AVK Report Checklist
AVK Report Checklist
Page 2
Customer:
.............................................................
Order No.:
.............................................................
Generator Type:
.............................................................
Operation Hours:
.............................................................
Bearing design:
Roller bearing
Sleeve bearing
Replacement of oil:
YES
NO
YES
NO
I.
Electrical Inspection
Pos. 1.1 - 1.19
II.
Mechanical Inspection
Pos. 2.1 - 2.20
III.
Test Run
Pos. 3.1 - 3.14
IV.
Maintenance Result
Page 2
Page 3
a) Location:
building
marine
b) Atmosperic conditions:
dry
dust
high humidity
salt
c) Ventilation:
unrestricted
restricted
adequate
inadequate
Air intake needs to prevent dust and moisture is transported into the generator by external ventilation. In
case of doubt please contact the customer support.
Operating Conditions:
Please add the operation charts and diagrams showing electrical parameters and temperatures including
alarm.
a) Site duty:
single
b) Duty cycle:
24 hours
daily
c) Load condition:
inductive
non linear
d) Operation:
manned
unmanned
a) Dirt content:
slight dust
thick dust
b) Corrosion:
parallel
idle
occasionally
standby
Generator Conditions:
c) Engine:
Type:
Serial No.:
Fuel:
steel/iron
severe
(....................)
....................
....................
....................
Page 3
3.15
Page 4
The regulating system has to be adjusted to the driving conditions and load at site for avoiding a swinging up
and assure an optimal regulation behaviour.
_______________
Cosimat
Type of Cosimat:
_______________
Additional module:
DECS 100
DECS 200
Unitrol
Other:
_______________
_______________
Droop [%]:
_______________
_______________
_______________
Additional module
XE2
SB2
EDM
Manual controller
Other:
_______________
Page 4
Page 5
Safety instructions:
Safety Regulations:
1.
2.
3.
4.
5.
Disconnect mains!
Prevent reconnection!
Test for absence of harmful voltages!
Ground and short circuit!
Cover or close off nearby live parts!
Only specially trained and experienced personell is allowed to perform work at the alternator.
Even small failures during work may result in damage of health or major machine failure.
Local safety rules have to be observed.
Caution!
The motor start function has to be blocked twice (Emergency stop & Power Supply Starter).
Before terminal box is opened, HV alternator has to be grounded in the switchboard.
This has to observed by the technician.
Alternator cables need to be proved to be without voltage.
After the terminal box is opened, the cables have to be proved to be without voltage again.
Never operate any alternator with open main terminal box!
Page 5
I.
Page 6
Electrical Inspection
performed
Complaints
see page 18
1.1
1.2
1.3
1.4
1.5
Incoming cables should be supported from either below or above the box level at a sufficient distance
from the centre line of the generating set so as to avoid a tight radius at the point of entry into the
terminal box panel, and allow movement of the generator set on its anti-vibration mountings without
excessive stress on the cable. The generator should be free to move at least 25 mm as per Figure 1.
In addition refer to the operating instructions under point Electrical connections.
Please see also the AvK documentation about commissioning instructions.
Page 6
Insulation measurement
Page 7
- Caution! -
The AVR plus any voltage transformers should be disconnected, and any temperature detector leads
(RTDs / Thermistors) grounded during the test. Refer to the generator wiring diagram for details.
After measurement discharge all windings and reconnect all cables.
performed
Complaints
see page 18
1.6
Insulation test of stator windings (star point must be opened and T24, T25, T26
disconnected)
a)
b)
c)
1.7
a)
b)
c)
Page 7
Page 8
MV & HV generators
A 2500V (MV) / 5000V (HV) motorised megger or similar instrument should be used. Separate the three
natural leads, ground V and W leads and megger U to ground. Repeat for V phase with U and W grounded
and W phase with U and V grounded. The 1 minute insulation resistance for each phase should not be less
than 100 M (MV) / 300 M (HV) and the polarisation index should be in the order of 2 or greater and
20 C. (PI = IR10min / IR1min)
If the IR is lower than described above, check for the reason of low IR values ( i.e. humidity, dirt, wrong
connection).
It should be noted that as winding temperature increases values of insulation resistance will significantly
reduce. Therefore true values of insulation resistance should be established with windings at ambient
temperatures.
performed
Complaints
see page 18
1.8
Caution!
Before static winding resistances are measured, the generator set should be shut
down, isolated and proved dead.
1.9
1.10
1.11
1.12
Page 8
Page 9
performed
Complaints
see page 18
1.13
1.14
1.15
............. V
............. A
The ambient conditions in which a generator is operated or stored should be fully understood, to ensure
the generator is maintained in a fully serviceable condition. Areas for consideration include
temperature, humidity and vibration levels. In stand-still the anti-condensation heaters should be activated.
Within the generators storage or installed area, thermostatic control of space heaters will be of
considerable assistance.
Observe CGT storage instructions in case of longer ( > 6 months) standstill time of the alternator.
1.16
a)
b)
1.17
A 500V megger or similar instrument should be used. Minimum acceptable values after 1 minute are:
New machine
Exciter stator
Combined rotor
10 M
200 M
In-service machine
5 M
100 M
If the IR is lower than described above, check for the reason of low IR values ( i.e. humidity, dirt, wrong
connection).
Page 9
Page 10
Complaints
see page 18
1.18
The rotating rectifier assembly is mounted on the generator shaft end near the non drive end
bearing. Access can be achieved by removal of the rectifier cover.
The diodes on the main rectifier assembly can be checked with a multimeter. The flexible leads
connected to each diode should be disconnected at the terminal end, and the forward and reverse
resistance checked. A healthy diode will indicate a very high resistance (infinity) in the reverse
direction. A faulty diode will give a full deflection reading in both directions with the test meter on the
10,000 ohms scale, or an infinity reading in both directions.
On an electronic digital meter a healthy diode will give a low reading in one direction and a high reading
in the other.
Compare the readings of the rectifiers in operation with new ones during same temperature condition.
Varistor and diode reverse check with 500V insulation measuring instrument.
Check for discolorations and signs of high temperature.
Check for cable chafing and mechanical stress to the cables and cracks in rectifier blocks.
1.19
1.20
Page 10
II.
Page 11
Mechanical Inspection
performed
Complaints
see page 18
NO
Pressure indication
After pump started:
2.1
O.K.
not O.K.
2.2
2.3
2.4
.................... mbar
Page 11
Page 12
performed
Complaints
see page 18
2.5
2.6
2.7
2.8
Check for any corrosion on drive side and non-drive side bearing
..............................................................
..............................................................
2.9
2.10
2.11
2.12
Scales available
Yes
No
Yes
No
Tools clean
Yes
No
Bearing grease colour has to be checked between rollers and running surface. Grease has to be soft and not
black.
2.13
2.14
Page 12
Page 13
performed
Complaints
see page 18
2.15
2.16
2.17
2.18
2.19
Check of inlet and outlet airducts for corrosion, dirt or loose particles
2.20
2.21
2.22
Dimension
Torque [Nm]
Dimension
Torque [Nm]
M4
2,5
M4
1,5
M5
4,5
M5
2,5
M6
M6
4,5
M8
20
M8
10
M10
40
M10
20
M12
65
M12
40
Page 13
Page 14
performed
Complaints
see page 18
2.23
Porperty class
Torque [Nm]
Abm.
Porperty class
Torque [Nm]
M4
8.8
10.9
12.9
3,0
4,6
5,1
M18
8.8
10.9
12.9
295
421
492
M5
8.8
10.9
12.9
5,9
8,6
10,0
M20
8.8
10.9
12.9
415
592
692
M6
8.8
10.9
12.9
10,1
14,9
17,4
M22
8.8
10.9
12.9
567
807
945
M7
8.8
10.9
12.9
16,8
24,7
28,9
M24
8.8
10.9
12.9
714
1017
1190
M8
8.8
10.9
12.9
24,6
36,1
42,2
M27
8.8
10.9
12.9
1050
1496
1750
8.8
10.9
12.9
8.8
10.9
12.9
48
71
83
84
123
144
8.8
10.9
12.9
8.8
10.9
12.9
1428
2033
2380
1928
2747
3214
M14
8.8
10.9
12.9
133
195
229
M36
8.8
10.9
12.9
2482
3535
4136
M16
8.8
10.9
12.9
206
302
354
M39
8.8
10.9
12.9
3208
4569
5346
M10
M12
M30
M33
Page 14
III.
Page 15
Test Run
Please attach a copy of the protection relay setting and a single line diagram of the power station.
performed
Complaints
see page 18
Precaution!
3.1
3.2
3.3
DE:
LR ..........
HR ..........
NDE:
LR ..........
HR ..........
3.4
3.5
3.6
3.7
Check signals and contacts between alternator and external control systems
3.8
DE:
NDE:
Frame:
.............
Output:
............. kW
Airduct inlet:
.............
Airduct outlet:
.............
Page 15
Page 16
performed
Complaints
see page 18
3.9
............. A
............. A
c) Supply voltage:
UH1-UH2:
............. V
UH1-WH2:
............. V
WH1-WH2:
............. V
3.10
............. Hz
.......... %
3.11
3.12
3.13
XE2
EDM200
Other modules
3.14
............. kV
............. kV
Page 16
Page 17
Complaints
see page 18
3.15
__________________________________________
__________________________________________
__________________________________________
__________________________________________
__________________________________________
__________________________________________
__________________________________________
__________________________________________
__________________________________________
Page 17
IV.
Page 18
Maintenance Result
Complaints:
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
___________________________________________________
________________
(Date)
________________________
(Signature Customer)
________________________
(AvK-Service-Technician)
Page 18
Page 19
Page 19