Earthing Calculation
Earthing Calculation
Introduction
The earthing system in a plant / facility is very important for a few reasons, all of which are related to
either the protection of people and equipment and/or the optimal operation of the electrical system.
These include:
Equipotential bonding of conductive objects (e.g. metallic equipment, buildings, piping etc.)
to the earthing system prevent the presence of dangerous voltages between objects (and
earth).
The earthing system provides a low resistance return path for earth faults within the plant,
which protects both personnel and equipment
For earth faults with return paths to offsite generation sources, a low resistance earthing
grid relative to remote earth prevents dangerous ground potential rises (touch and step
potentials)
The earthing system provides a low resistance path (relative to remote earth) for voltage
transients such as lightning and surges / over voltages
Equipotential bonding helps prevent electrostatic buildup and discharge, which can cause
sparks with enough energy to ignite flammable atmospheres
The earthing system provides a reference potential for electronic circuits and helps reduce
electrical noise for electronic, instrumentation and communication systems
This calculation is based primarily on the guidelines provided by IEEE Std. 80 (2000), "Guide for safety
in AC substation grounding". Lightning protection is excluded from the scope of this calculation (refer
to the specific lightning protection calculation for more details).
Determine the minimum size of the earthing conductors required for the main earth grid
Ensure that the earthing design is appropriate to prevent dangerous step and touch
potentials (if this is necessary)
This calculation should be performed when the earthing system is being designed. It could also be
done after the preliminary design has been completed to confirm that the earthing system is adequate,
or highlight the need for improvement / redesign. Ideally, soil resistivity test results from the site will
be available for use in touch and step potential calculations (if necessary).
For example, when all electricity is generated on-site and the HV/MV/LV earthing systems are
interconnected, then there is no need to do a touch and step potential calculation. In such a case, all
earth faults would return to the source via the earthing system (notwithstanding some small leakage
through earth).
However, where there are decoupled networks (e.g. long transmission lines to remote areas of the
plant), then touch and step potential calculations should be performed for the remote area only.
Calculation Methodology
This calculation is based on IEEE Std. 80 (2000), "Guide for safety in AC substation grounding". There
are two main parts to this calculation:
IEEE Std. 80 is quite descriptive, detailed and easy to follow, so only an overview will be presented
here and IEEE Std. 80 should be consulted for further details (although references will be given herein).
Prerequisites
The following information is required / desirable before starting the calculation:
Soil resistivity measurements at the site (for touch and step only)
Resistivity of any surface layers intended to be laid (for touch and step only
Determining the minimum size of the earthing grid conductors is necessary to ensure that the earthing
grid will be able to withstand the maximum earth fault current. Like a normal power cable under fault,
the earthing grid conductors experience an adiabatic short circuit temperature rise. However unlike a
fault on a normal cable, where the limiting temperature is that which would cause permanent damage
to the cable's insulation, the temperature limit for earthing grid conductors is the melting point of the
conductor. In other words, during the worst case earth fault, we don't want the earthing grid
conductors to start melting!
The minimum conductor size capable of withstanding the adiabatic temperature rise associated with
an earth fault is given by re-arranging IEEE Std. 80 Equation 37:
Where
is
is the thermal capacity of the conductor per unit volume(Jcm - 3C - 1)
The material constants Tm, r, r and TCAP for common conductor materials can be found in IEEE Std.
80 Table 1. For example. Commercial hard-drawn copper has material constants:
Tm = 1084 C
r = 0.00381 C - 1
r = 1.78 .cm
As described in IEEE Std. 80 Section 11.3.1.1, there are alternative methods to formulate this equation,
all of which can also be derived from first principles).
There are also additional factors that should be considered (e.g. taking into account future growth in
fault levels), as discussed in IEEE Std. 80 Section 11.3.3.
Touch voltages - there is a dangerous potential difference between the earth and a metallic object
that a person is touching
Step voltages - there is a dangerous voltage gradient between the feet of a person standing on
earth
The earthing grid can be used to dissipate fault currents to remote earth and reduce the voltage
gradients in the earth. The touch and step potential calculations are performed in order to assess
whether the earthing grid can dissipate the fault currents so that dangerous touch and step voltages
cannot exist.
the general characteristics of the soil (i.e. wet organic soil = 10 .m, moist soil = 100 .m, dry soil =
1,000 .m and bedrock = 10,000 .m).
Where
Where
Schwarz Equations
The Schwarz equations are a series of equations that are more accurate in modelling the effect of
earthing rods / electrodes. The equations are found in IEEE Std 80 Equations 53, 54, 55(footnote) and 56,
as follows:
Where
Where
for
conductors
metres, or simply
buried
at
depth
metres
and
with
:
:
cross-sectional
The coefficient
:
:
:
). This can be found from the power systems studies or from manual calculation.
Generally speaking, the highest relevant earth fault level will be on the primary side of the largest
distribution transformer (i.e. either the terminals or the delta windings).
Current Division Factor
Not all of the earth fault current will flow back through remote earth. A portion of the earth fault current
may have local return paths (e.g. local generation) or there could be alternative return paths other
than remote earth (e.g. overhead earth return cables, buried pipes and cables etc.). Therefore a
current division factor
must be applied to account for the proportion of the fault current flowing
is calculated by:
Decrement Factor
The symmetrical grid current is not the maximum grid current because of asymmetry in short circuits,
namely a dc current offset. This is captured by the decrement factor, which can be calculated from
IEEE Std. 80 Equation 79:
Where
The dc time offset constant is derived from IEEE Std. 80 Equation 74:
Where
50kg person:
70kg person:
Step voltage limit - is the maximum difference in surface potential experience by a person bridging a
distance of 1m with the feet without contact to any earthed object:
Where
50kg person:
70kg person:
is the touch voltage limit (V)
is the step voltage limit (V)
is the surface layer derating factor (as calculated in Step 2)
is the soil resistivity (.m)
is the maximum fault clearing time (s)
The choice of body weight (50kg or 70kg) depends on the expected weight of the personnel at the
site. Typically, where women are expected to be on site, the conservative option is to choose 50kg.
Where
Where:
Where
for grids with earth electrodes along the grid perimeter or corners
Geometric Factor n
The geometric factor
With
(m)
is the length of grid conductors on the perimeter (m)
is the total area of the grid (m2)
and
are the maximum length of the grids in the x and y directions (m)
is the maximum distance between any two points on the grid (m)
Irregularity Factor Ki
The irregularity factor
Where
is found as follows:
For grids with few or no earthing electrodes (and none on corners or along the perimeter):
Where
For grids with earthing electrodes on the corners and along the perimeter:
Where
are the maximum length of the grids in the x and y directions (m)
Where:
Where
Where
What Now?
Now that the mesh and step voltages are calculated, compare them to the maximum tolerable touch
and step voltages respectively. If:
, and
If not, however, then further work needs to be done. Some of the things that can be done to make the
earthing grid design safe:
Redesign the earthing grid to lower the grid resistance (e.g. more grid conductors, more
earthing electrodes, increasing cross-sectional area of conductors, etc). Once this is done,
re-compute the earthing grid resistance (see Step 3) and re-do the touch and step potential
calculations.
Limit the total earth fault current or create alternative earth fault return paths
Worked Example
In this example, the touch and step potential calculations for an earthing grid design will be performed.
The proposed site is a small industrial facility with a network connection via a transmission line and a
delta-wye connected transformer.
A rectangular earthing grid (see the figure right) with the following parameters is proposed:
22 earthing rods will be installed on the corners and perimeter of the grid
Using the simplified equation, the resistance of the earthing grid with respect to remote earth is:
kA
V
The maximum allowable step potential is:
V
The GPR far exceeds the maximum allowable touch and step potentials, and further analysis of mesh
and step voltages need to be performed.
is:
and
Where
is:
and
are the width and length of the grid respectively (e.g. 50m and 90m)
and
is:
is:
is:
m
Finally, the maximum mesh voltage is:
V
The maximum allowable touch potential is 1,720V, which exceeds the mesh voltage calculated above
and the earthing system passes the touch potential criteria (although it is quite marginal).
is:
is:
m
Finally, the maximum allowable step voltage is:
V
The maximum allowable step potential is 5,664V, which exceeds the step voltage calculated above and
the earthing system passes the step potential criteria. Having passed both touch and step potential
criteria, we can conclude that the earthing system is safe.
Figure 2. PTW Ground Mat software output (courtesy of SKM Systems Analysis Inc)
What next?
The minimum size for the earthing grid conductors can be used to specify the earthing grid conductor
sizes in the material take-offs and earthing drawings. The touch and step potential calculations (where
necessary) verify that the earthing grid design is safe for the worst earth faults to remote earth. The
earthing drawings can therefore be approved for the next stage of reviews.