METSEPM5330
METSEPM5330
Main
Range PowerLogic
Product name PowerLogic PM5000
Device short name PM5330
Product or component Power meter
type
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Complementary
Power quality analysis Up to the 31st harmonic
Device application Power monitoring
Multi-tariff
Type of measurement Active and reactive power
Energy
Power factor
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
Frequency
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Voltage
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Current
Supply voltage 125...250 V DC
100...415 V AC (45...65 Hz)
Network frequency 50 Hz
60 Hz
[In] rated current 1A
5A
Type of network 1P + N
3P
3P + N
Power consumption in VA 10 VA at 415 V
Display type Backlit LCD
Display resolution 128 x 128 pixels
Sampling rate 64 samples/cycle
Measurement current 10 mA...9 A
Analogue input type Voltage (impedance 5 MOhm)
Current (impedance 0.3 mOhm)
Measurement voltage 20...400 V AC 45...65 Hz between phase and neutral
35...690 V AC 45...65 Hz between phases
Frequency measurement range 45...65 Hz
Number of inputs 2 digital
Measurement accuracy +/- 0.5 % voltage
+/- 0.5 % current
+/- 0.005 % power factor
+/- 0.05 % frequency
+/- 0.5 % apparent power
+/- 0.5 % active power
+/- 2 % reactive energy
+/- 0.5 % active energy
Accuracy class Class 0.5S (active energy according to IEC 62053-22)
Number of outputs 2 digital
2 relay
Information displayed Tariff 4
Environment
Electromagnetic compatibility conducted and radiated emissions class class B, conforming to EN 55022
magnetic field at power frequency class level 4, conforming to IEC 61000-4-8
conducted RF disturbances class level 3, conforming to IEC 61000-4-6
electrostatic discharge class level 4, conforming to IEC 61000-4-2
limits for harmonic current emissions class class A, conforming to IEC
61000-3-2
IP degree of protection IP30 (body) conforming to IEC 60529
IP52 (front) conforming to IEC 60529
Relative humidity 5...95 % 50 C
Pollution degree 2
Ambient air temperature for operation -25...70 C
Ambient air temperature for storage -40...85 C
Operating altitude 2000 m
Offer Sustainability
Sustainable offer status Not Green Premium product