Datasheet Compack Controller
Datasheet Compack Controller
COMPACK CONTROLLER
Doc 242100.400.DS3 v7
Eltek Grterudveien 8, PB 2340 Strms, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek 2016 www.eltek.com
COMPACK CONTROLLER
FOR 12V, 24V, 30V, 48V & 60V SYSTEMS
ELECTRICAL SPECIFICATIONS
Input Voltage 9 - 75 VDC, shutdown < 8.5 VDC*
Temperature Range Nominal: -20 to +60 C (-4 to 140 F) Reduced accuracy: -40 to +70 C
Power Consumption 3W
MTBF > 550, 000 hours Telcordia SR-332 Issue I, method III (a) (Tambient : 25C)
Ethernet port 10/100 BASE-T HP Auto MDI/MDI-X
Relay Outputs (1,5 mm2) Form-C (dry contact NO-C-NC), Max 75V/2A/60W breaking capacity
Configurable Inputs (1,5 mm2) Temperature: External NTC, Digital: open/closed, Analog: 0-75V, Battery Symmetry: 0-75V
CONTROL FEATURES
Control System o Output Voltage Measurement o Output Voltage Measuremento Position
o Load Current Calculation (long/lat) for auto placement
o Energy Calculation o Generator start/stop control setup
o Load/Battery Disconnect o Test of Relay Outputs
o Real Time Clock with Battery Backup o Alarm grouping of events for relay outputs
o Stored Site Text/ID and Messages o Boolean AND of alarm groups
Battery o Battery Current Measurement o Temperature Compensated Charging
o Battery Temperature Measurement o Charge Current Limitation
Battery Testing o Battery Low Voltage Disconnect
(acc. to discharge table or set time limit) - Temperature dependent (optional)
o Setup of Battery Data/Table - Mains independent (optional)
o Battery Capacity Indication
o Battery Boost Charging
- Auto Ah discharge or voltage threshold
- Interval or Manual
Rectifier o Available information about each rectifier, o Energy calculation
e.g. serial number, version, internal o Efficiency Management
temperature o Emergency Voltage
o Individual Rectifier Current Measurement o Startup delay
o Individual Rectifier Input Voltage o Detailed internal alarms summary
DATA LOGGING
Control System Event log, Data log (configurable up to 20 monitors), Configuration Change log, Account Access log
Energy delivered from Rectifiers, Solar Charger and Battery, and consumed energy by the load for the
Energy
last 52 hours, 52 days and 52 weeks
Battery 10 last battery tests detailed, number of battery cycles for the last 52 hours, 52 days and 52 weeks
Generator Run time in minutes and fuel consumption for the last 52 hours, 52 days and 52 weeks
Dimensions (HxWxD) 75 x 30 x 115mm / 2.95 x 1.2 x 4.52 107.6 x 41.4 x 175.5mm / 2.24 x 1.63 x 6.91
Weight 240g / 0.53 lbs 380g / 0.84 lbs
* 12V support from HW rev. HW1.3. HW version 1.0 1.2 input voltage range: 17 75 VDC
Eltek Grterudveien 8, PB 2340 Strms, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek 2016 www.eltek.com