DC M&T Lecture Notes - 0
DC M&T Lecture Notes - 0
ON
P MABU HUSSAIN
Assistant Professor
Department of Electrical and Electronics Engineering
OBJECTIVES:
The course should enable the students to:
I. Illustrate the theory of electromechanical energy conversion and the concept of co energy.
II. Demonstrate the working principle of different types of dc machines and transformers.
III. Analyze the losses in dc machines to improve the efficiency by conducting various tests.
IV. Outline the principle of operation, construction and testing of single phase transformers.
UNIT-I
ELECTROMECHANICAL ENERGY CONVERSION: Electromechanical energy conversion:
Forces and torque in magnetic systems, energy balance, energy and force in a singly excited and
multi excited magnetic field systems, determination of magnetic force, coenergy.
UNIT-II
DC GENERATORS: Principle of operation, construction, armature windings, lap and wave
windings, simplex and multiplex windings, use of laminated armature, commutator, emf equation,
types of DC generators, voltage buildup, critical field resistance and critical speed, causes for failure
to self excite and remedial measures; Armature reaction: Cross magnetization and demagnetization,
ampere turns per pole, compensating winding, commutation, reactance voltage, methods of
improving commutation; Characteristics: Principle of parallel operation load sharing, use of
equalizer bars and cross connection of field windings problems.
UNIT-III
DC MOTORS AND TESTING: Principle of operation, back EMF, torque equation, condition for
maximum power developed, types of DC motors, armature reaction and commutation,
characteristics, methods of speed control, types of starters, numerical problems; Losses and
efficiency: Types of losses, calculation of efficiency, condition for maximum efficiency.
Testing of DC machines: Swinburnes test, brake test, regenerative testing, Hopkinsons test, fields
test, retardation test and separation of stray losses, problems.
UNIT-IV
SINGLE PHASE TRANSFORMERS: Single phase transformers: Principle of operation,
construction, types of transformers, EMF equation, concept of leakage flux and leakage reactance,
operation of transformer under no load and on load, phasor diagrams, equivalent circuit, efficiency,
regulation and all day efficiency; Testing of transformer: objective of testing, polarity test,
measurement of resistance, OC and SC tests, back to back test, heat run test, parallel operation,
problems.
UNIT-V
THREE PHASE TRANSFORMERS: Three phase transformer: Principle of operation, star to star,
delta to delta, star to delta, delta to star, three phase to six phase, open delta connection, scott
connection; Auto transformers: Principles of operation, equivalent circuit, merits and demerits, no
load and on load tap changers, harmonic reduction in phase voltages, problems.
TEXT BOOKS:
1. P S Bimbra, Electrical Machines, Khanna publications, 2nd edition, 2008.
2. J B Gupta, Theory and Performance of Electrical Machines, S K Kataria & Sons
publications, 14th edition, 2010.
3. I J Nagrath, D P Kothari, Electrical Machines, Tata Mc Graw Hill publications, 3rd Edition,
2010.
REFERENCE BOOKS:
1. Ian McKenzie Smith, Edward Hughes, Electrical Technology, Prentice Hall, 10th edition,
2015.
2. M G Say, E O Taylor, Direct current Machines, Longman higher education, 1st edition,
1985.
3. M V Deshpande, Electrical Machines, PHI learning private limited, 3rd edition, 2011.
UNIT I
The electromechanical-energy-conversion process takes place through the medium of the electric or
magnetic field of the conversion device of which the structures depend on their respective functions.
F= q(E+vB)
> Based on the principle of conservation of energy: energy is neither created nor destroyed; it is
merely changed in form.
> Fig. 1.2 shows a magnetic-field-based electromechanical-energy-conversion device.
- A lossless magnetic-energy-storage system with two terminals
- The electric terminal has two terminal variables: e (voltage), i (current).
- The mechanical terminal has two terminal variables: ffld (force), x (position)
- The loss mechanism is separated from the energy-storage mechanism.
Electrical losses: ohmic losses...
Mechanical losses: friction, windage...
> Fig. 1.3: a simple force-producing device with a single coil forming the electric terminal, and a
movable plunger serving as the mechanical terminal.
- The interaction between the electric and mechanical terminals, i.e. the electromechanical energy
conversion, occurs through the medium of the magnetic stored energy.
- Wfld : the stored energy in the magnetic field
- From the above equation force can be solved as a function of the flux and the mechanical terminal
position x.
- The above equations form the basis for the energy method
The ability to identify a lossless-energy-storage system is the essence of the energy method.
> This is done mathematically as part of the modeling process.
> For the lossless magnetic-energy-storage system of Fig. 1.2 can be rearranged and gives
>Here e is the voltage induced in the electric terminals by the changing magnetic stored energy. It is
through this reaction voltage that the external electric circuit supplies power to the coupling magnetic
field and hence to the mechanical output terminals.
> The basic energy-conversion process is one involving the coupling field and its action and
reaction on the electric and mechanical systems.
> Combining above two equation
Generators
There are two types of generators, one is ac generator and other is dc generator. Whatever may
be the types of generators, it always converts mechanical power to electrical power. An ac
generator produces alternating power.
A DC generator produces direct power. Both of these generators produce electrical power, based
on same fundamental principle of Faraday's law of electromagnetic induction. According to these
law, when an conductor moves in a magnetic field it cuts magnetic lines force, due to which an
emf is induced in the conductor. The magnitude of this induced emf depends upon the rate of
change of flux (magnetic line force) linkage with the conductor. This emf will cause an current
to flow if the conductor circuit is closed. Hence the most basic two essential parts of a generator
are
1. a magnetic field
Constructional Features
Yoke of DC Generator
1. It holds the magnetic pole cores of the generator and acts as cover of the generator.
In small generator, yoke are made of cast iron. Cast iron is cheaper in cost but heavier than steel.
But for large construction of DC generator, where weight of the machine is concerned, lighter
cast steel or rolled steel is preferable for constructing yoke of DC generator. Normally larger
yokes are formed by rounding a rectangular steel slab and the edges are welded together at the
bottom. Then feet, terminal box and hangers are welded to the outer periphery of the yoke frame.
The purpose of armature core is to hold the armature winding and provide low reluctance path
for the flux through the armature from N pole to S pole. Although a DC generator provides direct
current but induced current in the armature is alternating in nature. That is why, cylindrical or
drum shaped armature core is build up of circular laminated sheet. In every circular lamination,
slots are either die - cut or punched on the outer periphery and the key way is located on the
inner periphery as shown. Air ducts are also punched of cut on each lamination for circulation of
air through the core for providing better cooling.
Armature winding are generally formed wound. These are first wound in the form of flat
rectangular coils and are then pulled into their proper shape in a coil puller. Various conductors
of the coils are insulated from each other. The conductors are placed in the armature slots, which
are lined with tough insulating material. This slot insulation is folded over above the armature
conductors placed in it and secured in place by special hard wooden or fiber wedges.
Commutator of DC Generator
The commutator plays a vital role in dc generator. It collects current from armature and sends it
to the load as direct current. It actually takes alternating current from armature and converts it to
direct current and then send it to external load. It is cylindrical structured and is build up of
wedge - shaped segments of high conductivity, hard drawn or drop forged copper. Each segment
is insulated from the shaft by means of insulated commutator segment shown below. Each
commutator segment is connected with corresponding armature conductor through segment riser
or lug.
Brushes of DC Generator
The brushes are made of carbon. These are rectangular block shaped. The only function of these
carbon brushes of DC generator is to collect current from commutator segments. The brushes are
housed in the rectangular box shaped brush holder. As shown in figure, the brush face is placed
on the commutator segment with attached to the brush holder.
Bearing of DC Generator
For small machine, ball bearing is used and for heavy duty dc generator, roller bearing is used.
The bearing must always be lubricated properly for smooth operation and long life of generator.
Emf equation for dc generator
And,
Time taken to complete one revolution = 60/N
Where,
N = speed of the armature conductor in rpm.
Now,according to Faradays law of induction, the induced emf of the armature conductor is
denoted by e which is equal to rate of cutting the flux.
Therefore,
Let us suppose there are Z total numbers of conductor in a generator, and arranged in such a
manner that all parallel paths are always in series. Here,
An electric generator or electric motor consists of a rotor spinning in a magnetic field. The
magnetic field may be produced by permanent magnets or by field coils. In the case of a machine
with field coils, a current must flow in the coils to generate the field, otherwise no power is
transferred to or from the rotor. The process of generating a magnetic field by means of an
electric current is called excitation.
For a machine using field coils, which is most large generators, the field current must be
supplied, otherwise the generator will be useless. Thus it is important to have a reliable supply.
Although the output of a generator can be used once it starts up, it is also critical to be able to
start the generators reliably. In any case, it is important to be able to control the field since this
will maintain the system voltage.
Types of excitation
(1)seperately excited generator.
(2)self excited generator.
1.shunt generator.
2.series generator.
3.compound generator.
compoud generator is again classified into 2 types.
1.short shunt generator.
2.long shunt generator.
These kind of generators has provided field exciter terminals which are external DC
voltage source is supplies to produce separately magnetic field winding (shunt field) for
magnetize of the generator as illustrated in figure as below.
Self excited field generators.
This type of generator has produced a magnetic field by itself without DC sources from an
external. The electromotive force that produced by generator at armature winding is supply to a
field winding (shunt field) instead of DC source from outside of the generator. Therefore, field
winding is necessary connected to the armature winding. They may be further classified as
a) Shunt generator.
This generator, shunt field winding and armature winding are connected in parallel
through commutator and carbon brush as illustrated in the figure below.
Shunt generator
b) Series generator
The field winding and armature winding is connected in series. There is different from shunt
motor due to field winding is directly connected to the electric applications (load).
Therefore, field winding conductor must be sized enough to carry the load current
consumption and the basic circuit as illustrated below
Series generator
c) Compound generator
The compound generator has provided with magnetic field in combine with excitation of shunt
and series field winding, the shunt field has many turns of fine wire and caries of a small current,
while the series field winding provided with a few turns of heavy wire since it is in series with an
armature winding and caries the load current. There are two kinds of compound generator as
illustrated in figures below.
The generated electromotive force (EMF) is proportional to both of a magnetic density of flux
per pole and the speed of the armature rotated as expression by the relation as following.
Eg = n
Where
K = Constant for a specific machine
= The density of flux per pole
n = Speed of the armature rotation
Eg = Generator voltage
By holding the armature speed (n) at a constant value it can show that generator voltage (Eg) is
directly proportional to the magnetic flux density. Which, flux density is proportionately to the
amount of field current (If). The relation of field current and generate voltage as impressed by
figure .
From the figure when the field current (If) is become zero a small generate voltage is produce
due to a residual magnetism.
As the field current increases cause to increase generated voltage linearly up to the knee of the
magnetization curve. Beyond this point by increasing the field current still further causes
saturation of the magnetic structure.
Generator voltage (Eg) is also directly to the armature speed. The formula and a magnetization
curve can be both impressed about this relation.
Where
When we add load on the generator, the terminal voltage will decrease due to
(a) The armature winding resistance is mainly of armature resistance. It is cause directly
decrease in terminal voltage as following relation.
Vt = Eg - Ia Ra
Where,
To have some measure by how much the terminal voltage change from no-load condition and on
load condition, which is called voltage regulation.
Example 2
The separately excited generator of example 1 is driven at revolving speed 1000 rpm and the
field current is adjusted to 0.6 Amp. If the armature circuit resistance is 0.28 ohm, plot the output
voltage as the load current is varied from 0 to 60 Amp. Neglect armature reaction effects. If the
full-load current is 60 Amp, what is the voltage regulation?
Solution
From example 1, Eg = 153 volts when the field current is 0.6 Amp, which is the open circuit
terminal voltage. When the generator is loaded, the terminal voltage is decreased by internal
voltage drop,
namely.
Vt = Eg - Ia Ra
For a load current of, say 40 Amp.
Vt = 153 - (40 0.28) = 141.80 Volts.
This calculation is for a number of load currents and the external characteristic can
be plotted as show in fig. 10 at full load the terminal voltage.
The critical field resistance is the maximum field circuit resistance for a given speed with
which the shunt generator would excite. The shunt generator will build up voltage only if field
circuit resistance is less than critical field resistance. It is a tangent to the open circuit
characteristics of the generator at a given speed.
Suppose a shunt generator has built up voltage at a certain speed. Now if the speed of the
prime mover is reduced without changing Rf, the developed voltage will be less as because the
O.C.C at lower speed will come down (refer to figure). If speed is further reduced to a certain
critical speed (ncr), the present field resistance line will become tangential to the O.C.C at ncr.
For any speed below ncr, no voltage built up is possible in a shunt generator.
Critical Speed
Load characteristics
Self excited DC shunt generator
A shunt generator has its shunt field winding connected in parallel with the armature so that the
machine provides it own excitation. For voltage to build up, there must be some residual
magnetism in the field poles. There will be a small voltage (Er) generated.
If the connection of the field and armature winding are such that the weak main pole flux aids to
the residual flux, the induced voltage will become larger. Thus more voltage applied to the main
field pole and cause to the terminal voltage increase rapidly to a large value. When we add load
on the generator, the terminal voltage will decrease due to.
The armature winding resistance
a) The armature reaction
c) The weakened flux due to the connection of the generator to aids or oppose to the residual
Series Generator
The field winding of a series generator is connect in series with the armature winding. Since it
carries the load current, the series field winding consists of only a few turns of thick wire. At no-
load, the generator voltage is small due to residual field flux only. When a load is added, the
flux increase, and so does the generated voltage.
V t = Eg - Ia Ra + Rf
Where
Rf = The series field winding resistance
Ra = The armature winding resistance
The series generators are obviously not suited for applications requiring good voltage regulation.
Therefore, they have been used very little and only in special applications for example, as
voltage booster. The generator is placed in series with a supply line. When the current
consumption is increase, the generated voltage of the series machine goes up because the
magnetic field current is increases.
Compound generator
The compound generator has both a shunt and a series winding. The series field winding usually
wound on the top of a shunt field. The two winding are usually connected such that their ampere-
turns act in the same direction. As such the generator is said to be cumulatively compound.
(a) Curve s is represent the terminal voltage characteristic of shunt field winding alone. Under-
compound, this condition the addition of series field winding too short it is cause the terminal
voltage no rise to certain value and reduce while increasing in load current.
(b) Flat compound by increasing the number of a series field turns. It is cause to rise up in
terminal voltage and when no-load and full load condition a terminal voltage is made nearly
same value or equal.
(c) Over-compound, if the number of series field turns is more than necessary to compensated of
the reduce voltage. In this case while a full load condition a terminal voltage is higher than a
no-load voltage. Therefore over-compound generator may use where load is at some distance
from generator. Voltage drop in the line has compensated by used of an over-compound
generator.
(d) If a reversing the polarity of the series field occur this cause to the relation between series
field and shunt field, the field will oppose to each other more and more as the load current
increase. Therefore terminal voltage will drop, such generator is said to be a differentially
compound.
The compound generator are used more extensively than the other type of dc generator because
its design to have a wide variety of terminal voltage characteristics.
Machine Efficiency
The efficiency of any machine is the ratio of the ratio of the output power to the input power.
The input power is provided by the prime mover to drive the generator. Because part of the
energy delivered to the generator is converted into heat, it represents wasted energy. These losses
are generally minimized in the design stage; however, some of these losses are unavoidable.
Losses of generator
The losses of generators may be classified as
1) Copper losses
The copper losses are present because of the resistance of the windings. Currents flowing
through these windings create ohmic losses. The windings that may be present in addition to
the (I2 R ) armature winding are the field windings, inter-pole and compensate windings.
2) Iron losses
As the armature rotates in the magnetic field, the iron parts of the armature as well as the
conductors cut the magnetic flux. Since iron is a good conductor of electricity, the EMF s
induced in the iron parts courses to flow through these parts. These are the eddy currents.
Another loss occurring in the iron is due to the Hysteresis loss is present in the armature core.
Applications Of Dc Generators
Applications of Separately Excited DC Generators
These types of DC generators are generally more expensive than self-excited DC generators
because of their requirement of separate excitation source. Because of that their applications are
restricted. They are generally used where the use of self-excited generators are unsatisfactory.
1. Because of their ability of giving wide range of voltage output, they are generally used for
testing purpose in the laboratories.
2. Separately excited generators operate in a stable condition with any variation in field
excitation. Because of this property they are used as supply source of DC motors, whose
speeds are to be controlled for various applications. Example- Ward Leonard Systems of
speed control.
1.They are used for supplying field excitation current in DC locomotives for regenerative
breaking.
2.This types of generators are used as boosters to compensate the voltage drop in the feeder in
various types of distribution systems such as railway service.
3.In series arc lightening this type of generators are mainly used.
1. Cumulative compound wound generators are generally used lighting, power supply purpose
and for heavy power services because of their constant voltage property. They are mainly
made over compounded.
2. Cumulative compound wound generators are also used for driving a motor.
3. For small distance operation, such as power supply for hotels, offices, homes and lodges, the
flat compounded generators are generally used.
DC MOTORS
DC motors are highly versatile machines. For example, dc motors are better suited fore many
processes that demand a high degree of flexibility in the control of speed and torque. The dc
motor can provided high starting torque as well as high decelerating torque for application
requiring quick stop or reversals.
DC motors are suited in speed control with over wide range is easily to achieve compare with
others electromechanical.
F = B i l Newton (1)
where B is the density of the magnetic field, l is the length of conductor, and i the value of
current flowing in the conductor. The direction of motion can be found using Flemings Left
Hand Rule.
The first finger points in the direction of the magnetic field (first - field), which goes
from the North pole to the South pole. The second finger points in the direction of the current in
the wire (second - current). The thumb then points in the direction the wire is thrust or pushed
while in the magnetic field (thumb - torque or thrust).
Principle of operation
Consider a coil in a magnetic field of flux density B (figure ). When the two ends of the
coil are connected across a DC voltage source, current I flows through it. A force is exerted on
the coil as a result of the interaction of magnetic field and electric current. The force on the two
sides of the coil is such that the coil starts to move in the direction of force.
At the same time this torque is being produced, the conductors are moving in a magnetic
field. At /dt) as shown in different positions, the flux linked with it changes, which causes an
emf to be induced (e = d figure 5. This voltage is in opposition to the voltage that causes current
flow through the conductor and is referred to as a counter-voltage or back emf.
The value of current flowing through the armature is dependent upon the difference between the
applied voltage and this counter-voltage. The current due to this counter-voltage tends to oppose
the very cause for its production according to Lenzs law. It results in the rotor slowing down.
Eventually, the rotor slows just enough so that the force created by the magnetic field (F = Bil)
equals the load force applied on the shaft. Then the system moves at constant velocity.
Construction
DC motors consist of one set of coils, called armature winding, inside another set of coils or a set
of permanent magnets, called the stator. Applying a voltage to the coils produces a torque in the
armature, resulting in motion.
Stator
Torque Developed
The turning or twisting moment of a force about an axis is called torque. It is measured by the
product of the force and the radius at which this force acts.
Consider a pulley of radius meter acted upon by a circumferential force of newton which causes
it to rotate at rpm.
Shaft torque
Induced Counter-voltage (Back emf):
Due to the rotation of this coil in the magnetic field, the flux linked with it changes at different
positions, which causes an emf to be induced (refer to figure 2).
The total emf induced in the motor by several such coils wound on the rotor can be obtained by
integrating equation (4), and expressed as:
Eb = K m (5)
where K is an armature constant, and is related to the geometry and magnetic properties of
the motor, and m is the speed of rotation.
The armature conductors continually cut through this resultant field. So that voltages are
generated in the same conductors that experience force action. When operating the motor is
simultaneously acting as generator. Naturally motor action is stronger than generator action.
Although the counter EMF is opposite with the supplied voltage, but it cannot exceed to applied
voltage. The counter EMF is serves to limit the current in an armature winding. The armature
current will be limited to the value just sufficient to take care of the developed power needed to
drive the load.
In the case of no load is connected to the shaft. The counter EMF will almost equal to the applied
voltage. The power develops by the armature in this case is just the power needed to overcome
the rotational losses. Its mean that the armature current IA is controlled and limited by counter
EMF therefore
Where:
VL = Line voltage across the armature winding
Ra = Resistance of the armature winding
Ea = Induced EMF or generated voltage
Ia = Armature current
Since, EA is induced or generated voltage it is depend on the flux per pole and the speed of the
armature rotate (n) in rpm.
Therefore
Ea=Kn
Where:
K = the constant value depending on armature winding and number of pole of
machine.
Where:
Z = Total number of conductor in the armature winding
a = Number of parallel circuit in the armature winding between positive and negative brushes.
For wave wound armature a = 2
1.Shunt machine
The armature and field winding are connected in parallel.
The armature voltage and field voltage are the same.
2.Series DC machine
The field winding and armature winding are connected in series.
The field winding carries the same current as the armature winding.
A series wound motor is also called a universal motor. It is universal in the sense that it will run
equally well using either an ac or a dc voltage source.
Reversing the polarity of both the stator and the rotor cancel out. Thus the motor will always
rotate the same direction regardless of the voltage polarity.
Fig.7.Series Motor
Compound DC machine
If both series and shunt field windings are used, the motor is said to be compounded. In a
compound machine, the series field winding is connected in series with the armature, and the
shunt field winding is connected in parallel. Two types of arrangements are possible in
compound motors:
Cumulative compounding - If the magnetic fluxes produced by both series and shunt field
windings are in the same direction (i.e., additive), the machine is called cumulative compound.
Differential compounding - If the two fluxes are in opposition, the machine is differential
compound.
In both these types, the connection can be either short shunt or long shunt.
Speed control of DC motor
Many applications require the speed of a motor to be varied over a wide range. One of
the most attractive features of DC motors in comparison with AC motors is the ease with which
their speed can be varied.
From the above equation, it is evident that the speed can be varied by using any of the
following methods:
In normal operation, the drop across the armature resistance is small compared to Eb and
therefore: Eb VT
Since, Eb = K m
Angular speed can be expressed as:
m= VT/ K (8)
From this equation, If flux is kept constant, the speed changes linearly with VT.
As the terminal voltage is increased, the speed increases and vice versa.
The relationship between speed and applied voltage is shown in figure 8. This method
provides smooth variation of speed control.
The relationship between the field winding current and angular speed is shown in figure 10
For a load of constant torque VT and are kept constant, as the armature resistance Ra is
increased, speed decreases. As the actual resistance of the armature winding is fixed for a given
motor, the overall resistance in the armature circuit can be increased by inserting an additional
variable resistance in series with the armature. The variation if speed with respect to change in
this external resistance is shown in figure 12. This method provides smooth control of speed..
Applications of dc motors
The losses can be divided into three types in a dc machine (Generator or Motor). They are
1. Copper losses
2. Iron or core losses and
3. Mechanical losses.
All these losses seem as heat and therefore increase the temperature of the machine. Further the
efficiency of the machine will reduce.
1. Copper Losses:
This loss generally occurs due to current in the various windings on of the machine. The
different winding losses are;
2
Armature copper loss = I a Ra
2
Shunt field copper loss = I shRsh
2
Series field copper loss = I se Rse
Note: Theres additionally brush contact loss attributable to brush contact resistance (i.e.,
resistance in the middle of the surface of brush and commutator). This loss is mostly enclosed in
armature copper loss.
2. Iron Losses
This loss occurs within the armature of a d.c. machine and are attributable to the rotation of
armature within the magnetic field of the poles. Theyre of 2 sorts viz.,
Hysteresis loss:
Hysteresis loss happens in the armature winding of the d.c. machine since any given part of the
armature is exposed to magnetic field of reverses as it passes underneath sequence poles. The
above fig shows the 2 pole DC machine of rotating armature. Consider a tiny low piece ab of the
armature winding. Once the piece ab is underneath N-pole, the magnetic lines pass from a to b.
Half a revolution well along, identical piece of iron is underneath S-pole and magnetic lines pass
from b to a in order that magnetism within the iron is overturned. So as to reverse constantly the
molecular magnets within the armature core, particular quantity of power must be spent that is
named hysteresis loss. Its given by Steinmetz formula.
Where,
= Steinmetz hysteresis co-efficient
Bmax = Maximum flux Density in armature winding
F= Frequency of magnetic reversals
= NP/120 (N is in RPM)
3
V= Volume of armature in m
If you want to cut back this loss in a d.c. machine, armature core is created of such materials that
have an lesser value of Steinmetz hysteresis co-efficient e.g., silicon steel.
If never-ending cast-iron core is employed, the resistance to eddy current path is tiny attributable
to massive cross-sectional space of the core. Consequently, the magnitude of eddy current and
therefore eddy current loss are massive. The magnitudes of eddy current are often decreased by
creating core resistance as high as sensible. The core resistances are often greatly exaggerated by
making the core of skinny, spherical iron sheets referred to as lamination's shown in the fig. The
lamination's are insulated from one another with a layer of varnish. The insulating layer features
a high resistance, thus only small amount of current flows from one lamination to the opposite.
Also, as a result of every lamination is extremely skinny, the resistance to current passing over
the breadth of a lamination is additionally quite massive. Therefore laminating a core will
increase the core resistance that drops the eddy current and therefore the eddy current loss.
2 22
Eddy Current loss Pe=KeB maxf t V Watts
Where, ke = constant
2
Bmax = Maximum flux density in wb/m
T = Thickness of lamination in m
3
V = Volume of core in m
Note: Constant (Ke) depend upon the resistance of core and system of unit used.
It may well be noted that eddy current loss be subject to upon the sq. of lamination thickness. For
this reason, lamination thickness ought to be unbroken as tiny as potential.
3.Mechanical Loss
These losses rely on the speed of the machine. Except for a given speed, they're much constant.
The losses in a d.c. machine is also further classified into (i) constant losses (ii) variable losses.
Constant losses
Those losses in a d.c. generator that stay constant at all loads are referred to as constant losses.
Variable losses
Those losses in a d.c. generator that differ with load are referred to as variable losses. The
variable losses in a very d.c. generator are:
2
Copper loss in armature winding (I Ra)
2
Copper loss in series field winding (I seRse)
The figure above shows that typical representation diagram of a 3 point starter for DC shunt
motors with its protective devices. It contains 3 terminals namely L, Z, & A; hence named 3
point starter. The starter is made up of of starting resistances divided into many section and
which are connected in series within the armature. The each tapping point on the starting
resistances is carried out to a no. of studs. The starter 3 terminals L,Z & A are connected to the
positive terminal of line, shunt field and armature terminal of motor respectively. The remaining
terminal of the shunt and armature are connected to the negative line terminal. The No volt coil
release is connected in series with field winding. The handle one end is connected to the L
terminal by means of over load release coil. Then another end of handle travels against the
twisting spring & make touching base with every single stud in the course of starting operation,
tripping out the starting resistance as it moves above every stud in clockwise.
Working:
Note: If we were not used No volt coil release; then if the supply is cut off the handle would
remain in the same position, causing an extreme current in armature.
If any fault occurs on motor or overload, it will draw extreme current from the source. This
current raise the ampere turns of OLR coil (over load relay) and pull the armature Coil, in
consequence short circuiting the NVR coil (No volt relay coil). The NVR coil gets
demagnetized and handle comes to the rest position under the influence of spring. Therefore
the motor disconnected from the supply automatically.
Characteristic of DC Shunt Motor
Disadvantage:
In point starter, no volt relay coil is connected in series with field circuit; hence it carries shunt
current in the field. When the speed control of DC motor through field regulator, it may be
weakened the shunt field current to such extent the no volt coil release might not in a position to
hold the starter handle in ON position. This might the motor disconnected from the source when
it is not anticipated. This can be overcome by using the point starter.
In this technique, the DC Generator or DC Motor is run as a motor at no load; with that losses of
the DC machines are determined. When the losses of DC machine well-known, then we can find
the efficiency of a DC machine in advance at any desired load. In DC machines this test is
applicable only throughout the flux is constant at all load (DC Shunt machine and DC
Compound Machine). This test maintains of two steps;
The resistance of armature windings and shunt field windings are measured with the help of a
battery, ammeter and voltmeter. Since these armature and shunt filed resistances are measured
while the DC machine is cold, it should be transformed to values equivalent to the temperature at
which the DC machine would work at full load. These values are measured generally when the
o
room temperature increases above 40 C. Take on the hot resistance of armature winding and
shunt field winding be Ra and Rsh correspondingly.
On no load the DC machine run as a motor with the supply voltage is varied to the normal rated
voltage. With the use of the field regulator R the motor speed is varied to run the rated speed
which is shown in the figure.
Let
V = Supply Voltage
I0 = No load current read by A1
Ish = Shunt Field current ready by A2
No load armature current Iao = I0 Ish
No load Input power to motor = VI0
No load Input power to motor = VIa0
= V (I0 Ish)
As the output power is nil, the no loads input power to the armature provides Iron loss, armature
copper loss, friction loss and windage loss.
Constant Loss = Wc
Total Loss = (I-Ish2Ra)+Wc
Motor Efficiency = (Input power Losses)/ Input
2
= {VI (I-Ish Ra)} / VI
Constant Loss = Wc
2
Total Loss = (I+Ish Ra)+Wc
Merits:
Since this test is no load test, power required is less. Hence the cost is economic.
The efficiency of the machine can be found very easily, because the constant losses are
well known.
This test is appropriate.
Demerits:
When the DC machine is loaded, this test does not deliberate the stray load loss that
occurs.
Using this method we cannot check the DC machine performances at full load.
UNIT IV
TRANSFORMERS
The transformer is a device that transfers electrical energy from one electrical circuit to
another electrical circuit. The two circuits may be operating at different voltage levels but always
work at the same frequency. Basically transformer is an electro-magnetic energy conversion
device. It is commonly used in electrical power system and distribution systems.
.
The load is connected across the secondary winding, between the terminals a1, a2. Thus, the load
can be supplied at a voltage higher or lower than the supply voltage, depending upon the ratio
N1/N2
When a load is connected across the secondary winding it carries a current I2, called load
current. The primary current correspondingly increases to provide for the load current, in
addition to the small no load current. The transfer of power from the primary side (or source) to
the secondary side (or load) is through the mutual flux and core. There is no direct electrical
connection between the primary and secondary sides.
In an actual transformer, when the iron core carries alternating flux, there is a power loss in the
core called core loss, iron loss or no load loss. Further, the primary and secondary windings have
a resistance, and the currents in primary and secondary windings give rise to I 2 R losses in
transformer windings, also called copper losses. The losses lead to production of heat in the
transformers, and a consequent temperature rise. Therefore, in transformer, cooling methods are
adopted to ensure that the temperature remains within limit so that no damage is done to
windings insulation and material.
In the Figure 4.1 of a single-phase transformer, the primary winding has been shown connected
to a source of constant sinusoidal voltage of frequency f Hz and the secondary terminals are kept
open. The primary winding of N1 turns draws a small amount of alternating current of
instantaneous value i0, called the exciting current. This current establishes flux in the core (+ve
direction marked on diagram). The strong coupling enables all of the flux to be confined to the
core (i.e. there is no leakage of flux).
CONSTRUCTION OF A TRANSFORMER
There are two basic parts of a transformer:
1. Magnetic core
2. Winding or coils
MAGNETIC CORE:
The core of a transformer is either square or rectangular in size. It is further divided in two
parts. The vertical portion on which the coils are bound is called limb, while the top and bottom
horizontal portion is called yoke of the core as shown in fig. 2.
Core is made up of laminations. Because of laminated type of construction, eddy current losses get
minimized. Generally high grade silicon steel laminations (0.3 to 0.5 mm thick) are used. These
laminations are insulated from each other by using insulation like varnish. All laminations are
varnished. Laminations are overlapped so that to avoid the airgap at the joints. For this generally L
shaped or I shaped laminations are used which are shown in the fig. 3 below.
WINDING:
There are two windings, which are wound on the two limbs of the core, which are
insulated from each other and from the limbs as shown in fig. 4. The windings are made up of
copper, so that, they possess a very small resistance. The winding which is connected to the load
is called secondary winding and the winding which is connected to the supply is called primary
winding. The primary winding has N1 number of turns and the secondary windings have N2
number of turns.
A single phase transformer works on the principle of mutual induction between two magnetically
coupled coils. When the primary winding is connected to an alternating voltage of r.m.s value,
V1 volts, an alternating current flows through the primary winding and setup an alternating flux
in the material of the core. This alternating flux , links not only the primary windings but also
the secondary windings. Therefore, an e.m.f e1 is induced in the primary winding and an e.m.f e2
is induced in the secondary winding, e1 and e2 are given:
If the induced e.m.f is e1 and e2 are represented by their rms values E1 and E2 respectively, then
K is known as the transformation ratio of the transformer. When a load is connected to the
secondary winding, a current I2 flows through the load, V2 is the terminal voltage across the
load. As the power transfered from the primary winding to the secondary winding is same,
Power input to the primary winding = Power output from the secondary winding.
The directions of emfs E1 and E2 induced in the primary and secondary windings are such that,
they always oppose the primary applied voltage V1.
The flux in the core will vary sinusoidal as shown in figure, so that it increases from zero to
maximum m in one quarter of the cycle i.e, 1/4f second.
i.e, E1 =4.44fmN1 = 4.44fBmAN1
Similarly;
Transformation Ratio:
(1) Voltage Transformation Ratio
(2) Current Transformation Ratio
Let us consider one electrical transformer with only core losses, which means, it has only
core losses but no copper loss and no leakage reactance of transformer. When an alternating
source is applied in the primary, the source will supply the current for magnetizing the core of
transformer.
But this current is not the actual magnetizing current, it is little bit greater than actual
magnetizing current. Actually, total current supplied from the source has two components, one is
magnetizing current which is merely utilized for magnetizing the core and other component of
the source current is consumed for compensating the core losses in transformer. Because of this
core loss component, the source current in transformer on no-load condition supplied from the
source as source current is not exactly at 90 lags of supply voltage, but it lags behind an angle
is less than 90. If total current supplied from source is Io, it will have one component in phase
with supply voltage V1 and this component of the current Iw is core loss component. This
component is taken in phase with source voltage, because it is associated with active or working
losses in transformer. Other component of the source current is denoted as I. This component
produces the alternating magnetic flux in the core, so it is watt-less; means it is reactive part of
the transformer source current. Hence I will be in quadrature with V1 and in phase with
alternating flux .
Now you have seen how simple is to explain the theory of transformer in no-load.
TRANSFORMER ON LOAD
So total current, this transformer draws from source can be divided into two components, first
one is utilized for magnetizing the core and compensating the core loss i.e. Io. It is no-load
component of the primary current. Second one is utilized for compensating the counter flux of
the secondary winding. It is known as load component of the primary current. Hence total no
load primary current I1 of a electrical power transformer having no winding resistance and
leakage reactance can be represented as follows
Where 2 is the angle between Secondary Voltage and Secondary Current of transformer. Now
we will proceed one further step toward more practical aspect of a transformer.
Again in the case of secondary, the voltage induced across the secondary winding, E2 does not
totally appear across the load since it also drops by an amount I2R2, where R2 is the secondary
winding resistance and I2 is secondary current or load current.
Now we will consider the condition, when there is leakage reactance of transformer as well
as winding resistance of transformer.
Let leakage reactances of primary and secondary windings of the transformer are X1 and X2
respectively.
Hence total impedance of primary and secondary winding of transformer with resistance R1 and
R2 respectively, can be represented as,
We have already established the voltage equation of a transformer on load, with only
resistances in the windings, where voltage drops in the windings occur only due to resistive
voltage drop. But when we consider leakage reactances of transformer windings, voltage drop
occurs in the winding not only because of resistance, it is because of impedance of transformer
windings. Hence, actual voltage equation of a transformer can easily be determined by just
replacing resistances R1 & R2 in the previously established voltage equations by Z1 and Z2.
Resistance drops are in the direction of current vector but, reactive drop will be perpendicular to
the current vector as shown in the above vector diagram of transformer.
For drawing equivalent circuit of transformer referred to primary, first we have to establish
general equivalent circuit of transformer then, we will modify it for referring from primary side.
For doing this, first we need to recall the complete vector diagram of a transformer which is
shown in the figure below
In the figure above, the applied voltage to the primary is V1 and voltage across the primary
winding is E1. Total current supplied to primary is I1. So the voltage V1 applied to the primary is
partly dropped by I1Z1 or I1R1 + j.I1X1 before it appears across primary winding. The voltage
appeared across winding is countered by primary induced emf E1. So voltage equation of this
portion of the transformer can be written as,
The equivalent circuit for that equation can be drawn as below,
From the vector diagram above, it is found that the total primary current I1 has two components,
one is no - load component Io and the other is load component I2. As this primary current have
two components or branches, so there must be a parallel path with primary winding of
transformer. This parallel path of current is known as excitation branch of equivalent circuit of
transformer. The resistive and reactive branches of the excitation circuit can be represented as
The load component I2 flows through the primary winding of transformer and induced voltage
across the winding is E1 as shown in the figure right. This induced voltage E1 transforms to
secondary and it is E2 and load component of primary current I2 is transformed to secondary as
secondary current I2. Current of secondary is I2. So the voltage E2 across secondary winding is
partly dropped by I2Z2 or I2R2 + j.I2X2 before it appears across load. The load voltage is V2.
Therefore,
So, the complete equivalent circuit of transformer referred to primary is shown in the
figure below,
Approximate Equivalent Circuit of Transformer
Since Io is very small compared to I1, it is less than 5% of full load primary current, Io changes
the voltage drop insignificantly. Hence, it is good approximation to ignore the excitation circuit
in approximate equivalent circuit of transformer. The winding resistance and reactance being in
series can now be combined into equivalent resistance and reactance of transformer, referred to
any particular side. In this case it is side 1 or primary side.
1. Iron Loss
2. Copper Losses
IRON LOSS:
This is the power loss that occurs in the iron part. This loss is due to the alternating frequency of
the emf. Iron loss in further classified into two other losses.
b) Hysterisis loss
This power loss is due to the alternating flux linking the core, which will induced an emf in the
core called the eddy emf, due to which a current called the eddy current is being circulated in the
core. As there is some resistance in the core with this eddy current circulation converts into heat
called the eddy current power loss. Eddy current loss is proportional to the square of the supply
frequency.
b) Hysterisis Loss:
This is the loss in the iron core, due to the magnetic reversal of the flux in the core, which results
in the form of heat in the core. This loss is directly proportional to the supply frequency.
Eddy current loss can be minimized by using the core made of thin sheets of silicon steel
material, and each lamination is coated with varnish insulation to suppress the path of the eddy
currents. Hysterisis loss can be minimized by using the core material having high permeability.
COPPER LOSS:
This is the power loss that occurs in the primary and secondary coils when the transformer is on
load. This power is wasted in the form of heat due to the resistance of the coils. This loss is
proportional to the sequence of the load hence it is called the Variable loss where as the Iron loss
is called as the Constant loss as the supply voltage and frequency are constants
EFFICIENCY:
It is the ratio of the output power to the input power of a transformer
Input = Output + Total losses
= Output + Iron loss + Copper loss
where,
In general for the efficiency to be maximum for any device the losses must be minimum.
Between the iron and copper losses the iron loss is the fixed loss and the copper loss is the
variable loss. When these two losses are equal and also minimum the efficiency will be
maximum.
The efficiency and regulation of a transformer on any load condition and at any power
factor condition can be predetermined by indirect loading method. In this method, the actual load
is not used on transformer. But the equivalent circuit parameters of a transformer are determined
by conducting two tests on a transformer which are,
The parameters calculated from these test results are effective in determining the
regulation and efficiency of a transformer at any load and power factor condition, without
actually loading the transformer. The advantage of this method is that without much power loss
the tests can be performed and results can be obtained. Let us discuss in detail how to perform
these tests and how to use the results to calculate equivalent circuit parameters.
The transformer primary is connected to a.c. supply through ammeter, wattmeter and
variac. The secondary of transformer is kept open. Usually low voltage side is used as primary
and high voltage side as secondary to conduct O.C test.
The primary is excited by rated voltage, which is adjusted precisely with the help of a
variac. The wattmeter measures input power. The ammeter measures input current. The
voltemeter gives the value of rated primary voltage applied at rated frequency.
When the primary voltage is adjusted to its rated value with the help of variac, readings of
ammeter and wattmeter are to be recorded.
Let,
Vo = Rated voltage
Wo = Input power
Io = Input current = no load current
Im = Io sin o
Ic = Io cos o
Fig.
As secondary is open, I2 = 0. Thus its reflected current on primary is also zero. So we have
primary current I1 =Io. The transformer no load current is always very small, hardly 2 to 4 % of
its full load value. As I2 = 0, secondary copper losses are zero. And I1 = Io is very low hence
copper losses on primary are also very very low. Thus the total copper losses in O.C. test are
negligibly small. As against this the input voltage is rated at rated frequency hence flux density
in the core is at its maximum value. Hence iron losses are at rated voltage. As output power is
zero and copper losses are very low, the total input power is used to supply iron losses. This
power is measured by the wattmeter i.e. Wo. Hence the wattmeter in O.C. test gives iron losses
Wo = Vo Io cos
cos o = Wo /(Vo Io ) = no load power factor
Once cos o is known we can obtain,
Ic = Io cos o
and Im = Io sin o
Once Ic and Im are known we can determine exciting circuit parameters as,
Ro = Vo /Ic
and Xo = Vo /Im
Key Point : The no load power factor cos o is very low hence wattmeter used must be low
power factor type otherwise there might be error in the results. If the meters are connected on
secondary and primary is kept open then from O.C. test we get Ro'and Xo' with which we can
obtain Ro and Xo knowing the transformation ratio K.
In this test, primary is connected to a.c. supply through variac, ammeter and voltmeter as
shown in the Fig. 3.
As secondary is shorted, its resistance is very very small and on rated voltage it may
draw very large current. Such large current can cause overheating and burning of the
transformer. To limit this short circuit current, primary is supplied with low voltage which is
just enough to cause rated current to flow through primary which can be observed on an
ammeter. The low voltage can be adjusted with the help of variac. Hence this test is also
called low voltage test or reduced voltage test. The wattmeter reading as well as voltmeter,
ammeter readings are recorded.
Now the current flowing through the windings are rated current hence the total copper loss is
full load copper loss. Now the voltage supplied is low which is a small fraction of the rated
voltage. The iron losses are function of applied voltage. So the iron losses in reduced voltage
test are very small. Hence the wattmeter reading is the power loss which is equal to full load
copper losses as iron losses are very low.
.
.. Wsc = (Pcu) F.L. = Full load copper loss
Calculations : From S.C. test readings we can write,
Wsc = Vsc Isc cos sc
.
.. cos sc = Vsc Isc /Wsc = short circuit power factor
2
Wsc = Isc R1e = copper loss
. 2
.. R1e =Wsc /Isc
2 2
while Z1e =Vsc /Isc = (R1e + X1e )
. 2 2
.. X1e = (Z1e - R1e )
Thus we get the equivalent circuit parameters R1e, X1e and Z1e. Knowing the
transformation ratio K, the equivalent circuit parameters referred to secondary also can be
obtained.
Important Note : If the transformer is step up transformer, its primary is L.V. while
secondary is H.V. winding. In S.C. test, supply is given to H.V. winding and L.V is shorted.
In such case we connect meters on H.V. side which is transformer secondary through for S.C.
test purpose H.V side acts as primary. In such case the parameters calculated from S.C. test
readings are referred to secondary which are R2e, Z2e and X2e. So before doing calculations it
is necessary to find out where the readings are recorded on transformer primary or secondary
and accordingly the parameters are to be determined. In step down transformer, primary is
high voltage itself to which supply is given in S.C. test. So in such case test results give us
parameters referred to primary i.e. R1e, Z1e and X1e.
Key point : In short, if meters are connected to primary of transformer in S.C. test,
calculations give us R1e and Z1e if meters are connected to secondary of transformer in S.C.
test calculations give us R2e and Z2e.
From S.C. test we get the equivalent circuit parameters referred to primary or secondary.
The rated voltages V1, V2 and rated currents (I1) F.L. and (I2) F.L. are known for the
given transformer. Hence the regulation can be determined as,
For any other load the currents I1, I2 must be changed by fraction n.
.
. . I1, I2 at any other load = n (I1) F.L., n (I2) F.L.
Key Point : Thus regulation at any load and any power factor can be predetermined, without
actually loading the transformer.
Sumpner's Test Or Back-To-Back Test On Transformer
Sumpner's Test
Sumpner's test or back to back test can be employed only when two identical transformers are
available. Both transformers are connected to supply such that one transformer is loaded on
another. Primaries of the two identical transformers are connected in parallel across a supply.
Secondaries are connected in series such that emf's of them are opposite to each other.
Another low voltage supply is connected in series with secondaries to get the readings, as
shown in the circuit diagram shown below.
In above diagram, T1 and T2 are identical transformers. Secondaries of them are connected
in voltage opposition, i.e. EEF and EGH. Both the emf's cancel each other, as transformers are
identical. In this case, as per superposition theorem, no current flows through secondary.
And thus the no load test is simulated. The current drawn from V1 is 2I0, where I0 is equal to
no load current of each transformer. Thus input power measured by wattmeter W1 is equal
to iron losses of both transformers.
Modern power systems operate at some standard voltages. The equipments working on these
systems are therefore given input voltages at these standard values, within certain agreed
tolerance limits. In many applications this voltage itself may not be good enough for
obtaining the best operating condition for the loads. A transformer is interposed in between
the load and the supply terminals in such cases. There are additional drops inside the
transformer due to the load currents. While input voltage is the responsibility of the supply
provider, the voltage at the load is the one which the user has to worry about.
If undue voltage drop is permitted to occur inside the transformer the load voltage becomes
too low and affects its performance. It is therefore necessary to quantify the drop that takes
place inside a transformer when certain load current, at any power factor, is drawn from its
output leads. This drop is termed as the voltage regulation and is expressed as a ratio of the
terminal voltage (the absolute value per se is not too important).
The voltage regulation can be defined in two ways - Regulation Down and Regulation up.
These two definitions differ only in the reference voltage as can be seen below. Regulation
down: This is defined as the change in terminal voltage when a load current at any power
factor is applied, expressed as a fraction of the no-load terminal voltage.
Where,
Vnl is the no-load terminal voltage.
Vl is load voltage.
Normally full load regulation is of interest as the part load regulation is going to be lower.
This definition is more commonly used in the case of alternators and power systems as the
user-end voltage is guaranteed by the power supply provider. He has to generate proper no-
load voltage at the generating station to provide the user the voltage he has asked for. In the
expressions for the regulation, only the numerical differences of the voltages are taken and
not vector differences.
In the case of transformers both definitions result in more or less the same value for the
regulation as the transformer impedance is very low and the power factor of operation is quite
high. The power factor of the load is defined with respect to the terminal voltage on load.
Hence a convenient starting point is the load voltage. Also the full load output voltage is
taken from the name plate. Hence regulation up has some advantage when it comes to its
application. Fig. 23 shows the phasor diagram of operation of the transformer under loaded
condition. The no-load current I0 is neglected in view of the large magnitude of I2.
Fig. Regulation of Transformer
Fig. Variation of full load regulation with power factor
Predetermination of Efficiency
Transformers which are connected to the power supplies and loads and are in
operation are required to handle load current and power as per the requirements of the load.
An unloaded transformer draws only the magnetization current on the primary side, the
secondary current being zero. As the load is increased the primary and secondary currents
increase as per the load requirements. The volt amperes and wattage handled by the
transformer also increases. Due to the presence of no load losses and I2R losses in the
windings certain amount of electrical energy gets dissipated as heat inside the transformer.
This gives rise to the concept of efficiency.
Efficiency of power equipment is defined at any load as the ratio of the power output
to the power input. Putting in the form of an expression,
While the efficiency tells us the fraction of the input power delivered to the load, the
deficiency focuses our attention on losses taking place inside transformer. As a matter of fact
the losses heat up machine. The temperature rise decides the rating of the equipment.
The temperature rise of the machine is a function of heat generated the structural
configuration, method of cooling and type of loading (or duty cycle of load). The peak
temperature attained directly affects the life of the insulations of the machine for any class of
insulation.
Fig. Efficiency
A typical curve for the variation of efficiency as a function of output is given in Fig. The
losses that take place inside the machine expressed as a fraction of the input is sometimes
termed as deficiency. Except in the case of an ideal machine, a certain fraction of the input
power gets lost inside the machine while handling the power. Thus the value for the
efficiency is always less than one. In the case of a.c. machines the rating is expressed in terms
of apparent power. It is nothing but the product of the applied voltage and the current drawn.
The actual power delivered is a function of the power factor at which this current is drawn.
As the reactive power shuttles between the source and the load and has a zero average value
over a cycle of the supply wave it does not have any direct effect on the efficiency. The
reactive power however increases the current handled by the machine and the losses resulting
from it. Therefore the losses that take place inside a transformer at any given load play a vital
role in determining the efficiency. The losses taking place inside a transformer can be
enumerated as below:
3. Iron loss
4. Dielectric loss
Primary and secondary copper losses take place in the respective winding resistances due to
the flow of the current in them
The primary and secondary resistances differ from their d.c. values due to skin effect
and the temperature rise of the windings. While the average temperature rise can be
approximately used, the skin effect is harder to get analytically. The short circuit test gives
the value of Re taking into account the skin effect.
The iron losses contain two components - Hysteresis loss and Eddy current loss. The
Hysteresis loss is a function of the material used for the core.
For constant voltage and constant frequency operation this can be taken to be constant. The
eddy current loss in the core arises because of the induced emf in the steel lamination sheets
and the eddies of current formed due to it. This again produces a power loss Pe in the
lamination.
where t is the thickness of the steel lamination used. As the lamination thickness is
much smaller than the depth of penetration of the field, the eddy current loss can be reduced
by reducing the thickness of the lamination. Present day laminations are of 0.25 mm
thickness and are capable of operation at 2 Tesla. These reduce the eddy current losses in the
core. This loss also remains constant due to constant voltage and frequency of operation. The
sum of hysteresis and eddy current losses can be obtained by the open circuit test.
The dielectric losses take place in the insulation of the transformer due to the large
electric stress. In the case of low voltage transformers this can be neglected. For constant
voltage operation this can be assumed to be a constant.
The stray load losses arise out of the leakage fluxes of the transformer. These leakage
fluxes link the metallic structural parts, tank etc. and produce eddy current losses in them.
Thus they take place all round the transformer instead of a definite place , hence the name
stray. Also the leakage flux is directly proportional to the load current unlike the mutual
flux which is proportional to the applied voltage. Hence this loss is called stray load loss.
This can also be estimated experimentally. It can be modeled by another resistance in the
series branch in the equivalent circuit. The stray load losses are very low in air-cored
transformers due to the absence of the metallic tank
Thus, the different losses fall in to two categories Constant losses (mainly voltage dependant)
and Variable losses (current dependant). The expression for the efficiency of the transformer
operating at a fractional load x of its rating, at a load power factor of 2, can be written as
Here S in the volt ampere rating of the transformer (V2 I2 at full load), Pconst being
constant losses and Pvar the variable losses at full load.
UNIT - V
4.1 Introduction
Electric power is generated in generating stations, using three phase alternators at 11 KV.
This voltage is further stepped up to 66 KV, 110 KV, 230 KV or 400 KV using 3 phase
power transformers and power is transmitted at this high voltage through transmission
lines. At the receiving substations, these high voltages are stepped down by 3 phase
transformers to 11 KV. This is further stepped down to 400 volts at load centers by means
of distribution transformers. For generation, transmission and distribution, 3 phase system
is economical. Therefore 3 phase transformers are very essential for the above purpose.
The sectional view of a 3 phase power transformer is shown in Fig.4.1.
The three cores are 120 apart and their unwound limbs are shown in contact with each
other. The center core formed by these three limbs, carries the flux produced by the three
phase currents IR, IY and IB. As at any instant IR+Iy+IB=0, the sum of three fluxes (flux in
the center limb) is also zero.
Therefore it will make no difference if the common limb is removed. All the three limbs
are placed in one plane in case of a practical transformer as shown in fig 4.3.
The core type transformers are usually wound with circular cylindrical coils. The
construction and assembly of laminations and yoke of a three phase core type transformer
is shown in fig 4.4 one method of arrangement of windings in a three phase transformer is
shown.
In the other method the primary and secondary windings are wound one over the other in
each limb. The low-tension windings are wound directly over the core but are, of course,
insulated for it. The high tension windings are wound over the low tension windings and
adequate insulation is provided between the two windings.
The primary and secondary windings of the three phase transformer can also be
interconnected as star or delta.
The identical single phase transformers can be suitably inter-connected and used instead of
a single unit 3phase transformer. The single unit 3 phase transformer is housed in a
single tank. But the transformer bank is made up of three separate single phase
transformers each with its own, tanks and bushings. This method is preferred in mines and
high altitude power stations because transportation becomes easier. Bank method is
adopted also when the voltage involved is high because it is easier to provide proper
insulation in each single phase transformer.
As compared to a bank of single phase transformers, the main advantages of a single unit
3-phase transformer are that it occupies less floor space for equal rating, less weight costs
about 20% less and further that only one unit is to be handled and connected.
There are various methods available for transforming 3 phase voltages to higher or lower 3
phase voltages. The most common connections are (i) star star (ii) DeltaDelta (iii)
Star Delta (iv) Delta Star.
The delta delta connection is economical for large capacity, low voltage transformers in
which insulation problem is not a serious one. The transformer connection are as shown in
fig. 4.6.
The main use of star-delta connection is at the substation end of the transmission line
where the voltage is to be stepped down. The primary winding is star connected with
grounded neutral as shown in Fig. 4.7. The ratio between the secondary and primary line
voltage is 1/3 times the transformation ratio of each single phase transformer. There is a
30 shift between the primary and secondary line voltages which means that a star-delta
transformer bank cannot be paralleled with either a star-star or a delta-delta bank.
The connection of Dd0 is shown in fig. 4.10 and the voltages on primary and secondary
sides is also shown on the phasor diagram. The phase angle difference between the phase
voltage of high voltage side and low voltage side is zero degree (0).
The connection of Dd6 is shown in fig. 4.11 and the voltages on primary and secondary
sides is also shown on the phasor diagram. The phase angle difference between the phase
voltage of high voltage side and low voltage side is 180.
This connection proves to be economical for large low voltage transformers as it increases
number of turns per phase. Primary side line voltage is equal to secondary side line
voltage. Primary side phase voltage is equal to secondary side phase voltage. There is no
phase shift between primary and secondary voltages for Dd0 connection. There is 180
phase shift between primary and secondary voltages for Dd6 connection.
Advantages
Sinusoidal Voltage at Secondary: In order to get secondary voltage as sinusoidal, the
magnetizing current of transformer must contain a third harmonic component. The
delta connection provides a closed path for circulation of third harmonic
component of current. The flux remains sinusoidal which results in sinusoidal
voltages.
Suitable for Unbalanced Load: Even if the load is unbalanced the three phase voltages
remains constant. Thus it suitable for unbalanced loading also.
Carry 58% Load if One Transfer is Faulty in Transformer Bank:
If there is bank of single phase
transformers connected in delta-delta fashion and if one of the transformers is
disabled then the supply can be continued with remaining tow transformers of course
with reduced efficiency.
Economical for Low Voltage: Due to delta connection, phase voltage is same as line
voltage hence winding have more number of turns. But phase current is (1/3)
times the line current. Hence the cross-section of the windings is very less. This
makes the connection economical for low voltages transformers.
Reduce Cross section of Conductor: The conductor is required of smaller Cross section as
the phase current is 1/3 times of the line current. It increases number of turns per
phase and reduces the necessary cross sectional area of conductors thus insulation
problem is not present.
Absent of Third Harmonic Voltage: Due to closed delta, third harmonic voltages are absent.
Disadvantages
Due to the absence of neutral point it is not suitable for three phase four wire system.
More insulation is required and the voltage appearing between windings and core
will be equal to full line voltage in case of earth fault on one phase.
Application
Suitable for large, low voltage transformers.
The connection of Yy0 is shown in fig. 4.12 and the voltages on primary and secondary
sides is also shown on the phasor diagram. The phase angle difference between the phase
voltage of high voltage side and low voltage side is zero degree (0).
In Primary Winding Each Phase is120electrical degrees out of phase with the
other two phases.
In Secondary Winding Each Phase is120electrical degrees out of phase with the
other two phases.
Each primary winding is magnetically linked to one secondary winding through a
common core leg. Sets of windings that are magnetically linked are drawn parallel
to each other in the vector diagram. In the Y-Y connection, each primary and
secondary winding is connected to a neutral point.
The neutral point may or may not be brought out to an external physical connection
and the neutral may or may not be grounded.
No Phase Displacement: The primary and secondary circuits are in phase; i.e., there are
no phase angle displacements introduced by the Y-Y connection. This is an
important advantage when transformers are used to interconnect systems of
different voltages in a cascading manner. For example, suppose there are four
systems operating at 800, 440, 220, and 66 kV that need to be interconnected.
Substations can be constructed using Y-Y transformer connections to interconnect
any two of these voltages. The 800 kV systems can be tied with the 66 kV systems
through a single 800 to 66 kV transformation or through a series of cascading
transformations at 440,220 and 66 kV.
Required Few Turns for winding: Due to star connection, phase voltages is (1/3) times
the line voltage. Hence less number of turns is required. Also the stress on
insulation is less. This makes the connection economical for small high voltage
purposes.
Required Less Insulation Level: If the neutral end of a Y-connected winding is grounded,
then there is an opportunity to use reduced levels of insulation at the neutral end of
the winding. A winding that is connected across the phases requires full insulation
throughout the winding.
Handle Heavy Load: Due to star connection, phase current is same as line current.
Hence windings have to carry high currents. This makes cross section of the
windings high. Thus the windings are mechanically strong and windings can bear
heavy loads and short circuit current.
Use for Three phases Four Wires System: As neutral is available, suitable for three phases four
wiresystem.
Eliminate Distortion in Secondary Phase Voltage: The connection of primary neutral to the
neutral
Sinusoidal voltage on secondary side: Neutral give path to flow Triple frequency current to
flow Generator side thus sinusoidal voltage on primary will give sinusoidal voltage
on secondary side.
Used as Auto Transformer: A Y-Y transformer may be constructed as an
autotransformer, with the possibility of great cost savings compared to the two-
winding transformer construction.
Better Protective Relaying: The protective relay settings will be protecting better on the
line to ground faults when the Y-Y transformer connections with solidly grounded
neutrals are applied.
Disadvantages
The Third harmonic issue: The voltages in any phase of a Y-Y transformer are 1200
apart from the voltages in any other phase. However, the third-harmonic
components of each phase will be in phase with each other. Nonlinearities in the
transformer core always lead to generation of third harmonic. These components
will add up resulting in large (can be even larger than the fundamental component)
third harmonic component.
Overvoltage at Lighting Load: The presence of third (and other zero-sequence) harmonics
at an ungrounded neutral can cause overvoltage conditions at light load. When
constructing a Y-Y transformer using single-phase transformers connected in a
bank, the measured line-to-neutral voltages are not 57.7% of the system phase-to-
phase voltage at no load but are about 68% and diminish very rapidly as the bank is
loaded. The effective values of voltages at different frequencies combine by taking
the square root of the sum of the voltages squared. With sinusoidal phase-to-phase
voltage, the third-harmonic component of the phase-to-neutral voltage is about
60%.
Voltage drop at Unbalance Load: There can be a large voltage drop for unbalanced phase-
to-neutral loads. This is caused by the fact that phase-to-phase loads cause a voltage
drop through the leakage reactance of the transformer whereas phase-to-neutral
loads cause a voltage drop through the magnetizing reactance, which is 100 to 1000
times larger than the leakage reactance.
Overheated Transformer Tank: Under certain circumstances, a Y-Y connected three-
phase trans-can produce severe tank overheating that can quickly destroy the
transformer. This usually occurs with an open phase on the primary circuit and load
on the secondary.
Over Excitation of Core in Fault Condition: If a phase-to-ground fault occurs on the primary
circuit with the primary neutral grounded, then the phase-to-neutral voltage on the
un faulted phases increases to 173% of the normal voltage. This would almost
certainly result in over excitation of the core, with greatly increased magnetizing
currents and core losses
If the neutrals of the primary and secondary are both brought out, then a phase-to-
ground fault on the secondary circuit causes neutral fault current to flow in the
primary circuit. Ground protection re- laying in the neutral of the primary circuit
may then operate for faults on the secondary circuit
Neutral Shifting: If the load on the secondary side unbalanced then the performance of
this connection is not satisfactory then the shifting of neutral point is possible. To
prevent this, star point of the primary is required to be connected to the star point of
the generator.
Distortion of Secondary voltage: Even though the star or neutral point of the primary is
earthed, the third harmonic present in the alternator voltage may appear on the
secondary side. This causes distortion in the secondary phase voltages.
Over Voltage at Light Load: The presence of third (and other zero-sequence) harmonics
at an ungrounded neutral can cause overvoltage conditions at light load.
Difficulty in coordination of Ground Protection: In Y-Y Transformer, a low-side ground fault
causes
primary circuit with the primary neutral grounded, then the phase-to-neutral voltage
on the UN faulted phases increases to 173% of the normal voltage. If the neutrals
of the primary and secondary are both brought out, then a phase-to-ground fault on
the secondary circuit causes neutral fault current to flow in the primary circuit.
Trip the T/C in Line-Ground Fault: All harmonics will propagate through the transformer,
zero-sequence current path is continuous through the transformer, one line-to-
ground fault will trip the transformer.
Suitable for Core Type Transformer: The third harmonic voltage and current is absent in
such type of connection with three phase wire system or shell type of three phase
units, the third harmonic phase voltage may be high. This type of connection is
more suitable for core type transformers.
Application
This Type of Transformer is rarely used due to problems with unbalanced loads.
It is economical for small high voltage transformers as the number of turns per
phase and the amount of insulation required is less.
There is a +30 Degree or -30 Degree Phase Shift between Secondary Phase Voltage to
Primary Phase Voltage. The connection of Yd1 is shown in fig. 4.14 and the voltages on
primary and secondary sides is also shown on the phasor diagram. The phase angle
difference between the phase voltage of high voltage side and low voltage side is -30.
Fig 4.14. Yd1 connection and phasor diagram
The connection of Yd11 is shown in fig. 4.15 and the voltages on primary and secondary
sides is also shown on the phasor diagram. The phase angle difference between the phase
voltage of high voltage side and low voltage side is 30.
Advantages
The primary side is star connected. Hence fewer numbers of turns are required.
This makes the connection economical for large high voltage step down power
transformers.
The neutral point allows both types of loads (single phase or three phases) to be met.
The Y-D connection has no problem with third harmonic components due to
circulating currents inD. It is also more stable to unbalanced loads since the D
partially redistributes any imbalance that occurs.
The delta connected winding carries third harmonic current due to which potential
of neutral point is stabilized. Some saving in cost of insulation is achieved if HV
side is star connected. But in practice the HV side is normally connected in delta so
that the three phase loads like motors and single phase loads like lighting loads can
be supplied by LV side using three phase
four wire system.
Disadvantages
In this type of connection, the secondary voltage is not in phase with the primary.
Hence it is not possible to operate this connection in parallel with star-star or delta-
delta connected transformer.
One problem associated with this connection is that the secondary voltage is shifted
by
0
30 with respect to the primary voltage. This can cause problems when paralleling
3-phase transformers since transformers secondary voltages must be in-phase to be
paralleled. Therefore, we must pay attention to these shifts.
Application
It is commonly employed for power supply transformers.
This type of connection is commonly employed at the substation end of the
transmission line. The main use with this connection is to step down the voltage.
The neutral available on the primary side is grounded. It can be seen that there is
phase difference of 30 between primary and secondary line voltages.
The connection of Dy1 is shown in fig. 4.16 and the voltages on primary and secondary
sides is also shown on the phasor diagram. The phase angle difference between the phase
voltage of high voltage side and low voltage side is -30.
The connection of Dy11 is shown in fig. 4.17 and the voltages on primary and secondary
sides is also shown on the phasor diagram. The phase angle difference between the phase
voltage of high voltage side and low voltage side is 30.
Fig 4.17. Dy11 connection and phasor diagram
Advantages
Cross section area of winding is less at Primary side: On primary side due to
delta connection winding cross-section required is less.
Used at Three phase four wire System: On secondary side, neutral is available,
due to which it can be used for 3-phase, 4 wire supply system.
Handled large unbalanced Load: Large unbalanced loads can be handled without
any difficulty.
Disadvantages
In this type of connection, the secondary voltage is not in phase with the primary.
Hence it is not possible to operate this connection in parallel with star-star or delta-
delta connected transformer.
One problem associated with this connection is that the secondary voltage is shifted
by
0
30 with respect to the primary voltage. This can cause problems when paralleling
3-phase transformers since transformers secondary voltages must be in-phase to be
paralleled.
Application
Commonly used in a step-up transformer: As for example, at the beginning of a HT
transmission
line. In this case neutral point is stable and will not float in case of unbalanced
loading. There is no distortion of flux because existence of a -connection allows a
path for the third-harmonic components. The line voltage ratio is 3 times of
transformer turn-ratio and the secondary voltage leads the primary one by 30. In
recent years, this arrangement has become very popular for distribution system as it
provides 3- , 4-wire system.
Commonly used in commercial, industrial, and high-density residential locations: To supply three-
The connection of Dz0 is shown in fig. 4.18 and the voltages on primary and secondary
sides is also shown on the phasor diagram. The phase angle difference between the phase
voltage of high voltage side and low voltage side is 0.
The connection of Dz6 is shown in fig. 4.19 and the voltages on primary and secondary
sides is also shown on the phasor diagram. The phase angle difference between the phase
voltage of high voltage side and low voltage side is 180.
The connection of Yz1 is shown in fig. 4.20 and the voltages on primary and secondary
sides is also shown on the phasor diagram. The phase angle difference between the phase
voltage of high voltage side and low voltage side is -30.
These connections are employed where delta connections are weak. Interconnection
of phases in zigzag winding effects a reduction of third harmonic voltages and at
the same time permits unbalanced loading.
This connection may be used with either delta connected or star connected winding
either for step-up or step-down transformers. In either case, the zigzag winding
produces the same angular displacement as a delta winding, and at the same time
provides a neutral for earthing purposes.
The amount of copper required from a zigzag winding in 15% more than a
corresponding star or delta winding. This is extensively used for earthing
transformer.
1. To give a supply to an existing two phase system from a three phase supply.
Two phase 4-wire circuits are essentially just two ungrounded single-phase circuits that are
electrically 90 out of phase with each other. Two phase 5-wire circuits have four phase
wires plus a neutral; the four phase wires are 90 out of phase with each other.
A Scott-T transformer (also called a Scott connection) is a type of circuit used to derive
two-phase power from a three-phase source or vice-versa. The Scott connection evenly
distributes a balanced load between the phases of the source. Scott T Transformers require
a three phase power input and provide two equal single phase outputs called Main and
Teaser. The MAIN and Teaser outputs are 90 degrees out of phase. The MAIN and the
Teaser outputs must not be connected in parallel or in series as it creates a vector current
imbalance on the primary side. MAIN and Teaser outputs are on separate cores. An
external jumper is also required to connect the primary side of the MAIN and Teaser
sections. The schematic of a typical Scott T Transformer is shown below:
4.23 Connection diagram of Scott-connected transformer and vector relation of input and output
From the phasor diagram it is clear that the secondary voltages are of two phases with
equal magnitude and 90 phase displacement.
Scott T Transformer is built with two single phase transformers of equal power rating.
Assuming the desired voltage is the same on the two and three phase sides, the Scott-T
transformer connection consists of a center-tapped 1:1 ratio main transformer, T1, and an
86.6% (0.53) ratio teaser transformer, T2. The center-tapped side of T1 is connected
between two of the phases on the three-phase side. Its center tap then connects to one end
of the lower turn count side of T2, the other end connects to the remaining phase. The
other side of the transformers then connects directly to the two pairs of a two-phase four-
wire system.
If the main transformer has a turns ratio of 1: 1, then the teaser transformer requires a turns
ratio of
0.866: 1 for balanced operation. The principle of operation of the Scott connection can be
most easily seen by first applying a current to the teaser secondary windings, and then
applying a current to the main secondary winding, calculating the primary currents
separately and superimposing the results.
The primary three-phase currents are balanced; i.e., the phase currents have the same
magnitude and their phase angles are 120 apart. The apparent power supplied by the main
transformer is greater than the apparent power supplied by the teaser transformer. This is
easily verified by observing that the primary currents in both transformers have the same
magnitude; however, the primary voltage of the teaser transformer is only 86.6% as great
as the primary voltage of the main transformer. Therefore, the teaser transforms only
86.6% of the apparent power transformed by the main.
The total real power delivered to the two phase load is equal to the total real power
supplied from the three-phase system, the total apparent power transformed by both
transformers is greater than the total apparent power delivered to the two-phase
load.
The apparent power transformed by the teaser is 0.866 X IH1= 1.0 and the apparent
power transformed by the main is 1.0X IH2 =1.1547 for a total of 2.1547 of
apparent power transformed.
The additional 0.1547 per unit of apparent power is due to parasitic reactive power
owing between the two halves of the primary winding in the main transformer.
Single-phase transformers used in the Scott connection are specialty items that are
virtually impossible to buy off the shelf nowadays. In an emergency, standard
distribution transformers can be used.
If desired, a three phase, two phase, or single phase load may be supplied simultaneously
using scott-connection. The neutral points can be available for grounding or loading
purposes. The Scott T connection in theory would be suitable for supplying a three, two
and single phase load simultaneously, but such loads are not found together in modern
practice.
The Scott T would not be recommended as a connection for 3 phase
to 3 phase applications for the following reasons:
The loads of modern buildings and office buildings are inherently unbalanced and contain
equipment that can be sensitive to potential voltage fluctuations that may be caused by the
Scott T design.
A properly sized Scott T transformer will have to be a minimum of 7.75% larger than the
equivalent Delta-Wye transformer. Properly sized, it would be a bulkier and heavier option
and should not be considered a less expensive solution.
As seen previously in connection of three single phase transformers that if one of the
transformers is unable to operate then the supply to the load can be continued with the
remaining two transformers at the cost of reduced efficiency. The connection that obtained
is called V-V connection or open delta connection.
Consider the Fig. 4.24 in which 3 phase supply is connected to the primaries. At the
secondary side three equal three phase voltages will be available on no load.
The voltages are shown on phasor diagram. The connection is used when the three phase
load is very very small to warrant the installation of full three phase transformer.
Fig. 4.24 Open delta connection of transformer at noload
If one of the transformers fails in - bank and if it is required to continue the supply
even though at reduced capacity until the transformer which is removed from the bank is
repaired or a new one is installed then this type of connection is most suitable.
When it is anticipated that in future the load increase, then it requires closing of open delta.
In such cases open delta connection is preferred. It can be noted here that the removal of
one of the transformers will not give the total load carried by V - V bank as two third of the
capacity of - bank.
- capacity = 3 VL IL = 3 VL (3 Iph )
- capacity = 3 VL Iph
It can also be noted from the Fig. 4.25 V-V connection that the secondary line current IL is
equal to the phase current Iph.
V- V capacity = 3 VL IL = 3 VL Iph
3VL Iph
So, V-V capacity 1 0.577 58%
capacity 3V I 3
L ph
Thus the three phase load that can be carried without exceeding the ratings of the
transformers is 57.5 percent of the original load. Hence it is not 66.7 % which was
expected otherwise.
The reduction in the rating can be calculated as {(66.67 - 57.735)/(57.735)}x 100 = 15.476
Suppose that we consider three transformers connected in - fashion and supplying their
rated load. Now one transformer is removed then each of the remaining two transformers
will be overloaded. The overload on each transformer will be given as,
This overload can be carried temporarily if provision is made to reduce the load otherwise
overheating and breakdown of the remaining two transformers would take place.
The two transformers in V -V bank operate at different power factor except for
balanced unity p.f .load.
The terminals voltages available on the secondary side become unbalanced. This
may happen even though load is perfectly balanced.
With a bank of tow single phase transformers connected in V-V fashion supplying a
balanced
3 phase load with cos asp.f., one of the transformer operate at a p.f. of cos (30-)
and other at cos (30+). The powers of tow transformers are given by,
4.7Oscillating Neutral
In addition to the operation of transformers on the sinusoidal supplies, the harmonic behavior
becomes important as the size and rating of the transformer increases. The effects of the
harmonic currents are
In the present times a greater awareness is generated by the problems of harmonic voltages
and currents produced by non-linear loads like the power electronic converters. These
combine with non-linear nature of transformer core and produce severe distortions in
voltages and currents and increase the power loss. Thus the study of harmonics is of great
practical significance in the operation of transformers.
In the case of single phase transformers connected to form three phase bank, each
transformer is magnetically decoupled from the other. The flow of harmonic currents are
decided by the type of the electrical connection used on the primary and secondary sides.
Also, there are three fundamental voltages in the present case each displaced from the
other by 120 electrical degrees. Because of the symmetry of the a.c. wave about the time
axis only odd harmonics need to be considered. The harmonics which are triplen (multiples
of three) behave in a similar manner as they are co-phasal or in phase in the three phases.
The non-triplen harmonics behave in a similar manner to the fundamental and have 120
phase displacement between them.
When the connection of the transformer is Yy without neutral wires both primary and
secondary connected in star no closed path exists. As the triplen harmonics are always in
phase, by virtue of the Y connection they get canceled in the line voltages. Non-triplen
harmonics like fundamental, become 0 times phase value and appear in the line voltages.
Line currents remain sinusoidal except for non-triplen harmonic currents. Flux wave in
each transformer will be flat topped and the phase voltages remain peaked. The potential of
the neutral is no longer steady. The star point oscillates due to the third harmonic voltages.
This is termed as "oscillating neutral".
Apart from the Primary & Secondary windings, there sometimes placed a third winding in
power transformers called "Tertiary Winding". Its purpose is to provide a circulating path
for the harmonics (especially third harmonics) produced in the transformers along with
power frequency (50Hz. third harmonic means 150 Hz oscillations). In delta-delta, delta-
star and star-delta transformers
all voltages are balanced and there is no floating of neutral or oscillating neutral. The
floating of neutral is developed in the case star-star connection only. The transformers are
sometimes constructed with three windings. The main windings are connected to form star-
star connection and the third winding known as tertiary winding is used to make a closed
delta connection to stabilize the neutrals of both primary and secondary circuits. The
tertiary winding carries the third-harmonic currents.
Thus far we have looked at transformers which have one single primary winding and one
single secondary winding. But the beauty of transformers is that they allow us to have
more than just one winding in either the primary or secondary side. Transformers which
have three winding are known commonly as Three Winding Transformers.
The principal of operation of a three winding transformer is no different from that of an ordinary
transformer. Primary and secondary voltages, currents and turns ratios are all calculated the
same, the difference this time is that we need to pay special attention to the voltage
polarities of each coil winding, the dot convention marking the positive (or negative)
polarity of the winding, when we connect them together.
Three Winding Transformers can also be used to provide either a step-up, a step-down, or a
combination of both between the various windings. In fact a three winding transformers
have two secondary windings on the same core with each one providing a different voltage
or current level output.
In electronic circuits, one transformer is often used to supply a variety of lower voltage
levels for different components in the electronic circuitry. A typical application of three
winding transformers is in power supplies and Triac Switching Converters. So a
transformer have two secondary windings, each of which is electrically isolated from the
others, just as it is electrically isolated from the primary. Then each of the secondary coils
will produce a voltage that is proportional to its number of coil turns.
Certain conditions have to be met before two or more transformers are connected in
parallel and share a common load satisfactorily. They are,
2. The per unit impedance of each machine on its own base must be the same.
3. The polarity must be the same, so that there is no circulating current between the
transformers.
4. The phase sequence must be the same and no phase difference must exist between
the voltages of the two transformers.
Same voltage ratio : Generally the turns ratio and voltage ratio are taken to be the
same. If the ratio is large there can be considerable error in the voltages even if the
turns ratios are the same. When the primaries are connected to same bus bars, if the
secondaries do not show the same voltage, paralleling them would result in a
circulating current between the secondaries. Reflected circulating current will be
there on the primary side also. Thus even without connecting a load considerable
current can be drawn by the transformers and they produce copper losses. In two
identical transformers with percentage impedance of 5 percent, a no-load voltage
difference of one percent will result in a circulating current of 10 percent of full
load current. This circulating current gets added to the load current when the load is
connected resulting in unequal sharing of the load. In such cases the combined full
load of the two transformers can never be met without one transformer getting
overloaded.
Phase sequence- The phase sequence of operation becomes relevant only in the
case of poly phase systems. The poly phase banks belonging to same vector group
can be connected in parallel. A transformer with +30 phase angle however can be
paralleled with the one with 30 phase angle, the phase sequence is reversed for
one of them both at primary and secondary terminals. If the phase sequences are
not the same then the two transformers cannot be connected in parallel even if they
belong to same vector group. The phase sequence can be found out by the use of a
phase sequence indicator.
4.11 Load Sharing
When the transformers have equal voltage ratios, the magnitudes of secondary no-load
voltages are equal. Further if the primary leakage impedance drops due to exciting currents
are also equal, then
The equivalent circuit of two three phase transformer connected in parallel connected with a
load of
ZL impedance on per phase basis is drawn in fig 4.28. In this figure transformer A and B
are operating in parallel. IA and IB are the load current of the two transformer.
Ea IaZa VL IZL
Since E a Eb ; E b IaZa VL IZL
The voltage equation of transformer B is
Eb IbZb VL IZL
Eb IaZa Eb IbZb
IaZa IbZb
According to the voltage drops across the two equivalent leakage impedance Za and Zb are
equal.
Zb
Sa
S Za Zb
Za
similarly, S b
S Za Zb
Thus the power sharing in between two transformer is given in above equation in VA rating.