors to reduce the
momentary network capacitance.
Setting range:
1 sec. ... 20 min. (long time for HV- networks)
Default setting:
40 sec.
Selection is performed via the / keys. Continue with ENTER
12 DISCHARGE TIME
This is the time for which an individual output is blocked between connecting and
disconnecting. This blocking time has priority over connecting and disconnecting
times. It depends on the capacitor discharge rating and thus is specified by the
compensation network. The discharge time of a conventional network without
additional fast-discharge resistors or chokes should be set to no less than 40
seconds. For setting of a second discharge time compare 'Expert Mode1' point 12
Setting range:
1 sec ...20 min. Default setting: 60 sec.
Selection is performed via the / keys. Continue with ENTER
- 11 -
Prophi 7
12
Prophi 7
13 ALARM TEMP
[ 40...85]C
13th step
OFF
ERROR
ERROR inverse
FAN
5
6
7
SUPPLY
UNDERCURRENT
HARMONICS
8
9
10
11
12
13
OVERCOMPENSATED
UNDERCOMPENSATED
Warning switch. oper. Exceeding of set switching operations value
MODBUS-ERROR
only version -/S485
MMI-ERROR
only version -/S485
C-defect
only version -/S485
- 12 -
Prophi 7
13
Prophi 7
15 FAN TEMP *
[15...70]C
Input of the switching threshold for the fan. *Only active if option 'Fan' is selected
16 HARMONICS (harmonic limit)
[7] %
(OFF or 0.5 - 25.5)%
A limit for the total harmonic distortion THD-V (in%) can be entered here. When
this threshold is exceeded, a message is given. THD-V is the ratio of the
geometric sum of the harmonics to the fundamental.
17 HARMONICS
selection of harmonics for bar graph-display in Display-Mode
[3. 5. 7. - 19.]
Odd up to 19th
(factory setting)
[3. 5. 7. - 33.]
Odd up to 33th
[2. 3. 4. - 17.]
Even and odd up to 17th
18 CONTRAST
Adjustment of optimal contrast for the display possible
19 - 28 Programming of all values of the 2nd parameter set
*only active if under INTERFACE: 3 EXT. INPUT the function
2nd parameter set is activated
From factory side the values of the 2nd parameter are set equal to the ones of
the normal parameters. By changing of particular parameters for example the
target cos-phi can be changed here. Other cases of application are transformer
switch over or change of switching times.
By applying a control voltage (110230V) at the external input the 2nd
parameter set is activated with following indicated values:
19. I-transformer prim, 20. I-transformer sec., 21. End-stopp, 22. Control
series, 23. Control principle, 24. Output 1st step, 25. Target cos-phi, 26. Switch
on time, 27. Switch off time, 28. Discharge time.
Marking of the values of the 2nd parameter set and the display of activation
appears in the display with this symbol
BASIC SETTINGS: [ NO ]
( YES / NO )
When the selection is made with YES and confirmed with ENTER, all parameters
are reset to the basic setting made by the PFC-system manufacturer.
(Optimal network values when the controller was supplied with a complete PFCsystem). If the controller is supplied from the works, this point corresponds to
the default setting.
CAUTION: All user settings are lost!
- 13 -
Prophi 7
14
Prophi 7
Section 6
MANUAL MODE
------------------
MANUAL MODE
------------------
STOP
CAP ON
CAP OFF
1.000
1 2 3 4 5 6 7 8 9 10 11 12
device-Stop
0.871 CAP
1 2 3 4 5 6 7 8 9 10 11 12
connection of steps
0.871 CAP
1 2 3 4 5 6 7 8 9 10 11 12
disconnection of steps
Pressing ENTER takes the user to the menu point "Programming of fixed stages.
Normally, all stages are programmed for automatic operation (default setting).
MANUAL MODE
------------------
MANUAL MODE
------------------
MANUAL MODE
------------------
C1
C1
C1
[AUTO]
1 2 3 4 5 6 7 8 9 10 11 12
[ FIXED]
1 2 3 4 5 6 7 8 9 10 11 12
[OFF]
1 2 3 4 5 6 7 8 9 10 11 12
In special cases, all controller outputs (C1 - C12) may be permanently defined in
succession (continued switching via ENTER) for the following statuses:
AUTO: Automatic (normal) operation
The relevant output is marked by a capacitor symbol.
FIXED: The output is continuously connected, e.g. for fixed PFC. The output is
marked by an underlined capacitor symbol.
OFF: The output is continuously disconnected - e.g. for temporarily disconnecting a
defective capacitor. The capacitor symbol for this output is faded out. Minus ( - )
appears.
The active stage is blinking. The required status is set via /. By pressing ENTER, the
user saves this step and moves to the next stage.
The programmed statuses for the outputs also remain visible on the display in automatic
operation.
After the required settings have been made, pressing the "Operating Mode key takes the
user to the next menu ("Service) or further to "Automatic Operation.
- 14 -
Prophi 7
15
Prophi 7
Section 7
Service menu
Display
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
+/ENTER
+/ENTER
ENTER
ENTER
ENTER
ENTER
1
2
3
4
5
6
7
8
min/max. VOLTAGE
in V
max. REACTIVE POWER
in kvar
max. ACTIVE POWER
in kW
max. APPARENT POWER
in kVA
max. TEMPERATURE
in C / F
max. THD - V / THD - I
in %
RESET the maximum and energy values
SWITCHING OPERATIONS
C [1] - ...
to C [12]
9 OPERATING TIME
C [1] - ... in h
to C [12]
10 ERROR MEMORY E [1] - ....
in plaintext
11 ERROR MEMORY RESET
12 TEST RUN
13 C-POWER (only after a test-run or AUTO-INIT)
Back to 1
TEST-RUN
This menu point allows the user to check the settings of the PFC controller. After activation
of the test run, the controller switches each stage ON and OFF successively and calculates
the output of the capacitors connected (this procedure is done three times to eliminate
possible errors). The values calculated are stored and can be retrieved in the following
menu item (C-POWER). At the same time, a plausibility check is conducted with the values
programmed.
Discrepancies are displayed in plain text afterwards. The following errors can be
displayed:
-
Note: The results displayed are messages intended to help the user trace the cause of the
error. Final evaluation remains the responsibility of the user. Under complicated (high load
fluctuations) grid conditions, 100% error recognition cannot be guaranteed.
- 15 -
Prophi 7
16
Prophi 7
Section 8.1
Expert mode 1
The expert mode is meant for the adjustment of values which normally should not be
changed. As a protection against mal-operation this level has an access code.
Factory setting: 6343
The password can be changed in point 22 of expert mode 1.
1 PASSWORD ????
[NO]
(NO / YES)
Prophi 7
17
Prophi 7
13 PHASE I
14 PHASE V
Phase correction between voltage and current in the measuring system. (refer p.6)
15 C-TEST
[YES]
( YES / NO)
The power of the particular capacitor stage is calculated during each switching
operation and compared with the stage output of the capacitor. If the result varies
from the nominal value, an error message is generated. This test can be stopped
here.
16 C-FAULT
[40] %
(10...75 %)
The deviation from the rated value of the capacitor, for which a fault message is
generated, can be specified here (see point 14)
17 TEST ATTEMPTS
[6]
( 2...9)
When at least this number of successive measurements has resulted in a fault in the
capacitor power, a C-fault message is output.
18 OUTPUT 1. STEP
[0...255]
(0...2550; 0...25500)
The range for entering the stage output can be increased to [0...25500] here
(e.g. for high-voltage measurement)
19 CONTROL [3] PHASE
(3/1)
The measuring system of the controller is based on a single phase measurement.
3-phase CAP (factory setting): The measurement is converted and all outputs are
displayed 3-phase (presuming symmetry in the grid).
1-phase CAP: Display and control is only performed for the measured 1-phase value
(for example 1-phase compensation in non-symmetric grids)
3-phase IND: set-up of an inductive compensation with reactors possible (3- phase)
1-phase IND: set-up of an inductive compensation 1-phase
3-phase C/I : Mixed compensation possible (CAP/IND)
1-phase C/I : (Realization according separate application solution)
20 SUPPLY Setting of the controller in case supply of electric power takes place
(1) --- (no reaction) factory setting
(2) switch off stepwise
(3) total switch off
21 DISPLAY [cos j]
(cos j / tan j)
22 PASSWORD ?
The password for ExpertMode can be changed here. All combinations of letters
and figures are possible
27 ERROR - DISPLAY BACKLIGHT
If an error or warning message appears in the display -the backlight can change
to red light for better attention. Here a modification is possible.
(OFF/ white/ red/ pink)
Prophi 7
18
Prophi 7
[10] min.
(1...255min.)
Time after which the alarm relay will respond
3 UNDERVOLTAGE
[50] %
(20 ...100 %)
meas. voltage below this threshold will switch OFF all
stages at the same time
4 OVERVOLTAGE
[130] %
(105 ...140 %)
meas. voltage above this threshold will switch OFF
the stages step by step
C1
to
C12
RESET [NO]
(YES/NO)
RESET [NO]
(YES/NO)
Prophi 7
19
Prophi 7
Section 9
Control principle
- 19 -
Prophi 7
20
Prophi 7
Section 10
Display-Editor
Grid voltage
Apparent current
Reactive power
Active power
Apparent power
Difference reactive power
Frequency
Temperature
THD-V
THD-I
Cos Phi
Tan Phi
--- (no display)
DISPLAY-EDITOR
-----------------1.DISPLAY [ 1]
[ LINE VOLTAGE ]
223.0 V
I
268 A
-----------------Q
107 kvar
U
------------------
Selected parameters:
1. Grid voltage
2. Apparent current
3. Reactive power
Note:
Even in Display-Mode the device will continue to operate as P.F.controller in the
background with all functions programmed!
Section 11
Initial operation
The controller must have been installed before being set up and operated.
All network-specific parameters are fully programmed as described in section 5
(Programming) by being entered in sequence and stored. The controller is then set to
automatic operation with the operating mode key. It is now ready for operation.
Section 12 Maintenance and warranty
The Prophi7-1 should need no maintenance if the operating conditions are observed.
However, it is recommended that a functional check of the controller be performed in
conjunction with the regular checking of the capacitor bank. In the event of any
interventions in the controller during the warranty period, all warranty claims lapse.
- 20 -
Prophi 7
21
Prophi 7
2 FAN TEMPERATURE
Input of switching threshold, when message relay = FAN has been selected.
3
EXTERNAL INPUT
The function of the external input (110..230 V) can be selected here: (Not active
if message relay is programmed as External or Remote control.
[0] - OFF
[1] - 2nd parameter set
Activation of the input in this operation mode releases the 2nd parameter
set featuring the following settings: 19/20 I-transformer; 21 End stop;
22 Control series; 23 Control principle; 24 Output 1st step;
25 Target cos-phi; 26-28 Switching times
[2] - EXTERNAL ERROR
In this operation mode the activation of the input causes a controlled
switch off of all steps (remote switch off)
[3] - Q-OFFSET By activating of the input in this operation mode an additional
capacitive output is switched on independent from target cos-phi and
controlling (value in offset-power programmable).
[4] - Coupling operation parallel Coupling operation of two systems, the input
receives a signal of the coupling switch between the systems, the systems
symmetrically (parallel) switch on the steps.
[5] - Coupling operation serial Coupling operation of two systems, the input
receives the signal of the coupling switch between the systems, the
systems sequentially switch in the steps (first system 1, then system 2)
[6] [INPUT FIXED STEP]
MASTER MMI
EXTERNAL
SLAVE HYBRID
SLAVE MODE
MASTER MODE
Prophi 7
22
Prophi 7
Depending on the selected protocol the following settings may be partially deactivated:
11 BAUDRATE
12 ADRESS
[1]
(1...255)
13 Number MMI
[1]
(1...9)
(1...4)
[10] sec.
Vb
On
L1
N
(L3) (L2)
SERVICE
Im
INTERFACE RS 485
1 2
Switch for
terminating resistor
Vm
Gnd B
A PE
- 22 -
Prophi 7
23
Prophi 7
Annex 1: Troubleshooting
Fault
Check / Solution
Display:"UNDER CURRENT
Display: "OVERCURRENT
Alarm relay: after 10 min.
Display: "UNDERCOMPENSATED
Alarm relay: after 10 min.
Display: "OVERCOMPENSATED
Alarm relay: after 10 min.
See above
Display: "OVERTEMPERATURE
Alarm relay: after 10 min.
No operating voltage
Note: No display
- 23 -
Prophi 7
24
Prophi 7
Annex 2:
Technical data
Type series
Outputs
Languages
Switching power of relay outputs
Number of active outputs
Operation and display
Prophi7-1
12 (13)
D / E / ES / RU / NL / CZ / PL / F / PT / TR
250 VAC, 1000 W
Programmable
Illuminated graphic display, 128x64dot
20
1
Sequential connection, loop connection or
self-optimized switching response
Four-quadrant operation
YES
110...230 VAC +/-15%, 50 / 60Hz
30...440V~ (L-N) resp. 50...760V~ (L-L)
X : 5 / 1A selectable
< 5 VA
20 mA
0.1 inductive to 0.1 capacitive adjustable
Connecting time
Disconnecting time
Discharge time
Programmable
Standard
Standard
Prophi 7
25
Prophi 7
Control series
Loop connection
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1:1:1:1:1:1:1:1:1:1:1:1
1:2:2:2:2:2:2:2:2:2:2:2
1:2:3:3:3:3:3:3:3:3:3:3
1:2:3:4:4:4:4:4:4:4:4:4
1:2:4:4:4:4:4:4:4:4:4:4
1:2:3:6:6:6:6:6:6:6:6:6
1:2:4:8:8:8:8:8:8:8:8:8
1:1:1:1:2:2:2:2:2:2:2:2
1:1:1:1:1:6:6:6:6:6:6:6
1:1:2:2:2:2:2:2:2:2:2:2
1:1:2:2:2:4:4:4:4:4:4:4
1:1:2:2:4:4:4:4:4:4:4:4
1:1:1:2:2:2:2:2:2:2:2:2
1:1:2:3:3:3:3:3:3:3:3:3
1:1:2:4:4:4:4:4:4:4:4:4
1:1:2:4:8:8:8:8:8:8:8:8
1 : 2 : 2 : 3: 3 : 3 : 3 : 3 : 3 : 3 : 3 : 3
1:2:3:4:4:8:8:8:8:8:8:8
1:2:2:4:4:4:4:4:4:4:4:4
1:2:2:2:4:4:4:4:4:4:4:4
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
"E"
Control-series editor
Possible
Automatic
Programming
Control series
editor
Manual operation
Service
In the control-series editor, all stages can be set in succession to the desired value with
the selection keys / . The next stage in each case is reached by pressing ENTER.
In the control series editor, the various steps may be programmed up to a rating of 30 (!).
The rating >9 is indicated in the display as follows:
10=A, 11=B, 12=C, 13=D, 14=E, 15=F, 16=G .... 30=U
ALL control series can be generated (even downwards). The customer will decide
whether the generated control series is of sense.
The maximum number of stages can be limited by a programmed END STOPP < 12.
- 25 -
Prophi 7
26
Prophi 7
Parameter
Default setting
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
LANGUAGE
I CONVERTER prim.
I CONVERTER sec.
END STOPP
CONTROL SERIES
CONTROL PRINCIPLE
POWER 1. STAGE
TARGET COS-PHI
MEASURING VOLTAGE
V- CONVERTER RATIO
SWITCH- IN TIME
SWITCH- OFF TIME
DISCHARGE TIME
ALARM TEMP.
MESSAGE RELAY
TEMP. FAN ON
HARMONICS THD-V
HARMONICS bar diagram
CONTRAST
ENGLISH
1000 A
5 A
12
1
INTELLIGENT
25.00 kvar
0.98 IND
230 V L-N
- NO 40 sec.
40 sec.
60 sec.
55 C
FAN
30 C
7,0 %
3. 5. 7. - 33.
7
Capacitor stages
Password Expert-mode1/2
Integration time
Trigger value
AUTO
6343
1 sec.
66%
Max.simult.switch.power
Operating lock
Switch.operations warning
Fast discharge
Phase shift U/I
C - Test
C - Fail
Test Attempts
Power 1. stage
Control
Display power-factor
Protocol*
Baudrate*
Adress*
Device-type*
Number of BR7000-I*
ASCII interval*
4 x smallest stage
- NO 50,000
- NO 0
- YES 40 %
6
0...255 kvar
3 - phase
Cos Phi
Modbus-RTU
9600/None
1
MMI7000
1
10 sec.
- 26 -
Prophi 7
27
Prophi 7
Feed 1
Feed 2
Transformer 1
Transformer 2
Ct1
X / 5A
Ct2
X / 5A
Coupler
Consumer (1)
Consumer (2)
LAN-cable (CAT5/CAT6)
Interface
(RJ45)
Interface
(RJ45)
Prophi7-1/S485
(Master)
Prophi7-1/S485
(Slave)
Capacitor system 1
Capacitor system 2
Application example:
Two separate systems operate at two transformers; a coupling via a coupling switch exists between
both systems
1) Coupling is open: Both systems work completely independent.
2) Coupling is closed: Due to controller coupling, the two PFC systems are operated in PARALLEL
(symmetrically) or in SERIES (as extension).
Undesired interactions of the compensation system are avoided during operation at a common
bus bar (oscillation).
Description:
During controller coupling each controller measures its respective current. The measuring values of
reactive power difference are transmitted via interface to the Master. The Master controls and
synchronizes the switching of both controllers. No additional installation required.
Installation:
The coupling of the 2 PF-controllers Prophi7-1/S485 is done via interface (RJ45 plug) using a standard
LAN-cable CAT5 . The 110230~ signal Coupling switch closed has to be conducted to the potential
free external input of a controller ( Master).
Programming:
1. Master: Menu INTERFACE /
3 EXTERNAL INPUT:
COUPLING PAR. (systems will switching symmetrically) OR
COUPLING SER. (systems will switching one after another)
10 PROTOCOL: COUPLING MODE
11 BAUDRATE: free (the same at each device)
2. Controller of 2nd system: Menu INTERFACE/
10 PROTOCOL: MODBUS RTU; 11 BAUDRATE: equal to Master-controller; 12 ADRESS: 1
No additional settings are required.
Prophi 7
28
- 27 -
Prophi 7
up to 2 Prophi 7-1/S485
(for conventional steps)
Menu: PROGRAMMING
Menu: INTERFACE
2 CONTROL-MODE: 7...14
LAN-Cable (CAT5/CAT6)
Adress:[2]
LAN-Cable (CAT5/CAT6)
Adapter
CV-1xRJ45-BR6000
Prophi 7-1/TH
Prophi 7-1/S485
Prophi 7-1/S485
Variant 2:
Extended systems with up to 48 outputs by cascading of 2...4 pcs. Prophi 7-1/S485
(all controllers will switch symmetrically)
Programming in menu INTERFACE
10 PROTOCOL:
11 BAUDRATE:
12 ADRESS:
15 NUMBER:
[Master Mode]
[38400/NONE]
[Slave Mode]
[38400/NONE]
[1]
[2] (1...4)
LAN-Cable (CAT5/CAT6)
[Slave Mode]
[38400/NONE]
[2]
LAN-Cable (CAT5/CAT6)
Adapter
CV-1xRJ45-BR6000
Prophi7-1/S485
Prophi7-1/S485
Prophi7-1/S485
- 28 -
Prophi 7
29
Prophi 7
Application:
Application
For permanent current monitoring inside the compensation system the MMI6000 is recommended as
an accessory. This measuring device is able to determine the sum current of the complete PFC system
as well as the current of single capacitor branches.
By monitoring the current of the installed capacitors, extraordinary grid conditions (e.g. harmonic
currents which may cause an overload of capacitors) can be identified. In such a case, the power factor
controller switches off the relevant compensation stages as long as the extraordinary situation
continues. Monitoring of the capacitor current also means monitoring of the capacitor condition
(damages, aging ) and thus gives the opportunity to avoid consequential damages.
The MMI6000 will improve the reliability and safety of a PFC-system.
Method of operation:
The MMI6000 measures the sum current inside the PFC system. For this a current transformer has to be
installed at the power input of the compensation system. During each switching operation, the actual
current change is measured and compared to the rated current of the switched capacitor(s). In
between the switching operations the current of the complete system is monitored.
In case the current of a step is too high (default +50%), this step is switched off. The controllers display
shows an inverted capacitor symbol. The current is further on checked periodically is the rated
current reached again, the step is reactivated.
Is the sum current of the complete PFC system too high, stages are switched off one after another and
alarm relay is set. Periodical measurements are performed to check whether the current reaches the
nominal value again. If so, the step is reactivated.
Settings MMI6000:
Settings Prophi7-1:
Menu: INTERFACE
- 10 Protocol: MASTER-MMI
- 11 Baudrate
- 13 Numbers of MMI
Expert-mode 1:
- 15 C-Test: YES
- 16 C-Error (+/- 50%)
(setting of switching threshold)
MMI6000
L1
L2
L3
N
M M I - 6000
Program
Multi-Measuring
Interface
Enter
CAUTION:
- 29 -
Prophi 7
30
Prophi 7
AUTO MODE
-----------------cos
0.987 IND
A F
1 2 3 4 5 6 7 8 9 10 11 12
U H OC UC ME
A M
IND
CAP
MASTER
SLAVE
Display UNDERCURRENT
HARMONICS
OC
OVERCOMPENSATED
UC
UNDERCOMPENSATED
SWITCHING OPERATIONS (number of programmed switch. oper. exceeded)
ME
MODBUS-ERROR or MMI-ERROR
C-DEFECT
13. step (programming only possible for the alarm-relay)
- 30 -
Prophi 7
31
Prophi 7
AUTO MODE
---------------
PROGRAMMING
AUTO-INIT
[ NO ]
1 2 3 4 5 6 7 8 9 10 11 12
LANGUAGE
[ ENGLISH ]
1 CURRENT TRANSF.
[ KNOWN ]
2 APPARENT CURRENT
200.0 A
I-CT PRIMARY
[ 1000 ] A / X A
I-CT PRIMARY
[ 1000 ] A / X
3 REACTIVE POWER
88.88 kvar
I-CT SECONDARY
1000 A / [5] A
16
HARMONICS
THD-V [ 7 ] %
I-CT SECONDARY
ACTIVE POWER
88.88 kW
17
HARMONICS
[ 3. 5. 7. - 19.]
POWER 1. STAGE
[ 25 ].00 kvar
5 APPARENT POWER
88.88 kVA
2 19
I-CT PRIMARY
[ 1000 ] A / X
FREQUENCY
50.0 Hz
POWER 1. STAGE
[ 25 ]. 00 kvar
2 20
I-CT SECONDARY
1000 A / [5] A
TEMPERATURE
25 C
TARGET
cos Phi [ 0.98 IND ]
2 21
HARMONICS [ 3. ]
V: 0.5% - I: 0.1%
MEAS. VOLTAGE
[ 230 ] V - L/N
10 HARMONICS THD
V: 0.5% I: 0.3%
V - CT RATIO
[ NO ]
11 SYSTEM-POWER
88.88 kvar
10
SWITCH-IN TIME
[ 40 ] sec.
2 24
POWER 1.STAGE
[ 25 ]. 00 kvar
12
11 SWITCH-OFF TIME
[ 40 ] sec.
2 25
TARGET
cos Phi [ 0.98 IND ]
13 DATE - TIME
06.12.2013 - 15:17:40
12
DISCHARGE TIME
[ 60 ] sec.
2 26 SWITCH-IN TIME
[ 40 ] sec.
14 SOFTWAREVERSION
13
ALARM TEMP.
[ 55 C ]
2 27 SWITCH-OFF TIME
[ 40 ] sec.
14
ALARM RELAY
[ ERROR inverse]
2 28 DISCHARGE TIME
[ 60 ] sec.
15
FAN TEMP.
[ 30 C ]
LINE VOLTAGE
230.0 V-L/N
ENERGY
88.88 kWh ( + )
BACK TO 1
After 60 sec. without pressing
any button, automatic change
to auto-mode
Settings shown with grey background
colour are active only in case
of certain other settings.
If not needed they are not displayed.
Prophi 7
32
18
CONTRAST
*****[7]*****
BASIC SETTINGS
RESET - NO BACK
- 31 -
1000 / [5] A
TEST 1...3
(automatic TEST RUN)
Changing
of values
by buttons:
Prophi 7
MANUAL MODE
SERVICE
EXPERT.MODE 1
1 PASSWORD ????
[ 6343 ]
KVAR-RATIO C1 [ 1 ]
11 2 2 2 2 2 2 2 2 2 2
STOPP C
1 min/max VOLTAGE
0 / 250.0 V
1.00 IND
KVAR-RATIO C2 [ 1 ]
11 2 2 2 2 2 2 2 2 2 2
KVAR-RATIO C3 [ 2 ]
11 2 2 2 2 2 2 2 2 2 2
KVAR-RATIO C4 [ 2 ]
11 2 2 2 2 2 2 2 2 2 2
up to capacitor 12
KVAR-RATIO C12 [ 2 ]
11 2 2 2 2 2 2 2 2 2 2
BACK TO 1
5 max TEMPERATURE
40.0 C
max THD
V 2.7 % - I 1.0 %
7 MAXIMUM VALUES
RESET [ NO ]
SWITCHING OPER.
C [ 1 ] - 123
OPERATION TIME
C [ 1 ] - 12h
10 ERROR MEMORY
E [ 1 ] 08H ....
11 ERROR MEMORY
RESET [ NO ]
12
TEST RUN
[ NO ]
C - POWER
C[1] = 23 kvar MEAS
C[1] = 25 kvar NOM.
BACK TO 1
BACK TO 1
Selecting of
capacitors C1-C12
2 BASIC SETTINGS
NEW ? [ NO ]
3 SWITCH.OPERATION
RESET [ NO ]
4
OPERATING TIME
RESET [ NO ]
INTEGRATION
TIME [ 1 ] s
6 SWITCH. POWER
max [100] kvar
7 SWITCH. TRIGGER
IND [ 66 ] %
8 SWITCH. TRIGGER
CAP [ 66 ] %
9
PROGRAM LOCK
[ NO ]
10 SWITCH. OPERATION
WARNING [50 000]
11 FAST DISCHARGE
[ NO ]
12 FAST DISCHARGE TIME
[ 10 ] s
13 PHASE I 0
[ L1 ] - L1-N
14 PHASE V 0
L1 - [ L1- N ]
15
16
C - TEST
[ YES ]
C - FAILURE
+/- [ 40 ] %
17 TEST ATTEMPT
[6]
18
OUTPUT 1.STEP
[ 0 ... 255 kvar ]
19
CONTROL
[ 3 ] PHASE - CAP
20
SUPPLY
[ 1 ] -----
21
DISPLAY
[ cos j /tan j ]
22 CHANGE PASSWORD
[ NO]
27 ERROR - BACKLIGHT
[ PINK]
BACK TO 2
- 32 Prophi 7
33
Prophi 7
EXPERT.MODE2
DISPLAY EDITOR
INTERFACE
1 PASSWORD ????
[ 6343 ]
Release [YES] or
blocking [NO] or
delay-time of following
reports or alarms:
MEAS. VOLTAGE
OVERVOLTAGE
OVER-COMPENSATED
UNDERCOMPENSATED
HARMONICS !
OVERTEMPERATURE
OVERCURRENT
UNDERVOLTAGE
SWITCH. OPERATIONS !
MEAS. CURRENT< ??
MODBUS-ERROR
MMI-ERROR
REMOTE SWITCH-OFF
REMOTE STOP
REMOTE SWITCH-IN
MODBUS-REMOTE
SYSTEM CURRENT < ?
BUS ERROR EXTERN
C-DEFECT
SYSTEM CURRENT > 0
OVERLOAD SYSTEM
EXT. ERROR
C-DEFECT OFF
AUTO-INIT ERROR
1. DISPLAY [1]
[LINE VOLTAGE]
2. DISPLAY [2]
[APPAR. CURRENT]
FAN TEMPERATURE
[ 30C ]
3. DISPLAY [3]
[REACTIVE POWER]
OFFSET POWER
[25.00] kvar
TIME - HOUR
[10] : 55
TIME - MINUTE
10 : [55]
DATE - DAY
[07]. 12 . 2012
DATE - MONAT
07 . [12]. 2012
3 UNDERVOLTAGE
[ 50 ] %.
DATE - YEAR
07 . 12 .[2012]
OVERVOLTAGE
[ 130 ] %
10
PROTOCOL
[ MODBUS RTU ]
FREQUENCY
[ 50 ] Hz
11
BAUDRATE
[ 9600 / NONE]
BACK TO 1
6 SWITCH. OPERAT. C1
RESET [ NO ]
12
ADRESS
[1]
C1...C12 (C13)
17 SWITCH. OPERAT. C12
RESET [ NO ]
13 NUMBER of MMI
[1]
19 OPERAT. TIME C1
RESET [ NO ]
14
DEVICE TYPE
[ MMI6000 ]
C1...C12 (C13)
30 OPERAT. TIME C12
RESET [ NO ]
15 NUMBER of BR7000-1
[1]
BACK TO 2
- 33 -
Prophi 7
34
SEPARATOR
[ HT - 09H ]
Back to
START-IMAGE
Prophi 7
Prophi 7
35