Micom p127 Modbus Table
Micom p127 Modbus Table
Technical Manual
Note:
The technical manual for this device gives instructions for its installation, commissioning, and operation.
However, the manual cannot cover all conceivable circumstances or include detailed information on all
topics. In the event of questions or specific problems, do not take any action without proper authorization.
Contact the appropriate Schneider Electric technical sales office and request the necessary information.
Any agreements, commitments, and legal relationships and any obligations on the part of
Schneider Electric including settlements of warranties, result solely from the applicable purchase contract,
which is not affected by the contents of the technical manual.
This device MUST NOT be modified. If any modification is made without the express permission of
Schneider Electric, it will invalidate the warranty, and may render the product unsafe.
The Schneider Electric logo and any alternative version thereof are trademarks and service marks of Schneider Electric.
MiCOM is a registered trademark of Schneider Electric. All trade names or trademarks mentioned herein whether
registered or not, are the property of their owners.
This manual is provided for informational use only and is subject to change without notice.
2011, Schneider Electric. All rights reserved.
Technical Manual
MiCOM P125/P126 & P127
P12y/EN M/Fa5
Page 1/2
Pxxxx/EN SS/G11
Introduction
P12y/EN IT/Fa5
P12y/EN IN/Fa5
User Guide
P12y/EN FT/Fa5
P12y/EN HI/Fa5
P12y/EN TD/Fa5
Getting Started
P12y/EN GS/Fa5
Application Guide
P12y/EN AP/Fa5
Communication Database
P12y/EN CT/Fa5
P12y/EN CM/Fa4
Connection Diagrams
P12y/EN CO/Fa5
P12y/EN RS/Fa5
P12y/EN VC/Fa5
P12y/EN M/Fa5
Technical Manual
Page 2/2
BLANK PAGE
Pxxx/EN SS/G11
SAFETY SECTION
Pxxx/EN SS/G11
Safety Section
Page 1/8
INTRODUCTION
2.
3.
3.1
Symbols
3.2
Labels
4.
5.
6.
6.1
6.2
Protective Class
6.3
Installation Category
6.4
Environment
Pxxx/EN SS/G11
Page 2/8
Safety Section
BLANK PAGE
Pxxx/EN SS/G11
Safety Section
1.
Page 3/8
INTRODUCTION
This guide and the relevant equipment documentation provide full information on safe
handling, commissioning and testing of this equipment. This Safety Guide also includes
descriptions of equipment label markings.
Documentation for equipment ordered from Schneider Electric is despatched separately from
manufactured goods and may not be received at the same time. Therefore this guide is
provided to ensure that printed information which may be present on the equipment is fully
understood by the recipient.
The technical data in this safety guide is typical only, see the technical data section of the
relevant product publication(s) for data specific to a particular equipment.
Before carrying out any work on the equipment the user should be familiar with the
contents of this Safety Guide and the ratings on the equipments rating label.
Reference should be made to the external connection diagram before the equipment is
installed, commissioned or serviced.
Language specific, self-adhesive User Interface labels are provided in a bag for some
equipment.
2.
Are familiar with the installation, commissioning, and operation of the equipment and
of the system to which it is being connected;
Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorised to energize and de-energize equipment and
to isolate, ground, and label it;
Are trained in the care and use of safety apparatus in accordance with safety
engineering practices;
The equipment documentation gives instructions for its installation, commissioning, and
operation. However, the manual cannot cover all conceivable circumstances or include
detailed information on all topics. In the event of questions or specific problems, do not take
any action without proper authorization. Contact the appropriate Schneider Electric technical
sales office and request the necessary information.
Pxxx/EN SS/G11
Page 4/8
3.
Safety Section
3.1
Symbols
*NOTE:
3.2
Labels
See Safety Guide (SFTY/4L M/G11) for equipment labelling information.
4.
be
consulted
before
installing,
Pxxx/EN SS/G11
Safety Section
Page 5/8
To ensure that wires are correctly terminated the correct crimp terminal and tool
for the wire size should be used.
The equipment must be connected in accordance with the appropriate connection
diagram.
Protection Class I Equipment
-
Integrity of
applicable),
the
protective
conductor
(earth)
connection
(where
Pxxx/EN SS/G11
Page 6/8
Safety Section
UL and CSA/CUL Listed or Recognized equipment
To maintain UL and CSA/CUL Listing/Recognized status for North America the
equipment should be installed using UL or CSA Listed or Recognized parts for
the following items: connection cables, protective fuses/fuseholders or circuit
breakers, insulation crimp terminals and replacement internal battery, as
specified in the equipment documentation.
For external protective fuses a UL or CSA Listed fuse shall be used. The Listed
type shall be a Class J time delay fuse, with a maximum current rating of 15 A
and a minimum d.c. rating of 250 Vd.c., for example type AJT15.
Where UL or CSA Listing of the equipment is not required, a high rupture
capacity (HRC) fuse type with a maximum current rating of 16 Amps and a
minimum d.c. rating of 250 Vd.c. may be used, for example Red Spot type NIT or
TIA.
Equipment operating conditions
The equipment should be operated within the specified electrical and
environmental limits.
Current transformer circuits
Do not open the secondary circuit of a live CT since the high voltage produced
may be lethal to personnel and could damage insulation. Generally, for safety,
the secondary of the line CT must be shorted before opening any connections to
it.
For most equipment with ring-terminal connections, the threaded terminal block
for current transformer termination has automatic CT shorting on removal of the
module. Therefore external shorting of the CTs may not be required, the
equipment documentation should be checked to see if this applies.
For equipment with pin-terminal connections, the threaded terminal block for
current transformer termination does NOT have automatic CT shorting on removal
of the module.
External resistors, including voltage dependent resistors (VDRs)
Where external resistors, including voltage dependent resistors (VDRs), are fitted
to the equipment, these may present a risk of electric shock or burns, if touched.
Battery replacement
Where internal batteries are fitted they should be replaced with the recommended
type and be installed with the correct polarity to avoid possible damage to the
equipment, buildings and persons.
Insulation and dielectric strength testing
Insulation testing may leave capacitors charged up to a hazardous voltage. At the
end of each part of the test, the voltage should be gradually reduced to zero, to
discharge capacitors, before the test leads are disconnected.
Insertion of modules and pcb cards
Modules and PCB cards must not be inserted into or withdrawn from the
equipment whilst it is energized, since this may result in damage.
Insertion and withdrawal of extender cards
Extender cards are available for some equipment. If an extender card is used,
this should not be inserted or withdrawn from the equipment whilst it is energized.
This is to avoid possible shock or damage hazards. Hazardous live voltages may
be accessible on the extender card.
Pxxx/EN SS/G11
Safety Section
Page 7/8
External test blocks and test plugs
Great care should be taken when using external test blocks and test plugs such
as the MMLG, MMLB and MiCOM P990 types, hazardous voltages may be
accessible when using these. *CT shorting links must be in place before the
insertion or removal of MMLB test plugs, to avoid potentially lethal voltages.
*Note: When a MiCOM P992 Test Plug is inserted into the MiCOM P991 Test
Block, the secondaries of the line CTs are automatically shorted, making
them safe.
Fiber optic communication
Where fiber optic communication devices are fitted, these should not be viewed
directly. Optical power meters should be used to determine the operation or
signal level of the device.
Cleaning
The equipment may be cleaned using a lint free cloth dampened with clean water,
when no connections are energized. Contact fingers of test plugs are normally
protected by petroleum jelly, which should not be removed.
5.
Pxxx/EN SS/G11
Page 8/8
6.
Safety Section
6.1
6.2
Protective Class
IEC 60255-27: 2005
EN 60255-27: 2006
6.3
Installation Category
IEC 60255-27: 2005
EN 60255-27: 2006
6.4
Environment
The equipment is intended for indoor installation and use only. If it is required for use in an
outdoor environment then it must be mounted in a specific cabinet or housing which will
enable it to meet the requirements of IEC 60529 with the classification of degree of
protection IP54 (dust and splashing water protected).
Pollution Degree - Pollution Degree 2
Altitude - Operation up to 2000m
IEC 60255-27:2005
EN 60255-27: 2006
Introduction
P12y/EN IT/Fa5
MiCOM P125/P126/P127
INTRODUCTION
Introduction
P12y/EN IT/Fa5
MiCOM P125/P126/P127
Page 1/8
CONTENTS
1.
INTRODUCTION
2.
3.
4.
5.
MAIN FUNCTIONS
5.1
Main functions
5.2
General functions
P12y/EN IT/Fa5
Introduction
Page 2/8
MiCOM P125/P126/P127
BLANK PAGE
Introduction
MiCOM P125/P126/P127
1.
P12y/EN IT/Fa5
Page 3/8
INTRODUCTION
The MiCOM P125, P126 & P127 relays have been designed for controlling, protecting and
monitoring industrial installations, public distribution networks and substations. They can also
be used as part of a protection scheme for transformers and generator transformers. The
P125, P126 & P127 relays can also provide back-up protection for HV and EHV transmission
systems.
P12y/EN IT/Fa5
Introduction
Page 4/8
2.
MiCOM P125/P126/P127
Introduction
The introduction presents the documentation structure and a
brief presentation of the relay, including functions.
P12y/EN IN
P12y/EN FT
User Guide
This section provides relay settings with a brief explanation of
each setting and detailed description. It also provides recording
and measurements functions including the configuration of the
event and disturbance recorder and measurement functions.
P12y/EN HI
P12y/EN AP
Application Notes
This section includes a description of common power system
applications of the relay, calculation of suitable settings, some
typical worked examples, and how to apply the settings to the
relay.
P12y/EN TD
P12y/EN CT
P12y/EN CM
P12y/EN CO
Connection diagrams
This section provides the mechanical and electrical description.
External wiring connections to the relay are indicated.
P12y/EN RS
P12y/EN VC
Introduction
P12y/EN IT/Fa5
MiCOM P125/P126/P127
3.
Page 5/8
MiCOM products include extensive facilities for recording information on the state and
behaviour of a power system, using disturbance and fault records.
They can also provide measurements of the power system at regular intervals to a control
centre enabling remote monitoring and control to take place.
For up-to-date information on any MiCOM product, refer to the technical publications, which
can be obtained from: Schneider Electric or your local sales office; alternatively visit our web
site.
P12y/EN IT/Fa5
Introduction
Page 6/8
4.
MiCOM P125/P126/P127
MiCOM P126:
Three phase overcurrent and directional earth fault relay with earth
fault wattmetric element and autoreclose function.
MiCOM P127:
Introduction
P12y/EN IT/Fa5
MiCOM P125/P126/P127
5.
MAIN FUNCTIONS
5.1
Main functions
Page 7/8
The following table shows the functions available with the models.
ANSI
CODES
FEATURES
50/51P/N
50/51
3 phase overcurrent
50/51N
Earth overcurrent
64N
67P
67N
67N
51V
37
3 phase undercurrent
46
27/59
59N
47
Negative overvoltage
32
32N
81U/O
Under/over frequency
81R
Rate of Frequency
49
Thermal overload
86
79
Autoreclose
50BF
46BC
P125
P126
P127
Blocking Logic
Test of output relays (Maintenance)
CB control Local/remote
Inrush blocking
Switch on to fault (SOTF)
Phase rotation
VT supervision (VTS)
CT Supervision (CTS)
P12y/EN IT/Fa5
Introduction
Page 8/8
5.2
MiCOM P125/P126/P127
General functions
The following table shows the general features available.
GENERAL FEATURES
Number of digital inputs
Standard configuration
P125
P126
Optional configuration
Total number of outputs
relays
P127
7
12
Events recording
250
250
250
Fault recording
25
25
25
Disturbance recording
Setting group
Auxiliary timers
Standard configuration
Optional configuration
Communication
12
IEC60870-5-103 or Modbus
(port 2 optional)
Time synchronisation
IRIG-B Synchronization
(optional)
Settings software
Measurements
Metering (optional)
P12y/EN IN/Fa5
HANDLING, INSTALLATION
AND CASE DIMENSIONS
P12y/EN IN/Fa5
Page 1/12
CONTENT
1.
GENERAL CONSIDERATIONS
1.1
Receipt of relays
1.2
2.
3.
RELAY MOUNTING
4.
UNPACKING
5.
STORAGE
6.
CONNECTIONS
6.1
6.2
6.3
RS232 port
6.4
6.4.1
IRIG-B Modulated
6.4.2
IRIG-B demodulated
10
6.5
10
7.
CASE DIMENSIONS
11
7.1
11
7.2
MiCOM P125
11
P12y/EN IN/Fa5
Page 2/12
BLANK PAGE
1.
P12y/EN IN/Fa5
Page 3/12
GENERAL CONSIDERATIONS
BEFORE CARRYING OUT ANY WORK ON THE EQUIPMENT, THE
USER SHOULD BE FAMILIAR WITH THE CONTENTS OF THE SAFETY
GUIDE SFTY/4LM/G11 OR LATER ISSUE, OR THE SAFETY AND
TECHNICAL DATA SECTIONS OF THE TECHNICAL MANUAL AND
ALSO THE RATINGS ON THE EQUIPMENT RATING LABEL.
1.1
Receipt of relays
Protective relays, although generally of robust construction, require careful treatment prior to
installation on site. Upon receipt, relays should be examined immediately to ensure no
damage has been sustained in transit. If damage has been sustained during transit a claim
should be made to the transport contractor and Schneider Electric should be promptly
notified.
Relays that are supplied unmounted and not intended for immediate installation should be
returned to their protective polythene bags.
1.2
P12y/EN IN/Fa5
Page 4/12
2.
Before removing a module, ensure that you are at the same electrostatic potential as
the equipment by touching the case.
2.
Handle the module by its front-plate, frame or edges of the printed circuit board. Avoid
touching the electronic components, printed circuit track or connectors.
3.
Do not pass the module to another person without first ensuring you are both at the
same electrostatic potential. Shaking hands achieves equipotential.
4.
5.
P12y/EN IN/Fa5
3.
Page 5/12
RELAY MOUNTING
Relays are dispatched either individually or as part of a panel/rack assembly.
If an MMLG test block is to be included it should be positioned at the right-hand side of the
assembly (viewed from the front). Modules should remain protected by their metal case
during assembly into a panel or rack.
If external test blocks are connected to the relay, great care should be taken when using the
associated test plugs such as MMLB and MiCOM P992 since their use may make hazardous
voltages accessible. *CT shorting links must be in place before the insertion or removal of
MMLB test plugs, to avoid potentially lethal voltages.
NOTE:
NOTE: When a MiCOM P992 Test Plug is inserted into the MiCOM
P991 Test Block, the secondaries of the line CTs are automatically
shorted, making them safe.
For individually mounted relays an outline diagram is supplied in section 6 of this chapter
showing the panel cut-outs and hole centres.
P12y/EN IN/Fa5
Page 6/12
4.
UNPACKING
Care must be taken when unpacking and installing the relays so that none of the parts is
damaged or the settings altered. Relays must only be handled by skilled persons. The
installation should be clean, dry and reasonably free from dust and excessive vibration. The
site should be well lit to facilitate inspection. Relays that have been removed from their cases
should not be left in situations where they are exposed to dust or damp. This particularly
applies to installations which are being carried out at the same time as construction work.
5.
P12y/EN IN/Fa5
Page 7/12
STORAGE
If relays are not to be installed immediately upon receipt they should be stored in a place
free from dust and moisture in their original cartons. Where de-humidifier bags have been
included in the packing they should be retained. The action of the de-humidifier crystals will
be impaired if the bag has been exposed to ambient conditions and may be restored by
gently heating the bag for about an hour, prior to replacing it in the carton.
Dust which collects on a carton may, on subsequent unpacking, find its way into the relay; in
damp conditions the carton and packing may become impregnated with moisture and the dehumifier will lose its efficiency.
Storage temperature: 25C to +70C.
SUSTAINED EXPOSURE TO HIGH HUMIDITY DURING STORAGE MAY
CAUSE DAMAGE TO ELECTRONICS AND REDUCE THE LIFETIME OF
THE EQUIPMENT.
THEREFORE, ONCE THE MICOM PRODUCTS HAVE BEEN
UNPACKED, WE RECOMMEND THAT THEY ARE ENERGIZED WITHIN
THE THREE FOLLOWING MONTHS.
WHERE ELECTRICAL EQUIPMENT IS BEING INSTALLED, SUFFICIENT
TIME SHOULD BE ALLOWED FOR ACCLIMATISATION TO THE
AMBIENT TEMPERATURE OF THE ENVIRONMENT, BEFORE
ENERGISATION.
P12y/EN IN/Fa5
Page 8/12
6.
CONNECTIONS
6.1
P0166ENc
P0167ENc
To ensure the isolation of adjacent terminals, and to respect the security and safety
instructions, an insulated sleeve must be used.
We recommend the following cable cross-sections:
Auxiliary sources
Vaux: 1.5 mm
Communication Ports
Other circuits
1.0 mm
Because of the limitations of the ring terminals, the maximum wire cross-section which can
be used for the connector blocks (for current inputs and signals) is 6mm by using noninsulated ring terminals. When only pre-insulated terminals can be used, the maximum wire
cross-section is reduced to 2,63 mm per ring terminal. If a more significant wire crosssection is necessary, two wires can be connected in parallel, each one terminated by a
separate ring terminal.
P12y/EN IN/Fa5
Page 9/12
Except for the RS485 port(s) all the terminal blocks used for connections, can withstand a
maximum working voltage of 300V.
We recommend the auxiliary supply is protected by a NIT or TIA fuse type with a maximum
breaking capacity of 16A. For safety reasons, never install fuses in current transformers
circuits. Other circuits must be protected by fuses.
6.2
6.3
Each core:
Screen:
100pF/m
RS232 port
Short term connections to the RS232 port, located behind the bottom access cover, can be
made using a screened multi-core communication cable up to 15m long, or a total
capacitance of 2500pF. The cable should be terminated at the relay end with a 9-way, metal
shelled, D-type male plug.
6.4
6.4.1
IRIG-B Modulated
IRIG-B modulated terminals: + = terminal 82, = terminal 81.
NOTE:
The IRIG-B input and BNC connector (including BNC adaptor) have a characteristic
impedance of 50. It is recommended that connections between the IRIG-B equipment and
the relay are made using coaxial cable of type RG59LSF with a halogen free, fire retardant
sheath.
To connect the BNC connector to the relay, use the BNC adaptor fixed on the rear
connector:
Position the BNC adaptor (+ side on terminal 82) and screw the scre/washer
assembly (+ and GND sides are marked on the adaptor).
Retaining screw
washer
spacer
P3953ENa
P12y/EN IN/Fa5
Page 10/12
6.4.2
IRIG-B demodulated
IRIG-B demodulated terminals: + = terminal 84, = terminal 83.
The connections to IRIG-B unmodulated terminals are classical connections.
6.5
P12y/EN IN/Fa5
7.
CASE DIMENSIONS
7.1
Page 11/12
P0077ENb
NOTE:
7.2
For P127 with IRIG-B option with BNC adaptor, add 25 mm to the
length.
MiCOM P125
P0078ENb
NOTE:
P12y/EN IN/Fa5
Page 12/12
BLANK PAGE
User Guide
P12y/EN FT/Fa5
USER GUIDE
User Guide
P12y/EN FT/Fa5
Page 1/96
CONTENT
1.
1.1
User Interface
1.1.1
Relay Overview
1.1.2
1.1.3
1.1.4
LEDs
1.1.5
Description of the two areas under the top and bottom flaps
1.1.6
10
1.2
Menu structure
13
1.3
Password
13
1.3.1
Password Protection
13
1.3.2
Password Entry
13
1.3.3
14
1.3.4
14
1.4
14
1.4.1
14
1.4.2
14
1.5
General characteristics
19
1.5.1
Analogue Inputs
19
2.
MENU
21
2.1
OP PARAMETERS menu
22
2.2
ORDERS menu
23
2.3
CONFIGURATION menu
24
2.3.1
24
2.3.2
Voltage Connections
26
2.3.3
27
2.3.4
28
2.3.5
32
2.3.6
32
2.3.7
33
2.3.8
Submenu Alarms
34
2.3.9
Submenu Date
35
2.4
MEASUREMENTS menu
36
2.5
39
2.5.1
Submenu Frequency
39
2.5.2
Submenu Currents
40
2.5.3
Submenu Voltages
41
2.5.4
Submenu Powers
42
2.5.5
Submenu Energies
43
2.5.6
44
P12y/EN FT/Fa5
Page 2/96
User Guide
MiCOM P125/P126 & P127
2.6
COMMUNICATION menu
45
2.6.1
HMI submenu
45
2.6.2
45
2.6.3
46
2.7
PROTECTION menu
47
2.7.1
47
2.7.2
50
2.7.3
56
2.7.4
60
2.7.5
63
2.7.6
64
2.7.7
65
2.7.8
66
2.7.9
67
2.7.10
68
2.7.11
68
2.7.12
69
2.7.13
72
2.7.14
72
2.8
73
2.8.1
73
2.8.2
74
2.8.3
75
2.8.4
76
2.8.5
77
2.8.6
77
2.8.7
Submenu Inputs
80
2.8.8
82
2.8.9
83
2.8.10
84
2.8.11
84
2.8.12
85
2.8.13
85
2.8.14
86
2.8.15
87
2.8.16
88
2.8.17
90
2.9
RECORDS menu
91
2.9.1
91
2.9.2
94
User Guide
MiCOM P125/P126 & P127
P12y/EN FT/Fa5
Page 3/96
3.
WIRING
95
3.1
95
3.2
95
3.3
Digital Inputs
95
3.4
Output Relays
95
3.5
Communication
95
3.5.1
95
3.5.2
96
P12y/EN FT/Fa5
User Guide
Page 4/96
BLANK PAGE
User Guide
P12y/EN FT/Fa5
1.
Page 5/96
1.1
User Interface
1.1.1
Relay Overview
The next figures show the P125 and P126/P127 relays.
P125
P126/P127
As can be seen in above figures the case width dimensions differ between the P125 and the
P126/P127.
The table shows the case size for the relays.
Version
Height
Depth
Width
Type P125
4U (177mm)
226mm
20 TE
4U (177mm)
226mm
30 TE
P12y/EN FT/Fa5
User Guide
Page 6/96
The hinged covers at the top and bottom of the relay are shown closed. Extra physical
protection for the front panel can be provided by an optional transparent front cover; this
allows read only access to the relays settings and data but does not affect the relays IP
rating. When full access to the relay keypad is required to edit the settings, the transparent
cover can be unclipped and removed when the top and bottom hinged covers are open. If
the lower cover is secured with a wire seal, this will need to be removed. Using the side
flanges of the transparent cover, pull the bottom edge away from the relay front panel until it
is clear of the seal tab. The cover can then be moved vertically down to release the two
fixing lugs from their recesses in the front panel.
1.1.2
2.
The LEDs
3.
User Guide
P12y/EN FT/Fa5
Page 7/96
1.1.3.1
LCD display
In the front panel, a liquid crystal display (LCD) displays settings, measured values and
alarms. Data is accessed through a menu structure.
The LCD has two lines, with sixteen characters each. A back-light is activated when a key is
pressed and will remain lit for five minutes after the last key press. This allows the user to be
able to read the display in most lighting conditions.
1.1.3.2
Keypad
The keypad has seven keys divided into two groups:
Two keys located just under the screen (keys and c).
Keys and c are used to read and acknowledge alarms. To display successive alarms,
press key c. Alarms are displayed in reverse order of their detection (the most recent alarm
first, the oldest alarm last). To acknowledge the alarms, the user can either acknowledge
each alarm using or go to the end of the ALARM menu and acknowledge all the alarms
at the same time.
When navigating through submenus, key is also used to come back to the head line of
the corresponding menu.
NOTE:
They are used to navigate through the different menus and submenus and to do the setting
of the relay.
The key is used to validate a choice or a value (modification of settings).
P12y/EN FT/Fa5
User Guide
Page 8/96
1.1.4
LEDs
The LED labels on the front panel are by default written in English, however the user has
self-adhesive labels available with MiCOM relays on which it is possible to write using a ball
point pen.
The top four LEDs indicate the status of the relay (Trip condition, alarm LED, equipment
failure, auxiliary supply).
The four lower LEDs are freely programmable by the user and can be assigned to display a
threshold crossing for example (available for all models) or to show the status of the logic
inputs.The description of each one of these eight LEDs located in the left side of the front
view is given hereafter (numbered from the top to bottom from 1 to 8):
LED 1
LED 8
LED 1
P3951ENa
Colour: RED
Label: Trip
LED 1 indicates when a trip command has been issued by the relay to the cut-off element
(circuit breaker, protection trip). This LED copies the trip command issued to the trip output
relay contact (RL1). In its normal state the LED is not lit. It is illuminated as soon as a trip
order is issued. It is reset when the associated alarm is acknowledged.
LED 2
Colour: ORANGE
Label: Alarm
LED 2 indicates that an alarm has been registered by MiCOM P125, P126 & P127 relays.
The alarms are either threshold crossings (instantaneous) or tripping orders (time delayed).
The LED will flash until the alarms have been accepted (read key), after which the LED will
change to constant illumination. It will extinguish when the alarms have been cleared (clear
key) and the trip cause is reset.
LED 3
Colour: ORANGE
Label: Warning
LED 3 is dedicated to the internal alarms of MiCOM P125, P126 & P127 relays.
When a "non critical" internal alarm (i.e. a communication fault) is detected, the LED flashes
continuously. When the fault is classed as "critical", the LED is illuminated continuously. The
LED only extinguishes after the cause that provoked this fault has been removed (i.e. repair
of the module, disappearance of the fault).
LED 4
Colour: GREEN
Label: Healthy
LED 4 indicates that MiCOM P125, P126 and P127 relays are in correct working order and
the auxiliary power supply is present.
LED 5 to 8
Colour: RED
Label: Aux.1 to 4.
These LEDs can be programmed by the user on the basis of information on available
thresholds (instantaneous and time-delayed). The user selects the information he wishes to
see associates with each LED from the menu element (Logic OR). Each LED illuminates
when the associated information is valid. The extinguishing of each LED is linked to the
acknowledgement of the associated alarms.
User Guide
P12y/EN FT/Fa5
Description of the two areas under the top and bottom flaps
1.1.5.1
Relay Identification
Page 9/96
Under the top hinged cover there is an adhesive paper label that contains the relay model
number, serial number, sensitive earth current range, rating information and the Cortec code
for ordering etc.
Each item on the label is described below:
P127CAF11: CORTEC code
This code allows the user to identify
the characteristics of the relay.
No.: 0000000: Serial number
Cde: 00000/000: Reference to the
purchasing order.
These numbers are needed when
contacting Schneider Electric in case of
problems.
Un = 57 130V: Voltage input range.
Modbus: Communication protocol of the
RS485 communication port situated on
the rear of the relay.
0.002 Ien: Sensitivity of the earth fault
current (available are three sensitivity
levels).
Ua = 48-150V DC: Auxiliary power
supply range. In this example, the
power supply must be a DC voltage.
1.1.5.2
1.1.5.3
It is able to power the relay from its front port. This allows the user to view or modify
data on the relay even when the auxiliary power supply of the relay has failed or when
the relay is not connected to any power supply. The USB port of the PC supplies the
power necessary to energize the relay. This lasts as long as the battery of the PC can
last.
2.
It provides an USB / RS 232 interface between the MiCOM relay and the PC. This
allows the user to be able to change the setting of the relay using a PC with its USB
port.
It eases the use of the relay allowing the retrieval of records and disturbance files for
example when the auxiliary supply has failed or is not available.
The associated driver (supplied with the relay) needs to be installed in the PC. For more
information , please refer to MiCOM E2 User Manual.
P12y/EN FT/Fa5
User Guide
Page 10/96
1.1.6
1.1.6.1
29
30
31
32
33
34
35
36
10
37
38
11
12
39
40
13
14
41
42
15
16
43
44
17
18
45
46
19
20
47
48
21
22
49
50
23
24
51
52
25
26
53
54
27
28
55
56
Output 5
Common
output 1
Case earth
connection
29
30
Terminal
RS485
Common
output 5
Output 1
(NC)
RS485 terminal
31
32
RS485 +
Output 6
Output1
(NO)
Vaux
+ terminal
33
34
Vaux
terminal
Common
output 6
Common
output 2
Relay failed
(WD)
35
36
Common
"Watchdog
"
10
Output 2
(NC)
Relay healthy
(WD)
37
38
11
12
Output 2
(NO)
Residual volt.
input
39
40
13
14
Output 3
41
42
15
16
Common
output 3
43
44
Input 3
+ terminal
17
18
Output 4
45
46
Input 3
terminal
19
20
Common
output 4
47
48
Input 4
+ terminal
21
22
Input 1
+ terminal
49
50
Input 4
terminal
23
24
Input 1
terminal
51
52
25
26
Input 2
+ terminal
53
54
27
28
Input 2
terminal
55
56
Current input
(5A)
Current input
(1A)
Residual
volt. input
Current
input (5A)
Current
input (1A)
User Guide
P12y/EN FT/Fa5
Page 11/96
58
29
30
59
60
31
32
61
62
33
34
63
64
35
36
65
66
10
37
38
67
68
11
12
39
40
69
70
13
14
41
42
71
72
15
16
43
44
73
74
17
18
45
46
75
76
19
20
47
48
77
78
21
22
49
50
79
80
23
24
51
52
81
82
25
26
53
54
83
84
27
28
55
56
Input 7
+ terminal
57
58
Input 6
+ terminal
Output 5
Common
output 1
Case earth
connection
29
30
Terminal
RS485
Input 7
terminal
59
60
Input 6
terminal
Common
output 5
Output 1
(NC)
RS485 terminal
31
32
RS485 +
61
62
Output 6
Output1
(NO)
Vaux
+ terminal
33
34
Vaux
terminal
63
64
Common
output 6
Common
output 2
Relay failed
(WD)
35
36
Common
"Watchdog"
65
66
Common
output 7
10
Output 2
(NC)
Relay
healthy
(WD)
37
38
67
68
Output 7
11
12
Output 2
(NO)
39
40
69
70
Common
output 8
13
14
Output 3
Current input 41
IA (5A)
42
Current
input IA (5A)
71
72
Output 8
15
16
Common
output 3
Current input 43
IB (5A)
44
Current
input IB (5A)
73
74
Input 3
+ terminal
17
18
Output 4
Current input 45
IC(5A)
46
Current
input IC(5A)
75
76
Input 3
terminal
19
20
Common
output 4
Current input 47
Ie (5A)
48
Current
input Ie(5A)
77
78
Input 4
+ terminal
21
22
Input 1
+ terminal
Current input 49
IA (1A)
50
Current
input IA (1A)
79
80
Input 4
terminal
23
24
Input 1
terminal
Current input 51
IB (1A)
52
Current
input IB (1A)
81
82
Input 5
+ terminal
25
26
Input 2
+ terminal
Current input 53
IC (1A)
54
Current
input IC (1A)
83
84
Input 5
terminal
27
28
Input 2
terminal
Current input 55
Ie (1A)
56
Current
input Ie (1A)
Voltage
input Vr
Voltage
input Vr
P12y/EN FT/Fa5
User Guide
Page 12/96
1.1.6.3
P0072ENc
Input 7
+ terminal
57
58
Input 6
+ terminal
Output 5
Common
output 1
Case earth
connection
29
30
Terminal
RS485
Input 7
terminal
59
60
Input 6
terminal
Common
output 5
Output 1
(NC)
RS485 terminal
31
32
RS485 +
Input 8
61
(1)
+ terminal
62
Input COM
(1)
terminal
Output 6
Output1
(NO)
Vaux
+ terminal
33
34
Vaux
terminal
Input A
63
(1)
+ terminal
64
Input 9
(1)
+ terminal
Common
output 6
Common
output 2
Relay failed
(WD)
35
36
Common
"Watchdog"
Input C
65
(1)
+ terminal
66
Input B
(1)
+ terminal
Common
output 7
10
Output 2
(NC)
Relay
37
healthy (WD)
38
Current I1
67
meas. 1A/5A
68
Current I1
meas. 1A/5A
Output 7
11
12
Output 2
(NO)
39
40
Voltage
input VA
69
70
Voltage input
VA
Common
output 8
13
14
Output 3
Current input 41
IA (5A)
42
Current
input IA (5A)
Voltage
input VB
71
72
Voltage input
VB
Output 8
15
16
Common
output 3
Current input 43
IB (5A)
44
Current
input IB (5A)
Voltage
input VC/Vr
73
74
Voltage
input VC/Vr
Input 3
+ terminal
17
18
Output 4
Current input 45
IC(5A)
46
Current
input IC(5A)
Current I2
75
meas. 1A/5A
76
Current I2
meas. 1A/5A
Input 3
terminal
19
20
Common
output 4
Current input 47
Ie (5A)
48
Current
input Ie(5A)
Case earth
77
(2)
connection
78
RS485-2
(2)
term. Z
Input 4
+ terminal
21
22
Input 1
+ terminal
Current input 49
IA (1A)
50
Current
input IA (1A)
RS485-2
79
(2)
terminal
80
RS485-2
(2)
+ terminal
Input 4
terminal
23
24
Input 1
terminal
Current input 51
IB (1A)
52
Current
input IB (1A)
IRIG-B mod 81
(2)
terminal
82
IRIG-B mod
(2)
+ terminal
Input 5
+ terminal
25
26
Input 2
+ terminal
Current input 53
IC (1A)
54
Current
input IC (1A)
IRIG-B dem 83
(2)
terminal
84
IRIG-B dem
(2)
+ terminal
Input 5
terminal
27
28
Input 2
terminal
Current input 55
Ie (1A)
56
Current
input Ie (1A)
(3)
(3)
(1)
(3)
(3)
Available only for P127 5 opto-inputs option (product codes P127xx1 or P127xx3).
Input COM terminal is the common terminal for inputs 8 to 12.
(2)
Available only for P127 IRIG-B and 2nd rear port option option (product codes P127xx2
or P127xx3).
The 81 and 82 terminals are used to connect the optional BNC adaptor. This one must
be plugged according to the + and GND positions marked on the adaptor.
(3)
User Guide
P12y/EN FT/Fa5
Page 13/96
Menu structure
The relays menu is arranged in a tabular structure. Each setting in the menu is referred to
as a cell, and each cell in the menu may be accessed by reference to a row and column
address. The settings are arranged so that each column contains related settings, for
example all of the disturbance recorder settings are contained within the same column. As
shown in the figure, the top row of each column contains the heading that describes the
settings contained within that column. Movement between the columns of the menu can only
be made at the column heading level. A complete list of all of the menu settings is given in
the Menu Content tables (P12y/EH HI section).
Column header
OP
param
Config.
Measur.
Comm.
Protections
Autom. Ctrl
Records
Column
data
settings
P0106ENb
MENU STRUCTURE
1.3
Password
1.3.1
Password Protection
Password protection is applicable to most of the relay settings, especially to the selection of
the various alarm thresholds, trip thresholds, communication parameters, allocation of logic
inputs and outputs.
The password consists of four capital characters. When leaving the factory, the password is
set to AAAA. The user can define any combination of four characters.
Should the password be lost or forgotten, modification of the stored parameters is blocked. It
is then necessary to contact the manufacturer or his agent and a stand-by password specific
to the relay concerned may be obtained.
The programming mode is indicated with the letter "P" on the right hand side of the display
on each menu heading. The letter "P" remains present as long as the password is active
(5 minutes if there is no action on the keypad).
1.3.2
Password Entry
The input of the password is requested as soon as a modification of a parameter is made for
any one of the six/eight menus and the submenus. The user enters each of the 4 characters
and then validates the entire password with .
After 5 seconds, the display returns to the point of the preceding menu.
If no key is pressed inside of 5 minutes, the password is deactivated. A new password
request is associated with any subsequent parameter modification.
P12y/EN FT/Fa5
Page 14/96
1.3.3
User Guide
MiCOM P125/P126 & P127
1.3.4
1.4
1.4.1
1.4.2
User Guide
P12y/EN FT/Fa5
Page 15/96
microprocessor operation,
If the internal hardware or software fault is major (i.e. the relay cannot perform protection
functions), the WARNING LED (LED 3) lights up continuously.
If the internal hardware or software fault is minor (i.e. a communication failure that has no
influence on the protection and automation functions), the WARNING LED (LED 3) will flash.
Warning messages caused by internal hardware or software faults are:
< CALIBRATION ERROR >>
<< CLOCK ERROR >>
<< DEFAULT SETTINGS (*) >>
<< SETTING ERROR (**) >>
<< CT ERROR >>
<< COMMUNIC. ERROR >>
<< WATCH DOG >>
<< STAT RESET>>
(*) DEFAULT SETTINGS: Each time the relay is powered ON it will check its memory
contents to determine whether the settings are set to the factory defaults. If the relay detects
that the default settings are loaded an alarm is raised. The ALARM LED (YELLOW) will light
up and the Watch Dog contact will be activated.
Only one parameter in the relay's menu needs to be changed to suppress these messages
and to reset the watch dog. This alarm is only an indication to the user that the relay has its
default settings applied.
(**) SETTING ERROR: Should the CPU fails to get correctly store data during a setting
change, a "HARDWARE" ALARM will appear on the LCD display followed by "SETTING
ERROR" message (when pushing on the button). In addition, the ALARM LED (YELLOW)
will light up and the Watch Dog contact will be activated To reset this alarm it is necessary to
power ON and OFF the relay. Following this, the last unsuccessful setting change will then
need to be re-applied. If the alarm persists, i.e. the "SETTING ERROR" alarm is still
displayed, please contact Schneider Electric Customer Care Center for advice and
assistance.
Possible software alarm messages are:
I>
tI>
P12y/EN FT/Fa5
User Guide
Page 16/96
tI> PHASE
A
A
A
A
B
B
B
B
C
C
C
C
A
AB
AB
A
AB
AB
A
AB
ABC
A
AB
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
Self = self reset when time delayed alarm occurs (i.e. I> alarm is acknowledged when
tI> occurs),
Description
Type
Amps(n)
man
Recloser[79]
Blockedint.
locked
[79] ext. locked
auto
User Guide
P12y/EN FT/Fa5
Page 17/96
Alarm
Description
Type
Brkn.Cond.
man
CB Fail
man
CB Open NB
man
Conflict Recloser
auto
CTS
auto
dF/dt1 to dF/dt6
man
EQU. A to EQU.
H
inhib
F OUT
man
F1 to F6
I<
I>>
I>>>
I2>
I2>>
I2>>>
nd
rd
st
Ie>
Ie>>
Ie>>>
Ie_d>
Ie_d>>
Latched Relays
auto
Maintenance
mode
auto
P<
P<<
P>
nd
st
P12y/EN FT/Fa5
User Guide
Page 18/96
Alarm
Description
Type
P>>
st
Pe/IeCos>
Pe/IeCos>>
st
Q<
Q<<
st
Q>
Q>>
Recloser
Successful
auto
SF6 Low
auto
t U<
inhib
nd
t U<<
inhib
tAux1 to tAuxC
inhib
tF1 to tF6
Time delayed 1st, 2nd, 3rd, 4th, 5th and 6th frequency
threshold
man
Thermal Alarm
man
Thermal
Overload
man
tI<
man
tI>
man
nd
tI>>
man
tI>>>
man
st
tI2>
man
tI2>>
man
rd
tI2>>>
man
tIe>
man
nd
tIe>>
man
tIe>>>
man
tIe_d>
man
tIe_d>>
man
Toperating CB
man
tP<
man
tP<<
tP>
tP>>
tPe/IeCos>
nd
man
st
man
nd
man
st
User Guide
P12y/EN FT/Fa5
Page 19/96
Alarm
Description
Type
tPe/IeCos>>
st
tQ<
man
tQ<<
man
st
tQ>
man
tQ>>
man
Trip Circuit
Super.
man
tU>
man
tU>>
man
tUe>>>>
man
U<
nd
U<<
U>
nd
U>>
Ue>>>>
VTS
auto
1.5
General characteristics
1.5.1
Analogue Inputs
The analogue inputs for each relay are shown in the following table:
Type of Analogue Inputs
MiCOM
P125
MiCOM
P126
MiCOM
P127
1/0
2/3
2
Following is a description of the voltage inputs connection for the P127 relay.
Case A
2 phase to neutral voltage inputs
1 residual voltage input
VC is then calculated as VC= (VA+ VB)
To obtain a correct reading of the input voltage the exact voltage transformer ratio for Ve has
to be set.
P12y/EN FT/Fa5
Page 20/96
User Guide
MiCOM P125/P126 & P127
Case B
2 phase to phase voltage inputs
VCA is then calculated as VCA= (VAB + VBC)
Case C
3 phase to phase voltage inputs
No residual voltage input
Ve can be calculated as Ve = (VA+ VB+ VC )/3
On the MiCOM P125 relays rear terminals there is one current input rated 1A and one
current input rated 5A available and one voltage input. On the MiCOM P126 relay rear
terminals there are four current inputs rated 1A and four current inputs rated 5A
available and one voltage input. On the MiCOM P127 relay rear terminals there are
four current inputs rated 1A and four current inputs rated 5A available and three
voltages input.
By using the Cortec code (see the appropriate section) the user can choose the
voltage range for voltage inputs for the MiCOM P125 & P126 (one input) and P127
(three inputs).
All logic outputs can be programmed to respond to any of the available control or protection
functions. Logic inputs can be assigned to various control functions.
All logic digital inputs can be programmed to respond to any of the available control or
protection functions. Their supply level is the same as the power supply selected of the relay
by Cortec. They can be supplied in A.C or D.C current by Cortec choice.
The MiCOM relays are powered either from a DC or an AC auxiliary power supply.
Any short time voltage interruption (<50ms) is filtered and regulated through the auxiliary
power supply.
The front panel enables the user to navigate through the menu to access data, change
settings, read measurements etc.
Eight LEDs on the front panel allow a clear and simple presentation of events. The various
detected alarms are stored and can be displayed on the back-lit LCD.
No Password is required to read and acknowledge (clear) these alarm messages.
On their rear terminals the MiCOM P125, P126 & P127 relays have a standard RS485 port
available. The user can choose, by ordering, the communication protocol ModBus RTU, IEC
60870-5-103 or DNP3 (when available).
Using the communication channel RS485, all stored information (measurements, alarms,
and parameters) can be read and the settings can be modified if this functionality is allowed
by the chosen protocol.
Evaluation and modification of this data can be carried out on site with a normal PC and the
appropriate Schneider Electric software.
RS485 based communication allows MiCOM P125, P126 & P127 relays to be directly linked
to a digital control system.
All the available data is then placed at the disposal of the supervisor and can be processed
either local or remotely.
User Guide
P12y/EN FT/Fa5
2.
Page 21/96
MENU
The menu for the MiCOM P125, P126 & P127 relays is divided into the following sections.
To access these menus from the default display press .
To return to the default display from these menus or submenus press .
DEFAULT DISPLAY
OP PARAMETERS
ORDERS
CONFIGURATION
MEASUREMENTS
METERING
When displayed
COMMUNICATION
PROTECTION Gx
x = 1,2 or 1 to 8 (P127)
AUTOMAT. CTRL
RECORDS
P12y/EN FT/Fa5
User Guide
Page 22/96
2.1
OP PARAMETERS menu
To gain access to the OP PARAMETERS menu from the default display, press .
OP PARAMETERS
Password
****
Password
AAAA
WARNING:
Language
ENGLISH
Description
P125-2
Reference
MiCOM
Software Version
xx.x
Frequency
50 Hz
Active Group
Input
Status
7654321
0110110
Input
Status
CBA98
00000
Relay
Status
87654321
01011101
Date
Time
10/11/01
13:57:44
User Guide
P12y/EN FT/Fa5
Page 23/96
ORDERS menu
This menu gives the possibility:
to send open or close orders to the Circuit Breakers from the front panel. Open and close
orders are written in the event file. This action generates a Control Trip alarm, which can
be inhibited. If inhibited, the trip LED and the Alarm LED are not lit if the relay RL1 is
ordered by a control trip information (affected to an input in the configuration/inputs
submenu).
to start a disturbance recording from the protection relay.
ORDERS
Record reset
No
The reset order does not reset the latched trip output
relay RL1 or the latched output relays.
To change the setting, enter the password (if necessary).
In the confirmation ? cell, select Yes to apply the reset.
Open Order
Close Order
No
No
No
P12y/EN FT/Fa5
User Guide
Page 24/96
2.3
CONFIGURATION menu
The following parameters can be set in the CONFIGURATION menu:
ratios for the residual voltage and phase voltage transformers (VT),
The choice to enable alarms functionality as well as self reset on trip or instantaneous
protection or other function,
Transfo. ratio
Led 5
Led 6
Led 7
Led 8
Inputs
configuration
Output
relays
Group
Select
Alarms
Date
General
options
(1)
(1)
To gain access to the CONFIGURATION menu from the default display, press followed
by until the desired submenu header is displayed.
2.3.1
General Options
VT Connection
2Vpp+Vr
P127 only
Selection of the VT connection type (3Vpn, 2Vpp+Vr, 2Vpn+Vr).
3Vpn = 3 Phase-Neutral connection
2Vpp+Vr = two phase to phase plus an open delta connection
2Vpn+Vr = two phase to neutral plus an open delta connection
See 2.3.2 to select VTs configuration
VT Protection
Protect PN
User Guide
P12y/EN FT/Fa5
A-B-C
CTm1 phase ?
CTm2 phase ?
Page 25/96
P126 and P127 only
Choose the phase rotation between either A-B-C or A-C-B.
none
P127 only
Configuration the first measurement CT phase: select the
phase physically connected to CTm1.
(Setting choices: none, IA, IB, IC)
none
P127 only
Configuration the second measurement CT phase: select
the phase physically connected to CTm2.
(Setting choices: none, IA, IB, IC)
Quadrant conv ?
Quadrant 1
P127 only
Configuration of the active and reactive power quadrant
according to the following diagram.
(Setting choices: 1 to 4)
Im (+)
Quadrant 1
Quadrant 2
Re ()
Re (+)
Quadrant 3
Quadrant 4
Im ()
Default Displays
RMS IA IB IC IN
P3976ENa
IB RMS current
IN RMS current
P125 only
Choose a label (displayed with the associated
measurement value or in alarms messages) for earth
Possible choices: N, o or E (modified after entering the
password)
Phases/Earth Text
L1 L2 L3 N
xx A
xx A
xx A
P12y/EN FT/Fa5
User Guide
Page 26/96
dF/dt Cycles.nb.
dF/dt Validat.nb=
Inh.Block dF/dt
>20 Hz/s
No
Time Synchro.
IRIG-B
IRIG B
MODULATED
(1)
(2)
2.3.2
P127
P127 with optional functions only.
only
Voltage Connections
For the P127, it is important to select the VTs configuration in the Configuration / General
Options / VT Connection submenu, according to the relay wiring for a correct functionality of
the voltage protections, or of the three phase and earth fault directional protections.
For the P127, there are three connection schemes for the VTs (see section P12y/EN CT).
2.3.2.1
User Guide
P12y/EN FT/Fa5
Page 27/96
2.3.2.3
2.3.3
Transfo. Ratio
5A
E/Gnd CT primary
5A
E/Gnd CT sec
Line CT primary
Line CT sec
5A
Line VT primary
0.10 kV
Line VT sec
100.0 V
P12y/EN FT/Fa5
User Guide
Page 28/96
The two following lines are only displayed when the connection mode 2Vpp+Vr or 2Vpn+Vr
is selected.
E/Gnd VT primary
0.10 kV
E/Gnd VT sec
100.0 V
The following lines are only displayed when the measurement CT option is present.
Displays the rated primary current of the measurement CT,
from 1 to 9999 (2).
1A
WARNING:
These measurement values are called derived measurements. They depend on the selected
electrical voltage connection mode.
2.3.4
P125
P126
P127
Information
st
Information
P125
P126
P127
Ie>, Ie>>,
Ie>>>
tIe>, tIe>>,
tIe>>>
Ie_d>, Ie_d>>
tIe_d>,
tIe_d>>
User Guide
P12y/EN FT/Fa5
Page 29/96
P125
P126
P127
Information
st
Pe/IeCos>
Pe/IeCos>>
tPe/IeCos>
tPe/IeCos>>
P125
P126
P127
Information
st
I2>, I2>>,
I2>>>
tI2>, tI2>>,
tI2>>>
P126
P127
Thermal protection
TEXT
P125
Therm Trip
Information
Trip on Thermal overload
P125
P126
P127
Information
I<
tI<
P126
P127
Overvoltage protection
TEXT
P125
Information
st
U>, U>>
tU>, tU>>
Undervoltage protection
TEXT
P125
P126
P127
Information
U<, U<<
tU<, tU<<
P125
P126
P127
Information
Ue>>>>
tUe>>>>
P125
P126
P127
Information
V2>, V2>>
tV2>, tV2>>
P125
P126
P127
Information
Broken conductor detection
P12y/EN FT/Fa5
User Guide
Page 30/96
CB Fail
TEXT
P125
P126
P127
Information
P125
P126
P127
Information
CB Fail
Logic inputs
TEXT
Input1 to
Input4
Input5 to
Input7
Input8 to
InputC
Autoreclose function
TEXT
P125
P126
P127
Information
79 Run
79i.Blocked
79e.Blocked
Auxiliary timers
TEXT
P125
P126
P127
Information
tAux1 to tAux4
P126
P127
Information
tAux5 to tAux7
tAux8 to tAuxC
t SOTF FUNCTION
TEXT
P125
t SOTF
P125
P126
P127
Information
st
P>, P>>
tP>, tP>>
P125
P126
P127
Information
st
P<, P<<
tP<, tP<<
User Guide
P12y/EN FT/Fa5
Page 31/96
P125
P126
P127
Information
st
Q>, Q>>
tQ>, tQ>>
P125
P126
P127
Information
st
Q<, Q<<
tQ<, tQ<<
P125
P126
P127
Information
VTS
CTS
Frequency protection
TEXT
P125
P126
P127
Information
st
F1 to F6
tF1 to tF6
F Out
P125
P126
dF/dt1 to
dF/dt6
P127
X
Information
st
Logic Equation
TEXT
P125
P126
P127
tEQU.A to
tEQU.H
Information
Results of equations A to H.
P12y/EN FT/Fa5
User Guide
Page 32/96
CONFIGURATION
Heading Led submenu.
Led
2.3.5
Inputs
Inputs
:7654321
Inputs
:CBA98
Voltage Input
2.3.6
DC
Fail Safe R.
87654321
0000000
Maintenance Mode
Yes
User Guide
P12y/EN FT/Fa5
Page 33/96
Change Group
INPUT
Setting Group
Target group
P12y/EN FT/Fa5
User Guide
Page 34/96
Group if low
level
G1
Group if high
level
G2
Group Copy ?
No
copy from
G1
copy to
G1
2.3.8
Submenu Alarms
CONFIGURATION
Heading of Alarms submenu.
Alarms
Inst. Self-reset
Reset Led on
Fault
Yes
Yes
User Guide
P12y/EN FT/Fa5
Page 35/96
Event
Label description
Ctrl_Trip ?
tI< ?
tU< ?, tU<< ?
tU> ?, tU>> ?
tV2> ?, tV2>> ?
tP< ? / tP<< ?
tQ< ? / tQ<< ?
F1 ? to F6 ?
F.out
taux1? to tAux4? Aux1 (to Aux 4) delayed by tAux1 (to tAux 4) time
taux5? to tAux7? Aux5 (to Aux 7) delayed by tAux5 (to tAux 7) time
X
X
Case
RL1 assigned to Ctrl Trip
No
No
Yes
Yes
No
Yes
No
Yes
Off
Off
On
Off
blinking
Off
blinking
Off
Yes
No
Yes
No
Yes
Yes
Yes
Yes
No
No
Yes
Yes
RL1 activated
No
No
Yes
Yes
Result:
LED trip
LED Alarm
2.3.9
Submenu Date
CONFIGURATION
Date
Date Format
PRIVATE
P12y/EN FT/Fa5
User Guide
Page 36/96
2.4
MEASUREMENTS menu
By going to the MEASUREMENTS menu various system measurement values can be
shown on the LCD.
The displayed voltage measures depend on which wiring scheme is choose.
The direct measure is the signal wires to the terminal.
The derived measure is the calculated.
The RMS value is provided for the direct measures.
The fundamental value is provided for the derived (calculated) measures.
To gain access to the MEASUREMENTS menu from the default display, press then
until the header of menu is reached.
The following table lists the items available in the measurements menu for the P125, P126 &
P127 relays.
DISPLAY
UNIT
MEASUREMENTS
INFORMATION
Heading Measurements menu
Frequency
50.00 Hz
I A (or I L1, or I R)
I B (or I L2, or I S)
I C (or I L3, or I T)
IN (or I o, or I E)
I1
I2
RATIO I2/I1
UA
UB
UC
When a 3Vpn (three phases neutral) or 2Vpn+Vr (two phaseneutral + open delta connection) connection mode is choosen,
displays the RMS voltage value of phase A, or B or C (2),
UAB
UBC
UCA
UN
Pe
IeCos
IN ^ UN Angle
IA ^ IB Angle
IA ^ IC Angle
User Guide
P12y/EN FT/Fa5
Page 37/96
UNIT
INFORMATION
When a 3Vpn (three phases neutral) or 2Vpn+Vr (two phaseneutral + open delta connection) connection mode is choosen,
displays the angle value between phase IA and voltage VA, or
between phase IA and voltage VB, or between phase IA and
voltage VC
Va
Ia
Ic
Vc
Ib
IA ^ VAB Angle
IA ^ VBC Angle
IN ^ UN Angle
Vb
P03978ENa
IAm
UBC
ICm
IBm
UCA
P03978ENa
Cos (Phi)
Energy
RST=[C]
VAR As above for the positive & negative reactive power (see
P12y/EN AP).
Maximum measured value displayed is 9999MVAr. If the
measured value is above, this display remains on the LCD.
VA As above for the total apparent power (product of the perelement Volts and Amps).
The maximum measured value displayed is 9999MVA. If the
measured value is above, this display remains on the LCD.
P12y/EN FT/Fa5
User Guide
Page 38/96
UNIT
INFORMATION
3Ph VAHours
I N fn
RST=[C]
Displays the earth current I N (true RMS value) minus the earth
current value at the fundamental frequency (value of the
harmonic).
To clear the value, press
THERMAL STATUS
RST = [C]
Max IA Rms
Max IB Rms
Max IC Rms
Average IA Rms
Average IB Rms
Average IC Rms
Displays the true RMS maximum line voltage value for UAB or
UBC (2).
Displays the true RMS average line voltage value for UAB or
UBC (2).
MAX SUBPERIOD
RST = [C]
MAX SUBPERIOD
IA Rms
IB Rms
IC Rms
ROLLING AVERAGE
RST = [C]
ROLLING AVERAGE
IA Rms
IB Rms
IC Rms
Reclose Stats
RST = [C]
Allows the user to clear the statistics stored for the autoreclose
function
To clear the values, press (1).
Total recloses
Cycle1 Recloses
Cycle2 Recloses
Cycle3 Recloses
Cycle4 Recloses
(1)
(2)
User Guide
P12y/EN FT/Fa5
Page 39/96
frequency,
measured currents, total harmonics distortion (THD) and total demand distortion
(TDD), K Factor, measured harmonics,
To activate this menu, activate at least one CTm1 phase ? or CTm2 phase ? in the
CONFIGURATION / General options menu (a measurement CT must be connected). The
metering menu displays currents and voltages according to the table presented in the
P12y/EN AP section.
To access METERING menu from the default display, press then until the header of
menu is reached. The submenus of the Metering are:
The following table lists the items available in the Metering menu for the P127 relay:
2.5.1
Submenu Frequency
DISPLAY
UNIT
INFORMATION
Submenu FREQUENCY
Frequency
P12y/EN FT/Fa5
User Guide
Page 40/96
2.5.2
Submenu Currents
DISPLAY
UNIT
INFORMATION
Submenu CURRENTS
Phase A Phase B Phase C
IAm
IBm
ICm
Ic
KAm
KBm
KCm
P03978ENa
Ib
KAM = 100
IAmhi i
i=1
10
IAmhi
i =1
nd
to 10th harmonics of
User Guide
P12y/EN FT/Fa5
Page 41/96
Submenu Voltages
The voltage metering depends on the VT connection and VT Protection settings
(Configuration / General options menu). For more information about connection modes,
refer to 2.3.2. The voltage calculation mode, according to the connection, is given in the
section P12y/EN AP.
2.5.3.1
Connection mode = 3Vpn AND Protect P-N, or 2Vpn+Vr AND Protect P-N
DISPLAY
UNIT
INFORMATION
Submenu VOLTAGES:
Phase A Phase B Phase C
VAm
VBm
VCm
Ic
Vc
Vb
Ib
Ibm ^ Vb Icm ^ Vc
P03978ENa
Icm
Vc
Ibm
VAmh2
to
VAmh10
Vb
P03978ENa
P12y/EN FT/Fa5
User Guide
Page 42/96
2.5.3.2
UNIT
INFORMATION
Submenu VOLTAGES:
Phase A Phase B Phase C
UABm
UBCm
THDAm THDBm
UCAm
THDCm
UAB
IAm
UBC
ICm
IBm
P03978ENa
UCA
Iam
UBC
Icm
Ibm
UCA
P03978ENa
nd
to 10th harmonics of
Submenu Powers
DISPLAY
UNIT
INFORMATION
Submenu POWERS
Pm
Qm
Sm
DPF
See 2.5.6 to see the convention for the positive (+) or negative () sign.
User Guide
P12y/EN FT/Fa5
Page 43/96
Submenu Energies
DISPLAY
UNIT
INFORMATION
Submenu ENERGIES
RST = [C]
Date
Time
Export Power
Import Power
Lagging VARs
Leading VARs
See 2.5.6 to see the convention for the positive (+) or negative () sign.
P12y/EN FT/Fa5
User Guide
Page 44/96
2.5.6
LOAD
Metering point
ACTIVE POWER: P is positive when the power is from the source to the load
REACTIVE POWER: Q is positive when the load is inductive.
Im (+)
Quadrant 1
Quadrant 2
Re ()
Re (+)
Quadrant 3
Quadrant 4
Im ()
P3976ENa
with:
Quadrant 1
Quadrant 2
Quadrant 3
Quadrant 4
Active (P)
Reactive (Q)
Export Wh (Ea+)
Import Wh(Ea)
Power
Energy
NOTE:
User Guide
P12y/EN FT/Fa5
Page 45/96
COMMUNICATION menu
The COMMUNICATION menu depends:on the type of communications protocol: ModBus,
IEC 60870-5-103 or DNP3.0 and on the connection type (P127 optional configuration)
To gain access to the COMMUNICATION menu from the default display, press then
until the menu is reached.
COMMUNICATION
HMI ?
No
COMM1 ?
No
COMM2 ?
WARNING:
2.6.1
No
HMI submenu
The following menu is displayed when HMI = Yes is selected.
HMI ?
Yes
Relay Address
Modbus
Date format
2.6.2
Private
Yes
19200 bd
Parity
Stop Bits
Relay Address
None
1
1
P12y/EN FT/Fa5
User Guide
Page 46/96
2.6.3
GI select.
Basic
Measur. upload
ASDU 3.4
Yes
Measur. upload
ASDU 9
Yes
Measur. upload
Other
Yes
Events + Measur.
Blocking
Yes
Command
Blocking
Yes
Command duration
0.1s
COMM1 only
In order to avoid a transmission conflict between the two
RS485 ports (optional configuration), transmission using the
second port can be time-delayed. Transmission and
reception with comm2 will start after the end of the
Command duration.
Setting range: from 0.1 to 30s, step 0.1s
User Guide
P12y/EN FT/Fa5
Page 47/96
PROTECTION menu
The protection menus are designated as PROTECTION G1 and PROTECTION G2 menu
(available for the MiCOM P125 and P126) and PROTECTION G1 to PROTECTION G8
menu available for the MiCOM P127 relay. By opening the PROTECTION menu the user
can program the parameters of various protection functions and settings (thresholds, time
delay, logic) associated with each of the phase or earth protection functions.
The various submenus are:
PROTECTION
G1 / G2 G8
[32] Phase
power
(2)
[32N] Earth
Wattmetric
[37] Under
current
(1)
(1)
[79]
Autoreclose
[67/50/51]
Phase OC
(1)
[67N]E/
Gnd
[46] Neg
Seq OC
(1)
[49] Therm
OL
[59N] residual(1)
over voltage
(1)
(2)
2.7.1
(1)
[81]
Frequency
(1)
(2)
I> ?
I>> ?
No
Yes
P12y/EN FT/Fa5
User Guide
Page 48/96
I>>> ?
2.7.1.1
Yes
I>
I>
Torque
I>
Trip Zone
Delay Type
Yes
10.00 In
90
10
DMT
DMT
150.00 s
DMT is selected
Sets the time delay associated with I>. The setting range
is from 0.040 to 150.0s (step 10ms).
User Guide
P12y/EN FT/Fa5
Page 49/96
RI
2.500
60 ms
Yes
1.000
Rtms
t Reset
I> >> >>>
Interlock
2.7.1.2
IEC-STI
0.025
0.10 s
Yes
I>>
I>>
Torque
I>>
Trip Zone
Trip
Trip +/-
Yes
10.00 In
90
10
P12y/EN FT/Fa5
User Guide
Page 50/96
Delay Type
DMT
I>>>
Yes
10.00 In
I>>>
Torque
90
I>>>
Trip Zone
tI>>>
2.7.2
10
150.00 s
[67N] E/GND
Ie> ?
No
User Guide
P12y/EN FT/Fa5
Ie>>> ?
Ie_d> ?
Ie_d>> ?
2.7.2.1
No
No
No
No
Page 51/96
Setting choice: DIR, Yes or No
- Yes: the second earth overcurrent threshold (Ie>>)
protection is enabled. The second earth overcurrent
threshold submenu (see 2.7.2.2) is displayed.
- DIR: the relay operates like a three-phase directional
overcurrent protection and the directional choice window
(see 2.7.2.2) is displayed.
- No: the second earth overcurrent threshold (Ie>>) is not
enabled, and the next menu is the Ie>>> ? menu.
Setting choice Yes, No, DIR and Peak
- Yes: the third earth overcurrent threshold (Ie>>>)
protection is enabled. The third earth overcurrent threshold
submenu protection (see 2.7.2.3) is displayed.
- DIR: the relay operates like a three-phase directional
overcurrent protection and the directional choice window
(see 2.7.2.3) is shown.
- PEAK: The third threshold can be set to operate on the
peak of the measured phase current. It compares the
biggest peak value of the measured current against the
setting (see 2.7.2.3).
- No: the third earth fault threshold (Ie>>>) is not enabled.
P127 only.
Setting choice Yes, No or DIR
Yes: the first derived earth overcurrent threshold (see
2.7.2.4) is enabled.
No: the first derived earth overcurrent threshold is disabled.
P127 only.
Setting choice Yes, No or DIR
Yes: the second derived earth overcurrent threshold (see
2.7.2.5) is enabled.
No: the second derived earth overcurrent threshold is
disabled.
Ie>
Ue>
Ie>
Torque
Ie>
Trip Zone
Yes
1.000 Ien
5.0V
10
P12y/EN FT/Fa5
User Guide
Page 52/96
Delay Type
DMT
DMT
150.00 s
150.0 s
DMT is selected
Sets the time delay associated with Ie>. The setting
range is from 0.040 to 150.0s (step 10ms).
Sets the reset time value from 0 to 100s (step 10ms).
RI
1.000
0.10 s
Yes
IEC-STI
1.000
Rtms
t Reset
Ie> >> >>>
Interlock
0.025
0.10 s
Yes
User Guide
P12y/EN FT/Fa5
Page 53/96
Ie>>
Ue>>
Ie>>
Torque
Ie>>
Trip Zone
Delay Type
Yes
1.000 Ien
5.0 V
90
10
DMT
P12y/EN FT/Fa5
User Guide
Page 54/96
2.7.2.3
Ie>>>
Ue>>>
Ie>>>
Torque
Ie>>>
Trip Zone
tIe>>>
tReset
2.7.2.4
Yes
1.000 Ien
5.0 V
90
10
0.04 s
0.10 s
Sets the value for the reset time, from 0 to 100 s, in steps of
10ms.
Ie_d>
Ue(Ie_d>)
Ie_d>
Torque
Yes
1.000 Ien
100.0 V
90
User Guide
P12y/EN FT/Fa5
Delay Type
10
DMT
Page 55/96
If Ie_d> ? = DIR only
Sets angle value for the Trip Zone. This defines the
operating region to either side of the torque angle. Setting
range is from 10 to 170, in steps of 1.
Selects the time delay type associated with Ie_d>.
Setting choices DMT: see a, IDMT: see b, RI: see c.
DMT
DMT is selected
0.000 s
Set the value for the time delay associated with Ie_d>
from 0.00s to 150.0s (step 0.01s)
0 ms
Ie_d>>
Ue(Ie_d>>)
Ie_d>>
Torque
Ie_d>>
Trip Zone
Delay Type
Yes
1.000 Ien
100.0 V
90
10
DMT
P12y/EN FT/Fa5
User Guide
Page 56/96
DMT is selected
DMT
Set the value for the time delay associated with Ie_d>>
from 0.00s to 150.0s (step 0.01s)
0.000 s
0 ms
2.7.3
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Derived
measurement
Derived
measurement
Derived
measurement
Derived
measurement
Derived
measurement
Derived
measurement
Derived
measurement
Derived
measurement
Derived
measurement
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Derived
measurement
Derived
measurement
Derived
measurement
Derived
measurement
Derived
measurement
Derived
measurement
Derived
measurement
Derived
measurement
Derived
measurement
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
User Guide
P12y/EN FT/Fa5
Page 57/96
Threshold setting
In the following menu, default menu displayed for P>, P>>, P<, P<<, Q>, Q>>, Q< and Q<<
is noted 10000 1W. The value displayed on MiCOM P127 HMI depends on the input
voltage range and line secondary CT parameters. The following table gives the various
cases of the setting ranges:
Input voltage
range
2-130V
10-480V
Line
secondary
CT
Setting range
Min
Max
Step
Default value
Overpower
Underpower
1A
1 1W
10000 1W
1 1W
10000 1W
1 1W
5A
1 5W
10000 5W
1 5W
10000 5W
1 5W
1A
5 1W
40000 1W
1 1W
40000 1W
5 1W
5A
5 5W
40000 5W
1 5W
40000 5W
5 5W
To obtain the power value in W, multiply the selected number by 1W or 5W. Example, for
100:
if the secondary of the CT = 1A, the HMI will display 100 1W and P> = 100W,
if the secondary of the CT = 5A, the HMI will display 100 5W and P> = 500W.
PROTECTION
[32] Directional Power
2.7.3.2
P>
No
10000x 1W
P12y/EN FT/Fa5
User Guide
Page 58/96
Directional Angle
tP>
0.00 s
P>> ?
P>>
No
10000x 1W
Directional Angle
tP>>
2.7.3.3
0.00 s
Q>
No
10000x 1W
Directional Angle
tQ>
Q>> ?
0.00 s
No
User Guide
P12y/EN FT/Fa5
10000x 1W
Directional Angle
tQ>>
2.7.3.4
0.00 s
Page 59/96
If Q>> ? = Yes only
Sets the value for the second reactive overpower threshold
Q>>.
Default value: 10kW or 40kW or 50kW or 200kW (see
2.7.3.1)
If Q>> ? = Yes only
Selection of the directional angle between reactive power
and triggering power.
Setting range from 0 to 359, step 1
If Q>> ? = Yes only
Sets the time delay associated with Q>>.
The setting range is from 0 to 150s, in steps of 10ms.
P<
No
1x 1W
Directional Angle
tP<
0.00 s
P<< ?
P<<
No
10000x 1W
Directional Angle
tP<<
0.00 s
P12y/EN FT/Fa5
User Guide
Page 60/96
2.7.3.5
Underpower protection
This directional power protection part follows Q>> (if No) or tQ>> menu. This part of the
menu monitors the active underpower thresholds Q< and Q<<.
Q< ?
No
Q<
1x 1W
Directional Angle
tQ<
0.00 s
Q<< ?
Q<<
No
10000x 1W
Directional Angle
tQ<<
2.7.4
0.00 s
[32N] Earth
Wattmetric
[32N] Mode:
Pe> ?
Pe
No
User Guide
P12y/EN FT/Fa5
Pe> Pe>>
ANGLE
2.7.4.1
No
90
Page 61/96
Selection of the second earth wattmetric threshold (Pe>>)
protection. Setting choice: No, Yes
Yes the second earth wattmetric threshold (Pe>> IeCos>>) protection menu is shown (see 0)
Only activated if at least one of the Pe/IeCos thresholds is
enabled.
Displays the setting angle for Pe/IeCos from 0 to 359
(step 1). This angle is the RCA angle for the directional
earth fault power.
20 x 1 W
Sets the value for the first earth wattmetric threshold Pe>.
High sensitivity current: 0.001 to 1 In
Input voltage range 2-130V: The setting range is from 0.2
to 20 x Ien W, in steps of 0.02 x Ien W.
Input voltage range 10-480V: The setting range is from 1
to 80 x Ien W, in steps of 0.1 x Ien W.
The setting range for IeCos> is from 0.002 to 1Ien, in steps
of 0.001.
Medium sensitivity current: 0.01 to 8 In
Input voltage range 2-130V: The setting range is from 1
to 160 x Ien W, in steps of 0.1 x Ien W.
Input voltage range 10-480V: The setting range is from 4
to 640 x Ien W, in steps of 0.5 x Ien W.
The setting range for IeCos> is from 0.01 to 8 Ien, in steps
of 0.005.
Low sensitivity current: 0.1 to 40 In
For range 2-130V from 10 to 800 x Ien W, in steps of 1 x
Ien W.
For range 10-480V from 40 to 3200 x Ien W, in steps of 5
x Ien W.
The setting range for IeCos> is from 0.1 to 40 Ien, in steps
of 0.01.
Delay Type
t Pe>
TMS
DMT
150.00 s
1.000
1.000
P12y/EN FT/Fa5
User Guide
Page 62/96
RTMS
tReset
2.7.4.2
1.000
0.10 s
Yes
20 x 1 W
tPe>>
tReset
1.00 s
1.00 s
Sets the value for the reset time from 0 to 100 s, in steps of
10ms.
User Guide
P12y/EN FT/Fa5
Page 63/96
I2>> ?
I2>>> ?
2.7.5.1
No
No
No
I2>
Delay Type
tI2>
TMS
Yes
1.00 In
DMT
150.00 s
1.000
1.000
P12y/EN FT/Fa5
User Guide
Page 64/96
RTMS
1.000
tReset
2.7.5.2
0.10 s
Yes
I2>> =
t I2>>
5.00 In
150.00 s
I2>>>
t I2>>>
2.7.6
2.7.5.3
Yes
10.00 In
Sets the value for the third threshold of the negative phase
sequence overcurrent I2>>, from 0.5 to 40In (step 0.01In).
150.00 s
[49] Therm OL
Therm OL ?
I >
Te
K
Trip
Yes
0.50 In
10 mn
1.00
Sets the value for the K factor associated with the thermal
overload function, from 1 to 1.50 (step 0.01).
100%
User Guide
P12y/EN FT/Fa5
Alarm
2.7.7
Yes
80%
Page 65/96
Setting choice Yes or No.
Yes: the thermal overload alarm function is enabled. Then
the following menu is displayed.
No: the thermal overload function is not enabled and the
next menu is not activated.
Sets the percentage applicable to the thermal overload
alarm threshold, from 50 to 200% (step 0.01).
start as soon as the current of one phase is below I< threshold value (OR of the 3
phases current)
trip if the current of one phase - at least - remains below this threshold during more
than tI<.
PROTECTION G1
Heading of [37] undercurrent submenu.
[37] Under
Current
I< ?
I<
t I<
Yes
0.10 In
Sets the value for the undercurrent threshold I<, from 0.1 to
1In, in steps of 0.01In.
150.00 s
Sets the time delay associated with I<, from 0 to 150 s (step
10ms).
P12y/EN FT/Fa5
User Guide
Page 66/96
2.7.8
[59] Phase
Over Voltage
U> ?
AND
t U>
U>> ?
260.0 V
600.00 s
OR
If U> ? = AND or OR
Sets the value for the alarm threshold:
- Input voltage range 2130V: from 1 to 260V (step 0.1V).
- Input voltage range 10480V: from 10 to 960V (step0.5V).
If U> ? = AND or OR
Sets the time delay associated with U>, from 0 to 600s
(step 10ms).
Setting choice: No, AND or OR
Selection of the second phase overvoltage threshold (U>>)
protection.
If AND or OR is selected, the second phase overvoltage
threshold (U>>) protection is enabled. The second phase
overvoltage threshold (U>>) submenu is displayed,
if OR is selected, the second overvoltage stage alarm is emitted if
one phase (at least) is faulty. If AND is selected, this alarm
appears when the stage appears on the three phases.
t U>>
260.0 V
600.00 s
If U>> ? = AND or OR
Sets the value for the second phase overvoltage threshold
(U>>).
- Input voltage range 2130V: from 2 to 260V (step of 0.1V).
- Input voltage range 10480V: from 10 to 960V (step 0.5V).
If U>> ? = AND or OR
Sets the time delay associated with U>>, from 0 to 600s
(step 10ms)
User Guide
P12y/EN FT/Fa5
Page 67/96
[27] Phase
Under Voltage
U< ?
Yes
t U<
5.0 V
150.00 s
U<<
t U<<
Yes
2.0 V
600.00 s
If U< ? = AND or OR
Sets the value for the first phase undervoltage threshold
(U<).
- Input voltage range 2130V: from 2 to130V (step 0.1V).
- Input voltage range 10 480V: from 10 to 480V (step
0.5V).
If U< ? = AND or OR
Sets the time delay associated with U< from 0 to 600s,
(steps 10ms).
If U< ? = AND or OR
This function inhibits undervoltage protection on circuit
breaker (52A) trip. Setting choice Yes or No.
Setting choice: Yes or No
Selection of the second phase undervoltage threshold
(U<<) protection.
Yes, the second phase undervoltage threshold (U<<) is
enabled. The second phase undervoltage threshold (U<<)
protection submenu is displayed.
No: The second phase undervoltage threshold (U<<)
protection is not enabled, and no new window will be
shown.
If U<< ? = AND or OR
Sets the value for the second phase undervoltage threshold
(U<<).
- Input voltage range 2130V: from 2 to 260V (step 0.1V),
- Input voltage range 10480V: from 10 to 960V (step 0.5V).
If U<< ? = AND or OR
Sets the time delay associated with U<< from 0 to 600s
(step 10ms).
If U<< ? = AND or OR
This function inhibits undervoltage protection on circuit
breaker (52A) trip. Setting choice Yes or No.
P12y/EN FT/Fa5
User Guide
Page 68/96
2.7.10
[59N] Residual
Over Voltage
Ue>>>> ?
Yes
Ue>>>>
t Ue>>>>
2.7.11
5.0 V
600.00 s
V2> ?
NO
tV2>
V2>> ?
15.0 V
If V2> ? = YES
Sets the voltage for the first V2> alarm threshold:
- Input voltage range 57130V: from 1 to 130V (step 0.1V).
- Input voltage range 220480V: from 4 to 480V (step 0.5V).
5.00 s
If U> ? = YES
Sets the operating time delay associated with V2>, from 0
to 100s (step 10ms).
YES
User Guide
P12y/EN FT/Fa5
260.0 V
tV2>>
2.7.12
5.00 s
Page 69/96
If V2>> ? = YES
Sets the voltage for the second V2>> alarm threshold:
- Input voltage range 57130V: from 1 to 130V (step 1V).
- Input voltage range 220480V: from 4 to 480V (step 0.5V).
If U>> ? = YES
Sets the operating time delay associated with V2>>, from 0
to 100s (step 10ms).
and
In addition to these settings, the user can fully link the autoreclose function to the protection
function using the menus PROTECTION G1 / Phase OC and PROTECTION/ E/Gnd.
PROTECTION G1
Heading of [79] AUTORECLOSE submenu.
[79] Autoreclose
Autoreclose ?
2.7.12.1
Yes
Yes
P12y/EN FT/Fa5
User Guide
Page 70/96
2.7.12.2
2.7.12.3
Max cycles nb
Time period
2.7.12.4
Yes
10
10 mn
CB Status
52A
52B
-------------------
Valid
Invalid
Invalid
Valid
Within the tD a further time window is active.This time window starts together to the td.It
expires after 50ms.
If within this time window a threshold involved in the trip of the CB and in the ARC cycle is
intermittent the ARC will be lock.
Dead Time
tD1
0.30 s
Displays setting value of the first cycle dead time (tD1) for
the autoreclose function from 0.01 to 300s (step 10ms).
Dead Time
tD2
180.00 s
Dead Time
tD3
180.00 s
Dead Time
tD4
180.00 s
User Guide
P12y/EN FT/Fa5
2.7.12.5
Dead Time
tI>
tI>>
tI>>>
0.05 s
0.05 s
0.05 s
DeadTime
tIe>
tIe>>
tIe>>>
0.05 s
0.05 s
0.05 s
Sets the value after a first, second and third trip This dead
time is used with an IDMT electromagnetic relay, and starts
when the CB opens. The induction disk returns to its initial
position during this additional time
Setting range is from 50ms to 600s (step 10ms).
As above for IE>, IE>> and IE>>>
Setting range is from 50ms to 600s (step 10ms).
Reclaim Time
tR
180.00 s
Set the Reclaimer time value (tR). The reclaim time , starts
when the CB has closed. Setting range is from 20ms to
600s (step 10ms).
After the reclaim time, if the circuit breaker does not trip
again, the autoreclose function resets; otherwise, the relay
either advances to the next shot that is programmed in the
autoreclose cycle, or, if all the programmed reclose
attempts have been accomplished, it locks out.
If the protection element operates during the reclaim time
following the final reclose attempt, the relay will lockout and
the autoreclose function is disabled until the lockout
condition resets.
Inhib Time
tI
5.00 s
E/Gnd Cycles
2.7.12.6
Page 71/96
4321
1101
CYCLES
tI>>
4321
1101
CYCLES
tI>>>
4321
1101
CYCLES
tIe>
4321
1101
CYCLES
tIe>>
4321
1101
CYCLES
tIe>>>
4321
1101
P12y/EN FT/Fa5
User Guide
Page 72/96
2.7.13
CYCLES
tPe/Iecos>
4321
1101
CYCLES
tPe/Iecos>>
4321
1101
CYCLES
tAux1
4321
1101
CYCLES
tAux2
4321
1101
[81] Frequency
F1 ?
No
50 Hz
Displays setting value for the first alarm threshold, from 45.1
to 64.9Hz (step 0.01 Hz).
0.00 s
dF/dt1 ?
dF/dt1=
No
1.0 Hz/s
User Guide
P12y/EN FT/Fa5
Page 73/96
AUTOMAT.
CTRL
Trip
Commands
Latch
Relays
Blockin
Logic
Inrush
Blocking
(3)
Inputs
1/2/3/4/5/6/7
Brkn.
Cond ?
(2)
(3)
CT
Supervision
Logic
select 1/2
(2)
Output
relays
Cold
Load PU
(2)
51V
(3)
(3)
VT
Supervision
CB Fail
(2)
(2)
CB
Supervision
SOTF
Comm.Order
(3)
delay
(1)
(2)
(3)
2.8.1
(1)
(2)
Logic
Equations
(2)
INFORMATION
Trip tIe_d> or
tIe_d>>
Trip Thermal
Trip tPe/IeCos>,
tPe/IeCos>>
st
P12y/EN FT/Fa5
User Guide
Page 74/96
tUe>>>>
Trip dF/dt1 to
dF/dt6
INFORMATION
Trip tEQU A to
tEQU H
AUTOMAT. CTRL
Heading of Trip Commands submenu.
Trip Commands
function
No
2.8.2
2.8.2.1
User Guide
P12y/EN FT/Fa5
Page 75/96
AUTOMAT. CTRL
2.8.3
Latch Relays
Heading of submenu.
Latch
:87654321
01001000
INFORMATION
tIe_d> or
tIe_d>>
tP> or P>>
tP< or tP<<
tQ> or tQ>>
tQ< or tQ<<
tI2>, tI2>>or
tI2>>>
tThermal
tI<
Time delayed 1 or 2
tI>, tI>> or
tI>>>
tIe>, tIe>> or
tIe>>>
tPe/IeCos>,
tPe/IeCos>>
tU> or tU>
tU< or tU<<
st
nd
st
nd
overvoltage threshold
Time delayed 1 or 2
tV2> or
tV2>>
tF1 to tF6
dF/dt1 to
dF/dt6
tUe>>>>
tBrk. Cond
tAux1 to
tAux4
tAux5 to
tAux7
undervoltage threshold.
P12y/EN FT/Fa5
User Guide
Page 76/96
TEXT
tAux8 to
tAuxC
INFORMATION
Aux8 to Aux C delayed by tAux 8 to tAux C times (option)
Blocking Logic
Block function
2.8.4
No
INFORMATION
Ie_d> or Ie_d>>
AUTOMAT. CTRL
Heading of the Inrush Blocking logic submenu.
Blocking Inrush
Blocking Inrush
Yes
T Inrush reset =
Set the value for the Inrush tReset time. This provides a
reset delay of the Inrush Blocking signal (logic state=1)
once the 2nd harmonic level falls below the set threshold.
The setting range is from 0.0s to 2 s (step 10ms).
0 ms
Blocking Inrush Function
No
User Guide
P12y/EN FT/Fa5
Page 77/96
Sel1 tI>>
Sel1 tI>>>
Sel1 tIe>>
Sel1 tIe>>>
Sel1 tIe_d>
P127 only
First time delayed derived earth overcurrent threshold trip
Sel1 tIe_d>>
P127 only
Second time delayed derived earth overcurrent threshold
trip
t Sel1
2.8.6
150.00 s
P125
P126
P127
Output relays
The following functions can be assigned to output relays using this submenu.
Function
INFORMATION
Trip
I_R>, I_R>> or
I_R>>>
P12y/EN FT/Fa5
User Guide
Page 78/96
INFORMATION
tIe>, tIe>> or
tIe>>>
Ie_R>, Ie_R>> or
Ie_R>>>
Ie_d> or Ie_d>>
tIe_d> or tIe_d>>
Ie_dR> or tIe_dR>>
P> or P>>
tP> or tP>>
P< or P<<
tP< or tP<<
Q> or Q>>
tQ> or tQ>>
Q< or Q<<
tQ< or tQ<<
Pe/IeCos> or
Pe/IeCos>>
tPe/IeCos> or
tPe/IeCos>>
tI2>, tI2>> or
tI2>>>
ThermAlarm
thermal alarm.
ThermTrip
I<
tI<
U> or U>>
Instantaneous 1 or 2
tU> or tU>>
Time delayed 1 or 2
st
st
st
nd
U< or U<<
Instantaneous 1 or 2
tU< or tU<<
Time delayed 1 or 2
st
nd
nd
nd
overvoltage threshold
overvoltage threshold
undervoltage threshold
undervoltage threshold
Ue>>>>
tUe>>>>:
User Guide
P12y/EN FT/Fa5
Page 79/96
V2> or V2>>
INFORMATION
st
nd
st
nd
Time delayed 1 or 2
tV2> or tV2>>
Time delayed 1 or 2
F1 to F6
tF1 to tF6
F.OUT
dF/dt1 to dF/dt6
BrknCond
CBAlarm
52 Fail
CBFail
CB Close
tAux1 to tAux6
tAux5 ti Aux7
tAux8 to tAuxC
79 Run
79 Trip
79 int. Lock
79 ext. Lock
SOTF
SOTF functionality.
CONTROLTRIP
CONTROLCLOSE
ActiveGroup
Input1 to Input4
Input8 to inputC
VTS
CTS
Input5 to input7
tEQU.A to tEQU.H
Order Comm1 to
Order Comm4
P12y/EN FT/Fa5
User Guide
Page 80/96
AUTOMAT. CTRL
2.8.7
Output Relays
Function
:8765432
0000010
Function
:65432
00010
Submenu Inputs
Each relay model has a fixed number of opto-isolated logic inputs.
Logic inputs:
Model
Logic Input
P125
P126
P127
12
With the submenu Inputs it is possible to assign a label or an automation function to each
logic input (see the following table):
Label
designation
Label description
Unlatch
Blk Log 1
Blocking logic 1
Blk Log 2
Blocking logic 2
52 a
52 b
CB FLT
Aux 1 to Aux 4
Aux 5 to Aux 7
Strt Dist
Cold L PU
Log Sel 1
Logic selectivity 1
Log Sel 2
Logic selectivity 2
Change set
Block_79
Reset
Trip Circ
Start t BF
Maint. M
User Guide
P12y/EN FT/Fa5
Label description
SOTF
Local
Synchro.
LED Reset or
Reset Led
Ctrl Trip
Ctr Close
Inputs
Input 2
2.8.7.1
Page 81/96
AUTOMAT.
CTRL
Input 1
...
Input 8/C
Aux Times
Inputs
Input 1
Input 2
Input 3
Input 5
Input 6
Input 7
Input 8
Input C
52a
52b
Aux1
Log Sel 1
Block_79
Cold L PU
P12y/EN FT/Fa5
User Guide
Page 82/96
2.8.8
Aux1 Time
tAux1
200.00 s
Aux2 Time
tAux2
200.00 s
Aux 3 Time
tAux 3
200.00 s
Aux4 Time
tAux4
200.00 s
Aux5 Time
tAux5
200.00 s
Aux6 Time
tAux6
200.00 s
Aux7 Time
tAux7
200.00 s
Aux8 Time
tAux8
200.00 s
Aux C Time
tAuxC
200.00 s
As Aux1 for input Aux 8, Aux 9, Aux 10, Aux 11 and Aux 12
(optional configuration only).
Brkn. Cond ?
No
Brkn.Cond Time
tBC
14400 s
Ratio I2/I1
20 %
User Guide
P12y/EN FT/Fa5
Page 83/96
P126 P127
tI> ?
tI>> ?
tI>>> ?
tIe> ?
tIe>> ?
tIe>>> ?
tIe_d> ?
tIe_d>> ?
tI2> ?
tI2>> ?
ti2>>> ?
t Therm. ?
AUTOMAT. CTRL
Heading of Cold Load Pick-Up submenu.
Cold Load PU
In the following list, setting choice Yes assigns the corresponding function with the
loading pick-up function:
Cold Load PU ?
Input?
Auto?
No
Yes
No
Cold Load PU
Function ?
No
Cold Load PU
Level
200 %
Cold Load PU
tCL
3600.0 s
Displays delay timer setting (tCL) for the Cold Load Pick-up
function, from 0.1 to 3600s (step 100ms).
P12y/EN FT/Fa5
User Guide
Page 84/96
2.8.10
2.8.11
51V
V2>?
130V
V2>>?
130V
VT Supervision
VTS?
No
VTS Alarm?
No
No
The VTS function can block the 51V function when a VTS
alarm occurs (see 2.8.10). Setting choice: Yes or No
The VTS function can be used to block voltage dependent
functions and to change directional overcurrent into nondirectional functions. Setting choice: Yes or No.
Note: all voltage and power protections are blocked if VT
fault occurs.
VTS Non-dir
I>
I>>
I>>>
Ie>
Ie>>
Ie>>>
Ie_d>
Ie_d>>
tVTS
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
0.0s
User Guide
P12y/EN FT/Fa5
Page 85/96
CT Supervision?
Ie>
Ue<
tCTS
2.8.13
No
0.08 In
5V
0.2s
CB Fail
CB Fail ?
I< BF
CB Fail Time
tBF
Block I>?
Block Ie>?
No
0.02 In
0.00 s
Yes
Yes
P12y/EN FT/Fa5
User Guide
Page 86/96
2.8.14
AUTOMAT.
CTRL
CB Supervision
TC Supervision
No
CB Open S'vision
Yes
Yes
Amps(n) ?
No
CB Close S'vision
No
CB Open Alarm ?
Yes
CB Open Time
CB Close Time
t Open Pulse
Yes
CB Open NB =
t Close Pulse
Yes
Amps(n) ?
AUTOMAT. CTRL
CB Supervision
TC Supervision
Yes
t Trip Circuit
t SUP
200 ms
CB Open S'vision
Yes
CB Open Time
100 ms
CB Close S'vision
Yes
CB Close Time
100 ms
CB Open Alarm ?
Yes
CB Open NB =
Amps(n) ?
Amps(n) ?
0
Yes
1000 E6
n
t Open Pulse
t Close Pulse
100 ms
100 ms
User Guide
P12y/EN FT/Fa5
Page 87/96
SOTF
Sotf?
t Sotf
No
0.10 s
No
No
I>>?
I>>>?
Yes/No
Yes/No
[79] closing
Yes/No
SOTF Input
Yes/No
P12y/EN FT/Fa5
User Guide
Page 88/96
2.8.16
Information
None
No link/assignment
Pe> or Pe>>
tPe> or tPe>>
Alarm
Trip
I<
tI<
U> or U>>
tU> or tU>>
U< or U<<
tU< or tU<<
Ue>>>>
tUe>>>>
tBC
79 Trip
Input1 to Input 7:
Input8 to Input C
t Aux 1 to tAux 7
t Aux 8 to tAux C
P> or P>>
tP> or tP>>
P< or P<<
tP< or tP<<
Q> or Q>>
tQ> or tQ>>
User Guide
P12y/EN FT/Fa5
Page 89/96
TEXT
Information
Q< or Q<<
tQ< or tQ<<
V2>, V2>>
tV2>, tV2>>
F1 to F6
tF1 to tF6
dF/dt1 to dF/dt6
VTS
CTS
Ie_d>, Ie_d>>
tIe_d>, tIe_d>>
79 i.Blo
79 e.Blo
tEQU. A to tEQU. H
Results of equations A to H.
CB FLT
C.Order1 to C.Order4
P127 only
Remote communication orders (pulse commands from
remote devices through communication protocols)
Equ.A Toperat.
0.00s
0.00s
Equ.A Treset.
1/2
Null
Equation A.00
2/2
=
None
P12y/EN FT/Fa5
User Guide
Page 90/96
2.8.17
Comm. Order
delay
tOrder Comm 1
0.1s
User Guide
P12y/EN FT/Fa5
Page 91/96
RECORDS menu
With the RECORDS menu stored data, events, disturbances and monitoring signals from
various submenus can be displayed and read.
The different submenus are:
RECORDS
CB
Monitoring
Fault Record
Disturb
Record
(1)
Time Peak
Value
(1)
2.9.1
(1)
Rolling
Demand
(1)
Instantaneous
CB Monitoring
CB Opening Time
0.05 s
CB Closing Time
0.05 s
CB Operations
RST = [C]
Amps (n)
RST = [C]
Amps (n) IA
Amps (n) IB
Amps (n) IC
2 E04
2 E04
As above for phase C.
2 E04
P12y/EN FT/Fa5
User Guide
Page 92/96
2.9.1.1
RECORD
Heading of Fault Record submenu
Fault Record
Record Number
Fault Time
Fault Date
13:05:23
Displays the time when the fault was recorded. The format
of the time is hh:mm:ss.
In this example the fault was recorded at 1:05:23 pm.
12/11/01
Displays the date when the fault was recorded. The format
of the Date is DD/MM/YY.
In this example, the fault was recorded on November 12th
2001.
Faulted Phase
PHASE A
Threshold
Displays the origin of the fault that generated the trip order
Magnitude
IA Magnitude
IB Magnitude
IC Magnitude
----1200 A
1200 A
1200 A
1280 A
IN Magnitude
103 A
VAB Magnitude
10 KV
VBC Magnitude
10 KV
VCA Magnitude
10 KV
VN Magnitude
IA^VBC Angle
100 V
----
User Guide
P12y/EN FT/Fa5
IC^VAB Angle
IN^VN Angle
2.9.1.2
Page 93/96
----
----
----
Submenu Instantaneous
The instantaneous sub-menu makes possible to read the various parameters for each of the
last five starting information.
NOTE:
RECORD
Heading of the Instantaneous sub-menu.
Instantaneous
Number
Hour
Date
Origin
Lenght
Trip
13:05:23
12/11/01
----70 ms
No
P12y/EN FT/Fa5
User Guide
Page 94/96
2.9.2
Disturb Record
Records number ?
Pre-Time
0.1 s
2.9.2.1
Setting choices: 1, 2, 3, 4 or 5.
Sets the disturbance record length. This setting choice
adjusts the number of records according to the record
length. Setting choice allows 5 records of 3 seconds, 4
records of 3 seconds, 3 records of 5 seconds, 2 records of
7 seconds or 1 record of 9 seconds.
Selection of the disturbance record pre-time from 100 ms to
2.9s, 4.9s, 6.9s or 8.9s (record length minus 0.1s) in steps
of 100 ms.
The pre-time adjusts the beginning of the disturbance
record: In this example, the record starts 100ms before the
disturbance. Its length is fixed.
Selection of start criteria for the disturbance recording
function. Select between ON INST. (start on instantaneous
thresholds) and ON TRIP (start on trip conditions) by
pressing or . Press to confirm choice.
2.9.2.2
Time Window
5 mn
Sub Period
1 mn
1
User Guide
P12y/EN FT/Fa5
3.
Page 95/96
WIRING
The MiCOM P125, P126 & P127 relays have the same terminal layout for common
elements. The wiring diagram for each model is provided in Appendix 1 of the Technical
Guide.
3.1
3.2
3.3
Digital Inputs
The number of logic inputs depends on the relay model. The relays have programmable
opto-isolated logic inputs, which may be assigned to any available label or function.
Digital inputs for each relay model:
Model
Digital Inputs
P125
P126
P127
7 / 12
Output Relays
The number of logic outputs depends on the relay model. The relays have configurable logic
outputs, which may be assigned to any available function.
The normally closed (NC) contact of the Watchdog (RL0) is not configurable. The other
contacts are configurable to functions available in the relay. A basic output matrix is included
in the relay. Some logic outputs have changeover contacts. RL1 and RL2 can be configured
to be fail safe or not.
Logic outputs for each relay model:
Model
Logic outputs
P125
P126
P127
The first logic output (RL0) is dedicated to indicate a relay failure (Watchdog, WD) and is not
part of this table.
3.5
Communication
3.5.1
P12y/EN FT/Fa5
Page 96/96
3.5.2
User Guide
MiCOM P125/P126 & P127
P0073ENa
P12y/EN HI/Fa5
P12y/EN HI/Fa5
Page 1/24
CONTENTS
1.
2.
3.
13
P12y/EN HI/Fa5
Page 2/24
BLANK PAGE
****
11/06/07
Format Date
P rivate
Time
14 : 15 : 34
Date
Date
654321
001011
Relay
Status
Reset Led on
Fault
No
Alarm.Inh. Eq A?
Alarm.Inh. Eq H?
65W4321
0000000
Input
Setting group
1
Menu
Inst. Self-reset
No
Change group
Input
4321
0101
No
Relays
CMD
Yes
Maintenance Mode
No
Fail
654321
safe re.000000
Alarms
Group Select
Input
Status
Voltage input
DC
Inputs :4321
Output
relays
E/Gnd VT sec
100.0 V
Led
Ie>
tIe>
Ie>>
tIe>>
Ie>>>
tIe>>>
Pe/IeCos >
tPe/IeCos>
Pe/IeCos>>
tPe/IeCos>>
Ue>>>>
tUe>>>>
Input1/2/3/4
tAux1/2/3/4
Inputs
configuration
Active Group =
1
Software version
15.x
E/Gnd primary
0.10 kV
E/Gnd VT sec
5A
E/Gnd VT primary
5A
LED 5/6/7/8
Close Order
No
Reference
MiCOM
Transfo ratio
Frequency
50 Hz
Open Order
No
No
Earth text
Confirm ation ?
No
Yes
General
options
C ONFIGURATION
Record Reset
No
Description
P125 -0
Language
EN GLISH
P assword
ORDERS
1.
OP PARAMETERS
DEFAULT DISPLAY
IA = 1245 A
0.00A
0.00 W
3.15V
0.00A
IN^VN Angle
0.0
IeCos
Pe
UN
IN-fn
RST=[C]
3.15 A
No
None
Relay address
Stop Bits
Data Bits
P arity
Baud rate
19200 bd
Yes
Communication ?
Yes
Frequency
50.00 Hz
IN
COMMUN ICATION
MEASUREMENTS
No
Dir
No
Ie>>>
10.00 In
Ue>
260.0V
Ie> Torque
0
Ie> Trip 10.0%
tIe>>>
0.00s
tReset
0.04s
Ie>>> ?
Dir
Ie>>
10.00 In
Ie>> Torque
0
Ie>> Trip
Delay type
DMT
tIe>>
0.00s
Ie>> ?
Ie>>>
tIe >>>
tReset
10.00 In
0.00s
0.04s
Yes / Peak
Ie>>
10.00 In
Delay type
DMT
tIe >>
0.00s
Yes
Ie>
10.00 In
Delay ty pe
DMT
tIe>
0.00s
tReset
0.04s
Yes
No
No
Yes
Pe
No
Pe
Yes
No
160.0x1W
0.00s
0.04s
Pe/IeCos Angle
Pe>>
tPe>>
tReset
P e>>
Pe>
160.0x1W
Delay Type
DMT
tPe>
0.00s
tR eset
0.04s
Pe>
Mode
[32N] Earth
Wattmetric
No
No
Yes
No
IeCos
Yes
No
Pe/IeCos Angle
0
IeCos>> 8.000Ien
tIeCos>>
0.00s
tReset
0.04s
tIeCos>>
IeCos> 8.000Ien
Delay Type
DMT
tIeCos>
0.00s
tReset
0.04s
IeCos>
No
Ue>>>>
tU e>>>>
5.0 V
0.00s
Yes
Ue>>>> ?
260.0 V
[59N] residual
Over V oltage
Page 4/24
No
No
No
Dir
No
Ie>
10.00 In
Ue>
1.0V
Ie > Torque
0
Ie> Trip 50.0%
Delay type
DMT
tIe >
0.00s
tReset
0.04s
Ie> ?
[67N] E/Gnd
PROTECTION G1/G 2
DEFAULT DISPLAY
IA = 1245 A
P12y/EN HI/Fa5
Menu Content Tables
No
No
No
tAux1
tAux2
tAux3
tAux4
C trl Trip
Trip
Trip
Trip
Trip
Trip tUe>>>>
No
No
No
No
No
No
Trip tPe/IeCos>
No
Trip tPe/IeCos >>
No
Trip tIe>
Trip tIe>>
Trip tIe>>>
Trip Commands
AUTOMAT. CTRL
Latch
:654321
000000
Latch Relays
Block tAux1
Block tAux2
Block tAux3
Block tAux4
No
No
No
No
Block tUe>>>>
No
Block tPe/IeCos>
No
Block tPe/IeCos >>
No
Block tIe>
No
Block tIe>>
No
Block tIe>>> No
Blocking Loqic
DEFAULT DISPLAY
IA = 1245 A
65432
00100
Ie >
tle >
Ie >>
tle >>
Ie >>>
tle >>>
Pe/IeCos >
tPe/IeCos>
Pe/IeCos>>
tPe/IeCos>>
Ue>>>>
tUe>>>>
tAux1
tAux2
tAux3
tAux4
C ontrol trip
Control Close
Active Group
Input 1
Input 2
Input 3
Input 4
Trip
Output Relays
Aux1 Time
tAux1
tAux2
tAux3
tAux4
0.00
0.00
0.00
0.00
Aux Time
Unlatch
Blk Log
Aux 1
Aux 2
Aux 3
Aux 4
Strt Dist
Changeset
Maint. M.
Local
Synchro
Led Reset
Ctrl Trip
Ctrl C lose
Inputs 1/2/3/4
Inputs
s
s
s
s
I>
No
1.3 s
Pre-Time
Records number
5
Disturbance Record
Trip
IN^VN Angle
0
VN Magnitude
0.00V
IN Magnitude
103 A
Magnitude
1200 A
Threshold
57 ms
Faulted Phase
EARTH
Length
Ie>
Origin
09/01/01
Date
Fault Date
09/01/01
5
Hour
13:07:15:53
Number
Record Number
25
Fault Time
12:05:23:42
Instantaneous
Fault Record
RECORDS
****
50 Hz
Time
14 : 15 : 34
11/06/07
87654321
00001011
Relay
Status
Date
754321
000101
Input
Status
No
No
No
Phases/Earth Text
L1 L2 L3 N
Default Displays
RMS IA IB IC IN
Phase rotation
A-B-C
General options
CON FIGURATION
5A
Line VT primary
0.10 kV
E/Gnd CT sec
5A
E/Gnd CT primary
5A
Line CT sec
Line CT primary
5A
Transfo ratio
Led
I>
tI>
I>>
tI>>
I>>>
tI>>>
tIA>
tIB>
tIC>
Ie>
tIe>
Ie>>
tIe>>
Ie>>>
tIe>>>
Pe/IeCos>
tPe/IeCos>
Pe/IeCos>>
tPe/IeCos >>
I2>
tI2>
I2>>
tI2>>
I2>>>
tI2>>>
Therm Trip
I<
tI<
Ue>>>>
tUe>>>>
Brkn. Cond
CB Fail
LED 5 / 6 / 7 / 8
No
Input1 /2 /3 /4
Input5 /6 /7
79 Run
79Int Locked
79Ext Locked
tAux1 /2/3/4/5/6/7
t SOTF
Voltage input
DC
Inputs :7654321
Inputs
configuration
Relays8765W4321
CMD 000000000
Yes
Maintenance Mode
No
Fail 87654321
safe re.00000000
Output
relays
Input
Setting group
Menu
1
Change group
Input
Group Select
Page 6/24
Active Group =
1
Frequency
Software version
15.x
Close Order
Reference
MiCOM
Open Order
No
Confirmation ?
No
Yes
Record Reset
No
Description
P126-2
Language
ENGLISH
Password
ORDERS
2.
OP PARAMETERS
DEFAULT DISPLAY
IA = 1245 A
P12y/EN HI/Fa5
Menu Content Tables
Alarm.Inh. Eq A?
Alarm.Inh. Eq H?
0.00 A
600.00 A
3.15 A
600.00 A
IeCos
Pe
UN
0.00A
0.00 W
3.15V
RATIO I2 / I1 =
0%
I2
I1
IN
IC
IC Rms
600.00A
Average IA Rms
600.00A
Max
IB Rms
600.00A
IA Rms
600.00A
Max
Max
IA Rms
600.00A
Max
THERMAL STATUS
RST=[C] 0%
0.00A
C ycle 2 recloses
0
ROLLING AVE RAGE
IA Rms
600.00A
Reclose Stats
RST=[C]
ROLLING AV ERAGE
IC Rms
600.00A
Cycle 4 recloses
0
Cycle 3 recloses
0
Cycle 1 recloses
0
ROLLING AVERAGE
RST=[C]
ROLLING AVERAGE
IB Rms
600.00A
Total recloses
0
MAX SUBPERIOD
IC Rms
600.00A
MAX SUBPERIOD
IB Rms
600.00A
No
None
Relay address
Stop Bits
Data Bits
P arity
Baud rate
19200 bd
Yes
Communication ?
Yes
COMMUN ICATION
IN H Alarm tAux4?
Yes
IN H Alarm tAux2?
No
INH Alarm[79]DI.Lock?
No
IN H Alarm tI<?
No
No
600.00 A
IN -fn
RST=[C]
MAX SUBPERIOD
RST=[C] 0%
IB
IA^IC Angle
0.0
Reset Led on
Faul t
IA
Format Date
Private
Inst. Self-reset
600.00 A
Average IC Rms
600.00A
IA^IB Angle
0.0
Frequency
50.00 Hz
Date
Alarms
No
Average IB Rms
600.00A
IN^VN Angle
0.0
MEASUREMENTS
CONFIGURATION
No
No
I>>>
40.00 In
Delay type
DMT
(1)
0.00s
tI>>>
Yes
I>>> ?
I>>
40.00 In
Delay type
DMT
0.00s
tI>> (1)
Yes
I>> ?
No
No
No
Dir
No
No
Dir : Yes / Peak
Ie>>>
10.00 In
If Dir:
Ue >
260.0V
Ie> Torque
0
Ie> Trip
10.0%
If Dir or Yes:
tIe>>>
0.00s
tReset
0.04s
Ie>>> ?
Ie>>
10.00 In
If Dir:
Ie>> Torque
0
Ie>> Trip
If Dir or Yes
Delay type
DMT
0.00s
tIe>>(1)
Ie>> ?
Ie>
If Dir:
Ue>
1.0V
Ie> Torque
0
Ie> Trip 50.0%
If Dir or Yes:
Delay type
DMT
0.00s
tIe>(1)
0.04s
tReset (1)
Dir
10.00 In
No
No
No
Yes
Pe
No
Pe
No
160.0x1W
0.00s
0.04s
Yes
P e/IeCos Angle
Pe>>
tPe>>
tReset
Pe>>
Pe>
160.0x1W
Delay Type
DMT
(1)
tPe>
0.00s
(1)
0.04s
tReset
Pe>
Mode
[32N] Earth
Wattmetric
No
No
Yes
No
IeCos
Yes
No
P e/IeCos Angle
0
IeCos>> 8.000Ien
tIeCos>>
0.00s
t Reset
0.04s
tIeCos>>
IeCos> 8.000Ien
Delay Type
DMT
tIeCos> (1)
0.00s
(1)
0.04s
tReset
IeCos>
No
No
No
Yes
No
K
t Reset
I2>>>
tI2>>>
I2>>> ?
I2>>
tI2>>
I2>> ?
No
No
0.025
0.00s
RI
IEEE, IEC,
RECT or CO
TMS
0.025
Reset Delay TypeDMT
If reset delay type=IDMT:
Rtms
0.025
tReset
0.00s
(1)
40.00 In
0.00 s
Yes
Yes
40.00 In
0.00 s
Yes
I2>
25.00 In
Delay type
DMT
0.00 s
tI2> (1)
I2> ?
Page 8/24
No
No
No
I>
10.00 In
Delay type
DMT
(1)
tI>
0.00s
Yes
Ie> ?
I> ?
No
[67N] E/Gnd
[67] P hase OC
PROTECTION G1/G2
DEFAULT DISPLAY
IA = 1245 A
P12y/EN HI/Fa5
Menu Content Tables
No
No
Alarm
Alarm
I>
Te
K
Trip
Yes
90%
No
0.10 In
1 mn
1.05
100 %
Yes
No
0.10 In
0.00s
I< Inhibited on
52 a
No
I<
tI<
Yes
No
I< ?
Therm OL
No
[49] Therm OL
PROTECTION G1/G2
DEFAULT DISPLAY
IA = 1245 A
OR / AND
OR / AN D
No
Ue>>>>
tUe>>>>
5.0 V
0.00s
Yes
Ue>>>> ?
260.0 V
[59N] residual
Over Voltage
Yes
10 mn
Dead Time
TD1
5.00 s
TD2
5.00 s
TD3
5.00 s
TD4
5.00 s
Time period
Max cycles nb
10
0.05
0.05
0.05
0.05
0.05
0.05
s
s
s
s
s
s
Cycles
4321
tI>
1111
tI>>
1111
tI>>>
1111
tIe>
1111
tIe>>
1111
tIe>>>
1111
tPe/IeCos > 1111
tPe/IeCoss>>1111
tAux1
1111
tAux2
1111
tAux3
1111
tAux4
1111
E/Gnd Cycles
Phase Cycles
Reclaim Time
tR
5.00 s
Dead Time
tI>
tI>>
tI>>>
tIe>
tIe>>
tIe>>>
No
No
Ext Block
Rolling demand ?
No
Yes
No
No
No
Yes
Ext CB Fail ?
Yes
Autoreclose
[79] Autoreclose
No
No
No
Trip tIe>
Trip tIe>>
Trip tIe>>>
No
No
No
Trip Brkn.Cond
No
No
No
No
Trip SOFT
Ctrl Trip
Trip EQUATION A ?
No
Trip EQUATION H ?
No
No
No
No
No
No
No
No
tAux1
tAux2
tAux3
tAux4
tAux5
tAux6
tAux7
Trip
Trip
Trip
Trip
Trip
Trip
Trip
Latch :87654321
00000000
Latch Relays
No
No
No
Block tAux1
Block tAux2
Block tAux3
Block tAux4
Block tAux5
Block tAux6
Block tAux7
No
No
No
No
No
No
No
Block TBrk.Cond
No
Block tUe>>>>
No
Block Thermal No
Block tI<
No
Block tI2>
No
Block tI2>> N o
Block tI2>>> No
Block tPe/IeCos>
No
Block tPe/IeC os >>
No
Block tIe>
No
Block tIe>>
No
Block tIe>>> No
Block tI>
Block tI>>
Block tI>>>
Blocking Loqic
No
No
t Sel 1
150 ms
Sel 1 tI >>>
No
Sel1 tI >>
8765432
1000100
I>
tl >
I >>
tl >>
I >>>
tl >>>
tIA>
tIB>
tIC
Ie >
tle >
Ie >>
tle >>
Ie >>>
tle >>>
Pe/IeC os>
tPe/IeCos>
Pe/IeCos>>
tPe/IeC os >>
I2>
tI2>
I2>>
tI2>>
I2>>>
tI2>>>
Therm Alarm
Therm Trip
I<
tI<
Ue>>>>
tUe>>>>
Brkn Cond
Trip
Output Relays
8765432
1000100
CB Alarm
52 Fail
CB F ail
CB Close
tAux1
tAux2
tAux3
tAux4
tAux5
tAux6
tAux7
79 Run
79 Trip
79 int. Lock.
79 ext. Lock
SOFT
C ontrol trip
Control Close
Active G roup
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Equ. A
Equ. B
Equ. C
Equ. D
Equ. E
Equ. F
Equ. G
Equ. H
Trip
Page 10/24
Trip tUe>>>>
Trip Thermal No
Trip tI<
No
Trip tI2>
Trip tI2>>
Trip tI2>>>
Trip tPe/IeCos>
No
Trip tPe/IeC os >>
No
No
No
No
Trip tI>
Trip tI>>
Trip tI>>>
Trip Commands
AUTOMAT. CTRL
DEFAULT DISPLAY
IA = 1245 A
P12y/EN HI/Fa5
Menu Content Tables
Unlatch
Blk Log 1
Blk Log 2
52 a
52 b
CB FLT
Aux 1
Aux 2
Aux 3
Aux 4
Aux 5
Aux 6
Aux 7
Strt Dist
Cold L PU
Log Sel 1
Log Sel 2
Changeset
Block 79
Reset
Trip Circ
Start tBF
Maint. M.
SOTF
Local
Synchro
Led Reset
Ctrl Trip
Ctrl Close
Inputs 1/2/3/4/5/
6/7
Inputs
AUTOMAT. CTRL
Aux1 Time
tAux1
tAux2
tAux3
tAux4
tAux5
tAux6
tAux7
0.00
0.00
0.00
0.00
0.00
0.00
0.00
Aux Time
s
s
s
s
s
s
s
Yes
No
Ratio I 2/I 1
20 %
Brkn.Cond Time
tBC
32 s
Yes
Brkn.Cond ?
Broken Conductor
No
No
Bloc Ie > ?
Yes
Block I > ?
No
CB Fail Time
tBF
0.10 s
0.1 In
Yes
No
Amps (n)
No
3 E6
Yes
Amps (n) ?
[79] closing
CB Open NB
1500
Yes
CB Open Alarm ?
Yes
Yes
SOTF Input
Yes
CB Close Time
150
Yes ms
Yes
Yes
100 ms
No
I >>>
I >>
tSotf
Sotf
Sotf
CB Close Svision ?
Yes
CB Open Time
150 ms
CB Open Svision ?
No
Yes
No tOpen Pulse
300ms
No
No
No
Yes
t trip circui t
tSUP
3s
TC Supervision ?
No
C B Supervision
No
OR
A.00
NONE
NONE
NONE
N one
2/2 A.00
NONE
1/2
OR
AND NOT
AN D
OR NOT
Equ.A Treset
=
0.00s
Equ. A Toperat.
=
0.00s
Equation
A/B/C/D/E/F/G/H
Logic Equations
No
Cold Load PU
tCL
2s
Cold Load PU
Level
120 %
C old Load PU
tl> ?
Yes
tI>> ?
Yes
tI>>> ?
Yes
tIe> ?
Yes
tIe>> ?
Yes
tIe>>> ? Yes
tIe>>>> ? Yes
tI2> ?
Yes
tI2>> ?
No
tI2>>> ? Yes
tTherm ?
Yes
Auto?
Yes
I < BF
CB Fail ?
Cold load PU ?
No
Input?
CB Fail
C old Load P U
5 E6
5 E6
5 E6
Trip
Threshold
IN Magnitude
103 A
VN Magnitude
0.00V
IN^VN Angle
0
IB Magnitude
500 A
IC Magnitude
480 A
No
57 ms
Ie>
IA Magnitude
1200 A
Magnitude
1200 A
I>
Length
Origin
Faulted Phase
EARTH
0.1 s
Time Window
5 mn
Records number
5
Pre-Time
Disturbance Record
1mn
Num of Sub Per
1
Sub Period
Rolling Demand
Page 12/24
Amps (n) IC
Amps (n) IB
Amps (n) IA
Amps (n)
RST= [C]
09/01/01
Date
Fault Date
09/01/01
1312
CB Operations
RST = [C]
Hour
13:07:15:53
Fault Time
12:05:23:42
CB Closing Time
100 ms
Number
Record Number
25
CB Opening Time
83 ms
Instantaneous
Fault Record
CB Monitoring
RECORDS
DEFAULT DISPLAY
IA = 1245 A
P12y/EN HI/Fa5
Menu Content Tables
** **
(2)
14 : 15 : 34
11/06/07
No
No
No
Close Order
Open Order
Confirmation ?
No
Yes
Record Reset
No
P hase rotation
A-B-C
(2)
IRIG B
Modulated
Time synchro
IRIG B
Phases/Earth Text
L1 L2 L3 N
(2)
Inh.Block dF/ dt
>20 Hz/s
No
Default Displays
RMS IA IB IC IN
dF/dt Cycles.nb
(2)
dF/dt Validat.nb=
4
(2)
(2)
(2)
(2)
Quadrant conv. ?
Quadrant 1
CTm2 phase ?
none
VT Protection
Protect P -N
CTm1 phase ?
none
(2)
VT Connection
2Vpp+Vr
General options
CONFIGURATION
5A
1A
E/Gnd VT sec
100.0 kV
E/Gnd VT primary
0.10 kV
Line VT sec
100.0 kV
Line VT primary
0.10 kV
E /G nd C T sec
5A
E/Gnd CT primary
5A
Line CT sec
Line CT primary
5A
Transfo. ratio
(1)
(1)
CONFIGURATION (contd)
Time
Date
87654321
00001011
Relay
Status
Active Group =
1
50 Hz
CBA98
00000
Input
Status
Frequency
754321
000101
Input
Status
MiCOM
Software version
15.x
Reference
Description
P127 -1
Language
ENGLISH
Password
ORDERS
3.
OP PARAMETERS
DEFAULT DISPLAY
IA = 1245 A
Led
I>
tI>
I>>
tI>>
I>>>
tI>>>
tIA>
tIB>
tIC>
Ie>
tIe>
Ie>>
tIe>>
Ie>>>
tIe>>>
Ie_d>
tIe_d>
Ie_d>>
tIe_d>>
P>
tP>
P>>
tP>>
P<
tP<
P<<
tP<<
Q>
tQ>
Q>>
tQ>>
Q<
LED 5/6/7/8
CON FIGURATION
DEFAULT DISPLAY
IA = 1245 A
tQ<
tQ<<
Pe/IeC os>
tPe/IeCos>
Pe/IeCos>>
tPe/IeC os>>
I2>
tI2>
I2>>
tI2>>
I2>>>
tI2>>>
Therm Trip
I<
tI<
U>
tU>
U>>
tU>>
U<
tU<
U<<
tU<<
Ue>>>>
tUe>>>>
V2>
tV2>
V2>>
tV 2>>
F1
tF1
F2
tF2
F3
CONFIG URATION
tF3
F4
tF4
F5
tF5
F6
tF6
F.out
dF/dt1
dF /dt2
dF/dt3
dF/dt4
dF /dt5
dF/dt6
Brkn. Cond
CB Fail
VTS
CTS
Input 1 /2 /3 /4
Input 5 /6 /7
Input 8 /9 /A /B /C(2)
79 Run
79i.Blocked
79e.Blocked
tAux1 /2 /3 /4/5/6/7
tAux /8 /9 /A /B /C(2)
t SOFT
tEQU. A / B /H
No
Relays8765W4321
CMD 000000000
Yes
Maintenance Mode
No
Execution ?
copy to
copy from
No
G1
G1
No
Group if high.
level
Group Copy ?
Group if low
level
Input
Target G roup
Setting group
Menu
Change Group
Input
Group Select
No
No
Inh. Alarm F6 ?
Inh. Alarm F.out ?
Inh. Alarm [79] ext.blk ?
Inh Alarm tAux1?
Reset Led on
Fault
Inst. Self-reset
Alarms
Page 14/24
DC
:CBA98
Voltage input
Input(2)
Fail
87654321
safe re. 00000000
Input
:7654321
Output
relays
Inputs
configuration
MEASUREMENTS
P12y/EN HI/Fa5
Menu Content Tables
2Vpp+Vr
2Vpp+Vr
IN^UAB Angle
IA^UBC Angle
IA^IUN Angle
IN^VN Angle
IA^IB Angle
IA^IC Angle
Pe
IeCos
UAB
UBC
UCA
UN
RATIO I2 / I1 =
0%
IA
IB
IC
IN
I1
I2
Frequency
50.00 Hz
MEASUREMENTS
Fwd
Rev
Fwd
Rev
THERMAL STATUS
RST=[C] 0%
0.00A
WHours
WHours
VArHours
V ArHours
VAHours
IN-fn
RST=[C ]
3Ph
3Ph
3Ph
3Ph
3Ph
Energy
RST=[C ]
P
Q
S
C os(Phi)
MAX SUBPERIOD
IA Rms
IB Rms
IC Rms
Max
IA Rms
Max
IB Rms
Max
IC Rms
Average IA Rms
Average IB Rms
Average IC Rms
Max
UAB Rms
Max
UBC Rms
Average UAB Rms
Average UBC Rms
ROLLIN G AVERAGE
IA Rms
IB Rms
IC Rms
MAX SUBPERIOD
RST=[C] 0%
Total recloses
Cycle 1 recloses
Cycle 2 recloses
Cycle 3 recloses
Cycle 4 recloses
Reclose Stats
RST=[C]
METERING
IA^UA Angle
IA^UB Angle
IA^UC Angle
3Vpn/
2Vpn+Vr
UA
UB
UC
UN
3Vpn/
2Vpn+Vr
CONFIG URATION
IAm
THDAm
TDDAm
K Am:
IAmh2:
IAmh10:
Phase A
Currents
METERING
Ibm
THDBm
TDDBm
Iam^Ibm
KBm:
IBmh2
:
IBmh10:
Phase B
(1)
3Vpp+Vr
or Protect P-P
ICm
THDCm
TDDCm
Iam^Icm
KCm:
ICmh2:
ICmh10:
Phase C
V ABm
THDAm
Iam^Uab
Icm^Uab
VABmh2:
V ABmh10:
P hase A
VAm
THDAm
Iam^Va
VAmh2:
VAmh10:
Phase A
VBCm:
THDBm
Iam^Ubc
Ibm^Ubc
VBCmh2:
VBCmh10:
P hase B
VBm:
THDBm
Iam^Vb
Ibm^Vb
VBmh2:
VBmh10:
Phase B
Phase C
Pm:
Qm:
Sm:
DP F:
VCAm:
THDCm
Iam^Uca
Ibm^ Uca
VCAmh2:
VCAmh10:
P hase C
VC m:
THDCm
Iam^Vc
Icm^Vc
VCmh2:
VC mh10:
VT?
Voltages
Powers
HH:MM
DD/MM/YY
Export power
Import power
Lagging VARs
Leading VARs
Time
Date
RST = [C ]
Energies
COMMUNICATION
Page 16/24
Frequency
50.00Hz
Frequency
MEASUREMENTS
DEFAULT DISPLAY
IA = 1245 A
P12y/EN HI/Fa5
Menu Content Tables
Yes
No
No
Yes
No
None
Relay address
Stop Bits
Data Bits
Parity
Baud rate
19200 bd
COMM1
COMMUN ICATION
Date Format
Private
Relay Address
MODBUS
HMI ?
PROTECTION (prev)
DEFAULT DISPLAY
IA = 1245 A
No
Yes
(1)
No
Basic
0.1s
Yes
IEC60870-5-103 only
C OMM1 only
Delay type
If Dir or Yes:
Rtms
0.025
tReset
0.00s
Ie> I>> I>>
Interlock
Yes
If reset delay
type= IDMT:
TMS
0.025
Reset Delay
Type
DMT
IEEE, IEC,
REC T or C O
K
0.025
tReset
0.00s
I> I>> I>>>
Interlock
Yes
0.025
0.00s
0.00s
DMT
Rtms
tReset
0.025
0.00s
If reset delay
type= IDMT:
TMS
0.025
Reset Delay
Type
DMT
IEEE, IEC,
REC T or C O
K
tReset
RI
tI>>
RI
Dir / Yes
No
I>>
10.00 In
If D ir:
I>> Torque
0
I>> Trip Zone 50.0%
I>> ?
DMT
No
tI>
0.00s
DMT
0
50.0%
10.00 In
Dir / Yes
No
DMT
Delay type
If Dir or Yes:
I>
If Dir:
I> Torque
I> Trip Zone
I> ?
[67] Phase OC
No
Dir / Yes
No
Delay type
If Dir or Yes :
DMT
I>>>
10.00 In
If Dir :
I>> Torque
0
I>> Trip Zone 50.0%
I>>> ?
PROTECTION (contd)
to COMM2
Command
duration
Command
Blocking
Events + Measur.
Blocking
Yes
Measur. upload
Other
Yes
Measur. upload
ASDU 9
Yes
Measur. upload
ASDU 3.4
Yes
GI select.
COMM2
P ROTECTION G1/G2
(G3 G8)
0.00s
0.00s
DMT
1.0V
0
50.0%
0.010 Ien
Dir / Yes
No
Rtms
0.025
tReset
0.00s
Ie> I>> I>>
Interlock
Yes
If reset delay
type= IDMT:
TMS
0.025
Reset Delay
Type
DMT
IEEE, IEC,
REC T or CO
No
Delay type
tIe>> (1)
tReset
If Dir or Yes:
Ie>>
If Dir:
Ue>>
Ie>> Torque
Ie>> Trip
Ie>> ?
No
DMT
0.00s
0.00s
260.0V
0
50.0
8.000 Ien
Dir / Yes
P ROTECTION G1/G2
(G3 G8)
No
Dir / Yes
No
Delay type
tIe>>>
tReset
DMT
0.00s
0.00s
Ie>>>
8.000 Ien
If Dir:
Ue>>>
260.0V
Ie>>> Torque
0
Ie>>> Trip
10.0
If Dir or Yes:
Ie>>> ?
No
Delay type
tIe_d> (1)
tReset
If Dir or Yes:
DMT
0.00s
0.00s
100.0V
0
10.0
1.00 Ien
Dir / Yes
No
K
tReset
Ie_d>
If Dir:
Ue>(Ie_d>)
Ie_d> Tor que
Ie_d> Trip
Ie_d> ?
Delay type
tIe_d> (1)
tReset
0.025
0.00s
RI
No
Dir / Yes
TMS
0.025
Reset Delay TypeDMT
If reset delay type=IDMT:
Rtms
0.025
tReset
0.00s
IEEE, IE C,
RECT or CO
DMT
0.00s
0.00s
Ie_d>>
1.00 Ien
If Dir :
U e>(Ie_d>>)
5.0V
Ie_d>> Torque 10.0
Ie_d>> Trip
1.0
If Dir or Yes:
Ie_d>> ?
(1)
No
PROTECTION (contd)
Page 18/24
K
0.025
tReset
0.00s
Ie> I>> I>>>
Interlock
Yes
RI
tIe>
tReset
DMT
Delay type
If Dir or Yes:
Ie>
If Dir:
Ue>
Ie> Torque
Ie> Trip
Ie> ?
[67N] E/Gnd
METERING
DEFAULT DISPLAY
IA = 1245 A
P12y/EN HI/Fa5
Menu Content Tables
No
0.00s
(1)
No
or 10000x5W
or 40000x1W
or 40000x5W
Q>> 10000x1W
tQ>>
0.00s
Yes
Q>> ?
Yes
Q> ?
P>>
tP>>
No
10000x1W(1)
Yes
P>> ?
10000x1W (1)
0.00s
No
No
No
No
Yes
(2)
1x1W (2)
0.00s
No
1x1W(2)
0.00s
No
1x1W (2)
0.00s
No
1x1W
0.00s
(2)
No
or 1x5W or 4x1W
or 4x5W
Q<<
tQ<<
Yes
Q<< ?
Q<
tQ<
Yes
Q< ?
P <<
tP<<
Yes
P << ?
P<
tP<
P< ?
No
Yes
No
Yes
No
No
No
Yes
No
IeC os
Yes
No
IeCos>> 8.000Ien
tIeCos>>
0.00s
tReset
0.04s
Pe/IeCos Angle 0
tIeCos>>
IeCos> 8.000Ien
Delay Type
DMT
0.00s
tIeCos>(1)
tReset
0.04s
IeC os>
Pe>> 160.0x1W
tPe>>
0.00s
tReset
0.04s
N o Pe/IeCos A ngle 0
Pe>>
Pe>
160.0x1W
Delay Type
DMT
0.00s
tPe> (1)
tReset
0.04s
P e>
Pe
Pe
No
No
No
Yes
No
I2>>>
tI2>>>
I2>>> ?
I2>>
tI2>>
I2>> ?
No
40.00 In
0.00 s
Yes
Yes
40.00 In
0.00 s
Yes
No
I2>
25.00 In
Delay type
DMT
0.00 s
tI2> (1)
I2> ?
No
Yes
90%
No
0.10 In
1 mn
1.05
100 %
Yes
K
tReset
Alarm
Alarm
No
No
I>
Te
K
Trip
Therm OL
[49] Therm OL
I< Inhibited on
U<
5.0 V
Yes
I< Inhibited on
U<
No
0.025
0.00s
RI
U>>
tU>>
U>> ?
IEEE, IEC,
REC T or C O
No
No
U>
tU>
U> ?
260.0 V
0.00s
OR / AND
No
260.0 V
0.00s
OR / AND
No
TMS
0.025
Reset Delay TypeDMT
If reset delay type=IDMT:
Rtms
0.025
t Reset
0.00s
(1)
No
No
0.10 In
0.00s
Yes
No
I< Inhibited on
52 a
No
I<
tI<
I< ?
(1)
No
No
No
No
P>
tP>
Yes
Mode
P> ?
No
[32N ] Earth
Wattmetric
PROTECTION G1/G2
(G3 G 8)
[32] Directional
Power
PROTECTION (prev)
DEFAULT DISPLAY
IA = 1245 A
U<< ?
OR / AN D
No
U<<
5.0 V
tU <<
0.00s
52a Inhib. U<<? No
No
No
U<
5.0 V
tU<
0.00s
52a Inhib. U<? No
OR / AND
No
Ue>>>>
tU e>>>>
5.0 V
0.00s
Yes
No
No
V2>>
tV2>>
V2>> ?
V2>
tV2>
No
15.0 V
5.00s
OR / AND
No
15.0 V
5.00s
OR / AND
V2> ?
Ue>>>> ?
260.0 V
U< ?
No
[47 ] Negative
Over Voltage
[59 N] residual
Over Voltage
PROTECTION G1/G2
(G3 G8)
DEFAULT DISPLAY
IA = 1245 A
Ext Block
Yes
Yes
Dead Time
TD1
5.00 s
TD2
5.00 s
TD3
5.00 s
TD4
5.00 s
10 mn
Max cycles nb
10
Time period
No
No
Cycles
4321
tI>
1111
tI>>
1111
tI>>>
1111
tIe>
1111
tIe>>
1111
tIe>>>
1111
tPe/IeCos> 1111
tPe/IeCoss>>1111
tAux1
1111
tAux2
1111
5.00 s
E/Gnd Cycles
Phase Cycles
Inhib Time
tR
Reclaim Time
tR
5.00 s
No
F6
tF6
F2
F3
F4
F5
F6
F1
tF1
50.00 Hz
0.00 s
81> / 81<
No
No
No
No
No
50.00 Hz
0.00 s
81> / 81<
No
No
No
?
?
?
?
dF/dt6=
dF /dt6 ?
dF /dt2
dF /dt3
dF/dt4
dF /dt5
dF/dt1=
dF/dt1 ?
No
No
1.0 Hz/s
Yes
No
No
No
No
1.0 Hz/s
Yes
Page 20/24
No
No
Yes
Ext CB Fail ?
Yes
Rolling demand ?
No
Yes
No
0.05 s
0.05 s
0.05 s
0.05 s
0.05 s
0.05 s
F1 ?
Dead Time
tI>
tI>>
tI>>>
tIe>
tIe>>
tIe>>>
Autoreclose
No
[81] Frequency
[79] Autoreclose
AUTOMAT CTRL
P12y/EN HI/Fa5
Menu Content Tables
No
No
No
No
No
No
No
No
No
No
No
No
No
Trip tIe>
Trip tIe>>
Trip tIe>>>
Trip tIe_d>
Trip tIe_d>>
Trip
Trip
Trip
Trip
Trip
Trip
Trip
Trip
No
No
No
Trip Thermal No
Trip tI<
No
Trip tI2>
Trip tI2>>
Trip tI2>>>
tP>
tP >>
tP <
tP<<
tQ >
tQ >>
tQ<
tQ <
No
No
No
Trip tI>
Trip tI>>
Trip tI>>>
Trip Commands
P ROTECTION (prev)
DEFAULT DISPLAY
IA = 1245 A
No
No
No
No
tAux1
tAux2
tAux3
tAux4
tAux5
tAux6
tAux7
tAux8 (1)
tAux9 (1)
tAuxA (1)
tAuxB (1)
tAuxC (1)
tEQU. A ?
tEQU. H ?
Trip SOTF
Ctrl Trip
Trip
Trip
Trip
Trip
Trip
Trip
Trip
Trip
Trip
Trip
Trip
Trip
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Latch :87654321
00000000
Latch Relays
No
No
No
Block Thermal No
Block tI<
No
Block tI2>
Block tI2>>
Block tI2>>>
Block tPe/IeCos>
No
Block tPe/IeC os >>
No
tQ>
tQ>>
tQ<
tQ<<
No
No
No
No
No
No
No
No
Block
Block
Block
Block
Block
Block
Block
Block
No
No
Block tIe_d>
Block tIe_d>>
tP>
tP >>
tP <
tP<<
No
No
No
No
No
No
Block tIe>
Block tIe>>
Block tIe>>>
Block tI>
Block tI>>
Block tI>>>
Blocking Loqic 1 / 2
No
No
Block tU<
Block tU<<
No
No
No
No
No
No
No
No
No
No
No
No
Block TBrk.Cond
No
Block dF/dt1
Block dF/dt2
Block dF /dt3
Block dF/dt4
Block dF/dt5
Block dF /dt6
Block tF1
Block tF2
Block tF3
Block tF4
Block tF5
Block tF6
Block tV2> N o
Block tV2>> No
Block tUe>>>>
No
No
No
Block tU>
Block tU>>
No
Block tAux1 No
Block tAux2 No
Block tAux3 No
Block tAux4 No
Block tAux5 No
Block tAux6 No
Block tAux7 No
Block tAux8(1) No
Block tAux9(1) No
Block tAuxA(1) No
Block tAuxB(1) No
Block tAuxC(1)No
Inrush block. on
I>
Yes
I>>
No
I>>>
No
Ie>
Yes
Ie>>
No
Ie>>>
No
Ie_d>
No
Ie_d>>
No
I2>
Yes
I2>>
No
I2>>>
No
No
t Sel 1
150 ms
Sel 1 tle_d>>
No
Sel 1 tle_d>
No
T Inrush reset
0 ms
No
Sel 1 tI >>>
No
Sel1 tI >>
Inr. harmonic 2
ratio =
20.0%
Yes
Inrush blocking
No
Inrush blocking
Trip Brkn.Cond No
Trip dF /dt1
Trip dF/dt2
Trip dF/dt3
Trip dF /dt4
Trip dF/dt5
Trip dF/dt6
No
No
No
No
No
No
No
No
No
No
No
No
Trip
Trip
Trip
Trip
Trip
Trip
tF1
tF2
tF3
tF4
tF5
tF6
No
No
Trip tV2>
Trip tV2>>
Trip tUe>>>> No
Trip tU<
Trip tU<<
Trip tU>
Trip tU>>
AUTOMAT. C TRL
I>
tl >
I_R>
I >>
tl >>
I_R>>
I >>>
tl >>>
I_R>>>
tIA>
tIB>
tIC
Ie >
tle >
Ie_R>
Ie >>
tle >>
Ie_R>>
Ie >>>
tle >>>
Le_R >>>
Ie_d>
tIe_d>
tIe_dR>
Ie_d>>
tIe_d>>
tIe_dR>>
P>
tP>
P>>
tP>>
P<
tP<
P<<
tP<<
Q>
Trip
8765432
1000100
Output Relays
DEFAULT DISPLAY
IA = 1245 A
tQ >
Q>>
tQ >>
Q<
tQ<
Q<<
tQ<<
Pe/IeCos>
tPe/IeCos>
Pe/IeCos>>
tPe/IeCos>>
I2>
tI2>
I2>>
tI2>>
I2>>>
tI2>>>
Therm Alarm
Therm Trip
I<
tI<
U>
tU>
U>>
tU>>
U<
tU<
U<<
tU<<
Ue>>>>
tUe>>>>
V2>
tV2>
V2>>
tV 2>>
8765432
1000100
AUTOMAT. CTRL
F1
tF1
F2
tF2
F3
tF3
F4
tF4
F5
tF5
F6
tF6
F .OUT
dF/dt1
dF /dt2
dF /dt3
dF/dt4
dF /dt5
dF/dt6
Brkn Cond
CB Alarm
52 Fail
CB Fail
CB Close
tAux1
tAux2
tAux3
tAux4
tAux5(1)
tAux5
tAux6
tAux7
tAux8(1)
tAux9(1)
tAuxA(1)
8765432
1000100
tAuxB(1)
tAuxC(1)
79 Run
79 Trip
79 int. Lock.
79 ext. Lock.
SOTF
Control trip
Control Close
Active G roup
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Input 8 (1)
Input 9 (1)
Input A(1)
Input B (1)
Input C (1)
VTS
CTS
tEqu. A
tEqu. B
tEqu. C
tEqu. D
tEqu. E
tEqu. F
tEqu. G
tEqu. H
Order Comm1
Order Comm2
Order Comm3
Order Comm4
8765432
1000100
Unlatch
Blk Log 1
Blk Log 2
52 a
52 b
CB F LT
Aux 1
Aux 2
Aux 3
Aux 4
Aux 5
Aux 6
Aux 7
Aux 8 (1)
Aux 9 (1)
Aux A (1)
Aux B (1)
Aux C (1)
Strt Dist
Cold L PU
Log Sel 1
Log Sel 2
Changeset
Block 79
Reset
Trip Circ
Start tBF
Maint. M.
SOTF
Local
Synchro.
Reset led
Ctrl Trip
Ctr Close
Inputs 1/2/3/4/5/
6/7
8/9/A/B/C(1)
Inputs
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
s
s
s
s
s
s
s
s
s
s
s
s
Yes
No
Ratio I 2/I 1
20 %
Brkn.Cond Time
tBC
32 s
Yes
Brkn.Cond ?
No
No
Yes
Cold Load PU
tCL
2s
Cold Load PU
Level
120 %
Cold Load PU
tl> ?
Yes
tI>> ?
Yes
tI>>> ?
Yes
tIe> ?
Yes
tIe>> ?
Yes
tIe>>> ? Yes
tIe_d > ?
Yes
tIe_d>> ? Yes
tI2> ?
Yes
tI2>> ?
No
tI2>>> ? Yes
tTherm ?
Yes
Auto?
Input?
Cold Load PU ?
Yes
Cold Load PU
Page 22/24
Aux1 Time
tAux1
tAux2
tAux3
tAux4
tAux5
tAux6
tAux7
tAux8 (1)
tAux9 (1)
tAuxA (1)
tAuxB (1)
tAuxC(1)
Aux Time
Broken C onductor
P12y/EN HI/Fa5
Menu Content Tables
130.0V
No
V2>>
130.0V
Yes
(U<< OR V2>>)
& I>>>
No
No
V2>
Yes
(U< OR V2>)
& I>>
No
51V
No
tVTS
130.0V
VTS Non-dir
I> ?
Yes
I>> ?
Yes
I>>> ?
Yes
Ie> ?
Yes
Ie>> ?
Yes
Ie>>> ? Yes
Ie_d> ?
Yes
Ie_d>> ? Yes
Yes
V TS Blocks Protections ?
No
Yes
V TS Alarm ?
VT Supervision
DEFAULT DISPLAY
IA = 1245 A
No
tC TS
Ue<
Ie>
0.2s
5V
0.08 In
Yes
CT Supervision ?
No
CT Supervision
AUTOMAT. C TRL
No
Bloc Ie > ?
Yes
Block I > ?
No
Amps (n)
Amps (n) ?
3 E6
No
Yes
C B Open NB
1500
Yes
CB Open Alarm ?
Yes
C B Close Time
150 ms
Yes
CB Close Svision ?
Yes
CB Open Time
150 ms
Yes
Yes
Yes
No
[79] closing
SOTF Input
Yes
I >>>
I >>
Yes
100 ms
CB Open Svision ?
No
No
No
No
No
Yes
t trip circuit
tSUP
3s
tSotf
No
Sotf
SOTF
TC Supervision ?
No
C B Supervision
(1)
A.00
N ON E
A.00
N ON E
NONE
NONE
N one
tOrder Comm
tOrder Comm
tOrder Comm
tOrder Comm
Comm. Order
delay
2/2
OR
1/2
OR
AND NOT
AND
OR NOT
Equ.A Treset
=
0.00s
Equ.A Toperat.
=
0.00s
Equation
A/B/C/D/E/F/G/H
1
2
3
4
0.1s
0.1s
0.1s
0.1s
tClose Pulse
500 ms
tOpen Pulse
300ms
No
0.1 In
CB Fail Time
tBF
0.10 s
I < BF
No
Yes
CB F ail ?
CB Fail
5 E6
5 E6
5 E6
IC Magnitude
480 A
IB Magnitude
500 A
IA Magnitude
1200 A
Magnitude
1200 A
103 A
IN^VN ANGLE
103 A
IC^VBC ANGLE
103 A
IB^VBC AN GLE
IA^VBC ANGLE
103 A
Threshold
I>
VN Magnitude
103 A
VCA Magnitude
103 A
Faulted Phase
EARTH
Trip
Length
Origin
No
57 ms
Ie>
0.1 s
Time Window
5 mn
Records number
5
Pre-Time
Disturbance Record
1mn
N um of Sub P er
1
Sub Period
Rolling Demand
OP P ARAMETERS
Page 24/24
Amps (n) IC
Amps (n) IB
Amps (n) IA
Amps (n)
RST= [C]
09/01/01
Date
VBC Magnitude
103 A
Fault Date
09/01/01
1312
C B Operations
RST = [C]
Fault Time
12:05:23:42
CB Closing Time
100 ms
5
Hour
13:07:15:53
Number
Record Number
25
CB Opening Time
83 ms
VAB Magnitude
103 A
Instantaneous
Fault Record
RECORDS
CB Monitoring
DEFAULT DISPLAY
IA = 1245 A
P12y/EN HI/Fa5
Menu Content Tables
Technical Data
P12y/EN TD/Fa5
Technical Data
P12y/EN TD/Fa5
Page 1/46
CONTENT
1.
RATINGS
1.1
Power Supply
1.2
Frequency
1.3
Current Inputs
1.4
1.5
Voltage Inputs
1.6
Logic Inputs
1.7
2.
MECHANICAL DATA
3.
INSULATION WITHSTAND
4.
ELECTRICAL ENVIRONMENT
5.
ENVIRONMENT
6.
EU DIRECTIVE
10
6.1
EMC compliance
10
6.2
Product safety
10
7.
11
8.
13
9.
DEVIATION OF MEASUREMENTS
14
9.1
Measurements
14
9.2
14
10.
15
10.1
15
10.2
16
10.3
17
10.4
20
10.5
22
10.6
23
10.7
23
10.8
24
10.9
25
10.10
25
P12y/EN TD/Fa5
Page 2/46
Technical Data
MiCOM P125/P126 & P127
10.11
26
10.12
26
10.13
28
10.14
28
10.15
29
11.
31
11.1
Trip commands
31
11.2
Latch relays
31
11.3
Blocking logic
31
11.4
31
11.5
Logic select
32
11.6
Output relays
32
11.7
Inputs
32
11.8
33
11.9
33
11.10
34
11.11
34
11.12
CT Supervision (P127)
34
11.13
35
11.14
35
11.15
35
11.16
36
11.17
36
11.18
39
12.
RECORDING FUNCTIONS
40
12.1
Event Records
40
12.2
Fault Records
40
12.3
Instantaneous recorder
40
12.4
Disturbance Records
40
13.
COMMUNICATION
41
14.
IRIG-B INTERFACE
42
15.
CURVES
43
15.1
General
43
15.2
45
Technical Data
P12y/EN TD/Fa5
1.
RATINGS
1.1
Power Supply
1.2
1.3
Page 3/46
Operating range
DC 20% of Vx
AC 20%, +10% of Vx
Residual ripple
Up to 12%
50 ms for interruption of Vx
Burden P125
Stand by:
Max:
<3W DC or <8VA AC
<5W DC or <12VA AC
Burden P126
Stand by:
Max:
<3W DC or <8VA AC
<6W DC or <14VA AC
Burden P127
Stand by:
Max:
<3W DC or <8VA AC
<6W DC or <14VA AC
Frequency
Frequency protection functions
From 45 to 65Hz
Nominal frequency
50/60Hz
Current Inputs
Phase current inputs
1 and 5A by connection
1 and 5A by connection
Operating range
< 0.025VA
< 0.3VA
(1A)
(5A)
< 0.08VA
< 0.42VA
(1A)
(5A)
25 m
8 m
(1A input)
(5A input)
87 m
15 m
(1A input)
(5A input)
Thermal withstand
P12y/EN TD/Fa5
Technical Data
Page 4/46
1.4
1.5
1 and 5A by connection
Operating range
< 0.5VA
Bandwidth
500Hz
Thermal withstand
1s
4s
continuous
@ 20 x rated current
@ 10 x rated current
@ 2 x rated current
Voltage Inputs
Voltage input range Un
57 to 130V
220 to 480V
0 to 260V
0 to 960V
Burden
Resistive 44 k:
438 k:
0.074W/57V
0.38W/130V
1.54W/260V
0.1102W/220V
0.525W/480V
2.1W/960V
Thermal Withstand:
1.6
960V ph-ph
1300V ph-ph
Logic Inputs
1.6.1
Ordering
Code
< 5ms
Supply
Relay auxiliary power supply
Nominal
voltage range
Vx
Logic Inputs
Operating
Nominal
voltage range Voltage range
19,2 76 Vdc
Minimal
polarisation
voltage
Maximum
polarisation
current
Holding
current
after 2 ms
Maximum
continuous
withstand
24 - 60 Vdc
48 250 Vdc
48 240 Vac
24 250 Vdc
38.4 300 Vdc 24 240 Vac
38.4 264 Vac
19,2 Vdc
19,2 Vac
35 mA
2.3 mA
300 Vdc
264 Vac
48 250 Vdc
48 240 Vac
Special EA (**)
19,2 Vdc
19,2 Vac
35 mA
2.3 mA
300 Vdc
264 Vac
48 250 Vdc
48 240 Vac
129 Vdc
105 Vdc
145 Vdc
48 250 Vdc
48 240 Vac
110 Vdc
77 Vdc
132 Vdc
48 250 Vdc
48 240 Vac
220 Vdc
154 Vdc
262 Vdc
24 250 Vdc
24 250 Vac
19,2 Vdc
19,2 Vac
35 mA
300 Vdc
264 Vac
2.3 mA
(**) Logic input recognition time for EA approval. Dedicated filtering on 24 samples (15 ms at
50 Hz)
Technical Data
P12y/EN TD/Fa5
Page 5/46
Dry contact Ag Ni
Make current
Carry capacity
5A continuous
Rated Voltage
250Vac
Breaking characteristic
Breaking capacity AC
1500 VA resistive
1500 VA inductive (P.F. = 0.5)
220 Vac, 5A (cos = 0.6)
Breaking capacity DC
Operation time
<7ms
Durability
Loaded contact
Unloaded contact
P12y/EN TD/Fa5
Technical Data
Page 6/46
2.
MECHANICAL DATA
Design
MiCOM P125, P126 and P127 relays are available in a 4U metal case for panel or flush
mounting.
The table shows the case size of the different models:
Version
Height
Depth
Width
Type P125
4U (177mm)
230mm
20 TE
4U (177mm)
230mm
30 TE
Weight
P125 approx.:
3.0 Kg
P126/7 approx.:
4.0 Kg
Mounting
Rack or flush mounting
Connections
Rear (double fast on + M4 screw per connection)
Full draw-out with automatic CT shorting in the case of the relay
Enclosure protection
Per IEC 60529: 2001:
IP 50 Protection for the rear and sides of the case against dust,
IP 10 Product safety protection for the rear due to live connections on the terminal block
Dimensions
See dimensions diagram (P12y/EN IN chapter).
PC Interface
DIN 41652 connector (X6),
type D-Sub, 9-pin.
Technical Data
P12y/EN TD/Fa5
3.
Page 7/46
INSULATION WITHSTAND
Dielectric withstand
IEEE C39.90:1989
Impulse voltage
Insulation resistance
P12y/EN TD/Fa5
Technical Data
Page 8/46
4.
ELECTRICAL ENVIRONMENT
High frequency
disturbance
IEC 60255-22-1:1998
Fast transient
IEC 60255-22-4:2002
Class A
2 kV 5kHz terminal block comms
4 kV 2.5kHz all circuits excluding comms.
EN 61000-4-4:1995
Level 4
Electrostatic
discharge
EN 61000-4-2:1995 &
IEC60255-22-2:1996
Surge Immunity
EN 61000-4-5:1995 &
IEC 60255-22-5:2002
Conducted emissions
EN55022:1998 &
IEC 60255-25:2000
Radiated emissions
EN55022:1998 &
IEC 60255-25:2000
Conducted immunity
EN 61000-4-6:1996 &
IEC 60255-22-6:2001
Radiated Immunity
EN 61000-4-3:2002 &
IEC 60255-22-3:2000
Radiated Immunity
from digital
telephones
EN 61000-4-3:2002
ANSI/
IEEE C37.90.2:2004
EN 61000-4-8:1994
EN 61000-4-9:1993
Level 5, 1000A/m
EN 61000-4-10:1993
IEEE/
ANSI C37.90.1:2002
Magnetic field
immunity
Technical Data
P12y/EN TD/Fa5
5.
Page 9/46
ENVIRONMENT
Temperature
IEC 60255-6
Humidity
IEC 60068-2-78:2001
Enclosure
protection
Sinusoidal
Vibrations
IEC 60255-21-1:1998
Shocks
IEC 60255-21-2:1998
Bump
IEC 60255-21-2:1998
Seismic
IEC 60255-21-3:1998
Class 2
Creepage
Distances and
Clearances
Corrosive
Environments
P12y/EN TD/Fa5
Technical Data
Page 10/46
6.
EU DIRECTIVE
6.1
EMC compliance
89/336/EEC
93/31/EEC
Product safety
2006/95/EC
(replacing 73/23/EEC from
01/2007)
Technical Data
P12y/EN TD/Fa5
7.
Page 11/46
Phase current
Is
I2s
Ies
IesCos :
Pe
Pes
Us
Urs
V2
DT
Definite time
IDMT
Element
Range
Deviation
Phase overcurrent
elements
I> & I>> & I>>>
0.1 to 40 In
2%
Relay characteristic
angle RCA
(RCA-Torque angle)
0 to 359
Trip zone
10 to 170
0.002 to 1Ien
0.01 to 8 Ien
0.1 to 40 Ien
Active overpower
P>&P>>
Active underpower
P<&P<<
Reactive overpower
Q>&Q>>
Reactive underpower
Q<&Q<<
Wattmetric earth fault
elements
1 to 10000*1W
4 to 40000*1W
1 to 10000*5W
4 to 40000*5W
1 to 10000*1W
4 to 40000*1W
1 to 10000*5W
4 to 40000*5W
1 to 10000*1W
4 to 40000*1W
1 to 10000*5W
4 to 40000*5W
1 to 10000*1W
4 to 40000*1W
1 to 10000*5W
4 to 40000*5W
57 to 130V
0.2 to 20W
1 to 160W
10 to 800W
Trigger
Reset
Time deviation
DT: Is 2%
IDMT: 1.1Is 2%
0.95 Is 2%
1.05 Is 2%
2% +3050ms
5% +3050ms
2%
DT: Ies 2%
IDMT: 1.1Ies 2%
0.95 Ies 2%
1.05 Ies 2%
2% +3050ms
5% +3050ms
5%
2% +2040ms
5%
2% +2040ms
5%
2% +2040ms
5%
2% +2040ms
4% error
on cos
DT: Pes
accuracy
IDMT: 1.1Pes
accuracy
2% +3050ms
0.95 Pes
accuracy
1.05 Pes
accuracy
5% +3050ms
P12y/EN TD/Fa5
Technical Data
Page 12/46
Element
Deviation
Trigger
Reset
Time deviation
220 to 480V
1 to 80W
4 to 640W
40 to 3200W
4% error
on cos
DT: Pes
accuracy
IDMT: 1.1Pes
accuracy
0.95 Pes
accuracy
1.05 Pes
accuracy
2% +3050ms
0.002 to 1Ien
0.01 to 8 Ien
0.1 to 40 Ien
2% error
on cos
DT: IesCos
accuracy
IDMT: 1.1 IesCos
accuracy
0.95 IesCos
accuracy
1.05 IesCos
accuracy
2% +3050ms
Negative sequence
phase overcurrent
elements
I2>, I2>> & I2>>>
0.1 to 40 In
2%
DT: I2s 2%
IDMT: 1.1I2s 2%
0.95 I2s 2%
1.05 I2s 2%
2% +3050ms
5% +3050ms
Thermal overload
I>, Alarm, Trip
0.10 to 3.2 In
3%
IDMT: I> 3%
0.97 I>3%
5% +3050ms
(ref. IEC 60255-8)
Phase undercurrent
element I<
0.1 to 1 In
2%
DT: I< 2%
1.05 I< 2%
2% +3050ms
3%
DT: I2/I1 3%
57 to 130V
2 to 260V
2%
DT: Us 2%
0.95 Us 2%
2% +2040ms
220 to 480V
10 to 960V
2%
DT: Us 2%
0.95 Us 2%
2% +2040ms
57 to 130V
2 to 130V
2%
DT: Us 2%
1.05 Us 2%
2% +2040ms
220 to 480V
10 to 480V
2%
DT: Us 2%
1.05 Us 2%
2% +2040ms
57 to 130V
2%
DT: Urs 2%
0.95 Urs 2%
2% +2040ms
2%
DT: Urs 2%
0.95 Urs 2%
2% +2040ms
2%
or 0.2V
DT: Urs 2%
0.95 Urs 2%
2% +2040ms
2%
or 1V
DT: Urs 2%
0.95 Urs 2%
2% +2040ms
57 to 130V
1 to 130V
2%
DT: V2 2%
IDMT: 1.1 V2 2%
0.95 V2 2%
1.05 V22%
2% +3050ms
5% +3050ms
220 to 480V
4 to 480V
2%
DT: V2 2%
IDMT: 1.1 V2 2%
0.95 V2 2%
1.05 V2 2%
2% +3050ms
5% +3050ms
45,1 to 54,9Hz
2%
55,1 to 64,9Hz
DT: Fx 2%
0.95 Fx 2%
2% +80100ms
45,1 to 54,9Hz
2%
55,1 to 64,9Hz
DT: Fx 2%
1.05 Fx 2%
2% +80100ms
Overvoltage
U> & U>>
Undervoltage
U< & U<<
Residual overvoltage
(Direct input)
Ue>, Ue>>, Ue>>>,
Ue>>>>
5% +3050ms
5% +3050ms
1 to 260V
1 to 260V
220 to 480V
4 to 960V
5 to 960V
57 to 130V
Derived residual
overvoltage
Ue>, Ue>>, Ue>>>,
Ue>>>>
1 to 260V
1 to 260V
220 to 480V
4 to 960V
5 to 960V
Negative overvoltage
V2>, V2>>
Overfrequency
Fx>
Technical Data
MiCOM P125/P126 & P127
8.
P12y/EN TD/Fa5
Page 13/46
2% +1030ms
2% +1030ms
2% +1030ms
2% +2040ms
Inrush blocking
2% +2040ms
SOTF/TOR
2% +2040ms
2% +1030ms
P12y/EN TD/Fa5
Technical Data
Page 14/46
9.
DEVIATION OF MEASUREMENTS
9.1
Measurements
Measurement
Range
Deviation
Phase current
0.1 to 40 In
Typical 0.5% at In
Earth current
0.002 to 1Ien
0.01 to 8 Ien
0.1 to 40 Ien
57 to 260V
Typical 0.5% at Un
220 to 960V
Typical 0.5% at Un
Alpha
Typical 1 at Pn
P (active power)
Typical 5% at Pn
Q (reactive power)
Typical 5% at Pn
Voltage
Power
9.2
Cos
Deviation
Sin
Deviation
0.866
< 1.5%
0.866
< 3%
0.5
< 3%
0.5
< 1.5%
Accuracy
Phase current
<0.2% at IN
Voltage
<0.2% at VN
Power
Sampling rate
1600Hz
Technical Data
P12y/EN TD/Fa5
10.
10.1
10.1.1
P125
P126
P127
Phase current
Fundamental only
Fundamental only
Synchronous Polarisation
10.1.2
Page 15/46
[67] Phase OC
Min
Max
Step
I> ?
No or Yes or DIR
I>
0.1 In
Delay type
tI>
0s
150 s
0.01 s
I> TMS
0.025
1.5
0.001
DT or IDMT
I> RTMS
0.025
3.2
0.025
I> tReset
0.00 s
100 s
0.01 s
No or Yes
359
10
170
I>> ?
No or Yes or DIR
I>>
0.1 In
Delay type
tI>>
0s
25 In
40 In
150 s
0.01 In
0.01 In
0.01 s
P12y/EN TD/Fa5
Technical Data
Page 16/46
[67] Phase OC
10.2
Max
I>> TMS
0.025
DT or IDMT
I>> RTMS
Step
1.5
0.001
0.025
3,2
0.025
I>> tReset
0.00 s
100 s
0.01 s
359
10
170
I>>> ?
I>>>
0.1 In
40 In
0.01 In
tI>>>
0s
150 s
0.01 s
359
10
170
Phase current
NOTE:
10.2.1.1
Min
Fundamental only
When I> and I>> is associated to an IDMT curve, the maximum
setting recommended should be 2In.
[51] Phase OC
Min
Max
Step
I> ?
No or Yes
I>
0.1 In
Delay type
tI>
0s
150 s
0.01 s
I> TMS
0.025
1.5
0.001
DT or IDMT
I> RTMS
0.025
3.2
0.025
I> tReset
0.00 s
100 s
0.01 s
No or Yes
I>> ?
No or Yes
I>>
0.5 In
40 In
0.01 In
Delay type
tI>>
0s
150 s
0.01 s
I>> TMS
0.025
1.5
0.001
DT or IDMT
25 In
0.01 In
Technical Data
P12y/EN TD/Fa5
10.3
I>> RTMS
0.025
3.2
0.025
I>> tReset
0.00 s
100 s
0.01 s
I>>> ?
No or Yes or Peak
I>>>
0.5 In
40 In
0.01 In
tI>>>
0s
150 s
0.01 s
Fundamental only
Residual voltage
Fundamental only
0.7V
(Uen: 57 to 130V)
3.0V
NOTE:
10.3.1
Page 17/46
Setting Range
Min
Max
Step
Ie>
0.002 Ien
1 Ien
0.001 Ien
Ie>>
0.002 Ien
1 Ien
0.001 Ien
Ie>>>
0.002 Ien
1 Ien
0.001 Ien
Ie_d>
0.1 Ien
40 Ien
00.01 Ien
Ie_d>>
0.1 Ien
40 Ien
00.01 Ien
Ie>
0.01 Ien
1 Ien
0.005 Ien
Ie>>
0.01 Ien
8 Ien
0.005 Ien
Ie>>>
0.01 Ien
8 Ien
0.005 Ien
Ie_d>
0.1 Ien
40 Ien
00.01 Ien
Ie_d>>
0.1 Ien
40 Ien
00.01 Ien
Ie>
0.1 Ien
25 Ien
0.1 Ien
Ie>>
0.5 Ien
40 Ien
0.1 Ien
Ie>>>
0.5 Ien
40 Ien
0.1 Ien
Ie_d>
0.1 Ien
40 Ien
00.01 Ien
Ie_d>>
0.1 Ien
40 Ien
00.01 Ien
Ie> ?
No or Yes or DIR
P12y/EN TD/Fa5
Technical Data
Page 18/46
[67N] Earth OC
Min
Max
Step
Delay type
tIe>
0s
150 s
0.01 s
Ie> TMS
0.025
1.5
0.025
DT or IDMT
Ie> RTMS
0.025
3.2
0.025
Ie> tReset
0.00 s
100 s
0.01 s
No or Yes
359
10
170
1V
260 V
0.1 V
4V
960 V
0.5 V
Ie>> ?
No or Yes or DIR
Delay type
tIe>>
0s
150 s
0.01 s
Ie>> TMS
0.025
1.5
0.025
DT or IDMT
Ie>> RTMS
0.025
3.2
0.025
Ie>> tReset
0.00 s
100 s
0.01 s
tIe>>
0s
150
0.01 s
359
10
170
Ie>> tReset
0.00 s
100 s
0.01 s
1V
260 V
0.1 V
4V
960 V
Ie>>> ?
tIe>>>
0s
150 s
0.01 s
359
10
170
Ie>>> tReset
0.00 s
100 s
0.01 s
0.5 V
Technical Data
P12y/EN TD/Fa5
Page 19/46
Setting Range
[67N] Earth OC
Ue>>>
Min
1V
Max
260 V
Step
0.1 V
4V
960 V
0.5 V
1V
260 V
0.1 V
4V
960 V
0.5 V
Ie>>> ?
No or Yes or DIR
tIe>>>
0s
150 s
0.01 s
359
10
170
Ie>>> tReset
0.00 s
100 s
0.01 s
1V
260 V
0.1 V
4V
960 V
0.5 V
Ie_d> ?
No or Yes or DIR
Delay type
tIe_d>
0s
150 s
0.01 s
Ie_d> TMS
0.025
1.5
0.025
DT or IDMT
Ie> RTMS
0.025
3.2
0.025
Ie_d> tReset
0.00 s
100 s
0.01 s
Ie_d> Torque
359
10
170
1V
260 V
0.1 V
4V
720 V
0.5 V
Ie_d>> ?
No or Yes or DIR
Delay type
tIe_d>>
0s
150 s
0.01 s
Ie_d>> TMS
0.025
1.5
0.025
DT or IDMT
Ie>> RTMS
0.025
3.2
0.025
P12y/EN TD/Fa5
Technical Data
Page 20/46
[67N] Earth OC
Min
Max
Step
Ie_d>> tReset
0.00 s
100 s
0.01 s
Ie_d>> Torque
359
10
170
1V
130 V
0.1 V
4V
480 V
0.5 V
Fundamental only
Residual voltage
Fundamental only
ange from
57
to
130V
0.7 V
Range from
220
to
480V
3.0 V
0.002
to
1 Ien
1 mA
Range from
0.01
to
8 Ien
5 mA
Range from
0.1
to
NOTE:
10.4.1
40 Ien 50 mA
Functionality Mode
This protection element can operate in Pe or IeCos mode.
10.4.2
Technical Data
P12y/EN TD/Fa5
Page 21/46
The PE> threshold setting value is 20 W and is to be set from the front panel keypad:
if Ien = 1A, the internal relay setting value will be equal to 20 x 1 = 20W.
if Ien = 5a, the internal relay setting value will be equal to 20 x 5 = 100w.
Setting range
Min
Max
Step
Mode
Pe or IeCos
High sensitivity:
Pe> (*)
0.2xK W
20xK W
0.02xK W
Pe>> (*)
0.2xK W
20xK W
0.02xK W
Pe> (*)
1xK W
80xK W
0.1xK W
Pe>> (*)
1xK W
80xK W
0.1xK W
Med. Sensitivity:
Pe> (*)
1xK W
160xK W
0.1xK W
Pe>> (*)
1xK W
160xK W
0.1xK W
Pe> (*)
4xK W
640xK W
0.5xK W
Pe>> (*)
4xK W
640xK W
0.5xK W
Low sensitivity:
Pe> (*)
10xK W
800xK W
1xK W
Pe>> (*)
10xK W
800xK W
1xK W
Pe> (*)
40xK W
3200xK W
5xK W
Pe>> (*)
40xK W
3200xK W
5xK W
Pe> ?
No or Yes
Delay Type
tPe>
0s
150 s
0.01 s
Pe> TMS
0.025
1.5
0.025
DT or IDMT
Pe> RTMS
0.025
1.5
0.025
Pe> tReset
0.00 s
100 s
0.01 s
Pe>> ?
No or Yes
tPe>>
0s
150 s
0.01 s
Pe>> tReset
0.00 s
100 s
0.01 s
P12y/EN TD/Fa5
Technical Data
Page 22/46
10.5
10.5.1
Min
Max
Step
IeCos>
0.002 Ien
1 Ien
0.001 Ien
IeCos>>
0.002 Ien
1 Ien
0.001 Ien
IeCos>
0.01 Ien
8 Ien
0.005 Ien
IeCos>>
0.01 Ien
8 Ien
0.005 Ien
IeCos>
0.1 Ien
25 Ien
0.01 Ien
IeCos>>
0.5 Ien
40 Ien
0.01 Ien
IeCos> ?
Yes or No
Delay Type
tIeCos>
0s
150 s
0.01 s
IeCos> TMS
0.025
1.5
0.025
DT or IDMT
IeCos> RTMS
0.025
1.5
0.025
IeCos> tReset
0.00 s
100 s
0.01 s
IeCos>> ?
Yes or No
tIeCos>>
0s
150 s
0.01 s
IeCos> tReset
0.00 s
100 s
0.01 s
359
Undercurrent
Phase current:
Fundamental only
[37] Undercurrent
Min
Max
Step
I< ?
Yes or No
I<
0.1 In
1 In
0.01 In
tI<
0s
150 s
0.01 s
Yes or No
Yes or No
Yes or No
Technical Data
P12y/EN TD/Fa5
Phase current:
NOTE:
10.6.1
Page 23/46
Fundamental only
When I2> is associated to an IDMT curve, the maximum setting
recommended should be 2In.
[46] Neg.Seq. OC
10.7
Max
Step
I2> ?
No or Yes
I2>
0.1 In
Delay Type
tI2>
0s
150s
0.01s
I2> TMS
0.025
1.5
0.025
DT or IDMT
I2> RTMS
0.025
1.5
0.025
I2> tReset
0.04 s
100 s
0.01 s
I2>> ?
No or Yes
I2>>
0.5 In
40 In
0.01 In
tI2>>
0s
150s
0.01s
I2>>> ?
No or Yes
I2>>>
0.5 In
40 In
0.01 In
tI2>>>
0s
150s
0.01s
25 In
0.01 In
10.7.1
Min
Phase Current:
RMS
Setting range
Min
Max
Step
Therm. OL ?
No or Yes
0.1 In
3.2 In
0.01
Te
1 mn
200 mn
1mn
1,5
0.01
Trip
50%
200%
1%
Alarm ?
No or Yes
Alarm
50%
200%
1%
P12y/EN TD/Fa5
Technical Data
Page 24/46
10.8
10.8.1
AND or OR (*)
Min
Max
Step
U< ?
No or AND or OR
U<
2V
130 V
0.1 V
tU<
0s
600 s
0.01 s
Yes or No
U<< ?
No or AND or OR
U<<
2V
130 V
0.1 V
tU<<
0s
600 s
0.01 s
Yes or No
U< ?
No or AND or OR
U<
10 V
480 V
0.5 V
tU<
0s
600 s
0.01 s
Yes or No
U<< ?
No or AND or OR
U<<
10 V
480 V
0.5 V
tU<<
0s
600 s
0.01 s
Yes or No
Technical Data
P12y/EN TD/Fa5
10.9.1
Page 25/46
AND or OR (*)
Max
Step
U> ?
No or AND or OR
U>
2V
260 V
0.1 V
tU>
0s
260 s
0.01 s
U>> ?
No or AND or OR
U>>
2V
260 V
0.1 V
tU>>
0s
600 s
0.01 s
U> ?
No or AND or OR
U>
10 V
960 V
0.5 V
tU>
0s
600 s
0.01 s
U>> ?
No or AND or OR
U>>
10 V
960 V
0.5 V
tU>>
0s
600 s
0.01 s
(*)
10.10
Min
OR
trip caused by one or two or three phase values exceeding the threshold.
AND
OP PARAMETERS
Min
Max
Step
Frequency
50 Hz
60 Hz
N.A
[81] Frequency
Min
Max
Step
F1?
81> or 81< or No
F1
45,1 Hz
64,9 Hz
0.01 Hz
tF1
0s
600 s
0.01 s
F2?
81> or 81< or No
F2
45,1 Hz
64,9 Hz
0.01 Hz
tF2
0s
600 s
0.01 s
F3?
81> or 81< or No
F3
45,1 Hz
64,9 Hz
0.01 Hz
tF3
0s
600 s
0.01 s
F4?
81> or 81< or No
F4
45,1 Hz
64,9 Hz
0.01 Hz
P12y/EN TD/Fa5
Technical Data
Page 26/46
OP PARAMETERS
10.11
Min
600 s
Step
tF4
0s
F5?
81> or 81< or No
F5
45,1 Hz
64,9 Hz
0.01 Hz
tF5
0s
600 s
0.01 s
F6?
81> or 81< or No
F6
45,1 Hz
64,9 Hz
0.01 Hz
tF6
0s
600 s
0.01 s
0.01 s
OP PARAMETERS
10.12
Max
Min
dF/dt1 ?
Yes or No
dF/dt1
10Hz/s
dF/dt2 ?
Yes or No
dF/dt2
10Hz/s
dF/dt3 ?
Yes or No
dF/dt3
10Hz/s
dF/dt4 ?
Yes or No
dF/dt4
10Hz/s
dF/dt5 ?
Yes or No
dF/dt5
10Hz/s
dF/dt6 ?
Yes or No
dF/dt6
10Hz/s
Max
Step
+10Hz/s
0.1Hz/s
+10Hz/s
0.1Hz/s
+10Hz/s
0.1Hz/s
+10Hz/s
0.1Hz/s
+10Hz/s
0.1Hz/s
+10Hz/s
0.1Hz/s
Fundamental only
Power protection:
Technical Data
P12y/EN TD/Fa5
Page 27/46
Min
Max
Step
Yes or No
1 W*k (*)
Directional angle
359
0s
150 s
0.01 s
1 W*k (*)
Directional angle
359
0s
150 s
0.01 s
Yes or No
4 W*k (*)
Directional angle
359
0s
150 s
0.01 s
4 W*k (*)
Directional angle
359
0s
150 s
0.01 s
(*)
k = 1 if TC secondary ration = 1A
k = 5 if TC secondary ration = 5A
P12y/EN TD/Fa5
Technical Data
Page 28/46
10.13
Min
Max
Step
Ue>>>> ?
No or Yes
Ue>>>>
1V
260 V
0.1 V
tUe>>>>
0s
600 s
0.01 s
Ue>>>> ?
No or Yes
Ue>>>>
5V
960 V
0.5 V
tUe>>>>
0s
600 s
0.01 s
ATTENTION:
1
x(UA + UB + UC)
3
Min
Max
Step
V2> ?
No or Yes
V2>
1V
130 V
0.1 V
tV2>
0s
100 s
0.01 s
V2>> ?
No or Yes
V2>>
1V
130 V
0.1 V
tV2>>
0s
100 s
0.01 s
V2> ?
No or Yes
V2>
4V
480 V
0.5 V
tV2>
0s
100 s
0.01 s
V2>> ?
No or Yes
V2>>
4V
480 V
0.5 V
tV2>>
0s
100 s
0.01 s
Technical Data
P12y/EN TD/Fa5
Page 29/46
[79] Autoreclose
Min
Autoreclose ?
Yes or No
Ext. CB Fail ?
Yes or No
0.01 s
Aux1 ((I>) ?
Yes or No
Aux2 (Ie>) ?
Yes or No
Ext Block ?
Yes or No
Rolling Demand
Yes or No
Max cycles nb
Time period
Max
Step
600 s
0.01 s
100
10mn
24h
10mn
tD1
0.01 s
300 s
0.01 s
tD2
0.01 s
300 s
0.01 s
tD3
0.01 s
600 s
0.01 s
tD4
0.01 s
600 s
0.01 s
tI>
0.05 s
600 s
0.01 s
tI>>
0.05 s
600 s
0.01 s
tI>>>
0.05 s
600 s
0.01 s
tIe>
0.05 s
600 s
0.01 s
tIe>>
0.05 s
600 s
0.01 s
tIe>>>
0.05 s
600 s
0.01 s
0.02 s
600 s
0.01 s
tI
0.02 s
600 s
0.01 s
Phase Cycles
E/Gnd Cycles
Cycles
4321
Settings
tI>
1111
0 or 1 or 2
tI>>
1111
0 or 1 or 2
tI>>>
1111
0 or 1 or 2
tIe>
1111
0 or 1 or 2
tIe>>
1111
0 or 1 or 2
Dead time
Reclaim time
tR
Inhib time
P12y/EN TD/Fa5
Technical Data
Page 30/46
[79] Autoreclose
Max
tIe>>>
1111
0 or 1 or 2
tPe/Iecos>
1111
0 or 1 or 2
tPe/Iecos>>
1111
0 or 1 or 2
tAux1
1111
0 or 1 or 2
tAux2
1111
0 or 1 or 2
Step
With:
0 = no action on autorecloser: definitive trip
1 = trip on pick up of the protection element, followed by reclosing cycle
2 = no trip on pick up of the protection element also if this has been set in the CRTL/Trip
commands/Trip menu
10.15.2 Further timing
Fixed time out for lacking of CB opening signal on trip protection:
Time out for lacking of CB closing signal on close control after dead time:
tClose Pulse(*): from 0.1 to 5.00 s in steps of 0.01 s
(*) Setting available in CB monitoring menu.
2.00 s at 50 Hz
1.67 s at 60 Hz
Technical Data
P12y/EN TD/Fa5
Page 31/46
11.
11.1
Trip commands
Assignation of the following thresholds to trip output relays:
11.2
all models: tIe>, tIe>>, tIe>>>, tPe/IeCos>, tPe/IeCos>> , tUe>>>>, tAux 1, tAux 2, tAux
3, tAux 4, Ctrl Trip,
P126 and P127 only, tI> , tI>> , tI>>> , tI2>, tI2>>, tI2>>>, Thermal , Brkn. Cond ,
SOTF, tEQUATION A, tEQUATION B, tEQUATION C ,t EQUATION D , tEQUATION E ,
tEQUATION F, tEQUATION G, tEQUATION H
P127 only: tIe_d>, tIe_d>>, tP>, tP>>, tU>, tU>>, tU<, tU<<, tV2>, tV2>>, tF1, tF2 , tF3 ,
tF4 , tF5 , tF6 , dF/dt1, dF/dt2, dF/dt3, dF/dt4, dF/dt5, dF/dt6, tAux 5, tAux 6, tAux 7,
tAux 8, tAux 9, tAux A, tAux B, tAux C
Latch relays
Number of relay settable:
11.3
P125
P126
P127
Blocking logic
Possibility to block the following delayed thresholds:
11.4
all models: tIe>, tIe>>, tIe>>>, tPe/IeCos>, tPe/IeCos>>, tUe>>>>, tAux1, tAux2, tAux3,
tAux4,
P126 and P127: tI>, tI>>, tI>>>, tI2>, tI2>>, tI2>>>, tThermal , tI<, tBrk. Cond
P127: tIe_d>, tIe_d>>, tP>, tP>>, tP<, tP<<, tQ>, tQ>>, tQ<, tQ<<, tU>, tU>>, tU<,
tU<<, tV2>, tV2>>, tF1 , tF2 , tF3 , tF4 , tF5 , tF6 , dF/dt1, dF/dt2, dF/dt3, dF/dt4, dF/dt5,
dF/dt6, tAux5, tAux6, tAux7, tAux8, tAux9, tAuxA, tAuxB, tAuxC,
Setting range
Min
Max
Step
Inrush Block
Yes or No
Inrush H2 ration
10 %
35 %
0,1 %
Inrush tReset
0 ms
2s
0,1 s
Block I>
No
Yes
Yes or No
Block I>>
No
Yes
Yes or No
Block I>>>
No
Yes
Yes or No
Block Ie>
No
Yes
Yes or No
Block Ie>>
No
Yes
Yes or No
Block Ie>>>
No
Yes
Yes or No
Block I2>
No
Yes
Yes or No
Block I2>>
No
Yes
Yes or No
Block I2>>>
No
Yes
Yes or No
No
Yes
Yes or No
P12y/EN TD/Fa5
Technical Data
Page 32/46
11.5
Logic select
Logic selectivity 1 and logic selectivity 2: this function is used to assign each time delay to
threshold to the Log Sel input.
Setting range
Blocking Inrush
11.6
Min
Sel1 tI>>
Yes or No
Sel1 tI>>>
Yes or No
Sel1 tIe>>
Yes or No
Sel1 tIe>>>
Yes or No
Sel1 tIe_d>
Yes or No
Sel1 tIe_d>>
Yes or No
T Sel1
0s
Max
150s
Step
10ms
Output relays
Alarm and trip threshold assignation to a logic output: 6 relays (P125), 8 relays (P126 and
P127).
Assignable functions:
all models: Ie>, tIe>, Ie_R>, Ie>>, tIe>>, Ie_R>>, Ie>>>, tIe>>>, Ie_R>>>, Pe/IeCos>,
tPe/IeCos>, Pe/IeCos>>, tPe/IeCos>>, Ue>>>>, tUe>>>>, tAux1, tAux2, tAux3, tAux4,
CONTROLTRIP, CONTROLCLOSE, ActiveGroup, Input1, Input2, Input3:, Input4,
P126 and P127: Trip, I>, tI>, I_R>, I>>, tI>>, I_R>>, I>>>, tI>>>, I_R>>>, tIA>, tIB>,
tIC>, I2>, tI2>, I2>>, tI2>>, I2>>>, tI2>>>, ThermAlarm, ThermTrip, I<, tI<, BrknCond,
CBAlarm, 52 Fail, CBFail , CB Close , 79 Run, 79 Trip, SOTF, Input5, Input6, Input7,
t EQU.A, t EQU.B, t EQU.C, t EQU.D, t EQU.E, t EQU.F, t EQU.G, t EQU.H, 79 int.
Lock, 79 Ext Lock,
P127: Ie_d>, tIe_d>, Ie_dR>, tIe_dR>, Ie_d>>, tIe_d>>, Ie_dR>>, tIe_dR>>, P>, tP>,
P>>, tP>>, U>, tU>, U>>, tU>>, U<, tU<, U<<, tU<<, V2>, tV2>, V2>>, tV2>>, F1, tF1,
F2, tF2, F3, tF3, F4, tF4, F5, tF5, F6, tF6, dF/dt1, dF/dt2, dF/dt3, dF/dt4, dF/dt5, dF/dt6,
F.OUT, tAux5, tAux6, tAux7, tAux8, tAux9, tAuxA, tAuxB, tAuxC, VTS, CTS,
Command1, Command2, Command3, Command4
11.7
Inputs
11.7.1
Inputs assignation
Single function or multiple automation functions assignable to 4 (P125) or 7 (P126 and P127)
logic inputs:
all models: None, Unlatch, Blk Log 1, Aux 1, Aux 2, Aux 3, Aux 4, Maint. M, Man.
Close, Local, Synchronisation, LED Reset (or reset LED),
P126 and P127: Blk Log 2, 52 a, 52 b, CB FLT, Reset, Change set, Log Sel 2, Cold
L PU, Strt Dist, Block_79, Trip Circ, Start t BF, Ctrl Trip, Ctrl Close
P127: Aux 5, Aux 6, Aux 7, Aux 8, Aux 9, Aux A, Aux B, Aux C, Log Sel 1
Technical Data
P12y/EN TD/Fa5
Page 33/46
Auxiliary timers
11.8
11.8.1
Setting range
Min
Max
Step
tAux1
200 s
0.01 s
tAux2
200 s
0.01 s
tAux3
200 s
0.01 s
tAux4
200 s
0.01 s
tAux5
200 s
0.01 s
tAux6
200 s
0.01 s
tAux7
20000 s
0.01 s
tAux8
20000 s
0.01 s
tAux9
20000 s
0.01 s
tAuxA (tAux10)
200 s
0.01 s
tAuxB (tAux11)
200 s
0.01 s
tAuxC (tAux12)
200 s
0.01 s
I2/I1
11.9
Setting range
Min
Max
Step
Brkn.Cond ?
Yes or No
Ratio I2/I1
20%
100%
1%
1s
14400s
1s
Setting range
Min
Cold Load PU ?
Yes or No
Input?
Yes or No
Auto?
Yes or No
Max
Step
Cold Load pickup activable with: tI>, tI>>, tI>>>, tIe>, tIe>>, tIe>>>,
tIe_d, tIe_d>>, tI2>, tI2>>, tI2>>> and/or tTherm
Cold Load PU level
20%
800%
1%
tCL
0.1s
3600s
0.1s
P12y/EN TD/Fa5
Technical Data
Page 34/46
11.10
Setting range
Min
Max
Step
Yes or No
V2>
3V
Yes or No
V2>
3V
200V
0.1V
200V
0.1V
720V
0.5V
720V
0.5V
11.11
Yes or No
V2>
20V
Yes or No
V2>
20V
Yes or No
VTS Alarm
Yes or No
11.12
Setting range
Min
VTS?
Yes or No
VTS Alarm
Yes or No
Yes or No
Yes or No
Yes or No
tVTS
0s
Max
100s
Step
10ms
CT Supervision (P127)
Setting range
Min
Max
Step
CT Supervision
Yes or No
Ie>
0.08 In
1.0 In
0.01 In
Ue< (P127xA)
0.5V
22V
0.1V
Ue< (P127xB)
2V
88V
0.5V
tCTS
0s
100s
0.01s
Technical Data
P12y/EN TD/Fa5
Page 35/46
11.14
Setting range
Min
Max
Step
CB Fail ?
Yes or No
I< BF
0.02 In
1In
0.01 In
0s
10 s
0.01 s
Block I>
Yes or No
Block Ie>
Yes or No
11.15
Setting range
Min
TC Supervision ?
Yes or No
0.1 s
Max
10 s
Step
0.01 s
Setting range
Min
Max
Step
CB Open Svision?
Yes or No
CB Open time
0.05 s
CB Close Svision?
Yes or No
CB Close time
0.05 s
CB Open Alarm ?
Yes or No
CB Open NB
Amps(n) ?
Yes or No
Amps(n)
0 E6 A
4000 E6 A 1E6 A
tOpen Pulse(*)
0.10 s
5s
0.01 s
tClose Pulse(*)
0.10 s
5s
0.01 s
1s
0.01 s
1s
0.01 s
50000
(*) Note: The tOpen/Close Pulse is available in the P125 for the Local /Remote functionality
P12y/EN TD/Fa5
Technical Data
Page 36/46
11.16
11.17
Setting range
Min
SOTF?
Yes or No
t SOTF
0 ms
I>>
Yes or No
I>>>
Yes or No
Yes or No
SOTF input
Yes or No
Yes or No
[79] closing
Yes or No
Yes or No
Yes or No
Yes or No
Max
500 ms
Step
10ms
(1/2): logical gates (NOT, OR, AND, NOT AND, NOT OR)
Setting range
EQU. A Toperat
0s
600 s
0.01 s
EQU. A Treset
0s
600 s
0.01 s
EQU. B Toperat
0s
600 s
0.01 s
EQU. B Treset
0s
600 s
0.01 s
EQU. C Toperat
0s
600 s
0.01 s
EQU. C Treset
0s
600 s
0.01 s
EQU. D Toperat
0s
600 s
0.01 s
EQU. D Treset
0s
600 s
0.01 s
EQU. E Toperat
0s
600 s
0.01 s
EQU. E Treset
0s
600 s
0.01 s
EQU. F Toperat
0s
600 s
0.01 s
EQU. F Treset
0s
600 s
0.01 s
EQU. G Toperat
0s
600 s
0.01 s
EQU. G Treset
0s
600 s
0.01 s
Min
Max
Step
Technical Data
P12y/EN TD/Fa5
Page 37/46
logic equat
T delay
Setting range
EQU. H Toperat
0s
600 s
0.01 s
EQU. H Treset
0s
600 s
0.01 s
Min
Max
Step
Availability (1/2)
NOT
A00
B00
C00
D00
E00
F00
G00
H00
OR (by default)
A01 to A15
B01 to B15
C01 to C15
D01 to D15
E01 to E15
F01 to F15
G01 to G15
H01 to H15
AND
AND NOT
OR NOT
Signals (2/2)
Pe>, Pe>>
tPe>, tPe>>
t Aux 1 to t Aux 4
Alarm
Trip
I<
P12y/EN TD/Fa5
Technical Data
Page 38/46
TEXT
Signals (2/2)
tI<
tBC
U>, U>>
tU>, tU>>
U<, U<<
tU<, tU<<
Ue>>>>
tUe>>>>
tBC
79 Trip
P>, P>>
tP>, tP>>
P<, P<<
tP<, tP<<
Q>, Q>>
tQ>, tQ>>
Q<, Q<<
tQ<, tQ<<
V2>, V2>>
tV2>, tV2>>
F1 to F6
tF1 to tF6
dF/dt1 to dF/dt6
VTS
CTS
Ie_d>, Ie_d>>
tIe_d>, tIe_d>>
79 i.Blo
79 e.Blo
Technical Data
P12y/EN TD/Fa5
11.18
Page 39/46
TEXT
Signals (2/2)
tEQU. A to tEQU. H
Results of equations A to H.
CB FLT
C.Order1 to C.Order4
Setting range
tCommand 1
0s
600s
50ms
tCommand 2
0s
600s
50ms
tCommand 3
0s
600s
50ms
tCommand 4
0s
600s
50ms
Min
Max
Step
P12y/EN TD/Fa5
Technical Data
Page 40/46
12.
RECORDING FUNCTIONS
12.1
Event Records
12.2
12.3
Capacity
250 events
Time-tag
1 millisecond
Triggers
Fault Records
Capacity
25 faults
Time-tag
1 millisecond
Triggers
Data
Fault date
Protection thresholds
Setting Group
AC inputs measurements (RMS)
Fault measurements
Instantaneous recorder
Capacity
Time-tag
1 millisecond
Triggers
Data
date, hour
origin (any protection alarm)
length (duration of the instantaneous trip yes or no
12.4
Disturbance Records
12.4.1
Data
AC input channels
digital input and output states
frequency value
Default value
Setting range
Min
Max
Step
Records number
Pre-Time
0.1s
0.1
2.9 / 4.9 /
6.9 or 8.9
0.1
ON TRIP
ON TRIP or ON INST.
Trigger
Technical Data
P12y/EN TD/Fa5
13.
Type
Port
Page 41/46
COMMUNICATION
Relay
position
Physical Link
Protocol
P12y/EN TD/Fa5
Page 42/46
14.
Technical Data
MiCOM P125/P126 & P127
IRIG-B INTERFACE
The IRIG-B is a P127 optional interface used to receive synchronization signal from a GPS
clock.
Type: Modulated (1kHz) or demodulated
Interface:
Technical Data
P12y/EN TD/Fa5
15.
CURVES
15.1
General
Page 43/46
Although the curves tend towards infinite when the current approaches Is (general
threshold), the minimum guaranteed value of the operating current for all the curves with the
inverse time characteristic is 1.1Is (with a tolerance of 0.05Is).
15.1.1
t = T
+
L
(I I S ) 1
Where:
t
Operation time
Is
Type of curve
Standard
K factor
factor
L factor
Schneider
Electric
0.05
0.04
Standard inverse
IEC
0.14
0.02
Very inverse
IEC
13.5
Extremely inverse
IEC
80
Schneider
Electric
120
C02
0.02394
0.02
0.01694
Moderately Inverse
ANSI/IEEE
0.0515
0.02
0.114
C08
5.95
0.18
Very inverse
ANSI/IEEE
19.61
0.491
Extremely inverse
ANSI/IEEE
28.2
0.1217
Rectifier protection
RECT
45900
5.6
1
0 .339
0.236
I
Is
( )
P12y/EN TD/Fa5
Technical Data
Page 44/46
15.1.2
Reset Timer
The first stage thresholds for phase and earth overcurrent protection, negative sequence
overcurrent and wattmetric/IeCos are provided with a timer hold facility "t Reset".
It may be set to a definite time value or to an inverse definite minimum time characteristic
(IEEE/ANSI curves only). This may be useful in certain applications, for example when
grading with upstream electromechanical overcurrent relays that have inherent reset time
delays.
The second and third stage thresholds for the wattmetric/IeCos protection and earth fault
overcurrent protection only have a definite time reset.
A possible situation where the reset timer may be used is to reduce fault clearance times
where intermittent faults occur.
An example may occur in a cable with plastic insulation. In this application it is possible that
the fault energy melts the cable insulation, which then reseals after clearance, thereby
eliminating the cause for the fault. This process repeats itself to give a succession of fault
current pulses, each of increasing duration with reducing intervals between the pulses, until
the fault becomes permanent.
When the reset time of the overcurrent relay is set to minimum the P125, P126 and P127
relays will be repeatedly reset and will not be able to trip until the fault becomes permanent.
By using the reset timer hold function the relay will integrate the fault current pulses, thereby
reducing fault clearance time.
The mathematical formula applicable to the five curves is:
K
t = T
1 (I I S )
Where:
Reset time
Is
Type of curve
Standard
K factor
factor
C02
2.261
Moderately inverse
ANSI/IEEE
4.850
C08
5.950
Very inverse
ANSI/IEEE
21.600
Extremely Inverse
ANSI/IEEE
29.100
Technical Data
P12y/EN TD/Fa5
Page 45/46
(I (kxIFLC ) )
(I Ip )
Where:
t
IFLC
IP
The time to trip varies depending on the load current carried before application of the
overload, i.e. whether the overload was applied from "hot" or "cold".
Curves of the thermal overload time characteristic are given in Technical Data.
The mathematical formula applicable to MiCOM Relays is the following
K -
t Trip = Te In
K trip
Where:
t Trip
Te
Ieq
I>
= Full load current rating given by the national standard or by the supplier
alarm = Initial thermal state. If the initial thermal state = 30% then =0.3
trip
= Trip thermal state. If the trip thermal state is set at 100%, then trip = 1
The settings of these parameters are available in the various menus. The calculation of the
thermal state is given by the following formula:
Ieq
+1 =
kxI >
1 e
t
Te
+ e
t
Te
P12y/EN TD/Fa5
Technical Data
Page 46/46
BLANK PAGE
Getting Started
P12y/EN GS/Fa5
GETTING STARTED
Getting Started
MiCOM P125/P126 & P127
P12y/EN GS/Fa5
Page 1/30
CONTENT
1.
1.1
System Connections
1.2
2.
2.1
2.1.1
2.1.2
Password protection
2.1.3
2.1.4
2.1.5
Menu navigation
2.2
Menu structure
3.
LOCAL CONNECTION TO A PC
3.1
Configuration
3.1.1
REMOTE connection
3.2
3.3
3.4
3.5
MiCOM S1 Studio
3.5.1
3.5.2
12
3.5.3
Create a system
15
3.5.4
16
3.5.5
17
3.5.6
17
3.5.7
18
3.5.8
19
3.6
MiCOM S1
21
3.6.1
Starting MiCOM S1
21
3.6.2
23
3.6.3
25
3.6.4
MiCOM monitoring
25
3.7
27
4.
28
5.
30
P12y/EN GS/Fa5
Getting Started
Page 2/30
BLANK PAGE
Getting Started
P12y/EN GS/Fa5
1.
Page 3/30
1.1
1.2
System Connections
1.
2.
Check that the contacts of output relay RL1 are included in your trip circuit.
1.00 A
P12y/EN GS/Fa5
Getting Started
Page 4/30
2.
2.1
2.1.1
2.1.2
Password protection
Password protection is applicable to most of the relay parameter settings, especially to the
selection of the various thresholds, time delays, communication parameters, allocation of
logic inputs and logic outputs.
The password consists of four capital characters. When leaving the factory, the password is
set to AAAA. The user can define any combination of four characters.
Should the password be lost or forgotten, the modification of stored parameters is blocked. It
is then necessary to contact the manufacturer or his agent and by specifying the serial
number of the relay, a stand-by password specific to the relay concerned may be obtained.
NOTE:
The programming mode is indicated with the letter "P" on the right
hand side of the display on each menu heading. The letter "P"
remains present as long as the password is active (5 minutes if there
is no action on the keypad).
Go to the OP. Parameters menu by pressing and then to the password menu by
pressing ,
Enter the current password (default password = AAAA) and validate with (this
operation is not necessary if the password has been entered some minutes ago),
Enter the new password character by character, using and arrows to change a
letter (maintain the key pressed to scroll through the letter in the alphabet). Use and
arrows to select another character: a flashing cursor will indicate which character field of
the password may be entered.,
Validate using or cancel using . If the password is correct, the following message is
displayed on the LCD: PASSWORD OK
Getting Started
P12y/EN GS/Fa5
Page 5/30
As soon as the password has been entered, no setting change will be accepted via the
remote or local communication port (RS485 or RS232).
Alternatively, the password can be entered by using the Password window in the
OP.PARAMETERS menu. This password entry procedure is the same as above.
NOTE:
2.1.3
2.1.4
If the optional IRIG-B board is installed (P127 option), date and time
synchronization could be automatic.
Go to the OP. Parameters menu by pressing and then to the Date menu by
pressing (x9),
If necessary, enter the current password and validate with ,
Set the date using or arrow, and validate with (10/11/08 means November 10th
2008),
NOTE:
When you modify the date, the first digit for the day or the month can
be selected according to the second digit. For instance, if 13/09/08 is
displayed, you cannot select 33 for the day, or 29 for the month.
Menu navigation
A simple menu structure (refer to P12y/EN GS section) allows setting and reading of
parameters and functionality.
The keypad provides full access to the menu options, with informations displayed on the
LCD.
Press , , and keys for menu navigation:
Press or keys to navigate from a menu heading to another menu heading (refer to
the figure below),
Press key to access to a sub menu, then navigate using or keys.
Maintain these keys pressed to scroll through the menu,
If necessary, modify a parameter by pressing key.
Modify the corresponding parameter using arrows,
Validate using , or cancel using .
P12y/EN GS/Fa5
Page 6/30
2.2
Menu structure
The menu structure is shown below.
Getting Started
MiCOM P125/P126 & P127
Getting Started
P12y/EN GS/Fa5
3.
LOCAL CONNECTION TO A PC
3.1
Configuration
Page 7/30
MiCOM
io
S1 Stud
P0107ENc
For a local connection between a PC and the relay, a serial cable with metallic shield should
be used.
The wiring of the RS232 cable must be as shown in the following drawing.
RS232 PC PORT
9 pin male connector
P0073ENa
REMOTE connection
The figure shows the recommended way to connect a RS485 cable to the relay to build a
local network.
P12y/EN GS/Fa5
Getting Started
Page 8/30
3.2
31
shield
RS485 cable
P0253ENa
3.3
EARTH
Earth
P0254ENa
Getting Started
P12y/EN GS/Fa5
Page 9/30
3.5
MiCOM S1 Studio
3.5.1
P12y/EN GS/Fa5
Getting Started
Page 10/30
Select the Add option to add the new data model then click on the Next button.
The next panel is used to select the model source (CD ROM, local folder or Schneider
Electric FTP server [DEFAULT FTP]). Select the model source and click on the next button.
NOTE:
Getting Started
P12y/EN GS/Fa5
Page 11/30
The Data Model Manager loads data models details, and then displays automatically the
language selection option panel. Select the menu language(s) and click on the Next button.
1
2
The data models panel is displayed. Select the data model for your product (for instance, to
download P12x data models, open the Px10/Px20/Px20C/M/Modulex sub-menu (click on
+ then select data model according to your product). When data models are selected, the
Data Model Manager panel displays the selected models size to download.
1
2
P12y/EN GS/Fa5
Getting Started
Page 12/30
Click on Install button. The model files are downloaded and updated in the system.
When installation has been completed, close the Data Model Manager. This Data Model is
used with MiCOM S1 Studio when a system is opened or created. To open this default
setting file, refer to 3.5.8.
3.5.2
Toolbar
Toolbar
Start page
Search
Search results
results view
view
P0841FRb
Click on the Quick Connect button at the top left of the application:
Getting Started
MiCOM P125/P126 & P127
P12y/EN GS/Fa5
Page 13/30
When a system is opened (or created), the following device type window is displayed.
P12y/EN GS/Fa5
Page 14/30
Getting Started
MiCOM P125/P126 & P127
Upon a successful connection, a dialog will be displayed showing device type, model
number and plant reference. Options for language, device name and comment are also
available.
The device is displayed in the Studio Explorer panel.
Getting Started
P12y/EN GS/Fa5
Page 15/30
Create a system
In MiCOM S1 Studio, a System provides a root node in the Studio Explorer from which all
subsequent nodes are created.
Substations, bays, voltage levels and devices are added to the system. If a system is no
longer needed, It can be deleted using the delete command.
The use of Quick Connect will automatically create a default system, if one does not already
exist. Systems are not opened automatically, unless Reopen last System at start-up is
selected in Options / Preferences menu.
To create a new system:
By default, the window displays the message create new or open existing system: click
on new to create a new system.
If a system is loaded in the Studio Explorer window, right-click on the panel background
and select New System or select the corresponding icon on Studio Explorer's toolbar.
or
The following window is displayed: Enter the name of the system, and the path to save the
system file.
P12y/EN GS/Fa5
Getting Started
Page 16/30
NOTE:
3.5.4
Click on new substation icon (or select the menu using right-click). The following window is
displayed:
Getting Started
P12y/EN GS/Fa5
Page 17/30
The new substation is displayed and the menu bar is updated when a substation is selected:
Import SCL
Create a new voltage level
P0902ENa
P0903ENa
3.5.6
P12y/EN GS/Fa5
Getting Started
Page 18/30
3.5.7
1
2
3
4
Getting Started
P12y/EN GS/Fa5
Page 19/30
3.5.8
Extract Settings
P0904ENa
P12y/EN GS/Fa5
Getting Started
Page 20/30
1
2
Select the Model and click on the Finish button. The default settings are displayed.
1
2
Getting Started
P12y/EN GS/Fa5
MiCOM S1
3.6.1
Starting MiCOM S1
To start MiCOM S1 Studio, click on the icon:
Page 21/30
WARNING:
P12y/EN GS/Fa5
Getting Started
Page 22/30
-
).
NOTE:
Select the User Manual button to read setting & records and
Measurement Viewer description and operating procedures.
Getting Started
P12y/EN GS/Fa5
Page 23/30
P12y/EN GS/Fa5
Getting Started
Page 24/30
When this has been entered, a prompt for the password appears.
When these have been entered satisfactorily the relay is then able to communicate with
MiCOM S1. When a communication link has been established between the PC and a
MiCOM IED, both are said to be online. Data and information can be directly transferred from
and to the IED using the menu available under the DEVICE menu.
For further instruction on how to extract, download and modify settings files, please refer to
the MiCOM S1 User Manual.
Select the main function in the right hand window.
To modify a setting value, double click the corresponding line in the left hand window. It
opens a setting window.
A red star () indicates that a setting value is modified.
1
2
Getting Started
P12y/EN GS/Fa5
Page 25/30
This brings up a prompt for the relay model type where you can select the correct relay for
your application:
Clicking on OK will open the default file and you can start to edit settings. For further
instruction on how to extract, download and modify settings files, please refer to the MiCOM
S1 User Manual.
3.6.4
MiCOM monitoring
The monitoring module enables to connect to the front port, retrieve and monitor its
measurements.
Click on the monitoring button:
P12y/EN GS/Fa5
Page 26/30
Getting Started
MiCOM P125/P126 & P127
Getting Started
P12y/EN GS/Fa5
Page 27/30
),
Click on the presentation and Analysis of Disturbance Recording Data with Wavewin
window.
The Wavewin File Manager is displayed (refer to the Wavewin Users guide to operate
Wavewin).
P12y/EN GS/Fa5
Page 28/30
4.
Getting Started
MiCOM P125/P126 & P127
Depose the four retaining screws in the top and the bottom side of the relay. These screws
retain the relay to the case.
Getting Started
MiCOM P125/P126 & P127
P12y/EN GS/Fa5
Page 29/30
Insert a 3mm screwdriver into the hole situated under the upper hinged cover above the
LCD:
Insert the screwdriver into the second hole under the lower hinged cover, and the lower lock
pin is turned 90 to the right.
By this turning action, push slightly forward the module and
extract it by pulling on both sides of the front panel.
P12y/EN GS/Fa5
Page 30/30
5.
Getting Started
MiCOM P125/P126 & P127
Application Guide
P12y/EN AP/Fa5
APPLICATION GUIDE
Application Guide
P12y/EN AP/Fa5
Page 1/96
CONTENT
1.
INTRODUCTION
1.1
2.
2.1
2.2
2.2.1
Description
2.2.2
Synchronous Polarisation
2.2.3
I>I>>I>>> Interlock
10
2.2.4
Setting Guidelines
11
2.2.5
12
2.3
14
2.3.1
14
2.3.2
I>I>>I>>> Interlock
14
2.3.3
15
2.4
16
2.4.1
18
2.4.2
18
2.4.3
20
2.4.4
Application Considerations
21
2.4.5
Iecos protection
21
2.4.6
21
2.5
22
2.5.1
Ie>Ie>>Ie>>> Interlock
23
2.6
23
2.6.1
Overview
23
2.6.2
Relay Connection
24
2.6.3
25
2.6.4
26
2.6.5
26
2.7
26
2.7.1
27
2.7.2
27
2.7.3
Setting Guidelines
28
2.8
28
2.9
28
2.9.1
29
2.10
30
2.10.1
Introduction
30
P12y/EN AP/Fa5
Page 2/96
Application Guide
MiCOM P125/P126 & P127
2.10.2
30
2.10.3
Setting guide
31
2.10.4
32
3.
VOLTAGE PROTECTIONS
35
3.1
35
3.2
36
3.3
36
3.3.1
Setting Guidelines
36
3.4
36
3.4.1
Setting Guidelines
37
3.5
37
3.5.1
Setting Guidelines
38
3.6
38
3.6.1
Setting guideline
38
4.
39
4.1
39
4.1.1
Description
39
4.2
39
4.2.1
Description
39
4.2.2
dF/dt functionning
40
4.3
42
4.3.1
Description
42
4.3.2
42
4.3.3
Overview
44
5.
45
5.1
Introduction
45
5.2
46
5.2.1
Autorecloser activation
46
5.2.2
Logic Inputs
46
5.2.3
47
5.2.4
48
5.2.5
48
5.2.6
Recloser lockout
48
5.2.7
48
5.2.8
Rolling demand
48
5.3
Setting Guidelines
49
5.3.1
Number Of Shots
49
5.3.2
49
5.3.3
49
Application Guide
P12y/EN AP/Fa5
Page 3/96
5.3.4
52
5.3.5
53
5.3.6
Number Of Shots
56
5.3.7
56
5.3.8
Fuse application
58
6.
61
6.1
Trip Commands
61
6.2
Latch relays
61
6.3
61
6.3.1
Setting Guidelines
61
6.3.2
Example Setting
62
6.4
62
6.4.1
Overview
62
6.4.2
Operation
62
6.4.3
Principle
64
6.5
65
6.6
VTS
66
6.6.1
VTS occurrence
66
6.6.2
VTS alarm
66
6.6.3
66
6.6.4
67
6.6.5
Voltage/Power protection
67
6.7
67
6.7.1
67
6.8
68
6.9
71
6.10
71
6.11
72
6.12
73
6.13
73
6.14
73
6.14.1
Setting Guidelines
74
6.15
74
6.15.1
75
6.15.2
75
6.16
76
6.16.1
76
6.16.2
79
6.17
Switch onto Fault Protection & Trip on Reclose (SOTF/TOR) (P126 & P127)
81
6.17.1
General
81
6.17.2
SOTF/TOR description
81
P12y/EN AP/Fa5
Page 4/96
Application Guide
MiCOM P125/P126 & P127
6.18
82
6.18.1
General
82
6.18.2
Settings
82
6.19
83
7.
84
7.1
Event Records
84
7.2
Fault Records
84
7.3
Instantaneous Recorder
84
7.4
Disturbance Records
84
8.
85
8.1
Rolling demand
85
8.2
86
9.
87
9.1.1
87
9.1.2
Priority
87
10.
MEASUREMENTS
88
10.1
88
10.2
89
10.2.1
Frequency
89
10.2.2
Currents
90
10.2.3
Voltages
91
10.2.4
Powers
91
10.2.5
Energies
92
10.2.6
92
11.
93
11.1
Logic Inputs
93
11.2
Logic Outputs
93
12.
MAINTENANCE MODE
94
13.
CT REQUIREMENTS
95
13.1
95
13.2
95
13.3
95
Application Guide
P12y/EN AP/Fa5
1.
INTRODUCTION
1.1
Page 5/96
The secure and reliable transmission and distribution of power within a network is heavily
dependent upon the integrity of underground cables and overhead lines, which link the
various sections of the network together. Therefore the associated protection system must
also provide both secure and reliable operation.
The most common fault conditions, on underground cables and overhead lines, are short
circuit faults. These faults may occur between the phase conductors but will most often
involve one or more phase conductor becoming short-circuited to earth.
Faults caused by short circuits require the fastest faulted conductor clearance times but at
the same time allowing for suitable co-ordination with other downstream protection devices.
Fault sensitivity is an issue common to all voltage levels. For transmission systems, towerfooting resistance can be high. Also, high resistance faults might be prevalent where lines
pass over sandy or rocky terrain. Fast, discriminative faulted conductor clearance is required
for these fault conditions.
The effect of fault resistance is more pronounced on lower voltage systems, resulting in
potentially lower fault currents, which in turn increases the difficulty in the detection of high
resistance faults. In addition, many distribution systems use earthing arrangements designed
to limit the passage of earth fault current.
Earthed methods as such as using resistance, Petersen coil or insulated systems make the
detection of earth faults arduous. Special protection equipment is often used to overcome
these problems.
Nowadays, the supply continuity in the energy distribution is of paramount importance.
On overhead lines most of faults are transient or semi-permanent in nature.
In order to increase system availability multi-shot autoreclose cycles are commonly used in
conjunction with instantaneous tripping elements. For permanent faults it is essential that
only the faulted section of the network is isolated. High-speed, discriminative fault clearance
is therefore a fundamental requirement of any protection scheme on a distribution network.
Power transformers are installed at all system voltage levels and have their own specific
requirements with regard to protection. In order to limit the damage incurred by a transformer
under fault conditions, fast clearance of the windings with phase to phase and phase to earth
faults is a primary requirement.
Damage to electrical plant equipment such as transformers, cables and lines may also be
incurred by excessive loading conditions, which leads directly to overheating of the
equipment and subsequent degradation of their insulation. To protect against such fault
conditions, protective devices require thermal characteristics too.
Uncleared faults, arising either from the failure of the associated protection system or of the
switchgear itself, must also be considered. The protection devices concerned should be
fitted with logic to deal with breaker failure and relays located upstream must be able to
provide adequate back-up protection for such fault conditions.
Other situations may arise on overhead lines, such as broken phase conductors.
Traditionally, a series fault has been difficult to detect.
With today's digital technology, it is now possible to design elements, which are responsive
to such unbalanced system, conditions and to subsequently issue alarm and trip signals.
On large networks, time co-ordination of the overcurrent and earth fault protection relays can
often lead to problematic grading situations or, as is often the case, excessive fault
clearance times. Such problems can be overcome by relays operating in blocked overcurrent
schemes.
P12y/EN AP/Fa5
Application Guide
Page 6/96
2.
2.1
2.2
2.2.1
Description
If a fault current can flow in both directions through a relay location, it is necessary to add
directionality to the overcurrent relays in order to obtain correct co-ordination. Typical
systems that require such protection are parallel feeders (both plain and transformer) and
ring main systems, each of which are relatively common in distribution networks.
In order to give directionality to an overcurrent relay, it is necessary to provide it with a
suitable reference, or polarising signal. The reference generally used is the system voltage,
as its angle remains relatively constant under fault conditions. The phase fault elements of
the directional relay are internally polarised by the quadrature phase-phase voltages, as
listed in the table below:
Protected Phase
Operating Current
Polarising Voltage
A Phase
IA
VBC
B Phase
IB
VCA
C Phase
IC
VAB
UAB
IA
UBC
IC
IB
UCA
P0354ENa
Under system fault conditions, the fault current vector will generally lag its nominal phase
voltage by an angle dependent on the system X/R ratio.
It is important that the relay operates with maximum sensitivity for currents lying in this
region.
Application Guide
P12y/EN AP/Fa5
Page 7/96
This is achieved by means of the relay
characteristic angle (RCA) setting (also
referred to as torque angle). RCA
defines the angle by which the current
applied to the relay must be displaced
from the voltage applied to the relay to
obtain maximum relay sensitivity.
RCA
Iph
Uph-ph
Forward
tripping zone
Backward
tripping zone
Tripping zone is settable from:
10 to 170 in step of 1 with reference
to RCA (Torque angle)
RCA (Torque angle) is settable from
0 to 359 in step of 1
P0079ENa
U [V]
1.5
0.5
0.1
0.2
0.3
0.4
I [In]
P0080ENa
Current threshold
The system voltage provides the polarisation signal, the minimum voltage operating value is
0.6V secondary for the voltage input range 57-130V and 3V for the voltage input range 220480V.
The first and second thresholds can be set as definite delay time or inverse delay time using
the IEC, IEEE/ANSI, CO, RI and RECT curves where their parameters are shown in the
Technical Data of this Technical Guide.
The third threshold can be set as definite delay time only, but can be set to work on the peak
of the current measured in non-directional way.
The protection elements trip when the following conditions occur:
P12y/EN AP/Fa5
Application Guide
Page 8/96
DT/IDMT
DT/IDMT
DT/IDMT
Blocking Logic
Fwd: forward
Rev: reverse
P0355ENb
DT/IDMT
Blocking Logic
Fwd: forward
Rev: reverse
P0356ENb
Application Guide
P12y/EN AP/Fa5
Page 9/96
DT
Blocking Logic
Fwd: forward
Rev: reverse
P0357ENa
The following figures show the windows where the first phase trip forward and instantaneous
reverse trip can be assigned to an output relay. The same one is for the 2nd and 3rd stages.
2.2.2
tI>
8765432
0000100
I_R>
8765432
0100010
Synchronous Polarisation
The directional overcurrent elements are polarised by the line voltage (phase to phase) in
quadrature to the considered phase current.
The absolute phase angle of line voltages is measured every cycle and the last value is
stored in the relay memory.
When with close-up three phase faults the polarisation voltage is collapsed, the synchronous
polarisation is switched on.
The polarisation discrimination voltage value is 0.6V (fixed value) for relays with a system
voltage of 57 to 130V and 3V (fixed value) for relays with a system voltage of 220 to 480V.
Over this value the directional relay uses standard polarisation (the measured voltage),
under this value the synchronous polarisation (stored vector) is used. The synchronous
polarisation is maintained up to the restoration of an input voltage value.
If the input voltage loss continues longer than 5s the directional overcurrent protection is
blocked.
P12y/EN AP/Fa5
Application Guide
Page 10/96
2.2.3
I>I>>I>>> Interlock
The choice of this functionality is available when the IDMT delay trip time is chosen on the
first threshold.
The following figures show the window where the functionality can be or not to be assigned
I> >> >>>
Interlock
Yes
The 2nd and 3rd threshold pickup can suspend 1st threshold output control to save selectivity
Below it is shown the trend of the delay trip time of the first threshold in the both cases Yes
or No.
t
t_I>
t_I>>
t_I>>>
I>
I>>
I>
I>>
I>>>
I>
I>
I>>
I>>
I>>>
I>>>
t
P0358ENa
Application Guide
P12y/EN AP/Fa5
Page 11/96
Setting Guidelines
The applied current settings for directional overcurrent relays depend on the specific
application. In a parallel feeder arrangement, load current is always flowing in the nonoperating direction. Consequently the relay current setting may be less than the full load
rating of the circuit, typically 50% of In.
Note that the minimum setting that may be applied has to take into account the thermal
rating of the relay. Some electro-mechanical directional overcurrent relays have continuous
withstand ratings of only twice the applied current setting. Therefore 50% of rating was the
minimum setting that had to be applied.
With the latest generation relays the continuous current rating is 4 x rated current. If required
it is now possible to apply much more sensitive settings.
In a ring main arrangement, it is possible for load current to flow in either direction through
the point where the relay is located. Consequently the current setting must be above the
maximum load current, as in a standard non-directional application.
The required relay characteristic angle (RCA) settings for directional relays will depend on
the exact application in which they are used.
For instance for plain feeders where the zero sequence source is behind the relay, a RCA of
30 should be set.
The following picture shows the above examples.
90 connection, RCA 30 (lead)
Plain feeder, zero sequence source behind the relay
UA
UA
IA
IA fault
IA
RCA angle: 30
VBC
VBC
UB
UC
Normal:
UA^IA=30
UB
UC
Fault:
UA^IA=60- 80
P0359ENb
On the P127 relay, it is possible to set the relay characteristic angle (RCA) or torque angle,
as it is also called, in the range of 0 to +359 in steps of 1. The trip boundary zone
associated to the RCA is settable in the range from 10 to 170 in steps of 1.
Further information about the setting range for the directional overcurrent protection are
available in the Technical Data document.
P12y/EN AP/Fa5
Application Guide
Page 12/96
2.2.5
2.2.5.1
Parallel Feeders
R1
R2
P126
OC/EF
P126
OC/EF
R3
R4
P127
DOC/DEF
OC/EF
P127
DOC/DEF
OC/EF
11K
R5
P126
OC/EF
P0081ENa
Application Guide
P12y/EN AP/Fa5
Page 13/96
2,1s
51
0,1s
2,1s
51
67
Load
0,1s
67
Load
1,7s
Load
67
0,5s
Load
67
Load
1,3s
67
0,5s
1,3s
67
67
1,7s
Load
0,9s
67
67
67
0,9s
P0082ENa
P12y/EN AP/Fa5
Application Guide
Page 14/96
2.3
2.3.1
2.3.2
I>I>>I>>> Interlock
The choice of this functionality is available when the IDMT delay trip time is selected.
The 2nd and 3rd threshold pickup can suspend 1st threshold output control to save selectivity
Below it is shown the trend of the delay trip time of the first threshold in the both cases Yes
or No.
t
t_I>
t_I>>
t_I>>>
I>
I>>
I>
I>>
I>>>
I>
I>
I>>
I>>
I>>>
I>>>
t
P0358ENa
Application Guide
P12y/EN AP/Fa5
Page 15/96
Inst. I>
Fwd. IA> on relay 2...8
IA >
DT/IDMT
IB >
DT/IDMT
IC >
DT/IDMT
Blocking Logic
P0360ENb
Inst. I>>
IA >>
IB >>
DT/IDMT
Trip I>>
IC >>
Blocking Logic
P12y/EN AP/Fa5
Application Guide
Page 16/96
Inst. I>>>
IA >>>
IB >>>
DT
Trip I>>>
IC >>>
Blocking Logic
2.4
The protection's tripping area is defined by a tripping zone settable form 10 to 170 in
steps of 1 for each tripping threshold and a settable angle from 0 to 359 in steps of 1
named torque/RCA angle (Ie^Ue), which can be separately set for each tripping threshold
and
The same threshold can be set as non-directional with definite or inverse delay time.
The third current threshold can be set as directional or non-directional but with only definite
delay time setting. The same applies to the Pe or IeCos second threshold.
The third threshold can work on the measured peak by an opportune choice in the dedicated
submenu. (See the FT part of the TG)
The peak detection is applied where a CT saturation condition occurs and the measure is not
more trustworthy.
The reset delay time for each threshold provides protection against intermittent faults.
Application Guide
P12y/EN AP/Fa5
Page 17/96
The close figure shows the forward and
reverse tripping zone for the directional
earth fault protection.
RCA
Ue
Ie
Forward
tripping zone
Backward
tripping zone
Tripping zone is settable from:
10 to 170 in step of 1 with reference
to RCA (Torque angle)
RCA (Torque angle) is settable from
0 to 359 in step of 1
P0083ENa
The protection element also provides a non-sensitive area to avoid instability due to small
asymmetries and unbalances that can generally be present in the network system. This
condition is represented by the characteristic reproduced below, where the hatched area is
the tripping zone.
The tripping zone is limited by the equation Ie +(k x Ue) < (k x 18). (18 is a value derived
experimentally where stability is guaranteed).
The K factor is 1, if Ien=1A, 5 if Ien=5A.
Ie [mA]
30
25
Ie [mA]
Ue>
Ue>>
Ue>>>
100
20
Tripping Zone
90
Ie + Ue= 18
80
Ue>
Ue>>
Ue>> >
Tripping Zone
15
Ie + 5 x Ue= 90
60
10
Ie>
Ie>>
Ie>>>
10
15
20
25
40
Ie>
Ie>>
Ie>> >
20
30
Ue [V]
10
15
20
25
30
Ue [V]
P0068ENa
Ien=1A
P0067ENa
Ien=5A
The directional earth fault element needs a suitable voltage supply to provide the necessary
polarisation. (See the Technical data for further information)
The polarising signal must be representative of the earth fault condition. As residual voltage
is generated during earth fault conditions, and this quantity is used to polarise directional
earth fault elements. The P127 relay can derive this voltage internally from the 3 phase
voltage inputs when the VT connection option 3Vpn is set. It can also be measured directly
by a VT transformer when the VT connection option 2Vpp+Vr (two phase to phase) or
2Vpn+Vr (two phase to neutral) is set.
The P125 and P126 measures this voltage directly from a broken delta or single VT.
P12y/EN AP/Fa5
Application Guide
Page 18/96
2.4.1
180
Insulated systems
270
200
90-120
The setting ranges for directional/non-directional earth fault and wattmetric protection
(Pe/IeCos) can be found in the FT and TD chapters of the technical guide.
2.4.2
Application Guide
P12y/EN AP/Fa5
Page 19/96
A B C
Ia1
Ib1
IR1
-jXc1
IH1
Ia2
Ib2
IR2
-jXc2
IH2
Ia3
Ib3
IH1+IH2+IH3
IR3
-jXc3
IH3 IH1+ IH2
IR3=-(Ia1+Ib1+Ia2+Ib2)+Ia3+Ib3-(Ia3+Ib3)
IR3=-(IH1+IH2)+IH3-IH3
P0363ENa
From above figure and the vector diagram below it can be seen that the relays on the
healthy feeders see the unbalance in the charging currents on their own feeder. The relay on
the faulted feeder, however, sees the charging current from the rest of the system [IH1 and
IH2 in this case], with its own feeders charging current [IH3] being cancelled out
UA
UC
UB
UAf
IH1+IH2
Vr=3Ve
Ib1+Ib2
270
Ia1+Ia2
O'
UBf
TRIP ZONE
IR3=-(IH1+IH2)+IH3-IH3
A setting of Torque(RCA) angle of 270
shifts the center of the characteristic to
here
P0364ENa
Referring to the vector diagram, it can be seen that the C phase to earth fault causes the
phase voltages on the healthy phases to rise by a factor of
3.
P12y/EN AP/Fa5
Application Guide
Page 20/96
The A phase charging current (Ia), is then shown to be leading the resultant A phase voltage
by 90. Likewise, the IB phase charging current leads the resultant voltage Vb by 90.
The unbalance current detected by a core balance current transformer on the healthy
feeders can be seen as the vector addition of Ia1 and Ib1 (Ia2 and Ib2), giving a residual
current which lies at exactly 90 anticipating the polarising voltage (Vr=3Ve).
The vector diagram indicates that the residual currents on the healthy and faulted feeders,
IH1& IH2 and IR3 respectively, are in opposite direction to each other (180). A directional
element could therefore be used to provide discriminative earth fault protection.
If the polarising voltage of this element, equal to 3Ve, is shifted through +270, the residual
current seen by the relay on the faulted feeder will lie within the operate region (Trip Zone) of
the directional characteristic. As previously stated, the required RCA setting for the sensitive
earth fault protection when applied to insulated systems, is 270.
2.4.3
Pe/IeCos
Tripping zone
Pe> Pe>>
IeCos> IeCos>>
Q/IeSin
P0365ENa
In the following formula the power thresholds in the relay menu are called Pe> & Pe>>.
The Pe> and Pe>> settings are calculated as:
Vres x Ires x Cos (f fc) = 9 x Ve x Ie x Cos (f fc)
Where:
f
fc
Vres
Ires
Ve
Ie
2.4.3.1
= angle between the polarising voltage (Vres) and the residual current
= relay characteristic angle (RCA/torque angle)
= residual voltage
= residual current
= zero sequence voltage
= zero sequence current
Application Guide
P12y/EN AP/Fa5
Page 21/96
Ien = 1A, the internal relay setting value will be equal to 20 x 1 = 20W.
To set the thresholds for the Pe (Wattmetric/IeCos) protection the relay will display the menu
Wattmetric Protection \ Pe> (refer to P12y/EN FT section).
The same procedure is to be applied for setting the second Pe>> threshold.
For the settings of the trip delay time see the FT chapter of the TG)
2.4.4
Application Considerations
The protection Pe> and Pe>> require relay current and voltage connections to be actived.
The measurement of the Pe depends on the voltage wiring of the relay.
In case of 3Vpn wiring the Ve will be equal to Ve= 1/3(Va+VB+VC) in the other insertions
way the applied voltage to the relay is directly used to calculate the Pe.
Referring to the relevant application diagram for the P125, P126 and P127 relays, it should
be installed such that its direction for forward operation is 'looking into' the protected feeder
i.e. away from the busbar, with the appropriate RCA .
Resistance earthed systems
180
Insulated systems
270
200
90-120
As illustrated in the relay application diagram, it is usual for the earth fault element to be
driven from a core balance current transformer. This eliminates the possibility of spill current
that may arise from slight mismatches between residually connected line CTs. It also
enables a much lower CT ratio to be applied, thereby allowing the required protection
sensitivity to be more easily achieved.
2.4.5
Iecos protection
The Iecos protection follows the same concepts of the Pe protection.
The difference is that the thresholds take in account the active component of the earth fault
current.
The setting of the RCA follows the above listed table.
2.4.6
P12y/EN AP/Fa5
Application Guide
Page 22/96
IA + IB + IC :
IA + IB + IC = Ie_d>.
The derived earth overcurrent has two independent thresholds: Ie_d> and Ie_d>>.
The two thresholds can be set as definite delay time or inverse delay time using the IEC,
IEEE/ANSI, CO, RI and RECT curves. Their parameters are shown in the Technical Data
chapter of this Technical Guide.
IA
IB
IC
IA+IB+IC = Ie_d>
Ie>>>>
Ie = Tank Earth
P3940ENb
As soon as Ie_d> threshold is running, the instantaneous output associated with this
threshold is activated. This output indicates that the protection element has detected an
earth fault and that the time delay associated with the threshold has started. This time delay
can be blocked via the logic input "Block Logic" associated with this threshold. If this blocking
input is activated by an output contact of a downstream relay, the logic that will lead to the
trip command is then blocked only if the relay that is the closest to the fault can see and
therefore eliminate the fault. This principle is known as Blocking logic or Blocking. It is
described in more detail in this document.
Application Guide
P12y/EN AP/Fa5
Page 23/96
Ie>Ie>>Ie>>> Interlock
The choice of this functionality is available when the IDMT delay trip time is selected for the
first earth threshold.
The following figures show the window where this functionality can be or not to be actived.
The 2nd and 3rd threshold pickup can suspend 1st threshold output control to save
selectivity.Below the trend of the delay trip time of the first threshold is shown for both cases
Yes or No.
t
t_I>
t_I>>
t_I>>>
I>
I>>
I>
I>>
I>>>
I>
I>
I>>
I>>
I>>>
I>>>
t
P0358ENa
2.6
2.6.1
Overview
The MiCOM P125 relay is a single phase relay designed for stand alone directional earth
fault protection. This relay incorporates both an IeCos and a Zero Sequence Power
element. These elements can be configured to provide a single phase power measurement
or alternatively a sensitive directional overcurrent characteristic similar to that of the
MWTU11/TWL1111 Reverse Power relay.
Using a MiCOM P125 relay as a stand alone power relay provides a wide setting range, the
setting range available is dependent on the CT range ordered. The table below outlines the
settings available for each of the voltage and CT input ranges.
Analogue Input
P125AA
CT Range
VT Range
Pe
Ie Cos
0.1 40
57 130
10 800W
0.1 40
220 - 480
40 3200W
57 130
1 60W
220 - 480
4 640W
57 130
0.2 20W
220 - 480
1 80W
P125AB
P125BA
0.01 8
P125BB
P125CA
P125CB
0.002 1
0.01 8
0.002 1
Flexible connection arrangements allow for phase to phase or phase to ground connection of
the polarising voltage, a wide range of angle settings allows the relay to operate for Watts or
Vars, Import or export.
P12y/EN AP/Fa5
Application Guide
Page 24/96
The VT inputs for the MiCOM P125 relay are rated 57 to 130 Vac or 220 480 Vac
(Selected at time of order) these ranges make the relay suitable for connection to a VT
secondary or direct connection to a 415V systems.
2.6.2
Relay Connection
The relay setting angle which is discussed in further detail below allows the user to
customise the VT connection to suit the primary plant, available VT secondaries and the
protection philosophy of the customer.
The VT connection can be made phase to phase or phase to ground using the connection
table below
For simplicity the connection has been made so as a reverse power setting will require an
angle of 180 degrees.
Polarising Voltage
Terminals
Leading Subscript
(Eg Va-n)
Laging Subscript
(Eg Va-n)
40
39
Va-n
Vb-n
Vc-n
Va-b
Vb-c
Vc-a
One of the possible line CT connection is shown below, The CT input can be connected to
any available phase CT, (A, B or C).
Application Guide
P12y/EN AP/Fa5
Page 25/96
Voltage
Current
Va-n
Ia
Vb-n
Ib
Vc-n
Ic
Va-b
Ic
Vb-c
Ia
Vc-a
Ib
Va-n
Ia
Vb-n
Ib
Vc-n
Ic
Va-b
Ic
Vb-c
Ia
Vc-a
Ib
Va-n
Ia
Vb-n
Ib
Vc-n
Ic
Va-b
Ic
Vb-c
Ia
Vc-a
Ib
Va-n
Ia
Vb-n
Ib
Vc-n
Ic
Va-b
Ic
Vb-c
Ia
Vc-a
Ib
Angle Setting
180
270
90
180
90
270
Pe/IeCos
Tripping zone
Pe> Pe>>
IeCos> IeCos>>
Q/IeSin
P0365ENa
P12y/EN AP/Fa5
Page 26/96
2.6.4
Application Guide
MiCOM P125/P126 & P127
2.6.5
2.7
Application Guide
P12y/EN AP/Fa5
Page 27/96
(I
(k I FLC )2
(I
I 2p
Where:
t
I
IFLC
k
IP
=
=
=
=
=
=
The time to trip varies depending on the load current carried before application of the
overload, i.e. whether the overload was applied from hot or cold.
Curves of the thermal overload time characteristic are given in Technical Data.
2.7.2
Ix 2
t Trip = Te In
Ix 2 trip
With:
t Trip
Te
Ix
Ieq
=
=
=
=
I >
k
trip
=
=
=
=
+1
I eq
k I >
t
t
1 e Te + e Te
P12y/EN AP/Fa5
Application Guide
Page 28/96
2.7.3
Setting Guidelines
The current setting is calculated as:
Thermal Trip (trip) = Permissible continuous loading of the plant equipment / CT ratio.
Typical time constant values are given in the following tables.
The relay setting, Time Constant, is in minutes.
Paper insulated lead sheathed cables or polyethylene insulated cables, placed above ground
or in conduits. The table shows in minutes, for different cable rated voltages and conductor
cross-sectional areas:
CSA mm2
6 -11 kV
22 kV
33 kV
66 kV
25 - 50
10
15
40
70 - 120
15
25
40
60
150
25
40
40
60
185
25
40
60
60
240
40
40
60
60
300
40
60
60
90
Dry-type transformers
Limits
40
60 - 90
Air-core reactors
40
Capacitor banks
10
Overhead lines
10
Busbars
60
An alarm can be raised on reaching a thermal state corresponding to a percentage of the trip
threshold. A typical setting might be Thermal Trip = 70% of thermal capacity.
2.8
2.9
Application Guide
P12y/EN AP/Fa5
Page 29/96
This section describes how negative phase sequence overcurrent protection may be applied
in conjunction with standard overcurrent and earth fault protection in order to alleviate some
less common application difficulties.
In certain applications, residual current may not be detected by an earth fault relay
due to the system configuration. For example, an earth fault relay applied on the delta
side of a delta-star transformer is unable to detect earth faults on the star side.
However, negative sequence current will be present on both sides of the transformer
for any fault condition, irrespective of the transformer configuration. Therefore, a
negative phase sequence overcurrent element may be employed to provide timedelayed back-up protection for any un-cleared asymmetrical fault.
Where fuses protect motors on rotating machines, a blown fuse produces a large
amount of negative sequence current. This is a dangerous condition for the motor due
to the heating effects of negative phase sequence current at double frequency. A
negative phase sequence overcurrent element may be applied to provide efficient
back-up protection for dedicated motor protection relays.
It may also be required to simply set an alarm at the presence of negative phase
sequence currents on the system. Operators are then prompted to investigate the
cause of the unbalance.
The negative phase sequence overcurrent elements have a current pick up settings I2>,
I2>>, I2>>>, and are time delayed in operation by the adjustable timers tI2>, tI2>>, tI2>>>.
2.9.1
P12y/EN AP/Fa5
Application Guide
Page 30/96
2.10
2.10.1
Introduction
The restricted earth fault relay is a high impedance differential scheme which balances zero
sequence current flowing in the transformer neutral against zero sequence current flowing in
the transformer phase windings. Any unbalance for in-zone fault will result in an increasing
voltage on the CT secondary and thus will activate the REF protection.
This scheme is very sensitive and can then protect against low levels of fault current in
resistance grounded systems where the earthing impedance and the fault voltage limit the
fault current.
In addition, this scheme can be used in a solidly grounded system. It provides a more
sensitive protection, even though the overall differential scheme provides a protection for
faults over most of the windings.
The high impedance differential technique ensures that the impedance of the circuit is of
sufficiently high impedance such that the differential voltage that may occur under external
fault conditions is lower than the voltage required to drive setting current through the relay.
This ensures stability against external fault conditions and then the relay will operate only for
faults occurring inside the protected zone.
2.10.2
Saturated CT
Protected
circuit
Zm
Zm
A-G
RCT2
RCT1
IF
R L3
R L1
VS
R L2
R ST
R
R L4
Application Guide
P12y/EN AP/Fa5
Page 31/96
The maximum internal fault level for stage 3 of 0.002 to 1In board
must not exceed 20In.
A
B
C
STAB
E/F Input
P0343ENa
Setting guide
The characteristics of the relay and the value of K influence the stability of the scheme as
explained here above.
The typical setting values shall be chosen to provide a primary operating current less than
30 % of the minimum earth fault level for a resistance earthed system. For a solidly earthed
system, the typical setting shall provide an operating current between 10 and 60 % of the
rated current.
The primary operating current, at the secondary, depends on the following factors:
Current setting should be selected for a high impedance element so that the primary current
reaches its nominal current with a given CT, according to the following equation:
Is < {(Iop / CTRatio) - n.Ie}
P12y/EN AP/Fa5
Application Guide
Page 32/96
It is also possible to determine the maximum inrush current of the CT to reach a specific
primary operating current with a given relay setting.
The setting of the stabilising resistor must be calculated according to the above formula,
where the setting depends on the required stability voltage setting Vs and the relay setting Is
Vs k If (RCT+2RL)
Is =
IS
For MiCOM P12x, Is is equivalent to Ie>, so the above equation becomes:
Vs k If (RCT+2RL)
Ie> =
Ie>
with
K= 1 for Vk/Vs less or equal to 16 and
K= 1.2 for Vk/Vs > 16.
So
RST =
k If (RCT+2RL)
Ie>
with Vk 4.Is.RST (A typical value to ensure the high speed operation for an internal fault).
CT requirements for High Impedance Restricted Earth Fault Protection
The High Impedance Restricted Earth Fault element shall remain stable for through faults
and operate in less than 40ms for internal faults provided that the following equations are
met in determining CT requirements and the value of the associated stabilising resistor:
Rs
VK
4 * Is * Rs
with
K= 1 for Vk/Vs less or equal to 16 and
K= 1.2 for Vk/Vs > 16.
2.10.4
CT ratio
Application Guide
P12y/EN AP/Fa5
Page 33/96
Vf: maximum voltage that would be produced if CT saturation did not occur
When the value given by the formula is greater than 3KV peak, it is necessary to use
Metrosils. They are connected across the relay circuit and they allow to shunt the secondary
current output of the current transformer from the relay in order to prevent very high
secondary voltages.
Metrosils are externally mounted and have annular discs shape.
Their operating characteristics is according to the formula:
V = C.I0.25
Where
With the sinusoidal voltage applied across the Metrosil, the RMS current would be
approximately 0.25 times the peak current. This current value can be calculated as follows:
Vs(rms). 2
Irms = 0.52
Where
Vs(rms): RMS value of the sinusoidal voltage applied across the Metrosil.
This is due to the fact that the current waveform through the Metrosil is not sinusoidal but
appreciably distorted.
For satisfactory application of the non-linear resistor (Metrosil), its characteristics should
comply with the following requirements:
At the relay voltage setting, the non-linear resistor (Metrosil) current should be as
low as possible, but no greater than approximately 30mA rms for 1A current
transformers and approximately 100mA rms for 5A current transformer.
At the maximum secondary current, the non-linear resistor (Metrosil) should limit
the voltage to 1500V rms or 2120V peak for 0.25 second. At higher relay voltage
settings, it is not always possible to limit the fault voltage to 1500V rms, so higher
fault voltage may have to be tolerated.
The following tables show the typical types of Metrosil that will be required, depending on
relay current rating, REF voltage setting etc.
P12y/EN AP/Fa5
Application Guide
Page 34/96
At the relay voltage setting, the Metrosil current should be less than 30mA rms.
At the maximum secondary internal fault current, the Metrosil unit should limit the
voltage to 1500V rms if possible.
The Metrosil units normally recommended to be used with 1Amp CTs are shown in the
following table:
Relay Voltage
setting
Nominal Characteristics
C
Up to 125V rms
450
0.25
600A/S1/S256
600A/S3/1/S802
900
0.25
600A/S1/S1088
600A/S3/1/S1195
NOTE:
At the relay voltage setting, the Metrosil current should be less than 100mA rms (the
actual maximum currents passed by the units shown below their type description)
At the maximum secondary internal fault current the Metrosil unit should limit the
voltage to 1500V rms for 0.25 second. At the higher relay settings, it is not possible to
limit the fault voltage to 1500V rms, hence higher voltage have to be tolerated
( indicated by * ,** , *** ).
The Metrosil units normally recommended for the used with 5 Amps CTs and single pole
relays are shown in the following table:
Secondary
Internal fault
current
Amps rms
Up to 200V rms
250V rms
275V rms
300V rms
600A/S1/S1213
600A/S1/S1214
600A/S1/S1214
600A/S1/S1223
C= 540/640
C= 670/800
C= 670/800
C= 740/870*
35mA rms
40mA rms
50mA rms
50mA rms
600A/S2/P/S1217
600A/S2/P/S1215
600A/S2/P/S1215
600A/S2/P/S1196
C= 470/540
C= 570/670
C= 570/670
C= 620/740*
35mA rms
75mA rms
100mA rms
100mA rms
600A/S3/P/S1219
600A/S3/P/S1220
600A/S3/P/S1221
600A/S3/P/S1222
C= 430/500
C= 520/620
C= 570/670**
C= 620/740***
100mA rms
100mA rms
100mA rms
100mA rms
50A
100A
150A
NOTE:
* 2400V peak
** 2200V peak
*** 2600V peak
In some cases, single disc assemblies may be acceptable, contact
Schneider Electric for detailed information.
The Metrosil units used with 5 Amps CTs can also be used with triple
pole relays and consist of three single pole units mounted on the
same central stud but electrically insulated from each other. To order
these units please specify Triple pole Metrosil type, followed by the
single pole type reference.
Application Guide
MiCOM P125/P126 & P127
3.
VOLTAGE PROTECTIONS
3.1
P12y/EN AP/Fa5
Page 35/96
For the P127, it is important to select the VTs configuration and VT protection in the
Configuration/ General Options/ VT Connection and VT protection submenu in according to
the relay wiring for a corrected functionality of the voltage protections.
Protection thresholds are not automatically converted when the protection mode is modified;
they are directly expressed into the set protection mode. So, if the protection mode is
modified, the thresholds have to be recalculated. For example, to keep the same protection
level when the mode is converted from P-P to P-N, it is necessary to divide thresholds by 3.
In the above mentioned is menu you will find that for the P127 relay there are three
configurations of VTs.
1.
In this configuration, the relay directly measures Ua, Ub, and Uc and calculates internally the
zero sequence voltage Ue = (1/3)[Ua+Ub+Uc]. This internal value Ue will be used to be
compared to the threshold of Ue (the Earth Overvoltage Protection threshold and to evaluate
the angle with the earth current for the earth fault directional protection). However, none UN
is displayed in the measurement Menu.
2.
In this configuration, the relay directly measures Ua and Ub. The input voltage of phase C of
the relay (terminals 73-74) which is connected to the summation of the three voltage phases
is used to be compared to the Ue (The earth Overvoltage Protection function threshold). This
voltage at C input is considered as Ur and it is displayed in the measurement menu as UN.
Moreover for the phase Overvoltage and Undervoltage protection functions, the phase C
voltage value Uc is internally reconstituted using the equation:
Uc = Ua+Ub+Ur. This value will be compared to the U/V or O/V threshold in case of a
fault in phase C. Uc is not displayed in the measurement menu.
two used for the phase voltage Ua and Uc and the others used in Open delta
configuration for the Ur.
The relay directly measures Uab and Ubc, the phase to phase (A-C) voltage value Uca is
internally reconstituted using the equation Uca=Uab+Ubc.
The third input of voltage of the relay (terminals 73-74) can be connected to the output of a
delta transformer or to a dedicated voltage transformer, the measured value can be used to
compare to the earth overvoltage threshold.
This voltage is displayed in the measurement menu as UN and it is designed as the earth
voltage.
4.
VT Protection:
if "VT Protection" = "Protect P-N", set thresholds are P-N voltages, and effective
thresholds used for protections algorithm are set thresholds multiplied by 3. Example:
U> flag will be activated for measured P-N voltage higher than 57V, if threshold = 57V.
P12y/EN AP/Fa5
Page 36/96
3.2
Application Guide
MiCOM P125/P126 & P127
UN for the measurement and fault record menu is to intend residual, zero sequence voltage
earth voltage etc.
3.3
3.3.1
Setting Guidelines
The voltage setting applied to the protection elements is dependent upon the magnitude of
residual voltage that is expected to occur during an earth fault condition.
This in turn is dependent upon the method of system earthing employed. It must also be
ensured that the relay is set above any standing level of residual voltage that is present on
the system.
The protection element has one programmable element with delay time tUe>>>>.
The setting range and the functionality limits for the residual over-voltage are described in
the TD chapter, the setting menu is described in the User Guide chapter.
3.4
Application Guide
P12y/EN AP/Fa5
Page 37/96
Setting Guidelines
In the majority of applications, undervoltage protection is not required to operate during
system earth fault conditions. If this is the case, the protection element should be selected in
the menu to operate from a phase-to-phase voltage measurement, as this quantity is less
affected by the decrease of a single-phase voltage due to an earth fault.
The voltage threshold setting for the undervoltage protection element should be set at some
value below the voltage decreases which may be expected under normal system operating
conditions. This threshold is dependent upon the system in question but typical healthy
system voltage decreases may be in the order of -10% of nominal value.
The undervoltage protection element has two programmable thresholds with delay timers:
tU<, tU<<
After a trip command the thresholds will be reset when all phase voltages have risen above
105% of setting values.
The undervoltage protection element, which can be set as OR or AND logic, operates by
comparing each UAB, UBC and UCA voltage input with the U<, U<< thresholds.
The relay continuously monitors the phase-to-phase voltages.
NOTE:
3.
Exemple with a 400V analog VT input and a setting at 85% of this voltage:
if this voltage is a phase to phase (Vpp) setting, U< = 85% x Un, the setting will
be 340V
if this voltage is a phase to neutral (Vpn = 230V) setting, U< = (85% x Un) x
P12y/EN AP/Fa5
Application Guide
Page 38/96
3.5.1
Setting Guidelines
The relay with this type of protection element must be co-ordinated with any other overvoltage relay at other locations on the system. This should be carried out in a similar manner
to that used for grading current operated protection devices.
The protection element over-voltage has two programmable thresholds and two delay timers,
tU>, tU>>.
After a trip command the thresholds will be reset when all phase voltages have fallen below
95% of setting values.
The overvoltage protection element, which can be set as OR or AND logic, operates by
comparing each UAB, UBC and UCA voltage input with the U>, U>> thresholds.
NOTE:
3.
When OR operating logic is set and one or more voltage has risen above the threshold
value, the tripping command is sent after the tripping timer has reached the set overtime
condition.
When AND operating logic is set and all of the voltage values have risen above the threshold
value, the tripping command is sent after the tripping timer has reached the set overtime
condition.
Information as to the thresholds setting range can be found in the FT and TD parts of the
technical guide.
3.6
3.6.1
Setting guideline
The negative sequence overvoltage protection has two independent thresholds: V2> and
tV2>.
Any unbalanced condition occurring on the incoming supply will result in the presence of
negative phase sequence (nps) components of voltage. In the event of incorrect phase
rotation, the supply voltage would effectively consist of 100% negative phase sequence
typical.
The operation time of the element will be highly dependent on the application. A typical
setting would be in the region of 5s.
The relay will trip according to an inverse characteristic or a definite time characteristic for
the first stage and according to a definite time characteristic for the second stage.
The inverse characteristic is given by the following formula:
t = K / (M - 1)
Where:
Application Guide
P12y/EN AP/Fa5
4.
4.1
4.1.1
Description
Page 39/96
Time delayed under and over frequency protection available on P127 provides the
fundamental form of frequency protection.
Six thresholds are available: Each one can be configured to detect an under or over
frequency within the range [fn 4,9Hz, fn + 4,9Hz], where fn is the nominal frequency
selected (50Hz or 60Hz). A definite timer is assigned to each threshold.
When the frequency measured is crossing one of the 6 pre-defined thresholds, the relays
generates a start signal and after a user settable time delay, a trip signal.
NOTE:
4.2
4.2.1
Description
The calculation of the rate of change of frequency is an average measurement of the
instantaneous values over a programmable number of cycles (1 to 200); refer to the
CONFIGURATION / General options" menu. The instantaneous values of rate of change of
frequency are measured every cycle (20ms at 50Hz). The rate of frequency change
elements are very important to detect any power loss under severe disturbances and
eventually perform load shedding of secondary load.
These elements offer the possibility to detect the tendency of the variation of frequency, and
thus re establish the correct load/generation without waiting for big frequency reduction.
These elements could be combined to the frequency elements using the AND logic
equations to provide a very useful mechanism allowing a more secure trip decision to be
achieved during transient system disturbances.
According CONFIGURATION / General options setting, this function will be inhibited in the
following case:
if the voltage level for each phase is below the settable undervoltage blocking value
(see Prot. Freq. Block U< cell),
if the frequency is out of range: fmeasured > (fn+20Hz) or fmeasured < (fn20Hz)
P12y/EN AP/Fa5
Application Guide
Page 40/96
4.2.2
dF/dt functionning
f i-2
f i-1
fi
f i+1
df /dti - 2 =
fi - 2 - fi - 3
ti - 2 - ti - 3
fii -- 12 - fii -- 32
df /dti - 1 =
ti - 1 - ti - 2
df /dti =
fi - fi - 1
ti - ti - 1
df /dti + 1 =
fi + 1 - fi
ti + 1 - ti
P0399ENa
The rates of change of frequency are calculated every cycle based upon zero crossing.
NOTE:
To be insensitive to the phase shift and vector jumps, we can reject all
measurements of dF/dt greater than 20Hz/s .
Application Guide
P12y/EN AP/Fa5
Page 41/96
CONFIGURATION
General Options
dF/dt Cycles.nb = 3
dF/dt Cycles.nb
3
CONFIGURATION
General Options
dF/dt Validat.nb = 2
dF/dt Validat.nb
2
CONFIGURATION
General Options
dF/dt Cycles.nb = 3
dF/dt Validat.nb = 2
df/dt2
df/dt3
dF/dt 1 =
dF/dt1 =
df/dt1
PROTECTION
[81R] Freq. rate of change
0.5 Hz/s
dF/dtaverage2
dF/dtaverage1
df/dt1
df/dt2
df/dt3
Validation
P3974ENa
will be validated when dF/dtaverage1 and dfF/dtaverage2 exceed df/dt1 setting value
(protection menu).
will not be validated when only one of the average value exceeds df/dt1 setting value.
NOTE:
P12y/EN AP/Fa5
Application Guide
Page 42/96
4.3
4.3.1
Description
MiCOM P127 provides the three-phase power protection which monitors the active and
reactive power limits and detects (when selected):
A definite timer is assigned to each threshold. When the active and reactive power
measurements are inside the trip zone, the relays generates a start signal and after a user
settable time delay, a trip signal.
The directional angle between active (or reactive) over / under power and triggering power
can be adjusted between 0 and 359.
P
Triggering power
Triggering power
P>
and
P>>
Trip
P<
and
P<<
Q>
an
dQ
>>
Trip
zon
Tri
p
e
Q<
an
dQ
<< T
rip
Directional
Angle
zon
ne
Angle
zo
ne
0
270
270
90
90
180
180
4.3.2
zo
P3969ENa
P> 100x 1W if the secondary of the CT = 1A, and the setting of P>
= 100W
P> 100x 5W if the secondary of the CT = 5A, and the setting of P>
= 500W
Application Guide
P12y/EN AP/Fa5
Page 43/96
Example1:
VT connection = 3Vpn
CT Ratio = 100A / 1A
VT Ratio = 2kV / 100V
I = 10A primary = 100mA secondary injected on the 3 phases,
V = 1155V primary = 57.7V secondary injected on the 3 phases
Phase Difference = 0 degrees
P= 57.7 x 0.1 cos (0) + 57.7x 0.1 cos (0) + 57.7 x 0.1 cos (0) = 17.3 W sec
or 17.3 x CT Ratio x VT Ratio x K (K= CT 1A or 5A) = 17.5 x 100 X 20 x 1 = 35000 W
Primary
4.3.2.1 Active power (P)
The calculation of the active power is:
For a 3 Vpn or a 2Vpn+Vr connection:
P = Ua * Ia * cos(Ua Ia) + Ub * Ib * cos(Ub Ib) + Uc * Ic * cos(Uc Ic)
Sn = 3.In Un
For a 2Upp+Vr connection:
P = Uab * Ia * cos(Uab Ia) Ubc * Ic * cos(Ubc Ic)
Sn = 3.In Un
P" =
P
3.KI KU Un
InTA UnTV
P
3.KI KU Un
where:
where In and Un are respectively the nominal current and voltage to the secondary side
Since these are measurements used only for protection purposes, they arent displayed on
HMI.
4.3.2.2 Reactive power (Q)
The calculation of the reactive power is:
For a 3 Vpn or a 2Vpn+Vr connection:
Q = Ua * Ia * sin(Ua Ia) + Ub * Ib * sin(Ub Ib) + Uc * Ic * sin(Uc Ic)
Q
3.KI KU Un
InTA UnTV
Q
3.KI KU Uan
P12y/EN AP/Fa5
Application Guide
Page 44/96
where:
where In and Un are respectively the nominal earth current and voltage to the secondary
side
Since these are measurements used only for protection purposes, they arent displayed on
HMI.
4.3.2.3 Phase shifts of the power
The calculation of the phase shift of the power phi is:
Q
phi = arctan( )
P
4.3.3
Overview
Using a MiCOM P127 relay as a stand alone power relay provides a wide setting range, the
setting range available is dependent on the VT range ordered. The table below outlines the
settings available for each of the VT input ranges.
Analogue Input
P127AA
CT Range (A)
VT Range (V)
0.1 40
57 130
1 10000xk W with k = 1 or 5 A
220 - 480
4 40000xk W with k = 1 or 5 A
57 130
1 10000xk W with k = 1 or 5 A
220 - 480
4 40000xk W with k = 1 or 5 A
57 130
1 10000xk W with k = 1 or 5 A
220 - 480
4 40000xk W with k = 1 or 5 A
P127AB
P127BA
0.01 8
P127BB
P127CA
P127CB
0.002 1
Application Guide
P12y/EN AP/Fa5
Page 45/96
5.
5.1
Introduction
An analysis of faults on any overhead line network has shown that:
the remaining 10-20% of faults are either non-permanent (arcing fault) or permanent.
A transient fault is a self-clearing non-damage fault. This type of fault can be isolated and
cleared by the immediate tripping of one or more circuit breakers, and does not recur when
the line is re-energised. The most common cause of transient faults are lightning, insulator
flashover clashing conductors and wind blown debris.
The immediate trip will not clear a non-permanent or permanent fault, and the use of the
recloser may be necessary to clear it. A small tree branch falling on the line could cause a
non-permanent fault. Permanent faults could be broken conductors, transformer faults, cable
faults or machine faults that must be located and repaired before the supply can be restored.
Most of the time, if the faulty line is immediately tripped, and the fault arc has sufficient time
to de-ionise, reclose of the circuit breakers will result in the line being successfully reenergised. Autoreclose schemes are used to automatically reclose a switching device once a
time delay has elapsed and starting after the CB has opened.
On HV and MV distribution networks, the autoreclose function is applied mainly to radial
feeders where system stability problems do not generally arise. Using the autoreclose
minimises time of interruption and reduces operating costs.
Automatic autorecloser allows a substation to operate unattended:the number of visits to
manually reclose a circuit breaker is substantially reduced. This feature constitutes therefore
an important advantage for substations supervised remotely.
On circuits using time graded protection, the automatic autorecloser allows the use of
instantaneous protection to give a high speed first trip. With fast tripping, the duration of the
power arc resulting from an overhead line fault is reduced to a minimum, thus lessening the
chance of damage and to develop the transient fault into a permanent fault.
Using short time delay protection prevents blowing of fuses and reduces circuit breaker
maintenance by eliminating pre-arc heating when clearing transient faults.
Current
The next figure shows an example of 4 autoreclose cycles (maximum numbers of allowed
cycles) to the final trip (in the following diagram, td1, td2, td3, td4 = dead time 1, 2, 3 and 4
timers, tr = Reclaim time, O = CB open and C = CB closed).
O C
final trip
I threshold
td1
In
tr
td2
tr
td3
tr
td4
tr
Time
Fault
P0031ENa
P12y/EN AP/Fa5
Application Guide
Page 46/96
When short time delay protection is used with autoreclose, the scheme is normally arranged
to block the instantaneous protection after the first trip. Therefore, if the fault persists after reclosing, time-graded protection will give discriminative tripping with fuses or other protection
devices, resulting in the isolation of the faulted section. However, for certain applications,
where the majority of the faults are likely to be transient, it is not uncommon to allow more
than one instantaneous trip before the instantaneous protection is blocked.
Some schemes allow a number of re-closings and time graded trips after the first
instantaneous trip, which may result in the burning out and clearance of non-permanent
faults. Such an approach may also be used to allow fuses to operate in teed feeders where
the fault current is low.
Any decision to apply the autoreclose function would be influenced by all data known on the
frequency of transient faults (for instance feeders which consist partly of overhead lines and
partly of underground cables). When a significant proportion of the faults are permanent, the
advantages of autoreclose are small, particularly since re-closing on to a faulty cable is likely
to aggravate the damage.
5.2
5.2.1
Autorecloser activation
The autoreclose function is activated using AUTOMAT. CTRL/ PROTECTION G1 menu.
The same settings apply for the Menu PROTECTION G2.
The autoreclose function of the relay is available only if the following conditions are verified:
The auxiliary contact of the CB status 52a must be connected to the relay.
Refer to the AUTOMAT. CTRL/Inputs menu
The trip output relay RL1 must not be latched to the earth and/or phase protection
function.
Refer to the AUTOMAT. CTRL/Latch functions menu
NOTE:
In addition to Autoreclose settings, the user will be able to fully link the autoreclose function
to the protection function using the menus PROTECTION G1/Phase OC and
PROTECTION/E/Gnd.
5.2.2
Logic Inputs
The autoreclose function has four inputs that can be assigned to the autoreclose logic.
These inputs can be opto-isolated inputs configured for that under the AUTOMAT. CTRL
menu. External contacts can then be wired to be used as an input and influence the
autorecloser scheme. These 4 inputs are:
The following table gives the AUTOMAT.CTRL/Inputs menu assigned to the autoreclose
logic input. The second column presents the menu disabling the function if not assigned in
the PROTECTION G1/Autoreclose menu (Setting = No).
Inputs menu
Enabled with:
External CB Fail
CB FLT
EXT CB FAIL
Aux 1
Aux 2
CYCLES tAux1 *
CYCLES tAux2 *
Application Guide
P12y/EN AP/Fa5
Page 47/96
External CB fail
Most of circuit breakers provide one trip-close-trip cycle. A delay time is necessary to return
to the nominal state of the CB (for example, the spring that allows the circuit breaker to close
should be fully charged). The state of the CB can be checked using an input assigned to the
CB FLT function. If on completion of the Ext CB Fail time (tCFE), the CB FLT indicates
a failed state of the CB, a lockout occur and the CB remains open.
5.2.2.2
5.2.2.3
5.2.3
Autoreclose in progress
79 Run
79 Run
79Int. Locked
79 int. Lock.
79Ext. Locked
79 ext. Lock.
Autoreclose in progress
Final Trip:
5.2.3.1
Autoreclose in progress
The Autoreclose in progress signal is present during the complete reclose cycles from
protection initiation to the end of the reclaim time or lockout.
5.2.3.2
Final trip
The "Final trip" signal indicates that a complete autoreclose cycle has been completed and
that the fault has been cleared.
The "Final trip" signal can be reset after a manual closing of the CB after the settable inhibit
time (tI).
P12y/EN AP/Fa5
Application Guide
Page 48/96
5.2.4
At the end of the relevant dead time, CB FLT input is sent (see 5.2.2.1).
The reclaim time (tR) starts when the CB has closed. If the circuit breaker does not trip
again, the autoreclose function resets at the end of the reclaim time.
If the protection operates during the reclaim time, the relay either advances to the next shot
that is programmed in the autoreclose cycle, or it locks out (see 5.2.6).
The total number of reclosures is displayed under the MEASUREMENTS/Reclose Stats
menu.
5.2.5
5.2.6
Recloser lockout
If the protection element operates during the reclaim time, following the final reclose attempt,
the relay will lockout and the autoreclose function is disabled until the lockout condition
resets.
The lockout condition can reset by a manual closing after the "Inhib Time tI".
The Autoreclose can also be locked out using a CB FLT input. This information can be
issued from the "not charged" or "Low gas pressure" indications of CB springs.
Note that Autoreclose can also be locked by:
5.2.7
The fact that the CB doesnt open after tBf delay (CB Fail)
5.2.8
Rolling demand
This specific counter avoids a frequent operation of a CB in case of frequent intermittent
fault. The numbers of shoot can be adjusted from 1 to 100 in the cell Max cycles nb,
settable in a time period from 10min to 24 hours.
The rolling demand is used when a definite number of successfully recloses are made on a
definite time.
Application Guide
P12y/EN AP/Fa5
Setting Guidelines
5.3.1
Number Of Shots
Page 49/96
There is no perfect rule to define the number of shots for a particular application.
For medium voltage systems it is common to use two or three autoreclose shots, and, for
specific applications, four shots. Using four shots, final dead time can be set for a time long
enough to allow thunderstorms to stop before definitive final reclose. This scheme prevents
unnecessary lockout caused by consecutive transient faults.
Typically, the first trip, and sometimes the second, are caused by the instantaneous
protection. Since 80% of faults are transient, the following trips will be time delayed, and all
will have increasing dead times to clear non-permanent faults.
In order to determine the number of shots required; the first factor is the ability for the circuit
breaker to perform several trip-close operations in a short time and, the effect of these
operations on the maintenance period.
If a moderate percentage of non-permanent faults is present in a system, two or more shots
are justified. If fused tees are used and the fault level is low, the timer of the fuses may not
discriminate with the main IDMT relay: several shots are usefull. This would not warm up the
fuse to a such extent that it would eventually blow before the main protection operated.
5.3.2
5.3.3
P12y/EN AP/Fa5
Application Guide
Page 50/96
Trip time
Trip time
Upstream relay
Upstream relay
Trip
Downstream relay
Downstream relay
Trip
Trip time
Trip
Trip
NOTE:
5.3.3.1
Load
It is very difficult to optimize the dead time due to the great diversity of load on a system.
However, it is possible to study each type of load separately and thereby be able to define a
typical dead time.
The most common types of loads are synchronous or induction motors and lighting circuits.
Synchronous motors tolerate only extremely short interruptions of supply without loss of
synchronism. In practice, the dead time should be sufficient to allow the motor no-volt device
to operate. Typically, a minimum dead time of 0.2-0.3 seconds is recommended.
Induction motors, on the other hand, can withstand supply interruptions, up to a maximum of
0.5 seconds and re-accelerate successfully. In general dead times of 3-10 seconds are
normally satisfactory, but there may be special cases for which additional time is required to
allow the reset of manual controls and safety devices.
Loss of supply of lighting circuits, such as street lighting, can lead to important safety
problems (car circulation). Regarding domestic customers, the main consideration is linked
to the inconvenience caused.
The number of minutes lost per year to customers will be reduced on feeders using the
autorecloser and will also be affected by the dead time settings used.
Application Guide
P12y/EN AP/Fa5
Page 51/96
Circuit Breaker
For high speed autoreclose, the minimum dead time of the power system depends on the
minimum time delay imposed by the circuit breaker during a trip and reclose operation.
Since a circuit breaker is a mechanical device, it has an inherent contact separation time.
This operating time for a modern circuit breaker is usually within the 50-100ms range, but
could be longer with older designs.
NOTE:
Once the circuit breaker has reset, the breaker can start to close. The period of time
between the energisation of the closing mechanism and the making of the contacts is called
closing time. Because of the time constant of a solenoid closing mechanism and the inertia
of the plunger, a solenoid closing mechanism may take 0.3s. A spring operated breaker, on
the other hand, can close in less than 0.2 seconds.
Where high speed reclosing is required, for the majority of medium voltage applications, the
circuit breaker mechanism dictates itself the minimum dead time. However, the fault deionising time may also have to be considered.
High speed autoreclose may be required to maintain stability on a network that has two or
more power sources. For high speed autoreclose, the system disturbance time should be
minimised using fast protection, <50 ms, such as distance or feeder differential protection
and fast circuit breakers < 100 ms. Fast fault clearance can reduce the time for the fault arc
to de-ionise.
To ensure stability between two sources, a dead time of <300 ms is typically required.
Considering only the CB, this minimum time corresponds to the reset time of the mechanism
plus the CB closing time. Thus, a solenoid mechanism is not adapted for high speed
autoreclose due to the fact that the closing time is generally too long.
5.3.3.3
5.3.3.4
Protection Reset
It is essential that the protection fully resets during the dead time, so that correct time
discrimination is maintained after reclose on to a fault. For high speed autoreclose,
instantaneous reset of protection is required.
Typical 11/33kV dead time settings in the UK are as follow:
1st dead time = 5 - 10 seconds
2nd dead time = 30 seconds
3rd dead time = 60 - 100 seconds
4th dead time (uncommon in the UK, however used in South Africa) = 60 - 100 seconds
P12y/EN AP/Fa5
Page 52/96
5.3.4
Application Guide
MiCOM P125/P126 & P127
Supply continuity - Large reclaim times can result in unnecessary lockout for transient
faults.
Fault incidence/Past experience - Small reclaim times may be required where there is
a high incidence of lightning strikes to prevent unnecessary lockout for transient faults.
Charging time of the spring or resetting of electromagnetical induction disk relay - For
high speed autoreclose, the reclaim time may be set longer than the spring charging
time to ensure that there is sufficient energy in the circuit breaker to perform a tripclose-trip cycle. For delayed autoreclose, this setting is of no need as the dead time
can be extended by an extra CB healthy check window time if there is insufficient
energy in the CB. If there is insufficient energy after the check window time the relay
will lockout.
Switchgear Maintenance - Excessive operation resulting from short reclaim times can
mean shorter maintenance periods. A minimum reclaim time of 5s may be needed to
give sufficient time to the CB to recover after a trip and close before it can perform
another trip-close-trip cycle.
The reclaim time must be long enough to allow any time delayed protection leading to
autoreclose to operate. Failure to do so can cause the autoreclose scheme to reset too soon
and the reactivation of the instantaneous protection.
If that were the case, a permanent fault would look like some transient faults, caused by
continuous autorecloses. Applying a protection against excessive fault frequency lockout is
an additional precaution that can solve this problem.
It is possible to obtain short reclaim times to obtain less lockouts of the CB by blocking the
reclaim time from the protection start signals. If short reclaim times are to be used, then the
switchgear rating may dictate the minimum reclaim time.
Sensitive earth fault protection is used to detect high resistance earth faults. The time delay
of such protections is usually a long time delay, typically about 10-15s. If autoreclose is
generated by the SEF protection, this timer must be taken into account when deciding the
value of the reclaim time, if the reclaim time is not blocked by an SEF protection start signal.
Sensitive earth faults, caused by a broken overhead conductor in contact with dry ground or
a wood fence are rarely transient faults and may be dangerous to people.
It is therefore common practice to block the autoreclose using the sensitive earth fault
protection and lockout the circuit breaker.
Where motor-wound spring closed circuit breakers are used, the reclaim time must be at
least as long as the spring winding time for high speed autoreclose to ensure that the
breaker can perform a trip-close-trip cycle.
A typical 11/33kV reclaim time is 3-10 seconds, this prevents unnecessary lockout during
thunderstorms. However, times up to 60-180 seconds maybe used.
Application Guide
P12y/EN AP/Fa5
5.3.5.1
General setting
Page 53/96
Yes
At least 1
1234
0111
52a
max. 4 cycles
CB Close
P12y/EN AP/Fa5
Application Guide
Page 54/96
5.3.5.2
Yes
At least 1
1234
0111
At least a trip
command.
Application Guide
P12y/EN AP/Fa5
Page 55/96
Yes
At least 1
Cycles tAux1
Cycles tAux2
To achieve autoreclose only setting, external start should be wired on a digital input. This
digital input should be assigned to tAux1 and/or tAux2.
AUTOMA. CTRL / INPUTS
Automat control inputs
Aux
Within Autorecloser menu, both strip and start and inhib trip should be selected for tAux1
and/or tAux2
P12y/EN AP/Fa5
Application Guide
Page 56/96
To avoid any trip when tAux is ON, ensure that tAux is not selected in trip command menu.
AUTOMA. CTRL / TRIP COMMANDS
Trip Commands
5.3.6
Trip command
without tAux
Number Of Shots
There are no clear-cut rules for defining the number of shots for a particular application.
Generally medium voltage systems utilize only two or three shot autoreclose schemes.
However, in certain countries, for specific applications, four shot approaches are not
uncommon. Four shots have the advantage that the final dead time can be set sufficiently
long to allow any thunderstorms to pass before re-closing for the final time. This approach
will prevent unnecessary lockout for consecutive transient faults.
Typically, the first trip, and sometimes the second, will result from short time protection.
Since 80% of faults are transient, the subsequent trips will be time delayed, all with
increasing dead times to clear non-permanent faults.
In order to determine the required number of shots the following factors must be taken into
account:
An important consideration is the ability of the circuit breaker to perform several trip-close
operations in quick succession and the effect of these operations on the maintenance period.
If statistical information on a particular system shows a moderate percentage of nonpermanent faults, which could be burned out, two or more shots are justified. In addition to
this, if fused tees are used and the fault level is low, the fusing time may not discriminate
with the main IDMT relay and it would then be useful to have several shots. This would warm
up the fuse to such an extent that it would eventually blow before the main protection
operated.
5.3.7
Application Guide
P12y/EN AP/Fa5
Page 57/96
general dead times of 3 - 10 seconds are normally satisfactory, but there may be special
cases for which additional time is required to permit the resetting of manual controls and
safety devices.
Loss of supply to lighting circuits, such as street lighting may be important for safety reasons
as intervals of 10 seconds or more may be dangerous for traffic. The main considerations of
supply interruptions for domestic customers are those of inconvenience.
An important measurement criterion for many power utilities is the number of minutes lost
per year to customers, which will be reduced on feeders using autoreclose and will also be
affected by the dead time settings used.
For high-speed autoreclose the minimum dead time of the power system will depend on the
minimum time delays imposed by the circuit breaker during a tripping and re-closing
operation.
Since a circuit breaker is a mechanical device, it will have an inherent contact separation
time. The operating time for a modern circuit breaker is usually within the range of 50 - 100
ms, but could be longer with older designs.
After tripping, time must be allowed for the mechanism to reset before applying a closing
pulse. This resetting time will vary depending on the circuit breaker, but is typically 0.1
seconds.
Once the circuit breaker has reset, it can begin to close. The time interval between the
energizing of the closing mechanism and the making of the contacts is termed the closing
time. Owing to the time constant of a solenoid closing mechanism and the inertia of the
plunger, a solenoid closing mechanism may take 0.3 s. A spring-operated breaker, on the
other hand, can close in less than 0.2 seconds.
Where high-speed re-closing is required, which is true for the majority of medium voltage
applications, the circuit breaker mechanism itself dictates the minimum dead time. However,
the fault de-ionizing time may also have to be considered. High-speed autoreclose may be
required to maintain stability on a network with two or more power sources. For high-speed
autoreclose the system disturbance time should be minimized by using fast protection, <50
ms, such as distance or feeder differential protection and fast circuit breakers <100 ms. Fast
fault clearances can reduce the required fault arc de-ionizing time.
For stability between two sources a dead time of <300 ms may typically be required. When
only considering the CB the minimum system dead time is given by the mechanism reset
time plus the CB closing time. Thus, a solenoid mechanism will not be suitable for highspeed autoreclose as the closing time is generally too long.
For high-speed autoreclose the fault de-ionizing time may be the most important factor when
considering the dead time. This is the time required for ionized air to disperse around the
fault position so that the insulation level of the air is restored. This can be approximated from
the following formula:
Vsys
1
[s] (Vsys = System voltage in kV)
34.5 frequency
P12y/EN AP/Fa5
Page 58/96
5.3.7.1
Application Guide
MiCOM P125/P126 & P127
5.3.8
Supply continuity - long reclaim times can result in unnecessary lockout for transient
faults.
Fault incidence and past experience - short reclaim times may be required where
there is a high incidence of lightning strikes to prevent unnecessary lockout for
transient faults.
Spring charging time - for high-speed autoreclose the reclaim time may be set longer
than the spring charging time to ensure there is sufficient energy in the circuit breaker
to perform a trip-close-trip cycle. For delayed autoreclose there is no need to set the
reclaim time longer than the spring charging time as the dead time can be extended
by an extra CB healthy check window time if there is insufficient energy in the CB. If
there is insufficient energy after the check window time has elapsed the relay will
lockout.
Switchgear maintenance - excessive operation resulting from short reclaim times can
mean shorter maintenance periods. A minimum reclaim time of >5 s may be needed
to allow the CB time to recover after a trip and close operation before it can perform
another trip-close-trip cycle. This time will depend on the duty (rating) of the CB.
The reclaim time must be long enough to allow any time-delayed protection initiating
autoreclose to operate. Failure to do so would result in premature resetting of the
autoreclose scheme and re-enabling of instantaneous protection.
If this condition arose, a permanent fault would effectively look like a number of
transient faults, resulting in continuous autoreclose operations unless additional
measures were taken to overcome this, such as excessive fault frequency lockout
protection.
A sensitive earth fault protection is usually applied to detect high resistance earth
faults.
Usually, a long trip delay time is set, typically 10 - 15 s. This longer time may be taken
into consideration, if autoreclose is started by an earth fault protection, and when
deciding on a reclaim time, if the reclaim time is not blocked by a SEF protection start
signal. Sensitive earth faults, for example, a broken overhead conductor in contact
with dry ground or a wood fence, is rarely transient and presents great danger to
persons and animals. It is therefore common practice to block autoreclose by
operation of sensitive earth fault protection and lockout the circuit breaker.
Where motor-wound spring closed circuit breakers are used, the reclaim time must be
at least as long as the spring winding time for high-speed autoreclose to ensure that
the breaker can perform a trip-close-trip cycle.
Fuse application
An application of the ARC is the coordination with a fuse. This application is typical in rural
areas where derived lines are protected by a fuse.
P3880xxa-1
We suppose to have the following settings for the protection and the ARC narrow to the
configuration matrix. All the others have to be compliance with the rules above.
Application Guide
P12y/EN AP/Fa5
Page 59/96
67 protection
I> ON
I>> ON
I> 8 In
I>> 10 In
tI> 5 sec.
tI>> 0 sec
AUTORECLOSE
(only the matrix)
ARC cycles
AR init tI>
4321
0110
ARC cycles
AR init tI>>
4321
0021
ARC cycles
AR init tI>>>
4321
0000
ARC cycles
AR init tAux1
4321
0000
Number of phase
cycles
P3880xxa-2
2.
P3880xxa-3
3.
tD1 in progress.
4.
tD1 is expired.
5.
P12y/EN AP/Fa5
Page 60/96
Application Guide
MiCOM P125/P126 & P127
P3880xxa-4
P3880xxa-5
The above one is an example to show a basic using of the 2 setting in the ARC function.
Application Guide
MiCOM P125/P126 & P127
6.
6.1
Trip Commands
P12y/EN AP/Fa5
Page 61/96
This menu is used to assign the trip of the protection and the automatic control function to
the relay 1. See the P12y/EN FT (User Guide).
The relay 1 is usually used for the trip of the CB and the logic output is used to start all the
functionality relevant to the CB control.
6.2
Latch relays
Sometimes it occurs to memorise trips or alarms.
By this menu it is possible the latching of the relay from 1 to 8 the relevant relays to the 79
function must not be assigned latched.
6.3
6.3.1
Setting Guidelines
In the case of a single point earthed power system, there will be little zero sequence current
flow and the ratio of I2/I1 that flows in the protected circuit will approach 100%. In the case of
a multiple earthed power system (assuming equal impedance in each sequence network),
the ratio I2/I1 will be 50%.
The setting for the broken conductor protection element is described in Technical Data and
the menu is described in User Guide.
P12y/EN AP/Fa5
Page 62/96
6.3.2
Application Guide
MiCOM P125/P126 & P127
Example Setting
The following information was recorded by the relay during commissioning:
full load = 500A
I2 = 50A
therefore the quiescent ratio for I2/I1 is given by:
I2/I1 = 50/500 = 0.1
To allow for tolerances and load variations a setting of 200% of this value may be typical:
Therefore set RATIO I2/I1 = 20%
Set tBC = 60 s to allow adequate time for short circuit fault clearance by time delayed
protections.
6.4
6.4.1
Overview
Inrush Blocking function operates by measuring ratio of second to fundamental harmonic
current. It could be used as blocking logic of I >, I >>, I >>>, I0 >, I0 >>, I0 >>>, Ie_d>,
Ie_d>>, I2 >, I2 >> or I2 >>> in case the harmonic 2 ratio is higher than the settable
threshold. Indeed, inrush blocking functions will reset selected protection function starting.
The minimum duration of overcurrent threshold inhibition (tReset) can be also set. This value
depends on the transformer power transient inrush duration: between 0.1 second (for a
100kVA transformer) to 1.0 second (for a large unit). It is used to avoid any maloperation
during a fixed duration in case of too sensitive setting.
6.4.2
Operation
For each of the three phases currents (IA, IB, IC), the harmonic restraint function compares
the ratio of harmonic 2 to fundamental with the setting ratio (adjustable from Harmonic 2 /
Fundamental = 10 % up to 35 % step 1%).
Minimum fundamental current value required for operation of Inrush Blocking function. There
is 0.2In, and there is no upper limit to disable this feature. However, in transformer
protection, the high set overcurrent stage shall not be controlled by this Inrush Blocking
feature; this enables detection of all high current faults without inrush blocking.
Inrush Blocking feature will block selected protection stages, any time inrush conditions
occurs on the line (Ratio of 2nd Harmonics measured > Inrush H2 settings ratio), and will be
at least active during tReset.
Operating Inrush current is settable from 10% to 35% of fundamental current.
Application Guide
P12y/EN AP/Fa5
Page 63/96
tReset timer defines the minimum duration of overcurrent threshold inhibition (0-2s, settable).
This timer starts as soon as operating inrush current threshold picks up:
If inrush condition duration is smaller than tReset setting value, selected overcurrent
function will remain inhibited during tReset.
If inrush condition duration is longer than tReset setting value, selected overcurrent
function will be inhibited as long as inrush condition remains valid.
Under inrush condition, the following selectable protection stages will be blocked:
NOTE:
P12y/EN AP/Fa5
Application Guide
Page 64/96
6.4.3
Principle
Settable
blocking
Blocking logic 1
Blocking logic 2
LEVEL
LEVEL
hold
DELAY
hold
DELAY
hold
DELAY
LEVEL
Settable blocking IE
LEVEL
Settable blocking I2
LEVEL
Inrush
P0866ENA
Application Guide
P12y/EN AP/Fa5
Page 65/96
IB
In >
IA
IC
In >
Time more
than 200ms
Internel Virtual
threshold 5% In
IA
IB IC
One phase is
upper than 5% of
In at start.
Internel Virtual
threshold 5% In
T<200ms
T<200ms
CLP starts
In >
IA
IB IC
P3942ENa
Internel Virtual
threshold 5% In
P3942ENa
T<200ms
P12y/EN AP/Fa5
Application Guide
Page 66/96
&
>1
&
Start C.L.P.
P3941ENa
VTS
The voltage transformer supervision (VTS) feature is used to detect failure of the analog ac
voltage inputs to the relay. This may be caused by internal voltage transformer faults,
overloading, or faults on the interconnecting wiring to relays. This usually results in one or
more VT fuses blowing.
MiCOM P127 is able to detect a VT loss by using VTS automatism. As soon as VT loss is
detected, all voltage dependent functions will be blocked, an alarm can be raised and
directional overcurrent functions might be replaced by non-directional overcurrent functions.
6.6.1
VTS occurrence
VTS automation uses a fixed logic. A VT fault occurs if at least one of the two following
conditions is verified:
OR
negative sequence voltage is greather than 0,17*Vn (0,3*Vn for 3Vpn connexion) and
negative sequence current is smaller than 0,5*In
voltage is smaller than 0,1*Vn and current greather than 0,1*In.
VTS alarm
A VTS alarm occurs when a VT fault occurs during more than tVTS.
VTS Alarm wont occur if VTS conditions remain valid less than the timer tVTS (settable from
0 to 100s). If VTS condition remains longer than tVTS, this alarm will be latched until
HMI/communication reset.
The VTS alarm menu activates or deactivates the alarm message and LED (see diagram
6.7).
6.6.3
Application Guide
P12y/EN AP/Fa5
Page 67/96
to change directional overcurrents (I>, I>>, I>>>; Ie>, Ie>>, Ie>>>, Ie_d> and Ie_d>>)
into non-directional functions. For instance, when VTS Non dir I> is selected, the non
directional overcurrent protection is available for I> threshold.
6.6.5
VTS Blocks Protections? submenu will unblock all the non directional overcurrent
protection, or give the possibility to select individually the non directional overcurrent
protection(s),
When VTS Blocks protections? = yes, the non directional overcurrent protections (I>,
I>>, I>>>; Ie>, Ie>>, Ie>>>, Ied> and Ie_d>> thresholds) can be blocked: for instance,
if VTS Non dir I>> = Yes, when a VT fault occurs, the non directional overcurrent
protection is available for I>> threshold.
Voltage/Power protection
If VTS occurs, all voltage and power protection will be blocked:
6.7
6.7.1
P12y/EN AP/Fa5
Application Guide
Page 68/96
The following table shows the relay menu for the CT Supervision element, including the
available setting ranges and factory defaults:
Menu text
Setting range
Default setting
Min
max
step size
Automat. Ctrl
CT Supervision
6.7.1.1
CT Supervision ?
No
Yes / No
Ie>
0.08 In
0.08 In
1 In
0.01 In
Ue<
5 / 20 V
0.5 / 2V
22 / 88V
0.1 / 0.5V
tCTS
200ms
0s
100s
10ms
CTS
Ie>
&
Alarm
tCTS
Ue<
Calculation part
Logical part
P3975ENa
The residual voltage setting, Ue< and the residual current setting, Ie>, should be set to avoid
unwanted operation during healthy system conditions. For example Ue< should be set to
120% of the maximum steady state residual voltage. The Ie> will typically be set below
minimum load current. The time-delayed alarm, tCTS, is generally set to 5 seconds.
6.8
Application Guide
P12y/EN AP/Fa5
Page 69/96
(1)
Output relay
Equation
51V>
I>> output
t51V> (1)
tI>> output
51V>>
I>>>
t51V>> (1)
tI>>>
(tU<< or tV2>>) and tI>>>
Since software version 11. These functions are selected with (U< or V2>) & I>> and
(U<< or V2>>) & I>>> menus.
P12y/EN AP/Fa5
Application Guide
Page 70/96
Automat. Ctrl
51V
51V> selection
menu (U< or V2>)& I>>?
No
I>>
I>>
Yes
U<
&
&
V2>
No
tI>>
tI>>
Yes
tU<
&
&
tV2>
Automat. Ctrl
51V
51V>> selection
menu (U<< or V2>>)& I>>>?
(U<< or V2>>)&I>>>
No
I>>>
I>>>
Yes
U<<
&
&
V2>>
No
tI>>>
tI>>>
Yes
tU<<
&
&
tV2>>
Yes
VTS
Automat. Ctrl
No
No
VT Supervision
VTS Alarm?
VTS
Yes
VTS Alarm
P3963ENa
Application Guide
P12y/EN AP/Fa5
Page 71/96
6.10
P0024ENa
P12y/EN AP/Fa5
Application Guide
Page 72/96
6.11
P0024ENa
BLOCKING LOGIC
The allocations of the "Blocking Logic1 and 2 functions are available in the menu
AUTOMAT. CTRL/Blocking Logic1 / Blocking Logic2; this logic is initiated by energizing
the appropriate logic input (Blk Log1 or Blk Log2) selecting in the AUTOMAT.
CRTL/INPUTS menu.
This functionality involves all the current and voltage protections available in the relays.
Application Guide
P12y/EN AP/Fa5
Page 73/96
6.13
6.14
CB Closing Time
CB Operations
Amps(n) I1
Amps(n) I2
Amps(n) I3
The above counters in the CB condition monitoring function may be reset to zero, for
example, following a maintenance inspection and overhaul.
The circuit breaker condition monitoring counters will be updated every time the CB opens,
from all the different way. In cases where the breaker is tripped by an external protection
device it is also possible to update the CB condition monitoring. This is achieved by
allocating one of the logic inputs or via the communications to accept a trigger from an
external device.
The options available for the CB condition monitoring function include the set-up of the
broken conductor protection element and those features, which can be set to raise an alarm,
or to lockout the CB.
All the settings are available in the AUTOMAT. CTRL/CB Supervision menu.
P12y/EN AP/Fa5
Page 74/96
6.14.1
Setting Guidelines
6.14.1.1
Application Guide
MiCOM P125/P126 & P127
Where overhead lines are prone to frequent faults and are protected by oil circuit breakers
(OCB), oil changes account for a large proportion of the life cycle cost for the switchgear.
Generally, oil changes are performed at a fixed interval of circuit breaker fault operations.
However, this may result in premature maintenance where fault currents tend to be low, and
hence oil degradation is slower than expected.
The In counter monitors the cumulative severity of the duty placed on the interrupter
allowing a more accurate assessment of the circuit breaker condition to be made.
For OCBs, the dielectric withstand of the oil generally decreases as a function of
I2t. This is where I is the fault current broken, and t is the arcing time within the
interrupter tank (not the breaking time). As the arcing time cannot be determined accurately,
the relay would normally be set to monitor the sum of the broken current squared, by setting
n = 2.
For other types of circuit breaker, especially those operating on higher voltage systems,
practical evidence suggests that the value of n = 2 may be inappropriate. In such
applications n may be set to 1.
An alarm in this instance for example may be indicative of the need for gas/vacuum
interrupter HV pressure testing.
It is imperative that any maintenance programme must be fully compliant with the switchgear
manufacturers instructions.
6.14.1.2
6.14.1.3
6.15
Application Guide
P12y/EN AP/Fa5
Page 75/96
CB Fail Enabled
Any Trip
1
External CBF
Initiate
S
R
tBF
CB Fail Alarm
CBF Ia<
CBF Ib<
CBF Ic<
P0428ENa
6.15.2
P12y/EN AP/Fa5
Application Guide
Page 76/96
6.16
6.16.1
WARNING 2:
A 52 Fail (trip circuit failure) signal is generated if the logic input detects no voltage signal
during a time longer than the settable timer tSUP. See Chapter P12y/EN FT (User Guide)
and Chapter P12y/EN TD (Technical Data) for the settings.
As this function is disabled when the trip logic output (RL1) is energised, this function is
suitable for use with the enabled relay latching logic.
Logic input
Trip Circuit
tSUP
&
Tripping
Output 1(RL1)
energized
52 Fail
signal
P0367ENa
Application Guide
P12y/EN AP/Fa5
Page 77/96
Electrical panel
52a
Circuit breaker
P3966ENa
P12y/EN AP/Fa5
Application Guide
Page 78/96
Example 2
In this example both 52a and 52b auxiliary contacts are available; the MiCOM P126 and
P127 relays monitor the complete trip circuit when the CB is closed and a part of the trip
circuit when the CB is open.
In this case it is necessary to insert a resistor R1 in series with 52b, if either the output (RL1)
trip is latched or it stays involuntarily closed, or a long time trip pulse is programmed (See
6.16.2 for R1 calculation). Otherwise, a short circuit of DC trip supply would occur during
tripping sequence.
In this example, the protection is limited: the coil is only monitored when CB is closed.
Electrical panel
52b
52a
Circuit breaker
R1
P3967ENa
Application Guide
P12y/EN AP/Fa5
Page 79/96
Example 3
In this example both 52a and 52b auxiliary contacts are available, the MiCOM P126 & P127
relays monitor the complete trip circuit whatever the CB status (CB open or CB closed).
In this case it is necessary to insert a R1, if either the output (RL1) trip is latched, or it stays
involuntarily closed, or a long time trip pulse is programmed (See 6.16.2 for R1
calculation). Otherwise, a short circuit of DC trip supply would occur during tripping
sequence.
Electrical panel
52b
52a
Circuit breaker
R1
P3968ENa
P12y/EN AP/Fa5
Application Guide
Page 80/96
1 - Case of example no 2:
The R1 resistor maximum value (in Ohm) is defined by the following formula:
R1 <
0,8 U a U min
[Ohm]
I min
Where:
Ua =
Umin =
Imin =
Auxiliary voltage value (in this case a DC voltage; range is given on label under the
top hinged cover. See table below).
Internal minimum voltage value needed for the opto logic input to operate.
Minimum current value needed for the opto logic input to operate.
Relay auxiliary voltage range (Ua)
PR1 > 2
(1,2 U a ) 2 [W]
R1
2 - Case of example no 3:
The R1 resistor maximum value (in Ohm) is defined by the following formula:
R1 <
0,8 U a U min
R Coil [Ohm ]
I min
Where:
Ua =
Umin =
Imin =
Rcoil =
Auxiliary voltage value (in this case a DC voltage; range is given on label
the top hinged cover. See table below).
Internal minimum voltage value needed for the opto logic input to operate.
Minimum current value needed for the opto logic input to operate.
Trip coil resistance value.
under
PR1 > 2
(1,2 U a ) 2 [W]
(R1 + R Coil )
If the trip contact is latched or temporarily by-passed, the continuous current through the
tripping coil is:
ICONTINUOUS =
(R1 + RCOIL)
1.2 va
If the value is above admissible continuous current through the tripping coil, trip contact
latching must not be made and by-passing trip contact should never be made.
Application Guide
MiCOM P125/P126 & P127
P12y/EN AP/Fa5
Page 81/96
6.17
Switch onto Fault Protection & Trip on Reclose (SOTF/TOR) (P126 & P127)
6.17.1
General
Under particular conditions, it can happen that when the feeder is supplied by the closing of
the CB a fast trip command may be required if a fault is present (Closing on to fault).
Some faults may be caused by conditions not removed from the feeder after a reclosing
cycle or a manual trip, or due to earthed clamps left on after maintenance works. In these
cases, it may be desirable to clear the fault condition in fast time, rather than waiting for the
trip time delay DMT or IDMT associated with the involved protection.
In case of manually closing of the CB it can happen to switch on to an existing fault. This is a
particularly critical situation, because the overcurrent protection would not clear the fault until
the set operate delay had elapsed. This is another typical case of closing on to fault. Hence it
is desirable to clear the fault as fast as possible.
The P126 and P127 relays provide the SOTF/TOR functionality.
The SOTF acronym means switch on to fault.
The TOR acronym means trip on recloser.
The available setting to enable/disable/set the SOTF/TOR (Switch On To Fault/ Trip On
Reclose) function is written in a submenu of the AUTOMATIC CTRL menu.
The setting regarding the I>> and I>>> is provided to initiate the SOTF function.
6.17.2
SOTF/TOR description
When the SOTF/TOR function is enable, it can be initiated by a local manual CB control
close command detected by the digital input labelled Man.Close, or by a TC (closing
command by remote via network: Modbus, IEC 60870) or by an automatic reclosing cycle.
When CB has been closed on some faults caused by lightning or something else, the fault
detection needs a time period. This is the reason why a 500ms fixed time window after
initiatialization of the SOTF/TOR function is included.
When this fixed timer is elapsed and the I>> or I>>> is detected, the settable timer t Sotf
starts.
The existence of this settable timer is justified because in some applications selectivity for
fault occurring in stage two or three is requested.
Another justification of the SOTF/TOR tripping time delay is for cases where serious
transient happen and the three poles of the CB do not close at the same time and for those
cases where the CB may not be closed instantaneously.
Furthermore, the t SOFT can also be considered a trip delay time that substitutes the trip
timer of the started threshold such to accelerate the tripping.
If a trip due to switch on to fault occurs during the reclaim time of the ARC, the trip will be
definitive and the ARC will move in the blocked status.
If the I>> and I>>> reset during the settable timer t Sotf the SOTF/TOR function resets.
The following signals can activate the SOTF/TOR function:
-
P12y/EN AP/Fa5
Application Guide
Page 82/96
I>>
Autorecloser
&
Autorecloser
0
AR selected
I>>>
&
&
t SOTF
0.. 500 ms
valided by
setting
&
0
OR
Ctrl Close input
Monostable
500 ms
&
0
SOTF (Manual
close) input
d
SOTF (Manual close)
input selected
HMI order
HMI order selected
&
0
OR
Trip
tI> valided by
setting
tI>> valided by
setting
&
0
tI>>> valided by
setting
Close origin
SOTF setting
SOTF setting
Trip setting
P3939ENa
The trip by SOTF is settable in the AUTOMATIC CTRL/TRIP COMMAND submenu and in
the AUTOMATIC CTRL/Output relays submenu.
6.18
6.18.1
General
The goal of this feature is to be able to block commands sent remotely through
communication networks (like setting parameters, control command, etc.), to prevent any
accidents or maloperation during maintenance work performed on site.
A digital input labelled LOCAL MODE is assigned to this feature. In Local mode, only the
synchronising time signal is allowed.
Commands sent remotely (CTRL TRIP and CTRL CLOSE) as well as commands sent by the
autoreclose function (CB Close) can be set to activate their own dedicated output relay (and
not necessarily the same output relay as the protection trip output RL1).
6.18.2
Settings
In the AUTOMATIC CTRL/Trip Commands menu, TC item uses the CTRL TRIP function
to open the CB.
In the AUTOMATIC CTRL/Output relays menu, the CTRL TRIP and CTRL CLOSE
functions are assigned to remotely open and close the CB.
The CB CLOSE relay can be used for the close command.
In order to keep the normal functionality, the customer will have to assign both information
TRIP by protection and Ctrl Trip on (RL1), and to assign both information CLOSE CTRL and
CB CLOSE on the same auxiliary relay.
An application of the subject mentioned above is presented below.
In the following schematic, the customer will have to assign the TRIP and CTRL TRIP to the
TRIP RELAY, the CB CLOSE and the CTRL CLOSE to the auxiliary relay number two, in
accordance with setting above.
Application Guide
P12y/EN AP/Fa5
Page 83/96
If the Local input is energised any remote command will be ignored if the Local input is deenergised all the remote control will be considered.
DC V+
Switch
Local
Remote
P125/P126/P127
Local trip
RL 1
Control trip
Local close
RL 2
Control close
RL 2
AR close
RL 1
Protection trip
Input labeled
Local
DC V-
6.19
P0689ENa
I<
tAUX 1(input1)
&
5 sec
1
tAUX 2(input2)
10 sec
Output
P0717ENa
P12y/EN AP/Fa5
Page 84/96
7.
7.1
Event Records
Application Guide
MiCOM P125/P126 & P127
The relay records and time tags up to 250 events and stores them in a non-volatile memory.
This enables the system operator to analyse the sequence of events that occurred within the
relay following a particular power system condition, switching sequence etc. When the
available memory space is exhausted, the new fault automatically overwrites the oldest fault.
The real time clock within the relay provides the time tag to each event, to a resolution of
1ms.
The event records are available for viewing either on the front panel, or via the front panel
EIA RS232 port or remotely, via the rear EIA RS485 port.
7.2
Fault Records
Each time any of the programmed thresholds are crossed a fault record is created and
stored in a memory. The fault record tags up to 25 faults and stores them in a non-volatile
memory. This enables the system operator to identify and analyse network failures. When
the available memory space is exhausted, the new fault automatically overwrites the oldest
fault.
Note that viewing of the actual fault record is carried out in the RECORD/Fault Record
menu, which is selectable from up to 25 stored records. These records consist of fault flags,
fault measurements etc. Also note that the time stamp given in the fault record itself will be
more accurate than the corresponding stamp given in the event record as the event is
logged some time after the actual fault record is generated.
The fault records are available for viewing either on the display, or via the front panel EIA
RS232 port or remotely, via the rear EIA RS485 port.
7.3
Instantaneous Recorder
Each time any of programmed threshold is crossed an instantaneous record is created and
displayed in the RECORDS/Instantaneous menu. The last five starting information with the
duration of the information are available. The number of the fault, hour, date, origin (voltage,
current and wattmetric protection thresholds), length (duration of the instantaneous), trip (a
trip is appeared, yes or no) are displayed in the RECORDS/Fault Record menu.
7.4
Disturbance Records
The integral disturbance recorder has an area of memory specifically set aside for
disturbance record storage. The disturbance records that may be stored are 3, 5, 7 or 9
seconds length each. Disturbance records continue to be recorded until the available
memory space is exhausted, at which time the oldest disturbance record(s) is (are)
overwritten to make space for the newest disturbance record(s).
The recorder stores actual samples, which are taken at a rate of 16 samples per cycle.
Each disturbance record consists of analogue data channels and digital data channels. Note
that the relevant VTs and CTs ratios for the analogue channels are also extracted to enable
scaling to primary quantities.
The total disturbance recording time is 5 records of 3 seconds, or 4 3s, or 3 5s, or 2 7s
or 1 9s. The disturbance record starts with the disturbance. If the pre-time time is set to
100ms, the record starts 100 ms before the disturbance.
For the settings of the parameters see FT (User Guide) and TD (Technical Data) chapters of
this TG.
Application Guide
P12y/EN AP/Fa5
8.
Page 85/96
8.1
Rolling demand
The principle of the calculation of the rolling demand value for IA, IB and IC currents is
following:
Calculation of the average of the RMS values on a "Rolling Sub Period" period.
The setting of the width of the period "Rolling Sub Period" is in the "RECORDS/Rolling
Demand/Sub Period" menu.
Setting range: from 1 to 60 minutes.
Calculation of the average of these average values (sliding window values) on the
number of "Num. of Sub Periods" periods
The setting of the number of Sub Period "Num of Sub Periods" in the "RECORDS/Rolling
Demand/Num of Sub Per" menu.
Setting range: from 1 to 24.
Display of the first result in the MEASUREMENTS menu only after the storage of "Num of
Sub Periods" periods.
The 3 phases Rolling average value are displayed:
The calculation is reset by either "hand Reset" (by key _ ) without use of password, or a
remote command.
NOTE:
In case of loss of power supply the rolling demand are not stored.
A modification of the settings (either "Rolling Sub Period" or "Num of Sub Periods"
parameter) reset the calculation.
Example:
Sub Period = 5 mn
Num of Sub Period = 2
P12y/EN AP/Fa5
Application Guide
Page 86/96
8.2
The calculation is reset by either "hand Reset" (by key _ ) without use of password, or a
remote command.
NOTE:
In case of loss of power supply the Peak average values are stored.
A modification of the setting "Rolling Sub Period" parameter reset the calculation.
Application Guide
P12y/EN AP/Fa5
9.
Page 87/96
9.1.1
9.1.2
Priority
The front panel is priority level maximum due the fact when the user takes the hand on front
panel and enters a password , it is not possible to change of setting group via remote
communication as long as the password is active (5mn).
Below are listed the priorities in the different ways to switch between setting groups.
ORIGIN OF THE ORDER
PRIORITY LEVEL
FRONT PANEL
MAXIMUM
LOGIC INPUT
MEDIUM
REMOTE COMMUNICATIONS
MINIMUM
P12y/EN AP/Fa5
Application Guide
Page 88/96
10.
MEASUREMENTS
The measurement functions on MiCOM P125, P126 and P127 relays are described in
chapter User Guide of this Technical Guide.
Particular attention is to be given to the power and energy measurement.
10.1
Direct
measurement
Yes
Direct
measurement
Yes
N.A
-------------
Ub
Direct
measurement
Yes
Direct
measurement
Yes
N.A
-------------
Uc
Direct
measurement
Yes
Derived
measurement
Yes
N.A
-------------
Uab
Derived
measurement
Yes
Derived
measurement
Yes
Direct
measurement
Yes
Ubc
Derived
measurement
Yes
Derived
measurement
Yes
Direct
measurement
Yes
Uac
Derived
measurement
Yes
Derived
measurement
Yes
Derived
measurement
Yes
UN
Derived
measurement
Yes
Direct
measurement
Yes
Direct
measurement
Yes
The value for power is calculated in accordance with the following listed table.
VTs connection
3Vpn
2Vpn+Vr
2Vpp+Vr
P= PA+PB+PC
Q= QA+QB+QC
P= PA+PB+PC
Q= QA+QB+QC
Aron insertion
The value for energy is calculated by multiplying the calculated power value by time.
The calculated energy value is stored in a non-volatile memory (EPROM) every second, so
that in case of temporary power supply fault, the previous values calculated can be recalled.
The MiCOM P127 relay provides, on the display, the measurements of the power and of the
energy. Both refer to primary values and rely on the CT and VT ratio.
The maximum active and reactive power value displayed is 9999MW and 9999MVAr.
The maximum active and reactive energy value displayed is 4200GWh and 4200GVArh.
The sign of the active and reactive power/energy values is taken according to the diagram
below.
Application Guide
P12y/EN AP/Fa5
Page 89/96
They are in accordance with the wiring diagrams in the chapter P12y/EN CO in this
Technical Guide.
+
cos phi
+P
-Q
cos phi
V
-cos phi
-P
-Q
+P
+Q
-cos phi
-P
+Q
P0100ENa
10.2
CTM2 phase ?
METERING menu
= none
= none
= none
When CTm1 and CTm2 phases are connected, Metering menu displays frequency, 3phases currents, 3-phases voltage, power and energy measured values.
NOTE:
10.2.1
the following explanations are given for phase A. The same equations
are applicable to phase B or phase C using (IBm or ICm) and (VBm or
VCm).
Frequency
This menu displays network frequency.
P12y/EN AP/Fa5
Application Guide
Page 90/96
10.2.2
Currents
The Currents menu displays the magnitude of the measured currents (true RMS value). It
takes into account the CTm connection (see the previous table) and CTm ratio
(CONFIGURATION / Transfo ratio).
MiCOM P127 displays the magnitude of fundamental current, and the magnitude of the
currents up to the 10th harmonics.
10.2.2.1
IAmh
THD IAm = 100%
NOTE:
h=2
I1
The denominator I1 is the magnitude of the fundamental current.
IAmh
TDD IAm = 100%
h=2
IL
K Factor
K-Factor is a measure of the heating effects on transformers. The following equation is used,
for MiCOM P127, to determine phase A K-Factor, where "h" is the harmonic number and
"IAmh" is the magnitude of the hth harmonic.
10
IAmh h
K IAm = 100
h =1
10
IAmh
h =1
K-Factor is measured on each of the three phases of amps, however there is no "Total" KFactor. K-Factor, like THD, does not indicate the actual load on a device, since all three of
these measurements are ratios. Given the same harmonic ratio, the calculated K-Factor for a
lightly loaded transformer will be the same as the calculated K-Factor for a heavily loaded
transformer, although the actual heating on the transformer will be significantly different.
Application Guide
P12y/EN AP/Fa5
Page 91/96
Voltages
The following table lists the displayed voltage measurements, according to the VT
connection (CONFIGURATION / General options / VT Connection) and / or to the VT
protection (CONFIGURATION / General options / VT Protection).
Configuration
Configuration
Configuration
3Vpn
Displayed 2Vpn+Vr Displayed 2Vpp + Vr Displayed
AND
AND
OR
on HMI
on HMI
on HMI
Protect P-N
Protect P-N
Protect PP
Va
Direct
measurement
Yes
Direct
measurement
Yes
N.A
-------------
Vb
Direct
measurement
Yes
Direct
measurement
Yes
N.A
-------------
Vc
Direct
measurement
Yes
Derived
(calculated)
measurement
Yes
N.A
-------------
Uab
N.A
-------------
N.A
-------------
Direct
measurement
Yes
Ubc
N.A
-------------
N.A
-------------
Direct
measurement
Yes
Uca
N.A
-------------
N.A
-------------
Derived
measurement
Yes
The Voltages menu displays the magnitude of the measured voltages (true RMS value). It
takes in account the CTm connection (see the previous table) and CTm ratio
(CONFIGURATION / Transfo ratio).
MiCOM P127 displays the magnitude of fundamental voltage, and the magnitude of the
voltages up to the 10th harmonics.
10.2.3.1
VAmh
THD VAm = 100%
h=2
V1
Note the denominator V1 is the fundamental magnitude. For Individual Harmonic Distortion
there is no summation, only one component is used in the numerator.
10.2.4
Powers
The MiCOM P127 displays:
the measured total apparent power (product of the per-element Volts and Amps):
P12y/EN AP/Fa5
Application Guide
Page 92/96
See 10.2.6 to see the convention for the positive (+) or negative () sign.
10.2.5
Energies
Separate values are maintained for both positive and negative Watt-hours (export and import
powers) and positive and negative VAR-hours (Lagging and leading VARs. These energy
quantities are calculated every minute from the Total Watts and Total VARs.
See 10.2.6 to see the convention for the positive (+) or negative () sign.
10.2.6
LOAD
Metering point
ACTIVE POWER: P is positive when the power is from the source to the load
REACTIVE POWER: Q is positive when the load is inductive.
Im (+)
Quadrant 1
Quadrant 2
Re ()
Re (+)
Quadrant 3
Quadrant 4
Im ()
P3976ENa
with:
Quadrant 1
Quadrant 2
Quadrant 3
Quadrant 4
Active (P)
Reactive (Q)
Export Wh (Ea+)
Import Wh(Ea)
Power
Energy
Application Guide
P12y/EN AP/Fa5
11.
11.1
Logic Inputs
Page 93/96
In the logic input submenu can be set the digital inputs as active high or active low, can be
chosen the supply type DC or AC and it is possible to set the start/stop of the relevant
auxiliary timers assigned to the inputs by front or edge.
By the ordering code it is possible to select the relay with the digital inputs with EA approval
regulation.
See the technical data for further information.
The setting menu for this functionality is in the CONFIGURATION menu. For more details
see FT (User Guide).
In modern protective schemes it is often desirable to synchronize the relays real time clock
so that events from different relays can be placed in chronological order.
This can be done using the communication interface connected to the substation control
system or via an opto-input.
Any of the available opto-inputs on the P12x relay can be selected for synchronization.
Pulsing this input will result in the real time clock snapping to the nearest minute. The
recommended pulse duration is 20ms to be repeated no more than once per minute. An
example of the time synchronization function is shown.
Time of Sync. Pulse
Corrected Time
19:47:00.000 to 19:47:29.999
19:47:00.000
19:47:30.000 to 19:47:59.999
19:48:00.000
NOTE:
A single digital input can be used for several internal functions or assigned directly to any
output contact
11.2
Logic Outputs
A dedicated output relay is assigned to each logic output. It is possible to set the relays as
self reset or latching.
The two first output contacts (RL1 & RL2) can be used as failsafe relays to provide a fail
safe alarm in case of power supply loss or major hardware failure. Other available relays
can be inverted to reverse NO relays operating condition (output relays closing when logical
state of the signal changes from 1 to 0).
FAIL
SAFE RE.
87654321
00100010
RL3, 4, 5, 7 & 8: NO
RL6: Inverted (NO but output relays closed when logical state of the signal is going
down)
The setting menu for the functionality of the logic outputs is available in the AUTOMAT.
CTRL menu.
It is possible to assign a specific function to each output relay except RL1.
For more details see the chapter User Guide.
P12y/EN AP/Fa5
Application Guide
Page 94/96
12.
MAINTENANCE MODE
This menu allows the user to verify the operation of the protection functions without sending
any external order (Tripping or signalling).
The selection of the maintenance mode is possible by logic input, control command (rear or
front port), or by front display. The end of maintenance mode is done by logic input, by
control command or on the front display time out ( 5minutes) and by turning off the power
supply.
Maintenance Mode
YES
When activating this menu (YES), the Alarm led will start flashing and an alarm message will
appear MAINTENANCE MODE. In this case, all output contacts are blocked, no operation
will take place on these contacts even if a protection threshold associated to one of these
output contacts is exceeded.
(If protection threshold is exceeded, all the associated leds will become ON, even the TRIP
LED, if the threshold is associated to the RL1).
RELAYS
CMD
8765W4321
000000000
This window allows the user to verify the external wiring to the relay output contacts, to do
this, it is sufficient to assign a 1 to any of the output contacts, this will close the contact and
the wiring continuity could be verified.
Application Guide
P12y/EN AP/Fa5
13.
Page 95/96
CT REQUIREMENTS
The CT requirements for the MiCOM P12y relays are given below.
The current transformer requirements are based on a maximum prospective fault current of
50 times the relay rated current (In) and the relay having an instantaneous setting of 25
times rated current (In). The current transformer requirements are designed to provide
operation of all protection elements.
Where the criteria for a specific application are in excess of those detailed above, or the
actual lead resistance exceeds the limiting value quoted, the CT requirements may need to
be increased according to the formulae in the following sections.
13.1
Limiting lead
resistance
1A
2.5VA
10P
20
1.3 ohms
5A
7.5VA
10P
20
0.11 ohms
VK
Instantaneous element:
VK
Note that, in addition, it should be ensured that the phase error of the applied core balance
current transformer is less than 90 minutes at 10% of rated current and less than 150
minutes at 1% of rated current.
P12y/EN AP/Fa5
Page 96/96
Application Guide
MiCOM P125/P126 & P127
=
=
=
=
Icp
Isn
Isp
RCT
RL
Rrp
Rrn
=
=
=
=
=
=
Communications
P12y/EN CT/Fa5
MODBUS &
IEC 60870-5-103 &
DNP 3.0
DATABASE
MiCOM P125-P126P127 V15
Communications
P12y/EN CT/Fa5
Page 2
BLANK PAGE
Communications
P12y/EN CT/Fa5
Page 1/130
MODBUS DATABASE
MiCOM P125-P127 V15
P12y/EN CT/Fa5
Communications
Page 2/130
BLANK PAGE
Communications
MiCOM P125/P126 & P127
P12y/EN CT/Fa5
MODBUS DATABASE
Page 3/130
CONTENT
1.
INTRODUCTION
1.1
1.2
Glossary
2.
MODBUS protocol
2.1
2.1.1
2.1.2
2.1.3
2.1.4
Address
2.2
2.3
2.3.1
2.3.2
2.3.3
3.
DATABASE ORGANISATION
10
3.1
11
3.1.1
11
3.1.2
15
3.2
17
3.2.1
17
3.2.2
21
3.3
25
3.3.1
25
3.3.2
31
3.3.3
31
3.3.4
31
3.3.5
31
3.3.6
31
3.3.7
32
3.3.8
32
3.3.9
32
3.3.10
32
3.3.11
32
3.4
Boolean equations
33
3.4.1
33
P12y/EN CT/Fa5
MODBUS DATABASE
Page 4/130
Communications
MiCOM P125-P126-P127
3.5
38
3.5.1
38
3.5.2
38
3.5.3
38
3.6
Disturbance records
39
3.6.1
39
3.6.2
43
3.6.3
44
3.6.4
46
3.7
Events records
47
3.7.1
47
3.7.2
52
3.8
Fault records
53
3.8.1
53
3.8.2
55
3.9
Error counters
56
3.9.1
56
4.
57
4.1
83
4.1.1
83
4.1.2
83
4.1.3
Service requests
83
4.1.4
83
4.1.5
83
4.1.6
84
4.1.7
84
4.1.8
84
Communications
MiCOM P125/P126 & P127
1.
INTRODUCTION
1.1
P12y/EN CT/Fa5
MODBUS DATABASE
Page 5/130
This document describes the characteristics of the different communication protocols of MiCOM
P127, P126 and P125 relays (named P12y in this document).
The available communication protocols on the relay are listed below:
1.2
MODBUS
IEC 60870-5-103
DNP3
Glossary
Ie
Ue
Pe
IeCosPhi
MWh+
MWh-
MVARh+
MVARh-
MVAh
: apparent energy
pf
PF
Dec
Hex
P12y/EN CT/Fa5
MODBUS DATABASE
Page 6/130
2.
Communications
MiCOM P125-P126-P127
MODBUS PROTOCOL
MiCOM P12y relay can communicate by a RS 485 link. The terminals are placed on the rear panel
(terminals 31 and 32). See the GS document for further information on the wiring. The applied
ModBus protocol is compliance with the MODBUS RTU.
2.1
2.1.1
Communication speed can be configured by an operator dialog in the front panel of the relay:
Baud rate (dec)
300
600
1200
2400
4800
9600
19200
38400
Transmission mode of the configured characters by operator dialog
Mode
1 start / 8 bits / 1 stop: total 10 bits
1 start / 8 bits / even parity / 1 stop: total 11 bits
1 start / 8 bits / odd parity / 1 stop: total 11 bits
1 start / 8 bits / 2 stop: total 11 bits
2.1.2
2.1.3
The validation of a frame is performed with a 16-bit cyclical redundancy check (CRC).
The generator polynomial is:
Address
In order to integrate a protection device into a control and monitoring system, the address must be
set from the local control panel. The address may be selected from the range of 1 to 255. The
address 0 is reserved for broadcast messages.
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 7/130
Protection device data may be read or modified by using function codes. Following are the
available function codes. Function codes to read from or write into parameter cells in the
protection device are described in the listed following table.
Function Nr.
2.3
Data Read
Data Write
N bits
N bits
N words
N words
1 bit
1 word
Fast
8 bits
Diagnostics counter
11
Event counter
15
N bits
16
N words
2.3.1
Function code
1 byte
1 byte
0 to FFh
1 to 10h
Information
n bytes
CRC16
2 bytes
Slave address:
The slave address is in the range from 1 to 255. A transmitted frame with a slave address equal to
0 is a globally addressed to all installed equipment (broadcast frame)
Function code:
The function code returned from the slave in the exception response frame is the code in which the
most significant bit (bit 7) is forced to 1.
Error code:
Among the 8 exception codes of the MODBUS protocol, the protection device manages two:
Code 03: A value from the data field is unauthorised (incorrect code).
P12y/EN CT/Fa5
MODBUS DATABASE
Page 8/130
Communications
MiCOM P125-P126-P127
CRC16:
The slave calculates the CRC16 value.
NOTE:
2.3.2
The slave device does not respond to globally broadcast frames sent out
from the master.
Function code
1 byte
1 byte
1 to FFh
1 to 10h
Data
n bytes
CRC16
2 bytes
Slave address:
The slave address is in the range from 1 to 255.
Function code:
Processed MODBUS function (1 to 16).
Data:
Contains reply data to master query.
CRC 16:
CRC16 value calculated by the slave.
2.3.3
If the CRC is incorrect, the frame is discarded as invalid. The slave does not reply to the
request for data. The master must retransmit its request for data. With the exception of a
broadcast message, this is the only case where the slave does not reply to a request for data
from the master.
If the CRC is correct but the slave can not process the request for data, it sends an exception
response to the master.
Function code
1 byte
81h or 83h or 8Ah or 8Bh
Error code
1 byte
CRC16
2 bytes
pf ... PF
Slave number:
The address range of the slave device is between 1 and 255.
Function code:
The function code returned by the relay in the warning frame is the code in which the most
significant bit (bit 7) is forced to 1.
Communications
MiCOM P125/P126 & P127
P12y/EN CT/Fa5
MODBUS DATABASE
Page 9/130
Warning code:
On the 8 warning codes of the MODBUS protocol, the relay manages two of them:
P12y/EN CT/Fa5
MODBUS DATABASE
Page 10/130
3.
Communications
MiCOM P125-P126-P127
DATABASE ORGANISATION
Application mapping are organised in pages. The characteristics are the following:
Page
Data type
Read
permission
Write
permission
Function Nr
0h
1h
1, 2, 3, 4, 5, 6,
15 and 16
2h (24h)
3, 4, 6 and 16
3h (26h)
3, 4, 6 and 16
4h
Remote controls
1, 2, 3, 4, 5, 6,
15 and 16
5h
3, 4, 6 and 16
6h
1, 2, 3, 4, 5, 6,
15 and 16
7h
Device status
Fast
8h
Time synchronisation
9h 22h
Disturbance records
3 and 4
23h
Measurements (part 2)
3, 4 and 5
28h
3, 4, 6 and 16
2Ah
3, 4, 6 and 16
2Ch
3, 4, 6 and 16
2Eh
3, 4, 6 and 16
30h
3, 4, 6 and 16
32h
3, 4, 6 and 16
35h
36h
Event records
3 and 4
37h
Fault records
3 and 4
38h
3Dh
Disturbance selection
3 and 4
3Eh
Fault records
3 and 4
5Ah
Error counters
3 and 4
3, 4 and 5
3, 4 and 5
X
3, 4 and 16
P12y/EN CT/Fa5
MODBUS DATABASE
Page 11/130
3.1.1
Address
(hex)
0000
0001
0002
0003
0004
0005
0006
0007
0008
0009
000A
000B
000C
000D
000E
000F
0010
0011
0012
0013
0014
0015
0016
0017
0018
0019
001A-001F
0020
0021
0022
0023
0024
0025
0026
0027
0028
0029
002A
Group
Product
Information
Description
Values
range
Step
Unit
Format
32 - 127
F10
32 -127
F10
32 -127
32 - 127
32 - 127
100 xxx
1
1
1
0-3
0 - 256
0 -1
0-1
P1
F10
20
F10
F10
F21
AL
ST
121
F41
F1
F1
F1
F1
F95
F62
F20A
F24
F45
F12
F20
F22
F17
F17
F17
F13
0-5
Def.
value
P125
P126
P127
Communications
F16
F16
F16
F37
F17
F38A
F38
F36
F31
F61
F43
F36A
F36B
P12y/EN CT/Fa5
MODBUS DATABASE
Page 12/130
Group
002B
Alarms 4
002C
Alarms 5
002D
Alarms 6
002E
Relays
002F
00300031
00320033
00340035
00360037
00380039
003A003B
003C
003D
003E
003F0040
00410042
00430044
00450046
00470048
0049004A
004B004C
004D
Accessory
functions
Remote
measurements
Alarms 7
004E
004F
0050
0051
0052
0053
0054
0055
0056
0057
0058
0059
005A
005B
005C
005D
005E
005F
0060
00610062
Recloser 79
Energy
measures
MiCOM P125-P126-P127
Unit
Format
F36C
Def.
value
F38B
F36D
F36E
F27
10mA
F18
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
10mA
10mA
10mA
10mA
10mA
%
%
10mHz
10mA
10mA
10mA
10mA
10mA
10mA
10mA
F18
F18
F18
F18
F18
F1
F1
F1
F18
F18
F18
F18
F18
F18
F18
00650066
00670068
006B006C
Step
00630064
0069006A
Values
range
Description
P125
P126
P127
Address
(hex)
Communications
0 - 999
0 - 999
45006500
F36F
F1
F1
F1
F1
F1
F1
Deg
F1
0-359
0-359
0-359
Deg
Deg
Deg
F1
F1
F1
Deg
F1
0-999
0-999
0-999
0-999
0-999
0-999
0-999
from 1 to
4.200 x 109
from 1 to
4.200 x 109
from 1 to
4.200 x 109
from 1 to
4.200 x 109
F1
F1
F1
F1
F1
F1
F1
F1
F1
1
1
1
1
1
1
1
kWh
F18A
kWh
F18A
kVARh
F18A
kVARh
F18A
10mA
F18
10mA
F18
P12y/EN CT/Fa5
MODBUS DATABASE
Page 13/130
Group
Description
Values
range
Step
Unit
Format
0074
0-359
Deg
F1
0075
0-359
Deg
F1
006D006E
006F
Alarms 8
0070
Protection 27
0071
0072
Protection 32n
0073
0076
Protection 59
0077
00780079
007A
Protection 59n
007B
Protection 67n
007C
Protection 46
007D
007E
007F
00800081
00820083
00840085
00860087
0088
0089
008A
008B
008C
008D
008E
008F
00900092
00920093
00940095
00960097
00980099
009A009B
009C009D
Boolean
equations
Voltage
measurement
Power
measures
F17
F17
F16
F16
F17
F17
F16
F16
F17
F17
F17
F48
10mV
F18A
1
1
1
10mV
10mV
10mV
1
1
1
1
1
1
Deg
Deg
Deg
Deg
10mV
10mV
10mV
10mV
10mV
10mV
F18A
F18A
F18A
F1
F1
F1
F1
F1
F1
F1
F1
F18
F18
F18
F18
F18
F18
CAN
F18A
10Watt
F18
10VAR
F18
0.01
F2
10mA
F18A
10mA
F18A
10mA
F18A
0-359
0-359
0-359
0-359
Module Pe
00A000A1
00A2
3-Phase CosPHI
Rolling demand average RMS IA
value
Rolling demand average RMS IB
value
Rolling demand average RMS IC
value
00A700A8
F18
F36G
00A500A6
10mA
009E009F
00A300A4
Def.
value
P125
P126
P127
Communications
-999.9 10
to 999.9 106
6
-999.9 10
to 999.9 106
-100 to 100
P12y/EN CT/Fa5
MODBUS DATABASE
Page 14/130
00A900AA
Group
Power
measures
00AB-00AC
00AD-00AE
00AF
00B0
00B1
00B2
00B3
00B4
00B5
00B6
00B7
00B8
00B9
00BA
00BB
00BC
Description
Energy
measures
Measurement
00BD
00BE
00BF
00C0
Measurements
00C1
00C200C3
00C4
Protection 67n
00C5
00C6
00C7
00C8
00C9
00CA00DF
Measurements
00E000EF
HMI screen
CT Mease.
Protection 47
Values
range
Step
Unit
Module IeCos
3-Phase Apparent power (S)
IRIG-B Synchronisation
(Option)
Optional board
Inputs
Status
00F000FF
MiCOM P125-P126-P127
Apparent energy
3Ph V A Hours
Module VA
Module VB
Module VC
Angle IA^VA
Angle IA^VB
Angle IA^VC
Inf. of the threshold status f1
Inf. of the threshold status f2
Inf. of the threshold status f3
Inf. of the threshold status f4
Inf. of the threshold status f5
Inf. of the threshold status f6
F out
Date-and-time synchronisation
origin
Functions available ( read only )
Digital inputs state, part 3
df/dt protection status
df/dt
Voltage of the reference channel
Not used
Information of the threshold
status Ie_d>>
Module Ie der
Angle IA^Ie der
CT Measurement presence
V2> status protection
V2>> status protection
Reserved
Copy of HMI screen
Reserved
Format
Def.
value
F18A
6
-999.9 10
to 999.9 106
from 1 to
4.200 x 109
0-359
0-359
0-359
0 to 7
0 to 7
0 to 7
0 to 7
0 to 7
0 to 7
0 to 3
0 to 4
1
1
1
1
1
1
1
1
0 to 63
-20 000 to 20
000
ASCII code
kVAh
Deg
Deg
Deg
0 to 3
0 to 1
10VA
1
1
1
Deg
F18
F18A
F1
F1
F1
F1
F1
F1
F67
F67
F67
F67
F67
F67
F69
F79
F80
F20B
F94
mHz/s
P125
P126
P127
Address
(hex)
Communications
F2
F1
F16
F1
F1
F24
F16
F16
16 x
F10
0
0
0
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 15/130
Address
(hex)
2300-2301
2302
2303
2304
2305
2306
2307
2308
2309
230A
230B
230C2319
231A
231B
231C231D
231E
231F
2320-2321
2322
2323
2324
2325
2326
2327
2328
2329
232A
232B
232C2339
233A
IB measurement
233B
233C233D
233E
233F
2340-2341
2342
2343
2344
2345
2346
2347
2348
2349
234A
234B
234C2359
235A
IC measurement
235B
235C235D
235E
235F
2360-2361
2362
2363
2364
2365
2366
2367
2368
VA or UAB
Description
Values
range
Step
Unit
Format
A
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F88
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
0.01%
360
/65536
A
F1
F88
0.01%
A
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F1
F88
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
0.01%
360
/65536
A
F1
F1
F88
F1
Fondamental
THD
Harmonic 2
Harmonic 3
Harmonic 4
Harmonic 5
Harmonic 6
Harmonic 7
Harmonic 8
Harmonic 9
Harmonic 10
Reserve
TDD
Angle Iam^Iam ( always 0 )
Float 32bits
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
1
1
1
1
1
1
1
1
1
1
0-65534
0-65534
RMS
Reserved
K factor
Fondamental
THD
Harmonic 2
Harmonic 3
Harmonic 4
Harmonic 5
Harmonic 6
Harmonic 7
Harmonic 8
Harmonic 9
Harmonic 10
Reserve
TDD
Angle Ibm^Iam
Float 32bits
RMS
Reserved
K factor
Fondamental
THD
Harmonic 2
Harmonic 3
Harmonic 4
Harmonic 5
Harmonic 6
Harmonic 7
Harmonic 8
Harmonic 9
Harmonic 10
Reserve
TDD
Angle Icm^Iam
RMS
Reserved
K factor
Fondamental
THD
Harmonic 2
Harmonic 3
Harmonic 4
Harmonic 5
Harmonic 6
Harmonic 7
0-65534
Float 32bits
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
0-65534
0-65534
1
1
1
1
1
1
1
1
1
1
Float 32bits
F1
0-65534
Float 32bits
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
0.01%
1
1
1
1
1
1
1
1
1
1
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0-65534
0-65534
0.01%
360
/65536
A
F1
F88
0.01%
V
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F1
F88
F1
F1
F1
F1
F1
F1
F1
Float 32bits
0-65534
Float 32bits
10000
10000
10000
10000
10000
10000
10000
1
1
1
1
1
1
1
1
F1
F88
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
Def.
value
P125
P126
P127
3.1.2
P12y/EN CT/Fa5
MODBUS DATABASE
Page 16/130
Group
2369
236A
236B
236C2379
237A
Description
VB or UBC
Values
range
Step
Unit
Format
0.01%
0.01%
0.01%
F1
F1
F1
F1
Harmonic 8
Harmonic 9
Harmonic 10
Reserve
10000
10000
10000
1
1
1
0-65534
0-65534
237B
237C237D
237E
237F
2380-2381
2382
2383
2384
2385
2386
2387
2388
2389
238A
238B
238C2399
MiCOM P125-P126-P127
RMS
Reserved
K factor
Fondamental
THD
Harmonic 2
Harmonic 3
Harmonic 4
Harmonic 5
Harmonic 6
Harmonic 7
Harmonic 8
Harmonic 9
Harmonic 10
Reserve
Float 32bits
0-65534
Float 32bits
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
1
1
1
1
1
1
1
1
1
1
1
239A
0-65534
239B
0-65534
RMS
Reserved
K factor
Fondamental
Harmonic distortion percentage
Harmonic 2
Harmonic 3
Harmonic 4
Harmonic 5
Harmonic 6
Harmonic 7
Harmonic 8
Harmonic 9
Harmonic 10
Reserve
Float 32bits
239C239D
239E
239F
23A0-23A1
23A2
23A3
23A4
23A5
23A6
23A7
23A8
23A9
23AA
23AB
23AC23B9
VC or UCA
0-65534
Float 32bits
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
1
1
1
1
1
1
1
1
1
1
1
23BB
0-65534
RMS
Reserved
K factor
Float 32bits
0-65534
Active Power
Reactive Power
Apparent power
Displacement power factor
Reserve
Positive active energy
Negative active energy
Positive reactive energy
Negative reactive energy
23C2-23C3
23C4-23C5
23C6
23C7
23C8-23C9
23CA-23CB
23CC-23CD
23CE-23CF
23D0-23D3
23D4-23FF
Reserved
F88
0.01%
V
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F1
F88
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
360
/65536
360
/65536
V
0.01%
V
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
0.01%
F1
F88
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
Float 32bits
Float 32bits
100 to 100
10000
Float 32 bits
Float 32 bits
Float 32 bits
Float 32 bits
Private
format date
23C0-23C1
Float 32bits
0-65534
Power &
Energie
F1
0.01%
23BC23BD
23BE
23BF
360
/65536
360
/65536
V
360
/65536
360
/65536
V
23BA
1
1
Def.
value
P125
P126
P127
Address
(hex)
Communications
F1
F1
F88
F1
F1
F88
F1
F88
VAR
VA
0.01
0.01%
Wh
Wh
VAR h
VAR h
F88
F88
F2
F1
F88
F88
F88
F88
F97
P12y/EN CT/Fa5
MODBUS DATABASE
Page 17/130
3.2.1
Address
(hex)
0100
0101
0102
0103
0104
0105
01060108
0109
010A
Group
Remote setting
OP Parameters
General
Options
010B
010C
010D
010E
010F
0110
0111
01120113
CB monitoring
measurements
01140115
01160117
0118
0119
011A
011B
011C
011D
011E
011F
0120
0121
0122
0123
01240125
0126
0127
0128 0129
012A
012B
012C
012D
Digital input
Ratios CT
Ratios VT
Primary phase
VT
Secondary
phase VT
Scheme VTs
connection
Primary earth VT
Secondary earth
VT
Description
Address of front port:
MODBUS
Language
Password, ASCII digits 1 and 2
Password, ASCII digits 3 and 4
Rated frequency
Phase and Earth labels
Free (not used)
Default display
User reference, ASCII digits 1
and 2
User reference, ASCII digits 3
and 4
Number of the default records to
be displayed
Inputs mode configuration (edge
or level), part 2,
Maintenance Mode
Digital inputs signal type: AC
DC
CB operations number
CB operating time
Switched square Amps phase A
summation
Switched square Amps phase B
summation
Switched square Amps phase C
summation
Circuit breaker closing time
Digital input 1, part 2
Digital input 2, part 2
Digital input 3, part 2
Digital input 4, part 2
Digital input 5, part 2
Digital input 6, part 2
Digital input 7, part 2
Primary phase CT
Secondary phase CT
Primary earth CT
Secondary earth CT
57 - 130V operating range
220 - 480V operating range
57 - 130V operating range
220 - 480V operating range
VTs connection mode:
3Vpn, 2Vpp+Vr, 2Vpn+Vr
57 - 130V operating range
220 - 480V operating range
57 - 130V operating range
220 - 480V operating range
Maintenance mode relays
command
Obsolete
Number Instantaneous record to
be displayed
Values
range
Step
Unit
Format
Def.
value
P125
P126
P127
Communications
1 - 255
0 14
32 127
32 127
50 60
0-12
F1
1
1
10
1
F63
F10
F10
F1
F85
AA
AA
50
0
04
32 - 127
1
1
F26
F10
4
AL
32 - 127
F10
ST
1- 25
F31A
25
F54A
1
1
F24
F51
F1
10ms
An
F1
F18
An
F18
An
F18
0-1
0-1
1 - 9999
1 or 5
1 - 9999
1 or 5
1
1
1
1
1
1
1
1
1
1
Hz
10ms
A
A
A
A
F1
F15A
F15A
F15A
F15A
F15A
F15A
F15A
F1
F1
F1
F1
0
1
1
1
1
1
10 100000
220 480
570 -1300
2200
0, 2, 4
1
1
1
1
10V
V
100mV
100mV
F18A
F18A
F1
F1
F7
100V
220V
100V
220V
0
10 -100000
220 480
570 -1300
2200
1
1
1
1
10V
V
100mV
100mV
F18A
F18A
F1
F1
F13
100V
220V
100V
220V
1- 5
F31B
P12y/EN CT/Fa5
MODBUS DATABASE
Page 18/130
012E
Group
Communication
012F
0130
0131
0132
0133
0134
0135
0136
0137
0138
0139
013A
013B
013C
013D
013E
013F
0140
0141
0142
0143
Configuration
group
LED
Digital inputs
configuration
0144
0145
0146
0147
0148
0149
014A
014B
014C
014D
014E
Digital input
014F
Protection 49
Output relays
Protection 37
Alarm
0150
0151
Circuit breaker
0152
0153
0154
0155
0156
0157
0158
0159
015A
015B
015C
015D
Output Relays
015E
015F
Protection 67
MiCOM P125-P126-P127
Description
Values
range
0-1
0-5
0-1
0-7
0-2
1- 59999 / 1255
0-1
0 - 15
1-8
1-2
0-1
0-1
0-1
Step
Unit
Format
Def.
value
P125
P126
P127
Address
(hex)
Communications
0
0
0
0
0
0
0
0
0
0
0
0
F47
1
1
1
1
1
1
1
1
1
1
1
F15
F15
F15
F15
F15
F15
F15
F14
F14
F14
F24
0
0
0
0
0
0
0
0
0
0
0
F14
F14
F14A
1
1
1
F14
F14
F14
0
0
0
F14
1
1
1
1
1
1
1
1
F56
F24
F24
F14
F14
F14
F27
F14
0
0
0
0
0
0
0
0
1
1
F14
F14
0
0
F53
1
1
1
1
F52
F4
F5
F1
1
4
0
6
0
1
1
1
1
F29
F30
F55
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
F19
F19
F19
F19
F19A
F19A
F19A
F19A
F19B
F19B
F19B
F19B
F54
P12y/EN CT/Fa5
MODBUS DATABASE
Page 19/130
Group
Protection 67n
Protection 67
Protection 67n
Recloser 79
016C
Tripping
016D
016E
016F
0170
Breaker Failure
Blocking Logic
0171
0172
0173
0174
0175
0176
0177
0178
0179
017A
017B
017C
017D
Broken
Conductor
Cold Load PU
Breaker failure
Selectivity
Disturbance
017E
017F
0180
0181
0182
0183
CB monitoring
0184
0185
0186
0187
0188
0189
018A
018B
018C
018D
018E
018F
0190
0191
0192
0193
0194
Blocking logic
Tripping
Description
Output relays: tI>>>
Output relays: tIe>
Output relays: tIe>>
Output relays: tIe>>>
Output relays: I>
Output relays: I>>
Output relays: I>>>
Output relays: Ie>
Output relays: Ie>>
Output relays: Ie>>>
Output relays: recloser running
Output relays: definitive tripping
& Recloser int. locked (conf.)
Conf. tripping on relay RL1,
part 1
Current Threshold
Blocking logic 1, part 1
Blocking logic 2, part 1
Brkn. Cond. operating mode
Brkn. Cond. trip delay time
Brkn. Cond. limit
Operating mode
Cold load start thresholds
Percentage of desensitization
Desensitising timer
Breaker Failure operating mode
Breaker failure delay time
Digital selectivity 1
Digital selectivity 2
tSel1
tSel2
Pre-trigger time
Values
range
2 -100
0-1
0 - 14400
20 - 100
0-1
20 - 800
1 - 36000
0-1
0 - 1000
0 - 15000
0 - 15000
5 rec: 1 to 29
4 rec: 1 to 29
3 rec: 1 to 49
2 rec: 1 to 69
1 rec: 1 to 89
Unit
Step
Format
Def.
value
1
1
1
1
1
1
1
1
1
1
1
1
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14D
0
0
0
0
0
0
0
0
0
0
0
0
F6
P125
P126
P127
Communications
1
1
1
1
1/100 In
F1
F8
F8
F24
2
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
F1
F1
F24
F33
F1
F1
F24
F1
F40
F40
F1
F1
F1
1
100
0
0
100
1
0
0
0
0
0
0
1
F32
F24
F1
F24
F1
0
0
5
0
0
10E6 An
F24
F1
10ms
10ms
10ms
mn
F1
F1
F1
F1
F42
1
5
0
0
5
F1
F1
F24
F24
F1
F8A
F8A
F6A
10
10
0
0
F1
F1
0
0
0-1
0-1
5 - 100
0-1
0 - 50000
1
1
5
1
1
0-1
1-2
5 - 100
0 - 20000
0 - 20000
5 10 15
30 - 60
10 - 500
10 - 500
0-1
0-1
10 - 1000
1
5
1
1
VT
A
1
1
1
1
1
1
1
1
0 - 20000
0 - 20000
1
1
%
100ms
10ms
10ms
10ms
100ms
10ms
10ms
10ms
10ms
10ms
10ms
0
0
0
P12y/EN CT/Fa5
MODBUS DATABASE
Page 20/130
0195-019C
019D
019E
019F
01A0
01A1
01A2
01A3
01A4
01A5
01A6
01A7
01A8
01A9
01AA
01AB
01AC
01AD
01AE
01AF
01B0
01B1
01B2
01B3
01B4
01B5
01B6
01B7-01DE
01DF
01E0
01E1
01E2
01E3
01E4
01E5
01E6
01E7
01E8
01E9
01EA
01EB
01EC
01ED
01EE
01EF
01F0
01F1
01F2
01F3
01F4
01F5
01F6
Group
Protection 67n
Protection 32n
Protection 59
Protection 59N
Protection 67
Protection 27
Protection 46
Boolean
Equations
LED
01F7
01F8
01F9
01FA
01FB
51V function
V2> value
MiCOM P125-P126-P127
Description
Values
range
Step
Unit
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Format
Def.
value
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
P125
P126
P127
Address
(hex)
Communications
0 - 60000
10ms
F1
0 - 60000
10ms
0 - 60000
0 - 60000
1
1
10ms
10ms
0 - 60000
0 - 60000
1
1
10ms
10ms
0 - 60000
0 - 60000
1
1
10ms
10ms
1
1
F1
F14
F1
F1
F14
F1
F1
F14
F1
F1
F14
F14B
F14C
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
F14
F14
F19C
F19C
F19C
F19C
0
0
0
0
F24
F1
1
1
F1
100mV
F1
1
100
0
130
0
480
0
100mV
F58
F1
F59
F1
0-1
1 - 60
1
1
1 24
0 32771
0 500
03
30 -2000
1
1
1
1
200 -7200
mn
ms
P12y/EN CT/Fa5
MODBUS DATABASE
Page 21/130
Description
Values
range
Step
Unit
Format
01FD
01FE
VTS function
VTS configuration
VTS conv. directional to non-dir.
07
0-FFFFh
1
1
01FF
U< blocking
frequency
protection
50 -1300
100mV
F1
130
0
480
0
0
FFF
h
50
200 - 4800
100mV
F1
200
3.2.2
V2>> value
0601
0602
0603
0604
0605
0606-060B
060C
060D
060E
060F
0610
0611
0612
0613
0614
0615
0616
0617
0618
0619
061A
061B
061C
061D
061E
061F
0620
0621
0622
0623
0624
0625
0626
0627
0628
0629
062A
062B
062C
062D
062E
Group
Configuration
Disturbance
Cold Load PU
LED
Output relays
Tripping
062F
0630
0631
30 -2000
100mV
F1
200 -7200
100mV
F1
F60
F65
Address
(hex)
0600
Def.
value
Automation
Description
Values
range
Step
Unit
Format
F64
Def.
value
P125
P126
P127
01FC
Group
P125
P126
P127
Communications
0-1
F66
15
03
1
1
F1
F87
1FF
C
0
FF
0
5
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
F19D
F19D
F19D
F19D
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F6C
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
F6D
F24
F83
0
0
0-1
F64A
F64B
P12y/EN CT/Fa5
MODBUS DATABASE
Page 22/130
0632
0633
0634
0635
0636
0637
0638-063F
0640
0641
0642
0643
0644
0645
0646
0647
0648
0649
064A
064B
064C-064D
064E-064F
0650-0641
0652
0653
0654
0655
0656
0657
0658
0659
065A
065B
065C
065D
065E
065F
0660
0661
0662
0663
Group
Tripping
Boolean Equations
LED
Communication
port 2 (Option)
0664
0665
0666
0667
IEC870-5-103
port 1
0668
0669
066A
066B
066C
066D
IEC870-5-103
IEC870-5-103 port
2
MiCOM P125-P126-P127
Description
Inrush harmonic 2 ratio
tInrush_reset
Blocking logic 1, part 3
Blocking logic 2, part 3
Conf. tripping on relay RL1,
part 3
VTS delay time
Reserved
Tripping equation E time
Reset equation E time
Output relays: tEqu. E
Tripping equation F time
Time reset equation F time
Output relays: tEqu. F
Tripping equation G time
Reset equation G time
Output relays: tEqu. G
Tripping equation H time
Reset equation H time
Output relays: tEqu. H
Auxiliary timer 5
Auxiliary timer 6
Auxiliary timer 7
Reserved
Auxiliary timer 8 (Option)
Auxiliary timer 9 (Option)
Auxiliary timer A (Option)
Auxiliary timer B (Option)
Auxiliary timer C (Option)
Led 5, part 6
Led 6, part 6
Led 7, part 6
Led 8, part 6
Led 5, part 7
Led 6, part 7
Led 7, part 7
Led 8, part 7
Communication speed (Baud)
Parity
Stop bits
Address of rear port 2:
MODBUS
IEC 60870-5-103
DNP3
IEC870-5-103 only: source
setting group for copy
IEC870-5-103 only: destination
setting group for copy
IEC870-5-103 only:
Spontaneous event enabling
IEC870-5-103:
Measurements enabling
IEC870-5-103 Measurements/
Commands Blocking
IEC870-5-103 GI selection port 1
IEC870-5-103 command &
setting write timeout
IEC870-5-103 only, port 2:
Spontaneous event enabling
IEC870-5-103, port 2:
Measurements enabling
IEC870-5-103, port 2:
Measurements/ Commands
Blocking
Values
range
100-350
0 - 200
Step
Unit
1
10
1
1
1
0.1%
10ms
0 10000
0 - 60000
0 - 60000
Format
Def.
value
P125
P126
P127
Address
(hex)
Communications
F1
F1
F8B
F8B
F6B
200
0
0
0
0
10ms
F1
20
1
1
10ms
10ms
0 - 60000
0 - 60000
1
1
10ms
10ms
0 - 60000
0 - 60000
1
1
10ms
10ms
0 - 60000
0 - 60000
1
1
10ms
10ms
0 2 000 000
0 2 000 000
0 2 000 000
1
1
1
10ms
10ms
10ms
F1
F1
F14
F1
F1
F14
F1
F1
F14
F1
F1
F14
F18A
F18A
F18A
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0 - 20000
0 - 20000
0 - 20000
0 - 20000
0 - 20000
1
1
1
1
1
1
1
1
1
1
1
1
1
1
10ms
10ms
10ms
10ms
10ms
F1
F1
F1
F1
F1
F19E
F19E
F19E
F19E
F19F
F19F
F19F
F19F
F4
0
0
0
0
0
0
0
0
0
0
0
0
0
6
1
1
1
F5
F29
F1
0
0
1
F55
1-8
F55
0-3
F74
0-7
F75
0-3
F78
0-1
1 - 300
1
1
F93
F1
0
2
0-3
F74
0-7
F75
0-3
F78
0-7
0-2
0-1
1 - 255
1 254
1 - 59999
1-8
100 ms
P12y/EN CT/Fa5
MODBUS DATABASE
Page 23/130
Group
066E
066F
0670
0671
0672
0673
0674
0675-0678
0679
067A
067B
067C
067D
067E-0681
0682
0683
0684
0685
0686
0687
0688
0689
068A
068B
068C
068D
068E
068F
0690
0691
0692
0693
0694
0695
0696
0697
0698
0699
069A
069B
069C
069D
069E
069F
06A0
06A1
06A2
06A3
06A4
06A5
06A6
06A7
06A8
06A9
06AA
06AB
06AC
06AD
Digital input
(Option)
Output relays
Digital inputs
Automation/SOTF
Connexion
LED
CTS supervision
Output relays
General Config
Description
IEC870-5-103, port 2: GI
selection
Reserved
Digital input 8, part 1
Values
range
0-1
Unit
Format
Def.
value
F93
F15
1
1
1
1
F15
F15
F15
F15
0
0
0
0
1
1
1
1
1
F15A
F15A
F15A
F15A
F15A
0
0
0
0
0
F76
F77
1
1
1
1
F14
F14
F14
F14
0
0
0
0
0 127
0-1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
1
1
0-1
20 - 100
10 - 90
8 - 100
1
1
1
1
F14
F14
F14
F14
F14
F14
F14
F14
F14
F15B
F15B
F15B
F15B
F15B
F15B
F15B
F15B
F15B
F15B
F15B
F15B
F82
F84
F19G
F19G
F19G
F19G
F24
F1
F1
F1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1B
0
0
0
0
0
0
20
50
8
5 - 220
20 - 880
0 10000
1
5
1
1
1
1
1
F1
F1
F1
F14
F1
F1
F24
50
200
20
0
5
4
0
Step
P125
P126
P127
Communications
1 200
1 12
0-1
%
%
1/100 In
0.1V
0.1V
0.01 s
P12y/EN CT/Fa5
MODBUS DATABASE
Page 24/130
Group
06AE
06AF
06B0
06B1
06B2
06B3
06B4
06B5
06B6
06B7
06B8
06B9
06BA
06BB
06BC
Blocking Logic
06BD
Group changing
MiCOM P125-P126-P127
Description
Blocking logic 1, part 4
Blocking logic 2, part 4
Output relays: df/dt1
Output relays: df/dt2
Output relays: df/dt3
Output relays: df/dt4
Output relays: df/dt5
Output relays: df/dt6
Primary CTm
Secondary CTm
CTm1 connection
CTm2 connection
Quadrant power
Not used
Inputs mode configuration
(edge or level), part 3,
Group number for digital input
inactive
Group number for digital input
active
Target group
Output relays: P<
Output relays: tP<
Output relays: P<<
Output relays: tP<<
Output relays: Q>
Output relays: tQ>
Output relays: Q>>
Output relays: tQ>>
Output relays: Q<
Output relays: tQ<
Output relays: Q<<
Output relays: tQ<<
Output relays: Comm. order 1
Output relays: Comm. order 2
Output relays: Comm. order 3
Output relays: Comm. order 4
T comm. Order 1
T comm. Order 2
T comm. Order 3
T comm. Order 4
Iam Td demand
06D5
06D6
Output relays
Ratios CTm
CTm connection
Power
06BE
06BF
06C0
06C1
06C2
06C3
06C4
06C5
06C6
06C7
06C8
06C9
06CA
06CB
06CC
06CD
06CE
06CF
06D0
06D1
06D2
06D3
06D4
06D7
06D8
06D9
06DA
06DB
06DC
06DD
06DE-06FF
Output relays
Td demand
Output relays
Values
range
Unit
Step
Def.
value
F8C
F8C
F14
F14
F14
F14
F14
F14
F1
F1
F90
F90
F91
0
0
0
0
0
0
0
0
1
1
0
0
4
F54B
1-8
F55
1-8
F55
0-8
10 60000
10 60000
10 60000
10 60000
0 20000
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
5
5
5
5
1
F55
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F14
F1
F1
F1
F1
F1
Ibm Td demand
0 20000
F96
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
10
10
10
10
100
00
0
Icm Td demand
0 20000
F96
F14
F14
F14
F14
F14
F14
F14
0
0
0
0
0
0
0
1 - 9999
1 or 5
0-3
0-3
14
1
1
1
1
1
1
1
1
1
Format
P125
P126
P127
Address
(hex)
Communications
1
1
1
1
1
1
1
1
1
1
A
A
10ms
10ms
10ms
10ms
1/100%
IN
1/100%
IN
1/100%
IN
2
2
2
2
2
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 25/130
3.3.1
Address
(hex)
0200
Group
Description
Values
range
Step
Unit
0-1-2
10 - 2500
1/100 In
0 - 15000
25 - 1500
100 -10000
1
1
5
10ms
0.001
0.001
0206
0207
0208
0209
020A
020B
020C
020D
I> value
Trip time type I>
DMT Trip time I>
TMS: I> trip time multiplier
K: I>trip time multiplier for RI
type curve
Reset time type: DMT / IDMT
DMT reset time I>
RTMS: I> reset time multiplier
Torque (RCA) angle I^U>
Trip angle I^U>
Interlock I>
I>> operating mode
I>> value
0-1
0 - 10000
25 - 3200
0 - 359
10 -170
0-1
01-2
1
1
1
1
1
10ms
0.001
Degree
Deg
1
1
1/100 In
020E
020F
0210
0211
0212
0213
0214
0215
0216
0201
0202
0203
0204
0205
0217
Protection
50/51/67
Protection
50n/51n/67n
Ie> value
0218
0219
021A
021B
021C
021D
021E
021F
0220
0221
0222
0223
0224
0225
Ue> value
Ie>> value
50 - 4000
10 - 4000
0 - 15000
0 - 359
10 - 170
0-1-2-3
Format
Def.
value
F24A
F1
F3
F1
F1
F1
100
0
0
25
100
F34
F1
F1
F1
F1
F24
F24A
F1
0
100
25
0
50
0
0
400
0
F1
F1
F1
F24A
F1
0
0
50
0
400
0
10ms
Degree
Degree
50 - 4000
10 - 4000
0 - 15000
0 - 359
10 - 170
0-1-2
1
1
1
1
1
1
1
1
1
10ms
Degree
Degree
F1
F1
F1
F24A
0
0
50
0
2 - 1000
F1
10 -1000
100
0
10
10- 2500
1/1000
Ien
1/1000
Ien
1/100
Ien
1/100 In
F1
F1
0 - 15000
25 - 1500
100 -10000
1
1
5
10ms
0.001
0.001
F3
F1
F1
F1
0-1
0 - 10000
25 - 3200
10 - 2600
40 - 7200
1
1
1
1
5
10ms
0.001
1/10 V
1/10 V
F34
F1
F1
F1
F1
0 - 359
10 - 170
0-1
0-1-2
2 - 1000
1
1
1
1
1
10 - 8000
50 - 4000
0 - 15000
Degree
Degree
1/1000
Ien
1/1000
Ien
1/100
Ien
10ms
P125
P126
P127
250
0
0
0
25
100
F1
100
25
10
720
0
0
50
0
0
100
0
800
0
100
F1
F1
F1
F24
F24A
F1
F1
P12y/EN CT/Fa5
MODBUS DATABASE
Page 26/130
0226
0227
0228
0229
022A
022B
022C
022D
022E
022F
0230
0231
0232
0233
0234
0235
0236
0237
0238
0239
023A
Group
Ue>> value
Ie>>> value
Ue>>> value
Protection 49
Protection 37
Protection 46
023B
023C
023D
023E
MiCOM P125-P126-P127
Description
Values
range
Step
10 - 2600
100mV
F1
40 - 9600
100mV
F1
0 - 359
10 -170
0-1-2-3
2 - 1000
1
1
1
1
Degree
Degree
10 - 8000
50 - 4000
0 -15000
10 - 2600
1
1
1/1000
Ien
1/1000
Ien
1/100
Ien
10ms
100mV
F1
F1
F24A
F1
40 - 9600
100mV
F1
0 - 359
10 - 170
0-1
50 - 200
10 - 320
100 - 150
1 - 200
0-1
50 - 200
0-1
10 - 100
0 - 15000
0-1
10 -2500
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Degree
Degree
1/100 In
F1
F1
F24
F1
F1
F1
F1
F24
F1
F24
F1
F1
F24
F1
10ms
0.001
1/1000
F3
F1
F1
F1
0 -15000
25 - 1500
100-10000
1
1
5
023F
0240
0241
0242
0243
0-1
4 - 10000
25 -3200
0-1
50 -4000
1
1
1
1
1
0244
0245
0246
0 - 15000
0-1
50 - 4000
1
1
1
0 - 15000
0-1-2
20 -1300
100 - 4800
0 - 60000
0-1-2
20 -1300
100 - 4800
0 - 60000
0 - 359
0-1
1
1
1
5
1
1
1
5
1
1
1
0-1
20 - 2000
1
2
100 - 8000
10
Protection 27
U< value
024A
024B
024C
U<< value
024D
024E
024F
0250
0251
Protection 32n
Pe> value
Format
0247
0248
0249
Unit
%
1/100
1/100 In
Mn
%
1/100 In
10ms
10ms
0.001
1/100 In
10ms
1/100 In
10ms
100mV
100mV
10ms
100mV
100mV
10ms
10mW.
Ien
10mW.
Ien
F1
F1
F1
F1
F34
F1
F1
F24
F1
F1
F24
F1
F1
F24B
F1
F1
F1
F24B
F1
F1
F1
F1
F24C
F24
F1
F1
Def.
value
260
0
960
0
0
10
0
100
0
800
0
100
0
260
0
960
0
0
10
0
90
10
105
1
0
100
0
10
0
0
250
0
0
0
25
100
0
4
25
0
400
0
0
0
400
0
0
0
50
200
0
0
50
200
0
0
0
0
200
0
800
0
P125
P126
P127
Address
(hex)
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 27/130
Group
0252
0253
0254
0255
0256
0257
0258
0259
025A
025B
025C
025D
Pe>> value
IeCos> value
025E
025F
0260
0261
0262
0263
0264
0265
0266
0267
0268
0269
026A
026B
026C
IeCos>> value
Protection 59
U> value
U>> value
Description
Values
range
Format
Step
Unit
100 - 16000
10
400 - 64000
50
10 - 800
10mW.
Ien
10mW.
Ien
W.Ien
F1
40 - 3200
W.Ien
F1
0 - 15000
25 - 1500
100 -10000
1
1
5
10ms
0.001
0.001
0-1
0 - 10000
25 - 3200
0 -1
20 - 2000
1
1
1
2
100 - 8000
10
100 - 16000
10
400 - 64000
50
10 - 800
10mW.
Ien
10mW.
Ien
10mW.
Ien
10mW.
Ien
W.Ien
40 - 3200
W.Ien
F1
0 - 15000
0 1
2 - 1000
1
1
1
10ms
F1
F24
F1
10- 8000
10 - 2500
0 -15000
25 - 1500
100 -10000
1
1
5
0-1
0 - 10000
25 - 3200
01
2 - 1000
1
1
1
1
10 - 8000
50 - 4000
0 - 15000
0-1-2
20 -2600
10ms
1/1000
1/1000
Ien
1/1000
Ien
1/100
Ien
10ms
0.001
0.001
10ms
0.001
F1
Def.
value
F3
F1
F1
F1
320
0
0
0
25
100
F34
F1
F1
F24
F1
4
25
0
200
0
800
0
160
00
640
00
800
F3
F1
F1
F1
320
0
0
0
100
0
800
0
250
0
0
0
25
100
F34
F1
F1
F24
F1
4
25
0
100
0
800
0
400
0
1
0
260
0
720
0
0
0
260
0
960
0
F1
F1
F1
F1
F1
F1
F1
1
1
1
1/1000
Ien
1/1000
Ien
1/100
Ien
10ms
100mV
F1
F24B
F1
100 -9600
100mV
F1
0 - 60000
0 1-2
20 - 2600
1
1
1
10ms
100mV
F1
F24B
F1
100 - 9600
100mV
F1
F1
F1
160
00
640
00
800
P125
P126
P127
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 28/130
026D
026E
026F
Group
MiCOM P125-P126-P127
Description
Values
range
Step
Unit
0 - 60000
0-1
10 - 2600
1
1
1
100mV
F1
F24
F1
50 - 9600
100mV
F1
0 - 60000
0-1
0-1
1 -.60000
0-1
0 - 2222
1
1
1
1
1
1
10ms
F1
F24
F24
F18A
F24
F57
0277
0 - 2222
0278
0279
027A027B
027C027D
027E027F
02800281
0282
0283
0284
0285
0286
0287
Dead time 1
Dead time 2
Dead time 3
Dead time 4
Reclaim time
Inhibit time
Recloser cycles for phase faults
Recloser cycles for earth faults
DMT Reset time Ie>>
DMT Reset time Ie>>>
DMT Reset time IeCos>>
DMT Reset time Pe>>
1 - 30000
1 - 30000
1 - 60000
1 - 60000
2 - 60000
2 - 60000
0-4
0-4
0 - 10000
0 - 10000
0 - 10000
0 - 10000
1
1
1
1
1
1
1
1
1
1
1
1
0270
0271
0272
02730274
0275
0276
0288
0289
028A
028B
028C
028D
028E
028F
0290
Protection 59n
Ue>>>> value
Recloser 79
Protection
50n/51n/67n
10ms
Format
10ms
10ms
10ms
10ms
10ms
F1
F1
F18A
F18A
F18A
F18A
F1
F1
F1
F1
F1
F1
0
0
260
0
960
0
0
0
0
1
1
111
1
111
1
500
500
500
500
500
500
4
4
4
4
4
4
F3
F57
10ms
10ms
10ms
10ms
10ms
10ms
Def.
value
P125
P126
P127
Address
(hex)
Communications
25 - 1500
100 -10000
1
5
0.001
0.001
F1
F1
25
100
0-1
0 - 10000
25 - 3200
1
1
1
10ms
0.001
F34
F1
F1
F3
0
4
25
0
25 - 1500
100 - 10000
1
5
0.001
0.001
F1
F1
25
100
0-1
25 - 3200
0 - 2222
1
1
1
0.001
F34
F1
F57
0294
0 - 2222
F57
0295
0 - 2222
F57
0296
0 - 2222
F57
0297
0 - 2222
F57
0298
0 - 2222
F57
0299
0 - 2222
F57
029A
0 - 2222
F57
Reserved
P> operating mode
57-130V operating range
0
25
111
1
111
1
111
1
111
1
111
1
111
1
111
1
111
1
0-1
1-10000
1
1
W.In
F24
F1
4-40000
W.In
F1
0291
0292
0293
029B-029F
02A0
02A1
Recloser 79
Active Power
P> value
0
100
00
400
00
P12y/EN CT/Fa5
MODBUS DATABASE
Page 29/130
02AA
02AB
02AC
02AD
02AE
02AF
02B0
02B1
02B2
02B3
02B4
02B5
02B6
02B7
02B8
02B9
02BA
02BB
02BC
02BD
02BE
02BF
02C0
02C1
02C2
02C3
02C4
02C5
02C6
Group
Description
Values
range
Step
W.In
W.In
F1
0-15000
0-359
0-1
1-10000
4-40000
0-15000
0-359
0-2
4510-5490
1
1
1
1
1
1
1
1
1
10mS
Degree
10mHz
F1
F1
F24
F1
F1
F1
F1
F68
F1
60 Hz nominal frequency
5510-6490
10mHz
F1
0-60000
0-2
4510-5490
1
1
1
10ms
10mHz
F1
F68
F1
60 Hz nominal frequency
5510-6490
10mHz
F1
0-60000
0-2
4510-5490
1
1
1
10ms
10mHz
F1
F68
F1
60 Hz nominal frequency
5510-6490
10mHz
F1
0-60000
0-2
4510-5490
5510-6490
1
1
1
10ms
f4 value
F1
F68
F1
f5 value
0-60000
0-2
4510-5490
1
1
1
10mHz
F1
F68
F1
60 Hz nominal frequency
5510-6490
10mHz
F1
0-60000
0-2
4510-5490
1
1
1
10ms
10mHz
F1
F68
F1
60 Hz nominal frequency
5510-6490
10mHz
F1
0-60000
0-1
0-1
20-1300
100-4800
0-1
1-10000
1
1
1
1
5
1
1
10ms
W x In
F1
F24
F24
F1
F1
F24
F1
4-40000
W x In
F1
P>> value
P<< triggering
level
Frequency
f1 value
f2 value
f3 value
f6 value
Protection 37
U< value of
inhibition I<
Reactive Power
Q> triggering
level
0-15000
0-359
0-1
1-10000
4-40000
0-15000
0-359
0-1
1-10000
1
1
1
1
1
1
1
1
1
4-40000
10ms
Degree
Format
F1
F1
F24
F1
F1
F1
F1
F24
F1
P< triggering
level
Unit
W x In
W x In
10ms
Degree
W x In
W x In
10ms
Degree
10mHz
10ms
100mV
100mV
Def.
value
0
0
0
1
5
0
0
0
100
00
400
00
0
0
0
1
5
0
0
0
500
0
600
0
0
0
500
0
600
0
0
0
500
0
600
0
0
0
500
0
ou
600
0
0
0
500
0
600
0
0
0
500
0
600
0
0
0
0
50
200
0
100
00
400
00
P125
P126
P127
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 30/130
02C7
02C8
02C9
02CA
02CB
02CC
02CD
02CE
02CF
02D0
02D1
02D2
02D3
02D4
02D5
02D6
02D7
02D8-02D9
02DA-02DB
02DC-02DD
02DE-02DF
02E0-02E1
02E2-02E3
02E4
02E5
Group
Q< triggering
level
Q>> triggering
level
Q<< triggering
level
Recloser 79
[50N/51N] Ie_d>
02E6
02E7
02E8
02E9
02EA
02EB
02EC
02ED
02EE
02EF
02F0
02F1
02F2
02F3
02F4
02F5
02F6
02F7
02F8
02F9
02FA
02FB
02FC
02FD
02FE 02FF
Ue>>>> value
for Ie_d>
Protection 27
[81R] FREQ.
CHANGE OF
RATE
MiCOM P125-P126-P127
Description
Values
range
Step
0-15000
0-359
0-1
1-10000
4-40000
0-15000
0-359
0-1
1-10000
1
1
1
1
1
1
1
1
1
4-40000
Unit
Def.
value
W x In
F1
F1
F24
F1
F1
F1
F1
F24
F1
W x In
F1
0-15000
0-359
0-1
1-10000
4-40000
0-15000
0-359
0-1
2-100
10 - 1440
5 - 60000
5 - 60000
5 - 60000
5 - 60000
5 - 60000
5 - 60000
0-1-2
10 to 4000
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
10mS
Degree
F1
F1
F24
F1
F1
F1
F1
F24
F1
F1
F18A
F18A
F18A
F18A
F18A
F18A
F24A
F1
0
0
0
1
5
0
0
0
100
00
400
00
0
0
0
1
5
0
0
0
10
60
5
5
5
5
5
5
0
100
0 to 15000
25 to 1500
100 to 10000
1
1
5
F3
F1
F1
F1
0
0
25
100
01
F34
0 to 10000
25 - 3200
1
1
1/100 s
0.001
F1
F1
0
25
10 - 2600
1/10 V
F1
40 - 7200
1/10 V
F1
0 - 359
10 - 170
1
1
Degree
Degree
F1
F1
100
0
400
0
0
10
03
0-1
1
1
F86
F24
0
0
-100 - +100
0-1
-100 - +100
0-1
-100 - +100
0-1
-100 - +100
0-1
-100 - +100
0-1
-100 - +100
1
1
1
1
1
1
1
1
1
1
1
F2
F24
F2
F24
F2
F24
F2
F24
F2
F24
F2
+10
0
+10
0
+10
0
+10
0
+10
0
+10
df/dt1 threshold
df/dt2 activation
df/dt2 threshold
df/dt3 activation
df/dt3 threshold
df/dt4 activation
df/dt4 threshold
df/dt5 activation
df/dt5 threshold
df/dt6 activation
df/dt6 threshold
Unused
10ms
Degree
Format
P125
P126
P127
Address
(hex)
Communications
W x In
W x In
10ms
Degree
W x In
W x In
10ms
Degree
minutes
10 ms
10 ms
10 ms
10 ms
10 ms
10 ms
1/100
IEn
1/100 s
1/1000
1/1000
0.1Hz/s
0.1Hz/s
0.1Hz/s
0.1Hz/s
0.1Hz/s
0.1Hz/s
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 31/130
Address
(hex)
2500
Description
Values
range
Step
Unit
0-1-2
Ie_d>> Threshold
10 to 4000
1/100
IEn
0 to 15000
25 to 1500
100 to 10000
1
1
5
1/100 s
1/1000
1/1000
01
0 to 10000
25 - 3200
1
1
10 - 2600
2512
2513-257E
257F
3.3.3
[50N/51N]
Ie_d>>
2501
2502
2503
2504
2505
2506
2507
2508
2509
Ue value for
Ie_d>>
250A
250B
250C
250D
250E
[47] V2>
250F
2510
2511
[47] V2>>
Format
Def.
value
P125
P126
P127
3.3.2
F24A
F1
100
F3
F1
F1
F1
0
0
25
100
F34
1/100 s
0.001
F1
F1
0
25
1/10 V
F1
40 - 7200
1/10 V
F1
0 - 359
10 - 170
1
1
Degree
Degree
F1
F1
100
0
400
0
0
10
0-1
1-130V
4-480V
0 to 10000
0-1
1-130V
4-480V
0 to 10000
1
10
40
1
1
10
40
1
F24
F1
F1
F1
F24
F1
F1
F1
0
150
600
500
0
150
600
500
1/10V
1/10V
1/100s
1/10V
1/10V
1/100s
The addresses 03XX (page 03) are equivalent to addresses 26XX (page 26).
Same structure as group1 (page 2H): replace addresses 02XX by 03XX.
3.3.4
3.3.5
3.3.6
P12y/EN CT/Fa5
MODBUS DATABASE
Page 32/130
3.3.7
Communications
MiCOM P125-P126-P127
3.3.8
3.3.9
3.3.10
3.3.11
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 33/130
Boolean equations
3.4.1
Address
(hex)
0500
0501
0502
0503
0504
0505
0506
0507
0508
0509
050A
050B
050C
050D
050E
050F
0510
0511
0512
0513
0514
0515
0516
0517
0518
0519
051A
051B
051C
051D
051E
051F
0520
0521
0522
0523
0524
0525
0526
0527
0528
0529
052A
052B
052C
052D
052E
052F
0530
0531
0532
0533
0534
0535
0536
0537
0538
0539
053A
Group
Bool Equations
Description
Equation A.00 operator
Equation A.00 operand
Equation A.01 operator
Equation A.01 operand
Equation A.02 operator
Equation A.02 operand
Equation A.03 operator
Equation A.03 operand
Equation A.04 operator
Equation A.04 operand
Equation A.05 operator
Equation A.05 operand
Equation A.06 operator
Equation A.06 operand
Equation A.07 operator
Equation A.07 operand
Equation A.08 operator
Equation A.08 operand
Equation A.09 operator
Equation A.09 operand
Equation A.10 operator
Equation A.10 operand
Equation A.11 operator
Equation A.11 operand
Equation A.12 operator
Equation A.12 operand
Equation A.13 operator
Equation A.13 operand
Equation A.14 operator
Equation A.14 operand
Equation A.15 operator
Equation A.15 operand
Equation B.00 operator
Equation B.00 operand
Equation B.01 operator
Equation B.01 operand
Equation B.02 operator
Equation B.02 operand
Equation B.03 operator
Equation B.03 operand
Equation B.04 operator
Equation B.04 operand
Equation B.05 operator
Equation B.05 operand
Equation B.06 operator
Equation B.06 operand
Equation B.07 operator
Equation B.07 operand
Equation B.08 operator
Equation B.08 operand
Equation B.09 operator
Equation B.09 operand
Equation B.10 operator
Equation B.10 operand
Equation B.11 operator
Equation B.11 operand
Equation B.12 operator
Equation B.12 operand
Equation B.13 operator
Values
range
0-1
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-1
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
Step
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Unit
For- Def.
mat Value
F70
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F70
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
P12y/EN CT/Fa5
MODBUS DATABASE
Page 34/130
Address
(hex)
053B
053C
053D
053E
053F
0540
0541
0542
0543
0544
0545
0546
0547
0548
0549
054A
054B
054C
054D
054E
054F
0550
0551
0552
0553
0554
0555
0556
0557
0558
0559
055A
055B
055C
055D
055E
055F
0560
0561
0562
0563
0564
0565
0566
0567
0568
0569
056A
056B
056C
056D
056E
056F
0570
0571
0572
0573
0574
0575
0576
0577
0578
0579
Group
Communications
MiCOM P125-P126-P127
Description
Equation B.13 operand
Equation B.14 operator
Equation B.14 operand
Equation B.15 operator
Equation B.15 operand
Equation C.00 operator
Equation C.00 operand
Equation C.01 operator
Equation C.01 operand
Equation C.02 operator
Equation C.02 operand
Equation C.03 operator
Equation C.03 operand
Equation C.04 operator
Equation C.04 operand
Equation C.05 operator
Equation C.05 operand
Equation C.06 operator
Equation C.06 operand
Equation C.07 operator
Equation C.07 operand
Equation C.08 operator
Equation C.08 operand
Equation C.09 operator
Equation C.09 operand
Equation C.10 operator
Equation C.10 operand
Equation C.11 operator
Equation C.11 operand
Equation C.12 operator
Equation C.12 operand
Equation C.13 operator
Equation C.13 operand
Equation C.14 operator
Equation C.14 operand
Equation C.15 operator
Equation C.15 operand
Equation D.00 operator
Equation D.00 operand
Equation D.01 operator
Equation D.01 operand
Equation D.02 operator
Equation D.02 operand
Equation D.03 operator
Equation D.03 operand
Equation D.04 operator
Equation D.04 operand
Equation D.05 operator
Equation D.05 operand
Equation D.06 operator
Equation D.06 operand
Equation D.07 operator
Equation D.07 operand
Equation D.08 operator
Equation D.08 operand
Equation D.09 operator
Equation D.09 operand
Equation D.10 operator
Equation D.10 operand
Equation D.11 operator
Equation D.11 operand
Equation D.12 operator
Equation D.12 operand
Values
range
0 - 111
0-3
0 - 111
0-3
0 - 111
0-1
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-1
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
Step
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Unit
For- Def.
mat Value
F72
F71
F72
F71
F72
F70
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F70
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 35/130
Group
Description
Equation D.13 operator
Equation D.13 operand
Equation D.14 operator
Equation D.14 operand
Equation D.15 operator
Equation D.15 operand
Equation E.00 operator
Equation E.00 operand
Equation E.01 operator
Equation E.01 operand
Equation E.02 operator
Equation E.02 operand
Equation E.03 operator
Equation E.03 operand
Equation E.04 operator
Equation E.04 operand
Equation E.05 operator
Equation E.05 operand
Equation E.06 operator
Equation E.06 operand
Equation E.07 operator
Equation E.07 operand
Equation E.08 operator
Equation E.08 operand
Equation E.09 operator
Equation E.09 operand
Equation E.10 operator
Equation E.10 operand
Equation E.11 operator
Equation E.11 operand
Equation E.12 operator
Equation E.12 operand
Equation E.13 operator
Equation E.13 operand
Equation E.14 operator
Equation E.14 operand
Equation E.15 operator
Equation E.15 operand
Equation F.00 operator
Equation F.00 operand
Equation F.01 operator
Equation F.01 operand
Equation F.02 operator
Equation F.02 operand
Equation F.03 operator
Equation F.03 operand
Equation F.04 operator
Equation F.04 operand
Equation F.05 operator
Equation F.05 operand
Equation F.06 operator
Equation F.06 operand
Equation F.07 operator
Equation F.07 operand
Equation F.08 operator
Equation F.08 operand
Equation F.09 operator
Equation F.09 operand
Equation F.10 operator
Equation F.10 operand
Equation F.11 operator
Equation F.11 operand
Equation F.12 operator
Values
range
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-1
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-1
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
Step
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Unit
For- Def.
mat Value
F71
F72
F71
F72
F71
F72
F70
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F70
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
P12y/EN CT/Fa5
MODBUS DATABASE
Page 36/130
Address
(hex)
05B9
05BA
05BB
05BC
05BD
05BE
05BF
05C0
05C1
05C2
05C3
05C4
05C5
05C6
05C7
05C8
050C9
05CA
05CB
05CC
05CD
05CE
05CF
05D0
05D1
05D2
05D3
05D4
05D5
05D6
05D7
05D8
05D9
05DA
05DB
05DC
05DD
05DE
05DF
05E0
05E1
05E2
05E3
05E4
05E5
05E6
05E7
05E8
05E9
05EA
05EB
05EC
05ED
05EE
05EF
05F0
05F1
05F2
05F3
05F4
05F5
05F6
05F7
Group
Communications
MiCOM P125-P126-P127
Description
Equation F.12 operand
Equation F.13 operator
Equation F.13 operand
Equation F.14 operator
Equation F.14 operand
Equation F.15 operator
Equation F.15 operand
Equation G.00 operator
Equation G.00 operand
Equation G.01 operator
Equation G.01 operand
Equation G.02 operator
Equation G.02 operand
Equation G.03 operator
Equation G.03 operand
Equation G.04 operator
Equation G.04 operand
Equation G.05 operator
Equation G.05 operand
Equation G.06 operator
Equation G.06 operand
Equation G.07 operator
Equation G.07 operand
Equation G.08 operator
Equation G.08 operand
Equation G.09 operator
Equation G.09 operand
Equation G.10 operator
Equation G.10 operand
Equation G.11 operator
Equation G.11 operand
Equation G.12 operator
Equation G.12 operand
Equation G.13 operator
Equation G.13 operand
Equation G.14 operator
Equation G.14 operand
Equation G.15 operator
Equation G.15 operand
Equation H.00 operator
Equation H.00 operand
Equation H.01 operator
Equation H.01 operand
Equation H.02 operator
Equation H.02 operand
Equation H.03 operator
Equation H.03 operand
Equation H.04 operator
Equation H.04 operand
Equation H.05 operator
Equation H.05 operand
Equation H.06 operator
Equation H.06 operand
Equation H.07 operator
Equation H.07 operand
Equation H.08 operator
Equation H.08 operand
Equation H.09 operator
Equation H.09 operand
Equation H.10 operator
Equation H.10 operand
Equation H.11 operator
Equation H.11 operand
Values
range
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-1
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-1
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
Step
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Unit
For- Def.
mat Value
F72
F71
F72
F71
F72
F71
F72
F70
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F70
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
F71
F72
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 37/130
Group
Description
Equation H.12 operator
Equation H.12 operand
Equation H.13 operator
Equation H.13 operand
Equation H.14 operator
Equation H.14 operand
Equation H.15 operator
Equation H.15 operand
Values
range
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
0-3
0 - 111
Step
1
1
1
1
1
1
1
1
Unit
For- Def.
mat Value
F71
F72
F71
F72
F71
F72
F71
F72
0
0
0
0
0
0
0
0
P12y/EN CT/Fa5
MODBUS DATABASE
Page 38/130
Communications
MiCOM P125-P126-P127
3.5
3.5.1
Address
(hex)
0400
0401
0402
Group
Remote control
0403
0404
0405
3.5.2
Values
range
Step
Unit
For- Def.
mat Value
0 -.65535
F9
0 --511
F39
0
0
0
0 65535
0 65535
Binary
1
1
1
F9A
F9B
F81
0
0
0
Address
(hex)
Group
0700
3.5.3
Description
Description
Values
range
Relays status
Step
1
Unit
-
For- Def.
mat Value
F23
Address
(hex)
0800
0801
0802
0803
Nb
bytes
2
1 (Hi)
1 (Lo)
1 (Hi)
1 (Lo)
2
Mask
(hex)
FFFF
FF
FF
FF
FF
FFFF
0800
1 (Hi)
1 (Lo)
7F
0801
1 (Hi)
1 (Lo)
1 (Lo)
1 (Hi)
1 (Hi)
1 (Lo)
1 (Lo)
2
0F
E0
1F
80
1F
80
3F
FFFF
0802
0803
Values range
1994-2093
1 -12
1 - 31
0 - 23
0 - 59
0 - 59999
94-99 (1994-1999)
0-93 (2000-2093)
1 - 12
1 7 (Monday Sunday)
1 - 31
0 - 1 (summer winter)
0 - 23
0 - 1 (valid invalid)
0 - 59
0 - 59999
Unit
Years
Months
Days
Hours
Minutes
ms
Years
Months
Days
Days
Hours
Minutes
ms
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 39/130
Disturbance records
Pages 38h to 3Ch: mapping pages used to send a service request to select the record number to
be uploaded before uploading any disturbance record.
The answer following this request contain the following information:
1. Numbers of samples (pre and post time)
2. Phase CT ratio
3. Earth CT ratio
4. Internal phase and earth current ratios
5. Phase VT ratio
6. Earth VT ratio
7. Internal phase and earth voltage ratios
8. Number of the last disturbance mapping page
9. Number of samples in this last disturbance mapping page
Pages 9h to 21h: contain the disturbance data (25 pages)
A disturbance mapping page contains 250 words:
0900 to 09FAh:
0A00 to 0AFAh:
0B00 to 0BFAh:
2100 to 21FAh:
The disturbance data pages contain the sample of a single channel from a record.
Page 22h: contains the index of the disturbance
Page 38h to 3Ch: selection of the disturbance record and channel
Page 3Dh: a dedicated request allows to know the number of disturbance records stored.
3.6.1
Contents
0900h to 09FAh
0A00h to 0AFAh
0B00h to 0BFAh
0C00h to 0CFAh
0D00h to 0DFAh
0E00h to 0DFAh
0F00h to 0FFAh
1000h to 10FAh
1100h to 11FAh
1200h to 12FAh
P12y/EN CT/Fa5
MODBUS DATABASE
Page 40/130
MiCOM P125-P126-P127
Addresses (hex)
Contents
1300h to 13FAh
1400h to 14FAh
1500h to 15FAh
1600h to 16FAh
1700h to 17FAh
1800h to 18FAh
1900h to 19FAh
1A00h to 1AFAh
1B00h to 1BFAh
1C00h to 1CFAh
1D00h to 1DFAh
1E00h to 1EFAh
1F00h to 1FFAh
2000h to 20FAh
2100h to 21FAh
NOTE:
3.6.1.1
Communications
The disturbance data pages contain the values of one channel from one
given disturbance record.
The values are signed 16 bits words equivalent to the ADC value.
Phase current values calculation formula
Line phase current value (primary value) = value x phase primary CT ratio x 2 / 800
Earth current values calculation formula
The formula depends of nominal earth current:
0.1 to 40 Ien range
Line earth current value (primary value) = value x earth primary CT ratio x 2 / 800
0.01 to 8 Ien range
Line earth current value (primary value) = value x earth primary CT ratio x 2 / 3277
0.002 to 1 Ien range
Line earth current value (primary value) = value x earth primary CT ratio x 2 / 32700
The values are signed 16 bits words equivalent to the ADC value.
Phase voltage values calculation formula
The formula depends of nominal phase voltage:
57 to 130 V range
Line phase voltage value (primary value) = value x (phase primary VT ratio / phase secondary VT
ratio) x 2 / 126
220 to 480 V range
Line phase voltage value (primary value) = value x 2 / 34
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 41/130
57 to 130 V range
Line earth voltage value (primary value) = value x (earth primary VT ratio / earth secondary VT
ratio) x 2 / 126
220 to 480 V range
Line earth voltage value (primary value) = value x 2 / 34
Frequency channel:
Logical channels:
Logical channel 1 (if MODBUS or DNP3 on rear ports)
Logic channel
Contents
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
P12y/EN CT/Fa5
MODBUS DATABASE
Page 42/130
Communications
MiCOM P125-P126-P127
Contents
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Reserved (EL13)
Bit 6
Reserved (EL14)
Bit 7
Reserved (EL15)
Bit 8
Reserved (EL16)
Bit 9
Reserved
Bit 10
Reserved
Bit 11
Reserved
Bit 12
Reserved
Bit 13
Reserved
Bit 14
Reserved
Bit 15
Reserved
Contents
Bit 0
General Start
Bit 1
CB Failure
Bit 2
General Trip
Bit 3
trip tI>
Bit 4
Bit 5
trip tIe>
Bit 6
Bit 7
trip tPw>
Bit 8
trip tPw>>
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 43/130
3.6.2
Contents
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Reserved (EL13)
Bit 6
Reserved (EL14)
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
Bit 15
Contents
Disturbance data index frame
Contents
P12y/EN CT/Fa5
MODBUS DATABASE
Page 44/130
3.6.3
Communications
MiCOM P125-P126-P127
3808h
3809h
3900h
3901h
3902h
3903h
3904h
3905h
3906h
3907h
3908h
3909h
3A00h
3A01h
3A02h
3A03h
3A04h
3A05h
3A06h
3A07h
3A08h
3A09h
3B00h
3B01h
3B02h
3B03h
3B04h
3B05h
3B06h
3B07h
3B08h
3B09h
3C00h
3C01h
3C02h
3C03h
3C04h
3C05h
3C06h
3C07h
3C08h
3C09h
Channel
IA
IB
IC
Ie
UA
UB
UC / Ue
Frequency
Logical infos 1
Logical infos 2
IA
IB
IC
Ie
UA
UB
UC / Ue
Frequency
Logical infos 1
Logical infos 2
IA
IB
IC
Ie
UA
UB
UC / Ue
Frequency
Logical infos 1
Logical infos 2
IA
IB
IC
Ie
UA
UB
UC / Ue
Frequency
Logical infos 1
Logical infos 2
IA
IB
IC
Ie
UA
UB
UC / Ue
Frequency
Logical infos 1
Logical infos 2
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 45/130
Word Nr.
n 1
n 2
n 3
n 4
n 5
n 6
n 7
n 8
n 9
n 10
n 11
n 12
n 13
n 14
n 15
n 16
n 17
n 18
n 19
Contents
Number of samples included in the mapping
Sample number in pre-time
Sample number in post-time
Phase primary CT
Phase secondary CT
Earth primary CT
Earth secondary CT
Phase Internal CT ratio
Earth Internal CT ratio
Phase primary VT byte low
Phase primary VT byte high
Phase secondary VT
Earth primary VT byte low
Earth primary VT byte high
Earth secondary VT
Internal VT ratio numerator: 100
Internal VT ratio denominator: 12600 or 3400
Last mapping page
Last mapping page words number
P12y/EN CT/Fa5
MODBUS DATABASE
Page 46/130
Communications
MiCOM P125-P126-P127
3.6.4
Contains
Number of disturbance records available
Words description:
Word Nr.
1
2
3 to 6
8
9
10 to 13
14
15
16
17 to 20
IEC FORMAT: 17 to 20
21
22
23
24 to 27
28
29
30
31 to 36
35
36
Contents
Number of disturbance records available
Oldest disturbance record number (n)
Date is depending on address 012Fh format F52:
With private date format: see format F97
With IEC 60870-5-103 format: see format of time
synchronisation address 0800h
Disturbance record starting origin
1= trip relay (RL1)
2= instantaneous threshold
3= remote command
4= logical input
Acknowledge
Disturbance record previous number (n+1)
Date is depending on address 012Fh format F52:
With private date format: see format F97
With IEC 60870-5-103 format: see format of time
synchronisation address 0800h
Disturbance record starting origin
1= trip relay (RL1)
2= instantaneous threshold
3= remote command
4= logical input
Acknowledge
Disturbance record previous number (n+2)
Date is depending on address 012Fh format F52:
With private date format: see format F97
With IEC 60870-5-103 format: see format of time
synchronisation address 0800h
Previous disturbance record date (see format of time
synchronisation, address 0800h)
Disturbance record starting origin
1= trip relay (RL1)
2= instantaneous threshold
3= remote command
4= logical input
Acknowledge
Disturbance record previous number (n+3)
Date is depending on address 012Fh format F52:
With private date format: see format F97
With IEC 60870-5-103 format: see format of time
synchronisation address 0800h
Disturbance record starting origin
1= trip relay (RL1)
2= instantaneous threshold
3= remote command
4= logical input
Acknowledge
Disturbance record previous number (n+4)
Date is depending on address 012Fh format F52:
With private date format: see format F97
With IEC 60870-5-103 format: see format of time
synchronisation address 0800h
Disturbance record starting origin
1= trip relay (RL1)
2= instantaneous threshold
3= remote command
4= logical input
Acknowledge
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 47/130
Events records
To upload the events records two requests are allowed:
Page 35h: request to upload an event record without acknowledges of this event.
Used addresses:
3500h:
54Ah:
EVENT 1
EVENT 75
Page 36h: request to upload the non-acknowledged oldest stored event record.
Two modes are available for the acknowledgement: automatic acknowledgement or manual
acknowledgement
The mode depends of the state of bit 12 of remote control word (address 400 h).
If this bit is set, then the acknowledgement is manual else the acknowledgement is automatic.
In automatic mode, the reading of the event acknowledges the event.
In manual mode, it is necessary to write a specific command to acknowledge the oldest event
(set the bit 13 of control word addressed to 400 h)
3.7.1
Contents
MODBUS address
Reserved
5 to 8
Acknowledgement:
0 = event non acknowledged
1 = event acknowledged
P12y/EN CT/Fa5
MODBUS DATABASE
Page 48/130
Communications
MiCOM P125-P126-P127
Event meaning
Control close (Remote, input, HMI)
Control trip (Remote, input, HMI)
Disturbance recording start
Trip output unlatch
Settings change
Remote thermal reset
Maintenance Mode
Control relay in maintenance mode
U<
U<<
Pe/Iecos>
Pe/Iecos>>
I<
I2>
I2>>
I2>>>
alarm (Thermal overload)
U>
U>>
Ue>>>>
I>
I>>
I>>>
Ie>
Ie>>
Ie>>>
U< trip
U<< trip
Pe/Iecos> trip
Pe/Iecos>> trip
I< trip
I2> trip
I2>> trip
I2>>> trip
trip (Thermal overload)
U> trip
U>> trip
Ue>>>> trip
Reserved
Reserved
Reserved
I> trip
I>> trip
I>>> trip
Ie> trip
Ie>> trip
Ie>>> trip
Trip SOTF
X1 trip: t AUX3
X1 trip: t AUX4
Equ. Log. A trip
Equ. Log. B trip
Equ. Log. C trip
Equ. Log. D trip
Broken conductor
t AUX1 trip
t AUX2 trip
CB Flt or SF6 low (by logical input)
Working time
Format
MODBUS
address (Hex)
F9
F9
F73
F9
Address
F9
F9
F39
F17
F17
F16
F16
F17
F17
F17
F17
F37
F17
F17
F16
F17
F17
F17
F16
F16
F16
F17
F17
F16
F16
F17
F17
F17
F17
F37
F17
F17
F16
013
013
F17
F17
F17
F16
F16
F16
F38
F13
F13
F48
F48
F48
F48
F38
F38
F38
F20
F43
14
15
16
17
18
19
23
13
13
7F
7F
7F
7F
23
23
23
11
28
Alarm
013
0402
013
70
71
72
73
21
7C
7D
7E
020
76
77
7A
14
15
16
17
18
19
70
71
72
73
21
7C
7D
7E
20
76
77
7A
Auto
Inhib & Self
Inhib & Self
Yes & Self
Yes & Self
Yes & Self
Yes & Self
Yes & Self
Yes & Self
Yes
Yes & Self
Yes & Self
Yes & Self
Yes & Self
Yes & Self
Yes & Self
Yes & Self
Yes & Self
Yes & Self
Inhib
Inhib
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Inhib
Inhib
Inhib
Inhib
Yes
Inhib
Inhib
Auto
Yes
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 49/130
Event meaning
Operation numbers
Sum of switched square amps
Trip circuit supervision
Closing time
Reclose successful
Recloser final trip
Recloser settings error
Circuit Breaker Failure
Selective scheme logic 1 (by logical input)
Selective scheme logic 2 (by logical input)
Blocking logic 1 (by logical input)
Blocking logic 2 (by logical input)
Setting group change
O/O (by logical input)
F/O (by logical input)
All alarms acknowledgement (by logical
input)
Cold load pick up
Input logic state change
X1 trip: trip
X1 trip: t I>
X1 trip: t I>>
X1 trip: t I>>>
X1 trip: t Ie>
X1 trip: t Ie>>
X1 trip: t Ie>>>
X1 trip: t Pe/Iecos>
X1 trip: t Pe/Iecos>>
X1 trip: t U<
X1 trip: t U<<
X1 trip: t I<
X1 trip: t U>
X1 trip: t U>>
X1 trip: t I2>
X1 trip: t I2>>
X1 trip: t I2>>>
X1 trip: t Ue>>>>
X1 trip: Broken Conductor
X1 trip: Equ. Log. A
X1 trip: Equ. Log. B
X1 trip: Equ. Log. C
X1 trip: Equ. Log. D
X1 trip: t AUX1
X1 trip: t AUX2
Output relays command
Front panel single alarm acknowledge
All alarms front panel acknowledgement
Single alarm remote acknowledgement
All alarms remote acknowledgement
Major material alarm
Minor material alarm
Operating Latched Relays status
General Start protection (IEC 60870-5-103
protocol)
Recloser in Service (IEC 60870-5-103 only)
52a by recloser (IEC 60870-5-103 protocol)
Local parameter setting (password active) (IEC 60870-5-103 protocol)
Start timer Breaker failure (by logical input)
t AUX3 trip
t AUX4 trip
Manual Close (by logical input)
Format
MODBUS
address (Hex)
F43
F43
F43
F43
F43
F43
F43
F38
F20
F20
F20
F20
F55
F20
F20
F20
28
28
28
28
28
28
28
23
11
11
11
11
11
11
11
11
F20
F12
F13
F13
F13
F13
F13
F13
F13
F13
F13
F13
F13
F13
F13
F13
F13
F13
F13
F13
F13
F13
F13
F13
F13
F13
F13
F39
11
10
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
13
402
F45
F45
F27
F95
0F
0F
2E
0B
F43
Cycle
28
F20A
F38
F38
F20A
0D
23
23
0D
Alarm
Yes
Yes
Yes
Yes
Auto
Auto
Yes
Yes
Yes
Auto
Inhib
Inhib
P12y/EN CT/Fa5
MODBUS DATABASE
Page 50/130
Code
(Dec)
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
Event meaning
X1 trip: SOTF
Local Mode (by logical input)
I>> Blocked
I>>> Blocked
VTS
V2>
V2>>
Recloser int locked
Recloser in progress
Synchronization
Inrush blocking
P>
P>>
P> trip
P>> trip
X1 trip: t P>
X1 trip: t P>>
f1
f2
f3
f4
f5
f6
tf1
tf2
tf3
tf4
tf5
tf6
F out
X1 trip: tf1 Trip
X1 trip: tf2 Trip
X1 trip: tf3 Trip
X1 trip: tf4 Trip
X1 trip: tf5 Trip
X1 trip: tf6 Trip
Equ. Log. E trip
Equ. Log. F trip
Equ. Log. G trip
Equ. Log. H trip
X1 trip: Equ. Log. E
X1 trip: Equ. Log. F
X1 trip: Equ. Log. G
X1 trip: Equ. Log. H
Comm. IEC-103: Signals&Measurements
blocking
Comm. IEC-103: Commands blocking
t AUX5 trip
t AUX6 trip
t AUX7 trip
t AUX8 trip
t AUX9 trip
t AUX A trip
t AUX B trip
t AUX C trip
X1 trip: t AUX5
X1 trip: t AUX6
X1 trip: t AUX7
X1 trip: t AUX8
X1 trip: t AUX9
X1 trip: t AUXA
Communications
MiCOM P125-P126-P127
Format
MODBUS
address (Hex)
F38
F20A
F38A
F38A
F38A
F38A
F38A
F43
F43
F23
F38A
F38A
F38A
F38A
F38A
F13
F13
F67
F67
F67
F67
F67
F67
F67
F67
F67
F67
F67
F67
F69
F13
F13
F13
F13
F13
F13
F48
F48
F48
F48
F13
F13
F13
F13
F78
23
0D
22
22
22
22
22
28
28
F78
F38B
F38B
F38B
F38B
F38B
F38B
F38B
F38B
F13
F13
F13
F13
F13
F13
0668
2F
2F
2F
2F
2F
2F
2F
2F
13
13
13
13
13
13
22
22
22
22
22
13
13
B5
B6
B7
B8
B9
BA
B5
B6
B7
B8
B9
BA
BB
13
13
13
13
13
13
7F
7F
7F
7F
13
13
13
13
0668
Alarm
Auto
Auto
Inhib
Inhib
Inhib
Inhib
Inhib
Inhib
Inhib
Inhib
Inhib
Inhib
Inhib
Inhib
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 51/130
Event meaning
Format
MODBUS
address (Hex)
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
X1 trip: t AUXB
X1 trip: t AUXC
Start Earth (for IEC-103)
Ie_d>
Ie_d> trip
X1 trip: t Ie_d
Reset LEDs (by logical input)
CTS
df/dt1
df/dt2
df/dt3
df/dt4
df/dt5
df/dt6
X1 trip: df/dt1 Trip
X1 trip: df/dt2 Trip
X1 trip: df/dt3 Trip
X1 trip: df/dt4 Trip
X1 trip: df/dt5 Trip
X1 trip: df/dt6 Trip
Recloser ext locked
P<
P<<
P< trip
P<< trip
X1 trip: t P<
X1 trip: t P<<
Q>
Q>>
Q> trip
Q>> trip
X1 trip: t Q>
X1 trip: t Q>>
Q<
Q<<
Q< trip
Q<< trip
X1 trip: t Q<
X1 trip: t Q<<
Comm order 1
Comm order 2
Comm order 3
Comm order 4
General Trip (IEC 60870-5-103 protocol)
Trip Phase A (IEC 60870-5-103 protocol)
F13
F13
13
13
F16
F16
F13
F20B
F38A
F94
F94
F94
F94
F94
F94
F13
F13
F13
F13
F13
F13
F43
F38A
F38A
F38A
F38A
F13
F13
F38B
F38B
F38B
F38B
F13
F13
F38B
F38B
F38B
F38B
F13
F13
F9A
F9A
F9A
F9A
F95
F17
224
F17
225
F17
226
227
228
229
230
231
F9A
F2 unit
millivolt
F2 unit
millivolt
F2 unit
millivolt
F2 unit
millivolt
F2 unit
millivolt
1A
1A
13
BE
24
BF
BF
BF
BF
BF
BF
13
13
13
13
13
13
28
22
22
22
22
13
13
2F
2F
2F
2F
13
13
2F
2F
2F
2F
13
13
0403
0403
0403
0403
0B
14/15/16 or
76/77 or 70/71
14/15/16 or
76/77 or 70/71
14/15/16 or
76/77 or 70/71
0403
0x000F
Alarm
Auto
Yes
Yes
Yes
Yes
Yes
Yes
Auto
Yes & Self
Yes & Self
Yes
Yes
Yes & Self
Yes & Self
Yes
Yes
Yes & Self
Yes & Self
Yes
Yes
No
0x00C2
No
0x00C2
No
0x00C2
No
0x00C2
No
P12y/EN CT/Fa5
MODBUS DATABASE
Page 52/130
Code
(Dec)
Communications
MiCOM P125-P126-P127
Event meaning
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
3.7.2
Format
F2 unit
millivolt
F2 unit
millivolt
F2 unit CAN
MODBUS
address (Hex)
0x00C2
No
0x00C2
No
0x00C3
No
F2 unit CAN
0x00C3
No
F2 unit CAN
0x00C3
No
F2 unit CAN
0x00C3
No
F2 unit CAN
0x00C3
No
F2 unit CAN
0x00C3
No
F2 unit CAN
0x00C3
No
F2 unit CAN
0x00C3
No
F2 unit CAN
0x00C3
No
F16
F16
F13
F16
F16
F13
F16
F16
F13
C4
C4
13
C8
C8
13
C9
C9
13
NOTE:
ALARM:
Alarm
Contents
Oldest event data
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 53/130
Fault records
Page 37h: Page dedicated to upload fault record
Used addresses:
3700h:
FAULT 1
3701h:
3718h:
FAULT 2
FAULT 25
Page 3Eh: Request to upload the non-acknowledged oldest stored fault record.
Two modes are available for the acknowledgement: automatic acknowledgement or manual
acknowledgement
The mode depends of the state of bit 12 of remote control word (address 400 h).
If this bit is set, then the acknowledgement is manual else the acknowledgement is automatic.
In automatic mode, the reading of the fault acknowledges automatically the event.
In manual mode, it is necessary to write a specific command to acknowledge the oldest fault.
(set the bit 14 of control word addressed to 400 h)
3.8.1
Contents
Fault value record n1
Fault value record n2
Fault value record n3
Fault value record n25
7
8
9
10 & 11
12
13
14
15
16
17
18
19
20
21
Contents
Fault number
Event date is depending on address 012Fh format F52:
With private date format: see format F97
With IEC 60870-5-103 format: see format of time
synchronisation address 0800h
Fault date (season)
=
0 winter
=
1 summer
=
2 undefined
Active setting group during the fault (F55)
Phase origin ( F90 )
Fault recording starting origin (see format F61)
Fault value (10: LS word; 11: MS word) (1)
Phase A current value (nominal value)
Phase B current value (nominal value)
Phase C current value (nominal value)
Earth current value (nominal value)
Phase A voltage value (nominal value)
Phase B voltage value (nominal value)
Phase C voltage value (nominal value)
Earth voltage value (nominal value)
Angle between phase A current and phase B-C voltage values
Angle between phase B current and phase C-A voltage values
P12y/EN CT/Fa5
MODBUS DATABASE
Page 54/130
Communications
MiCOM P125-P126-P127
Word Nr.
22
23
24
Contents
Angle between phase C current and phase A-B voltage values
Angle between earth current and earth voltage values
Acknowledgement:
0 = fault not acknowledged
1 = fault acknowledged
(1) Fault value is a CAN value; it has to be processed according to the below formulas to find
corresponding primary value.
Phase current values calculation formula
Line phase current value (primary value) = value x phase primary CT ratio / 800
Earth current values calculation formula
The formula depends of nominal earth current:
0.1 to 40 Ien range
Line earth current value (primary value) = value x earth primary CT ratio / 800
0.01 to 8 Ien range
Line earth current value (primary value) = value x earth primary CT ratio / 3277
0.002 to 1 Ien range
Line earth current value (primary value) = value x earth primary CT ratio / 32700
Phase voltage values calculation formula
The formula depends of nominal phase voltage:
57 to 130 V range
Line phase voltage value (primary value) = value x (phase primary VT ratio / phase
secondary VT ratio) / 63
220 to 480 V range
Line phase voltage value (primary value) = value / 17
Earth voltage values calculation formula
The formula depends of nominal earth voltage:
57 to 130 V range
Line earth voltage value (primary value) = value x (earth primary VT ratio / earth secondary
VT ratio) / 63
220 to 480 V range
Line earth voltage value (primary value) = value / 17
Phase power values calculation formula
The formula depends of nominal phase voltage:
57 to 130 V range
Line phase power value (primary value) = value x (phase primary CT ratio x (phase primary
VT ratio / phase secondary VT ratio)) / (800 x 63)
220 to 480 V range
Line phase power value (primary value) = value x phase primary CT ratio / (800 x 17)
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 55/130
Contents
Oldest fault record
P12y/EN CT/Fa5
MODBUS DATABASE
Page 56/130
Communications
MiCOM P125-P126-P127
3.9
Error counters
3.9.1
Contents
Error counters
Words description:
Word Nr.
1
2
3
4
5
6
7
8
9
10
Contents
Number of errors in page 1
Last error address of page 1
Number of errors in page 2
Last error address of page 2
Number of errors in page 3
Last error address of page 3
Number of errors in calibration page
Last error address of calibration page
Number of data checksum errors
Number of calibration checksum errors
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 57/130
4.
F1
F2
F3
F4
F5
F6
F6A
DESCRIPTION
Unsigned integer: numerical data 0 to 65535
Signed integer: numerical data -32768 to 32767
Unsigned integer: trip / reset curves type (hex values)
000 : DMT
010 : IEC STI
011 : IEC SI
012 : IEC VI
013 : IEC EI
014 : IEC LTI
115: C02
116: IEEE MI
117: CO8
118: IEEE VI
119: IEEE EI
01A: RECT
020 : RI
Unsigned integer: UART Baud rate
0: 300
1: 600
2: 1200
3: 2400
4: 4800
5: 9600
6: 19200
7: 38400
Unsigned integer: Modbus and DNP3 parity bit
0: none
1: even
2: odd
Unsigned integer: conf. tripping on relay RL1, part 1
Bit 0: tI>
Bit 1: tI>>
Bit 2: tI>>>
Bit 3: tIe>
Bit 4: tIe>>
Bit 5: tIe>>>
Bit 6: tI<
Bit 7: trip
Bit 8: broken conductor trip
Bit 9: AUX 1 trip
Bit 10: AUX 2 trip
Bit 11: tI2>
Bit 12: tPe/Iecos>
Bit 13: tPe/Iecos>>
Bit 14: tUe>>>>
Bit 15: Control trip
Unsigned integer: conf. tripping on relay RL1, part 2
Bit 0: tU>
Bit 1: tU>>
Bit 2: tU<
Bit 3: tU<<
Bit 4: t Boolean equation A
Bit 5: t Boolean equation B
Bit 6: t Boolean equation C
Bit 7: t Boolean equation D
Bit 8: tI2>>
Bit 9: tI2>>>
Bit 10: tP>
Bit 11: tP>>
Bit 12: Reserved
Bit 13: AUX 3 trip
Bit 14: AUX 4 trip
Bit 15: SOTF/TOR
P12y/EN CT/Fa5
MODBUS DATABASE
Page 58/130
CODE
F6B
F6C
F6D
F7
Communications
MiCOM P125-P126-P127
DESCRIPTION
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 59/130
F8A
F8B
F8C
DESCRIPTION
Unsigned integer: blocking logic configuration, part 1
Bit 0: tI>+ tI>REV
Bit 1: tI>> + tI>>REV
Bit 2: tI>>> + tI>>>REV
Bit 3: tIe> + tIe>REV
Bit 4: tIe>> + tIe>>REV
Bit 5: tIe>>> + tIe>>>REV
Bit 6: tI<
Bit 7: trip
Bit 8: broken conductor trip
Bit 9: aux1 trip
Bit 10: aux2 trip
Bit 11: tI2>
Bit 12: tPe/Iecos>
Bit 13: tPe/Iecos>>
Bit 14: tUe>>>>
Bit 15: tIe_d> + tIe_d>REV
Unsigned integer: blocking logic configuration, part 2
Bit 0: tU>
Bit 1: tU>>
Bit 2: tU<
Bit 3: tU<<
Bit 4: aux3 trip
Bit 5: aux4 trip
Bit 6: t P<
Bit 7: t P<<
Bit 8: tI2>>
Bit 9: tI2>>>
Bit 10: tP >
Bit 11: tP >>
Bit 12: t Q>
Bit 13: t Q>>
Bit 14: t Q<
Bit 15: t Q<<
Unsigned integer: blocking logic configuration, part 3
Bit 0: tF1
Bit 1: tF2
Bit 2: tF3
Bit 3: tF4
Bit 4: tF5
Bit 5: tF6
Bit 6: Reserve
Bit 7: tIe_d> + tIe_d>REV
Bit 8: tAux 5
Bit 9: tAux 6
Bit 10: tAux 7
Bit 11: tAux 8
Bit 12: tAux 9
Bit 13: tAux A
Bit 14: tAux B
Bit 15: tAux C
Unsigned integer: blocking logic configuration, part 4
Bit 0: df/dt1
Bit 1: df/dt2
Bit 2: df/dt3
Bit 3: df/dt4
Bit 4: df/dt5
Bit 5: df/dt6
Bit 6: tV2>
Bit 7: tV2>>
Bit 8: reserve
Bit 9: reserve
Bit 10: reserve
Bit 11: reserve
Bit 12: reserve
Bit 13: reserve
Bit 14: reserve
Bit 15: reserve
P12y/EN CT/Fa5
MODBUS DATABASE
Page 60/130
CODE
F9
F9A
F9B
F10
F11
F12
Communications
MiCOM P125-P126-P127
DESCRIPTION
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 61/130
F14
F14A
F14B
DESCRIPTION
Unsigned integer: logical outputs status
Bit 0: logical output number RL1 (X1 tripping)
Bit 1: logical output number RL2
Bit 2: logical output number RL3
Bit 3: logical output number RL4
Bit 4: logical output number RL0 (Watch-Dog)
Bit 5: logical output number RL5
Bit 6: logical output number RL6
Bit 7: logical output number RL7
Bit 8: logical output number RL8
Bits 9 to 15: Reserved
Unsigned integer: Rl2 - RL8 output configuration
Bit 0: logical output number RL2 selection
Bit 1: logical output number RL3 selection
Bit 2: logical output number RL4 selection
Bit 3: logical output number RL5 selection
Bit 4: logical output number RL6 selection
Bit 5: logical output number RL7 selection
Bit 6: logical output number RL8 selection
Bits 7 to 15: Reserved
Unsigned integer: Rl2 - RL8 output configuration for CB & SOTF
Bit 0: logical output number RL2 selection (Recloser)
Bit 1: logical output number RL3 selection (Recloser)
Bit 2: logical output number RL4 selection (Recloser)
Bit 3: logical output number RL5 selection (Recloser)
Bit 4: logical output number RL6 selection (Recloser)
Bit 5: logical output number RL7 selection (Recloser)
Bit 6: logical output number RL8 selection (Recloser)
Bit 7: Reserved
Bit 8: logical output number RL2 selection (SOTF)
Bit 9: logical output number RL3 selection (SOTF)
Bit 10: logical output number RL4 selection (SOTF)
Bit 11: logical output number RL5 selection (SOTF)
Bit 12: logical output number RL6 selection (SOTF)
Bit 13: logical output number RL7 selection (SOTF)
Bit 14: logical output number RL8 selection (SOTF)
Bit 15: Reserved
Unsigned integer: Rl2 - RL8 output configuration for tAux3 & tAux4
Bit 0: logical output number RL2 selection (tAux3)
Bit 1: logical output number RL3 selection (tAux3)
Bit 2: logical output number RL4 selection (tAux3)
Bit 3: logical output number RL5 selection (tAux3)
Bit 4: logical output number RL6 selection (tAux3)
Bit 5: logical output number RL7 selection (tAux3)
Bit 6: logical output number RL8 selection (tAux3)
Bit 7: Reserved
Bit 8: logical output number RL2 selection (tAux4)
Bit 9: logical output number RL3 selection (tAux4)
Bit 10: logical output number RL4 selection (tAux4)
Bit 11: logical output number RL5 selection (tAux4)
Bit 12: logical output number RL6 selection (tAux4)
Bit 13: logical output number RL7 selection (tAux4)
Bit 14: logical output number RL8 selection (tAux4)
Bit 15: Reserved
P12y/EN CT/Fa5
MODBUS DATABASE
Page 62/130
CODE
F14C
F14D
F15
F15A
Communications
MiCOM P125-P126-P127
DESCRIPTION
Unsigned integer: Rl2 - RL8 output configuration for Control Trip & Close
Bit 0: logical output number RL2 selection (Control Trip)
Bit 1: logical output number RL3 selection (Control Trip)
Bit 2: logical output number RL4 selection (Control Trip)
Bit 3: logical output number RL5 selection (Control Trip)
Bit 4: logical output number RL6 selection (Control Trip)
Bit 5: logical output number RL7 selection (Control Trip)
Bit 6: logical output number RL8 selection (Control Trip)
Bit 7: Reserved
Bit 8: logical output number RL2 selection (Control Close)
Bit 9: logical output number RL3 selection (Control Close)
Bit 10: logical output number RL4 selection (Control Close)
Bit 11: logical output number RL5 selection (Control Close)
Bit 12: logical output number RL6 selection (Control Close)
Bit 13: logical output number RL7 selection (Control Close)
Bit 14: logical output number RL8 selection (Control Close)
Bit 15: Reserved
Unsigned integer: RL2 - RL8 output configuration for recloser trip final & locked
Bit 0: logical output number RL2 selection (recloser trip final)
Bit 1: logical output number RL3 selection (recloser trip final)
Bit 2: logical output number RL4 selection (recloser trip final)
Bit 3: logical output number RL5 selection (recloser trip final)
Bit 4: logical output number RL6 selection (recloser trip final)
Bit 5: logical output number RL7 selection (recloser trip final)
Bit 6: logical output number RL8 selection (recloser trip final)
Bit 7: Reserved
Bit 8: logical output number RL2 selection (recloser internaly locked)
Bit 9: logical output number RL3 selection (recloser internaly locked)
Bit 10: logical output number RL4 selection (recloser internaly locked)
Bit 11: logical output number RL5 selection (recloser internaly locked)
Bit 12: logical output number RL6 selection (recloser internaly locked)
Bit 13: logical output number RL7 selection (recloser internaly locked)
Bit 14: logical output number RL8 selection (recloser internaly locked)
Bit 15: Reserved
Unsigned integer: digital inputs configuration, part 1
Bit 0: auxuliary relays de-latching command
Bit 1: O/O (52A)
Bit 2: F/O (52B)
Bit 3: CB Flt
Bit 4: aux 1
Bit 5: aux 2
Bit 6: blocking logic 1
Bit 7: blocking logic 2
Bit 8: disturbance start
Bit 9: cold load start
Bit 10: digital selection 1
Bit 11: digital selection 2
Bit 12: settings group change (configuration must be equal to INPUT)
Bit 13: recloser latched
Bit 14: reset thermal status
Bit 15: control tripping circuit
Unsigned integer: digital inputs configuration, part 2
Bit 0: start Breaker Failure timer
Bit 1: maintenance mode
Bit 2: aux 3
Bit 3: aux 4
Bit 4: Reserved
Bit 5: SOTF (ex Manual close)
Bit 6: Local mode
Bit 7: Synchronization.
Bit 8: aux 5
Bit 9: aux 6
Bit A: aux 7
Bit B: aux 8
Bit C: aux 9
Bit D: aux A
Bit E: aux B
Bit F: aux C
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 63/130
F16
F17
F18
F18A
F19
DESCRIPTION
Unsigned integer: digital inputs configuration, part 3
Bit 0: Ctrl Trip
Bit 1: Ctrl Close
Bit 2: Led reset
Bit 3: Reserve 33
Bit 4: Reserve 34
Bit 5: Reserve 35
Bit 6: Reserve 36
Bit 7: Reserve 37
Bit 8: Reserve 38
Bit 9: Reserve 39
Bit A: Reserve 3A
Bit B: Reserve 3B
Bit C: Reserve 3C
Bit D: Reserve 3D
Bit E: Reserve 3E
Bit F: Reserve 3F
Unsigned integer: earth threshold (current, voltage & power) information status
Bit 0: info limit exceeding
Bits 1 to 3: Reserved
Bit 4: Ie> Interlock activated
Bit 5: info start
Bit 6: info tripping
Bit 7: info tripping reverse mode
Bits 8 to 15: Reserved
Unsigned integer: phase threshold (current, voltage & power) information status
Bit 0: info limit exceeding
Bit 1: phase A (or AB) trip
Bit 2: phase B (or BC) trip
Bit 3: phase C (or CA) trip
Bit 4: I> Interlock activated
Bit 5: info start
Bit 6: info tripping
Bit 7: info tripping reverse mode
Bits 8 to 15: Reserved
Signed long integer: numeric data: -2E31 to (2E31 1)
Unsigned long integer: numeric data: 0 to (2E32 -1)
Unsigned integer: leds configuration mask, part 1
Bit 0: I>
Bit 1: tI>
Bit 2: I>>
Bit 3: tI>>
Bit 4: I>>>
Bit 5: tI>>>
Bit 6: Ie>
Bit 7: tIe>
Bit 8: Ie>>
Bit 9: tIe>>
Bit 10: Ie>>>
Bit 11: tIe>>>
Bit 12: trip
Bit 13: tI2>
Bit 14: broken conductor trip
Bit 15: breaker failure trip
P12y/EN CT/Fa5
MODBUS DATABASE
Page 64/130
CODE
F19A
F19B
F19C
F19D
Communications
MiCOM P125-P126-P127
DESCRIPTION
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 65/130
F19F
F19G
F20
DESCRIPTION
Unsigned integer: leds configuration mask, part 6
Bit 0: Equ. A
Bit 1: Equ. B
Bit 2: Equ. C
Bit 3: Equ. D
Bit 4: Equ. E
Bit 5: Equ. F
Bit 6: Equ. G
Bit 7: Equ. H
Bit 8: tAux 5 (P126-P127).
Bit 9: tAux 6 (P126-P127).
Bit 10: tAux 7 (P126-P127).
Bit 11: tQ>>
Bit 12: Q<
Bit 13: tQ<
Bit 14: Q<<
Bit 15: tQ<<
Unsigned integer: leds configuration mask, part 7
(only with p127 optional board)
Bit 0: t Aux 8
Bit 1: t Aux 9
Bit 2: t Aux A
Bit 3: t Aux B
Bit 4: t Aux C
Bit 5: reserve
Bit 6: reserve
Bit 7: reserve
Bit 8: digital input 8
Bit 9: digital input 9
Bit 10: digital input A
Bit 11: digital input B
Bit 12: digital input C
Bit 13: reserve
Bit 14: reserve
Bit 15: reserve
Unsigned integer: leds configuration mask, part 8
Bit 0: df/dt1
Bit 1: df/dt2
Bit 2: df/dt3
Bit 3: df/dt4
Bit 4: df/dt5
Bit 5: df/dt6
Bit 6: Ie_d>
Bit 7: tIe_d>
Bit 8: CTS
Bit 9: [79] Ext locked
Bit 10: Ie_d>>
Bit 11: tIe_d>>
Bit 12: V2>
Bit 13: tV2>
Bit 14: V2>>
Bit 15: tV2>>
Unsigned integer: logical inputs state, part 1
Bit 0: logic selection 1
Bit 1: logic selection 2
Bit 2: relays de-latching
Bit 3: CB position (52a)
Bit 4: CB position (52b)
Bit 5: external CB failure
Bit 6: aux 1
Bit 7: aux 2
Bit 8: blocking logic 1
Bit 9: blocking logic 2
Bit 10: disturbance recording start
Bit 11: cold load start
Bit 12: settings group change
Bit 13: recloser locked
Bit 14: thermal status reset
Bit 15: trip circuit supervision
P12y/EN CT/Fa5
MODBUS DATABASE
Page 66/130
CODE
F20A
F20B
F21
F22
F23
F24
F24A
F24B
F24C
F25
F26
F27
Communications
MiCOM P125-P126-P127
DESCRIPTION
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 67/130
F31
F31A
F31B
F32
F33
F34
F35
F36
DESCRIPTION
Reserved
Unsigned integer: Modbus and DNP3 stop bits number
0: one stop bit
1: two stop bits
Unsigned integer: communication status (IEC 60870-5-103 protocol)
Bit 0: communication RS485 port 1 available if = 1
Bit 1: obsolete (previously IEC 60870-5-103 protocol private option)
Bit 2: communication RS232 available if = 1
Bit 3: communication RS485 port 2 available if = 1
Unsigned integer: numbers of available disturbance records
0: no records available
1: one events record available
2: two events records available
3: three events records available
4: four events records available
5: five events records available
Unsigned integer: numbers of default records to display
1: First record (the oldest)
P12y/EN CT/Fa5
MODBUS DATABASE
Page 68/130
CODE
F36A
F36B
F36C
F36D
Communications
MiCOM P125-P126-P127
DESCRIPTION
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 69/130
F36F
F36G
F37
DESCRIPTION
Unsigned integer: non acknowledged memorised alarms flags, part 6
Bit 0: AUX5 trip
Bit 1: AUX6 trip
Bit 2: AUX7 trip
Bit 3: AUX8 trip
Bit 4: AUX9 trip
Bit 5: AUXA trip
Bit 6: AUXB trip
Bit 7: AUXC trip
Bit 8: P<
Bit 9: tP<
Bit 10: P<<
Bit 11: tP<<
Bit 12: Q>
Bit 13: tQ>
Bit 14: Q>>
Bit 15: tQ>>
Unsigned integer: non acknowledged memorised alarms flags, part 7
Bit 0: Q<
Bit 1: tQ<
Bit 2: Q<<
Bit 3: tQ<<
Bit 4: dfdt1
Bit 5: dfdt2
Bit 6: dfdt3
Bit 7: dfdt4
Bit 8: dfdt5
Bit 9: dfdt6
Bit 10: Recloser externally locked
Bit 11: Ctrl Trip
Bit 12: CTS
Bit 13: Ie_d>>
Bit 14: tIe_d>>
Bit 15: Not used
Unsigned integer: non acknowledged memorised alarms flags, part 8
Bit 0: V2>
Bit 1: t V2>
Bit 2: V2>>
Bit 3: t V2>>
Bit 4: not used
Bit 5: not used
Bit 6: not used
Bit 7: not used
Bit 8: not used
Bit 9: not used
Bit 10: not used
Bit 11: not used
Bit 12: not used
Bit 13: not used
Bit 14: not used
Bit 15: not used
Unsigned integer: thermal overload information
Bit 0: thermal overload alarm
Bit 1: thermal overload trip
Bits 2 to 15: Reserved
P12y/EN CT/Fa5
MODBUS DATABASE
Page 70/130
CODE
F38
F38A
F38B
F39
Communications
MiCOM P125-P126-P127
DESCRIPTION
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 71/130
F41
F42
F43
F44
F45
F46
DESCRIPTION
Unsigned integer: selective scheme logic configuration
Bit 0: tI>>
Bit 1: tI>>>
Bit 2: tIe>>
Bit 3: tIe>>>
Bit 4: tIe_d>
Bit 5: tIe_d>>
Bit 6: not used
Bit 7: not used
Bit 8: not used
Bit 9: not used
Bit 10: not used
Bit 11: not used
Bit 12: not used
Bit 13: not used
Bit 14: not used
Bit 15: not used
Unsigned integer: remote communication configuration
0: front and rear MODBUS
1: front MODBUS rear IEC 60870-5-103
2: front MODBUS rear COURIER
3: front MODBUS rear DNP3
Unsigned integer: max & average current + voltage time window selection (dec values)
5: 5 min
10: 10 min
15: 15 min
30: 30 min
60: 60 min
Unsigned integer
Bit 0: CB operating time overreach
Bit 1: CB operation number overreach
Bit 2: square Amps sum overreach
Bit 3: trip circuit supervision
Bit 4: CB closing time overreach
Bit 5: recloser internaly locked
Bit 6: recloser successful
Bit 7: recloser in progress
Bit 8: closing command issued from recloser cycle
Bit 9: recloser configuration error
Bit 10: recloser in service (IEC 60870-5-103 protocol)
Bits 11: recloser final trip
Bit 12: "CB operations number / time" overreach
Bit 13: Recloser external locked
Bit 14: Recloser reinitialized
Bit 15: Not used
Reserved
Unsigned integer: HW alarm relay status
Bit 0: Watch-Dog operating
Bit 1: communication failure
Bit 2: data failure
Bit 3: analogue failure
Bit 4: datation failure
Bit 5: calibration failure
Bit 6: record data failure
Bit 7: Reserved
Bit 8: Reserved
Bit 9: factory alarm (default factory configuration reloaded)
Bit 10: main power supply
Bit 11: auxilliary power supplies
Bit 12: transformers offset failure
Bits 13 to 15: Reserved
Unsigned integer: Ie harmonic content extraction
Bit 0: calculation active
Bits 1 to 15: Reserved
P12y/EN CT/Fa5
MODBUS DATABASE
Page 72/130
CODE
F47
F48
F49
F50
F51
F52
F53
Communications
MiCOM P125-P126-P127
DESCRIPTION
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 73/130
F54A
F54B
F55
F56
DESCRIPTION
Unsigned integer: Digital inputs configuration mode, part 1:
Bit x = 0 level / 1 edge
Bit 0: logic selection 1; operating only on level; not configurable (0)
Bit 1: logic selection 2; operating only on level; not configurable (0)
Bit 2: relays de-latching; operating only on level; not configurable (0)
Bit 3: CB position (52a) ; operating only on level; not configurable (0)
Bit 4: CB position (52b) ; operating only on level; not configurable (0)
Bit 5: external CB failure; operating only on level; not configurable (0)
Bit 6: tAux 1; operating only on level; not configurable (0)
Bit 7: tAux 2; operating only on level; not configurable (0)
Bit 8: blocking logic 1; operating only on level; not configurable (0)
Bit 9: blocking logic 2; operating only on level; not configurable (0)
Bit 10: disturbance recording start; operating only on edge; not configurable (1)
Bit 11: cold load start; operating only on level; not configurable (0)
Bit 12: settings group change ; Attention: 0 Input / 1 Menu
Bit 13: recloser locked; operating only on level; not configurable (0)
Bit 14: thermal status reset; operating only on edge; not configurable (1)
Bit 15: trip circuit supervision; operating only on level; not configurable (0)
Unsigned integer: Digital inputs configuration mode, part2:
Bit x = 0 level / 1 edge
Bit 0: start Breaker Failure timer; operating only on level; not configurable (0)
Bit 1: maintenance mode; operating only on level; not configurable (0)
Bit 2: tAux 3; operating only on level; not configurable (0)
Bit 3: tAux 4; operating only on level; not configurable (0)
Bit 4: Reserved
Bit 5: Manual close; operating only on level; not configurable (0)
Bit 6: Local mode; operating only on level; not configurable (0)
Bit 7: Synchronisation; operating only on level; not configurable (0)
Bit 8: tAux 5
Bit 9: tAux 6
Bit 10: tAux 7
Bit 11: tAux 8
Bit 12: tAux 9
Bit 13: tAux A
Bit 14: tAux B
Bit 15: tAux C
Unsigned integer: Digital inputs configuration mode, part3:
Bit x = 0 level / 1 edge
Bit 0: Control trip(1)
Bit 1: Control close(1)
Bit 2: Leds reset(0)
Bits 3 to 15: Not used
Unsigned integer: active group
Group change format ( unsigned integer )
0:
toggle from group 1 to group 2
1
group 1
2
group 2
3
group 3
4
group 4
5
group 5
6
group 6
7
group 7
8
group 8
Unsigned integer: Fail safe and inversion relays
bit x = 0: relay normally de-energized.
bit x = 1: relay normally energized.
bit 0: Fail safe logical output number RL1 (tripping)
bit 1: Fail safe logical output number RL2
bit 2: Inversion logical output number RL3
bit 3: Inversion logical output number RL4
bit 4: Inversion logical output number RL5
bit 5: Inversion logical output number RL6
bit 6: Inversion logical output number RL7
bit 7: Inversion logical output number RL8
bits 8 15: Reserved
P12y/EN CT/Fa5
MODBUS DATABASE
Page 74/130
CODE
F57
F58
F59
F60
Communications
MiCOM P125-P126-P127
DESCRIPTION
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 75/130
DESCRIPTION
Unsigned integer: Information on the starting origin of the RL1 trip relay
01 - Remote X1 trip
02 - trip (Thermal overload)
03 - I> trip
04 - I>> trip
05 - I>>> trip
06 - Ie> trip
07 - Ie>> trip
08 - Ie>>> trip
09 - I< trip
10 - Broken conductor trip
11 - U< trip
12 - U<< trip
13 - Pe/Iecos> trip
14 - Pe/Iecos>> trip
15 - I2> trip
16 - I2>> trip
17 - I2>>> trip
18 - U> trip
19 - U>> trip
20 - Ue>>>> trip
21 - Aux 1 trip
22 - Aux 2 trip
23 - AND Logic equate A trip
24 - AND Logic equate B trip
25 - AND Logic equate C trip
26 - AND Logic equate D trip
27 - Aux 3 trip
28 - Aux 4 trip
29 - SOTF
30 - P >
31 - P >>
32 - f1
33 - f2
34 f3
35 f4
36 f5
37 f6
38 - AND Logic equate E trip
39 - AND Logic equate F trip
40 - AND Logic equate G trip
41 - AND Logic equate H trip
42 - t Aux 5 ( P126-7 )
43 - t Aux 6 ( P126-7 )
44 - t Aux 7 ( P126-7 )
45 - t Aux 8 ( P127 with logical inputs 8-12 )
46 - t Aux 9 ( P127 with logical inputs 8-12 )
47 - t Aux A ( P127 with logical inputs 8-12 )
48 - t Aux B ( P127 with logical inputs 8-12 )
49 - t Aux C ( P127 with logical inputs 8-12 )
50 - Ie_d> trip
51 - P <
52 - P <<
53 - Q >
54 - Q >>
55 - Q <
56 - Q <<
57 df/dt1
58 df/dt2
59 df/dt3
60 df/dt4
61 df/dt5
62 df/dt6
63 Ie_d>> trip
64 V2> trip
65 V2>> trip
P12y/EN CT/Fa5
MODBUS DATABASE
Page 76/130
CODE
F62
F63
F64
F64A
Communications
MiCOM P125-P126-P127
DESCRIPTION
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 77/130
F65
F66
F67
F68
F69
F70
F71
DESCRIPTION
Unsigned integer: Alarms inhibition part 3
Bit 0: F1 alarm inhibited
Bit 1: F2 alarm inhibited
Bit 2: F3 alarm inhibited
Bit 3: F4 alarm inhibited
Bit 4: F5 alarm inhibited
Bit 5: F6 alarm inhibited
Bit 6: F out inhibited
Bit 7: tU> inhibited
Bit 8: tU>> inhibited
Bit 9: tV2> inhibited
Bit 10: tV2>> inhibited
Bits 11 to 15: Not used
Unsigned integer: VTS conv. directional to non-dir
Bit 0: VTS I> non-Dir ? yes/no
Bit 1: VTS I>> non-Dir ? yes/no
Bit 2: VTS I>>> non-Dir ? yes/no
Bit 3: VTS Ie> non-Dir ? yes/no
Bit 4: VTS Ie>> non-Dir ? yes/no
Bit 5: VTS Ie>>> non-Dir ? yes/no
Bit 6: VTS Ie_d> non-Dir ? yes/no
Bit 7: VTS Ie_d>> non-Dir ? yes/no
Bits 8 to 15: Reserved
Unsigned integer: phase rotation
Value 0: Normal , A_B_C
Value 1: Reverse , A_C_B
Unsigned integer: frequency protection
Bit 0: information first crossing threshold
Bit 1: information of starting (second crossing)
Bit 2: information of tripping
Bit 3 to 15: Reserved
Unsigned integer: frequency operating mode
0: No
1: Protection under frequency 81<
2: Protection over frequency 81>
Unsigned integer: frequency measurement status
Bit 0: F out
Bit 1: F out because of U min
Unsigned integer: 1st Operator for Boolean equations
0: Nothing
1: NOT
Unsigned integer: Other than 1st Operator for Boolean equations
0: OR
1: OR NOT
2: AND
3: AND NOT
P12y/EN CT/Fa5
MODBUS DATABASE
Page 78/130
CODE
F72
Communications
MiCOM P125-P126-P127
DESCRIPTION
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 79/130
DESCRIPTION
Unsigned integer: Operand for Boolean equations
27: U>
28: tU>
29: U>>
30: tU>>
31: U<
32: tU<
33: U<<
34: tU<<
35: Ue>>>>
36: tUe>>>>
37: Broken conductor
38: Tripping 79
39: tAux1
40: tAux2
41: tAux3
42: tAux4
43: P>
44: tP>
45: P>>
46: tP>>
47: F1
48: tF1
49: F2
50: tF2
51: F3
52: tF3
53: F4
54: tF4
55: F5
56: tF5
57: F6
58: tF6
59: VTS
60: tAux 5 ( P126-P127 )
61: tAux 6 ( P126-P127 )
62: tAux 7 ( P126-P127 )
63: tAux 8 (P127 with logical inputs 8-12)
64: tAux 9 (P127 with logical inputs 8-12)
65: tAux A (P127 with logical inputs 8-12)
66: tAux B (P127 with logical inputs 8-12)
67: tAux C (P127 with logical inputs 8-12)
68: Input 1
69: Input 2
70: Input 3
71: Input 4
72: Input 5( P126-P127 )
73: Input 6( P126-P127 )
74: Input 7( P126-P127 )
75: Input 8 (P127 with Inputs 8-12)
76: Input 9 (P127 with Inputs 8-12)
77: Input A (P127 with Inputs 8-12)
78: Input B (P127 with Inputs 8-12)
79: Input C (P127 with Inputs 8-12)
80: Ie_d>
81: tIe_d>
82: [79] int. lock
83: [79] ext. lock
84: tEquation A
85: tEquation B
86: tEquation C
87: tEquation D
88: tEquation E
89: tEquation F
90: tEquation G
91: tEquation H
92: CB Fail
P12y/EN CT/Fa5
MODBUS DATABASE
Page 80/130
CODE
F72
(following)
F73
F74
F75
F76
F77
F78
F79
Communications
MiCOM P125-P126-P127
DESCRIPTION
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 81/130
F82
F83
F84
F85
F86
F87
F88
F89
DESCRIPTION
Unsigned integer: Optional board
bit 0: logical input 8 to 12 present
bit 1: IRIG-B + RS485_2 ( second rs485 rear port ) presents
Unsigned integer: Keyboard remote control word.
Only one bit simultaneously. The bit active simulate a pressure on the key.
bit 0: CLEAR key
bit 1: ALARM key
bit 2: UP key
bit 3: RIGHT key
bit 4: ENTER key
bit 5: DOWN key
bit 6: LEFT key
bit 7:
bit 8:
bit 9:
bit 10:
bit 11:
bit 12:
bit 13:
bit 14:
bit 15: Dialog re-init (factory test reserved)
SOTF parameters: Closing orders types for SOTF starting
Bit 0: Front port communication order
Bit 1: Rear port communication order
Bit 2: "Ctrl Close" logical input
Bit 3: "SOTF" logical input
Bit 4: Reclosing ordered by Autorecloser
Bit 5: Reclosing ordered by HMI
BIT 6: Rear port 2 (optional) communication order (P127 only)
Unsigned integer: Inrush blocking configuration
bit 0: I>
bit 1: I>>
bit 2: I>>>
bit 3: Ie>
bit 4: Ie>>
bit 5: Ie>>>
bit 6: reserved
bit 7: reserved
bit 8: reserved
bit 9: reserved
bit 10: reserved
bit 11: I2>
bit 12: I2>>
bit 13: I2>>>
bit 14: Ie_d>
bit 15: Ie_d>>
VT protection
0: V P-P
1: V P-N
Phases and Earth labels
0: L1, L2, L3, N
1: A, B, C, o
2: R, S, T, E
U< and U<< inhibition by 52a
Bit 0: U< inhibited
Bit 1: U<< inhibited
Unsigned integer: Cold load start starting mode
Bit 0: Detection with CLPU input
Bit 1: Automatic detection
IEEE 32 bits floating-point format
Default availlable range from + 3.2 E+38 to - 3.2 E+38
IEEE 64 bits floating-point format
P12y/EN CT/Fa5
MODBUS DATABASE
Page 82/130
CODE
F90
F91
F92
F93
F94
F95
F96
F97
F98
F99
Communications
MiCOM P125-P126-P127
DESCRIPTION
Phase designation
0 = none
1
= phase A
2
= phase B
3
= phase C
4
= phases A-B
5
= phases B-C
6
= phases C-A
7
= phases A-B-C
8 = earth
Measurement mode
1
Quadrant 1
2
Quadrant 2
3
Quadrant 3
4
Quadrant 4
P: direct Q: inverted
P: inverted
Q: direct
P: inverted
Q: inverted
P: direct Q: direct
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 83/130
4.1.1
4.1.2
1.
(optional):
2.
(compulsory):
Send a request with the record number and the channel number.
3.
(compulsory): Send one or several requests to upload the disturbance record data. It
depends of the number of samples.
4.
(compulsory):
Function code
03h
Word address
3Dh
00
Word number
00
24h
CRC
xx
xx
This request may generate an error message with the error code:
EVT_NOK(OF):
NOTE:
4.1.3
No record available
If there are less than 5 records available, the answer will contain zero in
non-used words.
Service requests
This request must be sent before uploading the disturbance record channel samples. It
allows knowing the record number and the channel number to upload.
It allows also knowing the number of samples in the channel.
Slave number
xx
Function code
03h
Word address
Word number
Refer to mapping 00
13h
CRC
xx
xx
This request may generate an error message with two different error codes:
4.1.4
CODE_DEF_RAM(02):
failure
CODE_EVT_NOK(03):
Function code
03h
Word address
Word number
CRC
xx
xx
This request may geberate an error message with two different error codes:
4.1.5
CODE_DEP_DATA(04):
CODE_SERV_NOK(05):
channel
Function code
03h
Word address
22h
00
Word number
00
07h
CRC
xx
xx
channel
the
P12y/EN CT/Fa5
MODBUS DATABASE
Page 84/130
4.1.6
Communications
MiCOM P125-P126-P127
Slave number
xx
Function code
03h
Word address
36h
00
Word number
00
09h
CRC
xx............xx
This event request may generate an error message with the error code:
EVT_EN_COURS_ECRIT (5):
NOTE:
4.1.7
Function code
03h
Word address
Refer to mapping
Word number
00
09h
CRC
xx............xx
This event request may generate an error message with the error code:
EVT_EN_COURS_ECRIT (5):
NOTE:
4.1.8
Communications
P12y/EN CT/Fa5
MODBUS DATABASE
Page 85/130
Function code
03h
NOTE:
Word address
3Eh
00
Word number
00
18h
CRC
xx............xx
4.1.8.2
Function code
03h
NOTE:
Word address
Refer to mapping
Word number
00
18h
CRC
xx............xx
This fault value retrieval does not acknowledge this fault record.
Communications
MiCOM P125/P126 & P127
P12y/EN CT/Fa5
IEC 60870-5-103 DATABASE
Page 87/130
IEC 60870-5-103
DATABASE
MiCOM P125-P126-P127 V15
P12y/EN CT/Fa5
IEC 60870-5-103 DATABASE
Page 88/130
Communications
MiCOM P125/P126 & P127
BLANK PAGE
Communications
MiCOM P125/P126 & P127
P12y/EN CT/Fa5
IEC 60870-5-103 DATABASE
Page 89/130
CONTENTS
1.
91
1.1
General information
91
1.2
Spontaneous messages
91
1.2.1
91
1.3
System state
97
1.4
Processed commands
102
1.4.1
System commands
102
1.4.2
General commands
102
1.4.3
103
1.5
Relay reinitialisation
105
1.6
Cyclic Messages
105
1.7
107
1.8
109
P12y/EN CT/Fa5
IEC 60870-5-103 DATABASE
Page 90/130
Communications
MiCOM P125-P126-P127
BLANK PAGE
Communications
P12y/EN CT/Fa5
IEC 60870-5-103 DATABASE
Page 91/130
1.
1.1
General information
Messages representation is expressed with the associated:
1.2
INFORMATION NUMBER:
INF
ASDU TYPE:
TYP
CAUSE OF TRANSMISSION:
COT
FUNCTION NUMBER:
FUN .
Spontaneous messages
These messages include a sub-assembly of the events, which are generated on the relay.
The messages considered are concerning highest priority events.
An event is always generated on the rising edge of the information; some can be generated also on
falling edge.
In the list below, events generated only on rising edge will be tagged with a *.
1.2.1
In the following list of processed events, FUNCTION NUMBERS (FUN) 160 and 161 are used for
Public range, respectively for current and voltage protections data, and FUNCTION NUMBERS
(FUN) 168 and 169 are used for Private range, respectively for current and voltage protections
data.
Status indications (monitor direction):
P127 + P126 + P125
LEDS reset:
Auxiliary input 1:
Auxiliary input 2:
Auxiliary input 3:
Auxiliary input 4:
P12y/EN CT/Fa5
IEC 60870-5-103 DATABASE
Page 92/130
Communications
MiCOM P125-P126-P127
Logical input 1:
Logical input 2:
Logical input 3:
Logical input 4:
Logical output 1:
Logical output 2:
Logical output 3:
Logical output 4:
Watch Dog:
Logical output 5:
Logical output 6:
Time synchronisation:
Logical selectivity 1:
Logical selectivity 2:
Logical blocking 1:
Logical blocking 2:
Latch relays:
Unlock relays:
General Reset:
P127 + P126
Autorecloser active:
Auxiliary input 5:
Auxiliary input 6:
Auxiliary input 7:
Logical input 5:
Logical input 6:
Logical input 7:
Logical output 7:
Logical output 8:
Auxiliary input 8:
Auxiliary input 9:
Logical input 8:
Communications
MiCOM P125/P126 & P127
P12y/EN CT/Fa5
IEC 60870-5-103 DATABASE
Page 93/130
Logical input 9:
Logical input A:
Logical input B:
Logical input C:
P127 only
Start IN>:
Start IN>>:
Start IN>>>:
Start / pick-up N:
Start UN>>>>:
Start PN>:
Start PN>>:
P127 + P126
Start I>:
Start I>>:
Start I>>>:
Start I<:
Start I2>:
Start I2>>:
Start I2>>>:
Start Therm:
P12y/EN CT/Fa5
IEC 60870-5-103 DATABASE
Page 94/130
Communications
MiCOM P125-P126-P127
CB Operating time:
CB Operation number:
SA2n:
CB Closing time:
Start tBF:
P127 only
Start IN>>>>:
Start U<:
Start U<<:
Start U>:
Start U>>:
Start VTS:
Start V2>:
Start V2>>:
Start CTS:
Start P>:
Start P>>:
Start P<:
Start P<<:
Start Q>:
Start Q>>:
Start Q<:
Start Q<<:
Blocking Inrush:
Start F1:
Start F2:
Start F3:
Start F4:
Start F5:
Start F6:
Communications
MiCOM P125/P126 & P127
P12y/EN CT/Fa5
IEC 60870-5-103 DATABASE
Page 95/130
Start / pick-up N:
General Trip:
Trip IN>:
Trip IN>>:
Trip IN>>>:
Trip UN>>>>:
Trip PN>:
Trip PN>>:
P127 + P126
Trip L1:
Trip L2:
Trip L3:
Trip I>:
Trip I>>:
Trip I>>>:
Trip I<:
Trip I2>:
Trip I2>>:
Trip I2>>>:
Trip Therm:
SOTF trip:
P12y/EN CT/Fa5
IEC 60870-5-103 DATABASE
Page 96/130
Communications
MiCOM P125-P126-P127
P127 only
Trip IN>>>>:
Trip U<:
Trip U<<:
Trip U>:
Trip U>>:
Trip P>:
Trip P>>:
Trip P<:
Trip P<<:
Trip Q>:
Trip Q>>:
Trip Q<:
Trip Q<<:
Trip F1:
Trip F2:
Trip F3:
Trip F4:
Trip F5:
Trip F6:
Trip dFdT1:
Trip dFdT2:
Trip dFdT3:
Trip dFdT4:
Trip dFdT5:
Trip dFdT6:
Autorecloser successful:
Communications
P12y/EN CT/Fa5
IEC 60870-5-103 DATABASE
Page 97/130
1.3
Trip TC:
Close TC:
System state
It is given in the answer to the General Interrogation (GI).
Relay state information is Class 1 data, they are systematically sent to the master station, during a
General Interrogation.
The list of processed data, following a General Interrogation, is given below; it is a sub-assembly of
the spontaneous messages list, so like spontaneous messages, these data are generated on rising
and falling edge.
The following indications are sent to the master station if the option Basic or Advanced
GI is chosen in the COMMUNICATION / GI Select menu.
Status indications (monitor direction):
P127 + P126 + P125
Auxiliary input 1:
Auxiliary input 2:
Auxiliary input 3:
Auxiliary input 4:
Auxiliary input 5:
Auxiliary input 6:
Auxiliary input 7:
Logical input 1:
Logical input 2:
Logical input 3:
Logical input 4:
Logical input 5:
Logical output 1:
Logical output 2:
Logical output 3:
Logical output 4:
Logical output 5:
Logical output 6:
P12y/EN CT/Fa5
IEC 60870-5-103 DATABASE
Page 98/130
Communications
MiCOM P125-P126-P127
P127 + P126
Autorecloser active:
Auxiliary input 5:
Auxiliary input 6:
Auxiliary input 7:
Logical input 6:
Logical input 7:
Logical output 7:
Logical output 8:
Auxiliary input 8:
Auxiliary input 9:
Logical input 8:
Logical input 9:
Logical input A:
Logical input B:
Logical input C:
P127 only
Start / pick-up N:
Start IN>:
Communications
MiCOM P125/P126 & P127
P12y/EN CT/Fa5
IEC 60870-5-103 DATABASE
Page 99/130
Start IN>>:
Start IN>>>:
Start UN>>>>:
Start PN>:
Start PN>>:
P127 + P126
Start I>:
Start I>>:
Start I>>>:
Start I<:
Start I2>:
Start I2>>:
Start I2>>>:
Start Therm:
P127 only
Start IN>>>>:
Start U>:
Start U>>:
Start U<:
Start U<<:
Start CTS:
Start VTS:
Start V2>:
Start V2>>:
Blocking Inrush:
Start F1:
Start F2:
Start F3:
Start F4:
Start F5:
Start F6:
Start P>:
Start P>>:
Start P<:
P12y/EN CT/Fa5
IEC 60870-5-103 DATABASE
Page 100/130
Communications
MiCOM P125-P126-P127
Start P<<:
Start Q>:
Start Q>>:
Start Q<:
Start Q<<:
General Trip:
Trip IN>:
Trip IN>>:
Trip IN>>>:
Trip UN>>>>:
Trip PN>:
Trip PN>>:
Trip L1:
Trip L2:
Trip L3:
Trip I>:
Trip I>>:
Trip I>>>:
Trip I<:
Trip I2>:
Trip I2>>:
Trip I2>>>:
Trip Therm:
Broken conductor:
SOTF trip:
Communications
MiCOM P125/P126 & P127
P12y/EN CT/Fa5
IEC 60870-5-103 DATABASE
Page 101/130
Trip IN>>>>:
Trip U<:
Trip U<<:
Trip U>:
Trip U>>:
Trip P>:
Trip P>>:
Trip P<:
Trip P<<:
Trip Q>:
Trip Q>>:
Trip Q<:
Trip Q<<:
Trip F1:
Trip F2:
Trip F3:
Trip F4:
Trip F5:
Trip F6:
Trip dFdT1:
Trip dFdT2:
Trip dFdT3:
Trip dFdT4:
Trip dFdT5:
Trip dFdT6:
P12y/EN CT/Fa5
IEC 60870-5-103 DATABASE
Page 102/130
1.4
Processed commands
1.4.1
System commands
Communications
MiCOM P125-P126-P127
General commands
Control direction: ASDU 20
P127 + P126 + P125
Trip TC:
Close TC:
Unlock relays:
General Reset:
P127 + P126
Auto-recloser On / Off:
tCOMM1 order:
tCOMM2 order:
tCOMM3 order:
tCOMM4 order:
Communications
P12y/EN CT/Fa5
IEC 60870-5-103 DATABASE
Page 103/130
This command must be used in association with data mapped at address 664h (source setting
group) and 665h (destination setting group).
After executing one of these commands, the relay sends an acknowledgement message, which
contains the result of command execution.
If a state change is the consequence of the command, it must be sent in a ASDU 1 with COT 12
(remote operation).
If the relay receives another command message from the master station before sending the
acknowledgement message, it will be discarded.
Commands which are not processed by the relay are rejected with a negative acknowledgement
message.
1.4.3
1.4.3.1
FUN and INF: same definition than ASDU 140, parameter is transmitted first low-byte, then high
byte, then a 4 byte time tag is transmitted.
This ASDU is used for all parameter pages: 1, 2, 3, 5, 6, 36 (group 1), 38 (group 2), 40 (group 3),
42 (group 4), 44 (group 5), 46 (group 6), 48 (group 7) and 50 (group 8).
FUN and INF: same definition than ASDU 140, parameter is transmitted in MW field, first low-byte,
then high byte, then a 4 byte time tag is transmitted.
This ASDU is used for signals and measurements pages: 0 and 35.
FUN and INF: same definition than ASDU 140, parameter is transmitted first low-word (low-byte,
then high byte), then high word, then a QDS quality descriptor, then a 4 byte time tag is
transmitted.
This ASDU is used for all parameter pages: 1, 2, 3, 6, 36 (group 1), 38 (group 2), 40 (group 3), 42
(group 4), 44 (group 5), 46 (group 6), 48 (group 7) and 50 (group 8).
FUN and INF: same definition than ASDU 140, floating-point parameter is transmitted first lowword (low-byte, then high byte), then high word, then relative date field forced to 0, then FAN field
forced to 0, then a 4 byte time tag is transmitted.
This ASDU is used for signals and measurements pages: 0 and 35.
P12y/EN CT/Fa5
IEC 60870-5-103 DATABASE
Page 104/130
1.4.3.2
Communications
MiCOM P125-P126-P127
FUN and INF: same definition than ASDU 140, parameter is transmitted first low-byte, then high
byte, then a 4 byte time tag is transmitted.
ASDU 201 (C9h) 32 bits analog protection value write:
FUN and INF: same definition than ASDU 140, parameter is transmitted first low-word (low-byte,
then high byte), then high word.
ASDU of answer to ASDU 201 setting write:
FUN and INF: same definition than ASDU 140, parameter is transmitted first low-word (low-byte,
then high byte), then high word, then a QDS quality descriptor, then a 4 byte time tag is
transmitted.
1.4.3.3
Error messages
All errors detected in settings management are returned to the master in a special message called
Rejection telegram, which is a special ASDU 49 with FUN = 7Fh and INF = FFh, and the error
code (rejection cause) contained in the MW value.
List of rejection causes used for P127:
CAUSE OF
REJECTION
MEANING
80H 01H
80H 06H
80H 07H
80H 0AH
80H 0BH
80H 15H
80H 30H
80H 33H
80H 64H
80H 72H
Communications
P12y/EN CT/Fa5
IEC 60870-5-103 DATABASE
Page 105/130
Relay reinitialisation
In case of relay re initialization, the relay send to the master station:
Availability
A
message
start/restart
indicating
relay
Each identification message of the relay (ASDU 5) contains the manufacturer name in 8 ASCII
characters (AREVA) and 2 free bytes containing: 127 or 126 , or 125 in decimal format,
then 2 free bytes containing the software version number in decimal (for ex.: 112 corresponds to
11.C).
1.6
Cyclic Messages
Only measurands can be stored in these messages.
Measurands values are stored in lower levels of communication, before polling by master station.
In ASDU 9
The following values are stored (with a rate such as: 2,4 * nominal value = 4096):
P127 + P126
RMS Ia,
RMS Ib,
RMS Ic,
P127 only
RMS Ua,
RMS Ub,
RMS Uc,
P,
Q,
In ASDU 3, (ASDU3.4)
the following values are stored (with a rate such as: 2,4 * nominal value = 4096):
RMS IN,
RMS Un.
The following values are stored (in IEEE 32 bits floating-point format):
P12y/EN CT/Fa5
IEC 60870-5-103 DATABASE
Page 106/130
Communications
MiCOM P125-P126-P127
P127 + P126
I1 (module, unit: V)
I2 (module, unit: V)
P127 + P126
P127 only
The following 4 energy values are stored (in IEEE 32 bits floating-point format):
P127 only
Communications
MiCOM P125/P126 & P127
1.7
P12y/EN CT/Fa5
IEC 60870-5-103 DATABASE
Page 107/130
P127 only
Channel 5: Ua voltage.
Channel 6: Ub voltage.
Channel 8: Frequency.
P12y/EN CT/Fa5
IEC 60870-5-103 DATABASE
Page 108/130
Communications
MiCOM P125-P126-P127
P126 only
Number of analog channels transmitted: 6, which are:
0
Channel 6: Frequency.
P125 only
Number of analog channels transmitted: 3, which are:
0
Channel 2: U0 voltage.
Channel 3: Frequency.
Communications
MiCOM P125/P126 & P127
1.8
P12y/EN CT/Fa5
IEC 60870-5-103 DATABASE
Page 109/130
- fault magnitude:
P12y/EN CT/Fa5
IEC 60870-5-103 DATABASE
Page 110/130
Communications
MiCOM P125-P126-P127
Communications
MiCOM P125/P126 & P127
P12y/EN CT/Fa5
DNP 3.0 DATABASE
Page 111/130
P12y/EN CT/Fa5
DNP3.0 DATABASE
Page 112/130
Communications
MiCOM P125/P126 & P127
BLANK PAGE
Communications
MiCOM P125/P126 & P127
P12y/EN CT/Fa5
DNP 3.0 DATABASE
Page 113/130
CONTENTS
1.
DNP-3 PROTOCOL
115
1.1
115
1.2
115
1.3
Implementation Table
118
1.4
Point List
120
1.4.1
120
1.4.2
125
1.4.3
Counters
127
1.4.4
Analog Inputs
128
P12y/EN CT/Fa5
DNP3.0 DATABASE
Page 114/130
Communications
MiCOM P125/P126 & P127
BLANK PAGE
Communications
P12y/EN CT/Fa5
DNP3.0 DATABASE
Page 115/130
1.
DNP-3 PROTOCOL
1.1
1.2
DNP V3.00
DEVICE PROFILE DOCUMENT
(Also see the Implementation Table in Section 1.3, beginning on page 117).
Vendor Name: Schneider Electric
Device Name: SERIAL 20 Platform using the Triangle MicroWorks, Inc. DNP 3.0 Slave
Source Code Library, Version 2.18.
Highest DNP Level Supported:
For Requests: Level 2
For Responses: Level 2
Device Function:
7
Master
Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels
Supported (the complete list is described in the attached table):
For static (non-change-event) object requests, request qualifier codes 00 and 01 (startstop), 07 and 08 (limited quantity), and 17 and 28 (index) are supported in addition to
request qualifier code 06 (no range or all points).
Static object requests received with qualifiers 00, 01, 06, 07, or 08, will be responded with
qualifiers 00 or 01. Static object requests received with qualifiers 17 or 28 will be
responded with qualifiers 17 or 28.
For change-event object requests, qualifiers 17 or 28 are always responded.
16-bit and 32-bit Analog Change Events with Time may be requested.
The read function code for Object 50 (Time and Date), variation 1, is supported.
Maximum Data Link Frame Size (octets):
Transmitted:
292
Received
292
None
Configurable
P12y/EN CT/Fa5
DNP3.0 DATABASE
Page 116/130
Communications
MiCOM P125/P126 & P127
DNP V3.00
DEVICE PROFILE DOCUMENT
(Also see the Implementation Table in Section 1.3, beginning on page 117).
Requires Data Link Layer Confirmation:
Never
Always
Sometimes
Configurable
Requires Application Layer Confirmation:
Never
Always
When reporting Event Data
When sending multi-fragment responses
Sometimes
Configurable
Timeouts while waiting for:
Data Link Confirm:
None
Complete Appl. Fragment: None
Configurable.
Configurable
Application Confirm:
Fixed at 1s
Variable
Configurable
Fixed at ____
Variable
Configurable
Others:
Binary input change scanning period:
Analog input change scanning period:
5ms
1s
None
Never
Never
Never
Never
Always
Always
Always
Always
Sometimes
Sometimes
Sometimes
Sometimes
Configurable
Configurable
Configurable
Configurable
Count > 1
Pulse On
Pulse Off
Latch On
Latch Off
Never
Never
Never
Never
Never
Always
Always
Always
Always
Always
Sometimes
Sometimes
Sometimes
Sometimes
Sometimes
Configurable
Configurable
Configurable
Configurable
Configurable
Queue
Clear Queue
Never Always
Never Always
Never
Only time-tagged for P126 and P127
Only non-time-tagged for P125
Configurable
Never
Configurable
Only certain objects
Sometimes (attach explanation)
ENABLE/DISABLE UNSOLICITED
Function codes supported
Sometimes
Sometimes
Configurable
Configurable
Never
When Device Restarts
When Status Flags Change
Communications
P12y/EN CT/Fa5
DNP3.0 DATABASE
Page 117/130
DNP V3.00
DEVICE PROFILE DOCUMENT
(Also see the Implementation Table in Section 1.3, beginning on page 117).
Default Counter Object/Variation:
No Counters Reported
Configurable
Default Object:
20
Default Variation:
5
Point-by-point list attached
Yes
No
No Counters Reported
Configurable (attach explanation)
16 Bits
32 Bits
Other Value: _____
Point-by-point list attached
P12y/EN CT/Fa5
DNP3.0 DATABASE
Page 118/130
1.3
Communications
MiCOM P125/P126 & P127
Implementation Table
The following table identifies the variations, function codes, and qualifiers supported by the
P12y in both request messages and in response messages.
For static (non-change-event) objects, requests sent with qualifiers 00, 01, 06, 07, or 08, will
be responded with qualifiers 00 or 01. Static object requests sent with qualifiers 17 or 28 will
be responded with qualifiers 17 or 28. For change-event objects, qualifiers 17 or 28 are
always responded.
In the table below the text shaded as indicates
Subset Level 3 functionality
(beyond Subset Level 2), and text shaded as
Subset Level 3
beyond Subset
Level 3
indicates
functionality
Variation
Number
0
Description
Function Codes
(dec)
REQUEST
(Library will
parse)
Qualifier
Codes (hex)
(read)
Binary Input
(read)
(read)
00, 01
(start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28
(index
(read)
1(default
see note 1 for
P120 - P121)
(read)
12
20
20
20
20
20
21
3
(select)
4
(operate)
5
(direct op)
6 (dir. op, noack)
1
(read)
7
(freeze)
8 (freeze noack)
9 (freeze clear)
10 (frz. cl. Noack)
1
(read)
7
(freeze)
8 (freeze noack)
9 (freeze clear)
10 (frz. cl. Noack)
1
(read)
7
(freeze)
8 (freeze noack)
9 (freeze clear)
10 (frz. cl. Noack)
1
(read)
7
(freeze)
8 (freeze noack)
9 (freeze clear)
10 (frz. cl. Noack)
1
(read)
7
(freeze)
8 (freeze noack)
9 (freeze clear)
10 (frz. cl. Noack)
1
(read)
21
2
10
10
(default
see note 1)
(default
see note 1)
(default
see note 1)
00, 01
(start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28
(index)
00, 01
(start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28
(index)
RESPONSE
(Library will
respond with)
Function
Qualifier
Codes (dec)
Codes (hex)
129
(response)
00, 01
17, 28
(start-stop)
(index
see note 2)
129
(response)
00, 01
17, 28
(start-stop)
(index
see note 2)
129
(response)
17, 28
(index)
(read)
129
(response)
17, 28
(index)
(read)
(read)
00, 01
(start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28
(index)
00, 01
(start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28
(index)
00, 01
(start-stop)
07, 08 (limited qty)
17, 28
(index)
129
(response)
00, 01
17, 28
(start-stop)
(index
see note 2)
129
(response)
00, 01
(start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28
(index)
129
(response)
00, 01
17, 28
(start-stop)
(index
see note 2)
00, 01
(start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28
(index)
129
(response)
00, 01
17, 28
(start-stop)
(index
see note 2)
00, 01
(start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28
(index)
129
(response)
00, 01
17, 28
(start-stop)
(index
see note 2)
00, 01
(start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28
(index)
129
(response)
00, 01
17, 28
(start-stop)
(index
see note 2)
129
(response)
00, 01
17, 28
(start-stop)
(index
see note 2)
22
(read)
echo of request
00, 01
(start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28
(index)
00, 01
(start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28
(index)
00, 01
(start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28
(index)
Communications
P12y/EN CT/Fa5
DNP3.0 DATABASE
Page 119/130
Variation
Number
2
21
Description
Function Codes
(dec)
(read)
(read)
21
10
(read)
30
(read)
(read)
30
30
(read)
30
(read)
32
(read)
30
32
32
(default
see note 1
(default
see note 1)
RESPONSE
(Library will
respond with)
Function
Qualifier
Codes (dec)
Codes (hex)
00, 01
(start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28
(index)
00, 01
(start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28
(index)
00, 01
(start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28
(index)
00, 01
(start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28
(index)
00, 01
(start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28
(index)
00, 01
(start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28
(index)
00, 01
(start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28
(index)
00, 01
(start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28
(index)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
00, 01
17, 28
(start-stop)
(index
see note 2)
129
(response)
00, 01
17, 28
(start-stop)
(index
see note 2)
129
(response)
00, 01
17, 28
(start-stop)
(index
see note 2)
129
(response)
00, 01
17, 28
(start-stop)
(index
see note 2)
129
(response)
00, 01
17, 28
(start-stop)
(index
see note 2)
129
(response)
00, 01
17, 28
(start-stop)
(index
see note 2)
129
(response)
00, 01
17, 28
(start-stop)
(index
see note 2)
(read)
129
(response)
17, 28
(index)
(read)
129
(response)
17, 28
(index)
(read)
129
(response)
17, 28
(index)
(read)
129
(response)
17, 28
(index)
(read)
129
(response)
00, 01
17, 28
(start-stop)
(index
see note 2)
1
2
(read)
(write)
00, 01
(start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28
(index)
00, 01
(start-stop)
06 (no range, or all)
07
(limited qty
= 1)
08
(limited qty)
17, 28
(index)
129
(response)
00, 01
17, 28
(start-stop)
(index
see note 2)
129
(response)
07
(limited qty)
(qty = 1)
(read)
32
32
50
52
60
(read)
60
Class 0 Data
(read)
129
17,28
60
Class 1 Data
(read)
129
17,28
60
Class 2 Data
(read)
129
17,28
60
Class 3 Data
(read)
129
17,28
80
Internal Indications
(write)
50
REQUEST
(Library will
parse)
Qualifier
Codes (hex)
(default
see note 1)
13 (cold restart)
14 (warm restart)
23 (delay meas.)
Note 1:
Note 2:
Note 3:
P12y/EN CT/Fa5
DNP3.0 DATABASE
Page 120/130
1.4
Communications
MiCOM P125/P126 & P127
Point Listt
The tables in the following sections identify all the individual data points provided by this
implementation of DNP 3.0. uses the database protection.
1.4.1
P126
Point
Index
P127
Point
Index
Output relay 2
Output relay 3
Output relay 4
Output relay 5
Output relay 6
Output relay 7
Output relay 8
Opto isolator 1
10
10
Opto isolator 2
11
11
Opto isolator 3
10
12
12
Opto isolator 4
13
13
Opto isolator 5
14
14
Opto isolator 6
15
15
Opto isolator 7
16
16
17
17
18
18
19
19
20
20
21
21
11
22
22
12
23
23
13
24
24
14
25
25
15
26
26
16
27
27
28
28
I min Start
29
29
tImin trip
30
30
I2> start
31
31
tI2> trip
32
32
I2>> start
33
33
tI2>> trip
34
34
I2>>> start
35
35
tI2>>> trip
36
U< start
37
tU< trip
38
U<< start
Name/Description
Communications
P12y/EN CT/Fa5
DNP3.0 DATABASE
Page 121/130
17
P126
Point
Index
36
P127
Point
Index
Name/Description
39
tU<< trip
40
U> start
41
tU> trip
42
U>> start
43
tU>> trip
44
UN>>>> start
18
37
45
tUN>>>> trip
19
38
46
PN> start
20
39
47
PN> trip
21
40
48
PN>> start
22
41
49
PN>> trip
42
50
Thermal start
43
51
Thermal trip
23
44
52
Taux1
24
45
53
Taux2
25
46
54
Taux3
26
47
55
Taux4
48
56
49
57
50
58
51
59
52
60
Broken conductor
27
53
61
cb failure
54
62
Number of cb operation
55
63
56
64
sa2n
57
65
58
66
59
67
60
68
Successful autoreclosure
61
69
In Progress autoreclosure
62
70
63
71
64
72
Fault Configuration of
autoreclosure
logic Selectivity 1
65
73
logic Selectivity 2
66
74
Blocking logic 1
67
75
Blocking logic 2
68
76
52a
69
77
52b
70
78
Lack of SF6
71
79
72
80
Start tBF
73
81
Trip SOTF
74
82
Manual Close
1
1
75
83
Local Mode
84
85
P12y/EN CT/Fa5
DNP3.0 DATABASE
Page 122/130
Communications
MiCOM P125/P126 & P127
P126
Point
Index
P127
Point
Index
Name/Description
init
val.
86
VTS
87
Start V2>
88
Start V2>>
28
76
89
29
77
90
30
78
92
31
79
92
80
93
32
81
94
Thermal Resetting by
communication
Shifting to maintenance mode (remote order)
33
82
95
34
83
96
84
97
85
98
86
99
35
87
100
36
88
101
37
89
102
90
103
92
104
92
105
93
106
107
108
109
110
38
94
111
39
95
112
40
96
113
97
114
98
115
41
99
116
42
100
117
43
101
118
44
102
119
103
120
45
104
121
105
122
106
123
107
124
108
125
109
126
110
127
Latching of Relay
111
128
112
129
113
130
114
131
Communications
P12y/EN CT/Fa5
DNP3.0 DATABASE
Page 123/130
P126
Point
Index
P127
Point
Index
Name/Description
init
val.
132
Start P>
133
Start P>>
134
Trip P>
135
Trip P>>
136
Blocking Inrush
137
Start F1
138
Start F2
139
Start F3
140
Start F4
141
Start F5
142
Start F6
143
Trip F1
144
Trip F2
145
Trip F3
146
Trip F4
147
Trip F5
148
Trip F6
149
115
150
116
151
117
152
118
153
154
155
156
157
158
159
160
161
162
163
164
165
166
119
167
Taux5
120
168
Taux6
121
169
Taux7
170
Taux8
171
Taux9
172
Taux10
173
Taux11
174
Taux12
122
175
123
176
124
177
178
179
P12y/EN CT/Fa5
DNP3.0 DATABASE
Page 124/130
Communications
MiCOM P125/P126 & P127
P126
Point
Index
P127
Point
Index
180
Name/Description
init
val.
183
184
185
181
182
125
186
187
Start P<
188
Start P<<
189
Start Q>
190
Start Q>>
191
Start Q<
192
Start Q<<
193
Trip P<
194
Trip P<<
195
Trip Q>
196
Trip Q>>
197
Trip Q<
198
Trip Q<<
199
200
201
202
203
204
205
Trip dFdT1
206
Trip dFdT2
207
Trip dFdT3
208
Trip dFdT4
209
Trip dFdT5
210
Trip dFdT6
211
212
213
214
215
216
217
CTS
Communications
P12y/EN CT/Fa5
DNP3.0 DATABASE
Page 125/130
P126
Point
Index
P127
Point
Index
Name/Description
Initial Status
Value
De Latch of relays
Acknowledgement of the 1
alarm
st
10
10
Initialization of Maximum
11
11
Reinitialization of I0 harmonic
calculation
12
Reinitialization of Energy
counters
12
13
Re initialization of autoreclosure
13
14
14
15
SA2n reset
15
16
Com1 order
16
17
Com2 order
17
18
Com3 order
18
19
Com4 order
P12y/EN CT/Fa5
DNP3.0 DATABASE
Page 126/130
Communications
MiCOM P125/P126 & P127
P126
Point
Index
P127
Point
Index
Name/Description
Initial Status
Value
19
20
General reset
21
Group 1 select
22
Group 2 select
23
Group 3 select
24
Group 4 select
25
Group 5 select
26
Group 6 select
27
Group 7 select
28
Group 8 select
Communications
MiCOM P125/P126 & P127
1.4.3
P12y/EN CT/Fa5
DNP3.0 DATABASE
Page 127/130
Counters
The following table lists both Binary Counters (Object 20) and Frozen Counters (Object 21).
When a freeze function is performed on a Binary Counter point, the frozen value is available in
the corresponding Frozen Counter point.
Binary Counters and Frozen Counters are not included in class 0 polls.
P125 do not support binary Counters and Frozen Counters.
Binary Counters
Static (Steady-State) Object Number: 20
Change Event Object Number:
not supported
Request Function Codes supported: 1 (read), 7 (freeze), 8 (freeze noack)
9 (freeze and clear), 10 (freeze and clear, noack)
Static Variation reported when variation 0 requested:
5 (32-Bit Binary Counter without Flag
Change Event Variation reported when variation 0 requested: none-not supported
Frozen Counters
Static (Steady-State) Object Number: 21
Change Event Object Number:
not supported
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested:
9 (32-Bit Frozen Binary without Flag)
Change Event Variation reported when variation 0 requested: none-not supported
P126
Point
Index
0
P127
Point
Index
0
D1
D1
D1
D1
D1
CB operation number
D2
sa2n ia
D3
sa2n ib
D3
sa2n ic
D3
10
10
D2
11
11
Number of cycles 1
D2
12
12
Number of cycles 2
D2
13
13
Number of cycles 3
D2
14
14
Number of cycles 4
D2
15
15
D2
16
16
D2
17
17
D1
18
18
D1
19
19
D1
20
20
D1
21
21
D1
22
22
D1
23
D1
24
D1
25
D1
26
D1
27
D1
28
D1
29
D1
30
D1
31
D1
32
D1
33
D1
Name/Description
Data type
D1
P12y/EN CT/Fa5
DNP3.0 DATABASE
Page 128/130
1.4.4
Communications
MiCOM P125/P126 & P127
Analog Inputs
The following table lists Analog Inputs (Object 30). It is important to note that 16-bit and 32-bit
variations of Analog Inputs, Analog Output Control Blocks, and Analog Output Statuses are
transmitted through DNP as signed numbers. Even for analog input points that are not valid
as negative values, the maximum positive representation is 32767. For each point, the
Scaling and Units column indicates the value of a transmitted 32767. This also implies the
value of a transmitted 32767. The entry in the column does not imply a valid value for the
point.
Always indicating the representation of 32767 in the tables below is a consistent method for
representing scale, applicable to all scaling possibilities.
The Default Deadband, and the Default Change Event Assigned Class columns are used
to represent the absolute amount by which the point must change before an analog change
event will be generated, and once generated in which class poll (1, 2, 3) will the change event
be reported. Only the default values for these columns are documented here because the
values may change in operation due to either local (user-interface) or remote (through DNP)
control.
Every Analog Inputs points are included in class 0 polls, because they are included in one of
classes 1, 2 or 3.
Analog Inputs
Static (Steady-State) Object Number:
30
Change Event Object Number:
32
Request Function Codes supported:
1 (read)
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o
Time)
Change Event Scan Rate:
The scan rate for analog input change events is fixed at 1s
P125
Point
Index
P126
Point
Index
P127
Point
Index
Active Group
12
Initial Change
Event Class
(1, 2, 3 or
none)
1
Magnitude IA
40 In
0 to 40 In
0.02 In
Magnitude IB
40 In
0 to 40 In
0.02 In
Magnitude IC
40 In
0 to 40 In
0.02 In
Magnitude IN
0 to 40 IEn
rms IA
0A
327.67A
rms IB
0A
327.67A
rms IC
0A
327.67A
rms IN
0A
327.67A
rms VA
0V
327.67V
10
rms VB
0V
327.67V
11
rms VC
0V
327.67V
0 to
40000000
A/100
0 to
40000000
A/100
0 to
40000000
A/100
0 to
40000000
A/100
0 to
500000000
V/100
0 to
500000000
V/100
0 to
500000000
V/100
0.02 IEn if
Low
sensitivity
0.004 IEn if
Medium
sensitivity
0.0008 IEn if
high
sensitivity
Name/Description
Initial
Value
Valid Range
Change
Event Deadband
2%
2%
2%
2%
2%
2%
2%
3
3
3
3
3
3
3
Communications
P12y/EN CT/Fa5
DNP3.0 DATABASE
Page 129/130
Analog Inputs
Static (Steady-State) Object Number:
30
Change Event Object Number:
32
Request Function Codes supported:
1 (read)
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o
Time)
Change Event Scan Rate:
The scan rate for analog input change events is fixed at 1s
P125
Point
Index
P126
Point
Index
P127
Point
Index
12
rms VN
13
Magnitude VA
14
Magnitude VB
15
Magnitude VC
16
Magnitude VN
Name/Description
Initial
Value
0V
10
11
17
Thermal State
0%
260V G1*
960V G2*
260V G1*
960V G2*
260V G1*
960V G2*
260V G1*
960V G2*
32767%
12
18
Frequency
327,67 Hz
13
19
Magnitude I2
14
20
Magnitude I1
21
Magnitude V2
22
Magnitude V1
23
24
Valid Range
0 to
500000000
V/100
0 to 260V
0 to 960V
0 to 260V
0 to 960V
0 to 260V
0 to 960V
0 to 260V
0 to 960V
0 to 65535
Change
Event Deadband
2%
0.5V
2V
0.5V
2V
0.5V
2V
0.5V
2V
10
Initial Change
Event Class
(1, 2, 3 or
none)
3
3
3
3
3
3
1Hz
40 In
45Hz to
65 Hz and
99.99Hz ==
ERROR
0 to 40 In
0.1 In
40 In
0 to 40 In
0.1 In
0.5V
2V
0.5V
2V
260V G1*
960V G2*
260V G1*
960V G2*
327.67kW
327.67kVAr
15
25
Harmonic power Pe
327.67 W
16
26
Harmonic power
IeCos
327.67 A
17
27
Angle Ie ^ Ue
32767
0 to 260V
0 to 960V
0 to 260V
0 to 960V
-9.999 E8 to
9.999 E8
kW/100
-9.999 E8 to
9.999 E8
kVAr/100
-9.999 E8 to
9.999 E8
W/100
-9.999 E8 to
9.999 E8
A/100
0 to 360
28
3-phase CosPhi
18
29
Tripping Time
327.67s
-100 to 100
(1/100)
0 to 10.00s
2
10 ms
19
30
Closing Time
327.67s
0 to 10.00s
10 ms
20
31
Fault number
32767
0 to 65535
21
32
group
32767
1 to 2
22
33
Fault phase
32767
0 to 8 (F1)
23
34
Fault origin
32767
24
35
Fault magnitude
40 In
0 to
29
(F2)
0 to 40 In
each new
fault
each new
fault
each new
fault
25
36
Fault magnitude IA
40 In
0 to 40 In
26
37
Fault magnitude IB
40 In
0 to 40 In
27
38
Fault magnitude IC
40 In
0 to 40 In
28
39
Fault magnitude IN
40 IEn
0 to 40 IEn
40
Fault magnitude VA
41
Fault magnitude VB
260V G1*
960V G2*
260V G1*
960V G2*
0 to 260V
0 to 960V
0 to 260V
0 to 960V
each new
fault
each new
fault
each new
fault
each new
fault
each new
fault
each new
fault
each new
fault
2%
2%
2%
2%
1
3
3
3
3
3
3
3
2
2
2
2
2
2
2
2
P12y/EN CT/Fa5
DNP3.0 DATABASE
Page 130/130
Communications
MiCOM P125/P126 & P127
Analog Inputs
Static (Steady-State) Object Number:
30
Change Event Object Number:
32
Request Function Codes supported:
1 (read)
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o
Time)
Change Event Scan Rate:
The scan rate for analog input change events is fixed at 1s
P125
Point
Index
42
Fault magnitude VC
43
Fault magnitude Ue
44
45
32767
0 to 360
46
32767
0 to 360
47
Fault angle Ie ^ Ue
32767
0 to 360
48
327.67kVA
31
49
Angle Ia ^ Ib
32767
-9.999 E8 to
9.999 E8
kVA/100
0 to 360
32
50
Angle Ia ^ Ic
32767
0 to 360
51
Angle Ia ^ Va
Or Angle Ia ^ Uab
Angle Ia ^ Vb
Or Angle Ia ^ Ubc
Angle Ia ^ Vc
Or Angle Ia ^ Uca
Angle Ia ^ Ue
32767
0 to 360
32767
0 to 360
32767
0 to 360
32767
0 to 360
P126
Point
Index
P127
Point
Index
29
30
52
53
33
54
Name/Description
Initial
Value
Valid Range
0 to 260V
0 to 960V
0 to 260V
0 to 960V
0 to 360
Change
Event Deadband
each new
fault
each new
fault
each new
fault
each new
fault
each new
fault
each new
fault
2%
Initial Change
Event Class
(1, 2, 3 or
none)
2
2
2
2
2
2
3
Format:
F1:
0: None, 1: Phase A, 2: Phase B, 4: Phase C, 3: Phase AB, 5: Phase AC, 6: Phase BC, 7:
Phase A B C, 8: Earth.
F2:
0: Null, 1: Remote trip, 2: thermal overload, 3: tI>, 4: tI>>, 5: tI>>>, 6: tIN>, 7: tIN>>, 8: tIN>>>,
9: tI<, 10: broken conductor, 11: tU<, 12: tU<<, 13: Pe/Iecos>, 14: Pe/Iecos>>, 15: tI2>, 16:
tI2>>, 17: tI2>>>, 18: tU>, 19: tU>>, 20: tUN>>>>, 21: tAux1, 22: tAux2, 23: tEqu.A, 24:
tEqu.B, 25: tEqu.C, 26: tEqu.D, 27:tAux3, 28: tAux4, 29: SOTF, 30: tP>, 31: tP>>, 32: tF1, 33:
tF2, 34: tF3, 35: tF4, 36: tF5, 37: tF6, 38: tEqu.E, 39: tEqu.F, 40: tEqu.G, 41: tEqu.H.
G1*: Voltage range 57 - 130 V.
G2*: Voltage range 220 480 V.
P12y/EN CM/Fa5
COMMISSIONING AND
MAINTENANCE GUIDE
P12y/EN CM/Fa5
Page 1/22
CONTENT
1.
2.
2.1
Important notes
2.1.1
2.1.2
2.1.3
Communication
2.2
3.
3.1
Allocation of terminals
3.2
3.3
Visual inspection
3.4
Earthing
3.5
3.6
3.6.1
3.6.2
Core CT polarity
3.7
Auxiliary supply
3.8
Logic inputs
3.9
Logic outputs
3.10
4.
SETTING CHECK
10
4.1
Settings
10
4.2
Measurements
10
4.2.1
MiCOM P125
10
4.2.2
MiCOM P126
11
4.2.3
MiCOM P127
11
4.3
Thresholds validation
12
4.3.1
MiCOM settings
12
4.3.2
15
4.4
Final checks
19
5.
MAINTENANCE
20
5.1
Equipment failure
20
5.1.1
Minor fault
20
5.1.2
Major fault
20
5.1.3
20
P12y/EN CM/Fa5
Page 2/22
5.2
Method of repair
21
5.2.1
21
5.2.2
21
5.3
Problem solving
21
5.3.1
21
5.3.2
Communication
22
P12y/EN CM/Fa5
1.
Page 3/22
Extracting the settings applied to the relay using the appropriate setting software
(preferred method)
To confirm that the product is operating correctly once the application-specific settings have
been applied, a test should be performed on a single protection element.
Unless previously agreed to the contrary, the customer will be responsible for determining
the application-specific settings to be applied to the MiCOM relays and for testing of any
scheme logic applied by external wiring.
Blank commissioning test and setting records are provided
P12y/EN RS of this Technical Guide for completion as required.
at
the
chapter
P12y/EN CM/Fa5
Page 4/22
2.
2.1
Important notes
All the commissioning tests of the MiCOM P125, P126, and P127 relays are carried out by
injecting currents and voltages to the secondary of the earth and/or phases CTs and VTs
using appropriate injection test sets provided for this purpose.
2.1.1
Test plugs and wires to carry out injections to the CT's secondary (dimension according to
the currents injected).
2.1.3
Communication
Using the RS 485 communication on the rear connector of the MiCOM P125, P126 & P127
relays or using the RS232 front port can make all commissioning test records.
All above in according
IEC 60870-5-103,).
to
each
RS
485
communication
protocol
(MODBUS,
P12y/EN CM/Fa5
Page 5/22
P12y/EN CM/Fa5
Page 6/22
3.
3.1
Allocation of terminals
It is necessary to consult the appropriate wiring diagram provided in the chapter
P12y/EN CO of this Technical Guide whilst observing the various polarities and ground/earth
connection.
3.2
3.3
Visual inspection
Carefully examine the relay to see if there has been any possible deterioration following
installation.
Check if the external wiring corresponds to the appropriate relay diagram or the assembly
diagram. The reference number of the relay diagram is indicated on a label situated under
the upper flap of the front panel.
When the relay is outside from its case, use a continuity tester to test that the current shortcircuits (phases and earth CT's) between the terminals indicated on the wiring diagram are
closed.
3.4
Earthing
Check if the earth connection of the case situated above the rear terminal block is used to
connect the relay to a local earth bar. With several relays present, make sure that the copper
earth bar is properly installed for solidly connecting the earthing terminals of each case.
3.5
P12y/EN CM/Fa5
Page 7/22
3.6.1
Screen shields
P1
S1
P2
S2
Other ends
of electrical cables
P0041ENa
Core CT polarity
It is necessary to check the polarity of the core CT by following the figure below:
Momentarily connect the battery + to P1 and to P2. The centre zero ammeter connected
with + to S1 and to S2 will deflect in the positive direction if the wiring is correct.
The phase CT may be tested using the same method.
P1
S1
P2
S2
+ mA
+
_
P0043ENa
P12y/EN CM/Fa5
Page 8/22
3.7
Auxiliary supply
Check the value of the auxiliary supply voltage (terminals 33 and 34). The value measured
shall be between 0.8 and 1.2 times the nominal auxiliary supply voltage indicated on the
MiCOM P125, P126 and P127.
You can read the Uaux range of the relay under the flap on the top of front relay.
3.8
24 - 60 Vdc
19 - 72 Vdc
80
336
Logic inputs
This test checks that all the opto-isolated inputs are functioning correctly. The P125 has 4
(+5 optional) opto-isolated inputs while P126 and P127 have 7 logic opto-isolated inputs.
The opto inputs should be energised a time. The status of the input can be viewed using
menu OP. PARAMETERS/Input Status, a 1 indicating an energised input and a 0 indicating
a de-energised input. When each logic input is energised one of the characters on the
bottom line of the menu display will change to the value show in the following table to
indicate the new state of the inputs.
(1)
Input
OP. PARAMETERS/Inputs
Satuts. cell value
Opto input 1
22-24 Terminals
7654321
0000001
Opto input 2
26-28 Terminals
7654321
0000010
Opto input 3
17-19 Terminals
7654321
0000100
Opto input 4
21-23 Terminals
7654321
0001000
Opto input 5
25-27 Terminals
P126, P127
7654321
0010000
Opto input 6
58-60 Terminals
P126, P127
7654321
0100000
Opto input 7
57-59 Terminals
P126, P127
7654321
1000000
Opto input 8
61-62 terminals
P127 (1)
CBA98
00001
Opto input 9
64-62 terminals
P127 (1)
CBA98
00010
Opto input 10
63-62 terminals
P127 (1)
CBA98
00100
Opto input 11
66-62 terminals
P127 (1)
CBA98
01000
Opto input 12
65-62 terminals
P127 (1)
CBA98
10000
Available only for P127 5 opto-inputs option (product codes P127xx1 or P127xx3).
Input COM terminal 62 is the common terminal for inputs 8 to 12.
P12y/EN CM/Fa5
Page 9/22
Logic outputs
This test checks that all output relays are functioning correctly. The P126 and P127 relays
have 8 outputs, P125 relay has 6 outputs.
The watch dog relay is always on. In case of relay failure the watch dog relay moves to the
off and the terminals 35-36 are opened.
The status of the outputs can be viewed using menu OP. PARAMETERS/ Relay Status, an
indicating 1 means relay supplied and a 0 indicating means relay non-supplied. When each
output relay is closed one of the characters on the bottom line of the menu display will
change to the value show in the following table to indicate the new state of the output relays.
Each output contact may have its own and independent power supply (refer to wiring
schemes).
MiCOM P125 range
OP. PARAMETERS/Relay
Status. cell value
Normal close
00000001
00000010
RL 3 Terminals 14-16
00000100
RL 4 Terminals 18-20
00001000
RL 5 Terminals 1-3
00010000
RL 6 Terminals 7-8
00100000
RL 7 Terminals 9-11
01000000
RL 8 Terminals 13-15
10000000
OUTPUT RELAYS
3.10
P12y/EN CM/Fa5
Page 10/22
4.
SETTING CHECK
The setting checks must ensure that all relay settings have been correctly applied to the
relay for the specific application.
Transfer the setting file to the relay using a laptop PC running the appropriate software via
the RS232 front port or the RS485 rear port.
This is the preferred setting transfer method, because it is faster and there are fewer margins
for errors.
If the setting software is not used, the relay settings must be checked manually via the relay
front panel interface.
The commissioning checks are as follows:
4.1
1.
2.
3.
Settings
Log the settings on the commissioning test sheets.
4.2
Measurements
The MiCOM P125 P126 P127 relays measure phase and earth currents, phase (phase to
phase) voltage, zero sequence voltage as a True RMS value up to the 10th harmonics. The
value(s) indicated take account of the phase and/or earth CT ratio and VT ratio.
WARNING:
4.2.1
MiCOM P125
Apply current to input terminals 55-56 (Ien= 1A) or 47-48 (Ien= 5A) and verify the IN
value shown on the LCD taking in account the relevant nominal current.
Apply earth voltage to 39-40 terminals and verify in measurements menu the UN value
shown on LCD.
Log the results to the Commissioning test sheets (Applied value and relay value
displayed).
4.2.3
P12y/EN CM/Fa5
Page 11/22
MiCOM P126
Note the select phase and earth CTs ratio and neutral VT ratio.
Apply current to input terminals 49-50 (In=1A) or 41-42 (In=5A) and verify the IA value
shown on the LCD.
Apply current to input terminals 51-52 (In=1A) or 43-44 (In=5A) and verify the IB value
shown on the LCD.
Apply current to input terminals 53-54 (In=1A) or 45-46 (In=5A) and verify the IC value
shown on the LCD.
Apply current to input terminals 55-56 (Ien= 1A) or 47-48 (Ien= 5A) and verify the IN
values on the LCD in relay measurement menu.
Apply earth voltage to 73-74 terminals and verify the UN values on the LCD in relay
measurement menu.
Log the results to the Commissioning test sheets (Applied values and relay values
displayed).
MiCOM P127
Note the select phase and earth CTs ratio, phase voltage VTs ratio and neutral
voltage VTs ratio.
Apply current to input terminals 49-50 (In=1A) or 41-42 (In=5A) and verify the IA value
shown on the LCD.
Apply current to input terminals 51-52 (In=1A) or 43-44 (In=5A) and verify the IB value
shown on the LCD.
Apply current to input terminals 53-54 (In=1A) or 45-46 (In=5A) and verify the IC value
shown on the LCD.
Apply current to input terminals 55-56 (Ien= 1A) or 47-48 (Ien= 5A) and verify the IN
values on the LCD in relay measurement menu.
Apply voltage to inputs terminals 69-70 and 71-72 and verify the UAB and UBC values
in relay measurement menu on the LCD.
Apply current to input terminals 55-56 (Ien= 1A) or 47-48 (Ien= 5A) and verify the IN
value in relay measurement menu on the LCD.
Apply voltage to inputs terminals 73-74 and verify the UN value in relay measurement
menu on the LCD.
Log the results to the Commissioning test sheets (Applied values and relay values
displayed).
P12y/EN CM/Fa5
Page 12/22
4.3
Thresholds validation
This test type demonstrates that the relay is operating correctly at the application specific
settings.
4.3.1
MiCOM settings
Set the following thresholds for the relay.
Applying the voltage and current to terminals as in wiring diagrams in chapter P12y/EN CO
of this Technical Guide.
The applied current and voltage must be great than setting value.
4.3.1.1
1A
E/Gnd CT Sec
1A
E/Gnd VT primary
0.100 kV
E/Gnd VT Sec
100.0 V
Protection Menu
Ie>
Yes
Ie>
1 Ien
tIe>
DT or IDMT or RI
10 s
IEC VI or IEEE VI
Ue>>>>
10 V
tUe>>>>
10 s
Automation Menu
TRIP tIe>
YES
TRIP tUe>>>>
YES
P12y/EN CM/Fa5
Page 13/22
1A
Line CT Sec
1A
E/Gnd CT primary
1A
E/Gnd CT Sec
1A
E/Gnd VT primary
0.100 kV
E/Gnd VT Sec
100.0 V
Protection Menu G1
I>
Yes
I>
1 In
tI>
DT or IDMT or RI
tI>
(if DT) 10 s
IEC VI or IEEE VI
Ie>
Yes
Ie>
1 In
tIe>
DT or IDMT or RI
20 s
IEC VI or IEEE VI
Ue>>>>
10V
tUe>>>>
10 s
Automation Menu
TRIP tI>
YES
TRIP tIe>
YES
TRIP tUe>>>>
YES
P12y/EN CM/Fa5
Page 14/22
4.3.1.3
1A
Line CT Sec
1A
E/Gnd CT primary
1A
E/Gnd CT Sec
1A
Line VT primary
0.100 kV
Line VT Sec
100.0 V
E/Gnd VT primary
0.100 kV
E/Gnd VT Sec
100.0 V
Protection Menu G1
I>
Yes
I>
1 In
tI>
DT or IDMT or RI
10 s
IEC VI or IEEE VI
U>
Yes
U>
20V
tU>
10 s
Ie>
Yes
Ie>
1 In
tIe>
DT or IDMT or RI
20 s
IEC VI or IEEE VI
Ue>>>>
10 V
tUe>>>>
10 s
Automation Menu
TRIP tI>
YES
TRIP tU>
YES
TRIP tIe>
YES
TRIP Ue>>>>
YES
P12y/EN CM/Fa5
Page 15/22
4.3.2.1
Supply the relay, inject current and voltage with magnitude greater then Ie> and
Ue>>>> setting value.
If the time delay tIe> is short, gradually increases injection current up to the value of
the Ie> threshold.
If the time delay tIe> is long, inject 0.95 x I threshold and check that there is no
tripping. Then inject 1,1 x Ie threshold and check the trip.
Gradually decreases the injected current and record the value of the drop out Ie>
threshold.
Checks:
Trip LED on
Ie>, tIe>
Supply the relay inject a current equal to 2 x Ie> threshold into one of the earth current
inputs. Repeat the operation for various current values (n x Ie threshold with n ranging
from 4 to 10, for example). Check that the values measured correspond to those
indicated in the table below (for TMS=1).
P12y/EN CM/Fa5
Page 16/22
IEC curves
Type of curve
IEC
2 x I threshold
10 x I threshold
Nominal
Min - Max
Nominal
Min - Max
STI
1.78
1.62 - 1.98
0.5
0.45 - 0.55
SI
10.1
9.1 - 11.1
2.7 - 3.3
VI
13.5
12.2 - 14.9
1.5
1.35 - 1.65
EI
26.7
24 - 29.5
0.8
0.72 - 0.88
LTI
120
108 - 132
13.3
12 - 14.6
IEEE/ANSI curves
Type of curve
IEEE/ANSI
2 x I threshold
10 x I threshold
Nominal
Min - Max
Nominal
Min - Max
STI
0.25
0.22 - 0.28
0.08
0.07- 0.09
MI
3.8
3.4 - 4.2
1.2
1.08 - 1.32
2.2
1.9 - 2.4
0.3
0.27 - 0.33
VI
7.2
6.5 - 8
0.7
0.63 - 0.77
EI
9.5
8.5 - 10.5
0.4
0.36 - 0.44
Checks:
4.3.2.2
Trip LED on
If the time delay tI> is short, gradually increase the injection current up to the value of
the I> threshold.
If the time delay tI> is long, inject 0.95 x I threshold and check that there is no tripping.
Then inject 1,1 x I threshold and check the trip.
Gradually decrease the injected current and record the value of the drop out off (I>
threshold).
P12y/EN CM/Fa5
Page 17/22
Checks:
Trip LED on
Apply a current into one of the phases and measure the time delay tI> by pre-setting
the current above the I> threshold (I injected > 2 x I threshold).
Apply a current onto one of the phases and measure the time delay tI> by pre-setting
the current above the I> threshold (I injected > 10 x I threshold).
Checks:
Alarm message on the LCD display for I> after that the setting trip delay time is
expired.
Alarm LED flashes > after that the setting trip delay time is expired.
Trip LED on after that the setting trip delay time is expired.
I> threshold LED on (if programmed) > after that the setting trip delay time is expired.
Trip output closes > after that the setting trip delay time is expired..
I> threshold output closes (if programmed) > after that the setting trip delay time is
expired.
I>, tI>
Supply the relay, inject a current equal to 2 x I> threshold into one of the earth current
inputs. Repeat the operation for various current values (n x Ie threshold with n ranging
from 4 to 10, for example). Check that the values measured correspond to those
indicated in the table below (for TMS=1).
IEC curves
Type of curve
IEC
2 x I threshold
10 x I threshold
Nominal
Min - Max
Nominal
Min - Max
STI
1.78
1.62 - 1.98
0.5
0.45 - 0.55
SI
10.1
9.1 - 11.1
2.7 - 3.3
VI
13.5
12.2 - 14.9
1.5
1.35 - 1.65
EI
26.7
24 - 29.5
0.8
0.72 - 0.88
LTI
120
108 - 132
13.3
12 - 14.6
P12y/EN CM/Fa5
Page 18/22
IEEE/ANSI curves
Type of curve
IEEE/ANSI
2 x I threshold
10 x I threshold
Nominal
Min - Max
Nominal
Min - Max
STI
0.25
0.22 - 0.28
0.08
0.07- 0.09
MI
3.8
3.4 - 4.2
1.2
1.08 - 1.32
2.2
1.9 - 2.4
0.3
0.27 - 0.33
VI
7.2
6.5 - 8
0.7
0.63 - 0.77
EI
9.5
8.5 - 10.5
0.4
0.36 - 0.44
RI electromechanical curve
Type of curve
Electromechanical
2 x I threshold
RI
10 x I threshold
Nominal
Min - Max
Nominal
Min - Max
4.5
4-5
3.2
2.8 - 3.6
For other injected current values, compare the values found with the theoretical values
calculated according to the formula of the curves.
NOTE:
Checks:
4.3.2.3
Trip LED on
If tU> time delay is short, gradually raise the injection voltage up to the value of U>
threshold.
If U> time delay is long, inject 0.95 x U> threshold setting and check there is no trip.
Then inject 1.1 x U> threshold setting and check the trip output is close.
Gradually lower the injected current and note the value of the drop out U> threshold.
P12y/EN CM/Fa5
Page 19/22
Checks:
4.4
Alarm message on the LCD display for U> after that the setting trip delay time is
expired.
Alarm LED flashes after that the setting trip delay time is expired.
Trip LED on, after that the setting trip delay time is expired.
U> threshold LED on (if programmed) > after that the setting trip delay time is expired.
Trip output closes U> after that the setting trip delay time is expired..
U> threshold output closes (if programmed) after that the setting trip delay time is
expired.
Final checks
1.
Remove all test or temporary shorting leads, etc If it is necessary to disconnect any
of the external wiring from the relay in order to perform the wiring verification tests, it
should be ensured that all connections are replace in accordance with the relevant
external connection or scheme diagram.
2.
If a MMLG test block is installed, remove the MMLB01 test plug and replace the
MMLG cover so that the protection is put into service.
3.
For MiCOM P126 and P127 models, ensure that all event, fault and disturbance
records, alarm and LEDs have been reset before leaving the relay.
4.
If the relays are in a new installation or the circuit breaker has been just maintained,
the circuit breaker maintenance and current counters should be zero. These counters
(only P126 & P127) have to be reset using relevant command in RECORD/CB
Monitoring menu (refer to User Guide).
P12y/EN CM/Fa5
Page 20/22
5.
MAINTENANCE
5.1
Equipment failure
MiCOM P125, P126 and P127 relays are full digital and permanent self-diagnosing. Any
failure of software or hardware elements is instantly detected. As soon as an internal fault is
detected, depending on its type (minor or major), an alarm message is displayed as a priority
on the front panel LCD before the fault LED is illuminated (fixed or flashing) and the
watchdog relay is closed (if the fault is a major one).
The watchdog facility provides two output relay contacts, one normally open and one
normally closed that are driven by the processor board. These are provided to give an
indication that the relay is in a healthy state.
An equipment failure (major or minor) cannot be acknowledged on the front panel (using the
dedicated tactile button keypad). Only the disappearance of the cause will acknowledge the
fault and hence reset the fault LED.
5.1.1
Minor fault
Regarded by the MiCOM P125, P126 and P127 relays as a minor fault is a communication
failure. If the communication is in fault, MiCOM P125, P126 and P127 protection and
automation modules are not affected.
Message:
"COMM.ERROR":
Communication fault
Cause:
Hardware or software failure of the communication module
Action:
Withdraw the active part and return it to the factory for repair.
Alternative:
If communication is not used, disable communication in the COMMUNICATION menu
(Communication ? = No).
5.1.2
Major fault
Major fault for MiCOM P125, P126 and P127 relays are all software and hardware failures
except the communication faults. As soon as this type of failure is detected, the watchdog
(WD) is closed and all operations are stopped (protection, automation, communication).
5.1.3
Method of repair
5.2.1
P12y/EN CM/Fa5
Page 21/22
Remove the upper and lower flap without exerting excessive force. Remove the external
screws. Under the upper flap, turn the extractor with a 3 mm screwdriver and extract the
active part of the relay by pulling from the upper and lower notches on the front panel of the
MiCOM relay.
The reinstall the repaired or replacement relay follow the above instruction in reverse,
ensuring that no modification has been done on the scheme wiring.
5.2.2
Remove all wiring (communication, logic inputs, outputs, auxiliary voltage, current inputs).
Disconnect the relay earth connection from the rear of the relay.
Remove the screws used to fasten the relay to the panel, rack, etc .These are the screws
with the larger diameter heads that are accessible when the upper and lower flaps are open.
Withdraw the relay from the panel, rack, etc carefully because it will be heavy due to the
internal transformers.
To reinstall the repaired or replacement relay follow the above instructions in reverse,
ensuring that each terminal block is relocated in the correct position and case earth,
communication are replaced.
Once reinstallation is complete the relay should be recommissioned using the instruction in
sections 1 to 4 inclusive of this chapter.
5.3
Problem solving
5.3.1
P12y/EN CM/Fa5
Page 22/22
Action:
There is an additional unique recovery password associated to the relay which can be
supplied by the factory or service agent, if given details of its serial number (under the upper
flap of the front panel). With this serial number, contact your Schneider Electric local dealer
or Schneider Electric Customer Care Center.
5.3.2
Communication
5.3.2.1
5.3.2.2
5.3.2.3
P12y/EN CO/Fa5
CONNECTIONS AND
WIRING DIAGRAMS
P12y/EN CO/Fa5
Page 1/12
CONTENT
1.
1.1
2.
2.1
3.
3.1
4.
10
4.1
10
4.2
11
P12y/EN CO/Fa5
Page 2/12
BLANK PAGE
P12y/EN CO/Fa5
1.
Page 3/12
29
30
31
32
33
34
35
36
10
37
38
11
12
39
40
13
14
41
42
15
16
43
44
17
18
45
46
19
20
47
48
21
22
49
50
23
24
51
52
25
26
53
54
27
28
55
56
Output 5
Common output
1
Case earth
connection
29
30
Terminal
RS485
Common
output 5
Output 1 (NC)
RS485 -
31
32
RS485 +
Output 6
Output1 (NO)
Vaux +
33
34
Vaux
Common
output 6
Common output
2
Relay faulty
35
36
Common
"Watchdog"
10
Output 2 (NC)
Relay healthy
37
38
11
12
Output 2 (NO)
Residual volt.
Input -
39
40
13
14
Output 3
41
42
15
16
Common output
3
43
44
Input3 +
17
18
Output 4
45
46
Input3
19
20
Common output
4
47
48
Input4 +
21
22
Input1 +
49
50
Input4
23
24
Input1
51
52
25
26
Input2 +
53
54
27
28
Input2
55
56
Current input
(5A)
Current input
(1A)
Residual volt.
Input +
Current input
(5A)
Current input
(1A)
P12y/EN CO/Fa5
Page 4/12
1.1
35
~/ + 33
WD
Auxiliary Voltage
~/ _ 34
37
36
4
RL1
6
2
10
55
RL2
12
8
14
Phase rotation
Trip direction
A B C
P1
S1
1A
56
32N
50N
67N
59N
51N
RL3
16
18
20
3
1
7
5
47
5A
48
RL4
RL5
RL6
MiCOM
P125
da
Programmable output
Programmable output
Programmable output
Programmable output
Programmable output
22
24
26
28
17
19
21
40
Watch Dog
Programmable input L1
Programmable input L2
Programmable input L3
Programmable input L4
23
N
dn
39
Case earth connection
29
30 Terminal RS485
31
32
RS485
Communication Port
P12y/EN CO/Fa5
2.
Page 5/12
58
29
30
59
60
31
32
61
62
33
34
63
64
35
36
65
66
10
37
38
67
68
11
12
39
40
69
70
13
14
41
42
71
72
15
16
43
44
73
74
17
18
45
46
75
76
19
20
47
48
77
78
21
22
49
50
79
80
23
24
51
52
81
82
25
26
53
54
83
84
27
28
55
56
Input 7 +
57 58 Input 6 +
Output 5
Common
output 1
Case earth
connection
29 30 Terminal
RS485
Input 7
59 60 Input 6
Common
output 5
Output 1
(NC)
RS485 -
31 32 RS485+
61 62
Output 6
Output1
(NO)
Vaux +
33 34 Vaux
63 64
Common
output 6
Common
output 2
65 66
Common
output 7
10 Output 2
(NC)
67 68
Output 7
11 12 Output 2
(NO)
39 40
Voltage
input VA
69 70 Voltage
input VA
Common
output 8
13 14 Output 3
41 42 Current input
Current
input IA (5A)
IA (5A)
Voltage
input VB
71 72 Voltage
input VB
Output 8
15 16 Common
output 3
43 44 Current input
Current
input IB (5A)
IB (5A)
Voltage
input VC/Vr
73 74 Voltage
input VC/Vr
Input 3 +
17 18 Output 4
45 46 Current input
Current
input IC(5A)
IC(5A)
75 76
Input 3
19 20 Common
output 4
47 48 Current input
Current
input Ie (5A)
Ie(5A)
77 78
Input 4 +
21 22 Input 1 +
49 50 Current input
Current
input IA (1A)
IA (1A)
79 80
Input 4
23 24 Input 1
51 52 Current input
Current
input IB (1A)
IB (1A)
81 82
Input 5 +
25 26 Input 2 +
53 54 Current input
Current
input IC(1A)
IC(1A)
83 84
Input 5
27 28 Input 2
55 56 Current input
Current
input Ie (1A)
Ie(1A)
Relay
healthy
37 38
P12y/EN CO/Fa5
Page 6/12
2.1
Phase rotation
35
A B C
~/ + 33
Auxiliary Voltage
~/ _ 34
WD
37
36
4
49
RL1
6
2
10
RL2
12
8
14
P1
S1
1A
50
50
51
32N
67N
50N
51N
51
P1
S1
1A
RL3
16
52
53
P1
S1
37
59N
79
50BF
TCS
BC
55
S1
20
49
RL5
54
Trip direction
46
1A
P1
18
RL4
1A
56
41
1
7
RL6
5
9
RL7
11
13
RL8
15
5A
22
42
24
43
Programmable inputL1
26
5A
28
17
44
45
5A
46
47
5A
48
Ad
19
21
MiCOM
P126
23
25
27
58
60
57
Programmable inputL2
Programmable inputL3
Programmable inputL4
Programmable inputL5
Programmable inputL6
Programmable inputL7
59
B
29
30
73
dn
74
31
32
Terminal RS485
RS485
Communication
P0075ENb
P12y/EN CO/Fa5
3.
Page 7/12
P0072ENc
Input 7 +
57 58 Input 6 +
Output 5
Common
output 1
Case earth
connection
29 30 Terminal
RS485
Input 7
59 60 Input 6
Common
output 5
Output 1
(NC)
RS485 -
31 32 RS485+
Input 8
(1)
+ terminal
61 62 Input COM(1)
Output 6
Output1
(NO)
Vaux +
33 34 Vaux
Input A
(1)
+ terminal
63 64 Input 9
(1)
Common
output 6
Common
output 2
Input C
(1)
+ terminal
65 66 Input B
(1)
Common
output 7
10 Output 2
(NC)
Output 7
11 12 Output 2
(NO)
39 40
(3)
terminal
+ terminal
+ terminal
(3)
37 38
Current I1
meas. 1A/5A
67
Voltage
input VA
69 70 Voltage
input VA
Common
output 8
13 14 Output 3
41 42 Current input
Current
input IA (5A)
IA (5A)
Voltage
input VB
71 72 Voltage
input VB
Output 8
15 16 Common
output 3
43 44 Current input
Current
input IB (5A)
IB (5A)
Voltage
input VC/Vr
73 74 Voltage
input VC/Vr
Input 3 +
17 18 Output 4
45 46 Current input
Current
input IC(5A)
IC(5A)
Input 3
19 20 Common
output 4
47 48 Current input
Current
input Ie (5A)
Ie(5A)
(3)
68 Current I1
meas. 1A/5A
Relay
healthy
(3)
Current I2
meas. 1A/5A
75
Case earth
(2
connection
term.
77 78 RS485-2
(2)
Input 4 +
21 22 Input 1 +
49 50 Current input
Current
input IA (1A)
IA (1A)
RS485-2
(2)
terminal
79 80 RS485-2
Input 4
23 24 Input 1
51 52 Current input
Current
input IB (1A)
IB (1A)
IRIG-B mod
(2)
terminal
81 82 IRIG-B mod
(2)
Input 5 +
25 26 Input 2 +
53 54 Current input
Current
input IC(1A)
IC(1A)
IRIG-B dem
(2)
terminal
83 84 IRIG-B dem
(2)
Input 5
27 28 Input 2
55 56 Current input
Current
input Ie (1A)
Ie(1A)
(1)
76 Current I2
meas. 1A/5A
Z
+ terminal
(2)
+ terminal
terminal
Available only for P127 5 opto-inputs option (product codes P127xx1 or P127xx3).
Input COM terminal is the common terminal for inputs 8 to 12.
(2)
Available only for P127 IRIG-B and 2nd rear port option option (product codes P127xx2
or P127xx3).
The 81 and 82 terminals are used to connect the optional BNC adaptor. This one must
be plugged according to the + and GND positions marked on the adaptor.
(3)
P12y/EN CO/Fa5
Page 8/12
3.1
Measurement CT
Watchdog (4)
Output 1
Output 2
Output 3
Output 4
Output 5
Output 6
Output 7
Output 8
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Input 8
Input 9
Input 10
Input 11
50
51
67
32N
50N
51N
67N
37
46
49
79
46BC
50BF
Input 12
TC S
59
59N
27
81
81R
32
VTS
51V
86
CTS
= optional
IRIG B
Unmodulated
P0076ENf
P12y/EN CO/Fa5
B
C
A
A
Measurement CT connection
(optional)
Page 9/12
P3947ENb
P12y/EN CO/Fa5
Page 10/12
4.
4.1
Auxiliary
voltage
Phase rotation
MiCOM
P126/P127
P0101ENa
P12y/EN CO/Fa5
Auxiliary
voltage
4.2
Page 11/12
Phase rotation
MiCOM
P126/P127
P0102ENa
P12y/EN CO/Fa5
Page 12/12
BLANK PAGE
P12y/EN RS/Fa5
COMMISSIONING TEST
AND RECORD SHEET
P12y/EN RS/Fa5
Page 1/70
CONTENT
1.
COMMISSIONING TEST
1.1
Relay identification
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
1.10
1.11
10
1.12
10
1.12.1
12
1.12.2
12
2.
13
2.1
OP PARAMETERS Menu
13
2.2
CONFIGURATION menu
13
2.2.1
General options
13
2.2.2
Transfo. Ratio
14
2.2.3
LEDs 5 to 8 configuration
14
2.2.4
Inputs configuration
18
2.2.5
18
2.2.6
18
2.2.7
Alarms configuration
18
2.3
COMMUNICATION menu
21
2.3.1
HMI communication
21
2.3.2
COMM1 communication
21
2.3.3
COMM2 communication
21
2.4
PROTECTION Menu
22
2.4.1
22
2.4.2
[67N] E/GND
24
2.4.3
28
2.4.4
29
2.4.5
30
2.4.6
[49] Thermal OL
31
2.4.7
31
2.4.8
31
2.4.9
32
6
1
P12y/EN RS/Fa5
Page 2/70
2.4.10
32
2.4.11
32
2.4.12
[79] Autoreclose
33
2.4.13
34
2.4.14
34
2.5
35
2.5.1
Trip Commands
35
2.5.2
Latch relays
37
2.5.3
37
2.5.4
38
2.5.5
40
2.5.6
41
2.5.7
41
2.5.8
42
2.5.9
47
2.5.10
48
2.5.11
49
2.5.12
51V allocation
49
2.5.13
VTS allocation
50
2.5.14
CTS allocation
50
2.5.15
CB FAIL allocation
51
2.5.16
51
2.5.17
SOTF
52
2.5.18
LOGIC EQUATIONS
52
2.5.19
56
2.6
RECORDING MENU
57
2.6.1
CB MONITORING Record
57
2.6.2
57
2.6.3
INSTANTANEOUS Record
58
2.6.4
58
2.6.5
58
2.6.6
ROLLING DEMAND
58
3.
59
3.1
Introduction
59
3.2
Test equipment
59
3.3
59
3.4
Test configuration
59
3.5
59
3.6
59
3.7
60
3.7.1
60
3.7.2
60
P12y/EN RS/Fa5
Page 3/70
3.7.3
61
3.7.4
61
3.7.5
62
3.7.6
63
3.7.7
63
3.7.8
64
3.7.9
64
3.7.10
65
3.7.11
66
3.7.12
Thermal overload
66
3.8
66
3.8.1
Under voltage
66
3.8.2
67
3.8.3
Over voltage
67
3.8.4
67
3.8.5
67
3.9
68
3.9.1
68
3.9.2
68
3.9.3
69
3.9.4
Broken Conductor
69
P12y/EN RS/Fa5
Page 4/70
BLANK PAGE
P12y/EN RS/Fa5
1.
Page 5/70
COMMISSIONING TEST
BEFORE CARRYING OUT ANY WORK ON THE EQUIPMENT, THE
USER SHOULD BE FAMILIAR WITH THE CONTENTS OF THE SAFETY
GUIDE SFTY/4LM/G11 OR LATER ISSUE, OR THE SAFETY AND
TECHNICAL DATA SECTION OF THE TECHNICAL MANUAL AND ALSO
THE RATINGS ON THE EQUIPMENT RATING LABEL.
1.1
Relay identification
Commissioning date :
Engineer :
Substation :
Circuit :
Network nominal frequency:
MiCOM relay model:
P125
P126
P127
Serial number:
Rated current In :
Rated current Ien :
Rated Voltage primary :
Rated Voltage secondary:
Auxiliary voltage Uaux :
Communication protocol :
Language :
1.2
1.3
_________Vdc/Vac
Watchdog contacts
With auxiliary supply off
Terminals 35 and 36
Terminals 36 and 37
P12y/EN RS/Fa5
Page 6/70
1.4
Set in the configuration menu in the submenu Transfo Ratio as shown below.
100V
0.10 kV
Phase A:
IA:
Phase B:
IB:
Phase C:
IC:
Earth current:
Measured value
A IN:
Measured value
Phase A:
UA:
Phase B:
UB:
100V
Measured value
1.5
0.10 kV
Measured value
V
UN:
Value
applied in
In
A
Value
applied in
In
A
0.2 x I>
2 x I>
Value
applied in
In
A
0.5x I>>
Drop value in
In
1s
Drop value in
In
1s
Drop value in
In
P12y/EN RS/Fa5
Page 7/70
Value
applied in
In
A
2.5x I>>
1.6
1s
0.5xI>>>
1s
2.5xI>>>
1s
0.2 x I<
Drop value in
In
1s
0.2 x I<
1s
Value
Delay Time Trip value in
applied in Ien Setting
In
Ie>:
0.2 x Ie>
Value
Delay Time Measured
applied in Ien Setting
Trip Delay
time
Ie>:
2 x Ie>
Value
Delay Time Trip value in
applied in Ien Setting
In
Ie>>:
0.2x Ie>>
Value
Delay Time Measured
applied in Ien Setting
Trip Delay
time
Ie>>:
2 x Ie>>
Drop value in
In
1s
Drop value in
In
1s
Drop value in
In
1s
1s
Drop value in
In
P12y/EN RS/Fa5
Page 8/70
1.8
Value
Delay Time Trip value in
applied in Ien Setting
In
Ie>>>:
0.5 x Ie>>>
Value
Delay Time Measured
applied in Ien Setting
Trip Delay
time
Ie>>>:
2 x Ie>>>
Drop value in
In
1s
Drop value in
Ien, Ue, R
1s
0.5 x Ie>
Ue>:10V
2 x 10V
Torque angle : 0
+/-85
Value
applied in In,
Measured
Delay Time
in Volt and
Trip Delay
Setting
the angles in
time
degrees
Ie>:
2 x Ie>
Ue>:10V
80V
Torque angle : 0
+/-85
1s
1s
P12y/EN RS/Fa5
Page 9/70
Pe>: 20W
Value
Delay Time Measured
applied in In, Setting
Trip Delay
in Volt and
time
the angles in
degrees
0.5 x
Ien=0.5A
Ue=45V
Ue^Ie =0
tPe>=1s
c = 0
Note: Change the angle between Ue^Ie and verify the trip and drop off of the Pe stage and
the value of the Pe in the measurement menu.
1.10
Value applied
in Volt
Delay
Time
Setting
U>:
2xU>
1s
Value applied
in Volt
Delay
Time
Setting
U>:
2xU>
1s
Value applied
in Volt
Delay
Time
Setting
U<:
0.2 x U <
1s
Value applied
in Volt
Delay
Time
Setting
U<<:
0.2 x U <<
1s
Trip value in
Volt
Drop value in
Volt
Measured
Trip Delay
time
Drop value in
Volt
Trip value in
Volt
Drop value in
Volt
Measured
Trip Delay
time
Drop value in
Volt
P12y/EN RS/Fa5
Page 10/70
1.11
1.12
Value applied
in Volt
Ue>>>>:
2 x Ue>>>>
1s
Value applied
in Volt
Measured
Delay Time
Trip Delay
Setting
time
Ue>>>>:
2 x Ue>>>>
1s
Drop value in
Volt
PROTECTION G1
[67] Phase OC
I>
Yes
I>
1 In
Delay type
DMT
tI>
1 sec
I>>
Yes
I>>
2 In
Delay
DMT
tI>>
1 sec
I>>>
No
[67N] E/GND
Ie>
Yes
Ie>
1 In
Delay type
DMT
tIe>
1 sec
tReset
0,04s
No
AUTORECLOSE
Autoreclose?
YES
Ext CB Fail?
NO
Ext Block?
NO
tD1
5 sec
tD2
5 sec
tD3
5 sec
tD4
5 sec
P12y/EN RS/Fa5
Page 11/70
MENU TEXT
Reclaim Time tR
10 sec
Inhibit Time tI
0.2 sec
Phase Cycles
E/Gnd Cycles
Cycles
tI>
4321
1111
Cycles
tI>>
4321
0000
Cycles
tI>>>
4321
0000
Cycles
tIe>
4321
2222
Cycles
tIe>>
4321
0000
Cycles
tIe>>>
4321
0000
Cycles
tPe/Iecos>,
4321
0000
Cycles
tPe/Iecos>>
4321
0000
Cycles
tAux1
4321
0000
Cycles
tAux2
4321
0000
In the below table are listed the setting to have a corrected functionality of the 79 function.
The output relay, the digital input and the led assigne are free.
The indicating setting are those used for internal test.
In the output relay none other functionality can be assigned to the relay CB Close.
AUTOMATIC CTRL MENU
Output relay
CB Close
relay 2
TRIP 79
relay 8
79 Run
relay 7
Inputs menu
52a
input 1
Trip Command
tI>
Yes
tIe>
Yes
No
Configuration menu
LED
Led 5
I>
Ie>
P12y/EN RS/Fa5
Page 12/70
Led 6
tI>
tIe>
Led 7
Recl. Blocked
Led 8
Recl Run
NOTE :
1.12.1
1.12.2
To execute the ARC test you have to connect an external relay for the
monitoring the CB status (52a OFF when the CB is open, ON when
CB is closed). Further the flowing of the current to the relay must be
interrupted when the 52a is OFF; CB is open.
Close the CB and inject current the led 7 lights for 0.2 s.
When we are to the td 4 when the CB close and after 1 sec the tI> trip the 79 trip and
Recl Blocked will be actived. 4 shots was done.
Close the CB and inject the Ie current, the led 7 lights for 0.2 s.
After 1 sec the CB does not open and tDx does not start none led will be light
Commissioning Engineer :
Date :
Remarks
P12y/EN RS/Fa5
Page 13/70
2.
2.1
OP PARAMETERS Menu
Password :
Reference :
Software version :
Frequency :
2.2
CONFIGURATION menu
2.2.1
General options
50 Hz
60 Hz
VT connection
3Vpn
2Vpp + Vr
2Vpn + Vr
VT connection
Not available
Modulated
Unmodulated
VT Protection
Protect P-N
Protect P-P
Phase rotation
A-B-C
A-C-B
None
IA
IB
IC
None
IA
IB
IC
None
IA
IB
IC
Default Displays
(P126/P127)
RMS IA
RMS IB
Phases/Eath Text
(P126 / P127)
L1 L2 L3 N
ABCo
RSTE
RMS IN
RMS IC
RMS IA IB IC IN
Yes
Time Synchro.
IRIG-B
Modulated
No
COMM2
Automatic
Demodulated
Not applicable
P12y/EN RS/Fa5
Page 14/70
2.2.2
Transfo. Ratio
P126
P127
Line CT Primary
Line CT Secondary
E/Gnd CT Primary
E/Gnd CT Secondary
A
1A
A
1A
5A
Line VT primary
Line VT sec
E/Gnd VT primary
Not visible
E/Gnd VT secondary
Not visible
Not visible
Not visible
LEDs 5 to 8 configuration
P126
P127
I>
tI>
I>>
tI>>
I>>>
tI>>>
tIA>
tIB>
tIC>
Functions
P125
2.2.3
P125
Ie>
tIe>
Ie>>
tIe>>
Ie>>>
tIe>>>
Ie_d>
tIe_d>
Ie_d>>
LED 5
LED 6
LED 7
LED 8
Yes
Yes
Yes
Yes
P12y/EN RS/Fa5
P127
P126
Functions
Page 15/70
P125
tIe_d>>
P>
tP>
P>>
tP>>
P<
tP<
P<<
tP<
Q>
tQ>
Q>>
tQ>>
Q<
tQ<
Q<<
tQ<
Pe/IeCos>
tPe/IeCos>
Pe/IeCos>>
tPe/IeCos>>
I2>
tI2>
I2>>
tI2>>
I2>>>
tI2>>>
Therm. Trip
I<
tI<
U>
tU>
U>>
tU>>
U<
tU<
LED 5
LED 6
LED 7
LED 8
Yes
Yes
Yes
Yes
P12y/EN RS/Fa5
P127
Functions
P126
Page 16/70
U<<
tU<<
Ue>>>>
tUe>>>>
V2>
V2>
V2>>
V2>>
F1
tF1
F2
tF2
F3
tF3
F4
tF4
F5
tF5
F6
tF6
F Out
dF/dt1
dF/dt2
dF/dt3
dF/dt4
dF/dt5
dF/dt6
F. out
Brkn. Cond
CB Fail
VTS
CTS
Input 1
Input 2
Input 3
Input 4
LED 5
LED 6
LED 7
LED 8
Yes
Yes
Yes
Yes
P12y/EN RS/Fa5
P126
P127
Page 17/70
Input 5
Input 6
Functions
P125
Input 7
Input 8
Input 9
Input A
Input B
Input C
79 Run
79i Blocked
79e. Blocked
tAux1
tAux2
tAux3
tAux4
tAux5
tAux6
tAux7
tAux8
tAux9
tAuxA
tAuxB
tAuxC
tSOTF
tEQU. A
tEQU. B
tEQU. C
tEQU. D
tEQU. E
tEQU. F
tEQU. G
tEQU. H
LED 5
LED 6
LED 7
LED 8
Yes
Yes
Yes
Yes
P12y/EN RS/Fa5
Page 18/70
2.2.4
Inputs configuration
= ,
=
3
DC
Voltage input DC
2.2.5
AC
YES
Maintenance Mode
Relays
CMD
P122 and P123 only
7
6
P125
Input
Menu
Setting group
(P125/P126)
YES
NO
YES
NO
NO
2.2.6
Alarms configuration
P12y/EN RS/Fa5
Page 19/70
P125
P126
P127
YES
YES
YES
P12y/EN RS/Fa5
Page 20/70
Inhibited alarms
Equ E
Equ F
Equ G
Equ H
P126
P127
YES
YES
YES
P12y/EN RS/Fa5
COMMUNICATION menu
2.3.1
HMI communication
HMI ?
Page 21/70
YES
NO
Private
IEC
YES
NO
Relay address
HMI ?
2.3.2
COMM1 communication
COMM1 ?
Baud rate
Parity
Even
Stop bits
Odd
None
1
Relay address
Spont. event & GI A11
None
Private only
IEC only
All
GI select.
Basic
Advanced
YES
NO
YES
NO
YES
NO
Events + Measur.
Blocking
YES
NO
Command Blocking
YES
NO
s
Command timeout
2.3.3
COMM2 communication
COMM1 ?
YES
NO
Baud rate
Parity
Even
Stop bits
Odd
None
1
Relay address
Spont. event & GI A11
None
IEC only
Private only
All
GI select.
Basic
Advanced
YES
NO
YES
NO
YES
NO
Events + Measur.
Blocking
YES
NO
Command Blocking
YES
NO
P12y/EN RS/Fa5
Page 22/70
2.4
PROTECTION Menu
For several groups with different settings, copy this section.
G1
G2
G3
G4
G5
G6
G7
G8
2.4.1.1
[(67/)50/51] I>
I> ?
Yes
DIR (P127)
No:
Next menu: I>> ?
In
I>
I> Torque
Not displayed
Not displayed
Delay Type
DMT
RI
IEC-STI
IEC SI
IEC VI
IEC-EI
IEC-LTI
CO2
IEEE-MI
CO8
IEEE-VI
IEEE-EI
RECT
2.4.1.1.1 [(67/)50/51] I> = DMT
s
tI>
2.4.1.1.2 [(67/)50/51] I> = RI
K
t Reset
I> >> >>> Interlock
Yes
No
DMT
IDMT
Rtms
tReset
I> >> >>> Interlock
Not displayed
Not displayed
s
Yes
Not displayed
No
P12y/EN RS/Fa5
Page 23/70
[(67/)50/51] I>>
I>> ?
Yes
DIR (P127)
No:
Next menu: I>>> ?
In
I>>
I>> Torque
Not displayed
Not displayed
Delay Type
DMT
RI
IEC-STI
IEC SI
IEC VI
IEC-EI
IEC-LTI
CO2
IEEE-MI
CO8
IEEE-VI
IEEE-EI
RECT
2.4.1.2.1 [(67/)50/51] I>> = DMT
s
tI>
2.4.1.2.2 [(67/)50/51] I>> = RI
K
t Reset
2.4.1.2.3 [(67/)50/51] I>> = IEC, RECT, CO or IEEE
TMS
Reset Delay Type
DMT
IDMT
Not displayed
Rtms
Not displayed
s
tReset
2.4.1.3
Not displayed
[(67/)50/51] I>>>
I>>>?
YES
DIR (P127)
PEAK
NO (last menu)
I>>> Torque
Not displayed
Not displayed
I>>>
In
tI>>>
P12y/EN RS/Fa5
Page 24/70
2.4.2
[67N] E/GND
2.4.2.1
[67N] Ie>
Ie> ?
Yes
DIR
NO:
Next menu: Ie>> ?
Ien
Ie>
Ue>
Not displayed
Ie> Torque
Not displayed
Not displayed
Delay Type
DMT
RI
IEC-STI
IEC SI
IEC VI
IEC-EI
IEC-LTI
CO2
IEEE-MI
CO8
IEEE-VI
IEEE-EI
RECT
2.4.2.1.1 [67N] Ie> = DMT
tIe>
tReset
t Reset
Ie> >> >>> Interlock
Yes
No
DMT
IDMT
Rtms
tReset
Ie> >> >>> Interlock
Not displayed
Not displayed
s
Yes
Not displayed
No
P12y/EN RS/Fa5
Page 25/70
[67N] Ie>>
Ie>> ?
Yes
DIR
No:
Next menu: Ie>>>?
Ien
Ie>>
Ue >>
Not displayed
Ie>> Torque
Not displayed
Not displayed
Delay Type
DMT
RI
IEC-STI
IEC SI
IEC VI
IEC-EI
IEC-LTI
CO2
IEEE-MI
CO8
IEEE-VI
IEEE-EI
RECT
2.4.2.2.1 [67N] Ie>> = DMT
2.4.2.2.2
tIe>
tReset
[67N] Ie>> = RI
K
s
t Reset
2.4.2.2.3 [67N] Ie>> = IEC, RECT, CO or IEEE
TMS
Reset Delay Type
DMT
IDMT
Not displayed
Rtms
Not displayed
s
tReset
2.4.2.3
Not displayed
[67N] Ie>>>
Ie>>>?
YES
PEAK
DIR
NO (last menu)
In
Ie>>>
Ue>>>
Not displayed
Ie>>> Torque
Not displayed
Not displayed
tIe>>>
tReset
P12y/EN RS/Fa5
Page 26/70
2.4.2.4
[67N] Ie_d>
Ie_d>?
Yes
DIR
No:
Next menu: e_d>>
Ien
Ie_d>
Ue (Ie_d>)
Not displayed
Ie_d> Torque
Not displayed
Not displayed
Delay Type
DMT
RI
IEC-STI
IEC SI
IEC VI
IEC-EI
IEC-LTI
CO2
IEEE-MI
CO8
IEEE-VI
IEEE-EI
RECT
2.4.2.4.1 [67N] Ie_d> = DMT
2.4.2.4.2
tIe>
tReset
[67N] Ie_d>= RI
K
s
t Reset
2.4.2.4.3 [67N] Ie_d> = IEC, RECT, CO or IEEE
TMS
Reset Delay Type
DMT
IDMT
Rtms
tReset
Not displayed
Not displayed
Not displayed
P12y/EN RS/Fa5
Page 27/70
[67N] Ie_d>>
Ie_d>>?
Yes
DIR
No:
(last menu)
Ien
Ie_d>>
Ue (Ie_d>>)
Not displayed
Ie_d>> Torque
Not displayed
Not displayed
Delay Type
DMT
RI
IEC-STI
IEC SI
IEC VI
IEC-EI
IEC-LTI
CO2
IEEE-MI
CO8
IEEE-VI
IEEE-EI
RECT
2.4.2.5.1 [67N] Ie_d>> = DMT
2.4.2.5.2
tIe>>
tReset
[67N] Ie_d>>= RI
K
s
t Reset
2.4.2.5.3 [67N] Ie_d>> = IEC, RECT, CO or IEEE
TMS
Reset Delay Type
DMT
IDMT
Rtms
tReset
Not displayed
Not displayed
Not displayed
P12y/EN RS/Fa5
Page 28/70
2.4.3
Relay:
P>?
YES
P>
Not displayed
Directional Angle
Not displayed
tP>
Not displayed
P>?
YES
P>
Not displayed
Directional Angle
Not displayed
tP>
Not displayed
Q>?
YES
Q>
Not displayed
Directional Angle
Not displayed
tQ>
Not displayed
Q>?
YES
Q>
Not displayed
Directional Angle
Not displayed
tQ>
Not displayed
P<?
YES
P<
Not displayed
Directional Angle
Not displayed
tP<
Not displayed
P<?
P<
YES
Not displayed
Directional Angle
Not displayed
tP<
Not displayed
P12y/EN RS/Fa5
Q<?
Page 29/70
YES
x
Q<
Not displayed
Directional Angle
Not displayed
tQ<
Not displayed
Q<?
YES
Q<
2.4.4
Not displayed
Directional Angle
Not displayed
tQ<
Not displayed
[32N] mode
Pe
Pe>? or
IeCos> ?
YES
Ie Cos
NO:
Next menu P>>??/IeCos>>??
Pe> or IeCos>
Not displayed
Delay Type
DMT
RI
IEC-STI
IEC SI
IEC VI
IEC-EI
IEC-LTI
CO2
IEEE-MI
CO8
IEEE-VI
IEEE-EI
RECT
s
tPe> or tIeCos>
Not displayed
Not displayed
TMS
Not displayed
DMT
IDMT
Rtms
Not displayed
s
tReset
Pe>>? or
IeCos>> ?
Not displayed
YES
Not displayed
tPe>> or
tIeCos>>
Not displayed
tReset
Not displayed
P12y/EN RS/Fa5
Page 30/70
2.4.5
[32N] mode
Pe
Ie Cos
I2> ?
YES
I2>
Delay Type
Not displayed
DMT
RI
IEC-STI
IEC SI
IEC VI
IEC-EI
IEC-LTI
CO2
IEEE-MI
CO8
IEEE-VI
IEEE-EI
RECT
s
tI2>
Not displayed
Not displayed
TMS
Not displayed
DMT
IDMT
Rtms
Not displayed
s
tReset
I2>> ?
Not displayed
Not displayed
NO:
Next menu I2>>>?
YES
I2>>
In
Not displayed
tI2>>
Not displayed
I2>>> ?
YES
I2>>>
In
Not displayed
tI2>>>
Not displayed
P12y/EN RS/Fa5
Page 31/70
[49] Thermal OL
Relay:
Therm OL ?
I >
In
Te
mn
K
Trip
Alarm ?
YES
Alarm
2.4.7
I< ?
YES
NO
I<
In
tI<
YES
NO
YES
NO
V
Relay:
U> ?
AND
OR
No:
Next menu: U>>?
U>
Not displayed
tU>
Not displayed
U>> ?
AND
OR
No:
Last menu
U>>
Not displayed
tU>>
Not displayed
P12y/EN RS/Fa5
Page 32/70
2.4.9
Relay:
U< ?
No:
Next menu: U>>?
Not displayed
tU<
Not displayed
U<< ?
AND
OR
AND
OR
Not displayed
No:
Last menu
U<<
Not displayed
tU<<
Not displayed
AND
OR
Not displayed
2.4.11
OR
U<
2.4.10
AND
YES
Ue>>>>
Not displayed
t Ue>>>>
Not displayed
YES
V2>
Not displayed
tV2>
Not displayed
V2>> ?
YES
V2>>
Not displayed
tV2>>
Not displayed
P12y/EN RS/Fa5
Page 33/70
[79] Autoreclose
Relay:
[79] Autoreclose ?
YES
NO
Last menu
Ext CB Fail ?
YES
NO
Next menu: Ext Block?
ms
YES
NO
Rolling demand ?
YES
NO
Max cycle nb
mn
Time period
Dead Time tD1
Reclaim time tR
Inhib Time tI
Phase Cycles
E/Gnd Cycles
Cycles
4
tI>
tI>>
tI>>>
tIe>
tIe>>
tIe>>>
tPe/IeCos>
tPe/IeCos>>
tAux 1
tAux 2
P12y/EN RS/Fa5
Page 34/70
2.4.13
Relay:
Fx =
tFx
Hz *
ms *
[81] F1
_______
_______
[81] F2
_______
_______
[81] F3
_______
_______
[81] F4
_______
_______
[81] F5
_______
_______
[81] F6
_______
_______
No
2.4.14
81>
81<
Relay:
dF/dtx =
Yes
Hz/s*
[81R] dF/dt1
_______
[81R] dF/dt2
_______
[81R] dF/dt3
_______
[81R] dF/dt4
_______
[81R] dF/dt5
_______
[81R] dF/dt6
_______
P12y/EN RS/Fa5
2.5.1
Trip Commands
Function
Trip tI>
Trip tI>>
Trip tI>>>
Trip tIe>
Trip tIe>>
Trip tIe>>>
Trip tIe_d>
Trip tIe_d>>
Trip tP>
Trip tP>>
Trip tP<
Trip tP<<
Trip tQ>
Trip tQ>>
Trip tQ<
Trip tQ<<
Trip tPe/IeCos>
Trip tPe/IeCos>>
Trip tI2>
Trip tI2>>
Trip tI2>>>
Trip Thermal
Trip tU>
Trip tU>>
Trip tU<
Trip tU<<
Trip tUe>>>>
Trip tV2>
Trip tV2>>
Trip tF1
Trip tF2
Page 35/70
P125
P126
P127
Yes
Yes
Yes
P12y/EN RS/Fa5
Page 36/70
Trip tF3
Trip tF4
Trip tF5
Trip tF6
Trip dF/dt1
Trip dF/dt2
Trip dF/dt3
Trip dF/dt4
Trip dF/dt5
Trip dF/dt6
Trip Brkn. Cond
Trip tAux 1
Trip tAux 2
Trip tAux 3
Trip tAux 4
Trip tAux 5
Trip tAux 6
Trip tAux 7
Trip tAux 8 (option)
Trip tAux 9 (option)
Trip tAux A (option)
Trip tAux B (option)
Trip tAux C (option)
Trip SOTF
Ctrl Trip
Trip tEQU A
Trip tEQU B
Trip tEQU C
Trip tEQU D
Trip tEQU E
Trip tEQU F
Trip tEQU G
Trip tEQU H
P125
P126
P127
Yes
Yes
Yes
P12y/EN RS/Fa5
Page 37/70
Latch relays
P125
Latch relays
2.5.3
P125
P126
P127
Yes
Yes
Yes
P12y/EN RS/Fa5
Page 38/70
P125
P126
P127
Yes
Yes
Yes
P125
P126
P127
Yes
Yes
Yes
tV2>
tV2>>
tF1
tF2
tF3
tF4
tF5
tF6
tBrk. Cond
tAux1
tAux2
tAux3
tAux4
tAux5
tAux6
tAux7
tAux8 (option)
tAux9 (option)
tAuxA (option)
tAuxB (option)
tAuxC (option)
2.5.4
P12y/EN RS/Fa5
Page 39/70
P125
P126
P127
Yes
Yes
Yes
P12y/EN RS/Fa5
Page 40/70
P125
P126
P127
Yes
Yes
Yes
tAux3
tAux4
tAux5
tAux6
tAux7
tAux8 (option)
tAux9 (option)
tAuxA (option)
tAuxB (option)
tAuxC (option)
2.5.5
Blocking Inrush
YES
NO
T Inrush reset
ms
Function
I>
I>>
I>>>
Ie>
Ie>>
Ie>>>
Ie_d>
Ie_d>>
I2>
I2>>
I2>>>
P127
Yes
P12y/EN RS/Fa5
Page 41/70
Sel1 tI>>
YES
NO
Sel1 tI>>>
YES
NO
Sel1 tIe>>
YES
NO
Sel1 tIe>>>
YES
NO
YES
NO
YES
NO
ms
t Sel1
2.5.7
Sel1 tI>>
YES
NO
Sel1 tI>>>
YES
NO
Sel1 tIe>>
YES
NO
Sel1 tIe>>>
YES
NO
Sel1 tIe_d>
YES
NO
YES
NO
t Sel2
ms
P12y/EN RS/Fa5
Page 42/70
OUTPUT RELAYS allocation
P125
= available
O = Option (P127)
P126
P127
P126 / P127
Trip
I>
tI>
I_R>
I>>
tI>>
I_R>>
I>>>
tI>>>
I_R>>>
tIA>
tIB>
tIC>
Function
P125
2.5.8
Ie>
tIe>
Ie_R>
Ie>>
tIe>>
Ie_R>>
Ie>>>
tIe>>>
Ie_d>
tIe_d>
Ie_dR>
Ie_d>>
tIe_d>>
Ie_dR>>
P>
tP>
P>>
tP>>
Yes
Yes
Yes
Yes
Yes
Yes
P12y/EN RS/Fa5
Page 43/70
P125
= available
O = Option (P127)
P127
P126
P125
Function
P126 / P127
P<
tP<
P<<
tP<<
Q>
tQ>
Q>>
tQ>>
Q<
tQ<
Q<<
tQ<<
Pe/IeCos>
tPe/IeCos>
Pe/IeCos>>
tPe/IeCos>>
I2>
tI2>
I2>>
tI2>>
I2>>>
tI2>>>
ThermAlarm
ThermTrip
I<
tI<
U>
tU>
U>>
tU>>
U<
tU<
Yes
Yes
Yes
Yes
Yes
Yes
P12y/EN RS/Fa5
Page 44/70
= available
O = Option (P127)
P127
P126
P125
Function
P126 / P127
U<<
tU<<
Ue>>>>
tUe>>>>:
V2>
tV2>
V2>>
tV2>>
F1
tF1
F2
tF2
F3
tF3
F4
tF4
F5
tF5
F6
tF6
F.OUT
dF/dt1
dF/dt2
dF/dt3
dF/dt4
dF/dt5
dF/dt6
BrknCond
CBAlarm
52 Fail
CBFail
CB Close
Yes
Yes
Yes
Yes
Yes
Yes
P12y/EN RS/Fa5
Page 45/70
P125
= available
O = Option (P127)
P125
P126
P127
P126 / P127
tAux1
tAux2
tAux3
tAux4
Function
tAux5
tAux6
tAux7
tAux8
tAux9
tAuxA
tAuxB
tAuxC
79 Run
79 Trip
79 int. Lock
79 ext. Lock
SOTF
CONTROLTRIP
CONTROLCLOSE
ActiveGroup
Input1 :
Input2
Input3 :
Input4
Input5
Input6
Input7
Input8
Input8
InputA
InputB
InputC
Yes
Yes
Yes
Yes
Yes
Yes
P12y/EN RS/Fa5
Page 46/70
= available
O = Option (P127)
P127
P126
P125
Function
P126 / P127
VTS
CTS
t EQU.A
t EQU.B
t EQU.C
t EQU.D
t EQU.E
t EQU.F
t EQU.G
T EQU.H
Order Comm1
Order Comm2
Order Comm3
Order Comm4
Yes
Yes
Yes
Yes
Yes
Yes
P12y/EN RS/Fa5
2.5.9.1
Inputs
Page 47/70
P125
= available
O = Option.
P125
P126
P127
P126 / P127
None
Unlatch
Blk Log 1
Blk Log 2
52 a
52 b
CB FLT
Function
Aux 1
Aux 2
Aux 3
Aux 4
Aux 5
Aux 6
Aux 7
Aux 8
Aux 9
Aux A
Aux B
Aux C
Strt Dist
Cold L PU
Log Sel 1
Log Sel 2
Change Set
Block_79
Reset
Trip Circ
Start t BF
Maint. M
SOTF
Local
Synchro.
option P127
Inputs
1
P12y/EN RS/Fa5
Page 48/70
= available
O = Option.
P125
P126
P127
Led Reset or
Reset Led
Ctrl Trip
Ctr Close
Function
2.5.9.2
2.5.10
P126 / P127
option P127
Inputs
1
tAux
Aux 1 : Time tAux 1
Brkn Cond ?
Broken Conductor time tBC
Ratio I2/I1
YES
NO
s
%
P12y/EN RS/Fa5
Page 49/70
Cold Load PU ?
YES
NO
Input ?
YES
NO
Auto ?
YES
NO
tI> ?
YES
NO
tI>> ?
YES
NO
tI>>> ?
YES
NO
tIe> ?
YES
NO
tIe>> ?
YES
NO
tIe>>> ?
YES
NO
tIe_d> ?
YES
NO
tIe_d>> ?
YES
NO
t2> ?
YES
NO
t2>> ?
YES
NO
T Therm ?
YES
NO
%
51V allocation
Relay:
V2>?
(U< OR V2>) & I>>?
V2>?
YES
YES
not displayed
NO (last menu)
not displayed
P12y/EN RS/Fa5
Page 50/70
2.5.13
VTS allocation
Relay:
VTS?
YES
NO (last menu)
VTS Alarm?
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
s
tVTS
2.5.14
CTS allocation
Relay:
CT Supervision?
YES
NO (last menu)
Ie>
In
Ue<
tCTS
P12y/EN RS/Fa5
CB FAIL allocation
Relay:
CB Fail ?
2.5.16
Page 51/70
YES
NO (last menu)
I< BF
In
not displayed
In
not displayed
Block I> ?
Yes
No
not displayed
Block Ie> ?
Yes
No
not displayed
TC Supervision?
YES
s
YES
YES
NO
ms
CB Close Time
CB Open Alarm?
NO
ms
CB Open Time
CB Close S'vision
NO
YES
NO
YES
NO
CB Open NB
Amps(n)?
Amps(n)
n
t Open Pulse
ms
t Close Pulse
ms
P12y/EN RS/Fa5
Page 52/70
2.5.17
SOTF
Relay:
SOTF?
YES
NO
ms
t SOTF
2.5.18
I>> ?
YES
NO
I>>> ?
YES
NO
YES
NO
SOTF input
YES
NO
YES
NO
[79] closing
YES
NO
YES
NO
YES
NO
YES
NO
LOGIC EQUATIONS
Equ. A
Boolean
A.00
A.01
OR
A.02
A.03
A.04
A.05
A.06
A.07
A.08
A.09
A.10
A.11
A.12
A.13
A.14
A.15
/
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
Logic
= NOT
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
/
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
T Operate
ms
T Reset
ms
P12y/EN RS/Fa5
Boolean
B.00
B.01
OR
B.02
B.03
B.04
B.05
B.06
B.07
B.08
B.09
B.10
B.11
B.12
B.13
B.14
B.15
Page 53/70
/
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
Logic
= NOT
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
/
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
T Operate
ms
T Reset
ms
Equ. C
Boolean
C.00
C.01
OR
C.02
C.03
C.04
C.05
C.06
C.07
C.08
C.09
C.10
C.11
C.12
C.13
C.14
C.15
/
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
Logic
= NOT
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
/
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
T Operate
ms
T Reset
ms
P12y/EN RS/Fa5
Page 54/70
Equ. D
D.00
D.01
OR
D.02
D.03
D.04
D.05
D.06
D.07
D.08
D.09
D.10
D.11
D.12
D.13
D.14
D.15
/
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
Logic
= NOT
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
/
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
T Operate
ms
T Reset
ms
Equ. E
Boolean
E.00
E.01
OR
E.02
E.03
E.04
E.05
E.06
E.07
E.08
E.09
E.10
E.11
E.12
E.13
E.14
E.15
/
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
Logic
= NOT
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
/
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
T Operate
ms
T Reset
ms
P12y/EN RS/Fa5
Boolean
F.00
F.01
OR
F.02
F.03
F.04
F.05
F.06
F.07
F.08
F.09
F.10
F.11
F.12
F.13
F.14
F.15
Page 55/70
/
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
Logic
= NOT
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
/
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
T Operate
ms
T Reset
ms
Equ. G
Boolean
G.00
G.01
OR
G.02
G.03
G.04
G.05
G.06
G.07
G.08
G.09
G.10
G.11
G.12
G.13
G.14
G.15
/
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
Logic
= NOT
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
/
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
T Operate
ms
T Reset
ms
P12y/EN RS/Fa5
Page 56/70
Equ. H
H.01
OR
H.02
H.03
H.04
H.05
H.06
H.07
H.08
H.09
H.10
H.11
H.12
H.13
H.14
H.15
2.5.19
H.00
/
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
OR /
Logic
= NOT
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
= OR NOT /
/
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND /
AND
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
= AND NOT
T Operate
ms
T Reset
ms
tCommand1
tCommand1
tCommand1
tCommand4
P12y/EN RS/Fa5
RECORDING MENU
2.6.1
CB MONITORING Record
Page 57/70
CB Closing Time
Amps (n) IA
Amps (n) IB
Amps (n) IC
2.6.2
Fault date
Faulted phase
None
Phase A
Phase B
Phase C
Earth
Threshold
Magnitude
IA Magnitude
IB Magnitude
IC Magnitude
IN Magnitude
VN Magnitude
IA^VBC Angle
IB^VCA Angle
IC^VAB Angle
IN^VN Angle
P12y/EN RS/Fa5
Page 58/70
2.6.3
INSTANTANEOUS Record
Number
Hour
Date
Origin
s
Length
Trip
2.6.4
YES
Post-Time
NO
On trip
On inst.
Time Window
2.6.6
ROLLING DEMAND
P126 and P127 only
mn
Sub Period
Num of Sub Per.
RECORDS
Fault Record
Record Number
N.A.
Pre-Time
N.A.
0.1
0.1
Post-Time
N.A.
0.1
0.1
N.A.
ON TRIP or
Time Window
N.A.
5 mn,
10 mn,
15mn,
30mn,
60mn
Rolling Demand
N.A.
5 mn,
10 mn,
15mn,
30mn,
60mn
Time Window
N.A.
1 mn
Disturb Record
ON INST.
60 mn
1 mn
P12y/EN RS/Fa5
Page 59/70
3.
3.1
Introduction
The following procedures are written for demonstrating the main protection functions of the
MiCOM P126 (where possible) & P127 relays using an Omicron test or similar. The tests do
not test the limits / boundaries of all available function characteristics. They do tests that the
function is operating at one or two chosen points an a characteristic. This document is not a
complete commissioning procedure but could be referred to when performing commissioning
tests in association with the commissioning section of the service manual.
The procedures will state if a deviation from the standard connections or default settings is
required for testing a particular function. For specific on site applications only enabled
functions would be tested using application specific settings.
3.2
Test equipment
The test procedure has been written on the assumption that an Omicron, or equivalent, test
set will be used. Auxiliary supplies of adequate rating will also be required.
3.3
3.4
Earth Current :
0.01 to 8Ien
Voltage input :
57-130V
130-250Vdc/110-250Vac
Communication protocol :
Mod Bus
HMI Language :
English
Relay software :
Current Version
Test configuration
Input the factory default settings. These settings shall then be downloaded and recorded in
the test results. Any changes to the settings required by this test procedure shall be recorded
in the test results. Any deviation from the default settings will be indicated for each test.
3.5
3.6
VT Connection :
3Vpn
Line CT primary :
1A
Line CT secondary :
1A
E/Gnd CT primary :
1A
E/Gnd CT secondary :
1A
Line VT primary :
0.10 kV
Line VT secondary :
100 V
P12y/EN RS/Fa5
Page 60/70
3.7
3.7.1
ON
1 In
Characteristic
IDMT
Curve
TMS
0.025
0.04 s
Inject current of 0.95 In into the A phase input. Increase the current in 0.01In steps, pausing
for 2.5s between each step, until the relay operates. The current must then be reduced in the
same manner until the protection resets.
Repeat the above tests for all phases.
Repeat the above test for other overcurrent stages taking in account that the delay time for
nthe second and third threshold is DMT (t=0s). Make the test before on I>> after on I>>>.
3.7.1.1
Pass Criteria
For the relay to pass it shall operate as detailed below.
Delay trip IDMT (inverse time only for I>):
1.1Is 2%.
1.04Is 2%.
3.7.2
Is 2%.
Is 2%.
Is
1 In
Characteristic
DT / IDMT
Curve
TMS
1.0
Time Delay
1s
Directionality
Non-directional
0s
Enable stage 1 overcurrent and prepare the tests set so that A phase current can be
instantaneously applied at 2In and 10In respectively. Measure the operating times of the
relay start and trip contacts. Repeat the test with the element set to IDMT. Repeat the test
with the element disabled and verify that no start or trip elements operate.
Repeat the above testing for all phases and stages (with the exception of IDMT which is only
for the first stage).
P12y/EN RS/Fa5
Page 61/70
Pass Criteria
For the relay to pass it shall operate as detailed below
DT operating time
1.0s 2%
10.070s 2% at 2 In.
2.991s 2% at 10 In.
3.7.3
3.7.3.1
0.1Ien
Characteristic
IDMT
Curve
TMS
0.025
Delay time
0s
Directionality
Non-directional
0.04s
Enable stage 1of Earth Fault protection and inject current of 0.095Ies into the Ie current
input. Increase the current in 0.001In steps, pausing for 2.5s between each step, until the
relay operates.
The current must then be reduced in the same manner until the protection resets.
Repeat the above test for all stages of Earth fault protection (delay type is DT).
3.7.3.2
Pass Criteria
For the relay to pass it shall operate as detailed below.
3.7.4
Characteristic
DT / IDMT
Curve
Standard Inverse
TMS
1.0
Time Delay
1s
Directionality
Non-directional
0s
Is
1 Ien
Enable stage 1 of Earth Fault protection and prepare the tests set so that Ie current can be
instantaneously applied at 2 Ies and 10 Ies respectively. Measure the operating times of the
relay start and trip contacts. Repeat the test with the element set to IDMT. Repeat the test
with the element disabled and verify that no start or trip elements operate.
Repeat the above testing for all stages (IDMT is only for the first stage).
P12y/EN RS/Fa5
Page 62/70
3.7.4.1
Pass Criteria
For the relay to pass it shall operate as detailed below.
DT operating time
1.0s 2%
10.07s 2% at 2 Ies
2.999s 2% at 10 Ies
3.7.5
3.7.5.1
E/GND Primary
5A
E/GND Secondary
5A
Ie>
0.2 Ien
Characteristic
IDMT
Curve
TMS
Ue
1V
Trip Zone
-45/+45
Torque Angle
180
Directionality
Directional
0.04s
3.7.5.2
Pass Criteria
For the relay to pass it shall operate as detailed below.
Pick-up should occur at 1.1 Ies 2%.
P12y/EN RS/Fa5
Page 63/70
3.7.6.1
Pass Criteria
For the relay to pass; it shall operate as detailed below.
The trip occurs after 5s.
Time accuracy: +/-2% or 20.40ms
3.7.7
VT connection
3Vpn.
Characteristic
DT
Is
0.2 Ien
Torque Angle(RCA)
180
+/-45
Enable stage and configure the test set applying Ua=50V, Ub=57.70V, Uc=57.70V.
Apply A phase current of twice setting at 50 leading the A phase voltage.
Increase/decrease the angle between the phase A voltage and current in step of 1 every
2.5s and determine the angle at which the start contacts non-operate and operate, once the
element has started decrease/increase the angle and determine the drop-off.
Repeat the same test for IDMT delay trip time using the previous settings.
3.7.7.1
Pass Criteria
For the relay to pass the following must be satisfied:
The directional decision shall be from the following equations:
Directional forward
The operating boundary shall be within 3 of the relay characteristic angle 45.
The element shall drop off within 3 of pick-up.
P12y/EN RS/Fa5
Page 64/70
3.7.8
Characteristic
DT / IDMT
Curve
Standard Inverse
TMS
1.0
Time Delay
1s
Directionality
Non-directional
0s
Is
1 Ien
Enable stage 1 of Earth Fault protection and prepare the tests set so that Ie current can be
instantaneously applied at 2 Ies and 10 Ies respectively. Measure the operating times of the
relay start and trip contacts. Repeat the test with the element set to IDMT. Repeat the test
with the element disabled and verify that no start or trip elements operate.
Repeat the above testing for all stages (IDMT is only for the first stage).
3.7.8.1
Pass Criteria
For the relay to pass it shall operate as detailed below.
DT operating time
1.0s 2%,
3.7.9
10.07s 2% at 2 Ies
2.999s 2% at 10 Ies
VT connection
3Vpn.
Characteristic
DT
Is
1 In
+/-80
Enable stage 1of Overcurrent and configure the test set to apply balanced three phase
nominal voltages (57.7V) to the voltage inputs.
Apply A phase current of twice setting at 30 leading the A phase voltage.
Increase/decrease the angle between the A phase voltage and current in step of 1 evry 2.5s
and determine the angle at which the start contacts non-operate and operate, once the
element has started decrease/increase the angle and determine the drop-off.
P12y/EN RS/Fa5
Page 65/70
Pass Criteria
For the relay to pass the following must be satisfied:
The directional decision shall be from the following equations:
Directional forward
The operating boundary shall be within 3 of the relay characteristic angle 80.
The element shall drop off within 3 of pick-up.
3.7.10
Relay settings:
Inject: Ua=57.7V, Ub= 57.7V, Uc=57.7V with these values the Ue is equal to 0.
Inject the Ia phase current with displacement 0 with Ua to have the following ratios Pe/Pe> :
2, 3, 4
=
Ue 1/3(Ua+Ub+Uc) (vectorial summation)
Pass Criteria
For the relay to pass it shall operate as detailed below.
IDMT operating time :
Accuracy: 2% or 30..40ms
P12y/EN RS/Fa5
Page 66/70
3.7.11
DT time Delay
10s
I2>
0.1In
Apply three phase currents to the relay at a magnitude of In. Step change the A phase
current to a magnitude of 0.5In. Verify that the fault record indicates that the negative
sequence overcurrent has started.
Repeat the above testing with the time delay set to 0s. The fault record should now indicate
trips.
3.7.11.1
Pass Criteria
For the relay to pass it shall operate as detailed above.
3.7.12
Thermal overload
Object:
The following tests verify that thermal overload starts and trips applied to the relay operate
correctly.
Test with the following relay settings:
0.5 In
No
Time Constant Te
1 min
Trip
100%
Configure the test set to apply 3 phase balanced current to the relay
Reset the thermal time state of the relay. Inject three phase 0.55 In to the relay and measure
the operating time of the contact. Verify that the fault record indicates that the thermal
overload alarm has operated followed by a thermal overload trip after 107 s 2%.
3.7.12.1
Pass Criteria
For the relay to pass it shall operate as detailed above.
3.8
3.8.1
Under voltage
Object:
The following tests verify that under voltage starts and trips applied to the relay operate
correctly.
Test with the following relay settings:
Mode
OR
Characteristic
DT
DT
30s
P12y/EN RS/Fa5
Page 67/70
U<
50V
Enable stage 1 over voltage and apply rated three phase voltages (57.7V per phase) to the
relay. After 2s reduce the phase A voltage and phase B voltage to 20V. Measure the
operating times of the relay start and trip contacts. Repeat the test with the element disabled
and verify that no start or trip elements operate.
Repeat the above tests for stage 2 under voltage.
3.8.3
Over voltage
Object:
To verify that over voltage starts and trips applied to the relay operate correctly.
Test with the following relay settings:
3.8.4
Mode
OR
Characteristic
DT
DT
10s
U>100V
Enable stage 1 and apply three phase voltages (50V per phase) to the relay. After 1s
increase the phase A voltage and phase B voltage to 60V. Measure the operating times of
the relay start and trip contacts. Repeat the test with the element disabled and verify that no
start or trip elements operate.
Repeat the above testing for stage 2 overvoltage.
3.8.5
Ue
Ue>>>>
10V
Trip Delay
10s
Enable stage of the residual overvoltage protection and apply balanced three phase voltages
to the relay (57.7V per phase) after 2s reduce UA phase voltage to 25V . Measure the
operating times of the relay start and trip contacts. Repeat the test with the element disabled
and verify that no start or trip elements operate.
3.8.5.1
Pass Criteria
For the relay to pass it shall operate as detailed below.
P12y/EN RS/Fa5
Page 68/70
3.9
3.9.1
+ Vdc
52a
Trip
order
Optoinput
MiCOM P126/P127
- Vdc
P0096ENa
Characteristic
DT
Time Delay
0s
Directionality
Non-directional
0s
Is (I>)
1 In
Time Delay
0s
I<BF
0.5 In
tBF
5s
CBF:
P12y/EN RS/Fa5
Page 69/70
The relay shall be configured with trip commands relay assigned to t_I>, with relay 2
assigned to CB fail function and with relay 2 assigned as latched.
Enable stage 1 overcurrent and apply three phase currents to the relay at 0.8 In for 1s;
instantaneously increase the currents applied to the ABC phase inputs to 2 In for 7s. Verify
after the increase that tat the relays number 2 change in the status display windows to level
1 after 5s.
3.9.2.1
Pass Criteria
For the relay to pass it shall operate as detailed above.
3.9.3
t_I>
Yes
Level
200%
tCL
5.0 s
Overcurrent:
Characteristic
DT
Time Delay
2s
Directionality
Non-directional
0s
Is (I>)
1In
Inputs:
Input 1
Cold L PU
Apply three phase currents to the relay at a magnitude of 1.5 In and supply the input 1.
Verify after 8 sec the trip of the overcurrent is recrided as a fault record
3.9.3.1
Pass Criteria
For the relay to pass it shall operate as detailed above.
3.9.4
Broken Conductor
Object:
The following tests verify that a broken conductor condition causes the relay to operate
correctly.
Test with the following relay settings:
I2/I1 setting
20%
Characteristic
DT
Time Delay
10s
Apply rated three phase currents (1In). After 10 seconds have elapsed, reduce the current in
A phase to zero and measure the time taken for the relay to indicate a broken conductor trip.
Repeat the test with the element disabled and verify that no start or trip elements operate.
3.9.4.1
Pass Criteria
For the relay to pass it shall operate as detailed below.
P12y/EN RS/Fa5
Page 70/70
BLANK PAGE
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
P12y/EN VC/Fa5
HARDWARE/SOFTWARE
VERSION
HISTORY AND
COMPATIBILITY
P125 P126-P127 V15
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
P12y/EN VC/Fa5
Page 1/28
CONTENTS
1.
INTRODUCTION
2.
MiCOM P125
3.
MiCOM P126
10
4.
MiCOM P127
18
P12y/EN VC/Fa5
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
Page 2/28
BLANK PAGE
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
1.
P12y/EN VC/Fa5
Page 3/28
INTRODUCTION
HARDWARE INSTALLED
HARD 4: First version of hardware (Px2x Phase 1)
HARD 5: Latest version of hardware (Px2x Phase 2)
P12y/EN VC/Fa5
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
Page 4/28
2.
MiCOM P125
P125 Serial number Hardware Correlation
Serial Number
Hardware installed
Phase 1
HARDWARE VERSION 4
Phase 2
HARDWARE VERSION 5
2001
Backward
S1
Compatibility
Compatiwith previous
bility
hardware
V2.03
HARD 4
V2.03
HARD 4
V2.10
HARD 4
2001
V5
2003
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
P12y/EN VC/Fa5
Page 5/28
09/2003
Backward
S1
Compatibility
Compatiwith previous
bility
hardware
V2.10
Hard 2
or
Hard 4
V2.11
Hard 4
V2.12
Hard 4
V2.12
Hard 4
09/2005
V6.F
09/2005
V6.F1
01/2007
P12y/EN VC/Fa5
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
Page 6/28
Relay Type P125
Software Date of
Version Issue
Backward
S1
Compatibility
Compatiwith previous
bility
hardware
V6.G
02/2007
V2.12
Software changes implemented in this version
- Software corrections:
. Angle Ie/Ue,
. [67n]U>> and [67N]U>>> initialization (comm. Modbus),
. data copy address during initialization,
. elimination of offset of analog input in the displayed measurement of
IE & UE,
. Initialization of minimum threshold of I0 & U0,
. trip and auxiliary relays latches,
. implementation of commands of group 1 and group 2 (IEC60870-5103),
. IN event start (IEC60870-5-103),
. Correction alarm string display,
. minimum of amplitude to calculate frequency,
. IeCos calculation with verification of Ue voltage,
. Control trip and Control close french label,
. Initialisation of the process after CT and VT ratio setting with modbus
comm.,
. DMT temporization parameter TiE>> visibility,
. Io_cos & Po_cos when IR injected is near saturation,
. Ue>>> fault records french label,
. Ia, Ib and Ic channels scale factor in disturbance record extraction.
Hard 4
V6.H
01/2008
V2.13
Hard 4
V2.13
Hard 5
08/2006
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
P12y/EN VC/Fa5
Page 7/28
06/2007
Backward
S1
Compatibility
Compatiwith previous
bility
hardware
V2.14
Hard 5
- Communication Modbus:
V2.14
. modification of the manual acknowledgement of oldest event and fault
record,
. modification of the disturbance record acknowledgement status,
. modification of the remote control for disturbances acknowledgement,
. disturbance record: correction of number of pages and number of
samples in the service frame.
Hard 5
V11.B
12/2007
P12y/EN VC/Fa5
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
Page 8/28
Relay Type P125
Software Date of
Version Issue
V11.C
06/2009
Backward
S1
Compatibility
Compatiwith previous
bility
hardware
V3.1
Hard 5
V3.1
Hard 5
V3.1
Hard 5
V3.1
Hard 5
V3.1
Hard 5
09/2009
V12.B
01/2010
V12.C
V14.A
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
P12y/EN VC/Fa5
Page 9/28
10/2011
Backward
S1
Compatibility
Compatiwith previous
bility
hardware
V3.1
Hard 5
P12y/EN VC/Fa5
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
Page 10/28
3.
MiCOM P126
P126 - Serial number Hardware Correlation
Serial Number
Hardware installed
Phase 1
HARDWARE VERSION 4
Phase 2
HARDWARE VERSION 5
2001
V4.A
to
V4.J
2001
2003
Backward
S1
Compatibility
Compatiwith previous
bility
hardware
V2.03
HARD 4
V2.03
HARD 4
V2.10
HARD 4
V5.A
V5.B
V5.C
2003
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
P12y/EN VC/Fa5
Page 11/28
09/2003
Backward
S1
Compatibility
Compatiwith previous
bility
hardware
V2.10
Hard 2
or
Hard 4
V2.11
Hard 4
10/2004
P12y/EN VC/Fa5
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
Page 12/28
Relay Type P126
Software Date of
Version Issue
V6.C
12/2004
Backward
S1
Compatibility
Compatiwith previous
bility
hardware
V2.11
Hard 4
V2.12
Hard 4
- Protocol IEC60870-5-103:
. management of private/public address added,
. Class 1 information corrected,
. no ASDU23 sent after disturbance creation if already connected
corrected,
. Reset LED not updated information corrected,
. time synchro. correction,
- Broken conductor: logic equation A, B, C and D corrected,
- Cyrillic character display corrected,
- Frequency tracking correction.
V6.D
09/2005
V6.F
09/2005
V2.12
01/2007
V2.12
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
P12y/EN VC/Fa5
Page 13/28
Backward
S1
Compatibility
Compatiwith previous
bility
hardware
V6.G
V2.12
Software changes implemented in this version
- Software defects corrections:
. Angle Ie/Ue,
. SF6 alarm text,
. [67n]U>> and [67N]U>>> initialisation (comm. Modbus),
. time synchronization frame reception (IEC60870-5-103),
. data copy address during initialization,
. verification of local mode to inhibit command (IEC60870-5-103),
. trip and auxiliary relays latches,
. IN event start (IEC60870-5-103),
. Correction alarm string display,
. minimum of amplitude to calculate frequency,
. IeCos calculation with verification of Ue voltage,
. Control trip and Control close french label,
. Initialisation of the process after CT and VT ratio setting with
modbus comm.,
. frequency of disturbance records is nominal network frequency
according to comtrade format,
. Equation logic for I2>>> and tI2>>>,
. DMT temporization parameter TiE>> visibility,
. blocking Logic of thermal state,
. protection thermal Ith> and Te initialization after setting,
. amplitude of IeCos fault,
. Io_cos & Po_cos when IR injected is near saturation,
. Ue>>> fault records french label,
. Period of samples of disturbance extracted (IEC60870-5-103),
. ASDU 9 unused fields,
. recloser blocked or VTS alarm after switching ON/OFF,
. Ia, Ib and Ic channels scale factor in disturbance record extraction,
. disturbance record upload of channels for U0 and frequeency,
. RAM content verification at starting.
V6.H
V2.13
Hard 4
P12y/EN VC/Fa5
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
Page 14/28
Relay Type P126
Software Date of
Version Issue
V10.D
08/2006
Backward
S1
Compatibility
Compatiwith previous
bility
hardware
V2.13
Hard 5
V2.14
Hard 5
06/2007
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
P12y/EN VC/Fa5
Page 15/28
12/2007
Backward
S1
Compatibility
Compatiwith previous
bility
hardware
V2.14
Hard 5
V3.1
Hard 5
06/2009
P12y/EN VC/Fa5
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
Page 16/28
Relay Type P126
Software Date of
Version Issue
V12.A
09/2009
Backward
S1
Compatibility
Compatiwith previous
bility
hardware
V3.1
Hard 5
V3.1
Hard 5
V3.1
Hard 5
01/2010
V12.C
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
P12y/EN VC/Fa5
Page 17/28
03/2011
Backward
S1
Compatibility
Compatiwith previous
bility
hardware
V3.1
Hard 5
V3.1
Hard 5
10/2011
P12y/EN VC/Fa5
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
Page 18/28
4.
MiCOM P127
P127 - Serial number Hardware Correlation
Serial Number
Hardware installed
Phase 1
HARDWARE VERSION 4
Phase 2
HARDWARE VERSION 5
2001
V4.A
to
V4.J
2001
2003
S1
Compatibility
Backward
Compatibility
with previous
hardware
V2.03
HARD 4
V2.03
HARD 4
V2.10
HARD 4
V5.A
V5.B
V5.C
2003
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
P12y/EN VC/Fa5
Page 19/28
09/2003
S1
Compatibility
Backward
Compatibility
with previous
hardware
V2.10
Hard 2
or
Hard 4
V2.10
Hard 2
or
Hard 4
09/2003
P12y/EN VC/Fa5
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
Page 20/28
Relay Type P127
Software Date of
Version Issue
V6.B
10/2004
S1
Compatibility
Backward
Compatibility
with previous
hardware
V2.11
Hard 4
V2.11
Hard 4
V2.12
Hard 4
V2.12
Hard 4
V6.C
12/2004
correction of I> and I>> start when I> or I>> are in yes or dir
mode, and I>>> in peak mode,
V6.D
09/2005
V6.E
09/2005
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
P12y/EN VC/Fa5
Page 21/28
09/2005
S1
Compatibility
Backward
Compatibility
with previous
hardware
V2.12
01/2007
V2.12
V6.G
02/2007
V2.12
Hard 4
P12y/EN VC/Fa5
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
Page 22/28
Relay Type P127
Software Date of
Version Issue
V6.H
01/2008
S1
Compatibility
V2.13
Software changes implemented in this version
- if U< and U<< protection is used with 51V, ther is no alarm and no
blocking of change group from this protection,
Backward
Compatibility
with previous
hardware
Hard 4
08/2006
V2.13
Hard 5
V2.14
Software changes implemented in this version
- 2nd harmonic blocking: For each three currents phases the
harmonic restraint compare the ratio of harmonic 2 to fundamental
with the ratio setting. Inrush detection could block I>, I>>, I>>>,
Ie>, Ie>>, Ie>>>, I2>, I2>> and I2>>>
Hard 5
V11.A
06/2007
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
P12y/EN VC/Fa5
Page 23/28
S1
Compatibility
Backward
Compatibility
with previous
hardware
P12y/EN VC/Fa5
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
Page 24/28
Relay Type P127
Software Date of
Version Issue
V11.B
12/2007
S1
Compatibility
Backward
Compatibility
with previous
hardware
V2.14
Hard 5
V3.1
Hard 5
06/2009
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
P12y/EN VC/Fa5
Page 25/28
09/2009
S1
Compatibility
Backward
Compatibility
with previous
hardware
V3.1
Hard 5
P12y/EN VC/Fa5
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
Page 26/28
Relay Type P127
Software Date of
Version Issue
V13.A
01/2010
V13.B
11/2011
S1
Compatibility
Backward
Compatibility
with previous
hardware
V3.1
Hard 6
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
P12y/EN VC/Fa5
Page 27/28
03/2011
S1
Compatibility
Backward
Compatibility
with previous
hardware
V3.1
Hard 5
V3.1
Hard 5
10/2011
P12y/EN VC/Fa5
Hardware/Software Version
History and Compatibility
MiCOM P125/P126/P127
Page 28/28
BLANK PAGE
http://www.schneider-electric.com/CCC
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone:
Fax:
+33 (0) 1 41 29 70 00
+33 (0) 1 41 29 71 00
www.schneider-electric.com
Publication: P12y/EN M/Fa5