Honeywell RM7800L1087 (Stock) 66-2028
Honeywell RM7800L1087 (Stock) 66-2028
SPECIFICATION DATA
The RM7800 is programmed to provide a level of safety, Local or remote annunciation of operation and fault
functional capability and features beyond the capacity of information (optional).
conventional controls. Nonvolatile memory for retaining history files and
sequencing status after loss of power.
Functions provided by the RM7800 include automatic burner
sequencing, flame supervision, system status indication, Remote reset (optional).
system or self-diagnostics and troubleshooting. Report generation (optional).
Burner controller data:
FEATURES Sequence status.
Sequence time.
Safety features: Hold status.
Lockout/alarm status.
Interlock check. Flame signal strength.
Closed loop logic test. Expanded annunciator status.
Dynamic AMPLI-CHECK. Total cycles of operation.
Dynamic input check. Total hours of operation.
Dynamic safety relay test. Fault history of six most recent faults:
Dynamic self-check logic. Cycles of operation at time of fault.
Expanded safe-start check. Expanded annunciator data at time of fault.
High Fire Purge Switch test. Fault message and code.
Internal hardware status monitoring. Hours of operation at time of fault.
Low Fire Start Switch test. Sequence status at time of fault.
Tamper resistant timing and logic. Sequence time at time of fault.
Access for external electrical voltage checks. Diagnostic information:
Application flexibility. Device type.
Flame amplifier type.
Provides 0.8 to 3.0 second Flame Failure Response Flame failure response time.
Time (FFRT), depending on amplifier selected. Manufacturing code.
Communication interface capability. On/Off status of all digital inputs and outputs.
Selected prepurge time.
Dependable, long-term operation provided by Software revision and version of RM7800 and
microcomputer technology. Keyboard Display Module.
Status of configuration jumpers.
Status of Run/Test Switch.
Approval Bodies:
Underwriters Laboratories Inc. listed, File No. MP268,
Guide No. MCCZ.
Canadian Standards Association certified, LR9S329-3.
Factory Mutual approved, Report No. J.I.1V9A0.AF.
IRI acceptable.
Federal Communications Commission, Part 15,
Class BEmissions.
Required Components:
Plug-in Flame Signal Amplifier, see Table 2.
ST7800A Plug-in Purge Timer Cards: selectable models:
two seconds to 30 minutes.
Q7800A or Q7800B Wiring Subbase.
66-20283 2
7800 SERIES RM7800E,G,L,M RELAY MODULE
3 66-20283
7800 SERIES RM7800E,G,L,M RELAY MODULE
66-20283 4
7800 SERIES RM7800E,G,L,M RELAY MODULE
BURNER CONTROL
5
(127)
POWER
PILOT
FLAME
MAIN
ALARM 1
RESET
5-1/4 (133)
5 (127)
6-3/32 (155)
M15518
Fig. 2. Mounting dimensions of RM7800 Relay Module, Q7800 Subbase, and Q7800 Subbase, respectively, in in. (mm).
5 66-20283
7800 SERIES RM7800E,G,L,M RELAY MODULE
66-20283 6
7 66-20283
Home and Building Control Home and Building Control Honeywell Asia Pacific Inc. Honeywell Europe S.A. Honeywell Latin American
Honeywell Honeywell Limited-Honeywell Limite Room 3213-3225 3 Avenue du Bourget Region
1985 Douglas Drive North 35 Dynamic Drive Sun Hung Kai Centre 1140 Brussels 480 Sawgrass Corporate Parkway
Golden Valley, MN 55422 Scarborough, Ontario No. 30 Harbour Road Belgium Suite 200
M1V 4Z9 Wanchai Sunrise FL 33325
Hong Kong